Schneider Electric_MasterPact-NW_48364.pdf

PDF 223 KB Posted

Attached to
JOFOC for switchgear system spare parts, PR15278420
Solicitation number
PR15278420
Issued by

About this file

This document is a product datasheet for the Schneider Electric Micrologic 6.0 P trip unit, a control unit designed for MasterPact NW circuit breakers in electrical distribution applications. The trip unit is an electronic device compatible with MasterPact NW08...63 drawout circuit breakers, offering multiple protection functions including overload, short-circuit, instantaneous, and ground-fault protection with adjustable settings across 9 different configurations.

Key technical specifications include a trip unit rating from 800A to 6300A at 50°C, operation at 50/60 Hz AC networks, and a wide range of protection adjustment capabilities. The device features a digital display, power meter functionality, and zone selective interlocking. Environmental characteristics include an operating temperature range of -25 to 70°C, and the product is compliant with EU RoHS regulations with some exemptions. Schneider Electric emphasizes sustainability, noting a carbon footprint of 40 kg CO2 equivalent and packaging made from recycled cardboard without single-use plastics. The product comes with an 18-month warranty and requires specific waste disposal procedures in the European Union.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Micrologic 6.0 P trip unit - LSIG - for NW 08..63 drawout 48364

Main Range MasterPact

Range of product MasterPact NW

Product or component type Control unit

Trip unit name MicroLogic 6.0 P

Trip unit technology Electronic

Range compatibility Masterpact NW08...40 Masterpact NW40b...63 Masterpact NW H10 Masterpact NW H2 corrosion protection

Device application Distribution

Number of poles 3P 4P

Protected poles description 4t 3t 3t + N/2

Trip unit protection functions Selective + earth-fault protection

Protection type for overload protection (long time) for short time short-circuit protection for instantaneous short-circuit protection for earth fault

Trip unit rating 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C 6300 A at 50 °C

Network type AC

Network frequency 50/60 Hz

Circuit breaker mounting mode Drawout

Complementary Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

0.4...1 x In

Long-time protection delay adjustment type tr

Adjustable 9 settings

[tr] long-time protection delay adjustment range

0.7…16.6 s at 7.2 x Ir 0.7…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir

Product datasheet Specifications

17 Apr 2025 1

Excluding VAT, FCA Jabal Ali & are subject to change – check with your local distributor.

D is cl ai m er

: T hi s do cu m en ta tio n is n ot in te nd ed a s a su bs tit ut e fo r a nd is n ot to b e us ed fo r d et er m in in g su ita bi lit y or re lia bi lit y of th es e pr od uc ts fo r s pe ci fic u se r a pp lic at io ns

Thermal memory 20 mn

Short-time protection pick-up adjustment type Isd

Adjustable 9 settings

[Isd] Short-time protection pick-up adjustment range

1.5...10 x Ir

Short-time protection delay adjustment type tsd

Adjustable

[tsd] Short-time protection delay adjustment range

0…0.4 s I²t=off 0.1…0.4 s I²t=on

Instantaneous protection pick-up adjustment type Ii

Adjustable 9 settings

[Ii] instantaneous protection pick-up adjustment range

Off 2...15 x In

Ground-fault protection pick-up adjustment type Ig

Adjustable 9 settings

[Ig] ground-fault protection pick-up adjustment range

0.2...1 x In for 400 A < In < 1250 A 0.3...1 x In for In <= 400 A 500...1200 A for In >= 1250 A

Ground-fault protection time delay adjustment type tg

Adjustable

[tg] ground-fault protection time delay adjustment range

0…0.4 s I²t=off 0.1…0.4 s I²t=on

Earth-leakage protection Without

Zone selective interlocking ZSI With

Local signalling 3 LEDs (red) for electrical fault 1 LED (red) for internal error

Display type Digital display

Type of measurement Power meter

Communication of data Measurement readout Protection and alarm settings Maintenance indicators

Environment Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-40…85 °C

Packing Units Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 6.7 cm

Package 1 Width 7.9 cm

Package 1 Length 21.5 cm

Package 1 Weight 450.0 g

Contractual warranty Warranty 18 months

2 17 Apr 2025

Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data explained

How we assess product sustainability

Environmental footprint

Carbon footprint (kg.eq.CO2 per CR, Total Life cycle) 40

Environmental Disclosure Product Environmental Profile

Use Better

Materials and Substances

Recycled metal content at CR level 0

Packaging made with recycled cardboard Yes

Packaging without single use plastic Yes

EU RoHS Directive Compliant with Exemptions

SCIP Number 6ac3934d-9e20-40a3-adef-08cec90e29e2

REACh Regulation REACh Declaration

Halogen content performance Product contains halogen above thresholds

PVC free No

Use Again

Repack and remanufacture

Circularity Profile End of Life Information

Removable battery User replaceable

Take-back No

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

17 Apr 2025 3 https://www.se.com/ae/en/about-us/sustainability/environmental-data-program/ https://www.se.com/ae/en/about-us/sustainability/environmental-data-program/ https://www.se.com/ae/en/about-us/sustainability/environmental-data-program/ https://www.se.com/ae/en/about-us/sustainability/environmental-data-program/ https://www.se.com/ae/en/about-us/sustainability/environmental-data-program/ https://www.se.com/ae/en/about-us/sustainability/environmental-data-program/ https://www.se.com/ae/en/about-us/sustainability/guide-to-product-sustainability.jsp https://www.se.com/ae/en/about-us/sustainability/guide-to-product-sustainability.jsp https://www.se.com/ae/en/about-us/sustainability/guide-to-product-sustainability.jsp https://www.se.com/ae/en/about-us/sustainability/guide-to-product-sustainability.jsp https://www.se.com/ae/en/about-us/sustainability/guide-to-product-sustainability.jsp https://www.se.com/ae/en/about-us/sustainability/guide-to-product-sustainability.jsp https://download.schneider-electric.com/files?p_enDocType=Environmental+Disclosure&p_Doc_Ref=ENVPEP2408039EN https://download.schneider-electric.com/files?p_enDocType=Environmental+Disclosure&p_Doc_Ref=ENVPEP2408039EN https://download.schneider-electric.com/files?p_Doc_Ref=48364_ROHS_DECLARATION&p_FileName=48364_ROHS_DECLARATION_AE_en-GB.pdf https://download.schneider-electric.com/files?p_Doc_Ref=48364_ROHS_DECLARATION&p_FileName=48364_ROHS_DECLARATION_AE_en-GB.pdf https://download.schneider-electric.com/files?p_enDocType=Declaration+of+Conformity+%28Sustainability%29&p_Doc_Ref=48364_REACH_DECLARATION&p_FileName=48364_REACH_DECLARATION_AE_en-GB.pdf https://download.schneider-electric.com/files?p_enDocType=Declaration+of+Conformity+%28Sustainability%29&p_Doc_Ref=48364_REACH_DECLARATION&p_FileName=48364_REACH_DECLARATION_AE_en-GB.pdf https://download.schneider-electric.com/files?p_enDocType=Circularity+Profile&p_Doc_Ref=ENVEOLI2408039EN https://download.schneider-electric.com/files?p_enDocType=Circularity+Profile&p_Doc_Ref=ENVEOLI2408039EN

Product datasheet