Project Drawings.pdf
PDF 7 MB Posted
- Solicitation number
- 36C24921R0050
About this file
This document package includes construction drawings and details for repairing rooftops on two buildings at a Department of Veterans Affairs medical center, along with the corresponding federal contract opportunity on FedBizOpps.
The drawings show the scope of work involves applying a new fluid-applied membrane system over 101,500 square feet of roof area on Buildings 1 and 1A. Key tasks include installing new roof drains, walkways, and flashing as needed, repairing water blisters, and removing unused roof curbs. The opportunity on FedBizOpps is for project #596A4-20-101 to repair the roofs under solicitation #36C24921R0050 issued by the VA Veterans Health Administration VISN 9. The deadline to respond has passed, and award is pending. The package provides contractors with the information required to understand the project requirements and prepare a bid to the VA.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24921R0050 0004.docx | DOCX document | |
| Roof Composition Data.pdf | ||
| N1197462 - Repair Building 1 and 1 A Roofs - Lexington VA Medical Center - Asbestos Survey Report 062920.pdf | ||
| 36C24921R0050 0003.docx | DOCX document | |
| Solicitation Questions _ Answers - 36C24921R0050.pdf | ||
| 36C24921R0050 0002.docx | DOCX document | |
| Site Visit Sign-In.pdf | ||
| 36C24921R0050 0001.docx | DOCX document | |
| Past Performance Questionnaire.pdf | ||
| Wage Determination KY20210090 01-15-2021.pdf | ||
| 36C24921R0050_1.docx | DOCX document | |
| Statement of Work.pdf | ||
| Project Specifications.pdf | ||
| Pricing Schedule.xlsx | XLSX spreadsheet |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G E N E R A L N O T E S
A. THE GENERAL CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS
AND FIELD CONDITIONS PRIOR TO WORK. IF PROVIDED, THE GENERAL
CONTRACTOR SHALL CAREFULLY EXAMINE EXISTING BUILDING
DOCUMENTS. THE CONTRACTOR SHALL BRING ANY DISCREPANCIES TO
THE IMMEDIATE ATTENTION OF THE ARCHITECT AND COR.
B. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF
EXISTING ITEMS TO REMAIN DURING DEMOLITION AND CONSTRUCTION.
C. UNLESS OTHERWISE NOTED, THE GENERAL CONTRACTOR IS
RESPONSIBLE FOR VERIFYING ALL EXISTING SALVAGED STOCK BEFORE
ORDERING NEW MATERIAL.
D. NEW HOLES IN EXISTING ROOF STRUCTURES FOR NEW WORK MUST BE
COORDINATED WITH THE EXISTING STRUCTURE SO THAT CRITICAL
STRUCTURAL MEMBERS ARE NOT DAMAGED.
E. PENETRATIONS THROUGH EXISTING FIRE RATED ROOF ASSEMBLIES MUST
BE PROPERLY CLOSED AND FIRE SAFE'D TO ACHIEVE THE PROPER FIRE
RATING BY THE END OF CONSTRUCTION OPERATIONS FOR EACH DAY.
F. ALL DEMOLITION AND CONSTRUCTION ACTIVITIES SHALL BE COORDINATED
WITH THE COR TO MINIMIZE DISRUPTIONS OF NORMAL FUNCTIONS OF THE
VAMC.
G. IF CONSTRUCTION NOISE IS ANTICIPATED, SUBMIT A WRITTEN REQUEST TO
THE COR FOR THE SCHEDULED TIME OF THE CONSTRUCTION ACTIVITIES.
NO WORK SHALL BE DONE WITHOUT THE WRITTEN APPROVAL OF THE
COR. THE COR RESERVES THE RIGHT TO DISCONTINUE NOISY
CONSTRUCTION AT ANY TIME. NO RADIOS SHALL BE PERMITTED AT ANY
TIME IN WORK AREAS ADJACENT TO OCCUPIED SPACES.
H. ALL EXISTING SERVICES AND UTILITIES SHALL BE MAINTAINED TO
ADJACENT AREAS THAT ARE IN OPERATION AND SERVED BY THEM.
COORDINATE ALL DISRUPTIONS OR DISCONTINUATIONS OF UTILITIES AND
SERVICES WITH THE COR. NO SHUT DOWN OF EXISTING SERVICES IS
ALLOWED TO OCCUR UNTIL RECEIVING THE COR'S WRITTEN APPROVAL OF
THE SHUT DOWN SCHEDULE. PROVIDE TEMPORARY SERVICES AND/OR
UTILITIES DURING INTERRUPTIONS AS REQUIRED AND APPROVED BY THE
COR.
I. THE GENERAL CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS
TO PREVENT DAMAGE TO THE VA'S OCCUPIED AREAS ADJACENT TO NEW
CONSTRUCTION OR OCCUPIED AREAS WHERE VARIOUS SYSTEM
CONNECTIONS OR EXTENSIONS ARE REQUIRED. IN THESE AREAS, THE
GENERAL CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY LACK
OF SUFFICIENT PROTECTION FROM THE WEATHER AND FROM THE
RESULTS OF ALL CONSTRUCTION ACTIVITY INCLUDING BUT NOT LIMITED
TO DUST AND WATER.
J. THE GENERAL CONTRACTOR SHALL RECEIVE WRITTEN APPROVAL FROM
THE COR BEFORE USING OPEN FLAMES, WELDING RODS AND TORCHES.
THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL MEANS AND
METHODS TO PROHIBIT THE MIGRATION OF SMOKE AND OTHER PRODUCTS
OF COMBUSTION INTO OCCUPIED AREAS OF THE EXISTING BUILDING AND
FOR OBTAINING ALL REQUIRED PERMITS RELATED TO HOT WORK.
K. THE CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT FOR ITEMS NOT
DEMOLISHED OR REMOVED AS REQUIRED UNTIL PERMANENT SUPPORT IS
PROVIDED IN THE FINAL CONSTRUCTION.
L. DO NOT OVERLOAD THE EXISTING BUILDING STRUCTURE. MAINTAIN THE
STRUCTURAL INTEGRITY OF ALL STRUCTURAL FRAMING MEMBERS AND
SYSTEMS AT ALL TIMES.
M. ALL DEMOLISHED MATERIAL, EXCEPT MATERIAL THAT IS LISTED OR
MARKED BY THE ARCHITECT OR THE COR FOR RETENTION, SHALL BECOME
THE PROPERTY OF THE CONTRACTOR AND IT SHALL BE DISPOSED OF. NO
DEBRIS RESULTING FROM WORK SHALL BE LEFT IN THE CONSTRUCTION
ROUTES BEYOND THE AREAS OF WORK.
N. WHERE EXISTING SURFACES ARE TO BE REFINISHED OR ARE TO SERVE AS
SUBSTRATE FOR THE ATTACHMENT OR APPLICATION OF NEW MATERIALS
OR CONSTRUCTION, PREPARE OR ALTER THE EXISTING SURFACES AS
NECESSARY TO PROPERLY ACCOMMODATE THE NEW MATERIALS.
O. CONTRACTOR SHALL PROVIDE COR THREE WEEKS NOTICE FOR ANY
WORK WITHIN PATIENT OR STAFF SPACE OR THAT WOULD INTERFERE
WITH NORMAL FUNCTIONS OF THE HOSPITAL.
P. SEE SPECIFICATIONS THAT ARE A PART OF THESE CONTRACT DOCUMENTS
FOR ADDITIONAL REQUIREMENTS.
Q. COORDINATE ALL DUMPSTER LOCATIONS WITH COR PRIOR TO DELIVERY
OF DUMPSTERS. ALL LOCATIONS MUST BE MINIMAL IMPACT TO FACILITY
OPERATIONS.
R. COORDINATE CONTRACTOR STAGING AREA WITH COR PRIOR TO
CONSTRUCTION. CONTRACTOR SHALL PROVIDE A CONSTRUCTION FENCE
AT THE PERIMETER OF THE CONTRACTOR STAGING AREA. SEE
SPECIFICATION 01 00 00 GENERAL REQUIREMENTS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS 100%
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Exp. 12/31/21#1616637
C :\U se rs
\b lim i\D oc um en ts \F
FE
_L ex in gt on
R oo f R ep ai r ( br et t.l im in g.
rv t
/6
/2
:5 7:
P
M
G000
COVER SHEET LEXINGTON COOPER DRIVE ROOF
REPAIR
1101 Veterans Dr, Lexington, KY 40502
596A4-19-106
1 & 1A
10/06/2020 PRQ BL
SHEET NO. SHEET NAME ISSUE DATE SD DD BD
GENERAL
G000 COVER SHEET 10/06/2020 * * *
ARCHITECTURE
AE101 OVERALL ROOF PLAN 10/06/2020 * * *
AE111 ROOF PLAN - SOUTH 10/06/2020 * * *
AE112 ROOF PLAN - NORTH 10/06/2020 * * *
AE501 ROOFING DETAILS 10/06/2020 * *
VAMC LEXINGTON, COOPER DRIVE
DEPARTMENT OF VETERANS AFFAIRS
D R A W I N G I N D E X
1101 Veterans Dr, Lexington, KY 40502
NTS
SITE LOCATION1
BID DOCUMENTS 100% - 10/06/2020
REPAIR ROOFS BLDGS. 1 AND 1A - #596A4-20-101
Revisions: Date:
CONSTRUCTION/BID DOCUMENTS 10/06/2020
10/06/2020
/1 AE111
/1 AE112
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
B13
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A12
A13
A11
A B C D E F G H J K
L M N O P
Q R S
T U V W X
2ND FL ROOF
EL 1022' +/-
GROUND FL ROOF
EL 994' +/-
GROUND FL ROOF
EL 994' +/-
7TH FL ROOF
EL 1098' +/-
6TH FL ROOF
EL 1076' +/-
2ND FL ROOF
EL 1022' +/-
2ND FL ROOF
EL 1022' +/-
3RD FL ROOF
EL 1035' - 4" +/-
1ST FL ROOF
EL 1008' - 8" +/-
2ND FL ROOF
EL 1022' +/-
2ND FL ROOF
EL 1022' +/-
4TH FL ROOF
EL 1048' - 8" +/-
CANOPY ROOF
EL 1013' +/-
6TH FL ROOF
EL 1076' +/-
6TH FL ROOF
EL 1076' +/-
6TH FL ROOF
EL 1076' +/-
6TH FL ROOF
EL 1076' +/-
7TH FL ROOF
EL 1098' +/-
1ST FL ROOF
EL 1008' - 8" +/-
1ST FL ROOF
EL 1008' - 8" +/-
1ST FL ROOF
EL 1008' - 8" +/-
1ST FL ROOF
EL 1008' - 8" +/-
2ND FL ROOF
EL 1022' +/-
3RD FL ROOF
EL 1035' - 4" +/-
1ST FL ROOF
EL 1008' - 8" +/-
NOT IN CONTRACT
PENTHOUSE ROOF
EL 1065' - 4" +/-
NOT IN CONTRACT
PENTHOUSE ROOF
EL 1065' - 4" +/-
NOT IN CONTRACT
PENTHOUSE ROOF
EL 1065' - 4" +/-
NOT IN CONTRACT
126 1/8"
126 1/8"
N.I.C. N.I.C.
2ND FL ROOF
EL 1022' +/-2ND FL ROOF
EL 1022' +/-
N.I.C.
N.I.C.
GROUND FLOOR ROOF
1ST FLOOR ROOF
2ND FLOOR ROOF
3RD FLOOR ROOF
4TH FLOOR ROOF
6TH FLOOR ROOF
7TH FLOOR ROOF
CANOPY ROOF
NOT IN CONTRACT (N.I.C.)
L E G E N D
ACCESS POINT
WALKWAY SYSTEM
ROOF DRAIN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS 100%
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Exp. 12/31/21#1616637
C :\U se rs
\b lim i\D oc um en ts \F
FE
_L ex in gt on
R oo f R ep ai r ( br et t.l im in g.
rv t
/6
/2
:5 4:
P
M
AE101
OVERALL ROOF PLAN LEXINGTON COOPER DRIVE ROOF
REPAIR
1101 Veterans Dr, Lexington, KY 40502
596A4-19-106
1 & 1A
10/06/2020 PRQ BL/JK
1/16" = 1'-0"1 OVERALL ROOF PLAN
R O O F S C H E D U L E
BASE LEVEL AREA COMMENTS
GROUND FLOOR ROOF 6100 SF
1ST FLOOR ROOF 32300 SF
CANOPY ROOF 1800 SF
2ND FLOOR ROOF 20700 SF
3RD FLOOR ROOF 5900 SF
4TH FLOOR ROOF 2200 SF
6TH FLOOR ROOF 22200 SF
7TH FLOOR ROOF 10400 SF
101500 SF
NOTE: CONTRACTOR IS RESPONSIBLE FOR AND SHALL VERIFY ALL QUANTITIES.
Revisions: Date:
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
B13
A B C D E F G H J K
L
/1 AE112
TYP.
TYP.
TYP.
AE501
AE501
3' - 8"
4' - 6"
AE501
Sim
AE501
Sim
AE501
Sim
AE501
Sim
AE501
Sim
AE501
Sim
TYP.
TYP.
TYP.
TYP.
G E N E R A L N O T E S
A. MINIMUM ROOF SLOPE SHALL BE 1/8” = 1’-0” - MAINTAIN MINIMUM 3" OF INSULATION.
MATCH ELEVATION WHERE TYING INTO EXISTING.
B. THE ROOFING SYSTEM SHALL BE COMPLETELY WATERTIGHT AT THE END OF EACH DAY’S
CONSTRUCTION ACTIVITY. IF TEMPORARY ROOFING STRATEGIES ARE USED, MATERIALS
INSTALLED SHALL SERVE THE SAME FUNCTION AS EXISTING MATERIALS AND WILL BE
COMPATIBLE WITH EXISTING ROOF SYSTEM.
C. CONTRACTOR SHALL RELOCATE EXISTING SURFACE-MOUNTED LIGHTNING PROTECTION
SYSTEM. REINSTALL SYSTEM AT COMPLETION OF ROOF WORK IN EACH ROOF AREA.
CONTRACTOR SHALL RECERTIFY ENTIRE LIGHTNING PROTECTION SYSTEM AT
CONCLUSION OF PROJECT.
D. SEE ASBESTOS ABATEMENT REPORT AND SPECIFICATIONS FOR ABATEMENT WORK.
E. EXISTING PLUMBING VENTS ARE NOT SHOWN ON ROOF PLAN BUT SHALL BE INCLUDED IN
THE PROJECT BID AND COMPLETED ACCORDING TO DETAILS AND/OR ROOFING SYSTEM
REQUIREMENTS.
F. MISCELLANEOUS CONDUITS THRU ROOF SLABS AT MECHANICAL UNITS ARE NOT SHOWN
BUT SHALL BE INCLUDED IN THE PROJECT BID AND COMPLETED ACCORDING TO DETAILS
AND/OR ROOFING SYSTEM REQUIREMENTS.
G. REPLACEMENT OF EXISTING BASE FLASHING AND COUNTERFLASHING AT BRICK WALLS
ARE NOT IN SCOPE OF WORK UNLESS NOTED OTHERWISE. EXISTING TO REMAIN.
H. CONTRACTOR SHALL VERIFY EXTENT OF UNUSED CURBS IN PROJECT AT AREAS OF ROOF
REPLACEMENT. ALL UNUSED CURBS SHALL BE REMOVED INFILL AT OPENING WITH METAL
DECKING OVER STEEL FRAMING.
I. EXISTING ROOF DRAINS SHALL REMAIN UNLESS NOTED OTHERWISE.
J. EXISTING FLASHING SHALL REMAIN UNLESS NOTED OTHERWISE. SEE DETAILS.
FLUID APPLIED REHABILITATION SYSTEM
BLISTER REPAIR
REPLACEMENT AND REMOVAL OF ROOFING
L E G E N D
10,450 SF
101,400 SF
656 SF
NOTE: CONTRACTOR IS RESPONSIBLE FOR AND SHALL VERIFY
ALL QUANTITIES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS 100%
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Exp. 12/31/21#1616637
C :\U se rs
\b lim i\D oc um en ts \F
FE
_L ex in gt on
R oo f R ep ai r ( br et t.l im in g.
rv t
/6
/2
:5 5:
P
M
AE111
ROOF PLAN - SOUTH LEXINGTON COOPER DRIVE ROOF
REPAIR
1101 Veterans Dr, Lexington, KY 40502
596A4-19-106
A
10/06/2020 PRQ BL/JK
1/16" = 1'-0"1 ROOF PLAN - SOUTH
D R A W I N G N O T E S
1 NO WORK ON THIS ROOF SURFACE.
2 APPLY NEW FLUID-APPLIED MEMBRANE SYSTEM TO FULL EXTENT OF ROOF SURFACE WITHIN
PROJECT AREA – SYSTEM SHALL BE APPLIED OVER ALL ALUMINUM ROOF CURBS TO TOP OF CURB.
3 INSTALL NEW ROOF DRAIN - SEE DETAIL 16 ON SHEET AE501
4 REMOVE EXISTING WALKPADS - REPLACE WITH NEW FIBERGLASS REINFORCED PLASTIC
WALKWAYS AT SAME LOCATION.
5 EXISTING ROOF CURB TO REMAIN
6 CUT OUT CAP SHEET AND FULLY DRY AREA OF WATER BLISTERS – APPLY ADDITIONAL 1-3/4" FASTENERS TO BASE MEMBRANE AT 4'-0" O.C. BOTH DIRECTIONS - REBOND EXISTING MODIFIED
BITUMEN ROOFING PLY AND PREPARE TO RECEIVE NEW FLUID-APPLIED MEMBRANE SYSTEM.
7 REMOVE EXISTING SATELLITE DISH AND ASSOCIATED SURFACE-WEIGHTED CMU ANCHORS – TURN
OVER DISH TO VA.
8 NEW FIBERGLASS REINFORCED PLASTIC WALKWAYS - MAINTAIN 10 FEET CLEARANCE FROM EDGE.
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A12
A13
A11
K
L M N O P
Q R S
T U V W X
/1 AE111
9 9
AE501
AE501
Sim
AE501
AE501
AE501
AE501
AE501
AE501
AE501
7' - 3"
AE501
AE501
Sim
AE501
AE501
2 7
AE501
Sim
AE501
AE501
TYP.
TYP.
TYP.
AE501
Sim
AE501
Sim
AE501
Sim
+7"+7"
+7"
+7"
+7"
+3"
+3" +3"
+7"
+7"
+7"
+7"
+7"+7"+7"
+7" +7"
+7" +7"
+7"+7"
+7"
+3" +3"
+3"
+3"
+3"+3"
+7"
+7"+7"
+7"
+7"
+7
+7"
+7"
TYP.
18 18
AE501
Sim
AE501
Sim
AE501
20' - 1 1/2"
.0 0°
+12"
+12"
TYP.
TYP.
19 TYP.
TYP.
TYP.
TYP.
11 11
G E N E R A L N O T E S
A. MINIMUM ROOF SLOPE SHALL BE 1/8” = 1’-0” - MAINTAIN MINIMUM 3" OF INSULATION.
MATCH ELEVATION WHERE TYING INTO EXISTING.
B. THE ROOFING SYSTEM SHALL BE COMPLETELY WATERTIGHT AT THE END OF EACH DAY’S
CONSTRUCTION ACTIVITY. IF TEMPORARY ROOFING STRATEGIES ARE USED, MATERIALS
INSTALLED SHALL SERVE THE SAME FUNCTION AS EXISTING MATERIALS AND WILL BE
COMPATIBLE WITH EXISTING ROOF SYSTEM.
C. CONTRACTOR SHALL RELOCATE EXISTING SURFACE-MOUNTED LIGHTNING PROTECTION
SYSTEM. REINSTALL SYSTEM AT COMPLETION OF ROOF WORK IN EACH ROOF AREA.
CONTRACTOR SHALL RECERTIFY ENTIRE LIGHTNING PROTECTION SYSTEM AT
CONCLUSION OF PROJECT.
D. SEE ASBESTOS ABATEMENT REPORT AND SPECIFICATIONS FOR ABATEMENT WORK.
E. EXISTING PLUMBING VENTS ARE NOT SHOWN ON ROOF PLAN BUT SHALL BE INCLUDED IN
THE PROJECT BID AND COMPLETED ACCORDING TO DETAILS AND/OR ROOFING SYSTEM
REQUIREMENTS.
F. MISCELLANEOUS CONDUITS THRU ROOF SLABS AT MECHANICAL UNITS ARE NOT SHOWN
BUT SHALL BE INCLUDED IN THE PROJECT BID AND COMPLETED ACCORDING TO DETAILS
AND/OR ROOFING SYSTEM REQUIREMENTS.
G. REPLACEMENT OF EXISTING BASE FLASHING AND COUNTERFLASHING AT BRICK WALLS
ARE NOT IN SCOPE OF WORK UNLESS NOTED OTHERWISE. EXISTING TO REMAIN.
H. CONTRACTOR SHALL VERIFY EXTENT OF UNUSED CURBS IN PROJECT AT AREAS OF ROOF
REPLACEMENT. ALL UNUSED CURBS SHALL BE REMOVED INFILL AT OPENING WITH METAL
DECKING OVER STEEL FRAMING.
I. EXISTING ROOF DRAINS SHALL REMAIN UNLESS NOTED OTHERWISE.
J. EXISTING FLASHING SHALL REMAIN UNLESS NOTED OTHERWISE. SEE DETAILS.
FLUID APPLIED REHABILITATION SYSTEM
BLISTER REPAIR
REPLACEMENT AND REMOVAL OF ROOFING
L E G E N D
10,450 SF
101,400 SF
656 SF
NOTE: CONTRACTOR IS RESPONSIBLE FOR AND SHALL VERIFY
ALL QUANTITIES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS 100%
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Exp. 12/31/21#1616637
C :\U se rs
\b lim i\D oc um en ts \F
FE
_L ex in gt on
R oo f R ep ai r ( br et t.l im in g.
rv t
/6
/2
:5 6:
P
M
AE112
ROOF PLAN - NORTH LEXINGTON COOPER DRIVE ROOF
REPAIR
1101 Veterans Dr, Lexington, KY 40502
596A4-19-106
1A
10/06/2020 PRQ BL/JK
1/16" = 1'-0"1 ROOF PLAN - NORTH
D R A W I N G N O T E S
1 NO WORK ON THIS ROOF SURFACE.
2 APPLY NEW FLUID-APPLIED MEMBRANE SYSTEM TO FULL EXTENT OF ROOF SURFACE WITHIN
PROJECT AREA – SYSTEM SHALL BE APPLIED OVER ALL ALUMINUM ROOF CURBS TO TOP OF CURB.
3 EXISTING SPLASHBLOCK TO BE REUSED - ANGLE TOWARDS NEAREST ROOF DRAIN.
4 EXTEND DOWNSPOUT TO DISCHARGE AS SHOWN – SECURE TO EXISTING WALL AND SEAL ALL
ANCHOR PENETRATIONS - PROVIDE STONE SPLASHBLOCK AT DISCHARGE.
5 INSTALL NEW ROOF DRAIN - SEE DETAIL 16 ON SHEET AE501
6 CUT OUT CAP SHEET AND FULLY DRY AREA OF WATER BLISTERS – APPLY ADDITIONAL 1-3/4" FASTENERS TO BASE MEMBRANE AT 4'-0" O.C. BOTH DIRECTIONS - REBOND EXISTING MODIFIED
BITUMEN ROOFING PLY AND PREPARE TO RECEIVE NEW FLUID-APPLIED MEMBRANE SYSTEM.
7 REMOVE MODIFIED-BITUMEN ROOFING AND TAPERED RIGID INSULATION – REPLACE WITH NEW
RIGID INSULATION AND 2-PLY MODIFIED BITUMEN ROOFING. PREPARE TO RECEIVE NEW
FLUID-APPLIED MEMBRANE SYSTEM - MINIMUM 3" RIGID INSULATION.
8 REMOVE EXISTING WALKPADS - REPLACE WITH NEW FIBERGLASS REINFORCED PLASTIC
WALKWAYS AT SAME LOCATION.
9 NEW WARNING STRIPE PAINTED AT 6 FT FROM ROOF EDGE – COLOR TO BE SAFETY YELLOW –
APPLY AT COMPLETION OF ROOF RESURFACING.
10 EXISTING MECHANICAL SCREEN WALL TO REMAIN
11 EXISTING GUARDRAIL TO REMAIN
12 EXISTING CONDENSER SHALL BE ADJUSTED AROUND APPLICATION OF NEW FLUID-APPLIED
REHABILITATION SYSTEM - CONTRACTOR SHALL CHOOSE TO EVACUATE REFRIGERANT AND
RECHARGE AFTER COMPLETION OF WORK, OR LEAVE FUNCTIONAL AND TEST SYSTEM AT
COMPLETION - ALL SPACES WITHIN THE VA HOSPITAL WILL REMAIN IN OPERATION AND SHALL BE
SUPPORTED BY FUNCTIONING HVAC THROUGHOUT THE DURATION OF CONSTRUCTION .
13 EXISTING BARRELS WILL BE RELOCATED BY VA PERSONNEL PRIOR TO THE START OF
CONSTRUCTION.
14 EXISTING ROOF DRAINS TO REMAIN - KEEP CLEAR OF ALL DEBRIS.
15 EXISTING AIR TRAFFIC LIGHTS TO REMAIN - SHIFT LIGHTS AND SUPPORTS TO ACCOMMODATE
INSTALLATION OF NEW FLUID-APPLIED REHABILITATION SYSTEM INSTALL.
16 REMOVE UNUSED CURBS (12 TOTAL) - CAP EXISTING PENETRATION WITH 3/8" STEEL PLATE 6"
BEYOND EXTENT OF OPENING - ANCHOR INTO EXISTING CONCRETE STRUCTURE WITH FOUR (4)
EXPANSION ANCHORS WITH 2.5" EMBED - PREPARE FOR NEW ROOFING. SEE
ASBESTOS-CONTAINING MATERIALS (ACM) REPORT AND SPECIFICATIONS FOR EXTENT OF ACM.
17 ALIGN WITH TOP OF EXISTING ADJACENT ROOFING.
18 NEW METAL EDGE FASCIA TO MATCH EXISTING IN MATERIAL, COLOR, PROFILE, AND DEPTH.
19 EXISTING ROOF CURB TO REMAIN
EXISTING CONCRETE ROOF DECK
PERIMETER INSULATION STOP
TAPERED RIGID INSULATION - 3" MIN.
TWO-PLY MODIFIED BITUMINOUS
MEMBRANE OVER 1/4" COVER BOARD
NEW CANT
EXISTING FLASHING AND COUNTERFLASHING
APPLY MEMBRANE AND SELF-FLASHING
FLUID-APPLIED REHAB. SYSTEM
UNDER EXISTING FLASHING
9"
TAPERED RIGID INSULATION
EXISTING CONCRETE
ROOF DECK
TWO-PLY MODIFIED BITUMINOUS
MEMBRANE OVER 1/4" ADHERED
COVER BOARD
BASE FLASHING
NEW CANT
EX. WOOD
BLOCKING
EXISTING CURB FLASHING
FLUID APPLIED, SELF-FLASHING
COATING - APPLY UNDER
METAL CURB FLASHING
EX. WOOD BLOCKING
EXISTING CONCRETE
ROOF DECK
EXISTING TAPERED
INSULATED CONCRETE
EXISTING MEMBRANE
EXISTING BASE FLASHING
EXISSTING FLASHING
EXISTING MECHANICAL SUPPORT L ANGLE
FLUID-APPLIED, SELF-FLASHING
COATING. APPLY COATING
UNDER EXISTING FLASHING
EXISTING CONCRETE
ROOF SLAB
EXISTING RAILING
NEW FLUID-APPLIED, SELF-
FLASHING COATING. WRAP
BOTTOM OF RAILING POST
EXISTING TAPERED
INSULATED CONCRETE
EXISTING CONCRETE
ROOF DECK
EXISTING PRESSURE
TREATED WOOD BLOCKING
NEW CANT
EXISTING MECHANICAL UNIT
FLUID-APPLIED, SELF-FLASHING
COATING - APPLY COATING UNDER
FLASHING.
NEW BASE FLASHING
NEW TAPERED INSULATION -
3" MIN. - SLOPE TO DRAIN
4" 6"
4"
8"
EXISTING STAINLESS STEEL
REGLET
NEW 1/4" ADHERED COVER BOARD
EXISTING CONCRETE DECK
TWO-PLY MODIFIED BITUMINOUS MEMBRANE
OVER 1/4" ADHERED COVER BOARD.
CONTINUOUS SEALANT
EXTEND NEW MEMBRANE UNDER
EDGE FASCIA
REMOVE EXISTING MEMBRANE AND
TAPERED INSULATED CONCRETE
FILL. INSTALL TAPERED INSULATION -
3" MIN. - SLOPE TO DRAIN
NEW EDGE FASCIA TO
MATCH EXISTING IN
MATERIAL, COLOR,
PROFILE, AND DEPTH.
EXISTING CONCRETE
ROOF DECK
EXISTING TAPERED
INSULATION
NEW FLUID-APPLIED, SELF-
FLASHING COATING.
BEND BACK COUNTERFLASHING
TO EXTEND FLUID-APPLIED
COATING UNDER FLASHING
EXISTING PARAPET CAP TO
REMAIN
12"
EXISTING CONCRETE
ROOF SLAB
NEW TAPERED
INSULATION - 3" MIN. -
SLOPE TO DRAIN
FLUID-APPLIED, SELF-FLASHING
COATING
TWO-PLY MODIFIED BITUMINOUS
MEMBRANE. OVERLAP MINIMUM 12"
EXISTING TAPERED
INSULATED
CONCRETE
EXISTING TWO-PLY
MODIFIED BITUMINOUS
MEMBRANE
NEW 1/4" ADHERED COVER
BOARD
TAPERED RIGID INSULATION - 3" MIN.
NEW TAPERED CANT
EXISTING CONCRETE ROOF SLAB
CONCRETE PRIMER
WOOD INSULATION STOP.
MECHANICALLY FASTENED
EXISTING ROUND
METAL STACK
8"
FLUID-APPLIED, SELF-FLASHING
COATING
1/4" ADHERED COVER BOARD
NEW CANT
FLUID-APPLIED, SELF-FLASHING
COATING. BEND BACK EXISTING
FLASHING TO APPLY COATING
UNDER FLASHING
NEW TAPERED INSULATION
EXISTING COUNTER
FLASHING
EXISTING ROOF HATCH
NEW 1/4" ADHERED COVER
BOARD
NEW TAPERED
INSULATION - 3" MIN. -
SLOPE TO DRAIN
NEW BASE FLASHING EXTEND
OVER TOP OF CURB SECURE
TO TOP OF CURB
EXISTING CURB EDGE OF
MECHANICAL UNIT
CONCRETE PRIMER
REMOVE EXISTING MEMBRANE AND
TAPERED INSULATED CONCRETE.
INSTALL NEW TAPERED RIGID
INSULATION.
EXISTING CANT (TYP)
FLUID-APPLIED, SELF-FLASHING
COATING
NEW 1/4" ADHERED COVER
BOARD 8" EXISTING MECHANICAL
CURB
EXISTING WOOD
INSULATED STOP
NEW TAPERED INSULATION - 3"
MIN. - SLOPE TO DRAIN
REMOVE EXISTING MEMBRANE
AND TAPERED INSULATION
FLUID-APPLIED, SELF-FLASHING
COATING. BEND BACK EXISTING
FLASHING TO APPLY COATING
UNDER FLASHING
NEW CANT
NEW 1/4" ADHERED COVER
BOARD
EXISTING CONCRETE
ROOF SLAB
CONCRETE PRIMER
REMOVE EXISTING ROOFING AND
TAPERED INSULATED CONCRETE.
INSTALL NEW TAPERED RIGID
INSULATION.
EXISTING WOOD POST FULL LENGTH
OF STEPS
EXTEND BASE FLASHING
OVER TOP OF CURB EXISTING STEEL STEPS
NEW STAINLESS STEEL CAP WELD
ALL CORNERS
EXISTING CANT (TYP)
EX. WOOD INSULATED
STOP
NEW 1/4" ADHERED COVER
BOARD
NEW TAPERED INSULATION
EXISTING CONCRETE
STRUCTURAL DECKPROVIDE FIRE SAFING INSULATION
AT ALL ABANDONED PENETRATIONS
THROUGH ROOF DECK - SECURE TO
CAVITY.
FLUID-APPLIED , SELF-
FLASHING COATING
3/8" STEEL PLATE 6" BEYOND
PERIMETER OF OPENING IN EACH
DIRECTION - PRE-DRILL HOLES AND
SECURE WITH FOUR (4) 3/8"
EXPANSION BOLTS - 3" EMBED.
APPLY CONTINUOUS SEALANT
AT UNDERSIDE OF PLATE AT
PERIMETER OF OPENING
6" TYP.
NEW 1/4" ADHERED COVER
BOARD
EXISTING CONCRETE
ROOF DECK
EXISTING TAPERED
INSULATION
NEW FLUID-APPLIED, SELF-
FLASHING COATING UNDER
EXISTING COPING
EXISTING PARAPET CAP TO
REMAIN
EXISTING MODIFIED BIT
MEMBRANE
EXISTING PARAPET
STRUCTURE
NEW TAPERED INSULATION
EXISTING CONCRETE
STRUCTURAL DECK
FLUID-APPLIED , SELF-
FLASHING COATING
NEW 3" DIA. DRAIN
PIPE TO TIE INTO
EXISTING
METAL DRAIN STRAINER
METAL CLAMPING RING
PROVIDE NO-HUB
CONNECTION
SINGLE-PLY MODIFIED BITUMINOUS
MEMBRANE - OVERLAP EXISTING
INSULATION 12 INCHES.1/4" ADHERED COVER BOARD
EXISITNG DRAIN
PIPE
METAL DRAIN PAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS 100%
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Exp. 12/31/21#1616637
C :\U se rs
\q ui nn \D oc um en ts
\F
FE
_L ex in gt on
R oo f R ep ai r ( pa tri ck
.q ui nn
FB
N
EU
.rv t
/7
/2
9:
:0
AM
AE501
ROOFING DETAILS LEXINGTON COOPER DRIVE ROOF
REPAIR
1101 Veterans Dr, Lexington, KY 40502
596A4-19-106
10/06/2020 PRQ BL/JK
1" = 1'-0"1 TYPICAL NORTH BUILDING WALL DETAIL
1" = 1'-0"2 MECHANICAL CURB DETAIL
1" = 1'-0"3
NORTH BUILDING MECHANICAL CURB
DETAIL WITH STEEL FRAMING
1" = 1'-0"4 PIPE RAILING DETAIL
1" = 1'-0"5
NORTH AND SOUTH BUILDING
MECHANICAL UNIT FLASHING
1" = 1'-0"13
TYPICAL NORTH BUILDING PARAPET
AND GRAVEL STOP DETAIL
1" = 1'-0"12
TYPICAL SOUTH BUILDING PARAPET
DETAIL
1" = 1'-0"7
CONNECTION BETWEEN EXISTING AND
NEW ROOFING
1" = 1'-0"6
NORTH BUILDING VENT FLASHING
DETAIL
1" = 1'-0"11 NORTH BUILDING ROOF HATCH DETAIL
1" = 1'-0"8
NORTH BUILDING A/C CONDENSER NEW
CURB DETAIL
1" = 1'-0"10
NORTH AND SOUTH BUILDING
MECHANICAL VENTILATOR DETAIL
1" = 1'-0"9
BUILDING A STEEL STEPS, FLASHING,
AND CURB
1" = 1'-0"14
NORTH BUILDING MECHANICAL CURB
INFILL DETAIL
Revisions: Date:
CONSTRUCTION/BID DOCUMENTS 10/06/2020
1" = 1'-0"15
BASE FLASHING AT PARAPET WALL
WITH METAL COPING
1" = 1'-0"16 ROOF DRAIN DETAIL
| 00.00 - Sheet - G000 - COVER SHEET |
| Sheets |
| AE101 - OVERALL ROOF PLAN |
| AE111 - ROOF PLAN - SOUTH |
| AE112 - ROOF PLAN - NORTH |
| AE501 - ROOFING DETAILS |
| G000 - COVER SHEET |
| 07.00 - Sheet - AE101 - OVERALL ROOF PLAN |
| Sheets |
| AE101 - OVERALL ROOF PLAN |
| AE111 - ROOF PLAN - SOUTH |
| AE112 - ROOF PLAN - NORTH |
| AE501 - ROOFING DETAILS |
| G000 - COVER SHEET |
| 07.01 - Sheet - AE111 - ROOF PLAN - SOUTH |
| Sheets |
| AE101 - OVERALL ROOF PLAN |
| AE111 - ROOF PLAN - SOUTH |
| AE112 - ROOF PLAN - NORTH |
| AE501 - ROOFING DETAILS |
| G000 - COVER SHEET |
| 07.02 - Sheet - AE112 - ROOF PLAN - NORTH |
| Sheets |
| AE101 - OVERALL ROOF PLAN |
| AE111 - ROOF PLAN - SOUTH |
| AE112 - ROOF PLAN - NORTH |
| AE501 - ROOFING DETAILS |
| G000 - COVER SHEET |
| 07.03 - Sheet - AE501 - ROOFING DETAILS |
| Sheets |
| AE501 - ROOFING DETAILS |
| 07.03 - Sheet - AE501 - ROOFING DETAILS.pdf |
| Sheets |
| AE501 - ROOFING DETAILS |
File details come from the government source that posted it. Updated .