Powell Buttes ES - COOLING UPGRADES - Mechanical and Plumbing~1.pdf

PDF 799 KB Posted

Attached to
Centennial 4- Site Mechanical Cooling
Solicitation number
S-P26028-00009492
Issued by
Multnomah County, Oregon

About this file

This document appears to be a set of mechanical and plumbing drawings and specifications for a cooling system upgrade project at the Meadows Elementary School, located in Portland, Oregon. The project involves installing new rooftop condensing units and wall-mounted fan coil units to provide cooling for the main office and support spaces at the school. The document includes a list of equipment, schedules, and details for the new HVAC system components, as well as notes on the controls integration with the existing building automation system.

The related state and local contract opportunity appears to be for the Centennial 4 - Site Mechanical Cooling project, which includes multiple sites in Multnomah County and the City of Portland, Oregon. This is likely a separate but related project to the Meadows Elementary School cooling upgrade.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET INDEX

MP0.1 SYMBOLS LIST, GENERAL NOTES DETAILS & SCHEDULES -

MECH & PLUMBING

MP1.0 OVER FLOOR PLAN - MECHANICAL & PLUMBING

MP2.0 ENLARGED FLOOR PLANS - MECHANICAL & PLUMBING

Abbreviations

AIR CONDITION(ED)A/C

ACCESS DOORAD

ABOVE FINISHED FLOORAFF

BACKDRAFT DAMPERBDD

BELOW FINISHED FLOORBFF

BACKFLOW PREVENTERBFP

BRAKE HORSEPOWERBHP

CEILING DIFFUSERCD

CONDENSATE DRAINCD

CONTINUATIONCONT.

COEFFICIENT OF PERFORMANCECOP

CONDENSING UNITCU

CHECK VALVECV

COLD WATERCW

DROPD

DECIBELDB

DRY BULBDB

DIAMETERDIA

DIRECT EXPANSIONDX

ENTERING AIR TEMPERATUREEAT

ENERGY EFFICIENCY RATINGEER

EXHAUST FANEF

EFFICIENTEFF

ELECTRICALELECT

ENTERING WATER TEMPERATUREEWT

EXHAUSTEXH

FAHRENHEITF

FIRE DAMPERFD

FULL LOAD AMPSFLA

FEETFT

GALLONSGAL

GALLONS PER HOURGPH

GALLONS PER MINUTEGPM

HEADHD

HORSEPOWERHP

HEATINGHTG

HEATERHTR

HOT WATER COILHWC

INSIDE DIAMETERID

INVERT ELEVATIONIE

INCHESIN

KILOWATTKW

LEAVING AIR TEMPERATURELAT

POUNDSLBS.

LATENT HEATLH

MIXED AIRMA

MAXIMUMMAX

THOUSAND BTU'S PER HOURMBH

MOTORIZED DAMPERMD

MINIMUMMIN

NOT APPLICABLEN/A

NOT IN CONTRACTNIC

NUMBERNO.

NOT TO SCALENTS

OUTSIDE AIROA

OPPOSED BLADE DAMPEROBD

ON CENTEROC

OUTSIDE DIAMETEROD

PRESSURE DROPPD

PHASEPH

PRESSURE REDUCING VALVEPRV

POUNDS PER SQUARE INCHPSI

QUANTITYQTY

RISER

RETURN AIRRA

RETURNRET

REVOLUTIONS PER MINUTERPM

SUPPLY AIRSA

SEASONAL ENERGY EFFICIENCY RATINGSEER

SQUARE FEETSF

SENSIBLE HEATSH

SHUT OFF VALVESOV

STATIC PRESSURESP

TEMPERATURET, TEMP

TEMPERATURE DIFFERENCETD

TOTAL HEATTH

TOTAL PRESSURETP

VOLTV

WITHW/

WATTW

WET BULBWB

WATER COLUMNWC

Piping Fittings, Appurtenances and Equipment

CAP

CONTINUATION

Piping Systems

REFRIGERANT LIQUID AND SUCTION

MECHANICAL SYMBOL LIST

NOTE: This is a standard symbol list and not all items listed may be used.

ROOF DECK.

LAP SEALANT.

CLAMPING STRAP.

STAINLESS STEEL

MEMBRANE.

ROOFING

SPLICE ADHESIVE.

NOTE:

INSULATION.

RIGID

ALUMINUM

PIPE COVER.

USE ROOF MEMBRANE

MANUFACTURER'S

MATERIALS. PATCH

AND REPAIR ROOF TO

COMPLY WITH ALL

ROOF WARRANTIES.

PRE-FAB

PIPE FLASHING.

LAP SEALANT.

SEE DETAIL 1/M0.1

PIPE COVER.

ALUMINUM

AIRTIGHT.

SPRAY FOAM INSULATION

FILL CAVITY WITH

TO FAN/COIL UNIT.

ROUTE REFRIGERATION PIPES

18 GA. SHEETMETAL CAP.

FLASHING.

ROOFING AND

SILICONE

ROOF.

SEAL.

COVER.

GALV OR ZINC-A-LUME

PIPES.

INSULATED REFRIGERANT

CONDENSING UNIT.

MAINTAIN CLEARANCES

AS SPECIFIED BY

MANUFACTURER.

PLATFORM CONSTRUCTION

TO BE COORDINATED WITH

ARCHITECT.

CURB (HEIGHT AS REQUIRED)

[1/8"] AIRCRAFT

CABLE. SEISMIC

GUY WIRE TYP.

OF FOUR SIDES.

SECURELY

FASTEN TO UNIT

CURB.

SEE STRUCTURAL FOR

ATTACHMENT TO ROOF.

METAL STUDS.

[5/8"] EYE BOLT

ATTACHED WITH

NUT AND WASHER

BOTH SIDES.

BOTH SIDES.

NUT AND WASHER

ATTACHED WITH

[5/8"] EYE BOLT

AIRCRAFT CABLE ATTACHMENT

CAPABLE OF WITHSTANDING

[80 LBS OF FORCE].

NOTE:

NO SCALE

1 REFRIGERANT PIPING COVER PENETRATION

ROOFTOP CONDENSING UNIT CURB2

NO SCALE

REF

HVAC CONTROLS NOTES

A. PROVIDE EACH MULTIZONE HEAT PUMP WITH A BAS INTEGRATION CONTROLLER

FOR COMBATIBILITY WITH INTERFACING WITH CONNECTION TO THE EXISTING

BACNET BUILDING AUTOMATION SYSTEM WITH AVAILABLE READ/WRITE POINTS

FROM THE HEAT PUMP CONTROLLER INCLUDING: ON/OFF, SET POINT, ROOM

TEMPERATURE, OPERATION MODE, FAN SPEED, LOUVER POSITION, ERROR CODE

AND INTERLOCK CONTROL WITH INDOOR UNIT ON/OFF.

B. EXTEND EXISTING BUILDING AUTOMATION SYSTEM TO CONNECT TO NEW HEAT

PUMP EQUIPMENT BUILDING AUTOMATION SYSTEM INTEGRATOR AND PROVIDE NEW

READ/WRITE AND BAS GRAPHICS FOR BUILDING AUTOMATION INTEGRATION.

C. NEW HEAT PUMP REFRIGERATION SYSTEM WILL BE CONTROLLED BY THE

MANUFACTURER PROVIDED CONTROLLER. SCHEDULING, ON/OFF CONTROL AND

TEMPERATURE SET POINT CONTROL WILL BE CONTROLLED THROUGH THE

BUILDING AUTOMATION SYSTEM. PROVIDE ADDITIONAL THIRD PARTY

TEMPERATURE SENSORS AS REQUIRED TO MAINTAIN BUILDING AUTOMATION

SYSTEM MONITORING FOR EACH ZONE SERVED BY NEW HEAT PUMPS.

D. HEAT PUMPS WILL OPERATE TO PROVIDE COOLING ONLY. HEATING AND

VENTILATION IS PROVIDED BY THE EXISTING HVAC SYSTEM. LOCK-OUT HEAT PUMP

HEATING OPERATION AND PROVIDE A TEMPERATURE SET POINT DEAD BAND

BETWEEN HEATING AND COOLING TO PREVENT SIMULTANEOUS HEATING AND

COOLING OPERATION OF THE EXISTING HEATING SYSTEM AND NEW HEAT PUMPS.

E. THE WORK OF THIS DIVISION SHALL BE PROVIDED BY A HONEYWELL AUTHORIZED

CONTROL INTEGRATOR (ACI). THE FOLLOWING CONTRACTORS ARE:

1. HUNTER-DAVISSON

2. MACDONALD MILLER

3. NORTHWEST CONTROL CO.

4. NO ALTERNATES OR SUBSTITUTION WILL BE ACCEPTED.

3 CONDENSATE DRAIN CONNECTION

NO SCALE

CONDENSATE DRAIN

DOWN IN WALL.

C.P. ESCUTCHEON.

3/4" COPPER DRAIN FROM

FURNACE.

3/4" I.D. APPROVED HOSE

AND S.S. HOSE CLAMPS.

P-TRAP.

NOTE:

ADJUST ROUGH-IN

HEIGHT AS REQ'D.

CABINET TOP.

LOCATE PENETRATION

THROUGH WALL NEAR

CONNECTION TO MINIMIZE

EXPOSED PIPING.

REVISIONS

DATE

JOB NO.

CHECKED BY

DRAWN BY

SHEET NUMBER

SHEET TITLE

100 SW Main Street Suite 1600 Portland, OR 97204

TEL 503.382.2266

www.interfaceengineering.com

Shem Heiple

2023-1707

1/23/2024

M

EA

D O

W S

EL

EM

EN

TA

R Y

C O

O

LI

N G

U

PG

R A

D

ES

M

A

IN

O

FF

IC

E

SU

PP

O R

T

SP

A C

ES

SE

B ro ok ly n St

PO

R

TL

A N

D , O

R

12/31/25EXPIRES:

SYMBOLS LIST,

GENERAL NOTES

DETAILS &

SCHEDULES -

MECH & PLUMBING

JR

MP0.1

FILE: MP0.1.DWG - MP0.1 | EDIT: 1/23/2024 2:14 PM BY JESUSR | PLOT: 1/23/2024 3:18 PM BY JESUS RODRIGUEZ

AMB. MAX. APPROX

NOM. CAP. TEMP. OF EFF. EFF. WT. DIMS

SYMBOL AREA SERVED TONS (MBH) ( °F ) DESIGN (EER2) (SEER2) (LBS) (WxDxH) VOLT/PH MCA MOCP NOTES CU-1 MAIN OFFICE 4 48.0 95 DAIKIN 5MXS48WVJU9 10.5 20.6 250 44x18x35 208/1 33.2 35 1

NOTES:

1. R-410A REFRIGERANT.

CONDENSING UNIT SCHEDULE

COOLING

BASIS MIN. MIN.

ELECTRICAL

BASIS MAX. APPROX

NOM. COND. TOTAL MIN SENS. OF WT. DIMS MOTOR

SYMBOL AREA SERVED TONS UNIT (MBH) (MBH) (F DB) (F WB) DESIGN (LBS) (WxDxH) VOLT/PH FLA NOTES FCU-1 OFFICE 0.75 CU-1 7.2 5.0 80.0 67.0 DAIKIN FTXS09WVJU9 30 32x9x12 208/1 0.09 1,2,3,4,5,6

FCU-2 OFFICE WAITING 1.25 CU-1 14.4 10.1 80.0 67.0 DAIKIN FTXS15WVJU9 50 42x10x14 208/1 0.09 1,2,3,4,5,6

FCU-3 NURSE 0.75 CU-1 7.2 5.0 80.0 67.0 DAIKIN FTXS09WVJU9 30 32x9x12 208/1 0.09 1,2,3,4,5,6

NOTES:

1. WALL MOUNTED FAN COIL. TOTAL CAPACITY LISTED IS THE CORRECTED CAPACITY FOR UNITS CONNECTED TO 4-TON MULTIZONE CONDENSING UNIT.

2. MANUFACTURER PROVIDED CONDENSATE PUMP KIT.

3. CONDENSATE OVERFLOW SHUT-OFF FLOAT SWITCH.

4. WIRED REMOTE THERMOSTAT WITH SCHEDULING, SETPOINT, FAN SPEED, AIRFLOW DIRECTION CAPABILITY.

5. INDOOR UNIT RECEIVES POWER FROM CONDENSING UNIT.

6. CONDENSATE PUMP RECEIVES POWER FROM FAN COIL UNIT.

DX FAN COIL SCHEDULE

COOLING ELECTRICAL

ENT. AIR

MP2.0

GYM

110 SOR

LAV

BOYS

GIRLS

STOR

OFFICE

VESTIBULE

RISER

ROOM

CORRIDOR

DN

W

CLASSROOM

CLASSROOM CLASSROOM

CLASSROOM CLASSROOM CLASSROOM CLASSROOM CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM CLASSROOM

CLASSROOM CLASSROOM

CLASSROOM CLASSROOM CLASSROOM CLASSROOM CLASSROOM CLASSROOM

CLASSROOM CLASSROOM CLASSROOM

RR BOYS RR GIRLS

RR RR

RR RR

RR

RR BOYS RR GIRLS

RR

RR

JAN STOR

JAN

LIBRARY

STAGE

OFFICE

STORAGE

LOCKERS

GIRLS

LOCKERS

BOYS JAN

STOR

RR

BOILER

ROOM

KITCHEN

STOR

KITCHEN

KITCHEN

COOLER

CAN WASH

STUDENT

WORKRM

TEACHER

WORKRM

OFFICE

STOR

TEACHER

WORKRM

OFFICE

OFFICE

MECH RM

COMMONS

ELECTRICAL

ROOM

STOR

CONT PIT

STAFF

OFFICE

OFFICE

OFFICE

WAITING

OFFICE

OFFICE

HEALTH

OFFICE

PRINCIP

OFFICE

WORKRM

AFTERSCHOOL

STOR

125A

RR

CORR

CLASSROOM

CLASSROOM

MULTIPURPOSE

CORRIDOR

CORR

EXISTING COVERED PLAY

CORRIDOR

FLEX

CLASSROOM

CORR

VESTIBULE

IDF

125B

DIV 26

SWITCHBOARD

ELECTRICAL

EQUIPMENT PAD

MDF

RR

RR

KNOXBOX

REVISIONS

DATE

JOB NO.

CHECKED BY

DRAWN BY

SHEET NUMBER

SHEET TITLE

100 SW Main Street Suite 1600 Portland, OR 97204

TEL 503.382.2266

www.interfaceengineering.com

Shem Heiple

2023-1707

1/23/2024

PO

W

EL

L

B U

TT

E

EL

EM

EN

TA

R Y

C O

O

LI

N G

U

PG

R A

D

ES

M

A

IN

O

FF

IC

E

SU

PP

O R

T

SP

A C

ES

S E

4t h A ve nu e

PO

R

TL

A N

D , O

R

12/31/24EXPIRES:

0 16' 32'

SCALE: 1/16"=1'-0"

8'

1 OVERALL FLOOR PLAN - MECHANICAL & PLUMBING

OVERALL FLOOR

PLANS -

MECHANICAL &

PLUMBING

SPL

MP1.0

OFFICE

OFFICE

203 NURSE

OFFICE

RR

RR

FCU-2

FCU-1

FCU-3

FCU-4

T

T

T T

REF

REF

R

EF

SHEET KEYNOTES

1. ROUTE PUMPED CONDENSATE DISCHARGE (PD) UP WITHIN

CEILING SPACE TO ADJACENT RESTROOM. EXTEND TO

PLUMBING WALL AND ROUTE DOWN WITHIN WALL TO CONNECT

TO SINK TAILPIECE. REFER TO DETAIL 3/MP0.1

2. ROUTE PUMPED CONDENSATE DISCHARGE (PD) DOWN ALONG

INTERIOR WALL, EXPOSED. EXTEND THROUGH EXTERIOR WALL

TO DISCHARGE 12 INCHES ABOVE EXTERIOR GRADE WITH

DOWNTURN.

GENERAL SHEET NOTES

A. CONTRACTOR TO FIELD VERIFY CONDENSATE ROUTING AND

TERMINATION LOCATIONS AND PROVIDE ALTERNATE ROUTING

IF LOCATION SHOWN IS NOT CONSISTENT WITH EXISTING

CONDITIONS.

B. FOR EXTERIOR CONDENSATE DISCHARGE: DO NOT TERMINATE

CONDENSATE FROM MECHANICAL UNITS ABOVE CONCRETE

OR OTHER NONPERMEABLE SURFACE.

C. INSTALL WALL MOUNTED FCU CLOSE TO CEILING WITH MFR'S

RECOMMENDED TOP CLEARANCE. IF EXISTING CONDITIONS DO

NOT PERMIT INSTALLATION, CONTACT ENGINEER WITH

PROPOSED NEW LOCATION FOR REVIEW PRIOR TO

INSTALLATION.

D. REFRIGERANT ROUTE SHOWN DEMONSTRATES DESIGN

INTENT TO MINIMIZE EXPOSED REFRIGERANT LINESETS.

VERIFY WITH EXISTING CONDITIONS AND OBTAIN APPROVAL

FROM OWNER AND ENGINEER BEFORE PROCEEDING WITH

INSTALLATION.

CU-1

R

EF

REVISIONS

DATE

JOB NO.

CHECKED BY

DRAWN BY

SHEET NUMBER

SHEET TITLE

100 SW Main Street Suite 1600 Portland, OR 97204

TEL 503.382.2266

www.interfaceengineering.com

Shem Heiple

2023-1707

1/23/2024

PO

W

EL

L

B U

TT

E

EL

EM

EN

TA

R Y

C O

O

LI

N G

U

PG

R A

D

ES

M

A

IN

O

FF

IC

E

SU

PP

O R

T

SP

A C

ES

S E

4t h A ve nu e

PO

R

TL

A N

D , O

R

12/31/24EXPIRES:

0 4' 8'

SCALE: 1/4"=1'-0"

2'

1 ENLARGED FLOOR PLAN - MECHANICAL

ENLARGED FLOOR

PLANS -

MECHANICAL &

PLUMBING

SPL

MP2.0

0 4' 8'

SCALE: 1/4"=1'-0"

2'

1 ENLARGED ROOF PLAN - MECHANICAL

Sheets and Views
MP0.1
MP1.0
MP2.0