Public_Works_Campus_Rev._1_-_22211_US_Hwy_19_N_-_Sealed.pdf

PDF 463 KB Posted

Attached to
EV Charging Infrastructure - 22211 US Highway 19 Clearwater - ARPA
Solicitation number
24-0470-ITB-C
Issued by
Pinellas County, Clewiston City, Florida

About this file

This document is an electrical design and specifications set for the Public Works Campus located at 22211 US Highway 19 in Clearwater, Florida, prepared by an engineering firm. The electrical drawings provide comprehensive details for electrical infrastructure, including power systems, electrical device mounting heights, panel schedules, and load calculations for a facility with multiple work areas such as sign manufacturing, infrastructure response, and bridge work areas. The plans include a 750 kVA utility transformer, a 750kW generator, and detailed electrical distribution information for the site, with specific focus on receptacle placements, conduit routing, and electrical system configurations.

The electrical design documents a 30-day load study conducted from June 21 to July 24, 2023, revealing a total estimated demand load of 10.04 kVA and 28 connected amps. The plans specify electrical requirements for various areas, including electric man lift charging stations, warehouse receptacles, and provisions for existing equipment. The electrical infrastructure is designed to support the facility's operational needs, with careful attention to mounting heights, circuit ratings, and compliance with national electrical codes. The documents include general notes emphasizing contractor responsibilities for coordination, field verification, utility coordination, and adherence to local regulations and safety standards.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

480/277 VOLT PANELBOARD, FLUSH AND SURFACE MOUNTED RESPECTIVELY. DESIGNATION AS

INDICATED. REFER TO PANELBOARD SCHEDULES FOR EXACT REQUIREMENTS.

208Y/120 OR 120/240 VOLT PANELBOARD, FLUSH AND SURFACE MOUNTED RESPECTIVELY.

DESIGNATION AS INDICATED. REFER TO PANELBOARD SCHEDULES FOR EXACT REQUIREMENTS.

ELECTRICAL POWER POLE, MOUNTING AND CONFIGURATION AS SPECIFIED.

MOTOR CONNECTION. ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL CONTRACTOR

FOR FINAL CONNECTION.

ENCLOSED CIRCUIT BREAKER. FRAME SIZE AND TRIP RATING AS INDICATED ON PLANS.

MANUAL MOTOR STARTER. STARTER TYPE AND SIZE AS INDICATED ON PLANS.

WALL FLOOR CEILING

125 VOLT, 3 WIRE DUPLEX RECEPTACLE FLUSH (FINISHED SPACES) OR SURFACE

(UNFINISHED SPACES) OUTLET BOX.

125 VOLT, 3 WIRE DUPLEX RECEPTACLE GFI FLUSH (FINISHED SPACES) OR SURFACE

(UNFINISHED SPACES) OUTLET BOX.

POWER DEVICESPOWER EQUIPMENT

GENERAL

DEMOLITION KEYED NOTE.#

NEW WORK KEYED NOTE.##

REMOVE WIRING, CABLING, ETC. TO THIS POINT.

CONNECT WIRING, CABLING, ETC. TO THIS POINT.

FEEDER TAG - SEE FEEDER SCHEDULE

X

XXX

PRESENT LIGHTING FIXTURE, SWITCH, DEVICE, ETC., TO REMAIN.PR

PRESENT LIGHTING FIXTURE, SWITCH, DEVICE, ETC., TO BE REMOVED AND REPLACED WITH NEW.PRN

PRESENT LIGHTING FIXTURE, SWITCH, DEVICE, ETC., SHOWN AT NEW LOCATIONPRR

PRESENT LIGHTING FIXTURE, SWITCH, DEVICE, ETC., TO BE REMOVED AND OUTLET BOX EXTENSION

INSTALLED FOR SURFACE CONDUIT OR SMR AND WIRE EXTENSION TO NEW OUTLET SHOWN.

REINSTALL PRESENT LIGHTING FIXTURE, SWITCH, DEVICE, ETC.

PRX

REMOVE PRESENT FIXTURE, SWITCH, DEVICE, ETC., AND CAP OUTLETRPC

REMOVE PRESENT FIXTURE, SWITCH, DEVICE, ETC., PATCH THE PLASTER IF IN PLASTER: CAP IF IN

METAL OR WOOD.

RPP

REMOVE PRESENT FIXTURE, SWITCH, DEVICE, ETC., TO BE REMOVED AND RELOCATED.RPR

REMOVE PRESENT FIXTURE, SWITCH, DEVICE, ETC., WIRE AND ALL RELATED EXPOSED RACEWAY

INSOFAR AS IS POSSIBLE. ALL DAMAGED SURFACES TO BE REPAIRED.

RPX

NON-FUSED DISCONNECT. FRAME SIZE AS INDICATED ON PLANS.

FUSED DISCONNECT. FRAME SIZE AND TRIP RATING AS INDICATED ON PLANS. PROVIDE FUSES PER

NAMEPLATE OF EQUIPMENT SERVED UNLESS OTHERWISE INDICATED.

COMBINATION MOTOR STARTER & DISCONNECT. FRAME SIZE, TRIP RATING, AND STARTER SIZE AS

INDICATED ON PLANS.

DISCONNECT SWITCH TAG KEY

SIZE

NF

3R

NO. OF POLES

NEMA TYPE

FUSE SIZE OR NF

VARIABLE FREQUENCY DRIVE - ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL

CONTRACTOR FOR FINAL CONNECTION.

AUTOMATIC TRANSFER SWITCH - SEE RISER DIAGRAM

TRANSFORMER - SEE RISER DIAGRAM

WIRING, RACEWAY, & GROUNDING

CONDUIT WITH BUSHING AND CAP

CONDUIT TURNED UP

CONDUIT TURNED DOWN

CONDUIT CONTINUED

SURFACE METAL RACEWAY, MOUNTING AND CONFIGURATION AS SPECIFIED.

CONCEALED CONDUIT AND WIRING

UNDER FLOOR OR UNDER GROUND CONDUIT AND WIRING

GROUND CABLEGND

GROUNDING TRIODE

EMERGENCY DUPLEX RECEPTACLE

QUAD RECEPTACLE

EMERGENCY QUAD RECEPTACLE

SPECIAL EQUIPMENT RECEPTACLE/EQUIPMENT CONNECTION. SUBSCRIPT INDICATES

NEMA CONFIGURATION, IF APPLICABLE. SEE EQUIPMENT CONNECTION SCHEDULE FOR

EXACT REQUIREMENTS.

JUNCTION BOX FLUSH (FINISHED SPACES) OR SURFACE (UNFINISHED SPACES) OUTLET

BOX. COORDINATE LOCATION WITH MANUFACTURER FOR EQUIPMENT MOUNTED BOXES.

ELECTRIC PUSH BUTTON - FLUSH (FINISHED SPACES) OR SURFACE (UNFINISHED SPACES) OUTLET BOX. MOUNT 46-INCHES ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED OR REQUIRED BY

SITE CONDITIONS.

PUSH BUTTON (3 POSITION) - FLUSH (FINISHED SPACES) OR SURFACE (UNFINISHED SPACES) OUTLET BOX. MOUNT 46-INCHES ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED OR REQUIRED BY

SITE CONDITIONS.

EMERGENCY STOP MUSHROOM TYPE BUTTON IN SURFACE MOUNTED BOX. MOUNT 46-INCHES ABOVE

FINISHED FLOOR UNLESS OTHERWISE INDICATED OR REQUIRED BY SITE CONDITIONS.

POKE-THRU. PROVIDE ELECTRICAL DEVICE. SAME DEVICE MAYBE SHOWN ON BOTH POWER AND

SYSTEMS PLANS.

POKE-THRU. PROVIDE COMBINATION ELECTRICAL/DATA DEVICE. SAME DEVICE IS SHOWN ON BOTH

POWER AND SYSTEMS PLANS.

POKE-THRU. PROVIDE DATA DEVICE. SAME DEVICE MAYBE SHOWN ON BOTH POWER AND SYSTEMS

PLANS.

ABOVE COUNTER+ WEATHER PROOFWP

CUSTOM MOUNTING HEIGHT+# ELECTRIC WATER COOLEREWC

ISOLATED GROUNDIG

DUPLEX WITH USB-A & USB-C

PORTS

USB

TAMPER RESIDENTTR

POWER DEVICE TAG KEY

INDICATES CIRCUIT

NUMBER

INDICATES PANEL NAME

DEVICE SYMBOL XX-XX

CORE DRILL

FLOOR BOX - PROVIDE DEVICES AND COUNTS AS SHOWN OR NOTED

FURNITURE FEED

CORD REEL

MOTORIZED DAMPER - PROVIDE 120V POWER AND LOCAL DISCONNECT. COORDINATE EXACT

LOCATIONS WITH M.C.

EQUIPMENT CONTROL PANEL. FINAL CONNECTION BY E.C.

CB

VFD

ATS

P

M M front

Txx

GROUNDING ROD

WIRING HOMERUN - INDICATES CIRCUIT CONDUIT AND WIRE TO PANELBOARD SEE PANEL SCHEDULE B1-3

J J J

CR

CP

M

POWER DEVICE NOMENCLATURE

EMERGENCY GFI DUPLEX RECEPTACLE

EXISTING PANELBOARD, FLUSH AND SURFACE MOUNTED RESPECTIVELY. DESIGNATION AS INDICATED.

REFER TO PANELBOARD SCHEDULES FOR EXACT REQUIREMENTS.

GENERAL NOTES

1. ALL ELECTRICAL WORK SHALL BE IN ACCORD WITH ALL APPLICABLE ORDINANCES, CODES AND REGULATIONS OF ALL AUTHORITIES HAVING JURISDICTION. ALL ELECTRICAL WORK SHALL BE INSPECTED AND APPROVED BY THE LOCAL ELECTRICAL INSPECTION AGENCY. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY FEES AND PERMITS, INCLUDING THE CERTIFICATE OF ELECTRICAL INSPECTION.

2. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR CONSTRUCTION SAFETY. ARCHITECT AND/OR ENGINEER SHALL ASSUME NO RESPONSIBILITY FOR WORKMAN'S, OR PEDESTRIAN'S SAFETY. NOTHING IN THE CONTRACT DOCUMENTS SHALL BE CONSTRUED TO INSTRUCT PROCEDURES OR COMPONENTS FOR

PROJECT SAFETY.

3. WHERE A CONFLICT ARISES BETWEEN PLANS, SPECIFICATIONS, DETAILS, SCHEDULES, APPLICABLE CODES

OR REGULATIONS, THE MOST STRINGENT SHALL APPLY.

4. NOTHING CONTAINED IN THE CONTRACT DOCUMENTS SHALL BE CONSTRUED TO CONFLICT WITH ANY NATIONAL, STATE, MUNICIPAL, OR LOCAL LAWS OR REGULATIONS GOVERNING THE WORK INDICATED OR SPECIFIED. THE ELECTRICAL CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE OWNER SHALL SATISFY

ALL SUCH REQUIREMENTS.

5. THE CONTRACT DOCUMENTS ARE COMPRISED OF DRAWINGS AND SPECIFICATIONS. EACH ELECTRICAL BIDDER SHALL VISIT SITE TO DETERMINE EXISTING CONDITIONS PRIOR TO SUBMITTING BID PROPOSAL.

BIDS SHALL BE BASED ON THE COMPLETE EXAMINATION OF THE DRAWINGS, SPECIFICATIONS AND EXISTING CONDITIONS. NO CONSIDERATION WILL BE GIVEN ANY CONTRACTOR WHO FAILS TO DO SO.

6. THE WORK UNDER THIS CONTRACT SHALL INCLUDE THE FURNISHING OF ALL NECESSARY MATERIALS, TOOLS, AND LABOR FOR A COMPLETE, AND WORKING INSTALLATION AS DEFINED BY THE PLANS AND SPECIFICATIONS. THE ELECTRICAL CONTRACTOR SHALL WARRANT THE WORK INDICATED AND SPECIFIED FOR A PERIOD OF ONE YEAR. THE WORK SHALL FUNCTION AS INTENDED, BE COMPLETE IN ALL DETAILS, AND SHALL INCLUDE ALL INDICATED, SPECIFIED, OR REQUIRED ACCESSORIES FOR A FUNCTIONING

SYSTEM.

7. THE ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY LIGHT AND POWER AS REQUIRED BY THE

GENERAL CONDITIONS OF THE SPECIFICATION.

8. THE ELECTRICAL CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER TRADES. ALL DEVICES PROVIDED BY OTHERS THAT REQUIRE LINE VOLTAGE ELECTRICAL POWER SHALL BE CONNECTED BY THE ELECTRICAL CONTRACTOR. POWER, PHONE, DATA, TV, AND SIMILAR DEVICE OUTLET LOCATIONS SHALL BE COORDINATED WITH THE ARCHITECTURAL INTERIOR LAYOUTS, THE GENERAL CONTRACTOR, AND THE

OWNER.

9. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OWNER'S PROJECT MANAGER PRIOR TO AND

FOR SCHEDULING ANY INTERRUPTION OF ANY BUILDING UTILITY.

10. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE LOCAL UTILITIES AND ARRANGE FOR THE FOLLOWING SERVICES: ELECTRICAL POWER, CABLE TV, AND TELEPHONE SERVICE. THE ELECTRICAL CONTRACTOR SHALL MEET WITH THE REPRESENTATIVES OF THE ELECTRICAL UTILITY & COMCAST TO CONFIRM DETAILS ON THE SERVICE AND METERING. THE ELECTRICAL CONTRACTOR SHALL PAY ALL

NECESSARY COSTS, FEES, AND PERMITS INVOLVED IN BRINGING SERVICE TO THE BUILDING.

11. THE ELECTRICAL CONTRACTOR AT THE SITE SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PERTAINING TO THE INSTALLATION OF THE ELECTRICAL SYSTEMS. WHERE A CONTRACTOR UNCOVERS CONDITIONS NOT INDICATED ON THE PLANS OR IN THE SPECIFICATIONS, HE SHALL NOTIFY THE ENGINEER

PRIOR TO PROCEEDING WITH ANY WORK. FAILURE TO NOTIFY THE ENGINEER WILL MAKE THE

CONTRACTOR RESPONSIBLE FOR ALL COSTS AND CONSEQUENCES OF SUCH FAILURE.

12. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND REPRESENT THE DESIGN/LAYOUT INTENT ONLY. THE ELECTRICAL CONTRACTOR SHALL DETERMINE CIRCUITING, ROUTING, WIRING ETC.., AS REQUIRED BY THE

SITE CONDITIONS, AND ALL APPLICABLE CODES.

13. ALL WIRING SHALL BE CONCEALED IN FINISHED AREAS AS SPECIFIED. WHERE PERMITTED IN THE SPECIFICATIONS, USE OF MC CABLE IN CONCEALED AREAS SHALL BE PER N.E.C., LOCAL CODES, AND INSPECTION AGENCY APPROVAL. OTHERWISE, USE EMT CONDUIT, MINIMUM 3/4" UNLESS NOTED OR

SPECIFIED OTHERWISE.

14. THE FOLLOWING CONDUCTORS SHALL BE RUN IN HEAVY WALL CONDUIT UNLESS OTHERWISE NOTED:

14.1.ALL FEEDERS RUN IN SLAB - MAY BY SCHEDULE 40 PVC.

14.2.WHERE REQUIRED BY THE N.E.C.

14.3.EXPOSED WIRING ON A ROOF - SEAL PROPERLY.

14.4.EXTERIOR, ABOVE GRADE WIRING.

15. FOLLOWING FEEDERS SHALL BE IN EMT UNLESS OTHERWISE NOTED:

15.1.BRANCH FEEDERS TO PANELS.

15.2.BRANCH RACEWAY RUN EXPOSED.

16. TRENCHING AND BACKFILL FOR UNDERGROUND CONDUITS SHALL BE BY THE ELECTRICAL CONTRACTOR.

17. UPON THE COMPLETION OF WORK THE E.C. SHALL PROVIDE ALL PANELBOARDS WITH TYPED PANEL

SCHEDULES TO CLEARLY DEFINE THE EQUIPMENT SERVED.

18. UPON THE COMPLETION OF WORK THE E.C. SHALL PROVIDE ALL DISTRIBUTION EQUIPMENT WITH TYPED NAMEPLATES TO CLEARLY DEFINE THE EQUIPMENT SERVED AND RECEPTACLE PLATES WITH CIRCUITS

SERVING EACH.

19. CHANNELING OF THE FLOORS SHALL BE MINIMIZED.

20. REFER TO REFLECTED CEILING PLANS FOR THE COORDINATED PLACEMENT OF LIGHTS, DIFFUSERS, SPRINKLERS, AND RETURN AIR GRIDS.

21. E.C. SHALL COORDINATE ALL RECEPTACLE AND LIGHT FIXTURES LOCATIONS WITH CASEWORK AND THE

OWNERS FIXTURES LAYOUT PLAN WHICH WILL BE DIMENSIONED.

22. ALL HOMERUNS WITH MORE THAN SIX (6) TOTAL CONDUCTORS SHALL BE A MINIMUM OF NO. 10 THWN

WIRE UNLESS SPECIFICALLY SIZED OTHERWISE.

23. ALL WORK SHOWN ON THE ELECTRICAL DRAWINGS SHALL BE BY THE ELECTRICAL CONTRACTOR UNLESS

SPECIFICALLY NOTED OTHERWISE.

24. CONTRACTOR SHALL REMOVE DEMOLITION DEBRIS COMPLETELY. CONTRACTOR SHALL SCHEDULE WITH

THE OWNER THE TIME, LOCATION, ELEVATOR AND HAULING ROUTE.

25. CONTRACTOR SHALL CLEAN UP ALL DEBRIS AT THE END OF EACH WORK DAY.

26. EXACT COUNTS/QUANTITIES FOR CONTRACT PURPOSES SHALL BE VERIFIED IN THE FIELD BY THE

CONTRACTOR AND INCLUDED AS PART OF THE BASE BID.

27. REFER TO ARCHITECTURAL DRAWING FOR ALL WALL HEIGHTS.

28. VERIFY EXACT LOCATION OF ALL MECHANICAL EQUIPMENT WITH THE MECHANICAL CONTRACTOR, PRIOR TO ROUGH-IN. E.C. SHALL ALSO INCLUDE COORDINATION WITH DEVICES BY M.C., WIRING REQUIREMENTS, INTERCONNECTIONS, AND TERMINATIONS AND PROVIDE AS REQUIRED.

29. ALL CONDUITS RUN IN EXPOSED AREAS SHALL BE MOUNTED TIGHT TO THE UNDERSIDE OF THE

STRUCTURAL STEEL. THIS APPLIES FOR ALL BRANCH CIRCUIT AND FEEDER CONDUITS.

30. ALL HOLES AND OPENINGS CREATED TO EXTEND THE ELECTRICAL SYSTEMS THROUGH FLOORS AND FIRE

RATED ASSEMBLIES SHALL BE FIRESTOPPED.

31. DURING THE BIDDING PROCESS, ELECTRICAL CONTRACTOR SHALL REVIEW DRAWINGS AND

SPECIFICATIONS OF ALL OTHER TRADES (GENERAL, HVAC, AND PLUMBING). ALL ITEMS REQUIRING POWER INDICATED ON THESE DRAWINGS BUT NOT INDICATED ON THE ELECTRICAL DRAWINGS SHALL BE CONSIDERED A PART OF THE ELECTRICAL CONTRACTORS WORK. THIS WORK SHALL BE INSTALLED AS PER

NEC AT NO ADDITIONAL COST TO THE OWNER

32. WHERE CONDUIT SIZES HAVE BEEN OMITTED, THE CONTRACTOR SHALL INSTALL THE CORRECT SIZES REQUIRED BY THE N.E.C. AS DETERMINED BY THE NUMBER OF WIRES TO BE INSTALLED. WHERE THE NUMBER AND OR SIZES OF HAVE BEEN OMITTED, THE CONTRACTOR SHALL INSTALL THE REQUIRED

NUMBER AND OR SIZES AS DETERMINED BY THE EQUIPMENT REQUIREMENTS OR FROM ADJACENT

SECTIONS AND CIRCUIT NUMBERS.

33. WIRE SIZE FOR BRANCH CIRCUITS SHALL BE ADJUSTED TO COMPENSATE FOR VOLTAGE DROP CALCULATIONS AS REQUIRED BY NEC. IF CIRCUIT RUN EXCEEDS 100FT. IN WIRE LENGTH, NEXT WIRE SIZE

(#10) SHALL BE USED.

34. STARTERS, COMBINATION STARTERS, CONTRACTORS, ETC.. FOR MECHANICAL EQUIPMENT SHALL BE

PROVIDED BY THE MECHANICAL CONTRACTOR. ALL POWER WIRING AND CONDUIT TO EQUIPMENT

TERMINALS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR. POWER TO MECHANICAL EQUIPMENT SHALL BE TURNED ON ONLY BY THE MECHANICAL CONTRACTOR. MECHANICAL NAME PLATE DATA SHALL

NOT BE COVERED BY ELECTRICAL DEVICES.

35. THE ELECTRICAL CONTRACTOR SHALL FURNISH SUBMITTALS IN ACCORDANCE WITH THE SPECIFICATIONS.

ALL SUBMITTALS SHALL BE REVIEWED AND STAMPED BY THE ENGINEER PRIOR TO INSTALLATION.

36. THE ELECTRICAL CONTRACTOR SHALL PROVIDE AS-BUILT DRAWINGS FOR THE ENTIRE PROJECT AS

DEFINED IN THE SPECIFICATIONS

37. THIS CONTRACTOR SHALL VISIT THE SITE AND FULLY INFORM HIMSELF OF ALL THE EXISTING CONDITIONS, WHICH IN ANY WAY WILL AFFECT THE EXECUTION OF HIS WORK AND THE REQUIREMENTS OF THIS CONTRACT AS SHOWN OR REASONABLY INFERRED ON THE DRAWINGS AND PRODUCT SPECIFICATIONS.

DESCRIPTIONABBREVIATIONDESCRIPTIONABBREVIATION DESCRIPTIONABBREVIATION

GROUNDG, GND,GRDAMPEREA/AMP NATIONAL FIRE PROTECTIONNFPA

GENERAL CONTRACTORGCARC FAULT INTERRUPTERAFCI ASSOCIATION

GENERATORGENABOVE FINISHED FLOORAFF NOT IN THIS CONTRACTNIC

GROUND FAULT INTERRUPTERGFIABOVE FINISHED GRADEAFG NON-METALLICNM

GROUND TERMINAL BOXGTBAUTHORITY HAVING JURISDICTIONAHJ NORMALLY OPENNO

HIGH INTENSITY DISCHARGEHIDALUMINUMAL NOT TO SCALENTS

HORSE POWERHPAMER. NATIONAL STANDARDS INSTITUTEANSI ON CENTEROC

HIGH POWER FACTORHPFAMERICAN STANDARDS ASSOCIATIONASA ORIGINAL EQUIPMENT MANUFACTUREROEM

HOMERUNHRAMER. SOCIETY OF TESTING MATERIALSASTM OCCUPATIONAL SAFETY AND HEALTHOSHA

HEATERHTRAMERICAN WIRE GAUGEAWG ADMINISTRATION

HEATING, VENTILATION, AIRHVACAMPERE TRIPAT POLEP

CONDITIONING CONTRACTORAUTOMATIC TRANSFER SWITCHATS PULL BOXPBOX

HIGH VOLTAGEHVBLANKBL PHOTOCELLPC

HERTZHZBREAKERBKR PLUMBING CONTRACTORP.C.

INTERNATIONAL CABLE ENGR. ASSOC.ICEACONDUITC PHASEPH / Ø

INSTITUTE OF ELECTRICAL ANDIEEECIRCUIT BREAKERCB, C/B PANELPNL

ELECTRONIC ENGINEERS-CKT BKR POSITIONPOS

ILLUMINATING ENGINEERING SOCIETYIESCIRCUITCKT PRIMARYPRI

INCHINCLOSED CIRCUIT TVCCTV POWERPWR

INCANDESCENTINCANCEILINGCLG RECEPTACLEREC / RECPT

INFRA-REDIRCONVENIENCE OUTLETCO RIGID GALVANIZED STEELRGS

JUNCTION BOXJB/JBOXCONNECTIONCONN RIGID GALVANIZED METAL CONDUITRMC

THOUSANDKCOPPERCU RAIN TIGHTRT

KILOVOLT-AMPEREKVADIRECT BURIALDB SCHEDULESCHED

KILOWATTKWDISCONNECTDISC SECONDARYSEC

KILOWATT HOURKWHDOWNDN SIGNALSIG

LIGHTING ARRESTERLADRAWINGDWG SURFACE MOUNTEDSM

LIGHTING CONTROL PANELLCPEACHEA SURFACE MOUNTED RACEWAYSMR

LIGHT EMITTING DIODELEDELECTRICAL CONTRACTORE.C. SPARESP

LIGHTSLTSEXHAUST FANEF SAFETY SWITCHSS

LIGHTINGLTGELECTRIC HEATEH SWSW

LOW VOLTAGELVELECTRONIC INDUSTRIES ASSOC.EIA SWITCHBOARDSWBD

METAL CLADMCELECTRIC METALLIC TUBINGEMT TELEPHONETEL / TELE

MECHANICAL CONTRACTORM.C.EXPLOSION PROOFXP TWIST LOCKTL

MAIN CIRCUIT BREAKERMCBEMERGENCYE, EM TAMPER PROOFTP

MOTOR CONTROL CENTERMCCELECTRICELEC TRANSFORMERTX / XFMR

MAIN DISTRIBUTION PANELMDPELECTRIC METALLIC TUBINGEMT TELEPHONE TERMINAL BOARDTTB

MANUFACTURERMFREQUIPMENTEQ/EQPM TELEVISIONTV

MANHOLEMHELECTRIC UNIT HEATEREUH TYPICALTYP

MAIN LUGS ONLYMLOELECTRIC WATER COOLEREWC UNIT HEATERUH

MISCELLANEOUSMISCEXISTINGEX UNDERWRITERS' LABORATORIES, INCUL

MOUNTEDMTDFIXTUREF UNLESS NOTED OTHERWISEUNO

MOUNTING HEIGHTMTG HGTFIRE ALARMFA VOLTAGEV

MOTORMTRFIRE ALARM ANNUNCIATOR PANELFAAP VAPOR TIGHTVT

NOT APPLICABLEN/AFIRE ALARM CONTROL PANELFACP WIRE; WATTW

NORMALLY CLOSEDNCFAN COIL UNITFCU WITHW/

ON-FUSED SAFETY SWITCHNFFEEDERFDR WITHOUTW/O

NATIONAL ELECTRIC CODENECFIXTUREFIXT WEATHER PROOFWP

NATIONAL ELECTRICALNEMAFLOORFL WATER TIGHTWT

MANUFACTURERS ASSOCIATIONFLUORESCENTFLUOR

FUSED SAFETY SWITCHFSS

FEETFT

ELECTRICAL ABBREVIATIONS

46" AFF

4" MIN

MAX

FOR COUNTERS

10"-24" DEEP

TYPICAL COUNTER HEIGHT

RECEPTACLE REFER TO

ARCHITECTURAL DETAILS

FOR ORIENTATION

18" AFF

TYPICAL

RECEPTACLE

ADA UNIT TYPE A & TYPE B

APARTMENT PANEL BOARD

TYPICAL WALL SWITCH

INTERCOM

CONTROL

TEMPERATURE

SENSORS

TOP OF HIGHEST

OPERABLE DEVICE

48" AFF

LOAD CENTERS &

PANELBOARDS (NON-ADA)

TOP OF HIGHEST

OPERABLE DEVICE

78" MAX AFF

24" AFF

BACK OF HOUSE

RECEPTACLE

(MECHANICAL/ELECTRICAL ROOM)

72" MAX AFF

DISCONNECT

SWITCHES,

STARTERS, AND

CONTACTORS

H a m le t

A v e n u e

C le a rw a te r, F lo ri d a

P h o n e

(7

-7

F a x (7

-3

C A

L ic

N o w w w .m c k im c re e d .c o m

DESCRIPTION DATE

REVISIONS

SCALE

DRAWING NUMBER

PROJ. MGR

REV.

REVISION

CHECKED

DESIGNED

DRAWN

MCE PROJ. #

PROJ START DATE:

STATUS:

PERMIT SET

NTS

Autodesk Docs://01030-0141_Pinellas_EV/01030-0141_22211 US Hwy 19 N_R22.rvt

PUBLIC WORKS

CAMPUS

22211 US HWY 19 N,

CLEARWATER, FL

33765

2023-03-16

01030-0141

AV

CP

BE

BD

E001

E L

E C

T R

IC

A

L D

A T

A S

H E

E T

P

IN

E L

L A

S C

O U

N T

Y

S

F T

H

A R

R

IS

O N

A V

E

C L

E A

R W

A T

E R

F

L O

R

ID

A

SCALE: NTS

DEVICE MOUNTING HEIGHT DETAIL

ELECTRICAL SHEET INDEX

E001 ELECTRICAL DATA SHEET

E100 ELECTRICAL PLAN AND RISER

Cody Pechacek, State of Florida, Professional Engineer, License No. PE95543. This item has been digitally signed and sealed by Cody Pechacek on the date indicated here. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

W P

W P

W P

W P

W P

W P

W P

W P

W P

W P

W P

W P

W P

W P

SIGN/SIGNAL

WAREHOUSE

C100

SIGN

MANUFACTURING

B110

BRIDGE WORK

AREA 2

B110B

BRIDGE WORK

AREA 1

B110A

E100

S

IG

N

S

IG

N

S

IG

N A

L

S

IG

N

A L

IN

F R

A S

T R

U C

T U

R E

R E

S P

O N

S E

S

IG

N

A L

E100

H2M

T-3

L2MA

MEZZANINE

B200

INTERIOREXTERIOR

FINAL GRADE

UTILITY

METER

PANEL

H2M

480Y/277VV

MLO

225A

PANEL

L2MA

208Y/120V

MCB

225A

PAD MOUNTED

TRANSFORMER

UTILITY

TRANSFORMER

750 KVA

480Y/277V

TRANSFORMER

T-3

75KVA

480-208Y/120V

GENERATOR

GEN 1

(TYPICAL OF 3)

480Y/277V

750KW

MSB

480Y/277V

3000A

MEZZANINE

INTERIOREXTERIOR

LOAD SUMMARY

EXISTING PNL DESIGNATION: L2MA

FED VIA PANEL: H2M

PNL RATED CAPACITY : 225A

EXISTING LOAD : 77A

REMOVED LOAD : 0A

ADDED LOAD : 28A

TOTAL: 104A

L2MA-341

L2MA-381

L2MA-391

L2MA-401

L2MA-301

L2MA-321

L2MA-361

SIGN

SIGNAL

SIGNAL

INFRASTRUCTURE

RESPONSE

H a m le t

A v e n u e

C le a rw a te r, F lo ri d a

P h o n e

(7

-7

F a x (7

-3

C A

L ic

N o w w w .m c k im c re e d .c o m

DESCRIPTION DATE

REVISIONS

SCALE

DRAWING NUMBER

PROJ. MGR

REV.

REVISION

CHECKED

DESIGNED

DRAWN

MCE PROJ. #

PROJ START DATE:

STATUS:

PERMIT SET

As indicated

Autodesk Docs://01030-0141_Pinellas_EV/01030-0141_22211 US Hwy 19 N_R22.rvt

PUBLIC WORKS

CAMPUS

22211 US HWY 19 N,

CLEARWATER, FL

33765

2023-03-16

01030-0141

AV

CP

BE

BD

E100

E L

E C

T R

IC

A

L P

L A

N A

N D

R

IS

E R

P

IN

E L

L A

S C

O U

N T

Y

S

F T

H

A R

R

IS

O N

A V

E

C L

E A

R W

A T

E R

F

L O

R

ID

A

GENERAL NOTES:

1. EXISTING CONDITIONS BASED ON OWNER PROVIDED DRAWINGS, INFORMATION, AND CASUAL FIELD

OBSERVATIONS.

2. CONTRACTOR SHALL FIELD VERIFY ALL APPLICABLE MEASUREMENTS AND AS-BUILT CONDITIONS THAT ARE TO BE

USED FOR NEW WORK PRIOR TO BEGINNING INSTALLATION.

3. ALL CONDUIT, CONDUCTORS, JUNCTION BOXES, AND ASSOCIATED APPURTENANCES SHALL MATCH EXISTING

INSTALLATION TYPE UNLESS OTHERWISE NOTED.

4. COORDINATE ALL DOWN TIME A MINIMUM OF 2 WEEKS IN ADVANCE OF EXPECTED INTERRUPTION. OWNER SHALL

APPROVE ALL DOWN TIME PRIOR TO EQUIPMENT BEING TAKEN OFFLINE.

# NEW WORK NOTES:

1. PROVIDE DUPLEX GFI RECEPTACLE WITH WHILE IN USE COVER MOUNTED TO SIDE OF BUILDING. COORDINATE

EXACT MOUNTING LOCATION AND HEIGHT WITH OWNER. CONDUIT AND FITTINGS SHALL MATCH EXISTING

INSTALLATION REQUIREMENTS.

SCALE: 1" = 20'-0"

POWER & SYSTEMS FIRST FLOOR PLAN

REF: E100SCALE: 1/8" = 1'-0"

POWER & SYSTEMS FLOOR PLAN MEZZANINE CALLOUT

SCALE: NTS

PARTIAL ELECTRICAL RISER

1. EXISTING LOAD DETERMINED FROM 30-DAY LOAD STUDY CONDUCTED FROM 06/21/2023 TO 07/24/2023.

NOTES:

TOTAL ESTIMATED DEMAND LOAD: 10.04 kVA

TOTAL ESTIMATED DEMAND AMPS: 28 A

TOTAL CONNECTED LOAD: 10.08 kVA

REC 10.08 kVA 99.60% 10.04 kVA TOTAL CONNECTED AMPS: 28 A

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR DEMAND

TOTAL CONN. LOAD (kVA): 2.88 4.32 2.88

-- - - ---SPACE--- -- 41 -- 0 42 20 (EXISTING) LPC MEZ - - --

REC 1-#10,1-#10,1-#10G. 0.75" REC - ELECTRIC MAN LIFT CHARGING 20 39 1.44 1.44 40 20 REC - ELECTRIC MAN LIFT CHARGING 0.75" 1-#10,1-#10,1-#10G. REC

-- - - (EXISTING) POWER POLE REC 20 37 0 1.44 38 20 REC - ELECTRIC MAN LIFT CHARGING 0.75" 1-#10,1-#10,1-#10G. REC

35 0 1.44 36 20 REC - ELECTRIC MAN LIFT CHARGING 0.75" 1-#10,1-#10,1-#10G. REC

33 0 1.44 34 20 REC - ELECTRIC MAN LIFT CHARGING 0.75" 1-#10,1-#10,1-#10G. REC-- - - (EXISTING) VACUUM FOR CUTTER 20

31 0 1.44 32 20 REC - ELECTRIC MAN LIFT CHARGING 0.75" 1-#10,1-#10,1-#10G. REC

29 0 1.44 30 20 REC - ELECTRIC MAN LIFT CHARGING 0.75" 1-#10,1-#10,1-#10G. REC

27 0 0 28-- - - (EXISTING) CUTTER 20

25 0 0 26

20 (EXISTING) REC - WAREHOUSE - - --

23 0 0 24

-- - - (EXISTING) REC - EXT 20

21 0 0 22

20 (EXISTING) REC - WAREHOUSE - - --

19 0 0 20

-- - - (EXISTING) REC - B110 20

17 0 0 18

20 (EXISTING) REC - WAREHOUSE - - --

15 0 0 16

-- - - (EXISTING) REC - B110 20

13 0 0 14

20 (EXISTING) REC - WAREHOUSE - - --

11 0 0 12

-- - - (EXISTING) REC - B110 20

9 0 0 10

20 (EXISTING) REC - WAREHOUSE - - --

7 0 0 8 20 (EXISTING) GARAGE DOOR - - --

-- - - (EXISTING) REC - B110 20

5 0 0 6 20 (EXISTING) GARAGE DOOR - - --

3 0 0 4 20 (EXISTING) GARAGE DOOR - - --

-- - - (EXISTING) REC - B110 20

1 0 0 2 20 (EXISTING) GARAGE DOOR - - --

LOAD

CLASS

WIRE SIZE

PH / N / GND

COND

IN. LOAD DESCRIPTION

BRKR

RTG

CIR

NO A B C

CIR

NO

BRKR

RTG LOAD DESCRIPTION

COND

IN.

WIRE SIZE

PH / N / GND

LOAD

CLASS

WIRE: 4 MCB RATING: 225 A MOUNTING: Surface LOCATION: MEZZANINE B200

PHASE: 3 MAINS RATING: 225 A ENCLOSURE NEMA RATING: NEMA 1

VOLTAGE: 208/120 Wye MAINS TYPE: MCB SERVED FROM: T-3 22 :KAIC RATING

Panelboard: L2MA

1 REVISION 1 24-03-19

REF: E100SCALE: 3/16" = 1'-0"

POWER & SYSTEMS FLOOR PLAN CALLOUT

Sheets
E100 - ELECTRICAL PLAN AND RISER
(828)252-8181
2024-03-19T12:32:46-0500
Cody Pechacek
I am the author of this document

File details come from the government source that posted it. Updated .