Provide Accessibility AC 17 and AC 18 Fire Dampers - Drawings.pdf
PDF 12 MB Posted
- Attached to
- Z2DA--Project 541-21-506 Accessibility for AC 17 & 18 Fire Dampers Fire Dampers VAMC CLEVELAND
- Solicitation number
- 36C25025B0035
About this file
These technical drawings detail a project to provide accessibility for AC-17 and AC-18 fire dampers at the Louis Stokes Cleveland VA Medical Center. The project involves modifying mechanical shafts across six floors (second through sixth) to improve fire safety and accessibility, with specific focus on installing new structural platforms, guardrails, ships ladders, and access doors within existing elevator and mechanical shaft spaces.
Key technical specifications include: constructing 4'-0" elevated galvanized steel structural platforms with bar grating, installing pre-engineered ships ladders, adding 48" high guardrails, and maintaining existing fire dampers throughout the renovation. The project is fully sprinklered, follows 2024 NFPA Life Safety Code and 2018 IBC standards, and is classified as a Type I-332 non-combustible, protected construction type. The project has a proposed duration of 165 days, with 60 days for pre-construction and 105 days for construction, and requires careful coordination to minimize disruption to the ongoing hospital operations.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: GLEN ZEISSET
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
ATE
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
P.O. Box 6723 Oak Ridge, TN 37831 P. 440.667.5120
MECHANICAL / ELECTRICAL ENGINEERING:
FFE, INC.
4445 Lake Forest Drive Suite 600
CINCINNATI, OH 45242
P. 513.758.2220
STRUCTURAL ENGINEERING:
THORSON BAKER & ASSOC.
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
FINAL CD SUBMISSION
C U s e rs \r ic h
\D o c u m e n ts \V
A M
C P
R O
V
ID
E A
C C
E S
S A
C
A
C ri c h
Q X
K
S .r v t
/1
/2
:1
:4
P
M
GI-1
TITLE SHEET & DRAWING INDEX PROVIDE ACCESSIBILITY FOR
AC-17 & AC-18 FIRE DAMPERS
10701 EAST BLVD. CLEVELAND, OHIO
541-21-506
02.25.25 CJK RLY
DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER - WADE PARK
PROVIDE ACCESSIBILITY FOR AC-17 & AC-18 FIRE DAMPERS
10701 EAST BLVD. CLEVELAND, OH 44106
PROJECT NO. 541-21-506
Cleveland Veterans Affairs Medical Center
SECOND FLOOR
NORT
H
CODE INFORMATION:
I. PROJECT LOCATION: CLEVELAND VETERANS AFFAIRS MEDICAL CENTER
10701 EAST BLVD.
CLEVELAND, OHIO
II. DESCRIPTION & USER GROUP CLASSIFICATION OF BUILDING
A. NATURE OF PROJECT: INTERIOR RENOVATIONS INSIDE EXISTING MECHANICAL SHAFT
B. DESIGN CODES: 2024 NFPA LIFE SAFETY CODE 101, IBC 2018
C. USE GROUP: I-2 HEALTH CARE - NO CHANGE PROPOSED
D. CONSTRUCTION TYPE: TYPE I-332, IB - NON-COMBUSTIBLE, PROTECTED
FIRE RATED CONSTRUCTION (LSC A.8.2.1.1)
EXTERIOR BEARING WALLS 3 HRS
INTERIOR BEARING WALLS 3 HRS
STRUCTURAL COLUMNS 3 HRS (SUPPORTING > 1 FLOOR)
2 HRS (SUPPORTING 1 FLOOR ONLY)
2 HRS (SUPPORTING ROOF ONLY)
BEAMS, GIRDERS, TRUSSES 3 HRS (SUPPORTING > 1 FLOOR, COLS., OR BEARING WALLS)
FLOOR-CEILING ASSEMBLIES 2 HRS
ROOF-CEILING ASSEMBLIES 1-1/2 HRS
INTERIOR NON-BEARING WALLS 0 HRS
EXTERIOR NON-BEARING WALLS 0 HRS
WALL ASSEMBLIES
EXIT ACCESS CORRIDOR WALLS 0 HR SMOKE PARTITIONS
E. PROJECT AREA: 632 SF TOTAL, 158 SF PER FLOOR (3RD, 4TH, 5TH, & 6TH)
F. PROJECT AREA OCCUPANT LOAD: 6 PERSONS TOTAL
G. FIRE PROTECTION: EXISTING BUILDING FULLY SPRINKLED. MODIFICATIONS AS REQUIRED PER
NEW IMPROVEMENTS PROPOSED
DRAWING INDEX:
BID ISSUE SUBMISSION
03.14.25
GI-1 TITLE SHEET & DRAWING INDEX
ARCHITECTURAL
LS-2.0 SECOND FLOOR LIFE SAFETY PLAN
LS-3.0 THIRD / FOURTH FLOOR LIFE SAFETY PLANS
LS-4.0 FIFTH / SIXTH FLOOR LIFE SAFETY PLANS
AS-X-2.0 EXISTING CONDITIONS FLOOR PLANS
AS-D-2.0 DEMOLITION FLOOR PLANS
AS-2.0 SECOND, THIRD, & FOURTH FLOOR IMPROVEMENT PLANS
AS-2.1 FIFTH & SIXTH FLOOR IMPROVEMENT PLANS
AS-200 EXHAUST SHAFT SECTIONS, & 3D PERSPECTIVE
AS-500 DOOR SCHEDULE, HEAD DETAIL, SHIP LADDER, & DETAILS
PHASING DURATION:
THE SCOPE OF WORK DESCRIBED IN THIS DRAWING PACKAGE REPRESENTS A NON-PHASED
PROJECT THAT MUST BE UNDERTAKEN SIMULTANEOUSLY WITH THE FULL OCCUPANCY AND
FUNCTION OF THE EXISTING HOSPITAL. THE PROPOSING DURATION PLAN IS AS FOLLOWS:
PRE-CONSTRUCTION: 60 DAYS
CONSTRUCTION: 105 DAYS
TOTAL TIMEFRAME: 165 DAYS
THE TIMEFRAMES IDENTIFIED ABOVE ARE IN REFERENCE TO NORMAL CONSTRUCTION ACTIVITIES AND, UNLESS APPROVED BY VA COR, SHALL NOT APPLY TO WORK INCLUDING BUT NOT LIMITED
TO:
-UTILITY SHUTDOWNS
-EXISTING MEP SYSTEM SHUTDOWNS
-WORK IN PUBLIC CORRIDORS
-WORK OUTSIDE OF TEMPORARY CONSTRUCTION PARTITIONED AREAS, INCLUDING
ACCESS OF CEILING PLENUM SPACES IN FLOORS ABOVE OR BELOW CONSTRUCTION
AREAS (CEILING/MEP WORK)
WORK IDENTIFIED ABOVE SHALL OCCUR EITHER IN THE EVENING SHIFT, OR IF REQUIRED BY THE
VA, ON WEEKENDS. ALL CONSTRUCTION ACTIVITIES AND SCHEDULES MUST BE REVIEWED AND
APPROVED BY COR. REFER TO SPEC DIVISION 01 FOR GENERAL PROJECT REQUIREMENTS
SCOPE OF WORK AREA IN GRAY:
FLOORS TWO, THREE, FOUR, FIVE, & SIX
ELECTRICAL
E-001 ELECTRICAL LEGENDS, SCHEDULES, AND ABBREVIATIONS
EE-101 ELECTRICAL PLANS - LEVEL 2
EE-102 ELECTRICAL PLANS - LEVELS 3-6
STRUCTURAL
SS-001 GENERAL NOTES AND SPECIFICATIONS
SS-100 THIRD & FOURTH FLOOR FRAMING PLANS
SS-101 FIFTH & SIXTH FLOOR FRAMING PLANS
SS-200 FULL-HEIGHT SHAFT SECTIONS
SS-300 SECTIONS & DETAILS
Revisions: Date:
65% CDs SUBMISSION 12.16.24
FINAL CD SUBMISSION 02.25.25
BID ISSUE SUBMISSION 03.14.25
VHACLEBrowE3 Sticky Note What are the red and black marks that stand out?
UP
UP
UP
UP
UP
UP
UP
UP
UP
LIFE SAFETY LEGEND:
TEMPORARY ZIP WALL PROTECTION TO BE PROVIDED AROUND CONSTRUCTION AREA PER VA
SAFETY STANDARDS. INSTALLATION OF ZIP WALL MAY NEED TO OCCUR AFTER RELOCATION OF
CASEWORK/FURNITURE. CONTRACTOR TO COORDINATE SEQUENCING OF INSTALL WITH COR
EXISTING/NEW 2 HOUR RATED FIRE BARRIER
EXISTING/NEW 1 HOUR RATED FIRE BARRIER
EXISTING/NEW 1 HOUR RATED SMOKE BARRIER
EXISTING/NEW O HOUR RATED SMOKE PARTITION
E EXIT
FE
FIRE EXTINGUISHER
EXIT SIGN LOCATION
LIFE SAFETY GENERAL NOTES:
1. SEE COVER SHEET FOR APPLICABLE CODE INFORMATION. PROJECT AREA IS CLASSIFIED AS A CATEGORY
"D", LARGE-SCALE CONSTRUCTION, RENOVATION, OR MAINTENANCE. CONSTRUCTION IN COMPLIANCE WITH
"NEW HEALTH CARE OCCUPANCY" PER NFPA 101 2018.
2. PROJECT SCOPE LINE IS INDICATED FOR GENERAL INTENT ONLY. CONTRACTOR WILL COMPLETE ALL WORK REGARDLESS IF IT IS LOCATED OUTSIDE OF PROJECT SCOPE AREA AS INDICATED ON ANY DRAWINGS
3. CONTRACTOR WILL NOT NEED TO COVER OR ALTER EXIT SIGNS, OR TEMPORARILY RELOCATE EXISTING EXIT SIGNS DUE TO CONSTRUCTION. TEMPORARY CONSTRUCTION BARRIERS DO NOT INTERFERE WITH
EXISTING EXIT PATHS.
4. TRAVEL DISTANCES OVER 200' WILL REQUIRE INTERIM LIFE SAFETY MEASURES. COORDINATE WITH VA.
5. EXISTING FLOOR SLABS ARE 2 HR RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, CONTRACTOR SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE COMPROMISED, AND SHALL NOTIFY COR AND A/E TEAM OF ANY ISSUES DISCOVERED IN FIELD.
CONTRACTOR SHALL PROVIDE NEW 2 HR RATED THRU-SLAB FIRESTOP ASSEMBLIES AT ALL PENETRATIONS.
FOR EXISTING THRU-SLAB UTILITIES THAT ARE REMOVED AS A PART OF DEMOLITION SCOPE, CONTRACTOR
SHALL PATCH CONC. SLAB FULLY WITH NEW CONCRETE TO MATCH EXISTING
6. PROVIDE FIRESTOPPING AT ALL PENETRATIONS THROUGH NEW AND EXISTING FIRE/SMOKE RATED BARRIER WALLS AND FLOOR SLABS TO COMPLY WITH THE REQUIRED BARRIER RATINGS. PROVIDE
FIRESTOPPING AROUND TEN (10) PENETRATIONS LESS THAN 6 SQUARE INCHES AND FOUR (4)
PENETRATIONS BETWEEN 16 AND 36 SQUARE INCHES TO COMPLY WITH REQUIRED RATING NOT
ASSOCIATED WITH NEW WORK. LARGER OPENINGS SHALL BE BROUGHT TO THE ATTENTION OF THE COR.
CONTRACTOR SHALL SUBMIT UL LISTED METHODS FOR PATCHING ALL FIRE BARRIERS THAT MEET THE MINIMUM FIRE RATING REQUIREMENTS OF THE PENETRATING BARRIER AND ARE IN COMPLIANCE WITH THE
OPENING SIZE AS DICTATED BY THE ASSEMBLY.
HAZARDOUS ROOM
EXISTING/NEW 2 HOUR RATED SMOKE BARRIER
FIRE-RATED PLASTIC SHEETING/METAL STUD WALL TEMPORARY PARTITION WALL W/3'-0" X 7'-0"
SCWD DOOR FOR CONTRACTOR ACCESS ONLY. WALL AND DOOR TO BE REMOVED UPON
COMPLETION OF WORK U.N.O. PATCH/REPAIR EXISTING CONDITIONS AS REQUIRED UPON
REMOVAL OF ALL TEMPORARY CONSTRUCTION. REFER TO "TEMPORARY CONSTRUCTION BARRIER"
TYPICAL PARTITION DETAIL ON SHEET AS-600. SCHEDULE NOTE: CONSTRUCTION OF TEMPORARY
BARRIERS SHALL BE PERFORMED AFTER NORMAL BUSINESS HOURS UNLESS OTHERWISE
APPROVED BY THE COR.
SEPARATE ALL OCCUPIED AREAS OF THE RENOVATION AREA BY TEMPORARY SMOKE-TIGHT
CONSTRUCTION PARTITIONS BUILT TO THE DECK ABOVE, AND FOR AREAS WITHOUT ACTIVE
SPRINKLER PROTECTION ON BOTH SIDES, THE PARTITION SHALL BE ONE-HOUR FIRE RATED.
PROJECT SCOPE BOUNDARY
SOLID WHITE AREA INDICATES
CONSTRUCTION AREA WITHIN SCOPE
OF WORK
GRAY HATCHED AREA INDICATES AREA
OUTSIDE OF SCOPE OF WORK
SUITE AREA DESIGNATION
INFECTION CONTROL CLASS & SAFETY MEASURES:
THE WORK IDENTIFIED IN THIS PROJECT IS CLASSIFIED AS PATIENT RISK CATEGORY - LOW RISK, AS IT IS LOCATED IN A NON-PATIENT CARE AREA SUCH AS A EMS STORAGE ROOM OFF OF A PUBLIC HALLWAY/
GATHERING AREA NOT IN A CLINICAL AREA.
ACTIVITY CATEGORY D, AND A LOW PATIENT RISK CATEGORY RESULTS IN THIS PROJECT BEING ASSIGNED A CLASS III INFECTION CONTROL CLASS AND SHALL APPLY TO THIS PROJECT THROUGHOUT THE ENTIRETY OF CONSTRUCTION. CONSTRUCTION AREAS MUST BE INSPECTED BY AN INFECTION PREVENTIONIST AND ENGINEERING REPRESENTIATIVE FOR FINAL ACTIVITY/PROJECT CLOSE OUT, AND REMOVAL OF INFECTION
PREVENTION AND CONTROL MEASURES.
REFER TO LIFE SAFETY AND DEMOLITION PLANS FOR SCOPE OF TEMPORARY CONSTRUCTION BARRIERS REQUIRED FOR THE PROJECT. REFER TO AND FOLLOW ALL PROTOCOL IDENTIFIED IN "SAFETY REQUIREMENTS"
01 35 26 THROUGHOUT THE ENTIRETY OF THE PROJECT.
SPECIAL NOTE:
* NOTE 1 - CONTRACTOR SHALL BE AWARE THAT NEGATIVE PRESSURIZATION MUST BE MAINTAINED IN ALL CONSTRUCTION AREAS THROUGHOUT CONSTRUCTION. THIS AREA OF THE SECOND FLOOR HAS BEEN HISTORICALLY DIFFICULT TO MAINTAIN NEGATIVE PRESSURE WITHOUT ADDITIONAL MEASURES DUE TO THE
FOLLOWING ISSUES:
1) EXHAUST FROM THE ADJACENT MAIN ATRIUM PULLS AIR DOWN THE CORRIDOR
2) THE LOCATION OF THE PROJECT IS IN THE EXHAUST SHAFT SERVING AC 17 & AC 18
CONTRACTOR SHALL INCLUDE IN BID, THE MEANS TO ACHIEVE PRESSURIZATION. TEMPORARY PARTITIONS SHALL ALSO BE CONSTRUCTED AS DEPICTED. GC SHALL PATCH/REPAIR ALL SURROUNDING CONDITIONS AS REQUIRED TO RESTORE TO ORIGINAL CONDITIONS. GC SHALL VERIFY AND OBTAIN APPROVAL FROM THE VA
REGARDING THE MEANS TO ACHIEVE PRESSURIZATION PRIOR TO PROCEEDING.
F E
FE
F E
E
E
E
E
SCOPE OF WORK
BOUNDARY
FE
OFFICE
2C137
UPS
ROOM
2C135
Comm.
2B149
Hemodialysis Storage
2B150
Elect.
2B148
E.P. Lab 2C144
Storage 2C143
Lockers 2C142
Toilet 2C141
Corridor 2C140
Scrub 2C145
Office 2C146
Intervention 2C148
Cath. Lab 2C147
Soiled Utility 2C149
Clean Utility 2C150
Staff Work 2C151Endo. Conf.
2C170
EMS Clos.
2C154
Corridor 2C157
Holding 2C153
Viewing/Fellows 2C155
Exam Room 2C424
Exam Room 2C425
Holding 2C423
G.I. Office 2C438
Storage 2C437
ICU
Cleveland
Clinic Resident
2C439
Sec'y Reception
2C422
G.U.
Urology Clinic 2C420
Stair #6 2C121
Cardiothoracic 2C440
F.A.C.
2C421
Office 2C415
Office 2C414
Office 2C413
Electrical Room 2C411
Corridor 2C400A
Fan Room 2C129
Reception Alcove 2C133
Control 2C133A
Elevator Lobby 2C400B
Endo/Cath Waiting 2C133B
TELECOMM
2C134
CORRIDOR
2C100C
OPEN
OFFICE
AREA
2C136
OXYGEN
STORAGE
(CLEAN)
2B121A
HOME
OXYGEN
CLINIC
2B119
CLEAN
UTILITY
2B120
OFFICE/CONSULT
2B122
OFFICE/CONSULT
2B123
OFFICE/CONSULT
2B124
ELECT.
ROOM
2B125
ELEC.
ROOM
2B126
RECEPTION/WAITING
2B141
PFT LAB
2B142
TOILET
2B143
PFT LAB
2B144
PFT LAB
(CPET)
2B145
Administration Center 2B336
Passage 2B330
Meds 2B339 Cubicle 6
2B336A
Cubicle 7 2B336B
Clean Utility 2B338
Soiled 2B337
Linen 2B338A
Chute 2B335
Water Processing/ Equip. Rm
2B332A
Toilet 2B334
Water Processing/ Equipment
Room 2B332
Waiting 2B310
PD Training Room 2B321
Stair #11 2B146
Endoscopy Procedure
Procedure Room
Medication
Male Lockers
Female Lockers
Toilet 2064A
Toilet 2065A
Workroom/ Inst Clean
Electrical Closet 2C156
Corridor
Corridor 2C100A
Corridor 2C100B
CORRIDOR
2B134
SLEEP
LAB
2B133
TOILET/SHOWER
2B133A
OFFICE
2B132
OFFICE
2B131
OFFICE
2B130
SLEEP
LAB
2B135
TOILET/SHOWER
2B135A
OFFICE
2B136
SLEEP
LAB DAY
TESTING
2B137
Stair #8 2B138
OFFICE
2B139
PCAS/CHECK-IN
2B140
OFFICE
2B127
FELLOWS
OFFICE
2B128
OFFICE
2B129
Corridor 2B147
CORRIDOR
2B100B
CORRIDOR
2B100A
CLOSET
2B126A
Stair #5 2C127
Service Elevator Lobby 2C400C
EMS
2C416
Office 2C417
EMS
2C100
Elect.
2C140A
Chute 2C134A
CONTROL
STATION
2B134A
ALCOVE
2B143A
Elect.
2B146A
Corridor 2B480A
Penthouse 2B480
HOME
O2/CPAP
2B121C
HOME
OXYGEN -
ENTRY
2B121
Clean Linen 2B412
Procedure 2B413
Exam 8 2B414
Exam 7 2B415
Staff Lounge
2B411
Exam 4 2B420
Exam 3 2B421
Corridor 2B410
Corridor 2B418
Corridor 2B419
Exam 6 2B416
Exam 5 2B417
Exam 2 2B423
Exam 1 2B422
ASMT.
2B432
Office 2B431
Nurse Intake 2B433
Storage 2B435
Corridor 2B430
Waiting 2B434
Recpt.
2B462
Pharmacy Buffer Room 2B461A
Pharmacy Anteroom
2B461 Staff Toilet
2B460
Patient Toilet 2B438
EMS
2B436
Family/ Consult
2B437
Patient Toilet 2B439
Private Infusion 1
2B440
Private Infusion 2
2B453
2B146B
Mech 2C412
OFFICE
2C138
OFFICE
2C139
HOME
O2/CPAP
2B121D
CONTRACTOR SHALL PROVIDE TEMP.
PROTECTION OF EX. FURNITURE/ITEMS
WITHIN EACH SPACE AS REQ'D. ICRA
MEASURES SHALL BE FULLY IN PLACE
DURING CONSTRUCTION
EGRESS PATHS THROUGH ALL EXISTING
CORRIDORS SHALL AND WILL NOT BE IMPEDED AS
A RESULT OF CONSTRUCTION IN ANY WAY
CONSTRUCTION AREA
PACU
PASSAGE
2C323A
PACU
ADMIN.
CENTER
2C323
PACU
MEDS.
2C324
PACU
CUBICLE
2C326E
PACU
TOILET
2C322
PACU
CLEAN
2C330A
PACU
STORAGE
2C328
PACU
CUBICLE
2C326H
PACU
CUBICLE
2C326G
PACU
CUBICLE
2C326F
PACU
SOILED
UTILITY
2C321
ELEC.
2C327
GC ACCESS DOOR IN TEMPORARY CONSTRUCTION
PARTITION. SEE WALL DETAIL ON AS-500, TYPICAL.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: GLEN ZEISSET
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
ATE
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
P.O. Box 6723 Oak Ridge, TN 37831 P. 440.667.5120
MECHANICAL / ELECTRICAL ENGINEERING:
FFE, INC.
4445 Lake Forest Drive Suite 600
CINCINNATI, OH 45242
P. 513.758.2220
STRUCTURAL ENGINEERING:
THORSON BAKER & ASSOC.
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
FINAL CD SUBMISSION
C U s e rs \r ic h
\D o c u m e n ts \V
A M
C P
R O
V
ID
E A
C C
E S
S A
C
A
C ri c h
Q X
K
S .r v t
/1
/2
:4
:5
P
M
LS-2.0
SECOND FLOOR LIFE SAFETY PLAN PROVIDE ACCESSIBILITY FOR
AC-17 & AC-18 FIRE DAMPERS
10701 EAST BLVD. CLEVELAND, OHIO
541-21-506
02.25.25 CJK DAK
SCALE: 3/32" = 1'-0"
SECOND FLOOR LIFE SAFETY PLAN
NORTH
Revisions: Date:
65% CDs SUBMISSION 12.16.24
FINAL CD SUBMISSION 02.25.25
BID ISSUE SUBMISSION 03.14.25
F E
E
E
SCOPE OF WORK
BOUNDARY
CONTRACTOR SHALL PROVIDE TEMP.
PROTECTION OF EX. FURNITURE/ITEMS
WITHIN EACH SPACE AS REQ'D. ICRA
MEASURES SHALL BE FULLY IN PLACE
DURING CONSTRUCTION
EGRESS PATHS THROUGH ALL EXISTING
CORRIDORS SHALL AND WILL NOT BE IMPEDED AS
A RESULT OF CONSTRUCTION IN ANY WAY
CONSTRUCTION AREA
Passenger Elevator Lobby 3C100BCorridor
3C100A
Service Elevator Lobby 3C100C
Stair #6 3C113
Passage 3C115
Office 3C115B
Office 3C115D
Office 3C115F
Office 3C115H
Passage 3C115
Office 3C115G
Office 3C115E
Office 3C115C
Office 3C115A
Elect.
3C114
Office 3C111
Office 3C107B
Office 3C107A
Office 3C107
Stair #5 3C106
Elect.
3C105
Staff Lockers
3B100
Male Restroom
3C100
Female Restroom
3C101
EMS
Storage
3C110
EMS
3C109
Corridor 3C100A
Corridor 3B100J
Office 3B180
Office 3C104
Mammography 3C103
Vacant 3A167
Office 3A171
Corridor 3A100A Equipment
Room 3A148
Lockers 3A146A
Waiting Room 3A146
Conference Room 3A102
Clean Supply 3A104
Shaft 3C102
IRM
3A101
Bed Room 3A103
Toilet/ Shower 3A103A
Toilet/ Shower 3A105A
Respiratory Therapy
Breakroom 3A105
Equipment Storage
3A107
Equipment Storage
3A109
Equipment Storage
3A111
3A111A
3A117A
1 Bed Dialysis
3A117
Elect.
3A113
E.C.
3A115
Storage 3A119
Toilet/ Shower 3A121A
1 Bed Dialysis
3A121
Clean Storage
3A106
Office 3A106A Nurse
Station 3A108
Corridor 3A100B
Corridor 3A100E
Equipment Room 3A110
1 Bed Dialysis
3A125
1 Bed Dialysis
3A114
Toilet/ Shower 3A114A
Storage 3A112
Stair #8 3A116
Corridor 3A100D
Nourish 3A118
Staff Toilet 3A120
3A107A
3A109A
GC ACCESS DOOR IN TEMPORARY CONSTRUCTION
PARTITION. SEE WALL DETAIL ON AS-500, TYPICAL.
F E
E
E
SCOPE OF WORK
BOUNDARY
CONTRACTOR SHALL PROVIDE TEMP.
PROTECTION OF EX. FURNITURE/ITEMS
WITHIN EACH SPACE AS REQ'D. ICRA
MEASURES SHALL BE FULLY IN PLACE
DURING CONSTRUCTION
EGRESS PATHS THROUGH ALL EXISTING
CORRIDORS SHALL AND WILL NOT BE IMPEDED AS
A RESULT OF CONSTRUCTION IN ANY WAY
CONSTRUCTION AREA
Office 4C111J
Medical Service Suite 4C111
Toilet 4C111I
Toilet 4C111H
Storage 4C111G
Office 4C111F
Office 4C111E
Office 4C111D
Storage 4C111C
Office 4C111B
On-Call 4C111A
Stair #6 4C112
Corridor 4C100A
Med Service Office 4C110
Cheif Residents
Office 4C107
Service/ Elevators
4C100C
EMS
4C109
Office 4C108
Patient/ Visitor
Elevators 4C100B
Conference 4C105
Stair #5 4C104
Elect.
4C103
Semi Private 4B101
Male Restroom
4C100
Female Restroom
4C101
Shaft 4A100
Telecommunications/ Data Room
4A101 Private 4A103
Toilet/ Shower 4A103A
Toilet/ Shower 4A105A
Private 4A105
Private 4A107
Toilet/ Shower 4A107A
Toilet/ Shower 4A111A
Private 4A111
Private 4A112
2 Bedroom 4A117
Toilet/ Shower 4A117A Elect.
4A116
Corridor 4B100G
Corridor 4B100K
Office 4B166
Corridor 4C100A
Corridor 4A100B
Offices 4C102
Associate Director of Inpatient Medicine
4A169 Corridor 4A100A
Clean Linen 4A102
Office 4A104
Equipment Storage
4A106 Passage
4A100C
Clean Utility 4A108
Office-Medicine 4A110
Office-Medicine 4A158
Toilet/ Shower 4A112A
Alcove 4A113
Toilet/ Shower 4A115A Elect.
4A114
2 Bedroom 4A115
Corridor 4A100E
Private 4A119
Stair #8 4A118
Toilet/ Shower 4A119A
2 Bedroom 4A124
Med Supplies
4A120
Nourish 4A122
Toilet 4A123
Nurse Station 4A121
Corridor 4A100F
Corridor 4A100H
GC ACCESS DOOR IN TEMPORARY CONSTRUCTION
PARTITION. SEE WALL DETAIL ON AS-500, TYPICAL.
LIFE SAFETY LEGEND:
TEMPORARY ZIP WALL PROTECTION TO BE PROVIDED AROUND CONSTRUCTION AREA PER VA
SAFETY STANDARDS. INSTALLATION OF ZIP WALL MAY NEED TO OCCUR AFTER RELOCATION OF
CASEWORK/FURNITURE. CONTRACTOR TO COORDINATE SEQUENCING OF INSTALL WITH COR
EXISTING/NEW 2 HOUR RATED FIRE BARRIER
EXISTING/NEW 1 HOUR RATED FIRE BARRIER
EXISTING/NEW 1 HOUR RATED SMOKE BARRIER
EXISTING/NEW O HOUR RATED SMOKE PARTITION
E EXIT
FE
FIRE EXTINGUISHER
EXIT SIGN LOCATION
LIFE SAFETY GENERAL NOTES:
1. SEE COVER SHEET FOR APPLICABLE CODE INFORMATION. PROJECT AREA IS CLASSIFIED AS A CATEGORY
"D", LARGE-SCALE CONSTRUCTION, RENOVATION, OR MAINTENANCE. CONSTRUCTION IN COMPLIANCE WITH
"NEW HEALTH CARE OCCUPANCY" PER NFPA 101 2018.
2. PROJECT SCOPE LINE IS INDICATED FOR GENERAL INTENT ONLY. CONTRACTOR WILL COMPLETE ALL WORK REGARDLESS IF IT IS LOCATED OUTSIDE OF PROJECT SCOPE AREA AS INDICATED ON ANY DRAWINGS
3. CONTRACTOR WILL NOT NEED TO COVER OR ALTER EXIT SIGNS, OR TEMPORARILY RELOCATE EXISTING EXIT SIGNS DUE TO CONSTRUCTION. TEMPORARY CONSTRUCTION BARRIERS DO NOT INTERFERE WITH
EXISTING EXIT PATHS.
4. TRAVEL DISTANCES OVER 200' WILL REQUIRE INTERIM LIFE SAFETY MEASURES. COORDINATE WITH VA.
5. EXISTING FLOOR SLABS ARE 2 HR RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, CONTRACTOR SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE COMPROMISED, AND SHALL NOTIFY COR AND A/E TEAM OF ANY ISSUES DISCOVERED IN FIELD.
CONTRACTOR SHALL PROVIDE NEW 2 HR RATED THRU-SLAB FIRESTOP ASSEMBLIES AT ALL PENETRATIONS.
FOR EXISTING THRU-SLAB UTILITIES THAT ARE REMOVED AS A PART OF DEMOLITION SCOPE, CONTRACTOR
SHALL PATCH CONC. SLAB FULLY WITH NEW CONCRETE TO MATCH EXISTING
6. PROVIDE FIRESTOPPING AT ALL PENETRATIONS THROUGH NEW AND EXISTING FIRE/SMOKE RATED BARRIER WALLS AND FLOOR SLABS TO COMPLY WITH THE REQUIRED BARRIER RATINGS. PROVIDE
FIRESTOPPING AROUND TEN (10) PENETRATIONS LESS THAN 6 SQUARE INCHES AND FOUR (4)
PENETRATIONS BETWEEN 16 AND 36 SQUARE INCHES TO COMPLY WITH REQUIRED RATING NOT
ASSOCIATED WITH NEW WORK. LARGER OPENINGS SHALL BE BROUGHT TO THE ATTENTION OF THE COR.
CONTRACTOR SHALL SUBMIT UL LISTED METHODS FOR PATCHING ALL FIRE BARRIERS THAT MEET THE MINIMUM FIRE RATING REQUIREMENTS OF THE PENETRATING BARRIER AND ARE IN COMPLIANCE WITH THE
OPENING SIZE AS DICTATED BY THE ASSEMBLY.
HAZARDOUS ROOM
EXISTING/NEW 2 HOUR RATED SMOKE BARRIER
FIRE-RATED PLASTIC SHEETING/METAL STUD WALL TEMPORARY PARTITION WALL W/3'-0" X 7'-0"
SCWD DOOR FOR CONTRACTOR ACCESS ONLY. WALL AND DOOR TO BE REMOVED UPON
COMPLETION OF WORK U.N.O. PATCH/REPAIR EXISTING CONDITIONS AS REQUIRED UPON
REMOVAL OF ALL TEMPORARY CONSTRUCTION. REFER TO "TEMPORARY CONSTRUCTION BARRIER"
TYPICAL PARTITION DETAIL ON SHEET AS-600. SCHEDULE NOTE: CONSTRUCTION OF TEMPORARY
BARRIERS SHALL BE PERFORMED AFTER NORMAL BUSINESS HOURS UNLESS OTHERWISE
APPROVED BY THE COR.
SEPARATE ALL OCCUPIED AREAS OF THE RENOVATION AREA BY TEMPORARY SMOKE-TIGHT
CONSTRUCTION PARTITIONS BUILT TO THE DECK ABOVE, AND FOR AREAS WITHOUT ACTIVE
SPRINKLER PROTECTION ON BOTH SIDES, THE PARTITION SHALL BE ONE-HOUR FIRE RATED.
PROJECT SCOPE BOUNDARY
SOLID WHITE AREA INDICATES
CONSTRUCTION AREA WITHIN SCOPE
OF WORK
GRAY HATCHED AREA INDICATES AREA
OUTSIDE OF SCOPE OF WORK
SUITE AREA DESIGNATION
INFECTION CONTROL CLASS & SAFETY MEASURES:
THE WORK IDENTIFIED IN THIS PROJECT IS CLASSIFIED AS PATIENT RISK CATEGORY - LOW RISK, AS IT IS LOCATED IN A NON-PATIENT CARE AREA SUCH AS A EMS STORAGE ROOM OFF OF A PUBLIC HALLWAY/
GATHERING AREA NOT IN A CLINICAL AREA.
ACTIVITY CATEGORY D, AND A LOW PATIENT RISK CATEGORY RESULTS IN THIS PROJECT BEING ASSIGNED A CLASS III INFECTION CONTROL CLASS AND SHALL APPLY TO THIS PROJECT THROUGHOUT THE ENTIRETY OF CONSTRUCTION. CONSTRUCTION AREAS MUST BE INSPECTED BY AN INFECTION PREVENTIONIST AND ENGINEERING REPRESENTIATIVE FOR FINAL ACTIVITY/PROJECT CLOSE OUT, AND REMOVAL OF INFECTION
PREVENTION AND CONTROL MEASURES.
REFER TO LIFE SAFETY AND DEMOLITION PLANS FOR SCOPE OF TEMPORARY CONSTRUCTION BARRIERS REQUIRED FOR THE PROJECT. REFER TO AND FOLLOW ALL PROTOCOL IDENTIFIED IN "SAFETY REQUIREMENTS"
01 35 26 THROUGHOUT THE ENTIRETY OF THE PROJECT.
SPECIAL NOTE:
* NOTE 1 - CONTRACTOR SHALL BE AWARE THAT NEGATIVE PRESSURIZATION MUST BE MAINTAINED IN ALL CONSTRUCTION AREAS THROUGHOUT CONSTRUCTION. THIS AREA OF THE SECOND FLOOR HAS BEEN HISTORICALLY DIFFICULT TO MAINTAIN NEGATIVE PRESSURE WITHOUT ADDITIONAL MEASURES DUE TO THE
FOLLOWING ISSUES:
1) EXHAUST FROM THE ADJACENT MAIN ATRIUM PULLS AIR DOWN THE CORRIDOR
2) THE LOCATION OF THE PROJECT IS IN THE EXHAUST SHAFT SERVING AC 17 & AC 18
CONTRACTOR SHALL INCLUDE IN BID, THE MEANS TO ACHIEVE PRESSURIZATION. TEMPORARY PARTITIONS SHALL ALSO BE CONSTRUCTED AS DEPICTED. GC SHALL PATCH/REPAIR ALL SURROUNDING CONDITIONS AS REQUIRED TO RESTORE TO ORIGINAL CONDITIONS. GC SHALL VERIFY AND OBTAIN APPROVAL FROM THE VA
REGARDING THE MEANS TO ACHIEVE PRESSURIZATION PRIOR TO PROCEEDING.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: GLEN ZEISSET
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
ATE
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
P.O. Box 6723 Oak Ridge, TN 37831 P. 440.667.5120
MECHANICAL / ELECTRICAL ENGINEERING:
FFE, INC.
4445 Lake Forest Drive Suite 600
CINCINNATI, OH 45242
P. 513.758.2220
STRUCTURAL ENGINEERING:
THORSON BAKER & ASSOC.
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
FINAL CD SUBMISSION
C U s e rs \r ic h
\D o c u m e n ts \V
A M
C P
R O
V
ID
E A
C C
E S
S A
C
A
C ri c h
Q X
K
S .r v t
/1
/2
:4
:3
P
M
LS-3.0
THIRD / FOURTH FLOOR LIFE SAFETY PLANS PROVIDE ACCESSIBILITY FOR
AC-17 & AC-18 FIRE DAMPERS
10701 EAST BLVD. CLEVELAND, OHIO
541-21-506
02.25.25 Checker Author
NORTH
SCALE: 3/32" = 1'-0"
THIRD FLOOR LIFE SAFETY PLAN
SCALE: 3/32" = 1'-0"
FOURTH FLOOR LIFE SAFETY PLAN
NORTH
Revisions: Date:
65% CDs SUBMISSION 12.16.24
F
E
E
SCOPE OF WORK
BOUNDARY
CONTRACTOR SHALL PROVIDE TEMP.
PROTECTION OF EX. FURNITURE/ITEMS
WITHIN EACH SPACE AS REQ'D. ICRA
MEASURES SHALL BE FULLY IN PLACE
DURING CONSTRUCTION
EGRESS PATHS THROUGH ALL EXISTING
CORRIDORS SHALL AND WILL NOT BE IMPEDED AS
A RESULT OF CONSTRUCTION IN ANY WAY
CONSTRUCTION AREA
GC ACCESS DOOR IN TEMPORARY CONSTRUCTION
PARTITION. SEE WALL DETAIL ON AS-500, TYPICAL.
Work Area 5C117
Office 5C118
Office 5C119
Office 5C120
Office 5C121
Corridor 5C100F
Nursing Administration
5C122
Nursing Administration
5C123
Nursing Administration
5C124
Nursing Administration
5C125
Stair #6 5C116
Corridor 5C100E
Storage Room 5C126
Office 5C127
Service Elevators
5C100D
Chief Nursing
5C114
Conference Room 5C113
Corridor 5C100B
Stair #5 5C112
Patient Elevators
5C100C
Elect.
5C128
Toilet/ Shower 5B100A
Storage 5B102
2 Bedroom 5B100
Elect.
5C111
Corridor 5B100G
Office 5B103
Office 5B101
Geriatrics Office 5C110
Corridor 5C100A
Men's Restroom
5C100
Women's Restroom
5C101
Comm.
Room 5A100
1 Bedroom 5A101
Toilet/ Shower 5A101A
Toilet/ Shower 5A103A
1 Bedroom 5A103
1 Bedroom 5A104
Toilet/ Shower 5A104A
Toilet/ Shower 5A109A
1 Bedroom 5A109
1 Bedroom 5A110
Meds Room 5A113C
Dict/ Report 5A113B
Clean Utility 5A107
Work Area 5A105
Corridor 5A100B
Team Work Room 5A169
Office 5A102
Corridor 5A100A
Surgical, Social Work 5A175
Psychology Office 5C102
Stair #8 5A118
2 Bedroom 5A117
Toilet/ Shower 5A117A
Storage Room 5A116
1 Bedroom 5A119
Toilet/ Shower 5A119A
2 Bedroom 5A115
Corridor 5A100D
2 Bedroom 5A122
Elect.
Room 5A114
Toilet/ Shower 5A115AAlcove
5A112
Toilet/ Shower 5A110A
Equipment 5A123
Corridor 5A100G
Head Nurse 5A121
Corridor 5A100E
Control Station 5A113
Work 5A113D
Closet 5A111
F E
E
E SCOPE OF WORK
BOUNDARY
CONTRACTOR SHALL PROVIDE TEMP.
PROTECTION OF EX. FURNITURE/ITEMS
WITHIN EACH SPACE AS REQ'D. ICRA
MEASURES SHALL BE FULLY IN PLACE
DURING CONSTRUCTION
EGRESS PATHS THROUGH ALL EXISTING
CORRIDORS SHALL AND WILL NOT BE IMPEDED AS
A RESULT OF CONSTRUCTION IN ANY WAY
CONSTRUCTION AREA
ACCESS TO MECHANICAL SHAFT & NEW
CONSTRUCTION IS THROUGH CONCEALED SPACE
Male Toilet 6C112
Female Toilet 6C111
Staff Lockers
6C110
Stair #5 6C109
EMS
6C113
Social Work Office
6C114
Service Lobby 6C100C
Corridor 6C100A Elevator
Lobby 6C100B
Elect.
6C101
Elect.
6C100
Conference Room 6C102
Bath 6B151A
2 Bedroom 6B151
Corridor 6B100J
Equipment Storage
6B101
Staff Work 6C108
Corridor 6C100A
Office 6C103
Corridor 6A100A
Dining 6A101
Telephone Data Room
6A100
SCI/Social Work Office
6A102
Staff Lounge
6A104
Urology Office 6A103
Office-SCI Officier 6A106
Learning & Resource
Center 6A108
SCI Office
Vocational Rehab 6A110
Recreational Therapy
6A107
Elect.
6A105
Office 6A107C
Bath 6A107A
6A109 Corridor 6A100B
Corridor 6A100D
Kitchen 6A113A
Elect.
6A112
Elect.
6A111
Closet 6A113D
Living/Dining 6A113
Occupational Therapy
6A118
Clean Utility 6A118A
Office 6A119
Office 6A117
Office 6A116
Office 6A115
Corridor 6A100C
Bath 6A113B
Bedroom 6A113C
Stair #8 6A114
GC ACCESS DOOR IN TEMPORARY
CONSTRUCTION PARTITION. SEE
WALL DETAIL ON AS-500, TYPICAL.
3'-0"
EXISTING 24"W x 30"H ACCESS
PANEL IN WALL
LIFE SAFETY LEGEND:
TEMPORARY ZIP WALL PROTECTION TO BE PROVIDED AROUND CONSTRUCTION AREA PER VA
SAFETY STANDARDS. INSTALLATION OF ZIP WALL MAY NEED TO OCCUR AFTER RELOCATION OF
CASEWORK/FURNITURE. CONTRACTOR TO COORDINATE SEQUENCING OF INSTALL WITH COR
EXISTING/NEW 2 HOUR RATED FIRE BARRIER
EXISTING/NEW 1 HOUR RATED FIRE BARRIER
EXISTING/NEW 1 HOUR RATED SMOKE BARRIER
EXISTING/NEW O HOUR RATED SMOKE PARTITION
E EXIT
FE
FIRE EXTINGUISHER
EXIT SIGN LOCATION
LIFE SAFETY GENERAL NOTES:
1. SEE COVER SHEET FOR APPLICABLE CODE INFORMATION. PROJECT AREA IS CLASSIFIED AS A CATEGORY
"D", LARGE-SCALE CONSTRUCTION, RENOVATION, OR MAINTENANCE. CONSTRUCTION IN COMPLIANCE WITH
"NEW HEALTH CARE OCCUPANCY" PER NFPA 101 2018.
2. PROJECT SCOPE LINE IS INDICATED FOR GENERAL INTENT ONLY. CONTRACTOR WILL COMPLETE ALL WORK REGARDLESS IF IT IS LOCATED OUTSIDE OF PROJECT SCOPE AREA AS INDICATED ON ANY DRAWINGS
3. CONTRACTOR WILL NOT NEED TO COVER OR ALTER EXIT SIGNS, OR TEMPORARILY RELOCATE EXISTING EXIT SIGNS DUE TO CONSTRUCTION. TEMPORARY CONSTRUCTION BARRIERS DO NOT INTERFERE WITH
EXISTING EXIT PATHS.
4. TRAVEL DISTANCES OVER 200' WILL REQUIRE INTERIM LIFE SAFETY MEASURES. COORDINATE WITH VA.
5. EXISTING FLOOR SLABS ARE 2 HR RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, CONTRACTOR SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE COMPROMISED, AND SHALL NOTIFY COR AND A/E TEAM OF ANY ISSUES DISCOVERED IN FIELD.
CONTRACTOR SHALL PROVIDE NEW 2 HR RATED THRU-SLAB FIRESTOP ASSEMBLIES AT ALL PENETRATIONS.
FOR EXISTING THRU-SLAB UTILITIES THAT ARE REMOVED AS A PART OF DEMOLITION SCOPE, CONTRACTOR
SHALL PATCH CONC. SLAB FULLY WITH NEW CONCRETE TO MATCH EXISTING
6. PROVIDE FIRESTOPPING AT ALL PENETRATIONS THROUGH NEW AND EXISTING FIRE/SMOKE RATED BARRIER WALLS AND FLOOR SLABS TO COMPLY WITH THE REQUIRED BARRIER RATINGS. PROVIDE
FIRESTOPPING AROUND TEN (10) PENETRATIONS LESS THAN 6 SQUARE INCHES AND FOUR (4)
PENETRATIONS BETWEEN 16 AND 36 SQUARE INCHES TO COMPLY WITH REQUIRED RATING NOT
ASSOCIATED WITH NEW WORK. LARGER OPENINGS SHALL BE BROUGHT TO THE ATTENTION OF THE COR.
CONTRACTOR SHALL SUBMIT UL LISTED METHODS FOR PATCHING ALL FIRE BARRIERS THAT MEET THE MINIMUM FIRE RATING REQUIREMENTS OF THE PENETRATING BARRIER AND ARE IN COMPLIANCE WITH THE
OPENING SIZE AS DICTATED BY THE ASSEMBLY.
HAZARDOUS ROOM
EXISTING/NEW 2 HOUR RATED SMOKE BARRIER
FIRE-RATED PLASTIC SHEETING/METAL STUD WALL TEMPORARY PARTITION WALL W/3'-0" X 7'-0"
SCWD DOOR FOR CONTRACTOR ACCESS ONLY. WALL AND DOOR TO BE REMOVED UPON
COMPLETION OF WORK U.N.O. PATCH/REPAIR EXISTING CONDITIONS AS REQUIRED UPON
REMOVAL OF ALL TEMPORARY CONSTRUCTION. REFER TO "TEMPORARY CONSTRUCTION BARRIER"
TYPICAL PARTITION DETAIL ON SHEET AS-600. SCHEDULE NOTE: CONSTRUCTION OF TEMPORARY
BARRIERS SHALL BE PERFORMED AFTER NORMAL BUSINESS HOURS UNLESS OTHERWISE
APPROVED BY THE COR.
SEPARATE ALL OCCUPIED AREAS OF THE RENOVATION AREA BY TEMPORARY SMOKE-TIGHT
CONSTRUCTION PARTITIONS BUILT TO THE DECK ABOVE, AND FOR AREAS WITHOUT ACTIVE
SPRINKLER PROTECTION ON BOTH SIDES, THE PARTITION SHALL BE ONE-HOUR FIRE RATED.
PROJECT SCOPE BOUNDARY
SOLID WHITE AREA INDICATES
CONSTRUCTION AREA WITHIN SCOPE
OF WORK
GRAY HATCHED AREA INDICATES AREA
OUTSIDE OF SCOPE OF WORK
SUITE AREA DESIGNATION
INFECTION CONTROL CLASS & SAFETY MEASURES:
THE WORK IDENTIFIED IN THIS PROJECT IS CLASSIFIED AS PATIENT RISK CATEGORY - LOW RISK, AS IT IS LOCATED IN A NON-PATIENT CARE AREA SUCH AS A EMS STORAGE ROOM OFF OF A PUBLIC HALLWAY/
GATHERING AREA NOT IN A CLINICAL AREA.
ACTIVITY CATEGORY D, AND A LOW PATIENT RISK CATEGORY RESULTS IN THIS PROJECT BEING ASSIGNED A CLASS III INFECTION CONTROL CLASS AND SHALL APPLY TO THIS PROJECT THROUGHOUT THE ENTIRETY OF CONSTRUCTION. CONSTRUCTION AREAS MUST BE INSPECTED BY AN INFECTION PREVENTIONIST AND ENGINEERING REPRESENTIATIVE FOR FINAL ACTIVITY/PROJECT CLOSE OUT, AND REMOVAL OF INFECTION
PREVENTION AND CONTROL MEASURES.
REFER TO LIFE SAFETY AND DEMOLITION PLANS FOR SCOPE OF TEMPORARY CONSTRUCTION BARRIERS REQUIRED FOR THE PROJECT. REFER TO AND FOLLOW ALL PROTOCOL IDENTIFIED IN "SAFETY REQUIREMENTS"
01 35 26 THROUGHOUT THE ENTIRETY OF THE PROJECT.
SPECIAL NOTE:
* NOTE 1 - CONTRACTOR SHALL BE AWARE THAT NEGATIVE PRESSURIZATION MUST BE MAINTAINED IN ALL CONSTRUCTION AREAS THROUGHOUT CONSTRUCTION. THIS AREA OF THE SECOND FLOOR HAS BEEN HISTORICALLY DIFFICULT TO MAINTAIN NEGATIVE PRESSURE WITHOUT ADDITIONAL MEASURES DUE TO THE
FOLLOWING ISSUES:
1) EXHAUST FROM THE ADJACENT MAIN ATRIUM PULLS AIR DOWN THE CORRIDOR
2) THE LOCATION OF THE PROJECT IS IN THE EXHAUST SHAFT SERVING AC 17 & AC 18
CONTRACTOR SHALL INCLUDE IN BID, THE MEANS TO ACHIEVE PRESSURIZATION. TEMPORARY PARTITIONS SHALL ALSO BE CONSTRUCTED AS DEPICTED. GC SHALL PATCH/REPAIR ALL SURROUNDING CONDITIONS AS REQUIRED TO RESTORE TO ORIGINAL CONDITIONS. GC SHALL VERIFY AND OBTAIN APPROVAL FROM THE VA
REGARDING THE MEANS TO ACHIEVE PRESSURIZATION PRIOR TO PROCEEDING.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: GLEN ZEISSET
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
ATE
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
P.O. Box 6723 Oak Ridge, TN 37831 P. 440.667.5120
MECHANICAL / ELECTRICAL ENGINEERING:
FFE, INC.
4445 Lake Forest Drive Suite 600
CINCINNATI, OH 45242
P. 513.758.2220
STRUCTURAL ENGINEERING:
THORSON BAKER & ASSOC.
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
FINAL CD SUBMISSION
C U s e rs \r ic h
\D o c u m e n ts \V
A M
C P
R O
V
ID
E A
C C
E S
S A
C
A
C ri c h
Q X
K
S .r v t
/1
/2
:5
:0
P
M
LS-4.0
FIFTH / SIXTH FLOOR LIFE SAFETY PLANS PROVIDE ACCESSIBILITY FOR
AC-17 & AC-18 FIRE DAMPERS
10701 EAST BLVD. CLEVELAND, OHIO
541-21-506
02.25.25 Checker Author
NORTH
NORTH
SCALE: 3/32" = 1'-0"
FIFTH FLOOR LIFE SAFETY PLAN
SCALE: 3/32" = 1'-0"
SIXTH FLOOR LIFE SAFETY PLAN
Revisions: Date:
65% CDs SUBMISSION 12.16.24
LL
L1L1
PP
18 20 23
MM
Elevator Lobby
2C400B
Endo/Cath Waiting
2C133B
Control
2C133A
Reception Alcove
2C133
EMS
2C100
EXISTING FIRE DAMPER LOCATION @ 2ND FLOOR
PLENUM TO REMAIN, BE CLEANED, & PROTECTED
THROUGHOUT CONSTRUCTION
EXISTING FIRE DAMPER LOCATIONS @ 2ND FLOOR
PLENUM TO REMAIN, BE CLEANED, & PROTECTED
THROUGHOUT CONSTRUCTION
EXISTING EXPANSION JOINT TO
REMAIN & BE PROTECTED
THROUGHOUT CONSTRUCTION,
TYP.
EXISTING EPOXY PAINTED CONCRETE FLOOR TO REMAIN & BE
PROTECTED WHEN ACCESSING ROOM DURING PROJECT.
Office
2C413
Electrical Room
2C411
Stair #5
2C127
Corridor
2C400A
Fan Room
2C129
Chute
2C134A
CORRIDOR
2C100C
EXISTING FLOOR SINK TO REMAIN & BE PROTECTED
EXISTING HOLLOW METAL DOOR TO
REMAIN & BE PROTECTED.
EXISTING WALL CABINET TO REMAIN & BE PROTECTED
TWO (2) EXISTING WALL-MTD. SOAP DISPENDING UNITS TO REMAIN
EXISTING FIRE LINE, MARKED "FL" TO REMAIN & BE
PROTECTED THROUGHOUT CONSTRUCTION
EXISTING FULL-HEIGHT SHEET OF PLYWOOD SECURED
TO WALL. WALL-MTD. CABLING, & METAL IT RACK W/
COMPUTER. PROTECT THROUGHOUT CONSTRUCTION
EXISTING GWB WALLS EXTEND TO UNDERSIDE OF EXISTING
PLASTER CEILING TO REMAIN
NO WORK IN
THIS ROOM
NO WORK IN
THIS ROOM
NO WORK IN
THIS ROOM
NO WORK IN
THIS ROOM
NO WORK IN
THIS ROOM
NO WORK IN
THIS ROOM
NO WORK IN
THIS ROOM
NO WORK IN
THIS ROOM
NO WORK IN
THIS ROOM
NO WORK IN
THIS ROOM
IN
S
ID
E C
L E
A R
2C100
7'-7" 10" 7'-8" 7 5/8"
8'-1" 10'-8" CLEAR
SPSD
EXISTING PLUMBING LINES ABOVE THE CEILING
TURN & ENTER EXISTING WEST CMU WALL
DIRECTLY ABOVE FINISHED CEILING
EXISTING 16"x16" METAL MATV BOX & WIRES
TO BE REMOVED. PATCH HOLE IN WALL WITH
SOLID CMU UNITS & GROUT, FLUSH W/
ADJACENT WALL SURFACE
EXISTING STEEL FRAMED ACCESS DOOR ABOVE
GENERAL NOTES:
CONSIDER ALL AREAS OWNER-OCCUPIED UNLESS NOTED OTHERWISE.
ALL 3-5/8" METAL STUD WALLS ARE DRAWN AND DIMENSIONED TO A 5" NOMINAL WIDTH, TYPICAL UNLESS OTHERWISE NOTED. ALL DIMENSIONS ARE CLEAR DIMENSIONS FROM FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD. ALL CMU WALLS ARE DRAWN AND DIMENSIONED TO AN 8" NOMINAL WIDTH, TYPICAL UNLESS
OTHERWISE NOTED.
CONTRACTOR (I.E. FIRE PROTECTION, HVAC, FIRE ALARM, ELECTRICAL, ETC.) TO INSTALL SYSTEM PER OWNER REQUIREMENTS AND IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF ALL APPLICABLE CODES.
PATCH AND REPAIR ALL EXISTING AREAS TO REMAIN AS REQUIRED TO MATCH EXISTING CONDITIONS.
WHERE NEW UTILITIES ARE TO BE INSTALLED IN EXISTING PARTITIONS, CONTRACTOR SHALL REMOVE EXISTING DRYWALL AS REQUIRED FOR INSTALLATION OF SAME AND PATCH AND REPAIR WITH NEW TO MATCH
EXISTING CONDITIONS UPON COMPLETION OF UTILITY INSTALLATION.
ALL DAMAGE TO EXISTING AREAS OCCURING AS A RESULT OF CONSTRUCTION SHALL BE REPAIRED AS REQUIRED BY THE CONTRACTOR. CONTRACTOR SHALL PROTECT ALL EXISTING WALL, CEILING, AND FLOOR FINISHES IN EACH AREA. ANY SURFACES DAMAGED BY CONTRACTOR SHALL BE REPLACED BY THE
CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
ALL NEW PENETRATIONS IN FIRE-RATED ASSEMBLIES TO MAINTAIN FIRE RATING OF ASSEMBLY AS REQUIRED.
NEW AND EXISTING FURNITURE SHOWN FOR REFERENCE ONLY. THE OWNER SHALL REMOVE, PRIOR TO CONSTRUCTION, ALL ITEMS THAT THE OWNER DESIRES TO SALVAGE. ALL REMAINING ITEMS INDICATED TO BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR AND LEGALLY DISPOSED OF IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. ALL ITEMS TO REMAIN IN SPACE SHALL BE PROTECTED THROUGHOUT BY THE CONTRACTOR THROUGHOUT CONSTRUCTION. NEW FURNITURE TO BE FURNISHED AND INSTALLED
BY THE OWNER UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL PROVIDE DUST-REMOVAL WALK-OFF MATS (TACKY MAT) AT ALL CONSTRUCTION ENTRY
POINTS.
CONTRACTOR SHALL PROVIDE HEPA FILTERED NEGATIVE AIR MACHINE(S) TO MAINTAIN NEGATIVE PRESSURE IN WORK AREAS ENSURING NO DUST OR FUMES WILL BE TRANSFERRED TO OCCUPIED AREAS. PROVIDE VISUAL PRESSURE MONITORING DEVICE AT DUST-PROOF BARRICADE TO CONFIRM PRESSURE. DUST MONITORING SHALL BE BY OWNER. SEE SPECIFICATION 01 00 00 "GENERAL REQUIREMENTS" ATTACHMENT
AND 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS.
ALL DEMOLITION WORK BEING DONE OUTSIDE TEMPORARY PARTITIONS IS TO BE APPROPRIATELY SEALED OFF TO PREVENT THE TRANSMISSION OF DUST AND DEBRIS. WORK SHALL BE DONE TO MINIMIZE DISRUPTION TO VISITORS, PATIENTS, AND STAFF. COORDINATE LOCATION OF BARRIERS WITH OWNER.
THE HOSPITAL'S SMOKE AND FIRE SUPPRESSION SYSTEM SHALL REMAIN IN OPERATION WITHIN THE
PROJECT AREA DURING THE ENTIRE CONSTRUCTION PHASE.
FIELD VERIFY LOCATION OF ALL EXISTING CONDITIONS. NOTIFY COR OF ANY DISCREPANCIES.
WHERE NEW DOORS ARE INDICATED IN EXISTING WALL ASSEMBLIES, CUT OPENINGS IN EXISTING WALL.
REFER TO DOOR SCHEDULE FOR DIMENSIONS. PREPARE OPENINGS FOR NEW DOOR, INCLUSIVE OF THE ADDITION OF JAMB AND HEAD REINFORCEMENT (I.E. DOUBLE STUDS, HEADERS, STEEL LINTELS) AND PATCH
ADJACENT WALLS TO MATCH EXISTING.
ALL FLOOR, WALL, CEILING, AND MISC. FIRE-RESISTIVE ASSEMBLIES AND CONSTRUCTION SHALL BE OF THE FIRE RATING CALLED FOR ON THE DRAWINGS AND/OR AS REQUIRED BY CODE. ALL EXISTING FIRE-RESISTIVE ASSEMBLIES SHALL BE MAINTAINED AND THE RATING NOT COMPROMISED. FIRE RATED ASSEMBLIES AND CONSTRUCTION INCLUDING ALL FIRESTOPPING, FIRE RATED DOORS, AND MISC. FIRE RESISTIVE
REQUIREMENTS SHALL BE LEFT UNCONCEALED AS REQUIRED FOR INSPECTION BY THE VA COR.
DEBRIS REMOVAL SHALL NOT INTERFERE WITH OWNER'S OPERATIONS AND SHALL OCCUR DURING OFF HOURS AS DETERMINED BY THE COR. SEE ALSO SPECIFICATION SECTION 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS REGARDING THE HAULING OF DEBRIS FROM THE PROJECT AREA.
ALL NOISE-GENERATING OPERATIONS SHALL BE SCHEDULED SO AS NOT TO IMPEDE OWNER'S OPERATIONS AS DETERMINED BY THE COR. ALL WORK IN PUBLIC CORRIDORS SHALL BE PERFORMED OFF-HOURS UNLESS
OTHERWISE APPROVED BY THE COR.
EXISTING FLOOR SLABS ARE 2 HR FIRE RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, CONTRACTOR SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE
COMPROMISED, AND CONTRACTOR SHALL NOTIFY COR AND A/E TEAM OF ANY ISSUES DISCOVERED IN FIELD.
CONTRACTOR SHALL PROVIDE NEW 2 HR RATED THRU-SLAB FIRESTOP ASSEMBLIES AT ALL PENETRATIONS.
FOR EXISTING THRU-SLAB UTILITIES THAT ARE REMOVED AS A PART OF DEMOLITION SCOPE, CONTRACTOR SHALL PATCH CONCRETE SLAB FULLY WITH NEW CONCRETE TO MATCH EXISTING OR APPROVED 2 HR RATED
INFILL FIRESTOP ASSEMBLY WHEN APPROVED BY THE COR.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
SYMBOL LEGEND:
INDICATES EXISTING DOOR
INDICATES NEW DOOR
EXISTING WALLS TO REMAIN
NEW WALLS
WALLS TO BE REMOVED FULL HEIGHT U.N.O.
DASHED LINES INDICATE ITEMS TO BE DEMOLISHED
HATCHED AREA OUTSIDE OF PROJECT SCOPE.
ACCESS INTO CEILING SPACES MAY OCCUR, REFER
TO MEP DWGS.
FIRE-RATED PLASTIC SHEETING/METAL STUD WALL TEMPORARY PARTITION WALL W/3'-0" X 7'-0"
SCWD DOOR FOR CONTRACTOR ACCESS ONLY. WALL AND DOOR TO BE REMOVED UPON
COMPLETION OF WORK U.N.O. PATCH/REPAIR EXISTING CONDITIONS AS REQUIRED UPON
REMOVAL OF ALL TEMPORARY CONSTRUCTION. REFER TO TEMPORARY CONSTRUCTION BARRIER
DETAIL ON SHEET AS-600. SCHEDULE NOTE: CONSTRUCTION OF TEMPORARY BARRIERS SHALL BE
PERFORMED AFTER NORMAL BUSINESS HOURS UNLESS OTHERWISE APPROVED BY THE COR.
TEMPORARY ZIP WALL PROTECTION TO BE PROVIDED AROUND CONSTRUCTION AREA PER VA
SAFETY STANDARDS. INSTALLATION OF ZIP WALL MAY NEED TO OCCUR AFTER RELOCATION OF
CASEWORK/FURNITURE. GC TO COORDINATE SEQUENCING OF INSTALL WITH COR
GENERAL CONSTRUCTION PARTITION NOTE: WHERE TEMP. CONST. PARTITIONS CONFLICT
W/EX. LIGHTS/DIFFUSER/MEP ITEM LOCATIONS (INDICATED ON CEILING DEMOLITION PLANS), GC
SHALL COORD. W/COR TO EITHER TEMPORARILY REMOVE SUCH ITEMS, OR ADJUST LOCATION
OF CONST. PARTITION ACCORDINGLY TO ALLOW ITEMS TO REMAIN IN PLACE. TEMPORARY
REMOVAL/REINSTALLATION SHALL BE PERFORMED BY THE CONTRACTOR
LL
L1L1
20 23
MM
Passenger Elevator Lobby
3C100B
Corridor
3C100A
EXISTING FIRE DAMPER LOCATION @ 3RD FLOOR PLENUM
EXISTING
EXPANSION JOINT
EXISTING PLUMBING VENT PIPES & H&C WATER LINES
OCCUR FROM SECOND FLOOR CEILING TO TOP OF SHAFT
EXISTING WALL-MTD. ELECTRICAL BOX, CONDUITS, &
PLUMBING LINES ABOVE 2ND FLOOR PLATFORM
LINE OF EXISTING 3RD FLOOR CONCRETE BEAM EXTENDS +/-13" INTO SHAFT,
SIMILAR ON ALL FLOORS
EXISTING FIRE DAMPERS LOCATION @ 3RD FLOOR PLENUM
LOOKING DOWN AT TOP OF CORRUGATED SURFACE (7'-10" ABOVE 2ND FLOOR)
EXISTING INSULATED PIPE, +/-26" ABOVE TOP OF
EXISTING 2ND FLOOR STRUCTURAL PLATFORM
DASHED LINES INDICATE GWB WALLS BELOW EXISTING 2ND FLOOR
STRUCTURAL PLATFORM & FINISHED CEILING
LINE OF EXISTING CONCRETE BEAM STICKING +/-2" INTO SHAFT
CONCRETE COLUMN EXTENDS 6" PAST FACE OF EASTERN MASONRY WALL.
THE COLUMN MAY ONLY EXTEND 4" PAST FACE OF EASTERN MASONRY
WALL ON UPPER FLOORS. (TO BE VERIFIED IN THE FIELD)
EXISTING INSULATED H&C WATER SUPPLY
PIPES +/-16" ABOVE 2ND FLR. PLATFORM
TWO (2) EXISTING CONDUITS ENTER AND EXIT SHAFT +/-12" BELOW
& +/-12" & 26" ABOVE CONCRETE BEAM THAT IS FLUSH WITH SHAFT
OVERALL SHAFT CLEAR DIMENSION IS CONSISTENT
FROM 2ND FLOOR UP TO UNDERSIDE OF 6TH FLOOR.
10'-8" CLEAR
5'-0" LONG EXISTING ELECTRICAL METAL POWER STRIP
EXISTING WALL PROTECTION (HAND RAIL & CRASH RAIL)
EXISTING LIGHT SWITCH & FIRE ALARM STROBE DEVICE
S
1'-11"
6"
/4
EXISTING UNISTRUT ATTACHED TO 3RD FLOOR BEAMS, W/ LIGHT FIXTURES
UNDERNEATH, & ALSO PROVIDING SUPPORT TO EXISTING SPRINKLER LINE
BELOW 3RD FLOOR STRUCTURE.
EXISTING SPRINKLER LINE +/-24" ABOVE EXISTING 2ND FLOOR STRUCTURAL PLATFORM
'-2
C
LE
A
R
SHADED PORTION OF EXISTING METAL DECK IS DENTED & NOT LEVEL
BTM +8'-7"
B T
M
7' -8
EXISTING 24"X32" STONE ACCESS PANEL
TO REMAIN & BE PROTECTED. SIMILAR
ACCESS PANEL OCCURS ON EACH FLOOR.
EXISTING 18"x18" & 12"x12" RECESSED ABANDONDED METAL JUNCTION BOXES BTM +8'-7"
EXISTING FIRE LINE W/ STL. ANGLE BRACE TO REMAIN & BE PROTECTED
SD
SP
EXISTING STEEL FRAMED ACCESS DOOR BELOW
L
L1
20 23
M
Patient/ Visitor
Elevators 4C100B
Corridor
4C100A
EXISTING EXPANSION JOINT
EXISTING SUPPLY, WASTE, & VENT PLUMBING LINES.
PIPE TRANSITION OCCURS AT THIS LEVEL
EXISTING CONDUIT ENTERS AND EXITS SHAFT +/-12"
BELOW & +/-12" ABOVE CONCRETE BEAM THAT IS
FLUSH WITH SHAFT
LINE OF EXISTING CONCRETE BEAM EXTENDS +/-13" INTO SHAFT
EXISTING FIRE DAMPER LOCATION @ 4TH FLOOR PLENUM
LOOKING DOWN INTO SHAFT
EXISTING CONDUITS LOCATED DIRECTLY UNDER FLOOR SLAB
LINE OF EXISTING CONCRETE BEAM STICKING +/-2" INTO SHAFT
CONCRETE COLUMN. COLUMN VISUALLY APPEARS TO EXTEND 4" PAST
FACE OF EASTERN MASONRY WALL. (TO BE VERIFIED IN THE FIELD)
EXISTING MAIL BOX, WALL FRAMING, GLASS PANELS, & METAL FRAMING
TO REMAIN
EXISTING ARTWORK TO BE REMOVED & RETURNED TO VA.
DASHED LINES INDICATE SOFFIT @ 7'-2" AFF ABOVE TO
REMAIN & BE PROTECTED THROUGHOUT CONSTRUCTION
EXISTING WALL PROTECTION TO REMAIN (HAND RAIL & CRASH RAIL).
EXISTING COVER PLATE & FIRE ALARM STROBE DEVICE
2'-0" 6'-0"
4"
BTM @ 8'-7"
EXISTING 24"X32" STONE ACCESS PANEL TO REMAIN & BE
PROTECTED
B T
M
'-1
1"
(2) - 3/4" WATER LINES IN CMU WALL.
TWO (2) LOCATIONS.
EXISTING ABANDONED FLOOR SINK &
3/4" WATER LINE IN CMU WALL
EXISTING FIRE LINE W/ STL. ANGLE BRACE TO REMAIN & BE PROTECTED
EXISTING 18"x18" & 12"x12" RECESSED ABANDONDED METAL JUNCTION BOXES
EXISTING 8"x16"x4" LEAVE-OUT IN CMU WALL
L
L1
20 23
M
Patient Elevators
5C100C
Corridor
5C100B
EXISTING EXPANSION JOINT
EXISTING CONDUIT ENTERS AND EXITS SHAFT +/-12" BELOW
& +/-12" ABOVE CONCRETE BEAM THAT IS FLUSH WITH SHAFT
LINE OF EXISTING CONCRETE BEAM EXTENDS INTO SHAFT
EXISTING FIRE DAMPER LOCATION
@ 5TH FLOOR PLENUM
LOOKING DOWN INTO SHAFT
LINE OF EXISTING CONCRETE BEAM
STICKING +/-2" INTO SHAFT
CONCRETE COLUMN.
EXISTING PLUMBING LINES, TYPICAL
EXISTING THERMOSTAT & WALL OUTLET TO REMAIN
EXISTING ARTWORK TO BE REMOVED &
RETURNED TO VA (THREE (3) PIECES)
LIGHT SWITCH TO REMAIN.
EXISTING WALL PROTECTION TO REMAIN
(HAND RAIL & CRASH RAIL)
DASHED LINES INDICATE SOFFIT ABOVE @ 7'-6" AFF TO REMAIN
& BE PROTECTED THROUGHOUT CONSTRUCTION
S
EXISTING FIRE DAMPER LOCATION @ 5TH FLOOR PLENUM
DASHED LINE OF 6TH FLOOR ABOVE
DASHED LINE INDICATES PATH OF
FIRE LINE ABOVE 6TH FLOOR
4"
BTM @ 8'-7"
EXISTING 24"X32" STONE ACCESS PANEL TO REMAIN & BE
PROTECTED
B T
M
'-8
EXISTING FIRE LINE W/ STL. ANGLE BRACE TO REMAIN & BE PROTECTED
BTM @ 9'-0"
L
L1
20 23
M
Elevator Lobby 6C100B
Elect.
6C100
Elect.
6C101
Corridor 6C100A
Conference Room 6C102
EXISTING EXPANSION JOINT
LINE OF EXISTING CONCRETE BEAM EXTENDING INTO SHAFT,
NORTH & EAST WALLS
LOOKING DOWN INTO SHAFT
EXISTING FIRE LINE W/ STL. ANGLE BRACE
DASHED LINE INDICATES PATH OF FIRE LINE ABOVE 6TH FLOOR
EXISTING FIRE DAMPER LOCATION
@ 6TH FLOOR PLENUM
EXISTING METAL STUD WALL W/ ONE (1) LAYER
OF GWB ON ONE (1) SIDE TO REMAIN.
IN
S
ID
E C
L E
A R
TO BE FIELD VERIFIED
+/- 8'-8" INSIDE CLEAR
+/- 18'-9"
10'-1" +/- 8'-8"
EXISTING 24"W x 32" H STONE ACCESS PANEL @ 12" AFF
TO REMAIN & BE USED TO ACCESS INACESSIBLE SPACE
DASHED LINES INDICATE WALLS OF SHAFT BELOW 6TH FLOOR
BTM @ 8'-4"
B T
M
'-4
EXISTING PLUMBING LINE TRANSITIONS FROM 5TH TO 6TH FLOOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: GLEN ZEISSET
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
ATE
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
P.O. Box 6723 Oak Ridge, TN 37831 P. 440.667.5120
MECHANICAL / ELECTRICAL ENGINEERING:
FFE, INC.
4445 Lake Forest Drive Suite 600
CINCINNATI, OH 45242
P. 513.758.2220
STRUCTURAL ENGINEERING:
THORSON BAKER & ASSOC.
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
FINAL CD SUBMISSION
C U s e rs \r ic h
\D o c u m e n ts \V
A M
C P
R O
V
ID
E A
C C
E S
S A
C
A
C ri c h
Q X
K
S .r v t
/1
/2
:5
:2
P
M
AS-X-2.0
EXISTING CONDITIONS FLOOR PLANS PROVIDE ACCESSIBILITY FOR
AC-17 & AC-18 FIRE DAMPERS
10701 EAST BLVD. CLEVELAND, OHIO
541-21-506
02.25.25 CJK DAK
SCALE: 1/4" = 1'-0"
SECOND FLOOR EXISTING CONDITIONS PLAN
NORTH
SCALE: 1/4" = 1'-0"
THIRD FLOOR EXISTING CONDITIONS PLAN
NORTH
SCALE: 1/4" = 1'-0"
FOURTH FLOOR EXISTING CONDITIONS PLAN
NORTH
SCALE: 1/4" = 1'-0"
FIFTH FLOOR EXISTING CONDITIONS PLAN
NORTH
SCALE: 1/4" = 1'-0"
SIXTH FLOOR EXISTING CONDITIONS PLAN
NORTH
LOOKING DOWN ONTO EXISTING STRUCTURAL PLATFORM BELOW
Revisions: Date:
65% CDs SUBMISSION 12.16.24
GENERAL NOTES:
CONSIDER ALL AREAS OWNER-OCCUPIED UNLESS NOTED OTHERWISE.
ALL 3-5/8" METAL STUD WALLS ARE DRAWN AND DIMENSIONED TO A 5" NOMINAL WIDTH, TYPICAL UNLESS OTHERWISE NOTED. ALL DIMENSIONS ARE CLEAR DIMENSIONS FROM FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD. ALL CMU WALLS ARE DRAWN AND DIMENSIONED TO AN 8" NOMINAL WIDTH, TYPICAL UNLESS
OTHERWISE NOTED.
CONTRACTOR (I.E. FIRE PROTECTION, HVAC, FIRE ALARM, ELECTRICAL, ETC.) TO INSTALL SYSTEM PER OWNER REQUIREMENTS AND IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF ALL APPLICABLE CODES.
PATCH AND REPAIR ALL EXISTING AREAS TO REMAIN AS REQUIRED TO MATCH EXISTING CONDITIONS.
WHERE NEW UTILITIES ARE TO BE INSTALLED IN EXISTING PARTITIONS, CONTRACTOR SHALL REMOVE EXISTING DRYWALL AS REQUIRED FOR INSTALLATION OF SAME AND PATCH AND REPAIR WITH NEW TO MATCH
EXISTING CONDITIONS UPON COMPLETION OF UTILITY INSTALLATION.
ALL DAMAGE TO EXISTING AREAS OCCURING AS A RESULT OF CONSTRUCTION SHALL BE REPAIRED AS REQUIRED BY THE CONTRACTOR. CONTRACTOR SHALL PROTECT ALL EXISTING WALL, CEILING, AND FLOOR FINISHES IN EACH AREA. ANY SURFACES DAMAGED BY CONTRACTOR SHALL BE REPLACED BY THE
CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
ALL NEW PENETRATIONS IN FIRE-RATED ASSEMBLIES TO MAINTAIN FIRE RATING OF ASSEMBLY AS REQUIRED.
NEW AND EXISTING FURNITURE SHOWN FOR REFERENCE ONLY. THE OWNER SHALL REMOVE, PRIOR TO CONSTRUCTION, ALL ITEMS THAT THE OWNER DESIRES TO SALVAGE. ALL REMAINING ITEMS INDICATED TO BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR AND LEGALLY DISPOSED OF IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. ALL ITEMS TO REMAIN IN SPACE SHALL BE PROTECTED THROUGHOUT BY THE CONTRACTOR THROUGHOUT CONSTRUCTION. NEW FURNITURE TO BE FURNISHED AND INSTALLED
BY THE OWNER UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL PROVIDE DUST-REMOVAL WALK-OFF MATS (TACKY MAT) AT ALL CONSTRUCTION ENTRY
POINTS.
CONTRACTOR SHALL PROVIDE HEPA FILTERED NEGATIVE AIR MACHINE(S) TO MAINTAIN NEGATIVE PRESSURE IN WORK AREAS ENSURING NO DUST OR FUMES WILL BE TRANSFERRED TO OCCUPIED AREAS. PROVIDE VISUAL PRESSURE MONITORING DEVICE AT DUST-PROOF BARRICADE TO CONFIRM PRESSURE. DUST MONITORING SHALL BE BY OWNER. SEE SPECIFICATION 01 00 00 "GENERAL REQUIREMENTS" ATTACHMENT
AND 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS.
ALL DEMOLITION WORK BEING DONE OUTSIDE TEMPORARY PARTITIONS IS TO BE APPROPRIATELY SEALED OFF TO PREVENT THE TRANSMISSION OF DUST AND DEBRIS. WORK SHALL BE DONE TO MINIMIZE DISRUPTION TO VISITORS, PATIENTS, AND STAFF. COORDINATE LOCATION OF BARRIERS WITH OWNER.
THE HOSPITAL'S SMOKE AND FIRE SUPPRESSION SYSTEM SHALL REMAIN IN OPERATION WITHIN THE
PROJECT AREA DURING THE ENTIRE CONSTRUCTION PHASE.
FIELD VERIFY LOCATION OF ALL EXISTING CONDITIONS. NOTIFY COR OF ANY DISCREPANCIES.
WHERE NEW DOORS ARE INDICATED IN EXISTING WALL ASSEMBLIES, CUT OPENINGS IN EXISTING WALL.
REFER TO DOOR SCHEDULE FOR DIMENSIONS. PREPARE OPENINGS FOR NEW DOOR, INCLUSIVE OF THE ADDITION OF JAMB AND HEAD REINFORCEMENT (I.E. DOUBLE STUDS, HEADERS, STEEL LINTELS) AND PATCH
ADJACENT WALLS TO MATCH EXISTING.
ALL FLOOR, WALL, CEILING, AND MISC. FIRE-RESISTIVE ASSEMBLIES AND CONSTRUCTION SHALL BE OF THE FIRE RATING CALLED FOR ON THE DRAWINGS AND/OR AS REQUIRED BY CODE. ALL EXISTING FIRE-RESISTIVE ASSEMBLIES SHALL BE MAINTAINED AND THE RATING NOT COMPROMISED. FIRE RATED ASSEMBLIES AND CONSTRUCTION INCLUDING ALL FIRESTOPPING, FIRE RATED DOORS, AND MISC. FIRE RESISTIVE
REQUIREMENTS SHALL BE LEFT UNCONCEALED AS REQUIRED FOR INSPECTION BY THE VA COR.
DEBRIS REMOVAL SHALL NOT INTERFERE WITH OWNER'S OPERATIONS AND SHALL OCCUR DURING OFF HOURS AS DETERMINED BY THE COR. SEE ALSO SPECIFICATION SECTION 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS REGARDING THE HAULING OF DEBRIS FROM THE PROJECT AREA.
ALL NOISE-GENERATING OPERATIONS SHALL BE SCHEDULED SO AS NOT TO IMPEDE OWNER'S OPERATIONS AS DETERMINED BY THE COR. ALL WORK IN PUBLIC CORRIDORS SHALL BE PERFORMED OFF-HOURS UNLESS
OTHERWISE APPROVED BY THE COR.
EXISTING FLOOR SLABS ARE 2 HR FIRE RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, CONTRACTOR SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE
COMPROMISED, AND…