Summary: Statement of Work - Chancery 3003 Integrated Window Blinds Retrofit

This is a Statement of Work (SOW) for the maintenance and motor retrofit of 104 integrated Venetian blinds located in the US Embassy office building in Bern, Switzerland. The project involves refurbishing Warema Type 1.16/25/35.07 (24v motor) blinds integrated within WICONA WICLINE aluminum composite windows to restore 100% motorized functionality while preserving the thermal, acoustic, and aesthetic integrity of the window units. The contracting agency is the Department of State US Embassy Bern (Solicitation Number: PR16077115).

The contractor must provide a comprehensive turnkey solution with all-inclusive, fixed pricing that covers labor (all technician, electrician, and logistical personnel hours), materials (motors, cables, lift tapes, ladder cords, and hardware), equipment (specialized tools, window opening devices, safety gear), transportation (travel, vehicle, and freight costs), and fees (disposal, administrative costs, permits, and insurance). Work scope includes furniture management and surface protection; inspection and lubrication of WICONA hardware and gaskets; replacement of failed motors with compatible alternatives and worn mechanical components; calibration and three-cycle testing of all 104 units; integration into the building KNX control system; and Swiss-compliant waste disposal with official certificates. All electrical work must be performed by Swiss-certified electricians with strict Lockout/Tagout procedures and zero-energy verification before any wiring contact. Final deliverables include internal cleaning, a comprehensive service report listing all units and motor models used, and evidence of proper disposal through authorized Swiss recycling collection points.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of Work (SOW): Maintenance & Motor Retrofit (Final Version) Project: Refurbishment of 104 Integrated Venetian Blinds Location: Office Building – Bern, Switzerland System Type: Warema Type 1.16/25/35.07 (24v motor) inside WICONA WICLINE Aluminum Composite Windows

1. Project Objective The contractor shall provide a turnkey solution for the inspection, repair, and motor retrofit of 104 integrated venetian blinds. The objective is to restore 100% motorized functionality while maintaining the thermal, acoustic, and aesthetic integrity of the WICONA window units.

2. Comprehensive Pricing & Scope The offer submitted by the contractor must be all-inclusive. No additional costs will be entertained after the contract award. The bid price shall include:

· Labor: All technician, electrician, and logistical personnel hours.

· Materials: All motors, cables, lift tapes, ladder cords, and hardware components.

· Equipment: All tools, specialized window opening devices, safety gear, and cleaning supplies.

· Transportation: All travel costs, vehicle expenses, and shipping/freight for parts.

· Fees: Disposal fees, administrative costs, and any required permits or insurance.

3. Logistics & Site Management

· Furniture Management: Contractor shall move office furniture and equipment as required to gain unobstructed access to the windows. All items must be protected and returned to their original positions upon completion.

· Surface Protection: Provide appropriate floor and wall protection during the transit of tools and components.

4. Health, Safety & Electrical Standards

· Qualified Personnel: Only certified electricians (per Swiss regulations) may perform electrical work.

· Lockout/Tagout (LOTO): A strict LOTO procedure must be implemented. Hazardous energy sources must be isolated, locked, and tagged before work commences.

· Verification: Zero-energy state must be verified via testing before physical contact with wiring.

· Controls: Each motor control shall be integrated into the Building KNX system.

5. Technical Execution: WICONA & Warema Systems

· Sash Access: Open the internal "sandwich" sash of the WICONA windows using the integrated latches.

· Hardware Maintenance: Inspect and lubricate all WICONA latching mechanisms and concealed hardware.

· Gasket Inspection: Verify the condition of internal gaskets. Damaged seals must be reported or replaced to ensure the cavity remains dust and moisture-free.

· Blind Retrofit:

· Identify and replace failed motors with compatible high-quality alternatives (e.g., Somfy, Elero) that fit the existing Warema headrails.

· Replace worn lift tapes and ladder cords as necessary to ensure smooth mechanical operation.

6. Commissioning & Integration

· Calibration: Set electronic end-limits (upper/lower) for every unit.

· Testing: Perform three full cycles (Up/Down/Tilt) per window to ensure defect-free operation.

· System Integration: Ensure new motors are integrated into the existing building control or radio systems.

7. Waste Disposal (Swiss Compliance)

· Swiss Codes: Disposal must comply with vREG/ORDEA (Electrical Waste) and VeVA/OMW (Waste Movements).

· Recycling: Deliver old motors and aluminum scrap to authorized SENS eRecycling or Swico collection points.

· Evidence: Contractor shall provide official disposal certificates (Entsorgungsnachweis).

8. Cleaning & Handover

· Internal Cleaning: Clean internal glass surfaces and aluminum slats before closing the sash.

· Final Report: Provide a list of all units serviced, including specific motor model numbers used.