Schneider Electric_MasterPact-NW_48364.pdf
PDF 223 KB Posted
- Solicitation number
- PR15278420
- Issued by
-
Department of State US Embassy Abu Dhabi
About this file
This document is a product datasheet for the Schneider Electric Micrologic 6.0 P trip unit, a control unit designed for MasterPact NW circuit breakers in electrical distribution applications. The trip unit is an electronic device compatible with MasterPact NW08...63 drawout circuit breakers, offering multiple protection functions including overload, short-circuit, instantaneous, and ground-fault protection with adjustable settings across 9 different configurations.
Key technical specifications include a trip unit rating from 800A to 6300A at 50°C, operation at 50/60 Hz AC networks, and a wide range of protection adjustment capabilities. The device features a digital display, power meter functionality, and zone selective interlocking. Environmental characteristics include an operating temperature range of -25 to 70°C, and the product is compliant with EU RoHS regulations with some exemptions. Schneider Electric emphasizes sustainability, noting a carbon footprint of 40 kg CO2 equivalent and packaging made from recycled cardboard without single-use plastics. The product comes with an 18-month warranty and requires specific waste disposal procedures in the European Union.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Micrologic 6.0 P trip unit - LSIG - for NW 08..63 drawout 48364
Main Range MasterPact
Range of product MasterPact NW
Product or component type Control unit
Trip unit name MicroLogic 6.0 P
Trip unit technology Electronic
Range compatibility Masterpact NW08...40 Masterpact NW40b...63 Masterpact NW H10 Masterpact NW H2 corrosion protection
Device application Distribution
Number of poles 3P 4P
Protected poles description 4t 3t 3t + N/2
Trip unit protection functions Selective + earth-fault protection
Protection type for overload protection (long time) for short time short-circuit protection for instantaneous short-circuit protection for earth fault
Trip unit rating 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C 6300 A at 50 °C
Network type AC
Network frequency 50/60 Hz
Circuit breaker mounting mode Drawout
Complementary Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
0.4...1 x In
Long-time protection delay adjustment type tr
Adjustable 9 settings
[tr] long-time protection delay adjustment range
0.7…16.6 s at 7.2 x Ir 0.7…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir
Product datasheet Specifications
17 Apr 2025 1
Excluding VAT, FCA Jabal Ali & are subject to change – check with your local distributor.
D is cl ai m er
: T hi s do cu m en ta tio n is n ot in te nd ed a s a su bs tit ut e fo r a nd is n ot to b e us ed fo r d et er m in in g su ita bi lit y or re lia bi lit y of th es e pr od uc ts fo r s pe ci fic u se r a pp lic at io ns
Thermal memory 20 mn
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
1.5...10 x Ir
Short-time protection delay adjustment type tsd
Adjustable
[tsd] Short-time protection delay adjustment range
0…0.4 s I²t=off 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type Ii
Adjustable 9 settings
[Ii] instantaneous protection pick-up adjustment range
Off 2...15 x In
Ground-fault protection pick-up adjustment type Ig
Adjustable 9 settings
[Ig] ground-fault protection pick-up adjustment range
0.2...1 x In for 400 A < In < 1250 A 0.3...1 x In for In <= 400 A 500...1200 A for In >= 1250 A
Ground-fault protection time delay adjustment type tg
Adjustable
[tg] ground-fault protection time delay adjustment range
0…0.4 s I²t=off 0.1…0.4 s I²t=on
Earth-leakage protection Without
Zone selective interlocking ZSI With
Local signalling 3 LEDs (red) for electrical fault 1 LED (red) for internal error
Display type Digital display
Type of measurement Power meter
Communication of data Measurement readout Protection and alarm settings Maintenance indicators
Environment Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Packing Units Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 6.7 cm
Package 1 Width 7.9 cm
Package 1 Length 21.5 cm
Package 1 Weight 450.0 g
Contractual warranty Warranty 18 months
2 17 Apr 2025
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental Data explained
How we assess product sustainability
Environmental footprint
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle) 40
Environmental Disclosure Product Environmental Profile
Use Better
Materials and Substances
Recycled metal content at CR level 0
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
EU RoHS Directive Compliant with Exemptions
SCIP Number 6ac3934d-9e20-40a3-adef-08cec90e29e2
REACh Regulation REACh Declaration
Halogen content performance Product contains halogen above thresholds
PVC free No
Use Again
Repack and remanufacture
Circularity Profile End of Life Information
Removable battery User replaceable
Take-back No
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
17 Apr 2025 3 https://www.se.com/ae/en/about-us/sustainability/environmental-data-program/ https://www.se.com/ae/en/about-us/sustainability/environmental-data-program/ https://www.se.com/ae/en/about-us/sustainability/environmental-data-program/ https://www.se.com/ae/en/about-us/sustainability/environmental-data-program/ https://www.se.com/ae/en/about-us/sustainability/environmental-data-program/ https://www.se.com/ae/en/about-us/sustainability/environmental-data-program/ https://www.se.com/ae/en/about-us/sustainability/guide-to-product-sustainability.jsp https://www.se.com/ae/en/about-us/sustainability/guide-to-product-sustainability.jsp https://www.se.com/ae/en/about-us/sustainability/guide-to-product-sustainability.jsp https://www.se.com/ae/en/about-us/sustainability/guide-to-product-sustainability.jsp https://www.se.com/ae/en/about-us/sustainability/guide-to-product-sustainability.jsp https://www.se.com/ae/en/about-us/sustainability/guide-to-product-sustainability.jsp https://download.schneider-electric.com/files?p_enDocType=Environmental+Disclosure&p_Doc_Ref=ENVPEP2408039EN https://download.schneider-electric.com/files?p_enDocType=Environmental+Disclosure&p_Doc_Ref=ENVPEP2408039EN https://download.schneider-electric.com/files?p_Doc_Ref=48364_ROHS_DECLARATION&p_FileName=48364_ROHS_DECLARATION_AE_en-GB.pdf https://download.schneider-electric.com/files?p_Doc_Ref=48364_ROHS_DECLARATION&p_FileName=48364_ROHS_DECLARATION_AE_en-GB.pdf https://download.schneider-electric.com/files?p_enDocType=Declaration+of+Conformity+%28Sustainability%29&p_Doc_Ref=48364_REACH_DECLARATION&p_FileName=48364_REACH_DECLARATION_AE_en-GB.pdf https://download.schneider-electric.com/files?p_enDocType=Declaration+of+Conformity+%28Sustainability%29&p_Doc_Ref=48364_REACH_DECLARATION&p_FileName=48364_REACH_DECLARATION_AE_en-GB.pdf https://download.schneider-electric.com/files?p_enDocType=Circularity+Profile&p_Doc_Ref=ENVEOLI2408039EN https://download.schneider-electric.com/files?p_enDocType=Circularity+Profile&p_Doc_Ref=ENVEOLI2408039EN
Product datasheet