This document is a product specification sheet for a trailer-mounted 1000 kW load bank system. The requirement specifies a mobile, high-capacity load-absorbing unit designed for durability and safe transport capable of accepting medium-voltage inputs of 2400V and 4160V with adjustable load steps up to 1000 kW to enable full-load generator testing. The system must include integrated cooling and over-temperature protection to ensure safe operation under continuous full-load conditions across varying environmental conditions.

The load bank shall be mounted on a road-ready trailer equipped with stabilizing outriggers, weather-resistant enclosures, and secure access panels with sufficient capacity to transport the equipment. The unit must incorporate digital monitoring capability for real-time display of voltage, current, frequency, and power factor, along with compliant grounding, medium-voltage connection points, and safety interlocks to ensure proper operation with BPUs (Balance of Plant Units). The specification emphasizes mobility and durability as critical design factors to support generator testing operations in the field.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Product Specifications Trailer Mounted 1000kW Load Bank

Description of Requirement:

Must be a mobile, high-capacity load-absorbing unit designed for durability, safe transport

Load bank must accept medium-voltage inputs of 2400V and 4160V and provide adjustable load steps up to 1000 kW to enable full-load generator testing.

Must include integrated cooling, and over-temperature protection

Digital monitoring for real-time display of voltage, current, frequency, and power factor.

The system shall be mounted on a road-ready trailer equipped with stabilizing outriggers, Weather-resistant enclosures, and secure access panels.

Unit must include compliant grounding, medium-voltage connection points, and safety interlocks to ensure proper operation with BPUs.

The load bank must be capable of continuous full-load operation under varying environmental conditions

The trailer must be big enough to transport the load bank