Project Drawings - WVDNR Chief Logan Rec Center Pool HVAC Renovation 12Oct26.pdf
PDF 2 MB Posted
- Attached to
- Chief Logan Rec Center New HVAC Construction
- Solicitation number
- CRFQ 0310 DNR2700000010 1
- Issued by
- Lewis County, West Virginia
About this file
This file contains project drawings for the West Virginia Department of Natural Resources (WVDNR) Chief Logan Recreation Center Pool HVAC Renovation. The drawings document the mechanical, electrical, and plumbing systems required for the HVAC renovation project at the facility. The project scope includes the design and installation of heating, ventilation, and air conditioning systems to support the recreation center's pool operations. The drawings serve as technical specifications and visual representations of the proposed system layouts, equipment placement, and integration points with existing building infrastructure necessary for contractors to prepare accurate bids and execute the renovation work.
The project drawings establish the technical baseline and design standards that bidders must follow in their proposals and project execution. As design documentation rather than a solicitation document, the drawings do not independently establish pricing terms, set-asides, contract award dates, or term conditions. These parameters would be detailed in the accompanying bid solicitation, contract specifications, or procurement notices issued by WVDNR for the Chief Logan Recreation Center Pool HVAC Renovation project.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PENNSYLVANIA OFFICE
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PHONE: (724) 966 - 5655
WEST VIRGINIA OFFICE
54 WEST RUN RD
MORGANTOWN, WV 26508
PHONE: (304) 291 - 2234
WVDNR CHIEF LOGAN REC CENTER POOL HVAC
RENOVATION
MEI PROJECT #26010
DWG TITLE
GENERAL
G000 COVER PAGE
G101 EXISTING & NEW FLOOR PLANS
G102 ENLARGED PLANS & DETAILS
MECHANICAL
M000 MECHANICAL ABBREVIATIONS
M001 MECHANICAL DUCTWORK DEMO PLAN
M101 MECHANICAL DUCTWORK PLAN
M102 MECHANICAL PIPING PLAN
M401 ENLARGED MECHANICAL DUCTWORK PLAN
M402 ENLARGED MECHANICAL PIPING PLAN PLAN
M501 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
M901 MECHANICAL PERSPECTIVE
ELECTRICAL
E000 ELECTRICAL ABBREVIATIONS
E001 ELECTRICAL DEMO POWER PLAN
E101 ELECTRICAL POWER PLAN
E102 ELECTRICAL POWER PLAN
E103 ELECTRICAL LIGHTING PLAN
E601 ELECTRICAL SCHEDULES & DETAILS
CHEM STG
62 SF
SPRINKLER
22 SF
POOL
103A
3381 SF
POOL DECK
4843 SF
POOL HEATER
105A
97 SF
ELEC
73 SF
POOL MECH
507 SF
MEN'S
SHOWERS/LOCKERS
773 SF
WOMEN'S
SHOWERS/LOCKERS
773 SF
STORAGE
195 SF
VENDING
124 SF
OFFICE
245 SF
LOBBY
550 SF
VEST
131 SF
JAN
103 SF
COURTS
23465 SF
POOL
103A
3381 SF
POOL DECK
4761 SF
VEST
131 SF
LOBBY
550 SF
OFFICE
245 SF
JAN
103 SF
STORAGE
195 SF
VENDING
124 SF
WOMEN'S
SHOWERS/LOCKERS
773 SF
MEN'S
SHOWERS/LOCKERS
773 SF
POOL MECH
507 SF
ELEC
73 SF
POOL HEATER
105A
97 SF
CHEM STG
62 SF
COURTS
23465 SF
SPRINKLER
22 SF
BOILER ROOM
104A
73 SF
G102
INSTALL NEW FLOAT VALVE ON
EXISTING PADDOCK VACSAND FILTER
CUT 16" x 16" HOLE AND INSTALL METAL ANGLE
PICTURE FRAME OF 1/4" STEEL PROVIDE FULL
COVERAGE STAINLESS STEEL PIANO HINGED LOCKING
DOOR FOR BULK CHLORINE FILL VALVE HOSE ACCESS PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
G101
EXISTING & NEW
FLOOR PLANS
12 OCT 2026
TRT
BCM
26010.1
ISSUED FOR
CONSTRUCTION
WVDNR
WVDNR CHIEF
LOGAN REC CENTER
POOL HVAC
RENOVATION
N O
D
ES
C
R
IP
TI
O
N D
A
TE
1/8" = 1'-0"1
EXISTING FIRST FLOOR PLAN
1/8" = 1'-0"2
NEW WORK FIRST FLOOR PLAN
104A
SPRINKLER
22 SF
POOL DECK
4761 SF
BOILER ROOM
104A
73 SF
G 3a
EXISTING
COLUMN WRAP
20' - 2 3/8"
4'
1/
4"
4' - 10"
G102
104A
G102
2' X 4' SIGN "CEILING ABOVE
NOT RATED FOR STORAGE"
SIGN BY OTHERS.
104A
ADOOR TYPE
1FRAME TYPE
FLUSH
# WIDTH
SOUND RATING
FIRE RATING
X
7/8" 1-5/8" 2-1/2" 3-5/8"
4" 5-1/2"
6"
8"
NONE
#G GYPSUM AND STEEL STUD TO CEILING - NO
INSULATION 45 STC RAL-TL99-103a
16 GA STRUCTURAL 6"
METAL STUD @ 16" O.C.
MOISTURE- AND MOLD-
RESISTANT 5/8" GYP. BOARD
MECHANICALLY FASTEN
BOTTOM TRACK TO FLOOR
SLAB @ 24" OC MAX
MOISTURE- AND MOLD-
RESISTANT 5/8" GYP. BOARD
PLAN
BASE
CEILING
WATER GUARD DRYWALL TRIM
CEILING
NOTE: PROVIDE CAULKING
AROUND ALL WALL
PENETRATIONS
DOUBLE TOP TRACK
RUBBER BASE
MARINE GRADE
3/4" PLYWOOD
16 GA STRUCTURAL 6"
METAL STUD @ 16" O.C.
MOISTURE- AND
MOLD-RESISTANT
5/8" GYP. BOARD
FASTEN TO
EXTERIOR WALL
SEAL ALL
PENETRATIONS
PER MEP
9'
0"
2" X 2" ALUMINUM
TRIM ALL SIDES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
G102
ENLARGED PLANS &
DETAILS
12 OCT 2026
TRT
BCM
26010.1
ISSUED FOR
CONSTRUCTION
WVDNR
WVDNR CHIEF
LOGAN REC CENTER
POOL HVAC
RENOVATION
N O
D
ES
C
R
IP
TI
O
N D
A
TE
1/2" = 1'-0"1
NEW WORK FIRST FLOOR PLAN - ENLARGED BOILER ROOM
1/2" = 1'-0"2 104A
DOOR SCHEDULE
FIRE
RATING WIDTH HEIGHT
PANEL FRAME
NOTES #TYPE MATL TYPE MATL
104A 6' - 0" 7' - 0" AA HM 1 HM 104A
1.
DOOR SCHEDULE NOTES:
EXTERIOR RATED W/ WEATHER STRIPPING, STOREROOM FUNCTION, INACTIVE LEAF W/ MANUAL FLUSH BOLTS.
DOOR TYPES
1/2" = 1'-0"3
WALL SECTION
PAINT WALLS, DOOR , AND PLYWOOD TO MATCH EXISTINGPAINT WALLS, DOOR , AND PLYWOOD TO MATCH EXISTING
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES
OR SPECIAL CONDITIONS. ALL WALL MOUNTED DEVICES ARE
FINAL HEIGHT BY. ARCH.
WIRING AND CONDUIT OR MC CABLE SHALL BE REQUIRED FOR
ALL OUTLETS AND DEVICES. FOLLOW INDICATED CIRCUITS
NUMBERS AND PANEL DESIGNATION. OBTAIN PRIOR APPROVAL
OF ENGINEER FOR DEVIATIONS.
ALL 15A AND 20A, 115V AND 120V RECEPTACLES LOCATED IN
DWELLING UNITS SHALL BE TAMPER RESISTANT.
ALTHOUGH ALL BRANCH CIRCUIT WIRING IS NOT SHOWN, IT IS
THE INTENT OF THESE DOCUMENTS THAT A COMPLETE
BRANCH CIRCUIT WIRING SYSTEM BE INSTALLED.
ALL NEUTRALS SHALL BE FULL CAPACITY. THE USE OF SHARED
OR COMMON NEUTRALS IS PROHIBITED ON ALL ELECTRIC
WIRING.
PROVIDE CONTROL AND FIRE ALARM WIRE AS NECESSARY TO
INSTALL ALL SYSTEMS DEVICES AND PANELS FOR COMPLETE
SYSTEMS. FINAL CONNECTION TO PERMANTLY MOUNTED
EQUIPMENT IS PART OF THE ELECTRICAL SCOPE OF THIS
PROJECT.
PROVIDE TEL/DATA AND CAT5 AS INDICATED. REVIEW DATA,
SWITCH, RECEPTACLE, ETC LOCATIONS AND HEIGHTS WITH
OWNER PRIOR TO INSTALLATION.
ALL INTERIOR WIRING SHALL BE THHN/THWN IN METAL CONDUIT
OR MC CABLE. MAX OF 3'-0" OF FLEXIBLE CONDUIT MAY BE
USED FOR FINAL EQUIPMENT TERMINATIONS.
EXTERIOR WIRING IS TO BE THHN/THWN IN PVC CONDUIT. MAX.
OF 3'-0" OF FLEXIBLE METALLIC SEATITLE CONDUIT MAY BE
USED TO EXTERIOR EQUIPMENT.
TV AND TELEPHONE CABLING SHALL BE INSTALLED FROM
LOCATIONS INDICATED ON DRAWINGS TO DEMARC LOCATION.
COORDINATE FINAL DEMARC LOCATIONS w/ TV AND
TELEPHONE COMPANY.
GROUP AND TRAIN ALL TEL/DATA AND CABLE TV CABLE.
SUPPORT FROM STRUCTURE.
VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK WITH OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES WITH ALL OTHER
TRADES PRIOR TO INSTALLATION.
PERFORM ALL WORK IN ACCORDANCE WITH 2020 NEC.
COORDINATE FINAL FIXTURE LOCATIONS WITH OWNER AND
GENERAL CONTRACTOR PRIOR TO INSTALLATION OF CEILING.
FINAL COORDINATION OF SCOPE OF WORK , DIMENSIONS,
FIXTURE PLACEMENT, ROUTINGS, ETC IS THE RESPONSIBILITY
OF THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS
PRIOR TO BIDDING.
ELECTRICAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
PROVIDE FIRE ALARM WIRING AND CONDUIT AS
NECESSARY TO MEET CODES, STANDARDS AND
REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION
(AHJ).
PROVIDE WIRING AND CONDUIT AS NECESSARY TO
INSTALL ALL FIRE ALARM DEVICES AND PANELS FOR A
COMPLETE SYSTEM.
RETAIN THE SERVICES OF A NICET LEVEL 3 OR 4
SYSTEM DESIGNER TO DESIGN A COMPLETE FIRE
ALARM SYSTEM AS NECESSARY TO MEET CURRENT
NFPA, STATE AND LOCAL REQUIREMENTS.
PROJECT DRAWINGS ARE DIAGRAMMATIC IN NATURE.
PROVIDE HORN/STROBES AS SHOWN AND SUPPLEMENT
AS NECESSARY TO MEET REQUIREMENTS OF CURRENT
NFPA, STATE AND LOCAL REQUIREMENTS. OBTAIN ALL
NECESSARY APPROVALS PRIOR TO INSTALLATION OF
SYSTEM. OBTAIN FINAL INSPECTION AS REQUIRED BY
AHJ AND INSURANCE UNDERWRITERS.
PROVIDE DUCT DETECTORS IN ACCORDANCE w/ NFPA
STANDARDS IN THE RETURN STREAM FOR ALL AIR
SYSTEMS 2,000 CFM & GREATER ALONG W/ THE SUPPLY
STREAM FOR SYSTEMS 15,000 CFM & GREATER.
FIRE ALARM WIRING IS TO BE IN CONDUIT OR MC CABLE
APPROPRIATELY LABELED AS REQUIRED BY NFPA 72.
PERFORM ALL WORK IN ACCORDANCE w/ NFPA 72 AND
2020 NEC.
FINAL COORDINATION OF SCOPE OF WORK,
DIMENSIONS, FIXTURE PLACEMENT, ROUTING, ETC IS
THE RESPONSIBILITY OF THE GENERAL CONTRACTOR
AND ALL SUB-CONTRACTORS PRIOR TO BIDDING.
VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS
PRIOR TO BIDDING. COORDINATE ALL WORK w/ OTHER
TRADES. COORDINATE ALL CEILING MOUNTED DEVICES
w/ ALL OTHER TRADES PRIOR TO INSTALLATION.
FIRE ALARM NOTES
LIGHTING LEGEND
SINGLE POLE SWITCH
3: THREE WAY
4: FOUR WAY
D: DIMMING
3D: THREE WAY DIMMING
K: KEYED
O: SWITCH W/ INTEGRAL OCCUPANCY SENSOR
OS
OCCUPANCY SENSOR. PROVIDE POWER SUPPLIES & ALL
ANCILLARY DEVICES AS NECESSARY FOR A COMPLETE
INSTALLATION.
ELECTRICAL LEGEND
120V, 20A, DUPLEX / QUADRUPLEX RECEPTACLE
G: GFCI
C: MOUNTED 6" ABOVE COUNTER HEIGHT
CG: GFCI, MOUNTED 6" ABOVE COUNTER HEIGHT
WP: GFCI INSTALLED IN WEATHERPROOF ENCLOSURE
TR: TAMPER RESISTANT
TV: MOUNTED 6'-0" A.F.F.
IG: ISOLATED GROUND
U: PROVIDED W/ USB PORTS
xD: EXISTING TO BE DEMOLISHED xR: EXISTING TO BE REPLACED W/ NEW DEVICE
SPECIALTY RECEPTACLE, COORDINATE NEMA
CONFIGURATION W/ EQUIPMENT SERVED BY RECEPTACLE
WIREMOLD 880 SERIES 3 GANG STANDARD DEPTH FLOOR BOX.
PROVIDE DUPLEX RECEPTACLE IN TWO GANGS.
WIREMOLD 880 SERIES 2 GANG STANDARD DEPTH FLOOR BOX.
PROVIDE DUPLEX RECEPTACLE IN ONE GANG
J EQUIPMENT TERMINATION. VERIFY TERMINATION METHOD w/
MANUFACTURER
M MOTOR SWITCH
EQUIPMENT TERMINATION. VERIFY TERMINATION METHOD w/
MANUFACTURER
1.
2.
3.
4.
5.
6.
7.
TELE/DATA AND CATV CONDUIT IS SHOWN ON DRAWINGS ONLY
FOR SPECIFIC ROUTES OR SPECIAL CONDITIONS. ALL WALL
MOUNTED DEVICES ARE FINAL HEIGHT BY ARCHITECT.
CONDUIT AND TEL/DATA OR CATV CABLING WILL BE REQUIRED
AT ALL TELE/DATA AND CATV LOCATIONS ON THE DRAWINGS.
PROVIDE TELE/DATA AND CATV AS INDICATED. REVIEW DATA,
SWITCH, RECEPTACLE, ETC LOCATIONS AND HEIGHTS w/
OWNER PRIOR TO INSTALLATION.
RACEWAY SHALL BE INSTALLED FROM LOCATIONS INDICATED
ON DRAWINGS TO DEMARC LOCATION. COORDINATE FINAL
DEMARC LOCATIONS w/ TV AND TELEPHONE COMPANY.
VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK w/ OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES w/ ALL OTHER
TRADES PRIOR TO INSTALLATION.
PERFORM ALL WORK IN ACCORDANCE 2020 NEC.
COORDINATION OF FINAL FIXTURE LOCATION w/ OWNER AND
GENERAL CONTRACTOR PRIOR TO INSTALLATION OF CEILING.
FINAL COORDINATION OF SCOPE OF WORK, DIMENSIONS,
FIXTURE PLACEMENT, ROUTINGS, ETC. IS THE RESPONSIBILITY
OF THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS
PRIOR TO BIDDING.
COMMUNICATION NOTES
COMMUNICATION LEGEND
TELE/DATA LOCATION. PROVIDE SINGLE GANG
BOX w/ 1" CONDUIT TO ABOVE ACCESSIBLE
CEILING. 2XCAT6 CABLE TO DEMARC.
WIREMOLD 880 FLOOR BOX PROVIDED & INSTALLED BY E.C.
INSTALL 1" CONDUIT FROM FLOOR BOX UP WALL TO ABOVE
ACCESSIBLE CEILING. PROVIDE (2) CAT6 JACKS & 2XCAT6 TO
DEMARC
TV
TELE LOCATION. PROVIDE SINGLE GANG BOX w/ 1"
CONDUIT TO ABOVE ACCESSIBLE CEILING. 1XCAT6
CABLE TO DEMARC.
DATA LOCATION. PROVIDE SINGLE GANG BOX w/
1" CONDUIT TO ABOVE ACCESSIBLE CEILING.
1XCAT6 CABLE TO DEMARC.
CATV LOCATION. PROVIDE SINGLE GANG BOX w/
1" CONDUIT TO ABOVE ACCESSIBLE CEILING.
1XRG59 COAX CABLE TO DEMARC.
1P SINGLE POLE
1PH SINGLE-PHASE
2/C TWO-CONDUCTOR
2WAY TWO-WAY
3/C THREE-CONDUCTOR
3PH THREE-PHASE
3WAY THREE-WAY
4/C FOUR-WIRE
4PDT FOUR-POLE DOUBLE THROW
4PST FOUR-POLE SINGLE THROW
4WAY FOUR-WAY
4W FOUR-WIRE
ø PHASE --------------------A------------------------------------------------------------------------------------
A AMPERE
AC ALTERNATING CURRENT; ARMORED CABLE
ACT ACOUSTIC CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
A/E ARCHITECT/ENGINEER
AFC ABOVE FINISHED COUNTER
AFCI ARC FAULT CIRCUIT INTERUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMP AMPERE
AMT AMOUNT
ANN ANNUNCIATOR
APPD APPROVED
APPROX APPROXIMATELY; APPROXIMATE
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING; AMPS SHORT CIRCUIT
ATS AUTOMATIC TRANSFER SWITCH
ATTN ATTENTION
AUTO AUTOMATIC
AUX AUXILIARY
A/V AUDIO VISUAL
AVG AVERAGE
AWG AMERICAN WRE GAUGE
---------------B----------------------------------------------------------------------------------------
BAS BUILDING AUTOMATION SYSTEM
BAT BATTERY
BFF BELOW FINISHED FLOOR
BG BELOW GRADE
BKBD BACKBOARD
BLDG BUILDING
BLT BUILT
BLW BELOW
BOT BOTTOM
BPS BOLTED PRESSURE SWITCH
BRKR BREAKER
BSMT BASEMENT
BTWN BETWEEN
BX INTERLOCKED ARMORED CABLE
BYP BYPASS
---------------C---------------------------------------------------------------------------------------
C CELSIUS
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION SYSTEM
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TV
CD CANDELA; CONSTRUCTION DOCUMENTS;
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CIR CIRCLE
CKT CIRCUIT
C CENTERLINE
CL CURRENT LIMITING; CENTER LINE; CLASS; CLOSE
CLG CEILING
CLR CLEAR
CND CONDUIT
COAX COAXIAL
COL COLUMN
COMB COMBINATION; COMBINED
COMM COMMUNICATION
COMPR COMPRESSOR
CONC CONCRETE
CONN CONNECT
CORR CORRIDOR; CORRECT
CP CONTROL PANEL
CR CONTROL RELAY
CS CONTROL SWITCH
CT CURRENT TRANSFORMER
CTR CENTER
CTRL CONTROL
CU COPPER; COEFFICIENT OF UTILIZATION; CUBIC
CU FT CUBIC FEET
CUR CURRENT
---------------D----------------------------------------------------------------------
D DEPTH
DB DIRECT BURIAL / DECIBEL
DBL DOUBLE
DC DIRECT CURRENT
DDC DIRECT DIGITAL CONTROL
DEL DELETE; DELIVER
DEMO DEMOLITION; DEMONSTRATION
DEPT DEPARTMENT
DIA DIAMETER
DIAG DIAGRAM; DIAGONAL
DIFF DIFFERENCE
DIM DIMENSION
DISC DISCONNECT
DIST DISTANCE; DISTRICT
DISTR PNL DISTRIBUTION PANEL
DIV DIVISION; DIVIDE
DN DOWN
DOC DOCUMENT
DPDT DOUBLE POLE; DOUBLE THROW
DPST DOUBLE POLE; SINGLE THROW
DS DISCONNECT SWITCH
DWG DRAWING
----------------E----------------------------------------------------------------------
E EAST
EA EACH
EC ELECTRICAL CONTRACTOR
EL ELEVATION
ELEC ELECTRIC
ELEV ELEVATOR
ELR END OF LINE RESISTOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
ENGR ENGINEER
ENGY ENERGY
ENT ELECTRICAL NONMETALLIC TUBING
ENTR ENTRANCE
EO ELECTRICAL OUTLET
EP ELECTRICAL PANEL
EQ EQUAL
EQUIP EQUIPMENT
EQUIV EQUIVALENT
EST ESTIMATE
ESTB ESTABLISH
EX EXISTING
EXH EXHAUST
EXP EXPANSION; EXPOSED; EXPAND
EXT EXTERIOR; EXTERNAL
EXTN EXTENSION
----------------F----------------------------------------------------------------------
F FAHRENHEIT; FEMALE
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FBO FURNISHED BY OWNER
FC FOOT-CANDLE
FCU FAN COIL UNIT
FDR FEEDER
FIN FINISH
FIN GR FINISH GRADE
FIXT FIXTURE
FL MT FLUSH MOUNT
FLEX FLEXIBLE
FLG FLOORING
FLR FLOOR
FLUOR FLUORESCENT
FM FREQUENCY MODULATION
FP FIREPROOF
FR FIRE RESISTANT
FREQ FREQUENCY
FS FUSIBLE SWITCH; FLOW SWITCH
FSC FOOD SERVICE EQUIPMENT CONTRACTOR
FT FEET; FIRE TREATED; FOOT
FU FUSE
FU SW FUSED SWITCH
FURN FURNISH; FURNACE; FURNITURE
FUT FUTURE
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
----------------G----------------------------------------------------------------------
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL; GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GOVT GOVERNMENT
GRN GROUND
GYP GYPSUM
----------------H----------------------------------------------------------------------
HDW HARDWARE
HF HIGH FREQUENCY
HID HIGH INTENSITY DISCHARGE
HO HOLD OPEN
HOA HAND-OFF-AUTOMATIC
HORIZ HORIZONTAL
HOSP HOSPITAL
HP HORSEPOWER; HEAT PUMP;
HIGH PRESSURE
HPS HIGH PRESSURE SODIUM
HT HEIGHT
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
HZ HERTZ; FREQUENCY IN CYCLES PER
SECOND
----------------I----------------------------------------------------------------------
ID INSIDE DIAMTER; INSIDE DIMENSION;
IDENTIFICATION
ILLUM ILLUMINATION
IMC INTERMEDIATE METAL CONDUIT
INFO INFORMATION
INSUL INSULATION
INTERCOM INTERCOMMUNICATION
INTL INTERNATIONAL
IR INFRARED; INSIDE RADIUS
IT INFORMATION TECHNOLOGY
----------------J----------------------------------------------------------------------
JB JUNCTION BOX
----------------K----------------------------------------------------------------------
KCMIL THOUSAND CIRCULAR MILS
KHz KILOHERTZ
KIT KITCHEN
KO KNOCKOUT
kV KILOVOLT kVA KILOVOLT AMPERES kVAh KILOVOLT AMPERE PER HOUR kVAR KILOVAR; KILOVOLT AMPERE
REACTIVE
kW KILOWAT kWh KILOWATT HOURS ----------------L----------------------------------------------------------------------
L LITER; ANGLE
LA LIGHTNING ARRESTER
LAN LOCAL AREA NETWORK
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LIN LINEAR
LM LUMEN
LOC LOCATION
LP LIGHT POLE; LOW PRESSURE
LPW LUMENS PER WATT
LT LIGHT
LT SW LIGHT SWITCH
LTD LIMITED
LTG LIGHTING
LV LOW VOLTAGE
----------------M----------------------------------------------------------------------
M METER
mA MILLIAMPERE
MACH MACHINE
MAG MAGNET
MAINT MAINTENANCE
MAN MANUAL
MATL MATERIAL
MAX MAXIMIM
MC MECHANICAL CONTRACTOR; METAL
CLAD CABLE
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM THOUSAND CIRCULAR MILS
MDP MAIN DISTRIBUTION PANEL
MDS MAIN DISTRIBUTION SWITCHBOARD
ME MECHANICAL ENGINEER
MECH MECHANICAL
MED MEDICAL; MEDIUM
MFD MANUFACTURED
MFR MANUFACTURER
MFR REC MANUFACTURER'S RECOMMENDATION
MH MANHOLE; METAL HALIDE
MHZ MEGAHERTZ
MI MINERAL INSULATED
MIC MICROPHONE
MID MIDDLE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MOD MODIFY; MODULE
MON MONITOR
MOT MOTOR
MOV MOTOR OPERATED VALVE
MS MOTOR STARTER
MTD MOUNTED
MTG MEETING; MOUNTING
MTL METAL
MTS MANUAL TRANSFER SWITCH
MULT MULTIPLE
mV MILLIVOLT
MVA MEGAVOLT-AMPERE
MW MEGAWATT; MICROWAVE
mW MILLIWATT
MWH MEGAWATT HOUR
----------------N----------------------------------------------------------------------
N NORTH
NC NORMALLY CLOSED
NE NORMAL EMERGENCY
NEC NATIONAL ELECTRICAL CODE
NEG NEGATIVE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NEUT NEUTRAL
NF NON-FUSED
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NFS NON-FUSED SWITCH
NIC NOT IN CONTRACT
NM NONMETALLIC
NMAG NONMAGNETIC
NO NORMALLY OPEN; NUMBER
NORM NORMAL
NTS NOT TO SCALE
----------------O----------------------------------------------------------------------
OA OVERALL; OUTSIDE AIR
OC ON CENTER
OCC OCCUPANCY
OCPD OVERCURRENT PROTECTION DEVICE
OD OUTSIDE DIAMETER; OUTSIDE DIMENSION
OF/CI OWNER FURNISHED / CONTRACTOR
INSTALLED
OF/OI OWNER FURNISHED / OWNER INSTALLED
OH OVERHEAD
OL OVERLOAD ELEMENT
OPP OPPOSITE
OPT OPTIONAL; OPTIMUM
OVC OVERCURRENT
----------------P----------------------------------------------------------------------
P POLE (S); PILOT
PA POWER AMPLIFIER; PUBLIC ADDRESS
PART PARTIAL
PB PULL BOX; PANEL BOARD; PANIC BAR;
PUSH-BUTTON
PC PLUMBING CONTRACTOR; PIECE
PE PHOTOELECTRIC, PNEUMATIC ELECTRIC
PEN PENETRATE
PERF PERFORATED
PERIM PERIMETER
PERM PERMANENT
PF POWER FACTOR
PH PHASE
PIV POST INDICATOR VALVE
PL PILOT LIGHT
PLBG PLUMBING
PNL PANEL
POS POSITION; POSITIVE
PP POWER POLE
PR PAIR
PRELIM PRELIMINARY
PREP PREPARATION
PRESS SW PRESSURE SWITCH
PREV PREVIOUS
PRI PRIMARY
PROJ PROJECT
PS PULL STATION
PT POTENTIAL TRANSFORMER
PVC POLYVINAL CHLORIDE (PLASTIC)
PWR POWER
----------------Q----------------------------------------------------------------------
QA QUALITY ASSURANCE
QC QUALITY CONTROL
QTY QUANTITY
QUAL QUALITY
----------------R----------------------------------------------------------------------
R RELAY; RADIUS
R/W RIGHT OF WAY
RC REMOTE CONTROL
RCP REFLECTED CEILING PLAN
REC RECESSED
RCPT RECEPTACLE
REF REFRIGERATOR; REFERENCE
REINF REINFORCED
REPL REPLACE
REQD REQUIRED
REV REVISION; REVOLUTIONS
RFI REQUEST FOR INFORMATION
RFP REQUEST FOR PROPOSAL
RH RIGHT HAND
RHC REHEAT COIL
ROW RIGHT OF WAY
RS RAPID START
RTG RATING
RTU ROOF TOP UNIT
----------------S----------------------------------------------------------------------
S/S START / STOP
SAMP SAMPLE
SCHED SCHEDULE
SCHEM SCHEMATIC
SD SMOKE DETECTOR
SDMPR SMOKE DAMPER
SEC SECONDARY
SECT SECTION
SEP SEPARATE
SHT SHEET
SIM SIMILAR
SLV SLEEVE
SMR SURFACE MOUNTED RACEWAY
SNSR SENSOR
SOLV SOLENOID VALVE
SPDT SINGLE POLE; DOUBLE THROW
SPEC SPECIFICATION
SPKR SPEAKER
SPLY SUPPLY
SPST SINGLE POLE; SINGLE THROW
SQ SQUARE
SS STAINLESS STEEL
ST SINGLE THROW; STAIRS; STREET
ST PR STATIC PRESSURE
STA STATION
STD STANDARD
STL STEEL
STOR STORAGE
STR STARTER; STRAIGHT; STRIKE; STRINGERS
STRB STROBE
STRB/HRN STROBE / HORN
STRUCT STRUCTURAL
SUB SUBSTITUTE
SUP SUPPLEMENTARY
SUPVR SUPERVISOR
SURF SURFACE
SUSP SUSPEND
SW SWITCH; SIDEWALK
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMBOL
SYS SYSTEM
----------------T----------------------------------------------------------------------
T&M TIME AND MATERIAL
TECH TECHNICAL
TEL TELEPHONE
TEMP TEMPORARY
TERM TERMINAL
THRU THROUGH
TL TWIST LOCK
TOC TOP OF CONCRETE; TOP OF CURB
TOL TOLERANCE
TP TWISTED PAIR; TELEPHONE POLE
TSP TWISTED SHIELDED PAIR
TSTAT THERMOSTAT
TV TELEVISION
TVOUT TELEVISION OUTLET
TYP TYPICAL
----------------U----------------------------------------------------------------------
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UP UTILITY POLE
UPS UNINTERRUPTIBLE POWER SUPPLY
UL UNDER WRITERS LABORATORIES
UTP UNSHIELDED TWITED PAIR
UTIL UTILITY
UV UNIT VENTILATOR; ULTRAVIOLET
----------------V----------------------------------------------------------------------
V VOLT
VA VOLT AMPERE
VAM VOLTAMMETER
VAR VARIATION; VARIES; VOLT AMPERE
REACTIVE
VD VOLTAGE DROP; VOLUME DAMPER
VERT VERTICAL
VF VARIABLE FREQUENCY
VFD VARIABLE FREQUENCY DRIVE
VID VIDEO
VIF VERIFY IN FIELD
VOLT VOLTAGE
VR VOLTAGE REGULATOR; VAPOR RETARDED
VRFY VERIFY
VRLY VOLTAGE RELAY
VS VOLTMETER SWITCH; VENT STACK
----------------W----------------------------------------------------------------------
W WIRE; WATT; WASTE; WEST; WIDE
W/ WITH
W/O WITHOUT
WHM WATTHOUR METER
WP WEATHERPROOF; WATER PUMP;
WATER HEATER
WR WEATHER RESISTANT; WATER REPELLENT
WW WIREWAY; WARM WHITE; WASTE WATER
----------------X----------------------------------------------------------------------
XFMR TRANSFORMER
XP EXPLOSION PROOF
FIRE ALARM LEGEND
M MANUAL PULL STATION
H HEAT DETECTOR
S SMOKE DETECTOR:
ER - ELEVATOR RECALL
DD - DUCT DETECTOR
LV - LINE VOLTAGE (120V)
HORN / STROBEF
STROBE LIGHTS
ADDRESSABLE MODULE:
FS - FLOW SWITCH
TS - TAMPER SWITCH
RT - REMOTE TEST
ST - SHUNT TRIP
PR - PRIMARY FLOOR RECALL
SR - SECONDARY FLOOR RECALL
FH - FIREMAN'S HAT
FL - FLASHING HAT
AIM - INPUT MODULE
AOM - OUTPUT MODULE
xx
FAAP
FIRE ALARM ANNUNCIATOR PANEL
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E000
ELECTRICAL
ABBREVIATIONS
12 OCT 2026
TRT
BCM
26010.1
ISSUED FOR
CONSTRUCTION
WVDNR
WVDNR CHIEF
LOGAN REC CENTER
POOL HVAC
RENOVATION
ELECTRICAL ABBREVIATIONS
N O
D
ES
C
R
IP
TI
O
N D
A
TE
DEMO POWER TO EXISTING UNITS AND MAKE SAFE
ANYTHING THAT REMAINS FOR RE-USE
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E001
ELECTRICAL DEMO
POWER PLAN
12 OCT 2026
TRT
BCM
26010.1
ISSUED FOR
CONSTRUCTION
WVDNR
WVDNR CHIEF
LOGAN REC CENTER
POOL HVAC
RENOVATION
N O
D
ES
C
R
IP
TI
O
N D
A
TE
1/8" = 1'-0"1
01 - DEMO ELECTRICAL POWER PLAN
GFCI
GFCI
G
FC
I G
FC
I
GFCI
GFCI
E101
L1
MDP
DPLN1
DPHN1
DPHN1
(NEW)-7,9,11
DPHN1
(NEW)-8,10,12
CH-1
AHU-1
DPHN1
(NEW)-20,22,24
DPHN1
(NEW)-19,21,23
ROUTE 4" EMT OVERHEAD WITH
COMPRESSION COUPLINGS FROM MDP TO
DPHN1, VERITY ROUTE PRIOR TO BIDDING
DPHN1 25, 27, 29
DPHN1 26, 28, 30
DPHN1
(NEW)-25,27,29
DPHN1
(NEW)-26,28,30
SW-1
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES
OR SPECIAL CONDITIONS. ALL WALL MOUNTED DEVICES ARE
FINAL HEIGHT BY. ARCH.
WIRING AND CONDUIT OR MC CABLE SHALL BE REQUIRED FOR
ALL OUTLETS AND DEVICES. FOLLOW INDICATED CIRCUITS
NUMBERS AND PANEL DESIGNATION. OBTAIN PRIOR APPROVAL
OF ENGINEER FOR DEVIATIONS.
ALL 15A AND 20A, 115V AND 120V RECEPTACLES LOCATED IN
DWELLING UNITS SHALL BE TAMPER RESISTANT.
ALTHOUGH ALL BRANCH CIRCUIT WIRING IS NOT SHOWN, IT IS
THE INTENT OF THESE DOCUMENTS THAT A COMPLETE
BRANCH CIRCUIT WIRING SYSTEM BE INSTALLED.
ALL NEUTRALS SHALL BE FULL CAPACITY. THE USE OF SHARED
OR COMMON NEUTRALS IS PROHIBITED ON ALL ELECTRIC
WIRING.
PROVIDE CONTROL AND FIRE ALARM WIRE AS NECESSARY TO
INSTALL ALL SYSTEMS DEVICES AND PANELS FOR COMPLETE
SYSTEMS. FINAL CONNECTION TO PERMANTLY MOUNTED
EQUIPMENT IS PART OF THE ELECTRICAL SCOPE OF THIS
PROJECT.
PROVIDE TEL/DATA AND CAT5 AS INDICATED. REVIEW DATA,
SWITCH, RECEPTACLE, ETC LOCATIONS AND HEIGHTS WITH
OWNER PRIOR TO INSTALLATION.
ALL INTERIOR WIRING SHALL BE THHN/THWN IN METAL CONDUIT
OR MC CABLE. MAX OF 3'-0" OF FLEXIBLE CONDUIT MAY BE
USED FOR FINAL EQUIPMENT TERMINATIONS.
EXTERIOR WIRING IS TO BE THHN/THWN IN PVC CONDUIT. MAX.
OF 3'-0" OF FLEXIBLE METALLIC SEATITLE CONDUIT MAY BE
USED TO EXTERIOR EQUIPMENT.
TV AND TELEPHONE CABLING SHALL BE INSTALLED FROM
LOCATIONS INDICATED ON DRAWINGS TO DEMARC LOCATION.
COORDINATE FINAL DEMARC LOCATIONS w/ TV AND
TELEPHONE COMPANY.
GROUP AND TRAIN ALL TEL/DATA AND CABLE TV CABLE.
SUPPORT FROM STRUCTURE.
VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK WITH OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES WITH ALL OTHER
TRADES PRIOR TO INSTALLATION.
PERFORM ALL WORK IN ACCORDANCE WITH 2020 NEC.
COORDINATE FINAL FIXTURE LOCATIONS WITH OWNER AND
GENERAL CONTRACTOR PRIOR TO INSTALLATION OF CEILING.
FINAL COORDINATION OF SCOPE OF WORK , DIMENSIONS,
FIXTURE PLACEMENT, ROUTINGS, ETC IS THE RESPONSIBILITY
OF THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS
PRIOR TO BIDDING.
ELECTRICAL NOTES
DPHN1
DPLN1
DPHN1
(NEW)-1,3,5 DPHN1
(NEW)-2,4,6
DPLN1
(NEW)-1
DPLN1
(NEW)-2
DPLN1
(NEW)-3
BOILER E-STOP SWITCH
D
PL
N
(N
EW
)-7
D
PL
N
(N
EW
)-8
GLYCOL PUMP
VFD
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E101
ELECTRICAL POWER
PLAN
12 OCT 2026
TRT
BCM
26010.1
ISSUED FOR
CONSTRUCTION
WVDNR
WVDNR CHIEF
LOGAN REC CENTER
POOL HVAC
RENOVATION
N O
D
ES
C
R
IP
TI
O
N D
A
TE
1/8" = 1'-0"1
LEVEL 1 ELECTRICAL POWER PLAN
1/2" = 1'-0"2
LEVEL 1 ELECTRICAL POWER PLAN - ENLARGED
L3
DPHN1 DPLN1
E102
L3
DPHN1
DPLN1
SUBFEED PANEL "L3" TO DPLN1.
60A BREAKER, USE (4) #6 CU W/ #8 CU GRN.
1-1/2" CND
400-500 KCMIL cu W/ 1-#2 GR. CU, IN 4" EMT, WITH
COMPRESSION CONNECTORS. EXTEND TO MDP
AND INSTALL ON NEW 400A FEEDER BREAKER.
SEE SHEET E101 FOR LOCATION OF MDP
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES
OR SPECIAL CONDITIONS. ALL WALL MOUNTED DEVICES ARE
FINAL HEIGHT BY. ARCH.
WIRING AND CONDUIT OR MC CABLE SHALL BE REQUIRED FOR
ALL OUTLETS AND DEVICES. FOLLOW INDICATED CIRCUITS
NUMBERS AND PANEL DESIGNATION. OBTAIN PRIOR APPROVAL
OF ENGINEER FOR DEVIATIONS.
ALL 15A AND 20A, 115V AND 120V RECEPTACLES LOCATED IN
DWELLING UNITS SHALL BE TAMPER RESISTANT.
ALTHOUGH ALL BRANCH CIRCUIT WIRING IS NOT SHOWN, IT IS
THE INTENT OF THESE DOCUMENTS THAT A COMPLETE
BRANCH CIRCUIT WIRING SYSTEM BE INSTALLED.
ALL NEUTRALS SHALL BE FULL CAPACITY. THE USE OF SHARED
OR COMMON NEUTRALS IS PROHIBITED ON ALL ELECTRIC
WIRING.
PROVIDE CONTROL AND FIRE ALARM WIRE AS NECESSARY TO
INSTALL ALL SYSTEMS DEVICES AND PANELS FOR COMPLETE
SYSTEMS. FINAL CONNECTION TO PERMANTLY MOUNTED
EQUIPMENT IS PART OF THE ELECTRICAL SCOPE OF THIS
PROJECT.
PROVIDE TEL/DATA AND CAT5 AS INDICATED. REVIEW DATA,
SWITCH, RECEPTACLE, ETC LOCATIONS AND HEIGHTS WITH
OWNER PRIOR TO INSTALLATION.
ALL INTERIOR WIRING SHALL BE THHN/THWN IN METAL CONDUIT
OR MC CABLE. MAX OF 3'-0" OF FLEXIBLE CONDUIT MAY BE
USED FOR FINAL EQUIPMENT TERMINATIONS.
EXTERIOR WIRING IS TO BE THHN/THWN IN PVC CONDUIT. MAX.
OF 3'-0" OF FLEXIBLE METALLIC SEATITLE CONDUIT MAY BE
USED TO EXTERIOR EQUIPMENT.
TV AND TELEPHONE CABLING SHALL BE INSTALLED FROM
LOCATIONS INDICATED ON DRAWINGS TO DEMARC LOCATION.
COORDINATE FINAL DEMARC LOCATIONS w/ TV AND
TELEPHONE COMPANY.
GROUP AND TRAIN ALL TEL/DATA AND CABLE TV CABLE.
SUPPORT FROM STRUCTURE.
VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK WITH OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES WITH ALL OTHER
TRADES PRIOR TO INSTALLATION.
PERFORM ALL WORK IN ACCORDANCE WITH 2020 NEC.
COORDINATE FINAL FIXTURE LOCATIONS WITH OWNER AND
GENERAL CONTRACTOR PRIOR TO INSTALLATION OF CEILING.
FINAL COORDINATION OF SCOPE OF WORK , DIMENSIONS,
FIXTURE PLACEMENT, ROUTINGS, ETC IS THE RESPONSIBILITY
OF THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS
PRIOR TO BIDDING.
ELECTRICAL NOTES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E102
ELECTRICAL POWER
PLAN
12 OCT 2026
TRT
BCM
26010.1
ISSUED FOR
CONSTRUCTION
WVDNR
WVDNR CHIEF
LOGAN REC CENTER
POOL HVAC
RENOVATION
N O
D
ES
C
R
IP
TI
O
N D
A
TE
1/8" = 1'-0"1
LEVEL 2 ELECTRICAL POWER PLAN
3/8" = 1'-0"2
LEVEL 2 ELECTRICAL POWER PLAN - ENLARGED
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES
OR SPECIAL CONDITIONS. ALL WALL MOUNTED DEVICES ARE
FINAL HEIGHT BY. ARCH.
WIRING AND CONDUIT OR MC CABLE SHALL BE REQUIRED FOR
ALL OUTLETS AND DEVICES. FOLLOW INDICATED CIRCUITS
NUMBERS AND PANEL DESIGNATION. OBTAIN PRIOR APPROVAL
OF ENGINEER FOR DEVIATIONS.
ALL 15A AND 20A, 115V AND 120V RECEPTACLES LOCATED IN
DWELLING UNITS SHALL BE TAMPER RESISTANT.
ALTHOUGH ALL BRANCH CIRCUIT WIRING IS NOT SHOWN, IT IS
THE INTENT OF THESE DOCUMENTS THAT A COMPLETE
BRANCH CIRCUIT WIRING SYSTEM BE INSTALLED.
ALL NEUTRALS SHALL BE FULL CAPACITY. THE USE OF SHARED
OR COMMON NEUTRALS IS PROHIBITED ON ALL ELECTRIC
WIRING.
PROVIDE CONTROL AND FIRE ALARM WIRE AS NECESSARY TO
INSTALL ALL SYSTEMS DEVICES AND PANELS FOR COMPLETE
SYSTEMS. FINAL CONNECTION TO PERMANTLY MOUNTED
EQUIPMENT IS PART OF THE ELECTRICAL SCOPE OF THIS
PROJECT.
PROVIDE TEL/DATA AND CAT5 AS INDICATED. REVIEW DATA,
SWITCH, RECEPTACLE, ETC LOCATIONS AND HEIGHTS WITH
OWNER PRIOR TO INSTALLATION.
ALL INTERIOR WIRING SHALL BE THHN/THWN IN METAL CONDUIT
OR MC CABLE. MAX OF 3'-0" OF FLEXIBLE CONDUIT MAY BE
USED FOR FINAL EQUIPMENT TERMINATIONS.
EXTERIOR WIRING IS TO BE THHN/THWN IN PVC CONDUIT. MAX.
OF 3'-0" OF FLEXIBLE METALLIC SEATITLE CONDUIT MAY BE
USED TO EXTERIOR EQUIPMENT.
TV AND TELEPHONE CABLING SHALL BE INSTALLED FROM
LOCATIONS INDICATED ON DRAWINGS TO DEMARC LOCATION.
COORDINATE FINAL DEMARC LOCATIONS w/ TV AND
TELEPHONE COMPANY.
GROUP AND TRAIN ALL TEL/DATA AND CABLE TV CABLE.
SUPPORT FROM STRUCTURE.
VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK WITH OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES WITH ALL OTHER
TRADES PRIOR TO INSTALLATION.
PERFORM ALL WORK IN ACCORDANCE WITH 2020 NEC.
COORDINATE FINAL FIXTURE LOCATIONS WITH OWNER AND
GENERAL CONTRACTOR PRIOR TO INSTALLATION OF CEILING.
FINAL COORDINATION OF SCOPE OF WORK , DIMENSIONS,
FIXTURE PLACEMENT, ROUTINGS, ETC IS THE RESPONSIBILITY
OF THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS
PRIOR TO BIDDING.
ELECTRICAL NOTES
F1 F1 F1
DPLN1
(NEW)-9
E103
F2 F2 F2
F1 F1 F1 E1
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E103
ELECTRICAL
LIGHTING PLAN
12 OCT 2026
TRT
BCM
26010.1
ISSUED FOR
CONSTRUCTION
WVDNR
WVDNR CHIEF
LOGAN REC CENTER
POOL HVAC
RENOVATION
N O
D
ES
C
R
IP
TI
O
N D
A
TE
1/4" = 1'-0"1
LEVEL 1 ELECTRICAL LIGHTING PLAN
1/2" = 1'-0"2
ENLARGED LEVEL 1 ELECTRICAL LIGHTING PLAN
PA OFFICE:
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E601
ELECTRICAL
SCHEDULES &
DETAILS
12 OCT 2026
TRT
BCM
26010.1
ISSUED FOR
CONSTRUCTION
WVDNR
WVDNR CHIEF
LOGAN REC CENTER
POOL HVAC
RENOVATION
N O
D
ES
C
R
IP
TI
O
N D
A
TE
Notes:
DPLN1 (NEW)-29 DPLN1 (NEW)-30
DPLN1 (NEW)-27 DPLN1 (NEW)-28
DPLN1 (NEW)-25 DPLN1 (NEW)-26
DPLN1 (NEW)-23 DPLN1 (NEW)-24
DPLN1 (NEW)-21 DPLN1 (NEW)-22
DPLN1 (NEW)-19 DPLN1 (NEW)-20
DPLN1 (NEW)-17 DPLN1 (NEW)-18
DPLN1 (NEW)-15 DPLN1 (NEW)-16
DPLN1 (NEW)-13 DPLN1 (NEW)-14
DPLN1 (NEW)-11 DPLN1 (NEW)-12
DPLN1 (NEW)-9 LTG BOILER ROOM 20 A 1 ... DPLN1 (NEW)-10
DPLN1 (NEW)-7 CONVENIENCE RCP BOILER... 20 A 1 ... 1 20 A RCP POOL SIDE DPLN1 (NEW)-8
DPLN1 (NEW)-5 SPARE 20 A 1 ... 1 20 A SPARE DPLN1 (NEW)-6
DPLN1 (NEW)-3 B-3 20 A 1 ... 1 20 A SPARE DPLN1 (NEW)-4
DPLN1 (NEW)-1 B-1 20 A 1 ... 1 20 A B-2 DPLN1 (NEW)-2
CKTCKT Circuit DescriptionCircuit Description TripTrip PolesPoles PolesPoles TripTrip Circuit DescriptionCircuit Description CKTCKT
ENCLOSURE:ENCLOSURE: NEMA 1 Indoor MAIN TYPE:MAIN TYPE: MLO
WIRES:WIRES: 4 MAIN:MAIN: 60 A
VOLTS:VOLTS: 120/208 Wye PHASES:PHASES: 3
Branch Panel:Branch Panel: DPLN1 (NEW)DPLN1 (NEW)
Notes:
41 SPARE 20 A 1 ... 42
39 SPARE 20 A 1 ... 40
37 SPARE 20 A 1 ...
3 60 A SUBFEED DPLN1
35 ... 1 20 A SPARE 36
33 - 20 A 2 ... 1 20 A SPARE 34
31 SPARE 20 A 1 ... 1 20 A SPARE 32
29 CEILING FANS #7,#8 20 A 1 ... 30
27 TV YOGA 20 A 1 ... 2 20 A - 28
25 CEILING FANS #3,#4 20 A 1 ... 1 20 A - 26
23 LOBBY FANS #1,#2 20 A 1 ... 1 20 A TREADMILL 24
21 - 20 A 1 ... 1 20 A TREADMILL 22
19 - 20 A 1 ... 1 20 A BATHROOM EXHAUST FAN 20
17 - 20 A 1 ... 18
15 YOGA ROOM LTG 20 A 1 ... 16
13 TV RCP 20 A 1 ...
3 20 A DH-2
11 EXERCISE RM RCP 20 A 1 ... 1 20 A EXERCISE RM RCP 12
9 EXERCISE RM RCP 20 A 1 ... 1 20 A EXERCISE RM RCP 10
7 SPARE 20 A 1 ... 1 20 A FANS YOGA 8
5 EXERCISE EQUIPMENT - TREAD 20 A 1 ... 1 20 A SPIN ROOM TV/FANS 6
3 EXERCISE EQUIPMENT 20 A 1 ... 1 20 A EXERCISE EQUIPMENT 4
1 EXERCISE EQUIPMENT 20 A 1 ... 1 20 A EXERCISE EQUIPMENT... 2
CKTCKT Circuit DescriptionCircuit Description TripTrip PolesPoles PolesPoles TripTrip Circuit DescriptionCircuit Description CKTCKT
ENCLOSURE:ENCLOSURE: NEMA 1 Indoor MAIN TYPE:MAIN TYPE: MLO
WIRES:WIRES: 4 MAIN:MAIN: 100 A
VOLTS:VOLTS: 120/208 Wye PHASES:PHASES: 3
Branch Panel:Branch Panel: L3(EXIST.)L3(EXIST.)
Notes:
59 60 57 58 55 56 53 54 51 52 49 50 47 ... 48 45 ... 46
SCOUR BLOWER 15 A 3
3 60 A SPARE
41 ... 42 39 ... 40
ASR PUMP 15 A 3
3 40 A RECIRC PUMP
35 ... 36 33 ... 34
ELEVATOR DISCONNECT SWITCH 60 A 3
3 400 A NEW SUBFEED DPHN1
29 ... 30 27 ... 28
HVAC UNIT PU-3 40 A 3
3 90 A L4 SUBFEED
23 ... 24 21 ... 22
HVAC UNIT PU-1 90 A 3
3 90 A HVAC UNIT PU-2
17 ... 18 15 ... 16
PANEL H2 100 A 3
3 40 A DUCT HEATER
11 ... 12 9 ... 10
SEWAGE LIFT STATION 70 A 3
3 150 A PANEL H1
5 ... 6 3 ... 4
L1 SUBFEED 90 A 3
3 90 A L2 SUBFEED
CKTCKT Circuit DescriptionCircuit Description TripTrip PolesPoles
AA BB CC
PolesPoles TripTrip Circuit DescriptionCircuit Description CKTCKT
ENCLOSURE:ENCLOSURE: NEMA 1 Indoor MAIN TYPE:MAIN TYPE: MCB
WIRES:WIRES: 4 MAIN:MAIN: 1200 A
VOLTS:VOLTS: 480/277 Wye PHASES:PHASES: 3
Branch Panel:Branch Panel: MDP(EXIST.)MDP(EXIST.)
DISCONNECT SWITCH SCHEDULE
TAG SERVES POLES VOLTS
RATING
NEMA ENCLOSURE TYPE
SWITCH FUSE
SW-1 EF-1 AND EF-2 3 480 V 30 A 15 A TYPE3R Fusible
LIGHT FIXTURE SCHEDULE
TAG MFR MODEL LUMENS COLOR TEMP VOLTS WATTS DESCRIPTION
F1 LITHONIA ZL1D L48 3000LM FST MVOLT 3500K 80CRI 4,456 3,500 K UNV 30 W 4' LED STRIP LIGHT F2 5,500 4,000 K 70 W
VARIABLE FREQUENCY DRIVE SCHEDULE
TAG SERVES POLES VOLTS ENCLOSURE STARTER SIZE MOTOR HP DESCRIPTION
VFD-1 EF-1 3 208 NEMA 1 Indoor 0 2 HVAC RATED VFD WITH INTEGRAL DISCONNECT AND DIGITAL OVERLOAD VFD-2 EF-2 3 208 NEMA 1 Indoor 0 2 HVAC RATED VFD WITH INTEGRAL DISCONNECT AND DIGITAL OVERLOAD
Notes:
DPHN1 (NEW)-35 DPHN1 (NEW)-36
DPHN1 (NEW)-33 DPHN1 (NEW)-34
DPHN1 (NEW)-31 DPHN1 (NEW)-32
DPHN1 (NEW)-29 ... DPHN1 (NEW)-30
DPHN1 (NEW)-27 ... DPHN1 (NEW)-28
DPHN1 (NEW)-25
P-8 15 A 3
3 15 A P-9
DPHN1 (NEW)-26
DPHN1 (NEW)-23 ... DPHN1 (NEW)-24
DPHN1 (NEW)-21 ... DPHN1 (NEW)-22
DPHN1 (NEW)-19
EF-1 15 A 3
3 15 A EF-2
DPHN1 (NEW)-20
DPHN1 (NEW)-17 ... DPHN1 (NEW)-18
DPHN1 (NEW)-15 ... DPHN1 (NEW)-16
DPHN1 (NEW)-13
P-6 15 A 3
3 15 A P-7
DPHN1 (NEW)-14
DPHN1 (NEW)-11 ... DPHN1 (NEW)-12
DPHN1 (NEW)-9 ... DPHN1 (NEW)-10
DPHN1 (NEW)-7
AHU-1 60 A 3
3 150 A CH-1
DPHN1 (NEW)-8
DPHN1 (NEW)-5 ... DPHN1 (NEW)-6
DPHN1 (NEW)-3 ... DPHN1 (NEW)-4
DPHN1 (NEW)-1
P-4 15 A 3
3 15 A P-5
DPHN1 (NEW)-2
CKTCKT Circuit DescriptionCircuit Description TripTrip PolesPoles PolesPoles TripTrip Circuit DescriptionCircuit Description CKTCKT
ENCLOSURE:ENCLOSURE: NEMA 1 Indoor MAIN TYPE:MAIN TYPE: MCB
WIRES:WIRES: 4 MAIN:MAIN: 400 A
VOLTS:VOLTS: 480/277 Wye PHASES:PHASES: 3
Branch Panel:Branch Panel: DPHN1 (NEW)DPHN1 (NEW)
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL
LABOR REQUIRED TO INSTALL, COMPLETE, AND OPERATE AS
INDICATED ON THE DRAWINGS, SPECIFICATIONS, AND
REQUIRED BY CODE.
SEPARATE BALANCE DAMPERS WILL BE INSTALLED AT ALL
TAKE-OFFS FROM MAIN DUCTS. FIRE DAMPERS WILL BE
INSTALLED AT LOCATIONS SHOWN OR WHERE ANY DUCT
PENETRATES A FIRE RATED WALL. REFER TO ARCHITECTURAL
SHEETS FOR RATED WALLS. FIRE DAMPERS ARE TO MATCH THE
RATING OF THE WALL OR CEILING BEING PENETRATED.
ALL DUCT TAKE-OFFS AND TRANSITIONS WILL BE TAPERED.
ELBOWS AND TURNS SHALL BE CONSTRUCTED w/ A SMOOTH
RADIUSED FITTING MIN 1.5 TIMES THE WIDTH OF THE DUCT.
TURNING VANES ARE NOT PERMITTED, UNLESS APPROVED BY
ENGINEER OR INDICATED ON DRAWINGS.
CERTAIN ITEMS SUCH AS RISERS AND DROPS IN DUCTWORK,
ACCESS DOORS, VOLUME DAMPERS, ETC. ARE INDICATED ON
THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY FOR A
SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE
INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR
THOSE ITEMS.
ALL DUCTWORK IS TO BE EXTERNALLY INSULATED. INTERIOR
MOUNTED DUCTWORK SHALL HAVE FOIL FACED 1-1/2 TO 2"
FIBERGLASS INSULATION AND SEALED w/ FIBERGLASS
REINFORCED FOIL TAPE.
CONSTRUCT ALL DUCTWORK PER SMACNA STANDARDS FOR
LOW PRESSURE DUCTWORK (2.0" STATIC). ALL JOINTS ARE TO
BE SEALED w/ MASTIC.
PROVIDE AIR LOUVERS w/ GRAVITY BACKDRAFT DAMPERS. ALL
EXTERIOR LOUVERS WILL HAVE 60% MIN. OPEN AREA AND BUG
SCREENS. INSTALL ALL w/ BIRD SCREEN. COLORS BY OWNER/ARCHITECT. COORDINATE LOCATIONS w/ GENERAL
CONTRACTOR.
PROVIDE FULLY ADHERED VELOCITY DUCT LINER FROM UNIT
DISCHARGE AND RETURN TO 10'-0" BEYOND UNIT. PROVIDE
NOSING AT THE BEGINNING AND END OF THE DUCT LINER.
UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM
THERMOSTATS AND HUMIDISTATS AT 5'-0" ABOVE FINISHED
FLOOR. FINAL THERMOSTAT LOCATION BY OWNER/ARCHITECT.
ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS.
ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS,
ARE INTERNAL CLEAR DIMENSIONS AND DUCT SIZE SHALL BE
INCREASED TO COMPENSATE FOR DUCT LINING WHERE
APPLICABLE.
COORDINATE DIFFUSERS, REGISTER, AND GRILLE LOCATIONS
w/ ARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING, AND
OTHER CEILING ITEMS. MAKE MINOR DUCT MODIFICATIONS TO
SUIT.
LOCATE ALL MECHANICAL EQUIPMENT FOR UN-OBSTRUCTED
ACCESS TO UNIT ACCESS PANELS, CONTROL, AND VALVING.
PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS
CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER
EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION.
OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO
THE UNDERSIDE OF THE STRUCTURAL, WITH SPACE FOR
INSULATION.
RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 3'-0". FLEXIBLE
DUCT IS TO BE USED FOR FINAL CONNECTIONS TO GRILLES
AND DIFFUSER ONLY.
ALL DUCTWORK SHALL BE COORDINATED w/ ALL TRADES
INVOLVED. OFFSETS IN DUCTS, INCLUDING DIVIDED DUCTS AND
TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE PROVIDED AT
NO ADDITIONAL COST TO THE OWNER.
PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS
FOR ALL SMOKE DETECTORS, FIRE DAMPERS, SMOKE
DAMPERS, HUMIDIFIERS, COILS AND OTHER ITEMS LOCATED IN
DUCTWORK WHICH REQUIRE SERVICE OR INSPECTION.
SEE SPEC FOR DUCTWORK GAUGES, BRACING, HANGERS, AND
OTHER REQUIREMENTS.
EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY.
DETAILED DESCRIPTIONS ARE PROVIDED IN THE
ARCHITECTURAL SPECIFICATIONS. LOUVER SIZES, LOCATIONS,
MOUNTING, AND DETAILS SHALL BE COORDINATED w/ OTHER
TRADES INVOLVED.
PERFORM WORK IN ACCORDANCE w/ CURRENT INTERNATIONAL
MECHANICAL CODE, FUEL GAS CODE, ASHRAE, SMACNA, STATE,
AND LOCAL CODES AND REQUIREMENTS.
VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK w/ OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES w/ ALL OTHER
TRADES PRIOR TO INSTALLATION. FINAL COORDINATION OF
SCOPE OF WORK, DIMENSIONS, FIXTURE PLACEMENT, ROUTING
ETC. IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR
AND ALL SUB-CONTRACTORS PRIOR TO BIDDING.
MECHANICAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL
LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE
PIPING SYSTEMS AS INDICATED ON THE DRAWINGS,
SPECIFICATIONS, AND REQUIRED BY CODE.
MAINTAIN A MIN. OF 3'-0" OF GROUND COVER OVER ALL
UNDERGROUND HAVC PIPING, UNLESS OTHERWISE NOTED.
NATURAL GAS / LP PIPING IS TO BE P40 STEEL w/ BLACK IRON
THREADED OR MECHANICALLY PRESSED FITTINGS.
MECHANICALLY PRESSED FITTINGS MUST BE LISTED FOR
NATURAL GAS OR LP PIPING. PROVIDE WELDED GAS PIPING BY
SIZE AS REQUIRED BY FUEL GAS CODE.
PROVIDE BALL VALVE STOPS AT ALL FIXTURES. PROVIDE
UNIONS, DIRT LEGS, AND REGULATORS ON ALL EQUIPMENT.
INSTALL APPLIANCE REGLUALTORS ON ALL NATURAL GAS / LP
EQUIPMENT. VENT REGULATORS PER THE FUEL GAS CODE &
REGULATOR MFR'S REQUIREMENTS.
COORDINATE ALL STUB-UPS AND FIELD ADJUST LOCATIONS FOR
COORDINATION AS NECESSARY. AVOID EXCESSIVE ADDITIONAL
PIPE FITTINGS.
PROVIDE AN AIR VENT AT THE HIGH POINT OF EACH DROP IN
THE HEATING WATER, CHILLED WATER, AND OTHER CLOSED
WATER PIPING SYSTEMS. ALL PIPING SHALL GRADE TO LOW
POINTS. PROVIDE HOSE END DRAIN VALVES AT BOTTOM OF
RISERS AND LOW POINTS.
UNLESS OTHERWISE NOTED, ALL PIPING IS TO OVERHEAD,
TIGHT TO UNDERSIDE OF STRUCTURE OR DECK w/ SPACE FOR
INSULATION.
INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS,
TRAPS, FLANGES, ETC. ARE ACCESSIBLE.
ALL BALANCING VALVES AND BUTTERFLY VALVES SHALL BE
PROVIDED w/ POSITION INDICATORS AND MANUAL ADJUSTABLE
STOPS.
ALL VALVES (EXCEPT CONTROL VALVES) AND STRAINERS SHALL
BE FULL SIZE OF PIPE BEFORE REDUCING SIZE TO MAKE
CONNECTIONS TO EQUIPMENT AND CONTROLS.
UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE
OF EQUIPMENT, IN BYPASSES, AND IN LONG PIPING RUNS O
PERMIT DISASSEMBLY FOR ALTERATIONS AND REPAIRS.
ALL PIPING SHALL CLEAR DOORS AND WINDOWS. ALL VALVES
SHALL BE ADJUSTED FOR SMOOTH AND EASY OPERATION.
ALL PIPING WORK SHALL BE COORDINATED w/ ALL TRADES
INVOLVED. OFFSETS IN PIPING AROUND OBSTRUCTIONS SHALL
BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS
CONNECTED TO PUMPS, CHILLERS, COOLING TOWERS, AND
OTHER EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION
EXCEPT WATER COILS.
ALL WORK TO MEET REQUIREMENTS OF CURRENT
INTERNATIONAL PLUMBING CODE, INTERNATIONAL MECHANICAL
CODE, APPLICABLE LOCAL CODES, LOCAL UTILITY
REQUIREMENTS, AND THE INTERNATIONAL FUEL GAS CODE.
FINAL COORDINATION OF SCOPE OF WORK, DIMENSIONS,
FIXTURE PLACEMENT, ROUTING, ECT. IS THE RESPONSIBILITY OF
THE PRIME CONTRACTOR AND ALL SUB-CONTRACTORS PRIOR
TO BIDDING.
PIPING NOTES
--------------------SYMBOLS------------------------------------------------------------------------
# NUMBER
& AND
º DEGREES
ºF DEGREES FAHRENHEIT
--------------------A------------------------------------------------------------------------------------
AAV AUTOMATIC AIR VENT
ABV ABOVE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
APPROX APPROXIMATELY
AUX AUXILIARY
AVG AVERAGE
---------------B----------------------------------------------------------------------------------------
BFV BUTTERFLY VALVE
BH BASEBOARD HEATER
BHP BRAKE HORESPOWER
BLR BOILER
BTUH BRITISH THERMAL UNIT PER HOUR
BV BALL VALVE
---------------C---------------------------------------------------------------------------------------
CA COMPRESSED AIR
CAP CAPACITY
CFM CUBIC FEET PER MINUTE
CHKV CHECK VALVE
CIRC CIRCULATING
CI CAST IRON
CKT CIRCUIT
CMU CONCRETE MASONARY UNIT
C/O CLEAN OUT
CON CONDENSATE
CONT CONTINUATION
CT COOLING TOWER
CU CONDENSING UNIT
---------------D----------------------------------------------------------------------
DIA DIAMETER
DWG DRAWING
DWH DOMESTIC WATER HEATER
----------------E----------------------------------------------------------------------
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE(ºF)
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EFF EFFICIENCY
ELEC ELECTRIC
ELEV ELEVATION
EQUIP EQUIPMENT
ESP EXTERNAL STATIC PRESSURE
EXH EXHAUST
EXIST EXISTING
EWT ENTERING WATER TEMPERATUR(ºF)
----------------F----------------------------------------------------------------------
ºF FAHRENHEIT
FCU FAN COIL UNIT
FD FIRE DAMPER/FLOOR DRAIN
FLA FULL LOAD AMPS
FLR FLOOR
FO FLAT OVAL
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FEET
----------------G----------------------------------------------------------------------
GAS NATURAL GAS
GALV GALVANIZED
GA GAUGE
GC GENERAL CONTRACTOR
GLV GLOBE VALVE
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GV GATE VALVE
----------------H----------------------------------------------------------------------
HCWL HYDRONIC CHILLED WATER LOOP
HCWR HYDRONIC CHILLED WATER RETURN
HCWS HYDRONIC CHILLED WATER SUPPLY
HHWL HYDRONIC HOT WATER LOOP
HHWR HYDRONIC HOT WATER RETURN
HHWS HYDRONIC HOT WATER SUPPLY
HORIZ HORIZONTAL
HP HORSEPOWER/HEAT PUMP
HR HOUR
HTG HEATING
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
HZ HERTZ
----------------I----------------------------------------------------------------------
ID INSIDE DIAMETER
IN INCHES
INV INVERT
----------------J----------------------------------------------------------------------
JB JUNCTION BOX
----------------K----------------------------------------------------------------------
KW KILOWATT
KWH KILOWATT HOUR
----------------L----------------------------------------------------------------------
LAT LEAVING AIR TEMPERATURE(ºF)
LBS POUNDS
LBS/HR POUNDS PER HOUR
LF LINEAR FEET
LP LIQUID PROPANE
LV LOUVER
LVG LEAVING
LWT LEAVING WATER TEMPERATURE(ºF)
----------------M----------------------------------------------------------------------
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIUM
MBH THOUSAND BTUH
MC MECHANICAL CONTRACTOR
MCC MOTOR CONTROL CENTER
MECH MECHANICAL
MFG MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MS MINI-SPLIT SYSTEM
----------------N----------------------------------------------------------------------
N/A NOT APPLICABLE
NC NORMALLY CLOSED; NOISE CRITERIA
NEC NATIONAL ELECTRICAL CODE
NEG NEGATIVE
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NO NORMALLY OPEN
NTS NOT TO SCALE
----------------O----------------------------------------------------------------------
OA OUTSIDE AIR
OC ON CENTER
OCC OCCUPANCY
OD OUTSIDE DIAMETER
OSHA OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION
OSV OIL SAFETY VALVE
OZ OUNCE
----------------P----------------------------------------------------------------------
P PUMP
PC PLUMBING CONTRACTOR
PNL PANEL
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAGE
PTAC PACKAGED TERMINAL AIR CONDITIONER
----------------Q----------------------------------------------------------------------
QTY QUANTITY
----------------R----------------------------------------------------------------------
RA RETURN AIR
RAD RADIATOR
RCP RADIANT CEILING PANEL
REFRIG REFRIGERANT
REQD REQUIRED
REV REVISION
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
RV RELIEF VALVE
----------------S----------------------------------------------------------------------
SA SUPPLY AIR
SCH SCHEDULE
SD SMOKE DAMPER
SENS SENSIBLE
SP STATIC PRESSURE (INCHES OF WATER)
SPEC SPECIFICATION
SQ SQUARE
SQFT SQUARE FOOT
SS STAINLESS STEEL
STD STANDARD
STRUCT STRUCTURAL
----------------T----------------------------------------------------------------------
T THERMOSTATE
TA TRANSFER AIR
TCV TEMPERATURE CONTROL VALVE
TDV TRIPLE DUTY VALVE
TEMP TEMPERATURE
TOT TOTAL
TRANS TRANSITION
TSTAT THERMOSTAT
TV TURNING VANES
TYP TYPICAL
----------------U----------------------------------------------------------------------
UH UNIT HEATER
UV UNIT VENTILATOR
----------------V----------------------------------------------------------------------
VOLTS VOLTAGE
VA VOLT AMPERES
VAC VACUUM
VAV VARIABLE AIR VOLUME
VEL VELOCITY
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
VOLTS VOLTAGE
VRF VARIABLE REFRIGERANT FLOW
VVT VARIABLE VOLUME AND TEMPERATURE
----------------W----------------------------------------------------------------------
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
WT WEIGHT
----------------Z----------------------------------------------------------------------
Z ZONE
ZCV ZONE CONTROL VALVE
A. SPACE SET POINTS:
1. GENERAL SPACES SETPOINTS
a. COOLING: 73°F, 55% RH
b. HEATING: 70°F
B. OUTSIDE AIR CONDITIONS
1. SUMMER: 91°F WB, 72°F DB
2. WINTER: 2°F DB, 0°F WB
C. BUILDING ENVELOPE
1. WALLS: R-19
2. ROOF: R-30
3. WINDOWS: 0.588 U-VALUE
4. DOORS: 0.30 U-VALUE W/ 0.588 U-VALUE GLASS
D. KITCHEN EXHAUST / MAKE UP AIR
1. KITCHEN HOOD:
a. WALL MOUNT CANOPY
b. HEAVY DUTY - 350 CFM/FT
c. CLASS I W/ FIRE SUPPRESSION
2. MAKE UP AIR UNIT:
a. 80% OF KITCHEN EXHAUST CFM
E. DISHWASHER EXHAUST
1. DISHWASHER HOOD:
a. WALL MOUNT CANOPY
b. 200 CFM/FT
c. CLASS II (NO SUPPRESSION)
F. RESTROOM EXHAUST
1. 50 CFM PER WATER CLOSET / URINAL
G. DEMAND CONTROL VENTILATION
1. CO2 BASED UPON SPACE SENSORS
2. SEE RTU SCHEDULES FOR MAX & MIN VENTILATION RATES.
HVAC BASIS OF DESIGN
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
M000
MECHANICAL
ABBREVIATIONS
12 OCT 2026
TRT
BCM
26010.1
ISSUED FOR
CONSTRUCTION
WVDNR
WVDNR CHIEF
LOGAN REC CENTER
POOL HVAC
RENOVATION
MECHANICAL ABBREVIATIONS
ANNOTATION STYLE DUCTWORK SHAPE
24" x 12" RECTANGULAR
24" ø ROUND
24" / 12" FLAT OVAL
DUCTWORK SHAPE LEGEND
DUCT SYSTEM LEGEND
ABBREVIATION SYSTEM NAME
EA EXHAUST AIR
OA OUTDOOR AIR
RA RETURN AIR
SA SUPPLY AIR
MECH PIPING SYSTEM LEGEND
ABBREVIATION SYSTEM TYPE
HCWR CHILLED WATER RETURN
HCWS CHILLED WATER SUPPLY
HHWL HEATING WATER LOOP
HHWR HEATING WATER RETURN
HHWS HEATING WATER SUPPLY
N O
D
ES
C
R
IP
TI
O
N D
A
TE
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL
LABOR REQUIRED TO INSTALL, COMPLETE, AND OPERATE AS
INDICATED ON THE DRAWINGS, SPECIFICATIONS, AND
REQUIRED BY CODE.
SEPARATE BALANCE DAMPERS WILL BE INSTALLED AT ALL
TAKE-OFFS FROM MAIN DUCTS. FIRE DAMPERS WILL BE
INSTALLED AT LOCATIONS SHOWN OR WHERE ANY DUCT
PENETRATES A FIRE RATED WALL. REFER TO ARCHITECTURAL
SHEETS FOR RATED WALLS. FIRE DAMPERS ARE TO MATCH THE
RATING OF THE WALL OR CEILING BEING PENETRATED.
ALL DUCT TAKE-OFFS AND TRANSITIONS WILL BE TAPERED.
ELBOWS AND TURNS SHALL BE CONSTRUCTED w/ A SMOOTH
RADIUSED FITTING MIN 1.5 TIMES THE WIDTH OF THE DUCT.
TURNING VANES ARE NOT PERMITTED, UNLESS APPROVED BY
ENGINEER OR INDICATED ON DRAWINGS.
CERTAIN ITEMS SUCH AS RISERS AND DROPS IN DUCTWORK,
ACCESS DOORS, VOLUME DAMPERS, ETC. ARE INDICATED ON
THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY FOR A
SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE
INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR
THOSE ITEMS.
ALL DUCTWORK IS TO BE EXTERNALLY INSULATED. INTERIOR
MOUNTED DUCTWORK SHALL HAVE FOIL FACED 1-1/2 TO 2"
FIBERGLASS INSULATION AND SEALED w/ FIBERGLASS
REINFORCED FOIL TAPE.
CONSTRUCT ALL DUCTWORK PER SMACNA STANDARDS FOR
LOW PRESSURE DUCTWORK (2.0" STATIC). ALL JOINTS ARE TO
BE SEALED w/ MASTIC.
PROVIDE AIR LOUVERS w/ GRAVITY BACKDRAFT DAMPERS. ALL
EXTERIOR LOUVERS WILL HAVE 60% MIN. OPEN AREA AND BUG
SCREENS. INSTALL ALL w/ BIRD SCREEN. COLORS BY OWNER/ARCHITECT. COORDINATE LOCATIONS w/ GENERAL
CONTRACTOR.
PROVIDE FULLY ADHERED VELOCITY DUCT LINER FROM UNIT
DISCHARGE AND RETURN TO 10'-0" BEYOND UNIT. PROVIDE
NOSING AT THE BEGINNING AND END OF THE DUCT LINER.
UNLESS OTHERWISE SHOWN, LOCATE…