Summary
This is an Asbestos and Lead Paint Inspection Report prepared by Asbestos Abatement Incorporated (AAI) for the Michigan State Police regarding the Powers Scale facility located at 3864 Highways 2 & 41, Powers, Michigan 49874. The inspection was conducted on February 16, 2018, to comply with Michigan Occupational Safety and Health Administration (MIOSHA) standards for asbestos and lead paint. The inspection included a thorough visual assessment of all accessible functional spaces and exterior areas, with representative bulk sampling of suspect asbestos-containing materials (ACM) and presumed asbestos-containing materials (PACM). Twelve distinct suspect ACMs were identified during the inspection, with samples submitted to QuanTEM Laboratories for polarized-light microscopy (PLM) analysis using EPA Method 600/R-93/116. Paint samples were collected and analyzed by GPI Laboratories, Inc. for lead content. The report was issued on April 5, 2018, and must be provided to State of Michigan employees, employers of housekeeping personnel, prospective bidders, and any tenants occupying the facility.
Analytical results determined that none of the twelve identified homogenous areas contained asbestos; however, three materials were assumed to contain asbestos and not sampled: glue pods above 1' x 1' white ceiling tiles, drywall above 1' x 1' white ceiling tiles, and roof shingles with tar paper. Two paint samples tested positive for lead: interior white paint at 0.81% and exterior white paint at 0.45%. The report notes that the attic space was not accessible due to a hatch issue, and one exterior room was locked without an available key; materials in these areas are assumed to contain asbestos. Prior to any demolition or renovation activities, a comprehensive Asbestos NESHAP inspection with destructive testing is required to identify hidden or concealed materials. The report emphasizes that quantities listed are estimates without guaranteed accuracy and recommends that contractors verify all quantities before submitting bids or establishing project budgets.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2420 N. Grand River Ave.
Lansing, Michigan 48906 www.asbestosabatementinc.com Ph. 517-323-0050 Fax 517-323-7382
April 5, 2018
Michigan State Police Attn: Mr. Paul Akeo PO Box 30634 Lansing MI 48909
Re: Asbestos and Lead Paint Inspection Report Powers Scale, 3864 Highways 2 & 41, Powers, MI 49874
Dear Mr. Paul Akeo:
Asbestos Abatement Incorporated, (AAI) was retained by the Michigan State Police to conduct an asbestos and lead paint inspection at the Powers Scale, 3864 Highways 2 & 41, Powers, MI 49874.
The asbestos inspection was requested to comply with the Michigan Occupational Safety and Health Administration (MIOSHA) Asbestos for General Industry Standard and the Asbestos Standards for Construction. Additionally, paint samples were collected and analyzed for lead to comply with the MIOSHA Lead in General Industry and Lead Exposure in Construction Standards.
This report includes the procedures and methodologies, analytical laboratory results and any applicable conclusions and recommendations made during the course of this inspection. This report must be provided to the following persons who work within this weigh station: 1) State of Michigan employees, 2) Employers of employees who perform housekeeping activities, 3) Prospective employers who are applying or bidding for work, 4) On multi-employer worksites, all employers of employees, and 5) Tenants who will occupy the building.
While a good faith effort was made to identify all ACM and PACM during this inspection, as the building was not scheduled for demolition or renovation, hidden, concealed or missed materials may exist within the building. If any materials not sampled as part of this survey are discovered, the material should be assumed to contain asbestos and, if necessary, immediately stop work and notify AAI so that additional testing and/or necessary clean-up can be performed. Additionally, prior to demolition or renovation, a comprehensive inspection in accordance with the Asbestos National Emissions Standards for Hazardous Air Pollutants (NESHAP) Standard is required. An Asbestos NESHAP inspection includes destructive testing to find hidden or concealed materials, such as those present in pipe chases and wall cavities.
Identification and testing of paint for lead was limited to accessible paints which were present in quantities and/or substrates which are likely to trigger the requirements of the MIOSHA Lead Standards during routine maintenance operations. Prior to demolition or renovation, in addition
2420 N. Grand River Ave.
Lansing, Michigan 48906 www.asbestosabatementinc.com Ph. 517-323-0050 Fax 517-323-7382 to an Asbestos NESHAP inspection, a comprehensive inspection to identify any hidden, concealed or missed paints should be conducted.
AAI appreciates the opportunity to perform these services for you and look forward to working with you in the future. In the meantime, if you have questions or comments regarding the information in this report or if we can be of further assistance please do not hesitate to contact AAI at 517-323-0050.
Sincerely, Asbestos Abatement Inc.
Mr. Jeff Suty Asbestos Inspector Accreditation #A32393
ASBESTOS AND LEAD PAINT INSPECTION REPORT
Conducted at:
Powers Scale, 3864 Highways 2 & 41
Powers, MI 49874
AAI Project Number: 1019
Date of Inspection:
February 16, 2018
Report prepared for:
Michigan State Police Mr. Paul Akeo PO Box 30634 Lansing MI 48909
Inspection conducted by:
Mr. Jeff Suty, Accreditation #A32393 Asbestos Abatement Inc.
2420 N. Grand River Ave.
Lansing, Michigan 48906 Phone: 517-323-0052 Fax: 517-323-7382
ASBESTOS NESHAP INSPECTION REPORT
AAI Project Number: 1019
TABLE OF CONTENTS
1.0 Introduction
2.0 Certification
3.0 Inspection Procedures
4.0 Analytical Results
5.0 Pertinent Observations
6.0 Regulatory Guidance
7.0 Recommendations
8.0 APPENDICES
APPENDIX A – DEFINITIONS & CLASSIFICATIONS
APPENDIX B – INSPECTOR(S) CREDENTIALS
APPENDIX C – LABORATORY CERTIFICATION
APPENDIX D – INSPECTION DATA
APPENDIX E – ANALYTICAL DATA
Asbestos NESHAP Inspection Report
P a g e | 1
1.0 Introduction
Asbestos Abatement Incorporated, (AAI) was retained by the Michigan State Police to conduct an asbestos and lead paint inspection at Powers Scale, 3864 Highways 2 & 41, Powers, MI 49874.
The asbestos inspection was requested to comply with the Michigan Occupational Safety and Health Administration (MIOSHA) Asbestos for General Industry Standard and the Asbestos Standards for Construction. Additionally, paint samples were collected and analyzed for lead to comply with the MIOSHA Lead in General Industry and Lead Exposure in Construction Standards. The on-site portion of asbestos and lead paint building inspection took place on February 16, 2018. Definitions and Classification explanations for select terms can be found in Appendix A.
Asbestos
During the inspection, good faith effort was made to identify the presence, location and quantity of all accessible ACM and PACM. However, as the building was not scheduled for demolition or renovation, AAI was not retained to conduct destructive testing. A such, hidden, concealed or missed materials may exist within the building. Destructive testing (i.e., and Asbestos NESHAP inspection) must be conducted prior to demolition or renovation to find all hidden, concealed or missed materials.
Lead
Identification and testing of paint for lead was limited to accessible paints which were present in quantities and/or substrates which are likely to trigger the requirements of the MIOSHA Lead Standards during routine maintenance operations. Prior to demolition or renovation, in addition to an Asbestos NESHAP inspection, a comprehensive inspection to identify any hidden, concealed or missed paints should be conducted.
2.0 Certification
Asbestos
The asbestos inspection was conducted by Mr. Jeff Suty, a State of Michigan Accredited Asbestos Inspector. A copy of his inspector credentials appears in Appendix B.
All of the collected asbestos bulk samples were submitted to QuanTEM Laboratories for analysis.
Bulk samples of suspect asbestos-containing materials were analyzed by polarized-light microscopy (PLM) using the EPA Method 600/R-93/116. QuanTEM Laboratories is accredited by the National Voluntary Laboratory Accreditation Program (NVLAP). A copy of their NVLAP Accreditation can be found in Appendix C.
P a g e | 2
Lead
Paint chip samples were also collected by Mr. Suty and were submitted to GPI Laboratories, Inc.
for total lead analysis. GPI Laboratories, Inc. is accredited by the National Lead Laboratory Accreditation Program (NLLAP). A copy of their NLLAP Accreditation can be found in Appendix C.
3.0 Inspection Procedures
Asbestos
This asbestos inspection was conducted to determine the presence, location and quantity of all accessible ACM and PACM in accordance with the requirements of the MIOSHA Asbestos for General Industry Standard and the MIOSHA Asbestos Standards for Construction. The inspection consisted of a thorough visual inspection of all functional spaces within the building and all exterior areas on the building for suspect ACM. Additionally, representative bulk sampling was conducted of most materials to determine whether the material is proven ACM or non-ACM.
Materials visibly identified as non-asbestos (metal, glass, wood, etc.) by the accredited inspector were not sampled.
Prior to collecting any samples, suspect ACMs were identified as homogenous areas (HAs) to develop a sampling strategy. A homogenous area is defined as an area of surfacing material, thermal system insulation, or miscellaneous material that is uniform in color and texture (e.g., exterior white window caulk).
The actual number of samples collected from each homogeneous sampling area may vary, based on the type of material and the professional judgment of the inspector. A minimum of two samples of each HA were collected and submitted to an accredited laboratory for analysis by PLM. The number of samples collected for each material identified was determined according to the following table:
Guidelines for Determining the Number of Samples Collected HA Category HA Size Samples Required
Miscellaneous Materials No Stipulation 2
Thermal Systems Insulation No Stipulation 3
Surfacing Material
< 1,000 SQ. FT 3
1,000 – 5,000 SQ. FT 5
> 5,000 SQ. FT 7
P a g e | 3
Determined by the visual inspection, a total of 12 distinct suspect ACMs were identified during this inspection. A complete list of all suspect ACMs identified, including analytical results, friability, location, and estimated quantities can be found in Appendix D.
Lead
Identification and testing of suspect lead-containing paint was limited to accessible paints which were present in quantities and/or substrates which are likely to trigger the requirements of the MIOSHA Lead Standards during routine maintenance operations. Paint samples were collected in a manner to minimize substrate dilution. Prior to demolition or renovation, in addition to an Asbestos NESHAP inspection, a comprehensive inspection to identify any hidden, concealed or missed paints should be conducted. A complete list of all sampled paints, including analytical results, can be found in Appendix D.
4.0 Analytical Results
Asbestos
A material is considered to be ACM when it contains greater than 1% asbestos. Such materials must be handled according to Federal, State and local regulations. For homogenous areas with multiple samples collected, only one sample with greater than 1% asbestos is required for the entire homogenous area to be considered ACM.
For friable materials, when the amount of asbestos in the sample material is reported as “None- Detected” by routine PLM analysis, no further verification of the sample results by Point Counting Methodology is recommended.
For friable materials, when the amount of asbestos in the sample material is reported at less than 10% by PLM analysis, the client may either assume the amount to be greater than 1% and treat the material as ACM or request further verification of the asbestos content by Point Counting Methods.
If the result obtained by Point Counting is different from the result obtained by routine PLM analysis, the Point Count Method result should be used.
For non-friable materials, when the amount of asbestos in the sample material is reported at greater than 1% by PLM analysis, no further verification of the sample results by alternative methods of identification is required.
The QuanTEM Laboratories PLM analytical report, including detailed information on individual sample layers, can be found in Appendix E.
P a g e | 4
None of the 12 identified homogenous areas were determined to contain asbestos.
The following identified suspect ACMs were not sampled and are assumed to contain asbestos:
Glue pods above 1' x 1' white ceiling tile with uniform holes Drywall above 1' x 1' white ceiling tile with uniform holes (assumed substrate to be present) Roof shingles and tar paper
The following identified materials were determined to not contain asbestos:
2' x 4' white lay-in ceiling tile with holes and fissures No-slip floor tiles, brown, and mastic 4" gray cove molding and mastic Textured wall and ceiling plaster 1' x 1' white ceiling tile with uniform holes (glue pods and associated substrate are assumed to contain asbestos) Cinderblock Cinderblock mortar Concrete floor Exterior white window caulk
A paint is considered lead-containing if any amount of lead is detected in the submitted sample.
The GPI Laboratories, Inc. analytical report can be found in Appendix E.
The following paints were determined to be lead-containing:
Interior white paint, and Exterior white paint
No tested paints were determined to be lead-free.
5.0 Pertinent Observations
During the visual inspection, select observations were made and documented. With the inspection procedures and analytical results taken into consideration, the pertinent observations are as follows:
All quantities listed in the Building Inventory Data form (Appendix D) are estimates and its accuracy is not guaranteed.
P a g e | 5
Due to an issue with the hatch, the attic space was not accessible. Any materials in the attic that were not identified in other areas of this building are assumed to contain asbestos.
A room accessible only by an exterior door was locked with no key available for access.
Any materials in the attic that were not identified in other areas of this building are assumed to contain asbestos.
6.0 Regulatory Guidance
This section offers regulatory guidance for ACM and lead-containing paint identified during this inspection and does not guarantee compliance with all regulatory requirements. Please refer to the applicable asbestos and/or lead regulation(s) or contact AAI for project-specific regulatory requirements.
Asbestos
This report must be maintained throughout the life of this building, and to comply with the MIOSHA asbestos hazard communication requirements, this report must be provided to the following persons who work within this weigh station:
State of Michigan employees, Employers of employees who perform housekeeping activities, Prospective employers who are applying or bidding for work, On multi-employer worksites, all employers of employees, and Tenants who will occupy the building.
Mechanical rooms/areas in which ACM is present must have signs at the entrance which identify the ACM materials which are present, its location, and appropriate work practices which, if followed, will ensure that ACM and/or PACM will not be disturbed.
Asbestos awareness training (or Class IV training) is required for the following employees:
Employees who are likely to be exposed to airborne concentrations of asbestos at or above the permissible exposure limit and/or excursion limit.
Employees who perform Class I and II work (e.g., asbestos removal).
Employees who perform Class III work (e.g., repair and maintenance operations, where
"ACM", including TSI and surfacing ACM and PACM, is likely to be disturbed).
Employees who perform Class IV work (maintenance and custodial activities during which employees contact but do not disturb ACM or PACM and activities to clean up dust, waste and debris resulting from Class I, II, and III activities).
P a g e | 6
Identification and testing of paint for lead was limited to accessible paints which were present in quantities and/or substrates which are likely to trigger the requirements of the MIOSHA Lead Standards during routine maintenance operations. Prior to demolition or renovation, in addition to an Asbestos NESHAP inspection, a comprehensive inspection to identify any hidden, concealed or missed paints should be conducted.
Known lead hazards should be communicated as required by the MIOSHA Hazard Communication standard and any real estate transaction laws. Additionally, State of Michigan employees shall be informed of the contents of Appendices A and B to 29 C.F.R. §1910.1025 ‘Lead.’
Lead awareness training is required for the following employees who are subject to exposure to lead at or above the action level, or for whom the possibility of skin or eye irritation exists.
This report shall not be used as a compliance tool. It is the responsibility of all employers of employees working within this to comply with all applicable laws and regulations.
This guidance is based on the visual inspection, analytical results, pertinent observations and AAI’s understanding of the project. This guidance may require modification should there be a change in building ownership, use and/or during demolition or renovation.
7.0 Recommendations
Based on the visual inspection (including pertinent observations), and the bulk sample analytical data, the following recommendations are offered:
Prior to establishing a project budget (including contractors submitting bids), verify quantities listed in the Building Inventory Data form (Appendix D) as they are estimates and accuracy is not guaranteed.
Prior to work in the attic space, assume all materials in the attic contain asbestos that are not identified in other areas of the building.
Prior to work in the inaccessible exterior room, assume all materials in the attic contain asbestos that are not identified in other areas of the building.
Utilize Section 6.0 as a guide for regulatory compliance including, but not limited to:
hazard communication and training. Refer to the appropriate regulation(s) for additional requirements and/or contact AAI for assistance.
Prior to demolition or renovation, conduct a comprehensive Asbestos NESHAP and lead-paint inspection to identify any hidden, concealed or missed suspect asbestos materials and suspect lead-containing paints.
APPENDIX A
DEFINITIONS & CLASSIFICATIONS
Asbestos Definitions and Classifications ACM (Asbestos Containing Material) – Commercial asbestos product containing more than 1% asbestos.
ACM must be disposed as regulated waste. Note: Federal OSHA and Cal-OSHA control materials containing any amount of asbestos.
ACBM (Asbestos Containing Building Material) – AHERA/ASHARA term for material containing more than 1% asbestos in or on interior structural members or other structural components. Includes covered walkways, porticos and exterior HVAC TSI.
ACCM (Asbestos Containing Construction Material) – California term for a manufactured construction material containing greater than .1% (one tenth of one percent) asbestos.
PACM (Presumed Asbestos Containing Material) OSHA considers all TSI and surfacing materials installed prior to1980 to be ACM unless proven otherwise.
Friable Asbestos Containing Material that can be crumbled pulverized or reduced to powder by hand pressure when dry.
NOA Naturally Occurring Asbestos. CARB defines as having >.25% by point counting.
ACM CARB term for naturally occurring asbestos >.25% by point counting DACM Designated Asbestos Containing Material: Floor tile installed before 1981
Categories of Asbestos Used BY EPA AHERA/ASHARA and OSHA/Cal-OSHA TSI (Thermal System Insulation) - “Thermal system insulation (TSI)” means ACM applied to pipes, fittings, boilers, breeching, tanks, ducts or other structural components to prevent heat loss or gain. “Thermal system insulation ACM” is thermal system insulation which contains more than 1% asbestos.
SURFACING
(usually mixed on site at time of application)
“Surfacing material” means material that is sprayed, troweled-on or otherwise applied to surfaces (such as acoustical plaster on ceilings and fireproofing materials on structural members, or other materials on surfaces for acoustical, fireproofing, and other purposes).
“Surfacing ACM” means surfacing material which contains more than 1% asbestos. NOTE:
OSHA/Cal-OSHA do not classify skim coat, taping mud, floor tile mastic, stucco, leveling compound, and hard wall plasters or wall texturing as surfacing.
MISC. All other ACM, including classify taping mud, floor tile mastic, stucco, leveling compound, and hard wall plasters or wall texturing as surfacing.
NESHAPS Categories for Asbestos (Used by Air Quality Management Districts for Renovation and Demolition)
Category I Cat I Non-friable Asbestos Containing Material(ACM) refers to asbestos containing packing, gaskets, resilient floor covering, Galbestos, and asphalt roofing products containing more than 1% asbestos.
Category II Cat II Non-friable Asbestos-Containing Material (ACM) is any material that is not Cat I that contains greater than 1% asbestos.
RACM “Regulated Asbestos-Containing Material.” – Friable manufactured asbestos material (ACM) or a Category I non-friable ACM that has become friable OR a Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting or abrading OR Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation operations. RACM should be removed prior to renovation or demolition.
APPENDIX B
INSPECTOR(S) CREDENTIALS
APPENDIX C
LABORATORY CERTIFICATION
APPENDIX D
INSPECTION DATA
Asbestos Inspection Data Powers Scale, 3864 Highways 2 & 41, Powers, MI 49874
HA # HA Description Friable ACM Quantity/Location
2' x 4' white lay-in ceiling tile with holes and fissures Yes No
300 SF
Throughout
No-slip floor tiles, brown, and mastic No No
300 SF
Throughout
4" gray cove molding and mastic No No
60 SF
Throughout
Textured wall and ceiling plaster No No
525 SF
Throughout
1' x 1' white ceiling tile with uniform holes Yes No*
300 SF
Throughout
6 Cinderblock No No
500 SF
Throughout
7 Cinderblock mortar No No
100 SF
Throughout
8 Concrete floor No No
345 SF
Throughout
Exterior white window caulk No No 10 SF
Glue pods above 1' x 1' white ceiling tile with uniform holes
No Assumed
300 SF
Throughout
Drywall above 1' x 1' white ceiling tile with uniform holes
No Assumed
300 SF
Throughout
12 Roof shingles and tar paper Yes Assumed 380 SF *Ceiling tile must be treated as ACM as the associated glue pods are assumed to contain asbestos
Lead Paint Chip Sample Log Powers Scale, 3864 Highways 2 & 41, Powers, MI
49874
HA # HA Description Lead Content 1 Interior white paint 0.81%
2 Exterior white paint 0.45%
APPENDIX E
ANALYTICAL DATA
Date Received: 03/19/2018
Project: NA
QuanTEM Lab No. 292089
Analyzed By: Dee Ammerman
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Powers Scale
Project Number: NA
Account Number: C008
Received By: Amber Bassett
Date Analyzed: 03/25/2018
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Asbestos Abatement, Inc.
2420 N. Grand River
Lansing, MI 48906
Non Fibrous
001 1-1 Homogeneous Perlite
Paint
Asbestos Not Present 50
Cellulose
Glass FiberCeiling Tile
White
002 1-2 Homogeneous Perlite
Paint
Asbestos Not Present 50
Cellulose
Glass FiberCeiling Tile
White
003 2-1 Layered Vinyl
CaCO3
Asbestos Not Present NA
Floor Tile
Brown
003a Layered Glue
CaCO3
Asbestos Not Present NA
Mastic
White
004 2-2 Layered Vinyl
CaCO3
Asbestos Not Present NA
Floor Tile
Brown
004a Layered Glue
CaCO3
Asbestos Not Present NA
Mastic
White
005 3-1 Layered CaCO3
Vinyl
Asbestos Not Present NA
Cove Base
Gray
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
Unless otherwise noted, upon receipt the condition of the sample was acceptable for analysis.
QuanTEM Lab No. 292089
Analyzed By: Dee Ammerman
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Powers Scale
Project Number: NA
Account Number: C008
Received By: Amber Bassett
Date Analyzed: 03/25/2018
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Asbestos Abatement, Inc.
2420 N. Grand River
Lansing, MI 48906
Non Fibrous
005a Layered Glue
CaCO3
Asbestos Not Present NA
Mastic
White
006 3-2 Layered CaCO3
Vinyl
Asbestos Not Present NA
Cove Base
Gray
006a Layered Glue
CaCO3
Asbestos Not Present NA
Mastic
White
007 4-1 Homogeneous CaCO3
Sand
Asbestos Not Present NA
Texture
White
008 4-2 Homogeneous CaCO3
Paint
Asbestos Not Present NA
Texture
White
009 4-3 Homogeneous CaCO3
Paint
Asbestos Not Present NA
Wall Texture
White
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 292089
Analyzed By: Dee Ammerman
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Powers Scale
Project Number: NA
Account Number: C008
Received By: Amber Bassett
Date Analyzed: 03/25/2018
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Asbestos Abatement, Inc.
2420 N. Grand River
Lansing, MI 48906
Non Fibrous
010 6-1 Homogeneous CaCO3
Sand
Asbestos Not Present NA
Cement
Gray
011 6-2 Homogeneous CaCO3
Sand
Asbestos Not Present NA
Cement
Gray
012 7-1 Homogeneous CaCO3
Sand
Asbestos Not Present NA
Mortar
Gray
013 7-2 Homogeneous CaCO3
Sand
Asbestos Not Present NA
Mortar
Gray
014 8-1 Homogeneous CaCO3
Sand
Asbestos Not Present NA
Concrete
Gray
015 8-2 Homogeneous CaCO3
Sand
Asbestos Not Present NA
Concrete
Gray
016 9-1 Homogeneous CaCO3
Binder
Asbestos Not Present NA
Caulk
White
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 292089
Analyzed By: Dee Ammerman
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Powers Scale
Project Number: NA
Account Number: C008
Received By: Amber Bassett
Date Analyzed: 03/25/2018
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Asbestos Abatement, Inc.
2420 N. Grand River
Lansing, MI 48906
Non Fibrous
017 9-2 Homogeneous CaCO3
Binder
Asbestos Not Present NA
Caulk
White
Date of Report
3/26/2018
Dee Ammerman, Analyst
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
ANALYTICAL LABORATORY REPORT Friday, March 23, 2018 Page 1 of 2
CUSTOMER: Asbestos Abatement, Inc
2420 N Grand River
Lansing, MI 48906
DATE RECEIVED: Tuesday, March 20, 2018
PO/PROJECT #:
SUBMITTAL #: 2018-03-20-005
LAB NUMBER: AC51164
Sampled By: Jeff Suty
Job Location: Powers Scale
Sample Identification: P-1: Interior White
Date Sampled: February 16, 2018
Sample Description: Paint Chips
Preparation Method: EPA 3050B-P-M (Acid Digestion for Paints)
Analysis Method: EPA 6010C-M (ICP-AES Method for Determination of Metals)
Date Analyzed: Thursday, March 22, 2018
ELEMENT RESULT (by dry weight)
REPORTING
LIMIT (RL)
Lead 0.81 % 0.0025 %
LAB NUMBER: AC51165
Sampled By: Jeff Suty
Job Location: Powers Scale
Sample Identification: P-2: Exterior White
Date Sampled: February 16, 2018
Sample Description: Paint Chips
Preparation Method: EPA 3050B-P-M (Acid Digestion for Paints)
Analysis Method: EPA 6010C-M (ICP-AES Method for Determination of Metals)
Date Analyzed: Thursday, March 22, 2018
ELEMENT RESULT (by dry weight)
REPORTING
LIMIT (RL)
Lead 0.45 % 0.0025 %
GPI Laboratories, Inc. has obtained accreditation under the programs detailed on the final page of the laboratory report. The accreditations pertain only to the testing performed for the elements, and in accordance with the test methods, listed in the scope of accreditation table. Testing which is performed by GPI
Laboratories, Inc. according to other test methods, or for elements which are not included in the table fall outside of the current scope of laboratory accreditation.
This report shall not be reproduced except in full, without written approval of GPI Laboratories, Inc..
4403 Donker CT SE · Grand Rapids, MI 49512-4054 · (616) 940-3112 · www.gpinet.com
ANALYTICAL LABORATORY REPORT Friday, March 23, 2018 Page 2 of 2
CUSTOMER: Asbestos Abatement, Inc
2420 N Grand River
Lansing, MI 48906
DATE RECEIVED: Tuesday, March 20, 2018
PO/PROJECT #:
SUBMITTAL #: 2018-03-20-005
Tests Reviewed By: Michael J. Swiech, Technical Manager
Unless otherwise noted, the condition of each sample was acceptable upon receipt, all laboratory quality control requirements were met, and sample results have not been adjusted based on field blank or other analytical blank results. Individual sample results relate only to the sample as received by the laboratory.
Reporting Limit (RL): The lowest concentration of analyte in a sample that can be reported with a defined, reproducible level of certainty. This value is based on the lowest standard used for instrument calibration and must be at least twice the MDL.
GPI Laboratories, Inc. has obtained accreditation under the following programs:
· National Lead Laboratory Accreditation Program (NLLAP)
AIHA-LAP: Environmental Lead Laboratory Accreditation Program (ELLAP), Laboratory ID#101030 ( www.aihaaccreditedlabs.org)
· OH: Ohio Department of Health Lead Poisoning Prevention Program, Approval #E10013 ( www.odh.ohio.gov)
· AIHA-LAP: Industrial Hygiene Laboratory Accreditation Program (IHLAP) , Laboratory ID#101030 (www.aihaaccreditedlabs.org)
· National Environmental Laboratory Accreditation Program (NELAP)
NY: State of New York Department of Health, Laboratory ID#11609 (Serial # 56089, 56973-56975, & 57314) (518-485-5570)
LA: State of Louisiana Department of Environmental Quality, Laboratory ID#180321 (Certificate 05036) ( www.deq.louisiana.gov)
OK: Oklahoma Department of Environmental Quality, Laboratory ID#9993 (Certificate 2017-067) ( www.deq.state.ok.us)
Testing which is performed by GPI Laboratories, Inc. according to test methods, or for elements which are not included in the table below fall outside of the current scope of laboratory accreditation. Customers are encouraged to verify the current accreditation status with the individual accreditation programs by calling or visiting the appropriate website for the applicable program.
SCOPE OF ACCREDITATION
Air and Emissions
Element/Test Method Accreditation(s)
Suspended Particulates: PM10 / TSP 40 CFR 50 Appendix J / 40 CFR 50 Appendix B NY, LA
Lead in Airborne Dust 40 CFR 50 Appendix G ELLAP, IHLAP, LA
Lead in Airborne Dust NIOSH 7300 ELLAP, OH, NY, LA
Lead in Airborne Dust EPA 600/R-93/200/ EPA 6010C ELLAP, OH
Metals in Airborne Dust EPA 600/R-93/200/ NIOSH 7300/ EPA 6010C IHLAP
Solid Chemical Materials
Element/Test Method Accreditation(s)
TCLP EPA 1311(Sample Preparation Method) NY, LA, OK
Lead in Soil EPA 3050B/ EPA 6010C ELLAP, OH, NY, LA, OK
Lead in Paint EPA 3050B/ EPA 6010C ELLAP, OH, NY, LA
Lead in Paint ASTM D 3335-85A/ EPA 6010C NY
Lead in Dust Wipes EPA 3050B/ EPA 6010C NY, LA
Lead in Dust Wipes EPA 600/R-93/200/ EPA 6010C ELLAP, OH
Ignitability EPA 1010A NY
Non-Potable Water / Analysis by ICP Solid Chemical Materials
Element/Test Method Accreditation(s) Method Accreditation(s)
Arsenic EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK
Barium EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK
Cadmium EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK
Chromium EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK
Copper EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK
Lead EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK
Mercury EPA 245.1 Rev.3/ EPA 7470A NY, LA, OK EPA 7471B NY, LA, OK
Nickel EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK
Selenium EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK
Silver EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK
Zinc EPA 6010C/ EPA 200.7 Rev 4.4 NY, LA, OK EPA 6010C NY, LA, OK
Cobalt ---- ---- EPA 6010C NY, LA, OK
Manganese ---- ---- EPA 6010C NY, LA, OK
Acid Digestion EPA 3010A NY, LA EPA 3050B NY, LA
This report shall not be reproduced except in full, without written approval of GPI Laboratories, Inc..
4403 Donker CT SE · Grand Rapids, MI 49512-4054 · (616) 940-3112 · www.gpinet.com
| Powers Report - Word.pdf |
| 292089_C008_PLM_With_COC.pdf |
| 2018-03-20-005.pdf |
| 2018-03-20-005.pdf |
| 2018-03-20-005c |
| 2018-03-23T15:15:52-0400 | |
| Michael Swiech |
File details come from the government source that posted it. Updated .