Moore Pool Equipment Update - Project Plan Set
This is a previous renovation plan set document prepared by RenoSys Corporation for the City of Pittsburgh Department of Public Works for the Moore Pool facility located at 1801 Pioneer Avenue, Pittsburgh, Pennsylvania 15226. The plan set includes comprehensive design specifications for pool renovation encompassing a gutter-based circulation system, main drain installation, grounding and bonding details, and PVC liner membrane specifications. The project involves a competitive swimming pool with dimensions of 90 feet by 166 feet, a total volume of 530,649 gallons, and water depths ranging from 2 feet 8 inches to 7 feet 2 inches. The circulation system is designed with a suction-feed configuration providing an 8-hour turnover rate (480 minutes) at a flow rate of 1,106 gallons per minute, utilizing 187 inlets spaced at 2 feet 7 inches on-center. The plan set includes detailed specifications for a DuraTech stainless steel gutter system with 51 sections, 143 gutter anchor assemblies, two 8-inch collector boxes, one 6-inch supply box, two 18-by-36-inch main drains, 28 floor inlets, and ancillary equipment including depth markers, ladders, rope hooks, and wall targets. The document underwent multiple revisions between November 5, 2020 and January 6, 2021, with the final revision removing the RecDeck system and ADA lift component.
The plan set was marked "NOT FOR CONSTRUCTION" as of the November 5, 2020 release date and required approval and field verification prior to implementation. Key design standards referenced include the 2015 International Swimming Pool and Spa Code, 2010 ADA Standards for Accessible Design, NCAA and FINA governing body requirements for competitive swimming and diving, 2014 National Electrical Code, and local Pittsburgh and Pennsylvania health and building codes. The design specifications include detailed construction notes addressing concrete work, reinforcement standards, plumbing requirements with minimum 1-inch per 10-foot gravity drainage slopes, electrical grounding and bonding per NEC Article 250, and pool-specific safety features including "No Diving" signage, depth markers, and safety equipment. The project design was completed by Brandon Mays of RenoSys Corporation with engineering support from Walsh Engineering and represents preliminary planning documentation for the comprehensive Moore Pool renovation initiative.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Moore_Pool_-_Equipment_Update_(Addendum_#1_Revision).pdf | ||
| Moore_Pool_-_Equipment_Update.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E t h
P l a c e
I n d i a n a p o l i s
N
T o l l
F r e
P h o n e
F a x w w w r e n o s y s c o m
SHEET NO
DWG BY
SCALE DATE
DWG TITLE
CHK BY
BMAYS
11/5/2020
M o o r a r k
P
A
P I O
N E E R
A V E N
U E
P I T T S B U
R G
H
P A
All designs and data included and implied within the contents of these documents are proprietary of ARS. ARS will not be held liable based upon inaccurate, unknown or limited information or conditions provided by the purchaser/owner to create enclosed contents. All submitted drawings, details and data are subject to verification, accuracy and approval by the purchaser/owner. We reserve the right to modify details without notice where conditions require. No documents shall be modified, copied or reproduced without express written consent of ARS. 2004-2020
ARS, Inc, All Rights Reserved.
SHEET SIZE
24 x 36 (inches)
ARCH D
AS SHOWN
FILE LOCATION:
N O
T
F O
R
C O
N S T R U
C T I O
N
D:\CUSTOMERS\#4832 Moore Park, PA\#4832 Moore Park, PA.dwg
11/5/2020
Rejected: Re-Submit Rejected: Re-Submit as Noted
Approved: As Noted Approved: Release for Fabrication Process
X: ______________________________________________
Signature
X: ______________________________________________
Signature
POOL CONTRACTOR
State License # -
RenoSys Corporation
2825 E. 55th Place
Indianapolis, IN 46220
P: (317) 251-0207
F: (317) 251-0360
W: www.renosys.com
POOL SUPPLY & INSTALL
2825 E. 55th Place
Indianapolis, IN 46220
P: (317) 251-0207
F: (317) 251-0360
DESIGN
Brandon Mays
2825 E. 55th Place
Indianapolis, IN 46220
P: (317) 734-3311
F: (317) 251-0360
E: brandonm@renosys.com
POOL ENGINEERING
Walsh Engineering
8826 Southeastern Ave
Indianapolis, IN 46239
(317) 862-4738
ARCHITECT
N/A
GENERAL CONTRACTOR
N/A
OWNER
CITY OF PITTSBURGH
414 GRANT STREET CITY COUNTY BUILDING 3RD FLOOR
PITTSBURGH, PA 15219
SP 0 COVER SHEET
SP 1 NOTES & SYMBOLS
SP 2 DEMO
SP 3 POOL PLAN
SP 4 GUTTER PLAN
SP 5 GUTTER DETAILS
SP 6 MAIN DRAIN DETAILS
SP 7 GROUNDING & BONDING DETAILS
SP 8 MEMBRANE DETAILS
#4832 Moore Park, PA
1801 PIONEER AVENUE
PITTSBURGH, PA 15226
REGIONAL MAP LOCAL MAP
PROJECT TEAM
SHEET INDEX
COVER SHEET
SP 0
POOL DATA
CODES, STANDARDS & REGULATIONS
CODE JURISDICTION
1801 PIONEER AVENUE
PITTSBURGH, PA 15226
CODES, STANDARDS & REGULATIONS:
CONTRACTOR SHALL BE FAMILIAR WITH ALL CODES AND STANDARDS LISTED BELOW AND ALERT
THE ARCHITECT/ENGINEER TO CONFLICTS IN THE DRAWINGS.
HEALTH & SAFETY CODE
1801 PIONEER AVENUE
PITTSBURGH, PA 15226
MODEL CODES
2015 INTERNATIONAL SWIMMING POOL & SPA CODE
ACCESIBLILITY STANDARDS AND REGULATIONS
UNITED STATES 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
COMPETITIVE SWIMMING GOVERNING BODIES
SWIMMING: NCAA NATIONAL COLLEGIATE ATHELTIC ASSOCIATION
USA SWIMMING
DIVING:
FINA FEDERATION INTERNATIONALE DE NATATION (INTERNATIONAL SWIMMING FEDERATION)
NCAA NATIONAL COLLEGIATE ATHLETIC ASSOCIATION
PROJECT STAGE
POOL VOLUME - 530,649 GAL
PERIMETER - 488'-6 7/8"
POOL LENGTH & WIDTH - 90'-0" x 166'-0"
SURFACE AREA - 14,740 SQFT
TURN OVER RATE - 8 HRS (480 MINS)
FLOW RATE - 1,106 GPM
SYSTEM TYPE - SUCTION FEED
DEPTHS - 2'-8" - 7'-2"
INLETS - 187 INLETS @ 5.91 GPM PER INLET @ 17.19 FT/SEC & SPACED @ 2'-7"
O.C.
SURGE WEIRS - N/A
BATHER LOAD - N/A
REVISION HISTORY
REV DATE DESCRIPTION AUTHOR
OR 11.5.20 ORIGINAL RELEASE BMAYS
1 11.9.20 PLUMBING CHANGES BMAYS
2 11.18.20 SUBMITTAL CHANGES BMAYS
3 1.6.20
REMOVE RECDECK &
ADA LIFT
BMAYS
E t h
P l a d i a n a p o l i s
T o l l
F r e o n e
F a x w w w r e n o s y s c o m
SHEET NO
DWG BY
SCALE DATE
DWG TITLE
CHK BY
BMAYS
11/5/2020
M o o r k
P
A
P I O
N E E R
A V E N
U E
P I T T S B U
R G
H
P A
All designs and data included and implied within the contents of these documents are proprietary of ARS. ARS will not be held liable based upon inaccurate, unknown or limited information or conditions provided by the purchaser/owner to create enclosed contents. All submitted drawings, details and data are subject to verification, accuracy and approval by the purchaser/owner. We reserve the right to modify details without notice where conditions require. No documents shall be modified, copied or reproduced without express written consent of ARS. 2004-2020
ARS, Inc, All Rights Reserved.
SHEET SIZE
24 x 36 (inches)
ARCH D
AS SHOWN
FILE LOCATION:
N O
T
F O
R
C O
N S T R U
C T I O
N
D:\CUSTOMERS\#4832 Moore Park, PA\#4832 Moore Park, PA.dwg
11/5/2020
NOTES & SYMBOLS
SP 1
GENERAL NOTES & PROJECT INFORMATION (IF APPLICABLE)
CODES, SAFETY & SIGNAGE
1. Pool rules shall be posted at, or near, pool sides with letters at a minimum of 1" in height and shall include at least the following:
2. No Diving ( in 4" letters)
3. No food, drinks, or Animals allowed in pool area
4. Pool Hours: AM to PM
5. Bathing load: N/A persons
6. Shower before entering pool
7. No Lifeguard on Duty
8. Swim at your own risk
GENERAL NOTES
1. Glass used in glazing shall be tempered or laminated safety glass. Glass used in glazing shall not be located adjacent to activity areas.
2. Reference shall be made to the publication " Minimum Standards for Public Swimming Pools" available from the National Spa & Pool Institute. 2111 Eisenhower Avenue, Alexandria, Virginia 22314.
CONSTRUCTION NOTES (IF APPLICABLE)
CONCRETE
1. Pool concrete decks to slope away from pool at 1/4" per foot
2. Pool concrete decks to have light broom finish
3. The restroom floors shall slope to floor drains and shall be constructed of an impervious slip-resistant surface.
4. Depth markers and anchors to be provided by RenoSys Coporation and installed by concrete contractor.
5. All metallic items required to be bonded and grounded as required by the 2014 National Electrical Code.
6. All assumed allowable soil bearing pressure is 2000 PSF, to be verified by contractor.
7. Footings are to be placed on undisturbed natural soil (not pervious fill material) or engineered fill.
8. Engineered fill shall be free of organic material, rocks larger than 2" and clay shall not have a PSI greater than 12. Fill shall be compacted to a max. dry density of 95% of the modified proctor per ASTM-D1157, and placed in 8" lifts.
9. Granular material is soil with a rounded shape, free of organic and clay material with max. size aggregate to be 3/8".
10. All concrete shall have the following 28 day compressive strengths:
11. Footings 3000 PSI with 2% air entrapment, W/C=.55
12. Exterior and Interior Slabs 4000 PSI with 6% air entrapment W/C=.45
13. All reinforcing shall shall be ASTM A-615 grade 60. all welded wire fabric shall be ASTM A-185 with yield of 65 KSI.
14. All concrete shall use Type I Portland cement.
15. Provide sleeves for all opening in grade beams, to separate pipe from concrete.
16. Concrete work shall conform to all requirements of ACI-301 specifications for structural concrete for buildings and ACI-347, guide to form work for concrete.
17. All reinforcement shall placed per the Concrete Reinforcing Steel Institute, manual of standard practice.
18. Provide 1" deep by 1/4" wide control joints at 15'-0" max. in slabs on grade.
19. Provide 3/4" chamfers on all exposed edges of concrete.
20. Minimum concrete cover over reinforcement bar cast against earth 3"
21. Minimum concrete cover over reinforcement bar exposed to earth or weather 2"
22. Interior concrete slabs 3/4"
23. All corners to be formed and poured 6'-0" minimum in both directions, unless otherwise noted
24. Subgrade shall be compacted to a max. dry density of 95% of the modified proctor per ASTM-D1157, and placed in 8" lifts.
25. Provide concrete test samples meeting requirements for approval prior to final concrete pour if required.
GUTTER ANCHORS
1. Shall be designed and installed to meet or exceed National, State & Local codes.
WALL PANELS
BUTTRESSES
PLUMBING NOTES (IF APPLICABLE)
1. The following notes apply to all pool/slide piping plans
2. All metallic items required to be bonded and grounded as required by the 2014 National Electrical Code.
3. The piping layouts on this drawings are schematic and for reference only. Piping as shown as spread out for clarity. Contractor shall be responsible for determining final pipe routing and elevations.
4. Reduce the use of fittings and long pipe runs to minimize head loss in the system.
5. All piping shall be installed in a pipe trench with bedding and cover materials per specifications. Piping may be stacked in the pipe trench.
6. Arrows denote direction of flow.
7. Refer to all disciplines documentation and coordinate all piping and embedments with affected trades.
8. All gravity piping shall be installed at a minimum slope of 1" drop per 10' length. all outdoor piping shall be installed with a slope to allow completete draining. provide winterizing/draining instructions and schematics to owner.
9. Contractor shall use swing joints or other means and methods as required to provide pool inlet fittings flush and perpendicular with the pool floor and as required for proper slope to drain for winterization.
10. All piping shall be in accordance with the pumbing code and the local (county) department of health code. the A.S.T.M. designation number d-1785 and NSF seal for potable water.
11. All piping designed for 6'/second max suction, 8'/second max pressure, and 3'/second max gravity.
12. All zero depth gutter and inlet supply piping must be laid on a grade so it will drain to the surge tank completley by gravity to prevent damage during freezing weather. Main drain line piping must be laid on a grade so; (a) all piping from beneath the pool to the elevation change shall pitch to drain to the pool main drain sumps and; (b) all piping from the elevation change to the surge tank shall pitch to drain to the surge tank. In all instances where gravity rainage is not provided; the contractor shall install drain valves so that all lines can be drained completely to surge tank or another approved location. Drainage plugs shall be provided in the piping system to allow for location. Drainage plugs shall be provided in the piping system to allow for draining of pool piping. Contractor shall provide operation and winterization instructions to owner.
13. All elevations to be field verified to allow for proper pitch and drainage. Pitch approximate 1"/10'-0". Pool contractor shall make every effort to curtail the use of fittings to reduce head.
14. This drawing is intended for schematic use only!! Final locations shall be field verified with all other trades, by Contractor.
15. Contracor shall coordinate all work with architectural, mechanical, electrical and strucural drawings.
DRAINAGE
1. Deck drains shall be provided in locations where standing water may be prevalent.
2. The restroom floors shall slope to floor drains and shall be constructed of an impervious slip-resistant surface.
3. All drain fittings to carry 100% of recirculation rate at a velocity not to exceed 1.5'/second through the clear area of the grate.
4. All drains and outlets shall conform with ANSI/APSP-16 2011 or any successor standard.
WASTE WATER
1. A minimum air gap of 6" must be provided on all waste water lines.
FILL/MAKE-UP WATER
1. A minimum air gap of 6" must be provided on all make-up water.
FIXTURES AND EQUIPMENT
1. Furnish all fixtures and equipment indicated and scheduled on drawings, complete with all accessories, controls and installation items required.
2. Install in full accordance with manufacturer's recommendations and place in satisfactory operation.
3. A hose bib shall be provided within 50 feet of site and must be provided with a vacuum breaker.
4. Public restrooms for bathers shall be equipped with a conveniently located hose bib with a vacuum breaker.
WATER PIPING
1. Coordinate domestic water from 5'-0" outside building to city main with local utilty company. Install domestic water distribution piping to all fixtures and equipment requiring same, including backflow preventor and water meter with remote register. Include all fittings, valves, hangers, and other accessories required for complete installation.
2. Include unions, or other disconnect means, stops or valves for isolation of fixtures and equipment. Valves to be fully compatible with piping for service intending as manufactured by Nibco, Crane or other approved manufacturer. Include hose or drain valves at low points where fixtures cannot be used for drainage.
3. Install air cushions or shock absorbers at each fixture or where required to prevent water hammer. Shock absorbers to be precision plumbing products 15c series or equal.
4. Hangers on insulated pipe to be outside of insulation and sized accordingly and with sufficient saddle to protect insulation.
5. Water piping above grade shall be tube "l" hard copper ASTM B 88-832 with wrought copper fittings ASTM Bb 16.22-1980 and non-lead or antimony solder joints and type "K" copper ASTM B-88 with wrought copper brazed joints below grade.
6. Flush, vent and sanitize all water piping upon completion. sanitize in accordance with American water work association AWWA0601d or local board of health requirements.
SUPPORTS & HANGERS
1. Hangers and supports are to be provided to properly support, secure and align piping and to meet conditions. Spacing to comply with ASHRAE standards and local code requirements.
INSULATION
1. Insulate all above-grade hot and cold water piping and rain conductors inside building with one-half (1/2) inch thick molded fiberglass having type ASJ jacket and manufactured by owens-corning fiberglass company.
2. Insulate hot and cold water supplies and p-trap, including tail piece and trap arm under all lavatories with vinyl closed cell insulation, Truebro model 102 handi lav-guard kit.
3. Include insulation of fittings and valves. Keep vapor barriers intact. Apply to manufacturer's recommendations.
GAUGES
1. Pressure gauges to be installed on all filter suction & discharge lines.
2. All vacuum gauges to be installed in front of pump.
VALVES
1. Provide backwater valves and gear operated sub-surface butterfly valves with valve extension for all pool ans surge tank drain lines.
2. Each valve shall have a permanent idntifying lable or tag attached to it. the sequence of operation, briefly stated, shall be prominently displayed.
ELECTRICAL NOTES (continued) (IF APPLICABLE)
MOTOR STARTERS
1. For single phase motors, provide toggle switches with thermal overload protection and NEMA 4x housing, unless otherwise noted.
2. Combination motor starters shall have an overload device for each phase of the motor.
3. Combination motor starters to be housed in NEMA 4x enclosures.
4. Provide engraved nameplate for each motor starter switch indicating voltage, phase, load served, and circuit origin.
SWITCHES, SAFETY
1. Safety switches shall be heavy duty, size and electrical characteristics indicated, surface mounted, fusible rated at 250 volts on the 208 volt system. Ampere ratings as noted on the drawings, 60 hertz, three (3) blades incorporating quick-make, quick-break type switches.
2. Fuses: Unless indicated on the drawings as non-fused type, provide fuses for safety switches. Fuses to be time-delay, current-limiting u.l. class RKI, and have an interrupting rating of 200,000 RMS amperes symmetrical.
3. Switches shall be housed in NEMA 4x enclosures.provide engraved nameplate for each disconnect switch indicating voltage, phase, load served, and circuit origin.
LIGHTING AND POWER PANEL BOARDS
1. Provide dead-front safety type lighting and power panel boards as indicated, with switching and protective devices in quantities, ratings, types and arrangement as shown, equipped with copper bus bars, full-sized neutral bar, with bolt-in type molded case branch circuit breakers for each circuit, with toggle handles that indicate when tripped.
Provide a bare un-insulated grounding bar suitable for bolting to enclosure. Provide typed directory.
2. Provide engraved nameplate for each panel board indicating voltage, phase, panel name, and feeder origin.
3. Panel boards shall be housed in NEMA 4x enclosures.
GROUNDING
1. Entire power system shall be effectively grounded, including all exposed non-current carrying parts of electrical equipment in full accordance with 2014 NEC article 250.
2. A green pigtail shall be installed from grounding slots of grounding outlets to outlet boxes.
3. Extend ground to domestic water main.
TEMPORARY
1. This contractor to provide all temporary lighting and power as required for all trades.
2. All temporary wiring installed shall be removed by this contractor.
SWIMMING POOL BONDING
1. A bonding system shall be installed to eliminate voltage gradients in the pool area.
2. All work shall meet the requirements set forth by the 2014 national electrical code.
3. All work shall conform to the requirements of all federal, state, local and municipal ordinance.
4. All metallic parts shall be bonded together with #8 AWG solid or larger conductor as described on this drawings and in accordance with NEC 680.26. the copper bonding conductor shall not be required to be attached to remote panel boards, service equipment or electrodes.
5. Bonding jumpers shall be connected by exothermic welding, listed pressure connectors, listed clamps, or other listed means. connection devices that depend solely on solder shall not be used.
PLUMBING NOTES (continued) (IF APPLICABLE)
FLOW METERS
1. Flow meter shall be provided in the filtration pump discharge line and in each inlet return line as indicated on the drawings. Flow meters shall be installed on a straight lenght of pipe without any valve, elbow or other source of turbulence (uninterrupted flow of install per manufacturer's recommendations.
2. Main flow meter shall be used to monitor recirculation rate.
FILTERS
1. Filter shall be provided with the following appropriately located accessories: pressure gauges, backwash sight glass on waste discharge line, an air relief valve at the height point of the filter and valved line.
HEATERS
1. Shall be equipped with thermometers, 80-240 Degrees F with 2 Degree graduations: automatic temperature limiting device: flow switch: heater bypass valve: all lnfluent/effluent heater piping to be metallic: pressure relief valve to be provided and piped to within 6" of floor. the automatic temperature switch on the pool heater shall be set for a max of 100 degrees. furnish and install thermoters in inlet and outlet piping to heater and downstream in the blended water system.
POOL GUTTER SYSTEM
POOL MAIN DRAINS
1. Shall be designed and installed to meet or exceed National, State & Local codes. VGB Compliant.
POOL SUPPLY & COLLECTOR BOXES
DECK EQUIPMENT (IF APPLICABLE)
CODES, SAFETY & SIGNAGE
1. Provide depth markers and "No Diving" markers on center around pool perimeter as required by local and state codes
2. All new equipment and installations shall conform to the Local Dept. of Fire and Building Services "Swimming Pool Bathing Places" and the regulations of the Indiana
Department of Homeland Security and County Health Department.
3. No carpets will be acceptable in, or around, bathhouse.
4. Depth markers and anchors to be provided by RenoSys Coporation and installed by concrete contractor.
DEPTH MARKERS
1. Provide depth markers, deep and shallow ends and "No Diving" markers around pool perimeter as required by local and state codes
DIVING BOARDS
STARTING PLATFORMS
WATER FEATURES
POOL EQUIPMENT (IF APPLICABLE)
1. All new equipment and installations shall conform to the Local, State & National fire, health & building codes.
POOL LINER
1. All dimensions and locations to be field verified prior to installation.
2. Liner and RecDeck membranes are reflective systems.
3. Racing lane markings to be field located, centered between existing rope anchors or to match existing.
4. Weep holes are part of the membrane system and will be installed in the pool structure as required
LANE & WALL TARGETS
1. Shall be designed and installed to meet or exceed National, State & Local codes. NCAA Compliant.
LIGHTING
MECHANICAL ROOM NOTES (IF APPLICABLE)
1. Verify eqquipment pad height requirements from manufacturer and provide shop drawings to pool engineer.
2. Verify all openings, penetrations, and elevations and provide shop drawings to pool engineer.
3. Coordinate all piping and embedments with affected trades.
4. Refer to structural drawings for future cored openings.
5. Refer to architectrual plans for actual room dimensions and finished floor elvations.
6. Support pipes according the drawing details.
7. All supports, bracing, fasteners and hardware in the surge tank(s) shall be stainless steel.
EQUIPMENT
1. All new equipment and installations shall conform to the Local, State & National fire, health & building codes.
ELECTRICAL NOTES (IF APPLICABLE)
Where Applicable
CODES AND REGULATIONS
1. All work shall conform to the latest edition of the national electrical code, and all federal, state, local and municipal ordinances.
2. This contractor shall obtain and furnish all necessary permits and inspection certificates for all material and labor furnished by him. The cost shall be borne by this contractor.
3. This contractor shall keep his entire portion of the work in repair, without additional cost to the owner, so far as defects in workmanship, apparatus, material, or construction are concerned for one year from date of approval for final payment.
4. All material provided for the project shall be new with manufacturer's warranty and shall be approved for use by Underwriter's Laboratory, Inc. where applicable.
5. Manufacturer's names are used on the drawings to establish type and quality. substitutions may be used when approved by the architect. Approval of equals is the sole right of the architect.
6. All metallic items required to be bonded and grounded as required by the 2014 National Electrical Code.
SCOPE
1. Include all labor, equipment, tools and materials for electrical distribution to perform and complete a timely project.
2. All electrical work including power wiring from panel in building and wiring of other items indicated.
3. Furnish and install new lighting as indicated on drawings.
4. Provide facilities for a new underground electrical service.
5. Any installation costs assessed by utility companies for incoming service installation shall be included in bid and paid for by the electrical contractor.
CONDUIT INSTALLATION
1. All wiring to be installed in conduit in accordance with the 2014 NEC. and so the required conductors may be pulled without injury or strain and properly supported.
2. All conduits to be concealed in building new construction where possible.
3. Exposed conduits are to be run at right angles to building construction.
4. Interior wiring to be installed in metal clad cable (MC) listed for corrosive atmospheres.
5. Branch circuits for pool-associated motors shall be installed in rigid galvanized steel (RGS), intermediate metal conduit (IMC), or metal clad cable (MC) listed for corrosive atmospheres. Connections to these motors shall be made with liquid tight flexible conduit listed for corrosive atmospheres with approved fittings.
6. Conduit on building exterior shall be rigid galvanized steel with weather-tight fittings and devices.
7. Underground conduit below grade shall be rigid schedule 80 PVC with solvent weld fittings. Install code sized ground conductor in all PVC conduit. Penetrations of floor slabs shall be made with rigid galvanized steel.
8. Provide all pull boxes and fittings wherever necessary or shown. All straight conduit runs shall not exceed 100 feet without pull box not over 75 feet for run with one (1) right angle bend and not over 50 feet for run with two (2) right angles.
9. All conduit shall be properly supported in accordance with the 2014 NEC. Conduit shall be hung independently from structure and not from ductwork, ceiling hangers or ceiling support wires.
10. Final connection to light fixtures and equipment shall be made with flexible steel conduit ("greenfield" - 6' maximum length) in dry areas and liquid tight flexible metallic conduit
("sealtite") listed for corrosive atmospheres, in damp or wet areas.
11. All empty conduits are to be provided with pull wires and nylon bushings at both ends.
OUTLET BOXES
1. Secure all boxes from building structure independent of conduit.
2. Flush device boxes in masonry walls shall be designed for the purpose with raised cover.
3. Wiring device boxes for surface conduit work shall be FS series cast boxes.
4. All boxes shall be corrosion resistant.
WIRE AND CABLE
1. Wire and cable shall be as follows:
2. #12 AWF and #10 AWG solid or stranded conductor copper, 600 volt, type THWN, XHHW, or THW (75 degrees c).
3. #8 AWG to and including #500 MCM AWG, stranded conductor, copper, 600 volt, type THWN, XHHW or THW (75 degrees c).
4. Type THHN (90 degrees c.) wire from outlet box to light fixtures.
5. #14 AWG may be used for low voltage control wiring only.
6. Color coding shall be used for all wire and cables in accordance with 2014 NEC coding standards. Control conductors shall be continuously color coded. Ground conductor shall be green.
7. Joints in #10 AWG and smaller wire shall be made with "Scotch Locks" (or equal) and be insulated with Scotch #33 electrical tape.
8. Joints in #8 AWG and larger shall be made with pressure type mechanical connector and insulated with electrical tape to 150% of the insulating value of the conductor.
WARNING: These notes are suggestive only. All Contractors are responsible for ensuring National, State and Local code enforcement on projects.
CL CENTERLINE
SB SUPPLY BOX
CB COLLECTOR BOX
MD MAIN DRAIN
GPM GALLONS PER MINUTE
TYP TYPICAL
EJ EXPANSION JOINT
CJ CONTROL JOINT
FF FINISHED FLOOR ELEVATION
OC ON CENTER
TO TOP OF
BO BOTTOM OF
SWL STATIC WATER LEVEL
OWE OPERATING WATER LEVEL
EW EACH WAY
DIA DIAMETER
SS STAINLESS STEEL
NPS NOMINAL PIPE SIZE
ID INSIDE DIAMETER
OD OUTSIDE DIAMETER
MIN MINIMUM
MAX MAXIMUM
SCH SCHEDULE
WD WATER DEPTH
PL POOL LIFT
SE SLOPED ENTRY
PS POOL STAIRS
UNO UNLESS NOTED OTHERWISE
TOS TOP OF STEEL
AIR RELIEF VALVE
EMERGENCY PUMP OUT
INLET
POOL LIGHT
ROPE HOOK
SYMBOLS & ABBREVIATIONS
REVISION HISTORY
REV DATE DESCRIPTION AUTHOR
OR 11.5.20 ORIGINAL RELEASE BMAYS
1 11.9.20 PLUMBING CHANGES BMAYS
2 11.18.20 SUBMITTAL CHANGES BMAYS
3 1.6.20
REMOVE RECDECK &
#4832 Moore Park, PA
DEMO PLAN | SCALE 1/8" = 1'-0"
SECTION B-B
SCALE 1/8" = 1'-0"
SECTION C-C
SCALE 1/8" = 1'-0"
B
B
C
C
E t h
P l a d i a n a p o l i s
T o l l
F r e o n e
F a x w w w r e n o s y s c o m
SHEET NO
DWG BY
SCALE DATE
DWG TITLE
CHK BY
BMAYS
11/5/2020
M o o r k
P
A
P I O
N E E R
A V E N
U E
P I T T S B U
R G
H
P A
All designs and data included and implied within the contents of these documents are proprietary of ARS. ARS will not be held liable based upon inaccurate, unknown or limited information or conditions provided by the purchaser/owner to create enclosed contents. All submitted drawings, details and data are subject to verification, accuracy and approval by the purchaser/owner. We reserve the right to modify details without notice where conditions require. No documents shall be modified, copied or reproduced without express written consent of ARS. 2004-2020
ARS, Inc, All Rights Reserved.
SHEET SIZE
24 x 36 (inches)
ARCH D
AS SHOWN
FILE LOCATION:
N O
T
F O
R
C O
N S T R U
C T I O
N
D:\CUSTOMERS\#4832 Moore Park, PA\#4832 Moore Park, PA.dwg
11/5/2020
DENOTES REMOVAL
SECTION B-B
NOT TO SCALE
SECTION C-C
NOT TO SCALE
SECTION A-A
NOT TO SCALE
SECTION D-D
NOT TO SCALE
DEMO
SP 2
REVISION HISTORY
REV DATE DESCRIPTION AUTHOR
OR 11.5.20 ORIGINAL RELEASE BMAYS
1 11.9.20 PLUMBING CHANGES BMAYS
2 11.18.20 SUBMITTAL CHANGES BMAYS
3 1.6.20
REMOVE RECDECK &
ADA LIFT
BMAYS
NEW COLLECTOR
BOX LOCATION
1'-4 3/8" MIN
EXISTING
GUTTER
PROFILE
7'-2"
2'-8"
FIELD VERIFY DIMENSIONS
FOR EXISTING MAIN DRAIN
REMOVAL & NEW MAIN DRAIN
INSTALLATION.
NOTES:
FIELD VERIFY ALL DIMENSIONS.
EXISTING STAIRS
CUT, REMOVE & TRENCH TO MECHANICAL
ROOM TO ALLOW FOR NEW PLUMBING.
EXPOSE EXISTING PIPING.
NEW CONCRETE FLOOR
EXISISTING CONCRETE FLOOR
FIBERGLASS REBAR @ 12" O.C.
with 2" CLEAR
166'-0"
NEW 8" CONCRETE FLOOR
WITH FIBERGLASS REBAR @ 12" O.C. EACH WAY
11'-0"
CONNECT NEW SCHEDULE 80 PVC PIPING TO THE
EXISTING RECIRCULATION PIPING OUTSIDE OF THE
MECHANICAL ROOM.
11'-0"
EXISTING
GUTTER
PROFILE
EXISTING
GUTTER
PROFILE
119'-0"34'-0"
13'-0"
13'-0"
19'-0"
8'-0"
10'-0"
8'-0"
19'-0"
188'-0"
6'-0"
11'-0"
11'-0"
DEMO ACCESS
POOL PLAN | SCALE 1/8" = 1'-0"
E t h
P l a d i a n a p o l i s
T o l l
F r e o n e
F a x w w w r e n o s y s c o m
SHEET NO
DWG BY
SCALE DATE
DWG TITLE
CHK BY
BMAYS
11/5/2020
M o o r k
P
A
P I O
N E E R
A V E N
U E
P I T T S B U
R G
H
P A
All designs and data included and implied within the contents of these documents are proprietary of ARS. ARS will not be held liable based upon inaccurate, unknown or limited information or conditions provided by the purchaser/owner to create enclosed contents. All submitted drawings, details and data are subject to verification, accuracy and approval by the purchaser/owner. We reserve the right to modify details without notice where conditions require. No documents shall be modified, copied or reproduced without express written consent of ARS. 2004-2020
ARS, Inc, All Rights Reserved.
SHEET SIZE
24 x 36 (inches)
ARCH D
AS SHOWN
FILE LOCATION:
N O
T
F O
R
C O
N S T R U
C T I O
N
D:\CUSTOMERS\#4832 Moore Park, PA\#4832 Moore Park, PA.dwg
11/5/2020
2'-8"
3 STEP LADDER
4 STEP LADDER
4 STEP LADDER
4 STEP LADDER
4 STEP LADDER
3 STEP LADDER
2 STEP LADDER
166'-0"
2 STEP LADDER
7FT
2IN
7FT
2IN
7FT
2IN
2IN
7FT
2IN
7FT
NO DIVING
8IN
2FT
NO DIVING
8IN
2FT
NO DIVING
8IN
2FT
8IN
NO DIVING
2FT
NO DIVING
0IN
3FT
25'-0"58'-0"53'-0"30'-0"
30'-0" 53'-0" 58'-0" 25'-0"
• LINER & POOL MARKINGS, SEE MEMBRANE DETAILS SHEETS.
• SEE SPEC BOOK FOR LADDER INSTALLATION DETAILS.
• FULL PARTS LIST LOCATED ON SP 4
POOL PLAN
SP 3
33'-0"
Recessed Rope Hook
10'-0"
LOCATED AT
5'-0" BREAKLINE
SEE MEMBRANE DETAILS
28'-0" (5 ROPE HOOKS @ 7'-0")
REPEAT OPPOSITE SIDE
18'-0"25'-0"25'-0"25'-0"25'-0"25'-0"23'-0"
6FT
3IN
5FT
0IN
NO DIVING
4FT 6IN
NO DIVING
4FT
0IN
NO DIVINGNO DIVING
6IN
3FT
NO DIVING
0IN
3FT
18'-0"25'-0"25'-0"25'-0"25'-0"25'-0"23'-0"
NO DIVING
0IN
3FT
NO DIVING
6IN
3FT
NO DIVING
0IN 4FT
NO DIVING
6IN
4FT
NO DIVING
0IN
5FT
3IN
6FT
7'-0" TYP
21'-0" 3 SPACES @ 7'-0"
REPEAT OPPOSITE SIDE
Wall Target
7'-2"
5FT
3IN
NO DIVING
5'-0"
5'-0"
NO DIVING
3IN 5FT
REVISION HISTORY
REV DATE DESCRIPTION AUTHOR
OR 11.5.20 ORIGINAL RELEASE BMAYS
1 11.9.20 PLUMBING CHANGES BMAYS
2 11.18.20 SUBMITTAL CHANGES BMAYS
3 1.6.20
REMOVE RECDECK &
ADA LIFT
BMAYS
2 STEP LADDER
2 STEP LADDER
33'-0"
RRH
SP 5
GUTTER ANCHOR & GUTTER PLAN | SCALE 1/16" = 1'-0"
#4832 Moore Park, PA
PLUMBING PLAN | SCALE 1/16" = 1'-0"
DETAIL F
SCALE 1/8" = 1'-0"
DESCRIPTIONPART NUMBERQTY
SR Smith #10112 23in 3-Step Ladder with .065 tubing3 STEP LADDER2
SR Smith #10115 23in 4-Step Ladder with .065 tubing.4 STEP LADDER4
SR Smith #10109 23in 2-Step Ladder with .065 tubing2 STEP LADDER4
EP-100F Escutcheon 304 SS for 1.90" OD TubingESCUTCHEON20
2ft Depth Marker with 6" high numbers2FT4
8in Depth Marker with 6" high numbers8IN4
No Diving Depth Marker with 6" high numbersNO DIVING17
0in Depth Markers with 6" high numbers.0IN7
5ft Depth Marker with 6" numbers.
5FT4
7ft Depth Marker with 6" high numbers.7FT5
3ft Depth Marker with 6" high numbers3FT5
6in Depth Marker with 6" numbers.6IN4
4ft Depth Marker with 6" high numbers.4FT4
2in Depth Marker with 6" high numbers.2IN5
6ft Depth Marker with 6" high numbers.6FT2
3in Depth Marker - 6"x6"x1/4" Ceramic Tile with 4" Numbers for Deck3IN4
AS-100B Bronze Anchor for 1.90 OD Concete Deck AnchorDECK ANCHOR20
6in SS Supply Box6in SS SUPPLY1
3/8" Drilled Holes @ 2'-7" O.C.INLET187
8in Stainless Steel Collector Box8in SS COLLECTOR BOX2
DuraTech Roll-Out Stainless Steel Gutter System 11" H x 10" W w/ 6in Deck to Water @ 10'-0" sections. 304L 12GA SS #4 Finish.DTRO 11-10-6 Gutter51
304L SS Gutter Anchor Assembly with SS all-thread and zinc drop in anchor.Gutter Anchor Assembly143
18x36-10 Main Drain18x36-10 Main Drain2
Stainless Steel Recessed Rope HookRecessed Rope Hook10
Wall Targets SEE PVC LINER MEMBRANE DETAILSWall Target8
#00340 Astral Pool 2" Floor Inlet2" Floor Inlet28
RECIRCULATION PUMP1
DTRO 11-10-6 Surge Weir @ 50GPM50 GPM Surge Weir22
F
SP6
E t h
P l a d i a n a p o l i s
T o l l
F r e o n e
F a x w w w r e n o s y s c o m
SHEET NO
DWG BY
SCALE DATE
DWG TITLE
CHK BY
BMAYS
11/5/2020
M o o r k
P
A
P I O
N E E R
A V E N
U E
P I T T S B U
R G
H
P A
All designs and data included and implied within the contents of these documents are proprietary of ARS. ARS will not be held liable based upon inaccurate, unknown or limited information or conditions provided by the purchaser/owner to create enclosed contents. All submitted drawings, details and data are subject to verification, accuracy and approval by the purchaser/owner. We reserve the right to modify details without notice where conditions require. No documents shall be modified, copied or reproduced without express written consent of ARS. 2004-2020
ARS, Inc, All Rights Reserved.
SHEET SIZE
24 x 36 (inches)
ARCH D
AS SHOWN
FILE LOCATION:
N O
T
F O
R
C O
N S T R U
C T I O
N
D:\CUSTOMERS\#4832 Moore Park, PA\#4832 Moore Park, PA.dwg
11/5/2020
Ø
C O
L L E C T O
R
Ø
C
O
L
L
E
C
T
O
R
Ø
S
U
P
P
L
Y
Ø
F
L
O
R
L
E
T
M
A
D
R
A
I
N
C
L
L
E
C
T
O
R
Ø6"
GUTTER PLAN
SP 4
POOL LENGTH & WIDTH - 90'-0" x 166'-0"
SURFACE AREA - 14,740 SQFT
TURN OVER RATE - 8 HRS (480 MINS)
FLOW RATE - 1,106 GPM
SYSTEM TYPE - SUCTION FEED
DEPTHS - 2'-8" - 7'-2"
INLETS - 187 INLETS @ 5.91 GPM PER INLET @ 17.19 FT/SEC & SPACED @ 2'-7" O.C.
SURGE WEIRS - N/A
BATHER LOAD - N/A
REVISION HISTORY
REV DATE DESCRIPTION AUTHOR
OR 11.5.20 ORIGINAL RELEASE BMAYS
1 11.9.20 PLUMBING CHANGES BMAYS
2 11.18.20 SUBMITTAL CHANGES BMAYS
3 1.6.20
REMOVE RECDECK &
ADA LIFT
GUTTER CALCULATION DATA
TURN OVER RATE - 8 HRS (480 MINS)
FLOW RATE - 1,106 GPM
COLLECTOR BOXES -
TROUGH WIDTH - 12
DMAX - 9.5
Ud - 6.21 (less than DMAX within 5%)
8in SS COLLECTOR BOX
18x36-10 Main Drain
8in SS COLLECTOR BOX
6in SS SUPPLY
166'-0"
2'-7"( O.C.) GUTTER INLETS TYP
AROUND PERIMETER OF POOL.
166'-0"
T Y P
10'-0" TYP
2'-8" 2'-8"
T Y P
10'-0" TYP
45°
45°
16'-0"
144'-0" (36 SPACES @ 4'-0" MAX)
REPEAT OTHER SIDE
11106
SP 5
11106
SP 5
INLET
P
P
GOC
SP 5
6"
S P A C E
M
A X
R E P E A T
O
T H
E R
S I D
E
Gutter Anchor Assembly
10MD
SP 5
Ø2" TYP
FLOOR INLET
7'-2"
7'-2"
37'-6"
7'-0"
91'-0" ( 13 SPACES @ 7'-0") 37'-6"
Ø2" SCHED 80
PVC PIPE TYP
S P A C E
R E P E A T
O
T H
E R
S I D
E
8CB
SP 5
6SB
SP 5
20'-9"
20'-9" 124'-6" (6 SPACES @ 20'-9")
REPEAT OTHER SIDE
50 GPM Surge Weir
10MD
SP 5
CAP
OFF
Ø2”
DTRO 11-10-6 Gutter
DETAIL VIEW | SCALE 6" = 1'-0"
Gutter Anchor Assembly
SIDE VIEW | SCALE 1 1/2" = 1'-0"
Gutter Inside Corner
TOP VIEW | SCALE 1" = 1'-0"
Gutter Outside Corner
TOP VIEW | SCALE 1" = 1'-0"
6in Skirt
FOLDED SIDE VIEW | SCALE 6" = 1'-0"
6in SS SUPPLY
6in SS Supply Box w/ DTRO 11-10-6 Gutter
SIDE VIEW | SCALE 1" = 1'-0"
NOTE: ENCASE IN CONCRETE AFTER INSTALLATION
8in SS COLLECTOR BOX
SIDE VIEW | SCALE 1" = 1'-0"
SHOWN w/ DTRO 11-10-6 GUTTER
NOTE: ENCASE IN CONCRETE AFTER INSTALLATION
DESCRIPTIONPART NUMBER
2 3/8" Dia SS Recessed Rope Hook AssemblyRECESSED ROPE HOOK
DESCRIPTIONPART NUMBER
SS Gutter Anchor Assembly with zinc drop in anchor. Placed 4'-0" on-center max.Gutter Anchor Assembly
DESCRIPTIONPART NUMBER
12GA 304L SS #4 - DTRO 11-10-6 TroughTrough
12GA 304L SS #4 - DTRO 11-10-6 Supply BackSupply Back
10in wide, integral slip-resistant, impact resistant PVC resin Interlock Grate - White10" INTERLOCK GRATING
12GA 304L SS #4 Finish - 6in Gutter Skirt6in Skirt
12GA 304L SS 2B - DTRO 11-10-6 Grating Support AGrating Support A
SS L 1" x 1" x 1/8" x 20'-0" - DTRO 11-10-6 Grating Support BGrating Support B
304L SS Gutter Anchor Assembly with SS all-thread and zinc drop in anchor.Gutter Anchor Assembly
Standard SS Drive Anchor .25in X 2in (Zamac Hammer-Screw Mushroom Head)1/4" X 2" SS Drive Anchor
2 3/8" Dia SS Recessed Rope Hook AssemblyRECESSED ROPE HOOK
Non-shrink grout. By others.Grout (by others)
DTRO 11-10-6 Surge Weir @ 50GPM50 GPM Surge Weir
E t h
P l a d i a n a p o l i s
T o l l
F r e o n e
F a x w w w r e n o s y s c o m
SHEET NO
DWG BY
SCALE DATE
DWG TITLE
CHK BY
BMAYS
11/5/2020
M o o r k
P
A
P I O
N E E R
A V E N
U E
P I T T S B U
R G
H
P A
All designs and data included and implied within the contents of these documents are proprietary of ARS. ARS will not be held liable based upon inaccurate, unknown or limited information or conditions provided by the purchaser/owner to create enclosed contents. All submitted drawings, details and data are subject to verification, accuracy and approval by the purchaser/owner. We reserve the right to modify details without notice where conditions require. No documents shall be modified, copied or reproduced without express written consent of ARS. 2004-2020
ARS, Inc, All Rights Reserved.
SHEET SIZE
24 x 36 (inches)
ARCH D
AS SHOWN
FILE LOCATION:
N O
T
F O
R
C O
N S T R U
C T I O
N
D:\CUSTOMERS\#4832 Moore Park, PA\#4832 Moore Park, PA.dwg
11/5/2020
PVC Inter-Locking grating thread cutting screw
SC750 - S/S
x 1"
Stainless steel anchor clip
10 - 12 Bantam anchor
(Use in concrete gutter only)
"Inter-Lock grating"
Side View
800-783-7005 www.renosys.com
Top View
DENOTES SLIP-RESISTANT DIMPLING
50 GPM SURGE WEIR (22 REQ’D)
NOT TO SCALE
10" INTERLOCK GRATING - WHITE
DETAIL | NOT TO SCALE
11106
SP 5
10ILG
SP 5
GIC
SP 5
GOC
SP 5
DTRO 11-10-6 GUTTER &
ACCESSORIES DETAILS
SP 5
Technical Data:
Width of I-bar top 5/8"
Gap between bars 3/8"
Open area per sqft 40%
Grating height 1"
Deflection 300lbs @ 18" 3/16"
Surface texture Slip-resistant
Warranty 10 Years
Design & Product Information:
DuraTech Inter-locking PVC grating is formulated with maximum U.V. inhibitors addes to 100% virgin exterior grade impact resistant PVC resin. Integral slip-resistance is embossed into the grating top surface as a standard safety feature. White is the standard
DuraTech color. Custom colors are available upon request.
Installation
Locate grating on support ledge, slide the stainless steel anchor clip into place as shown. Anchor assemblies should be installed max 15" on center, staggering from one side of grating to the other.
It is necessary to support all grating ends for proper safety requirements.
Concrete Gutter - Mark hole location and drill a 1/4" Dia. hole. Insert bantam sleeve into hole, replace anchor clip and fasten through the anchor clip and secure into the bantam anchor.
S/S Gutter - Mark hole location and drill a 5/32" Dia. hole into support angle. Replace anchor clip and fasten through the anchor clip and secure into the support angle. Do not over tighten.
AS NOTED
GUTTER CALCULATION DATA
TURN OVER RATE - 8 HRS (480 MINS)
FLOW RATE - 1,106 GPM
TROUGH WIDTH - 12
DMAX - 9.5
Ud - 6.21 (less than DMAX within 5%)
* SEE GUTTER PROFILE
2 3/8"
1 1/2" TYP ALL
GUTTER HANDHOLD
FINISHED DECK
CONFIRM ROPE HOOK DIAMETER
PRIOR TO DRILLING GUTTER FACE.
RRH
SP 5
RECESSED ROPE HOOK
NOT TO SCALE
TOP VIEW
8CB
SP 5
6SB
SP 5
D
M A X
6 3/16" (TROUGH WIDTH)
Grating Support B
Grating Support B
Grating Support A
Supply Back
Trough
0 1/2"
1"
2"
1'-1 3/8"
10 3/8"
0 3/16"
0 3/16"
10ILG
SP 5
M
I N
INLET AREA
3" 6"
3" MIN
1'-4 3/8"
FINISHED DECK
Gutter Anchor Assembly
1'-2"
10" INTERLOCK GRATING
RECESSED ROPE HOOK
POOL SIDE
Gutter Anchor Assembly
6" TYP
GA
SP 4
6" TYP
Gutter Anchor Assembly
GA
SP 5
DENOTES CENTERLINE
REVISION HISTORY
REV DATE DESCRIPTION AUTHOR
OR 11.5.20 ORIGINAL RELEASE BMAYS
1 11.9.20 PLUMBING CHANGES BMAYS
2 11.18.20 SUBMITTAL CHANGES BMAYS
3 1.6.20
REMOVE RECDECK &
ADA LIFT
BMAYS
6in Skirt
Grout (by others)
1 1/16"
1/4" X 2" SS Drive Anchor
GA
SP 5
SKIRT
SP 5
RRH
SP 5
SKIRT
SP 5
WATER
FLOW
GUTTER PROFILE
(POOL SIDE)
6in SS Sched 10 Pipe
SUPPLY BOX
FINISHED DECK
1'-0 11/16"
2'-2 1/16"
6" SS SUPPLY BOX - (1) REQ
PIPE SIZE PIPE AREA
GPM@8FT/SEC
BOX WIDTH
6 IN
26.07 SQ IN
650 GPM 12 IN
6"
GA
SP 5
FINISHED DECK
GUTTER PROFILE
(POOL SIDE)
8in SS Sched 10 Pipe
1'-2 5/8"
2'-0 5/8"
8" COLLECTOR BOX - (2) REQ.
PIPE SIZE PIPE AREA
GPM@ 6FT/SEC SUCTION
BOX WIDTH
8 IN
45.66 SQ IN
854 GPM 16 IN
CLOSED CELL FOAM FLOAT
1/4 x 2” SLOTS IN FACE
OF GUTTER SYSTEM
STAINLESS STEEL
SUPPORT ROD
PVC FLOW STOP
BOTTOM PLATE
1/2” x 16” FLOW SLOT
WEIR
SP 5
WATER LEVEL
18x36-10 Main Drain
SIDE VIEW | SCALE 1 1/2" = 1'-0"
18x36-10 Main Drain
TOP VIEW | SCALE 1 1/2" = 1'-0"
18x36-10 Main Drain
OUTLET VIEW | SCALE 1 1/2" = 1'-0"
18x36-10 Main Drain
ISOMETRIC VIEW | SCALE 1 1/2" = 1'-0"
DETAIL A
SCALE 3" = 1'-0"
18x36-10 Main Drain
ISOMETRIC VIEW | SCALE 3/4" = 1'-0"
DETAIL F
TOP VIEW | SCALE 1" = 1'-0"
A
E t h
P l a d i a n a p o l i s
T o l l
F r e o n e
F a x w w w r e n o s y s c o m
SHEET NO
DWG BY
SCALE DATE
DWG TITLE
CHK BY
BMAYS
11/5/2020
M o o r k
P
A
P I O
N E E R
A V E N
U E
P I T T S B U
R G
H
P A
All designs and data included and implied within the contents of these documents are proprietary of ARS. ARS will not be held liable based upon inaccurate, unknown or limited information or conditions provided by the purchaser/owner to create enclosed contents. All submitted drawings, details and data are subject to verification, accuracy and approval by the purchaser/owner. We reserve the right to modify details without notice where conditions require. No documents shall be modified, copied or reproduced without express written consent of ARS. 2004-2020
ARS, Inc, All Rights Reserved.
SHEET SIZE
24 x 36 (inches)
ARCH D
AS SHOWN
FILE LOCATION:
N O
T
F O
R
C O
N S T R U
C T I O
N
D:\CUSTOMERS\#4832 Moore Park, PA\#4832 Moore Park, PA.dwg
11/5/2020
18x36-10 Main Drain
(GRAVITY FEED SYSTEM)
SP 6
10MD
SP 6
10in SS Sched 10 Pipe
NON-COMPACT GRANULAR FILL
Hydrostatic Relief Valve
2in Full Coupling
Collector Tube
M
I N
3'-5 13/16"
3'-9 13/16"
NO-LEAK FLANGE
BOTTOM OF
MAIN DRAIN BOX
M
A Y
V A R Y
18"x36"-10" MAIN DRAIN DATA
PIPE SIZE
PIPE AREA: SQ IN
PIPE GPM @ 3FT/SEC GRAVITY
MAIN DRAIN BOX WIDTH
10 IN
71.84 SQ IN
672 GPM APPROX. 18" X 36"
3'-1 3/8"
REVISION HISTORY
REV DATE DESCRIPTION AUTHOR
OR 11.5.20 ORIGINAL RELEASE BMAYS
1 11.9.20 PLUMBING CHANGES BMAYS
2 11.18.20 SUBMITTAL CHANGES BMAYS
3 1.6.20
REMOVE RECDECK &
ADA LIFT
BMAYS
6”
ADAPTOR
Ø2” SS FULL COUPLING
PIPE NIPPLE
Ø2” BALL VALVE
Ø2” PVC PIPE
FLANGES NOT
SHOWN FOR CLARITY
E t h
P l a d i a n a p o l i s
T o l l
F r e o n e
F a x w w w r e n o s y s c o m
SHEET NO
DWG BY
SCALE DATE
DWG TITLE
CHK BY
BMAYS
11/5/2020
M o o r k
P
A
P I O
N E E R
A V E N
U E
P I T T S B U
R G
H
P A
All designs and data included and implied within the contents of these documents are proprietary of ARS. ARS will not be held liable based upon inaccurate, unknown or limited information or conditions provided by the purchaser/owner to create enclosed contents. All submitted drawings, details and data are subject to verification, accuracy and approval by the purchaser/owner. We reserve the right to modify details without notice where conditions require. No documents shall be modified, copied or reproduced without express written consent of ARS. 2004-2020
ARS, Inc, All Rights Reserved.
SHEET SIZE
24 x 36 (inches)
ARCH D
AS SHOWN
FILE LOCATION:
N O
T
F O
R
C O
N S T R U
C T I O
N
D:\CUSTOMERS\#4832 Moore Park, PA\#4832 Moore Park, PA.dwg
11/5/2020
SP 7
POOL GROUNDING &
BONDING DETAILS
REVISION HISTORY
REV DATE DESCRIPTION AUTHOR
OR 11.5.20 ORIGINAL RELEASE BMAYS
1 11.9.20 PLUMBING CHANGES BMAYS
2 11.18.20 SUBMITTAL CHANGES BMAYS
3 1.6.20
REMOVE RECDECK &
E t h
P l a d i a n a p o l i s
T o l l
F r e o n e
F a x w w w r e n o s y s c o m
SHEET NO
DWG BY
SCALE DATE
DWG TITLE
CHK BY
BMAYS
11/5/2020
M o o r k
P
A
P I O
N E E R
A V E N
U E
P I T T S B U
R G
H
P A
All designs and data included and implied within the contents of these documents are proprietary of ARS. ARS will not be held liable based upon inaccurate, unknown or limited information or conditions provided by the purchaser/owner to create enclosed contents. All submitted drawings, details and data are subject to verification, accuracy and approval by the purchaser/owner. We reserve the right to modify details without notice where conditions require. No documents shall be modified, copied or reproduced without express written consent of ARS. 2004-2020
ARS, Inc, All Rights Reserved.
SHEET SIZE
24 x 36 (inches)
ARCH D
AS SHOWN
FILE LOCATION:
N O
T
F O
R
C O
N S T R U
C T I O
N
D:\CUSTOMERS\#4832 Moore Park, PA\#4832 Moore Park, PA.dwg
11/5/2020
SP 8
PVC LINER MEMBRANE
TYPCIAL DETAILS
L1
SP 8
L2
SP 8
L3
SP 8
L4
SP 8
L5
SP 8
L6
SP 8
L7
SP 8
L8
SP 8
L9
SP 8
L10
SP 8
L14
SP 8
L13
SP 8
L11
SP 8
REVISION HISTORY
REV DATE DESCRIPTION AUTHOR
OR 11.5.20 ORIGINAL RELEASE BMAYS
1 11.9.20 PLUMBING CHANGES BMAYS
2 11.18.20 SUBMITTAL CHANGES BMAYS
3 1.6.20
REMOVE RECDECK &
ADA LIFT
BMAYS