Public_Works_Campus_Rev._1_-_22211_US_Hwy_19_N_-_Sealed.pdf
PDF 463 KB Posted
- Solicitation number
- 24-0470-ITB-C
- Issued by
- Pinellas County, Clewiston City, Florida
About this file
This document is an electrical design and specifications set for the Public Works Campus located at 22211 US Highway 19 in Clearwater, Florida, prepared by an engineering firm. The electrical drawings provide comprehensive details for electrical infrastructure, including power systems, electrical device mounting heights, panel schedules, and load calculations for a facility with multiple work areas such as sign manufacturing, infrastructure response, and bridge work areas. The plans include a 750 kVA utility transformer, a 750kW generator, and detailed electrical distribution information for the site, with specific focus on receptacle placements, conduit routing, and electrical system configurations.
The electrical design documents a 30-day load study conducted from June 21 to July 24, 2023, revealing a total estimated demand load of 10.04 kVA and 28 connected amps. The plans specify electrical requirements for various areas, including electric man lift charging stations, warehouse receptacles, and provisions for existing equipment. The electrical infrastructure is designed to support the facility's operational needs, with careful attention to mounting heights, circuit ratings, and compliance with national electrical codes. The documents include general notes emphasizing contractor responsibilities for coordination, field verification, utility coordination, and adherence to local regulations and safety standards.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
480/277 VOLT PANELBOARD, FLUSH AND SURFACE MOUNTED RESPECTIVELY. DESIGNATION AS
INDICATED. REFER TO PANELBOARD SCHEDULES FOR EXACT REQUIREMENTS.
208Y/120 OR 120/240 VOLT PANELBOARD, FLUSH AND SURFACE MOUNTED RESPECTIVELY.
DESIGNATION AS INDICATED. REFER TO PANELBOARD SCHEDULES FOR EXACT REQUIREMENTS.
ELECTRICAL POWER POLE, MOUNTING AND CONFIGURATION AS SPECIFIED.
MOTOR CONNECTION. ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL CONTRACTOR
FOR FINAL CONNECTION.
ENCLOSED CIRCUIT BREAKER. FRAME SIZE AND TRIP RATING AS INDICATED ON PLANS.
MANUAL MOTOR STARTER. STARTER TYPE AND SIZE AS INDICATED ON PLANS.
WALL FLOOR CEILING
125 VOLT, 3 WIRE DUPLEX RECEPTACLE FLUSH (FINISHED SPACES) OR SURFACE
(UNFINISHED SPACES) OUTLET BOX.
125 VOLT, 3 WIRE DUPLEX RECEPTACLE GFI FLUSH (FINISHED SPACES) OR SURFACE
(UNFINISHED SPACES) OUTLET BOX.
POWER DEVICESPOWER EQUIPMENT
GENERAL
DEMOLITION KEYED NOTE.#
NEW WORK KEYED NOTE.##
REMOVE WIRING, CABLING, ETC. TO THIS POINT.
CONNECT WIRING, CABLING, ETC. TO THIS POINT.
FEEDER TAG - SEE FEEDER SCHEDULE
X
XXX
PRESENT LIGHTING FIXTURE, SWITCH, DEVICE, ETC., TO REMAIN.PR
PRESENT LIGHTING FIXTURE, SWITCH, DEVICE, ETC., TO BE REMOVED AND REPLACED WITH NEW.PRN
PRESENT LIGHTING FIXTURE, SWITCH, DEVICE, ETC., SHOWN AT NEW LOCATIONPRR
PRESENT LIGHTING FIXTURE, SWITCH, DEVICE, ETC., TO BE REMOVED AND OUTLET BOX EXTENSION
INSTALLED FOR SURFACE CONDUIT OR SMR AND WIRE EXTENSION TO NEW OUTLET SHOWN.
REINSTALL PRESENT LIGHTING FIXTURE, SWITCH, DEVICE, ETC.
PRX
REMOVE PRESENT FIXTURE, SWITCH, DEVICE, ETC., AND CAP OUTLETRPC
REMOVE PRESENT FIXTURE, SWITCH, DEVICE, ETC., PATCH THE PLASTER IF IN PLASTER: CAP IF IN
METAL OR WOOD.
RPP
REMOVE PRESENT FIXTURE, SWITCH, DEVICE, ETC., TO BE REMOVED AND RELOCATED.RPR
REMOVE PRESENT FIXTURE, SWITCH, DEVICE, ETC., WIRE AND ALL RELATED EXPOSED RACEWAY
INSOFAR AS IS POSSIBLE. ALL DAMAGED SURFACES TO BE REPAIRED.
RPX
NON-FUSED DISCONNECT. FRAME SIZE AS INDICATED ON PLANS.
FUSED DISCONNECT. FRAME SIZE AND TRIP RATING AS INDICATED ON PLANS. PROVIDE FUSES PER
NAMEPLATE OF EQUIPMENT SERVED UNLESS OTHERWISE INDICATED.
COMBINATION MOTOR STARTER & DISCONNECT. FRAME SIZE, TRIP RATING, AND STARTER SIZE AS
INDICATED ON PLANS.
DISCONNECT SWITCH TAG KEY
SIZE
NF
3R
NO. OF POLES
NEMA TYPE
FUSE SIZE OR NF
VARIABLE FREQUENCY DRIVE - ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL
CONTRACTOR FOR FINAL CONNECTION.
AUTOMATIC TRANSFER SWITCH - SEE RISER DIAGRAM
TRANSFORMER - SEE RISER DIAGRAM
WIRING, RACEWAY, & GROUNDING
CONDUIT WITH BUSHING AND CAP
CONDUIT TURNED UP
CONDUIT TURNED DOWN
CONDUIT CONTINUED
SURFACE METAL RACEWAY, MOUNTING AND CONFIGURATION AS SPECIFIED.
CONCEALED CONDUIT AND WIRING
UNDER FLOOR OR UNDER GROUND CONDUIT AND WIRING
GROUND CABLEGND
GROUNDING TRIODE
EMERGENCY DUPLEX RECEPTACLE
QUAD RECEPTACLE
EMERGENCY QUAD RECEPTACLE
SPECIAL EQUIPMENT RECEPTACLE/EQUIPMENT CONNECTION. SUBSCRIPT INDICATES
NEMA CONFIGURATION, IF APPLICABLE. SEE EQUIPMENT CONNECTION SCHEDULE FOR
EXACT REQUIREMENTS.
JUNCTION BOX FLUSH (FINISHED SPACES) OR SURFACE (UNFINISHED SPACES) OUTLET
BOX. COORDINATE LOCATION WITH MANUFACTURER FOR EQUIPMENT MOUNTED BOXES.
ELECTRIC PUSH BUTTON - FLUSH (FINISHED SPACES) OR SURFACE (UNFINISHED SPACES) OUTLET BOX. MOUNT 46-INCHES ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED OR REQUIRED BY
SITE CONDITIONS.
PUSH BUTTON (3 POSITION) - FLUSH (FINISHED SPACES) OR SURFACE (UNFINISHED SPACES) OUTLET BOX. MOUNT 46-INCHES ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED OR REQUIRED BY
SITE CONDITIONS.
EMERGENCY STOP MUSHROOM TYPE BUTTON IN SURFACE MOUNTED BOX. MOUNT 46-INCHES ABOVE
FINISHED FLOOR UNLESS OTHERWISE INDICATED OR REQUIRED BY SITE CONDITIONS.
POKE-THRU. PROVIDE ELECTRICAL DEVICE. SAME DEVICE MAYBE SHOWN ON BOTH POWER AND
SYSTEMS PLANS.
POKE-THRU. PROVIDE COMBINATION ELECTRICAL/DATA DEVICE. SAME DEVICE IS SHOWN ON BOTH
POWER AND SYSTEMS PLANS.
POKE-THRU. PROVIDE DATA DEVICE. SAME DEVICE MAYBE SHOWN ON BOTH POWER AND SYSTEMS
PLANS.
ABOVE COUNTER+ WEATHER PROOFWP
CUSTOM MOUNTING HEIGHT+# ELECTRIC WATER COOLEREWC
ISOLATED GROUNDIG
DUPLEX WITH USB-A & USB-C
PORTS
USB
TAMPER RESIDENTTR
POWER DEVICE TAG KEY
INDICATES CIRCUIT
NUMBER
INDICATES PANEL NAME
DEVICE SYMBOL XX-XX
CORE DRILL
FLOOR BOX - PROVIDE DEVICES AND COUNTS AS SHOWN OR NOTED
FURNITURE FEED
CORD REEL
MOTORIZED DAMPER - PROVIDE 120V POWER AND LOCAL DISCONNECT. COORDINATE EXACT
LOCATIONS WITH M.C.
EQUIPMENT CONTROL PANEL. FINAL CONNECTION BY E.C.
CB
VFD
ATS
P
M M front
Txx
GROUNDING ROD
WIRING HOMERUN - INDICATES CIRCUIT CONDUIT AND WIRE TO PANELBOARD SEE PANEL SCHEDULE B1-3
J J J
CR
CP
M
POWER DEVICE NOMENCLATURE
EMERGENCY GFI DUPLEX RECEPTACLE
EXISTING PANELBOARD, FLUSH AND SURFACE MOUNTED RESPECTIVELY. DESIGNATION AS INDICATED.
REFER TO PANELBOARD SCHEDULES FOR EXACT REQUIREMENTS.
GENERAL NOTES
1. ALL ELECTRICAL WORK SHALL BE IN ACCORD WITH ALL APPLICABLE ORDINANCES, CODES AND REGULATIONS OF ALL AUTHORITIES HAVING JURISDICTION. ALL ELECTRICAL WORK SHALL BE INSPECTED AND APPROVED BY THE LOCAL ELECTRICAL INSPECTION AGENCY. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY FEES AND PERMITS, INCLUDING THE CERTIFICATE OF ELECTRICAL INSPECTION.
2. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR CONSTRUCTION SAFETY. ARCHITECT AND/OR ENGINEER SHALL ASSUME NO RESPONSIBILITY FOR WORKMAN'S, OR PEDESTRIAN'S SAFETY. NOTHING IN THE CONTRACT DOCUMENTS SHALL BE CONSTRUED TO INSTRUCT PROCEDURES OR COMPONENTS FOR
PROJECT SAFETY.
3. WHERE A CONFLICT ARISES BETWEEN PLANS, SPECIFICATIONS, DETAILS, SCHEDULES, APPLICABLE CODES
OR REGULATIONS, THE MOST STRINGENT SHALL APPLY.
4. NOTHING CONTAINED IN THE CONTRACT DOCUMENTS SHALL BE CONSTRUED TO CONFLICT WITH ANY NATIONAL, STATE, MUNICIPAL, OR LOCAL LAWS OR REGULATIONS GOVERNING THE WORK INDICATED OR SPECIFIED. THE ELECTRICAL CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE OWNER SHALL SATISFY
ALL SUCH REQUIREMENTS.
5. THE CONTRACT DOCUMENTS ARE COMPRISED OF DRAWINGS AND SPECIFICATIONS. EACH ELECTRICAL BIDDER SHALL VISIT SITE TO DETERMINE EXISTING CONDITIONS PRIOR TO SUBMITTING BID PROPOSAL.
BIDS SHALL BE BASED ON THE COMPLETE EXAMINATION OF THE DRAWINGS, SPECIFICATIONS AND EXISTING CONDITIONS. NO CONSIDERATION WILL BE GIVEN ANY CONTRACTOR WHO FAILS TO DO SO.
6. THE WORK UNDER THIS CONTRACT SHALL INCLUDE THE FURNISHING OF ALL NECESSARY MATERIALS, TOOLS, AND LABOR FOR A COMPLETE, AND WORKING INSTALLATION AS DEFINED BY THE PLANS AND SPECIFICATIONS. THE ELECTRICAL CONTRACTOR SHALL WARRANT THE WORK INDICATED AND SPECIFIED FOR A PERIOD OF ONE YEAR. THE WORK SHALL FUNCTION AS INTENDED, BE COMPLETE IN ALL DETAILS, AND SHALL INCLUDE ALL INDICATED, SPECIFIED, OR REQUIRED ACCESSORIES FOR A FUNCTIONING
SYSTEM.
7. THE ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY LIGHT AND POWER AS REQUIRED BY THE
GENERAL CONDITIONS OF THE SPECIFICATION.
8. THE ELECTRICAL CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER TRADES. ALL DEVICES PROVIDED BY OTHERS THAT REQUIRE LINE VOLTAGE ELECTRICAL POWER SHALL BE CONNECTED BY THE ELECTRICAL CONTRACTOR. POWER, PHONE, DATA, TV, AND SIMILAR DEVICE OUTLET LOCATIONS SHALL BE COORDINATED WITH THE ARCHITECTURAL INTERIOR LAYOUTS, THE GENERAL CONTRACTOR, AND THE
OWNER.
9. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OWNER'S PROJECT MANAGER PRIOR TO AND
FOR SCHEDULING ANY INTERRUPTION OF ANY BUILDING UTILITY.
10. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE LOCAL UTILITIES AND ARRANGE FOR THE FOLLOWING SERVICES: ELECTRICAL POWER, CABLE TV, AND TELEPHONE SERVICE. THE ELECTRICAL CONTRACTOR SHALL MEET WITH THE REPRESENTATIVES OF THE ELECTRICAL UTILITY & COMCAST TO CONFIRM DETAILS ON THE SERVICE AND METERING. THE ELECTRICAL CONTRACTOR SHALL PAY ALL
NECESSARY COSTS, FEES, AND PERMITS INVOLVED IN BRINGING SERVICE TO THE BUILDING.
11. THE ELECTRICAL CONTRACTOR AT THE SITE SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PERTAINING TO THE INSTALLATION OF THE ELECTRICAL SYSTEMS. WHERE A CONTRACTOR UNCOVERS CONDITIONS NOT INDICATED ON THE PLANS OR IN THE SPECIFICATIONS, HE SHALL NOTIFY THE ENGINEER
PRIOR TO PROCEEDING WITH ANY WORK. FAILURE TO NOTIFY THE ENGINEER WILL MAKE THE
CONTRACTOR RESPONSIBLE FOR ALL COSTS AND CONSEQUENCES OF SUCH FAILURE.
12. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND REPRESENT THE DESIGN/LAYOUT INTENT ONLY. THE ELECTRICAL CONTRACTOR SHALL DETERMINE CIRCUITING, ROUTING, WIRING ETC.., AS REQUIRED BY THE
SITE CONDITIONS, AND ALL APPLICABLE CODES.
13. ALL WIRING SHALL BE CONCEALED IN FINISHED AREAS AS SPECIFIED. WHERE PERMITTED IN THE SPECIFICATIONS, USE OF MC CABLE IN CONCEALED AREAS SHALL BE PER N.E.C., LOCAL CODES, AND INSPECTION AGENCY APPROVAL. OTHERWISE, USE EMT CONDUIT, MINIMUM 3/4" UNLESS NOTED OR
SPECIFIED OTHERWISE.
14. THE FOLLOWING CONDUCTORS SHALL BE RUN IN HEAVY WALL CONDUIT UNLESS OTHERWISE NOTED:
14.1.ALL FEEDERS RUN IN SLAB - MAY BY SCHEDULE 40 PVC.
14.2.WHERE REQUIRED BY THE N.E.C.
14.3.EXPOSED WIRING ON A ROOF - SEAL PROPERLY.
14.4.EXTERIOR, ABOVE GRADE WIRING.
15. FOLLOWING FEEDERS SHALL BE IN EMT UNLESS OTHERWISE NOTED:
15.1.BRANCH FEEDERS TO PANELS.
15.2.BRANCH RACEWAY RUN EXPOSED.
16. TRENCHING AND BACKFILL FOR UNDERGROUND CONDUITS SHALL BE BY THE ELECTRICAL CONTRACTOR.
17. UPON THE COMPLETION OF WORK THE E.C. SHALL PROVIDE ALL PANELBOARDS WITH TYPED PANEL
SCHEDULES TO CLEARLY DEFINE THE EQUIPMENT SERVED.
18. UPON THE COMPLETION OF WORK THE E.C. SHALL PROVIDE ALL DISTRIBUTION EQUIPMENT WITH TYPED NAMEPLATES TO CLEARLY DEFINE THE EQUIPMENT SERVED AND RECEPTACLE PLATES WITH CIRCUITS
SERVING EACH.
19. CHANNELING OF THE FLOORS SHALL BE MINIMIZED.
20. REFER TO REFLECTED CEILING PLANS FOR THE COORDINATED PLACEMENT OF LIGHTS, DIFFUSERS, SPRINKLERS, AND RETURN AIR GRIDS.
21. E.C. SHALL COORDINATE ALL RECEPTACLE AND LIGHT FIXTURES LOCATIONS WITH CASEWORK AND THE
OWNERS FIXTURES LAYOUT PLAN WHICH WILL BE DIMENSIONED.
22. ALL HOMERUNS WITH MORE THAN SIX (6) TOTAL CONDUCTORS SHALL BE A MINIMUM OF NO. 10 THWN
WIRE UNLESS SPECIFICALLY SIZED OTHERWISE.
23. ALL WORK SHOWN ON THE ELECTRICAL DRAWINGS SHALL BE BY THE ELECTRICAL CONTRACTOR UNLESS
SPECIFICALLY NOTED OTHERWISE.
24. CONTRACTOR SHALL REMOVE DEMOLITION DEBRIS COMPLETELY. CONTRACTOR SHALL SCHEDULE WITH
THE OWNER THE TIME, LOCATION, ELEVATOR AND HAULING ROUTE.
25. CONTRACTOR SHALL CLEAN UP ALL DEBRIS AT THE END OF EACH WORK DAY.
26. EXACT COUNTS/QUANTITIES FOR CONTRACT PURPOSES SHALL BE VERIFIED IN THE FIELD BY THE
CONTRACTOR AND INCLUDED AS PART OF THE BASE BID.
27. REFER TO ARCHITECTURAL DRAWING FOR ALL WALL HEIGHTS.
28. VERIFY EXACT LOCATION OF ALL MECHANICAL EQUIPMENT WITH THE MECHANICAL CONTRACTOR, PRIOR TO ROUGH-IN. E.C. SHALL ALSO INCLUDE COORDINATION WITH DEVICES BY M.C., WIRING REQUIREMENTS, INTERCONNECTIONS, AND TERMINATIONS AND PROVIDE AS REQUIRED.
29. ALL CONDUITS RUN IN EXPOSED AREAS SHALL BE MOUNTED TIGHT TO THE UNDERSIDE OF THE
STRUCTURAL STEEL. THIS APPLIES FOR ALL BRANCH CIRCUIT AND FEEDER CONDUITS.
30. ALL HOLES AND OPENINGS CREATED TO EXTEND THE ELECTRICAL SYSTEMS THROUGH FLOORS AND FIRE
RATED ASSEMBLIES SHALL BE FIRESTOPPED.
31. DURING THE BIDDING PROCESS, ELECTRICAL CONTRACTOR SHALL REVIEW DRAWINGS AND
SPECIFICATIONS OF ALL OTHER TRADES (GENERAL, HVAC, AND PLUMBING). ALL ITEMS REQUIRING POWER INDICATED ON THESE DRAWINGS BUT NOT INDICATED ON THE ELECTRICAL DRAWINGS SHALL BE CONSIDERED A PART OF THE ELECTRICAL CONTRACTORS WORK. THIS WORK SHALL BE INSTALLED AS PER
NEC AT NO ADDITIONAL COST TO THE OWNER
32. WHERE CONDUIT SIZES HAVE BEEN OMITTED, THE CONTRACTOR SHALL INSTALL THE CORRECT SIZES REQUIRED BY THE N.E.C. AS DETERMINED BY THE NUMBER OF WIRES TO BE INSTALLED. WHERE THE NUMBER AND OR SIZES OF HAVE BEEN OMITTED, THE CONTRACTOR SHALL INSTALL THE REQUIRED
NUMBER AND OR SIZES AS DETERMINED BY THE EQUIPMENT REQUIREMENTS OR FROM ADJACENT
SECTIONS AND CIRCUIT NUMBERS.
33. WIRE SIZE FOR BRANCH CIRCUITS SHALL BE ADJUSTED TO COMPENSATE FOR VOLTAGE DROP CALCULATIONS AS REQUIRED BY NEC. IF CIRCUIT RUN EXCEEDS 100FT. IN WIRE LENGTH, NEXT WIRE SIZE
(#10) SHALL BE USED.
34. STARTERS, COMBINATION STARTERS, CONTRACTORS, ETC.. FOR MECHANICAL EQUIPMENT SHALL BE
PROVIDED BY THE MECHANICAL CONTRACTOR. ALL POWER WIRING AND CONDUIT TO EQUIPMENT
TERMINALS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR. POWER TO MECHANICAL EQUIPMENT SHALL BE TURNED ON ONLY BY THE MECHANICAL CONTRACTOR. MECHANICAL NAME PLATE DATA SHALL
NOT BE COVERED BY ELECTRICAL DEVICES.
35. THE ELECTRICAL CONTRACTOR SHALL FURNISH SUBMITTALS IN ACCORDANCE WITH THE SPECIFICATIONS.
ALL SUBMITTALS SHALL BE REVIEWED AND STAMPED BY THE ENGINEER PRIOR TO INSTALLATION.
36. THE ELECTRICAL CONTRACTOR SHALL PROVIDE AS-BUILT DRAWINGS FOR THE ENTIRE PROJECT AS
DEFINED IN THE SPECIFICATIONS
37. THIS CONTRACTOR SHALL VISIT THE SITE AND FULLY INFORM HIMSELF OF ALL THE EXISTING CONDITIONS, WHICH IN ANY WAY WILL AFFECT THE EXECUTION OF HIS WORK AND THE REQUIREMENTS OF THIS CONTRACT AS SHOWN OR REASONABLY INFERRED ON THE DRAWINGS AND PRODUCT SPECIFICATIONS.
DESCRIPTIONABBREVIATIONDESCRIPTIONABBREVIATION DESCRIPTIONABBREVIATION
GROUNDG, GND,GRDAMPEREA/AMP NATIONAL FIRE PROTECTIONNFPA
GENERAL CONTRACTORGCARC FAULT INTERRUPTERAFCI ASSOCIATION
GENERATORGENABOVE FINISHED FLOORAFF NOT IN THIS CONTRACTNIC
GROUND FAULT INTERRUPTERGFIABOVE FINISHED GRADEAFG NON-METALLICNM
GROUND TERMINAL BOXGTBAUTHORITY HAVING JURISDICTIONAHJ NORMALLY OPENNO
HIGH INTENSITY DISCHARGEHIDALUMINUMAL NOT TO SCALENTS
HORSE POWERHPAMER. NATIONAL STANDARDS INSTITUTEANSI ON CENTEROC
HIGH POWER FACTORHPFAMERICAN STANDARDS ASSOCIATIONASA ORIGINAL EQUIPMENT MANUFACTUREROEM
HOMERUNHRAMER. SOCIETY OF TESTING MATERIALSASTM OCCUPATIONAL SAFETY AND HEALTHOSHA
HEATERHTRAMERICAN WIRE GAUGEAWG ADMINISTRATION
HEATING, VENTILATION, AIRHVACAMPERE TRIPAT POLEP
CONDITIONING CONTRACTORAUTOMATIC TRANSFER SWITCHATS PULL BOXPBOX
HIGH VOLTAGEHVBLANKBL PHOTOCELLPC
HERTZHZBREAKERBKR PLUMBING CONTRACTORP.C.
INTERNATIONAL CABLE ENGR. ASSOC.ICEACONDUITC PHASEPH / Ø
INSTITUTE OF ELECTRICAL ANDIEEECIRCUIT BREAKERCB, C/B PANELPNL
ELECTRONIC ENGINEERS-CKT BKR POSITIONPOS
ILLUMINATING ENGINEERING SOCIETYIESCIRCUITCKT PRIMARYPRI
INCHINCLOSED CIRCUIT TVCCTV POWERPWR
INCANDESCENTINCANCEILINGCLG RECEPTACLEREC / RECPT
INFRA-REDIRCONVENIENCE OUTLETCO RIGID GALVANIZED STEELRGS
JUNCTION BOXJB/JBOXCONNECTIONCONN RIGID GALVANIZED METAL CONDUITRMC
THOUSANDKCOPPERCU RAIN TIGHTRT
KILOVOLT-AMPEREKVADIRECT BURIALDB SCHEDULESCHED
KILOWATTKWDISCONNECTDISC SECONDARYSEC
KILOWATT HOURKWHDOWNDN SIGNALSIG
LIGHTING ARRESTERLADRAWINGDWG SURFACE MOUNTEDSM
LIGHTING CONTROL PANELLCPEACHEA SURFACE MOUNTED RACEWAYSMR
LIGHT EMITTING DIODELEDELECTRICAL CONTRACTORE.C. SPARESP
LIGHTSLTSEXHAUST FANEF SAFETY SWITCHSS
LIGHTINGLTGELECTRIC HEATEH SWSW
LOW VOLTAGELVELECTRONIC INDUSTRIES ASSOC.EIA SWITCHBOARDSWBD
METAL CLADMCELECTRIC METALLIC TUBINGEMT TELEPHONETEL / TELE
MECHANICAL CONTRACTORM.C.EXPLOSION PROOFXP TWIST LOCKTL
MAIN CIRCUIT BREAKERMCBEMERGENCYE, EM TAMPER PROOFTP
MOTOR CONTROL CENTERMCCELECTRICELEC TRANSFORMERTX / XFMR
MAIN DISTRIBUTION PANELMDPELECTRIC METALLIC TUBINGEMT TELEPHONE TERMINAL BOARDTTB
MANUFACTURERMFREQUIPMENTEQ/EQPM TELEVISIONTV
MANHOLEMHELECTRIC UNIT HEATEREUH TYPICALTYP
MAIN LUGS ONLYMLOELECTRIC WATER COOLEREWC UNIT HEATERUH
MISCELLANEOUSMISCEXISTINGEX UNDERWRITERS' LABORATORIES, INCUL
MOUNTEDMTDFIXTUREF UNLESS NOTED OTHERWISEUNO
MOUNTING HEIGHTMTG HGTFIRE ALARMFA VOLTAGEV
MOTORMTRFIRE ALARM ANNUNCIATOR PANELFAAP VAPOR TIGHTVT
NOT APPLICABLEN/AFIRE ALARM CONTROL PANELFACP WIRE; WATTW
NORMALLY CLOSEDNCFAN COIL UNITFCU WITHW/
ON-FUSED SAFETY SWITCHNFFEEDERFDR WITHOUTW/O
NATIONAL ELECTRIC CODENECFIXTUREFIXT WEATHER PROOFWP
NATIONAL ELECTRICALNEMAFLOORFL WATER TIGHTWT
MANUFACTURERS ASSOCIATIONFLUORESCENTFLUOR
FUSED SAFETY SWITCHFSS
FEETFT
ELECTRICAL ABBREVIATIONS
46" AFF
4" MIN
MAX
FOR COUNTERS
10"-24" DEEP
TYPICAL COUNTER HEIGHT
RECEPTACLE REFER TO
ARCHITECTURAL DETAILS
FOR ORIENTATION
18" AFF
TYPICAL
RECEPTACLE
ADA UNIT TYPE A & TYPE B
APARTMENT PANEL BOARD
TYPICAL WALL SWITCH
INTERCOM
CONTROL
TEMPERATURE
SENSORS
TOP OF HIGHEST
OPERABLE DEVICE
48" AFF
LOAD CENTERS &
PANELBOARDS (NON-ADA)
TOP OF HIGHEST
OPERABLE DEVICE
78" MAX AFF
24" AFF
BACK OF HOUSE
RECEPTACLE
(MECHANICAL/ELECTRICAL ROOM)
72" MAX AFF
DISCONNECT
SWITCHES,
STARTERS, AND
CONTACTORS
H a m le t
A v e n u e
C le a rw a te r, F lo ri d a
P h o n e
(7
-7
F a x (7
-3
C A
L ic
N o w w w .m c k im c re e d .c o m
DESCRIPTION DATE
REVISIONS
SCALE
DRAWING NUMBER
PROJ. MGR
REV.
REVISION
CHECKED
DESIGNED
DRAWN
MCE PROJ. #
PROJ START DATE:
STATUS:
PERMIT SET
NTS
Autodesk Docs://01030-0141_Pinellas_EV/01030-0141_22211 US Hwy 19 N_R22.rvt
PUBLIC WORKS
CAMPUS
22211 US HWY 19 N,
CLEARWATER, FL
33765
2023-03-16
01030-0141
AV
CP
BE
BD
E001
E L
E C
T R
IC
A
L D
A T
A S
H E
E T
P
IN
E L
L A
S C
O U
N T
Y
S
F T
H
A R
R
IS
O N
A V
E
C L
E A
R W
A T
E R
F
L O
R
ID
A
SCALE: NTS
DEVICE MOUNTING HEIGHT DETAIL
ELECTRICAL SHEET INDEX
E001 ELECTRICAL DATA SHEET
E100 ELECTRICAL PLAN AND RISER
Cody Pechacek, State of Florida, Professional Engineer, License No. PE95543. This item has been digitally signed and sealed by Cody Pechacek on the date indicated here. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
W P
W P
W P
W P
W P
W P
W P
W P
W P
W P
W P
W P
W P
W P
SIGN/SIGNAL
WAREHOUSE
C100
SIGN
MANUFACTURING
B110
BRIDGE WORK
AREA 2
B110B
BRIDGE WORK
AREA 1
B110A
E100
S
IG
N
S
IG
N
S
IG
N A
L
S
IG
N
A L
IN
F R
A S
T R
U C
T U
R E
R E
S P
O N
S E
S
IG
N
A L
E100
H2M
T-3
L2MA
MEZZANINE
B200
INTERIOREXTERIOR
FINAL GRADE
UTILITY
METER
PANEL
H2M
480Y/277VV
MLO
225A
PANEL
L2MA
208Y/120V
MCB
225A
PAD MOUNTED
TRANSFORMER
UTILITY
TRANSFORMER
750 KVA
480Y/277V
TRANSFORMER
T-3
75KVA
480-208Y/120V
GENERATOR
GEN 1
(TYPICAL OF 3)
480Y/277V
750KW
MSB
480Y/277V
3000A
MEZZANINE
INTERIOREXTERIOR
LOAD SUMMARY
EXISTING PNL DESIGNATION: L2MA
FED VIA PANEL: H2M
PNL RATED CAPACITY : 225A
EXISTING LOAD : 77A
REMOVED LOAD : 0A
ADDED LOAD : 28A
TOTAL: 104A
L2MA-341
L2MA-381
L2MA-391
L2MA-401
L2MA-301
L2MA-321
L2MA-361
SIGN
SIGNAL
SIGNAL
INFRASTRUCTURE
RESPONSE
H a m le t
A v e n u e
C le a rw a te r, F lo ri d a
P h o n e
(7
-7
F a x (7
-3
C A
L ic
N o w w w .m c k im c re e d .c o m
DESCRIPTION DATE
REVISIONS
SCALE
DRAWING NUMBER
PROJ. MGR
REV.
REVISION
CHECKED
DESIGNED
DRAWN
MCE PROJ. #
PROJ START DATE:
STATUS:
PERMIT SET
As indicated
Autodesk Docs://01030-0141_Pinellas_EV/01030-0141_22211 US Hwy 19 N_R22.rvt
PUBLIC WORKS
CAMPUS
22211 US HWY 19 N,
CLEARWATER, FL
33765
2023-03-16
01030-0141
AV
CP
BE
BD
E100
E L
E C
T R
IC
A
L P
L A
N A
N D
R
IS
E R
P
IN
E L
L A
S C
O U
N T
Y
S
F T
H
A R
R
IS
O N
A V
E
C L
E A
R W
A T
E R
F
L O
R
ID
A
GENERAL NOTES:
1. EXISTING CONDITIONS BASED ON OWNER PROVIDED DRAWINGS, INFORMATION, AND CASUAL FIELD
OBSERVATIONS.
2. CONTRACTOR SHALL FIELD VERIFY ALL APPLICABLE MEASUREMENTS AND AS-BUILT CONDITIONS THAT ARE TO BE
USED FOR NEW WORK PRIOR TO BEGINNING INSTALLATION.
3. ALL CONDUIT, CONDUCTORS, JUNCTION BOXES, AND ASSOCIATED APPURTENANCES SHALL MATCH EXISTING
INSTALLATION TYPE UNLESS OTHERWISE NOTED.
4. COORDINATE ALL DOWN TIME A MINIMUM OF 2 WEEKS IN ADVANCE OF EXPECTED INTERRUPTION. OWNER SHALL
APPROVE ALL DOWN TIME PRIOR TO EQUIPMENT BEING TAKEN OFFLINE.
# NEW WORK NOTES:
1. PROVIDE DUPLEX GFI RECEPTACLE WITH WHILE IN USE COVER MOUNTED TO SIDE OF BUILDING. COORDINATE
EXACT MOUNTING LOCATION AND HEIGHT WITH OWNER. CONDUIT AND FITTINGS SHALL MATCH EXISTING
INSTALLATION REQUIREMENTS.
SCALE: 1" = 20'-0"
POWER & SYSTEMS FIRST FLOOR PLAN
REF: E100SCALE: 1/8" = 1'-0"
POWER & SYSTEMS FLOOR PLAN MEZZANINE CALLOUT
SCALE: NTS
PARTIAL ELECTRICAL RISER
1. EXISTING LOAD DETERMINED FROM 30-DAY LOAD STUDY CONDUCTED FROM 06/21/2023 TO 07/24/2023.
NOTES:
TOTAL ESTIMATED DEMAND LOAD: 10.04 kVA
TOTAL ESTIMATED DEMAND AMPS: 28 A
TOTAL CONNECTED LOAD: 10.08 kVA
REC 10.08 kVA 99.60% 10.04 kVA TOTAL CONNECTED AMPS: 28 A
LOAD CLASSIFICATION CONNECTED DEMAND FACTOR DEMAND
TOTAL CONN. LOAD (kVA): 2.88 4.32 2.88
-- - - ---SPACE--- -- 41 -- 0 42 20 (EXISTING) LPC MEZ - - --
REC 1-#10,1-#10,1-#10G. 0.75" REC - ELECTRIC MAN LIFT CHARGING 20 39 1.44 1.44 40 20 REC - ELECTRIC MAN LIFT CHARGING 0.75" 1-#10,1-#10,1-#10G. REC
-- - - (EXISTING) POWER POLE REC 20 37 0 1.44 38 20 REC - ELECTRIC MAN LIFT CHARGING 0.75" 1-#10,1-#10,1-#10G. REC
35 0 1.44 36 20 REC - ELECTRIC MAN LIFT CHARGING 0.75" 1-#10,1-#10,1-#10G. REC
33 0 1.44 34 20 REC - ELECTRIC MAN LIFT CHARGING 0.75" 1-#10,1-#10,1-#10G. REC-- - - (EXISTING) VACUUM FOR CUTTER 20
31 0 1.44 32 20 REC - ELECTRIC MAN LIFT CHARGING 0.75" 1-#10,1-#10,1-#10G. REC
29 0 1.44 30 20 REC - ELECTRIC MAN LIFT CHARGING 0.75" 1-#10,1-#10,1-#10G. REC
27 0 0 28-- - - (EXISTING) CUTTER 20
25 0 0 26
20 (EXISTING) REC - WAREHOUSE - - --
23 0 0 24
-- - - (EXISTING) REC - EXT 20
21 0 0 22
20 (EXISTING) REC - WAREHOUSE - - --
19 0 0 20
-- - - (EXISTING) REC - B110 20
17 0 0 18
20 (EXISTING) REC - WAREHOUSE - - --
15 0 0 16
-- - - (EXISTING) REC - B110 20
13 0 0 14
20 (EXISTING) REC - WAREHOUSE - - --
11 0 0 12
-- - - (EXISTING) REC - B110 20
9 0 0 10
20 (EXISTING) REC - WAREHOUSE - - --
7 0 0 8 20 (EXISTING) GARAGE DOOR - - --
-- - - (EXISTING) REC - B110 20
5 0 0 6 20 (EXISTING) GARAGE DOOR - - --
3 0 0 4 20 (EXISTING) GARAGE DOOR - - --
-- - - (EXISTING) REC - B110 20
1 0 0 2 20 (EXISTING) GARAGE DOOR - - --
LOAD
CLASS
WIRE SIZE
PH / N / GND
COND
IN. LOAD DESCRIPTION
BRKR
RTG
CIR
NO A B C
CIR
NO
BRKR
RTG LOAD DESCRIPTION
COND
IN.
WIRE SIZE
PH / N / GND
LOAD
CLASS
WIRE: 4 MCB RATING: 225 A MOUNTING: Surface LOCATION: MEZZANINE B200
PHASE: 3 MAINS RATING: 225 A ENCLOSURE NEMA RATING: NEMA 1
VOLTAGE: 208/120 Wye MAINS TYPE: MCB SERVED FROM: T-3 22 :KAIC RATING
Panelboard: L2MA
1 REVISION 1 24-03-19
REF: E100SCALE: 3/16" = 1'-0"
POWER & SYSTEMS FLOOR PLAN CALLOUT
| Sheets |
| E100 - ELECTRICAL PLAN AND RISER |
| (828)252-8181 | |
| 2024-03-19T12:32:46-0500 | |
| Cody Pechacek | |
| I am the author of this document |
File details come from the government source that posted it. Updated .