PORTAGE PUBLIC SCHOOLS - NORTHERN CAMPUS STORAGE BUILDINGS DRAWINGS 2021 05-21 (1).pdf
PDF 3 MB Posted
- Attached to
- PORTAGE NORTHERN CAMPUS STORAGE BUILDINGS
- Solicitation number
- RFP PPS 210000001991 1
- Issued by
- Kalamazoo County, Michigan
About this file
This file contains construction documents for Portage Public Schools in Portage, Michigan, specifically architectural and engineering drawings for Northern Campus storage buildings (two pole barns). The project includes the design and construction of two storage barn structures: Barn A (2,048 square feet) and Barn B (1,280 square feet), both classified as Use Group S-1 (moderate-hazard storage) with Type VB construction. The project site is located at the Northern High School campus on a 66-acre parcel. The construction documents, dated May 21, 2021, include civil, architectural, and electrical plans with full specifications for foundation, framing, roof systems, exterior elevations, code compliance plans, electrical distribution, and site utilities. Both buildings feature engineered wood trusses at 24-inch on-center spacing, treated wood posts, concrete slab-on-grade foundations with turned-down edges, steel siding (Fabral Grandrib), asphalt shingle roofing, and multiple overhead door openings. The site plan indicates storm water retention requirements (833 cubic feet of storage provided on 3,278 square feet of impervious area) and includes utility coordination for water, electrical, and storm drainage systems.
The electrical design provides separate distribution panels for each building: Panel RPA (60 amps, 208/120V, 3-phase) for Barn A with a total estimated demand of 3,950 VA, and Panel RPB (100 amps, 208/120V, 3-phase) for Barn B with a total estimated demand of 7,900 VA. Both buildings include duplex receptacles (standard and GFCI-protected), industrial lighting fixtures, and provisions for overhead door operation with electric controls. The project references the 2015 Michigan Building Code, 2017 National Electrical Code with Michigan amendments, and compliance with Michigan Energy Code and barrier-free accessibility standards. Construction notes specify that the general contractor is responsible for obtaining all permits, tap fees, and permanent utility applications with the City of Portage. Erosion and sediment control measures are required in accordance with MDOT-EGLE standards, and the owner must obtain a soil erosion permit from the county and permit coverage from EGLE prior to construction. The documents indicate coordination with existing utilities, including relocation of water service lines and integration with existing electrical infrastructure from the main building.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 00 1113 - ADVERTISEMENT FOR BIDS - 6-8 opening (1).docx | DOCX document | |
| PORTAGE PUBLIC SCHOOLS - NORTHERN CAMPUS STORAGE BUILDINGS SPEC 2021 05-21 (1).pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN TEAM
ARCHITECT/ENGINEER
REFERENCED CODES
SITE ADDRESS
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig a n
-5
.3
.6
P H
O N
E
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
XPORTAGE - NORTHERN HIGH SCHOOL -
STORAGE BARNS
PORTAGE PUBLIC SCHOOLS
Portage, Michigan
CONSTRUCTION DOCUMENTS
C O
V E
R S
H E
E T
-2
.0
G
M A
Y
P O
R T
A G
E
N O
R T
H E
R N
H
IG
H S
C H
O O
L
S T
O R
A G
E B
A R
N S
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
DRAWING INDEX
CIVIL CONSULTANT
5725 VENTURE PARK DRIVE, SUITE A
KALAMAZOO, MI 49009
PHONE: 269.250.5991
PORTAGE PUBLIC SCHOOLS
1000 IDAHO AVE
PORTAGE, MI 49024
GENERAL
G 001 COVER SHEET
GA 101 FIRST FLOOR CODE COMPLIANCE PLAN BARN A, TYPICAL SYMBOLS AND
GENERAL NOTES
GB 101 FIRST FLOOR CODE COMPLIANCE PLAN BARN B
CIVIL - STORAGE BARN A
CA 100 SITE PLAN
CIVIL - STORAGE BARN B
CB 100 SITE PLAN
ARCHITECTURAL - STORAGE BARN A
AA 100 FOUNDATION AND FRAMING PLAN
AA 101 FIRST FLOOR PLAN, ROOF FRAMING PLAN AND DOOR SCHEDULE
AA 301 EXTERIOR ELEVATIONS, BUILDING SECTIONS, 3D VIEW AND WALL
SECTIONS
ARCHITECTURAL - STORAGE BARN B
AB 100 FOUNDATION AND FRAMING PLAN
AB 101 FIRST FLOOR PLAN, ROOF FRAMING PLAN AND DOOR SCHEDULE
AB 301 EXTERIOR ELEVATIONS, BUILDING SECTIONS, AND 3D VIEW
ELECTRICAL
EA 101 STORAGE BARN A ELECTRICAL PLAN
EB 101 STORAGE BARN A ELECTRICAL PLAN
242 E. KALAMAZOO AVE, SUITE 100
KALAMAZOO, MICHIGAN 49007
PHONE: 269.343.6133
FAX: 269.343.6633
BUILDING: 2015 MICHIGAN BUILDING CODE AND 2012 NFPA 101 LIFE SAFETY CODE
ENERGY: 2015 MICHIGAN ENERGY CODE
PLUMBING: 2015 MICHIGAN PLUMBING CODE
MECHANICAL: 2015 MICHIGAN MECHANICAL CODE
FUEL GAS: (IFGC) 2015 INTERNATIONAL FUEL GAS CODE
ELECTRICAL: 2017 NATIONAL ELECTRICAL CODE WITH MICHIGAN AMENDMENTS
BARRIER-FREE: 2015 MICHIGAN BUILDING CODE AND 2009 ICC & C A117.1
USE GROUP: S-1
CONSTRUCTION TYPE: TYPE VB
AUTOMATIC SPRINKLERS: NON SPRINKLED
PROJECT AREA
STORAGE BARN A 2,048 SQ. FT.
4 EAST FULTON STREET, SUITE 200
GRAND RAPIDS, MICHIGAN 49503
PHONE: 616.456.9944
FAX: 616.456.5936
STORAGE BARN B 1,280 SQ. FT.
ISSUED FOR DATE
1. ALL PENETRATIONS THROUGH A FIRE OR SMOKE RATED PARTITION SHOULD BE
SEALED WITH AN APPROVED U.L. RATED PRODUCT.
2. THE TOPS OF ALL FIRE RATED PARTITIONS SHALL BE SEALED TO THE
CONTINUOUS STRUCTURE ABOVE WITH A U.L. RATED SYSTEM OR ASSEMBLY.
3. WOOD BLOCKING IN FIRE-RATED PARTITIONS SHALL BE NON-COMBUSTIBLE
TREATED WOOD.
4. REFER TO SPECIFICATION U.L. RATING INFORMATION.
5. FIRE-RATED WALLS ENDING INTO AN ACOUSTICAL DECK MUST HAVE THE FLUTES
FILLED, REFER TO 'TOP OF WALL DETAIL AT ACOUSTIC DECK' SHOWN ON THIS
SHEET.
• FOR MASONRY WALLS THE MASON SHALL FILL VOIDS AND FIRE SPRAY WITH UL LISTED
MATERIAL.
• FOR STUD WALLS USE FIRE SAFING AND FIRE CAULK.
CODE COMPLIANCE KEY
EGRESS SYMBOLS
EGRESS EXIT NUMBER FROM ROOM OR SPACE
MAXIMUM NUMBER OF OCCUPANTS PERMITTED
BY EGRESS WIDTH
ROOM OR SPACE EGRESS IS FROM
TRAVEL DISTANCE : 100'-0"
PERMITTED TRAVEL DISTANCE - 200'-0"
EXISTING TRAVEL DISTANCE
TO EGRESS DOOR
PERMITTED MAXIMUM TRAVEL
DISTANCE PER CONDITION
DIRECTION OF EGRESS
FIRE SAFETY SYMBOLS
XFE
XFEC
FE
FEC
EXISTING FIRE EXTINGUISHER
EXISTING FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FIRE-RATING KEY
DESIGNATION PARTITION RATING PRIORITY
3 HOUR 1
2 HOUR FIRE/SMOKE
2 HOUR
1 HOUR FIRE/SMOKE
1HOUR
SMOKE RESISTANT
EGRESS
Door #
EGRESS ROOM
GENERAL NOTES - ARCHITECTURAL
1. THE OWNER RESERVES THE RIGHT TO REMOVE ANY ITEM FROM THE PROJECT PRIOR
TO COMMENCEMENT OF CONTRACTED DEMOLITION WORK.
2. ALL EXISTING CONDITIONS SHOULD BE FIELD VERIFIED BEFORE WORK BEGINS.
3. DIMENSIONS GIVEN ARE ACTUAL AND ARE TO THE FACE OF MASONRY UNITS OR TO
THE FACE OF STUD FRAMING, UNLESS NOTED OTHERWISE.
4. DETAILS SHOWN ILLUSTRATE DESIGN INTENT, NOT ALL POSSIBLE CONDITIONS. FOR
CONDITIONS NOT SHOWN, USE DETAILS CLOSEST TO CONDITION IN QUESTION.
5. EXTEND ALL INTERIOR WALL PARTITIONS FROM FLOOR TO STRUCTURE/DECK ABOVE
UNLESS NOTED OR DETAILED OTHERWISE.
6. WITHIN BUILDING INTERIOR PROVIDE BULLNOSE BLOCK IN CMU WALL ASSEMBLIES AT
ALL EXPOSED OUTSIDE CORNERS, INCLUDING WINDOW AND DOOR JAMBS, UNLESS
NOTED OR DETAILED OTHERWISE. PROVIDE SQUARE OUTSIDE CORNERS AT ALL
LOCATIONS FINISHED WITH WALL TILE, REFER TO FINISH PLANS (A600 SHEETS)
FOR LOCATIONS.
7. TOOTH-IN MASONRY AT NEW OPENINGS IN EXISTING WALLS.
8. TOOTH-IN NEW MASONRY INFILL INTO EXISTING OPENINGS AT ALL BULLNOSE BLOCK
LOCATIONS.
9. STUD WALLS SPANNING OVER 12'-0" IN HEIGHT SHALL BE A MINIMUM OF 20 GAGE.
10. STUD WALL SUPPORTING WALL CABINETS SHALL BE A MINIMUM OF 20 GAGE.
11. DOORS ARE TO BE 4" FROM CORNER OF ROOM, UNLESS NOTED OR DIMENSIONED
OTHERWISE.
12. FIRESTOP ALL INTERCONNECTIONS BETWEEN VERTICAL AND HORIZONTAL SPACES AND
CONCEALED WALL SPACES AT CEILING, FLOOR AND ROOF LEVELS.
13. FIRESEAL ALL PENETRATIONS, SUCH AS, PIPES, DUCTS, CONDUITS, ETC. THROUGH
FIRE AND/OR SMOKE RATED ASSEMBLIES.
14. FOR CONTROL JOINT (C.J.) LOCATIONS REFER TO EXTERIOR ELEVATIONS AND/OR
FLOOR PLANS.
15. PAINT ALL ELECTRICAL PANEL COVERS AND ACCESS PANELS TO MATCH ADJACENT
FINISHES. USING OIL-BASED PAINT, NOT LATEX WALL PAINT.
16. PROVIDE WOOD BLOCKING IN WALLS THAT REQUIRE WALL MOUNTED EQUIPMENT OR
ACCESSORIES. COORDINATE WITH EQUIPMENT OR ACCESSORY MANUFACTURER.
17. PROVIDE ALL ASSOCIATED CURBS FOR ROOF TOP EQUIPMENT AND MECHANICAL
ROOF TOP UNITS. LARGE VOIDS BELOW THE AIR HANDLING UNITS SHALL BE FILLED
WITH INSULATION AS SPECIFIED FOR NOISE CONTROL.
18. ALL EXISTING ROOF TOP PENETRATIONS BEING REMOVED REQUIRE ROOF PATCHING
TO MATCH EXISTING ADJACENT.
A101A
TYPICAL SYMBOLS & REFERENCES
NOTE:
ROOM NAMES AND NUMBERS ON PLANS ARE
FOR CONSTRUCTION PURPOSES ONLY.
COORDINATE WITH OWNER REGARDING
PROPOSED NUMBERS FOR ALL SIGNAGE,
SCHEDULE AND PANEL DESIGNATIONS.
ROOM IDENTIFICATION TAG
ROOM NAME
ROOM NUMBER
DETAIL TITLE
1 DETAIL TITLE
1" = 0'-1"A101
DETAIL NUMBER
SHEET NUMBER
UNIT MATCHLINES
U N
IT
A
U N
IT
B
TYPICAL NOTATION SYMBOLS
CALLOUT REFERENCE BUBBLE
A351
DETAIL NUMBER
SHEET NUMBER
EXTERIOR ELEVATION REFERENCE BUBBLE
A301
A
ELEVATION LETTER
SHEET NUMBER
INTERIOR ELEVATION REFERENCE BUBBLE
4 A 652
ELEVATION NUMBER
SHEET NUMBER
DETAIL REFERENCE BUBBLE
A351
DETAIL NUMBER
SHEET NUMBER
BUILDING SECTION REFERENCE BUBBLE
A 311
DETAIL NUMBER
SHEET NUMBER
ELEVATION AND SECTION REFERENCE TOOLS
ELEVATION TAG - EXISTING
FINISH FLOOR
ELEVATION 100'-0"
ELEVATION TAG FOR EXTERIOR ELEVATIONS
AND BUILDING SECTIONS
100'-0" ELEVATION TAG FOR FLOOR PLANS AND
REFLECTED CEILING PLANS
ELEVATION TAG - NEW
FINISH FLOOR
ELEVATION 100'-0"
100'-0"
ELEVATION TAG FOR EXTERIOR ELEVATIONS
AND BUILDING SECTIONS
ELEVATION TAG FOR FLOOR PLANS AND
REFLECTED CEILING PLANS
WORKING POINT LAYOUT TAG
100'-0" : 100'-0"
DISTANCE IN THE "Y" DIRECTION FROM THE
"X" BASE LINE
DISTANCE IN THE "X" DIRECTION FROM THE
"Y" BASE LINE
BORROWED LIGHT AND DOOR IDENTIFICATION
A 502
SHEET NUMBER
ELEVATION NUMBER
DOOR NUMBER - CORRESPONDS TO THE ROOM NUMBER
LETTER DESIGNATES MORE THAN ONE IN ROOM
SYMBOLS
BARRIER-FREE
B1 REVISION IDENTIFIER (ADDENDUM AND BULLETIN)
COLUMN BUBBLE AND LINE
CLASSROOM
A000A
GENERAL DEMOLITION NOTES
1. CONTRACTORS ARE REQUIRED TO INSPECT/REVIEW THE EXISTING BUILDING PRIOR TO
RELATED DEMOLITION WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY WALL,
FLOOR OR CEILING INCLUDES ALL GENERAL MECHANICAL AND ELECTRICAL ITEMS
WHICH ARE A PART OF, OR ATTACHED TO IT.
2. CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE CONDITIONS AND DIMENSIONS
AND BE RESPONSIBLE FOR THE SAME. ADVISE CONSTRUCTION MANAGER OF ANY
AND ALL DISCREPANCIES.
3. PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING CONSTRUCTION AND
DEMOLITION AS REQUIRED. FINISH TO MATCH EXISTING.
4. ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.
5. PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.
6. REFER TO DEMOLITION ELEVATIONS, SECTIONS AND DETAILS FOR ADDITIONAL
INFORMATION.
7. REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL PLANS FOR
ADDITIONAL DEMOLITION NOTES.
8. SALVAGE ALL UNISTRUT AND PROTECT FOR RE-USE IN NEW CONSTRUCTION, IF
REQUIRED.
9. AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED ITEMS ATTACHED TO THE WALL
ARE TO BE REMOVED. SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS,
TACKBOARDS, TACK STRIPS, ETC.
A B C D E
STORAGE
E G
R E
S S
O
C C
TR
A V
EL
D
IS
TA
N C E:
'-0
TR
A V
EL
D
IS
TA
N C E:
'-0
E G
R E
S S
3 2
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
X
F
IR
S T
F L O
O R
C O
D E
C O
M P
L
IA
N C
E P
L A
N B
A R
N A
T
Y P
IC
A
L S
Y M
B O
L S
A N
D G
E N
E R
A L N
O T
E S
-2
.0
G A
M A
Y
P O
R T
A G
E
N O
R T
H E
R N
H
IG
H S
C H
O O
L
S T
O R
A G
E B
A R
N S
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
Michigan Building Code – 2015 Edition
Section 311.2: The storage room to be classified as Moderate-hazard Storage Group
S-1. (Must comply with the maximum allowable quantities of hazardous materials listed in Table 307.1 (1).
Table 504.3: Allowable Height: Occupancy S-1, Type V-S: 40 feet
Table 504.4: Allowable Stories: Occupancy S-1, Type V-S: 1 Story
Section 506.2: Allowable Area: Occupancy S-1, Type V-NS: 9,000 sf
Section 506.3: A frontage increase is not required. The building area complies with the allowable area in Table 506.2.
Section 602.2: Table 601 – Construction Type V-B (Non-sprinklered – Single Story)
Construction in which structural elements, and exterior walls, and interior walls are of any materials permitted by this code.
Table 1004.1.2: Occupant Load Factors
Storage Areas: 300 gross
Calculated Occupancies
Storage (2,048 gross sq. ft.) – 7 Occupants
Section 1005.3: Egress Capacity Factors
1005.3.2 All others = 0.2 inches per Occupant
Table 1006.2.1: Maximum Common Path of Travel shall not exceed: Storage: 100 ft without sprinkler system and occupant load is less than 30 occupants
Section 1007.1.1 Where two exits, exit access doorways, exit access stairways or ramps, or any combination thereof, are required from any portion of the exit access, they shall be placed a distance apart equal to not less than one-half of the length of the maximum overall diagonal dimension of the building or area to be served measured in a straight line between them.
Table 1017.2 Exit Access Travel Distance shall not exceed:
Storage: 200 feet
1/8" = 1'-0"
FIRST FLOOR CODE COMPLIANCE PLAN
1. ALL PENETRATIONS THROUGH A FIRE OR SMOKE RATED PARTITION SHOULD BE
SEALED WITH AN APPROVED U.L. RATED PRODUCT.
2. THE TOPS OF ALL FIRE RATED PARTITIONS SHALL BE SEALED TO THE
CONTINUOUS STRUCTURE ABOVE WITH A U.L. RATED SYSTEM OR ASSEMBLY.
3. WOOD BLOCKING IN FIRE-RATED PARTITIONS SHALL BE NON-COMBUSTIBLE
TREATED WOOD.
4. REFER TO SPECIFICATION U.L. RATING INFORMATION.
5. FIRE-RATED WALLS ENDING INTO AN ACOUSTICAL DECK MUST HAVE THE FLUTES
FILLED, REFER TO 'TOP OF WALL DETAIL AT ACOUSTIC DECK' SHOWN ON THIS
SHEET.
• FOR MASONRY WALLS THE MASON SHALL FILL VOIDS AND FIRE SPRAY WITH UL LISTED
MATERIAL.
• FOR STUD WALLS USE FIRE SAFING AND FIRE CAULK.
CODE COMPLIANCE KEY
EGRESS SYMBOLS
EGRESS EXIT NUMBER FROM ROOM OR SPACE
MAXIMUM NUMBER OF OCCUPANTS PERMITTED
BY EGRESS WIDTH
ROOM OR SPACE EGRESS IS FROM
TRAVEL DISTANCE : 100'-0"
PERMITTED TRAVEL DISTANCE - 200'-0"
EXISTING TRAVEL DISTANCE
TO EGRESS DOOR
PERMITTED MAXIMUM TRAVEL
DISTANCE PER CONDITION
DIRECTION OF EGRESS
FIRE SAFETY SYMBOLS
XFE
XFEC
FE
FEC
EXISTING FIRE EXTINGUISHER
EXISTING FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FIRE-RATING KEY
DESIGNATION PARTITION RATING PRIORITY
3 HOUR 1
2 HOUR FIRE/SMOKE
2 HOUR
1 HOUR FIRE/SMOKE
1HOUR
SMOKE RESISTANT
EGRESS
Door #
EGRESS ROOM
F G H I
STORAGE
TR
A V
EL D
IS
TA
N C E: 6
'-0
TR
A V
EL D
IS
TA
N C E: 2
'-0
AB 301
AB 301
E G
R E
S S
O
C C
E G
R E
S S
O
C C
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
X
F
IR
S T
F L O
O R
C O
D E
C O
M P
L
IA
N C
E P
L A
N B
A R
N B
-2
.0
G B
M A
Y
P O
R T
A G
E
N O
R T
H E
R N
H
IG
H S
C H
O O
L
S T
O R
A G
E B
A R
N S
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
Michigan Building Code – 2015 Edition
Section 311.2: The storage room to be classified as Moderate-hazard Storage Group
S-1. (Must comply with the maximum allowable quantities of hazardous materials listed in Table 307.1 (1).
Table 504.3: Allowable Height: Occupancy S-1, Type V-S: 40 feet
Table 504.4: Allowable Stories: Occupancy S-1, Type V-S: 1 Story
Section 506.2: Allowable Area: Occupancy S-1, Type V-NS: 9,000 sf
Section 506.3: A frontage increase is not required. The building area complies with the allowable area in Table 506.2.
Section 602.2: Table 601 – Construction Type V-B (Non-sprinklered – Single Story)
Construction in which structural elements, and exterior walls, and interior walls are of any materials permitted by this code.
Table 1004.1.2: Occupant Load Factors
Storage Areas: 300 gross
Calculated Occupancies
Storage (1,280 gross sq. ft.) – 5 Occupants
Section 1005.3: Egress Capacity Factors
1005.3.2 All others = 0.2 inches per Occupant
Table 1006.2.1: Maximum Common Path of Travel shall not exceed: Storage: 100 ft without sprinkler system and occupant load is less than 30 occupants
Section 1007.1.1 Where two exits, exit access doorways, exit access stairways or ramps, or any combination thereof, are required from any portion of the exit access, they shall be placed a distance apart equal to not less than one-half of the length of the maximum overall diagonal dimension of the building or area to be served measured in a straight line between them.
Table 1017.2 Exit Access Travel Distance shall not exceed:
Storage: 200 feet
1/8" = 1'-0"
FIRST FLOOR CODE COMPLIANCE PLAN
20' WATERMAIN EASEMENT
CITY OF PORTAGE
DOC # 2019-025061
STM
WV
WV
WV
C B
4.0' BLOCK STM CBS
RIM = 889.08
INV. 18" E RCP = 884.06
INV. 12" W RCP = 885.03
INV. 24" N SLCPP = 884.03
INV. 6" S CLAY = 885.08
WATER = 884.03
SEDIMENT = 882.08
STM
CB
893.09
893.09
893.09
3.
893.05
893.05
893.05
893.05
893.05
892.95
892.10 M
.E.
892.39 M
.E.
892.63 M
.E.
892.92 M
.E.
893.09 M
.E.
893.05
8" HDPE SW I.E. 888.78
6" HDPE SE I.E. 8887.78
LB-2
4' DIA. - EJ 1020 O2 BEEHIVE
RIM: 892.00
8" HDPE SW I.E. 888.26
LB-4
4' DIA. - EJ 1020 SOLID
RIM: 892.27
8" HDPE NE I.E. 889.05
6" HDPE S I.E. -2.02
LB-1
2' DIA. - EJ 1020 O2 BEEHIVE
RIM: 891.60
8" HDPE NE I.E. 888.57
CO-3
2' DIA. - CLEANOUT
RIM: 893.02
893.05
893.05
892.95
6" PVC NE I.E. 889.05
BTM: 884.90
6" PVC SE I.E. 888.78
BTM: 884.78
6" PVC NE I.E. 888.26
BTM: 884.27
893.06 M
.E.
892.79 M
.E.
" N
.5
0%
" N
.5
0%
12" STM.
6" S
TM
S H
E E
T
T
I T
L E
S H
E E
T
N
U M
B E
R
O W
N E
R P
R O
J E
C T
I T
L E
D A
T E
E a s t
K a l a m a z o o
A v e n u e
S u i t e
K a l a m a z o o
M i c h i g
P
H O
.3
.6
F
A X
T O
W E
R P
I N
K S
T E
R C
O M
A L
L
R
I G
H T
S
R
E S
E R
V E
D
E a s t
F u l t o n
S t r e e t
S u i
G r a n d
R a p i d s
M i c h i g a n
4 P
H O
N E
.4
.5
F
A X
1. DIMENSIONS TAKE PRECEDENCE OVER SCALE. CONTRACTOR
TO VERIFY ALL DIMENSIONS IN FIELD.
2. IF ANY ERRORS, DISCREPANCIES, OR OMISSIONS BECOME
APPARENT, THESE SHALL BE BROUGHT TO THE ATTENTION
OF THE ARCHITECT/ ENGINEER PRIOR TO CONSTRUCTION OF
ANYTHING AFFECTED SO THAT CLARIFICATION OR REDESIGN
MAY OCCUR.
1. PROPERTY INFORMATION:
PARCEL #s: 00017-095-O
SITE AREA: 2,875,000 SF (66 AC)
OWNER: PORTAGE PUBLIC SCHOOLS
8107 MUSTANG DR
PORTAGE, MI 49002
2. ZONING:
R-1B RESIDENTIAL
ABUTTING PROPERTY CURRENTLY ZONED:
NORTH: R-1B RESIDENTIAL
SOUTH: PD RESIDENTIAL
EAST: R-1B RESIDENTIAL
WEST: PD RESIDENTIAL/RM-1 RESIDENTIAL
3. SETBACKS
FRONT = 0'
SIDES = 0' (25' IF ABUTS R DISTRICT)
REAR = 0' (25' IF ABUTS R DISTRICT)
4. PARKING: NOT APPLICABLE
5. STORM WATER RETENTION REQUIRED
TOTAL IMPERVIOUS AREA: 3,278 SQFT
REQUIRED STORM WATER VOLUMES
BASED ON 3" OVER IMPERVIOUS AREA:
REQUIRED STORAGE VOLUME: 820 CFT
PROVIDED VOLUME: 833 CFT
SITE DATA
GENERAL NOTES
A. 6" CONCRETE PAVEMENT (SEE DETAIL THIS SHEET)
B. CONNECT ELECTRIC SERVICE AND METER, COORDINATE WITH UTILITY PROVIDER
C. 10' OVERHEAD DOOR
D. MAN DOOR
SITE PLAN NOTES
1. ALL WORK SHALL CONFORM TO ALL LOCAL, STATE AND FEDERAL LAWS, RULES AND REGULATIONS
IN FORCE AT TIME OF CONSTRUCTION.
2. ALL WORK SHALL CONFORM TO THE MICHIGAN HANDICAPPED ACCESSIBILITY CODE AND THE
AMERICANS WITH DISABILITIES ACT.
3. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PERMIT
COSTS, TAP FEES, METER DEPOSITS, PERMANENT UTILITY APPLICATIONS, BONDS, AND OTHER
FEES REQUIRED FOR PROPOSED WORK.
4. CONTACT "MISS DIG" AT 1-800-482-7171 FOR LOCATION OF UNDERGROUND UTILITIES A MINIMUM
OF 48 HOURS BEFORE COMMENCING EXCAVATION WORK. THIS DOES NOT RELIEVE THE
CONTRACTOR OF THE RESPONSIBILITY OF NOTIFYING UTILITY OWNERS WHO ARE NOT PART OF
THE "MISS DIG" ALERT SYSTEM. THE CONTRACTOR SHALL CONDUCT HIS OPERATIONS IN A
MANNER AS TO ENSURE THAT THOSE UTILITIES NOT REQUIRING RELOCATION WILL NOT BE
DISTURBED.
5. MANHOLE AND CATCH BASIN STRUCTURES SHALL BE PRECAST AND HAVE A MAXIMUM OF 2
ADJUSTING RINGS FOR FINISH GRADE ADJUSTMENT.
6. DEMOLISH & REMOVE ALL EXISTING SITE FEATURES AS REQUIRED.
1. SOILS EXPOSED IN THE BASE OF ALL SATISFACTORY FOUNDATION EXCAVATIONS SHOULD BE
PROTECTED AGAINST ANY DETRIMENTAL CHANGES IN CONDITION SUCH AS FROM DISTURBANCE,
RAIN AND FREEZING. SURFACE RUN-OFF WATER SHOULD BE DRAINED AWAY FROM THE
EXCAVATION AND NOT ALLOWED TO POND. IF POSSIBLE, ALL FOOTING CONCRETE SHOULD BE
POURED THE SAME DAY THE EXCAVATION IS MADE. IF THIS IS NOT PRACTICAL, THE FOOTING
EXCAVATIONS SHOULD BE ADEQUATELY PROTECTED.
2. REMOVE ALL SUBGRADE GRADE MATERIAL THAT MAY BE SOFTENED BY RAINS, FREEZING, OR
CONSTRUCTION TRAFFIC, ETC. AND REPLACE WITH COMPACTED GRANULAR FILL.
3. THE CONTRACTOR SHALL INSTALL A PEDESTRIAN FENCE AROUND ALL EXCAVATIONS TO BE LEFT
OPEN OVERNIGHT AS REQUIRED.
4. EXTERIOR CONCRETE SHALL HAVE A COMPRESSIVE STRENGTH OF 4000 PSI AND SHALL HAVE
LIMESTONE AGGREGATE AND SHALL HAVE 4 - 6 % AIR ENTRAINMENT WITH A BROOM FINISH.
5. EXPANSION JOINTS IN CONCRETE PAVEMENT AND WALLS SHALL BE 1/2" ASPHALT IMPREGNATED FULL DEPTH 40' O.C. MAXIMUM & AT SIDEWALK INTERSECTIONS. CRACK CONTROL SCORING AT
SIDEWALK WIDTH DIMENSION AND @ 10'-0" O.C. IN DRIVES.
SITE MATERIALS & CONSTRUCTION NOTES:
GENERAL CONSTRUCTION NOTES
LIMITS OF CONSTRUCTION
LEGEND
SAWCUT
1. ALL WORK SHALL CONFORM TO ALL LOCAL, STATE AND FEDERAL LAWS, RULES AND REGULATIONS IN
FORCE AT TIME OF CONSTRUCTION.
2. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PERMIT COSTS, TAP FEES, METER DEPOSITS, PERMANENT UTILITY APPLICATIONS, BONDS, AND OTHER FEES
REQUIRED FOR PROPOSED WORK. THIS SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO THOSE
REQUIRED BY THE CITY OF PORTAGE
3. CONTACT "811" AT 1-800-482-7171 FOR LOCATION OF UNDERGROUND UTILITIES A MINIMUM OF 48
HOURS BEFORE COMMENCING EXCAVATION WORK. THIS DOES NOT RELIEVE THE CONTRACTOR OF
THE RESPONSIBILITY OF NOTIFYING UTILITY OWNERS WHO ARE NOT PART OF THE "811" ALERT SYSTEM. THE CONTRACTOR SHALL CONDUCT HIS OPERATIONS IN A MANNER AS TO ENSURE THAT
THOSE UTILITIES NOT REQUIRING RELOCATION WILL NOT BE DISTURBED.
4. DEMOLISH & REMOVE ALL EXISTING SITE FEATURES AS REQUIRED.
5. MATCH EXISTING GRADES AROUND PERIMETER WITH SLOPES AS SHOWN.
6. ALL SPOT ELEVATIONS ARE TOP OF PAVEMENT GRADES AT EDGE OF METAL (EOM) UNLESS
OTHERWISE NOTED.
7. ALL SOIL EROSION CONTROL MEASURES SHALL BE IN PLACE PRIOR TO MASS GRADING.
8. ALL EXCAVATION SHALL BE IN ACCORDANCE WITH THE TECHNICAL SPECIFICATIONS AND
GEOTECHNICAL REPORT.
9. ALL EXISTING ELEVATIONS ARE TO BE VERIFIED AND ACCEPTED AS SHOWN PRIOR TO
COMMENCEMENT OF WORK.
10. CONTRACTOR SHALL TAKE PRECAUTIONS TO AVOID TRACKING SOIL ONTO ADJACENT ROADWAYS.
CONTRACTOR SHALL SWEEP IMMEDIATELY IF OCCURS.
11. ANY DISTURBED AREA WHICH WILL BE LEFT UNWORKED 15 DAYS OR LONGER MUST BE SEEDED TO
ESTABLISH VEGETATION FOR TEMPORARY STABILIZATION. BASINS TO BE SEEDED AND MULCH
BLANKETS APPLIED IMMEDIATELY TO PROVIDE A STABLE BASE AND AVOID EXCESSIVE EROSION.
GRADING NOTES
DENOTES PERMANENT SEEDING. ALL DISTURBED AREAS NOT PAVED OR GRAVELED SHALL
BE RESTORED. PLACE TOPSOIL SURFACE, SALV, 3 INCH, MDOT SEEDING, MIXTURE TUF
APPLIED AT A RATE OF 220 LB/ACRE, FERTILIZER, CHEMICAL NUTRIENT, CL A APPLIED AT A
RATE OF 228 LB/ACRE; MULCH AT A RATE OF 2 TON/ACRE AND MULCH ANCHORING.
(APPLIES TO ENTIRE PROJECT)
DENOTES TEMPORARY SILT FENCE. SILT FENCE SHALL BE INSTALLED AT CREEK
CROSSINGS, ADJACENT TO ALL WETLANDS AND SURFACE WATERS, AND OTHER
LOCATIONS AS DIRECTED BY THE ENGINEER. EACH SILT FENCE SHALL BE INSTALLED
GENERALLY ALONG THE SAME CONTOUR ELEVATION.
SOIL EROSION & SEDIMENTATION CONTROL NOTES
1 ALL CONSTRUCTION METHODS SHALL BE DONE IN COMPLIANCE WITH MDOT-EGLE. THE OWNER SHALL BE RESPONSIBLE FOR OBTAINING A "SOIL EROSION PERMIT" FROM THE COUNTY AND A "PERMIT BY RULE/NOTICE OF COVERAGE" FROM EGLE, IF APPLICABLE, PRIOR TO START OF CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ALL REQUIREMENTS OF THE COUNTY "SOIL EROSION PERMIT" AND FOR ALL CERTIFIED STORM WATER INSPECTION SERVICE REQUIRED BY THE "PERMIT BY RULE." EROSION CONTROL MEASURES SHOWN ON THE PLANS ARE THE MINIMUM REQUIREMENTS AND SHALL NOT RELIEVE THE CONTRACTOR'S
RESPONSIBILITY FOR PROVIDING ALL REQUIRED EROSION CONTROL MEASURES.
2. AVOID UNNECESSARY DISTURBING OR REMOVING OF EXISTING VEGETATED TOPSOIL OR EARTH COVER, THESE COVER
AREAS ACT AS SEDIMENT FILTERS.
3. ALL TEMPORARY SOIL EROSION PROTECTION SHALL REMAIN IN PLACE UNTIL REMOVAL IS REQUIRED FOR FINAL CLEAN
UP AND APPROVAL.
4. GEOTEXTILE SILT FENCE SHALL BE INSTALLED AS REQUIRED WHEN CROSSING CREEKS OR WHEN ADJACENT TO WETLANDS OR SURFACE WATER BODIES TO PREVENT SILTATION AND ELSEWHERE AS DIRECTED BY THE ENGINEER.
SEEDING AND/OR SODDING SHALL BE INSTALLED ON CREEK BANKS IMMEDIATELY AFTER CONSTRUCTION TO PREVENT
EROSION.
5. MAINTENANCE, CLEANING, AND REMOVAL OF THE VARIOUS SEDIMENT CONTROL MEASURES SHALL BE INCLUDED IN
THE VARIOUS EROSION CONTROL ITEMS.
NUMBER IN CIRCLE REFERS TO NUMBERED DETAILS ON MDOT STANDARD PLAN R-96-D, SOIL EROSION & SEDIMENTATION CONTROL MEASURES. "P" DENOTES PERMANENT MEASURE AND "T" DENOTES TEMPORARY MEASURE.
SOIL EROSION CONTROL PLANS DENOTE MINIMUM EROSION MEASURES REQUIRED AS DESCRIBED BELOW.
3P
26T
SILT FENCE
M.E. MATCH EXISTING GRADE
DENOTES INLET PROTECTION FABRIC DROP. SHALL BE INSTALLED AT EXISTING AND
PROPOSED STORM SEWER INLETS TO PROVIDE SETTLING AND FILTERING OF SILT LADEN
WATER PRIOR TO ENTRY INTO THE DRAINAGE SYSTEM.
29T
S I T
E
P
L A
N
A
M A
Y
P O
R T
A G
E
W
E S
T
S T
O R
A G
E
B
A R
N
P o r t a g e
M i c h i g a n
P O
R T
A G
E
P
U B
L I C
S C
H O
O L
S
ISSUED FOR DATE
EX. 8" W.M.
EX. 8" W.M.
E X
. 8 " W
.M
GROUND SURFACE EJIW 1410
3' M
A X
THREADED PLUG CAP
UNLESS OTHERWISE
SPECIFIED
SIZE OF PIPE AS
SHOWN ON PLANS GRAVEL FILL (WITHIN OPENING
AROUND PIPE END SECTION)
CONCRETE REINFORCED
FOOTING
GRADE 35S OR PRECAST
REINFORCED SECTION
UNLESS OTHERWISE
SPECIFIED
CONCRETE ADJUSTING
RING GRADE35S, CONC.
REINF. BATTER BLOCKS
AND MORTAR, OR
REINF. PRECAST
MANHOLE SECTION.
(2) 45° (1
8 BEND)
PIPE SECTION
6" MINIMUM COMPACTED (98%)
SAND SUB-BASE (MDOT CLASS II)
OR AS RECOMMENDED BY
GEOTECHNICAL
ENGINEER
6" (4" CONCRETE WHEN
REPLACING SIDEWALK)-4,000 P.S.I.
NON-REINFORCED
CONCRETE TOPSOIL
ACCEPTABLE COMPACTED SUB-BASE (AS
RECOMMENDED BY GEOTECHNICAL ENGINEER)
1.0' MIN.
N 1 inch = ft.
10 2015
3P
29T
3P
3P
PAVEMENT REMOVAL/
RECONSTRUCTION
REMOVE & REPLACE ASPHALT
AS NECESSARY TO
CONSTRUCT PROPOSED
STORM IMPROVEMENTS.
PROPOSED POLE
BARN A
2,145 SFT
SLAB ON GRADE
F.F. - 893.09
EX. ASPHALT
EX. ASPHALT
EX. CONC.
EX. CONC.
33'
A
A
A
A
A
B
C
C
D
8'
EJIW 1020 M3
(OR APPROVED EQUAL)
48" DIA.
2' 2'
1'
24" MIN., 36" MAX.
PRECAST REINFORCED CONCRETE
BASE SECTION
COARSE AGGREGATE,
WASHED MDOT 6A
PRECAST PERFORATED
CONCRETE STRUCTURE
COARSE AGGREGATE,
WASHED MDOT 6A
NONWOVEN GEOTEXTILE
FABRIC, AMOCO 4553
OR EQUAL
NOTE:
INLET SHALL BE
CONSTRUCTED IN
ACCORDANCE WITH ASTM
SPECIFICATION C-478
LEACHING BASIN DETAIL
NOT TO SCALE
CLEANOUT DETAIL
NOT TO SCALE
CONC. PAVEMENT SECTION
NOT TO SCALE
EXSISTING GATE
CONCRETE SIDEWALK SEE
DETAIL THIS SHEET
D
S
T
A
O
F M
I C
H
I
G
A
N
L
S
D
P
R
O
F
E S S I
O
L
G
29T
29T
29T
3.5'
3.
5'
3.
5'
ALL UTILITIES AS SHOWN ARE APPROXIMATE LOCATIONS DERIVED
FROM ACTUAL MEASUREMENTS AND AVAILABLE RECORDS. THEY
SHOULD NOT BE INTERPRETED TO BE EXACT LOCATION NOR
SHOULD IT BE ASSUMED THAT THEY ARE THE ONLY UTILITIES IN THE
AREA. FIELD WORK PERFORMED BY: H & S ENGINEERING
Civil Engineers & Surveying
MICHIGAN | INDIANA | ILLINOIS | OHIO
AR Engineering www.arengineeringllc.com
269.250.5991 PHONE | 866.569.0604 FAX
-2
.0
G
WV
WV
CB CB
STM
CB
CB
HIGH
SCHOOL
BUILDING
AHU
BM
4"
N
.3 0%
26' - 24" N12 @ 0.30%
24" HDPE N I.E. 883.38
24" HDPE N I.E. 883.38
24" HDPE S I.E. 883.38
12" HDPE SW I.E. 883.38
CB-8
4' DIA. - EJ 1020 SOLID
RIM: 889.88
24" HDPE E I.E. 883.17
24" HDPE N I.E. 882.53
CB-6
4' DIA. - EJ 1020 M3
RIM: 889.63
" S
TM
" S
TM
EX. GATE
EX. 9 CONDUITS
EX. 4 CONDUITS
STONES
SIGN
24" HDPE W I.E. 883.25
24" HDPE S I.E. 883.10
CB-7
4' DIA. - EJ 1020 M3
RIM: 889.47
12" HDPE NE I.E. 883.43
IN-9
18" DIA. - ADS NYLOPLAST YARD DRAIN
RIM: 889.18
15' - 12" HDPE @ 0.33%
EXISTING WOOD
FENCE
EXISTING CHAIN
LINK FENCE
EX. TO BE REMOVED
EX. TO BE REMOVED
6" PVC SW I.E. 884.17
6" PVC SE I.E. 884.17
6" PVC SE I.E. 884.24
CB-21
18" DIA. - ADS NYLOPLAST GRATE
RIM: 889.31
CB-20
18" DIA. - ADS NYLOPLAST GRATE
RIM: 889.11
8" PVC W I.E. 886.13
8" PVC W I.E. 886.12
889.67
889.67
889.67 889.67
889.67
889.47
889.37
889.48
889.60 889.60
889.36
889.67
889.88
889.58
889.52
889.47
889.56 M
.E.
889.66 M
.E.
889.81 M
.E.
890.01 M
.E.
890.17 M
.E.
890.53 M
.E.
889.16 M
.E.
889.27 M
.E.889.40 M
.E.
889.29 M
.E.889.32 M
.E.889.39 M .E.
889.35 M
.E.
889.53 M
.E.
889.14 M
.E.
889.60
889.67
889.17889.57
889.58
889.18
889.33
889.27
890.10 M
.E.
889.60
889.17
889.38
889.35 M
.E.
889.14 M
.E.
4.0' CONCRETE STM CBR
RIM = 887.45
INV. 24" N SLCPP = 882.95
INV. 24" S SLCPP = 882.95
WATER = 882.95
SEDIMENT = 882.65
WV
WV
CB
WOODEN PATH
WITH HANDRAILS
HIGH
SCHOOL
BUILDING
WOODEN STOOP3 CONDUITS
S
TO
R
Y B
U
IL
D
IN
G
BM
EX. GATE
EX. 4 CONDUITS
STONES
S H
E E
T
T
I T
L E
S H
E E
T
N
U M
B E
R
O W
N E
R P
R O
J E
T
L E
D A
T E
E a s t
K a l a m a z o o
A v e n u e
S u i
K a l a m a z o o
M i c h i g
P
H O
.3
.6
F
A X
T O
W E
R P
I N
K S
T E
R C
O M
A L
L
R
I G
H T
S
R
E S
E R
V E
D
E a s t
F u l t o n
S t r e e t
S u i
G r a n d
R a p i d s
M i c h i g a n
4 P
H O
N E
.4
.5
F
A X
A. 6" CONCRETE PAVEMENT (SEE DETAIL THIS SHEET)
B. CONNECT ELECTRIC SERVICE AND METER,
COORDINATE WITH UTILITY PROVIDER
C. 10' OVERHEAD DOOR
D. MAN DOOR
SITE PLAN NOTES
S I T
E
P
L A
N
B
M A
Y
P O
R T
A
R
T H
E R
N
S T
O R
A G
E
B
A R
N
P o r t a g e
M i c h i g a n
P O
R T
A G
E
P
U B
L I C
S C
H O
O L
S
ISSUED FOR DATE
LIMITS OF CONSTRUCTION
LEGEND
SAWCUT
SILT FENCE
M.E. MATCH EXISTING GRADE
REMOVE BLDG.,
ADJACENT STOOP,
AND HANDRAILS.
REMOVE CONC.
SIDEWALK
REMOVE TREE
REMOVE DRAINAGE
STRUCTURE, AND STM.
PIPING.
DEMOLITION PLAN
SCALE:1"=20'
SITE PLAN
SCALE:1" = 10'
E X
. 8 " W
.M
E X
. 8 " W
.M
20' WATERMAIN EASEMENT
19'
21'
5'
N 1 inch = ft.
10 2015
N
3P
29T29T
3P
PROPOSED POLE
BARN B
1,869 SFT
SLAB ON GRADE
F.F. - 889.67
4.2'
UTILITY REMOVAL
REMOVE/RELOCATE
WATER LINE
A
A
B
C
C
D
29T
1. DIMENSIONS TAKE PRECEDENCE OVER SCALE. CONTRACTOR
TO VERIFY ALL DIMENSIONS IN FIELD.
2. IF ANY ERRORS, DISCREPANCIES, OR OMISSIONS BECOME
APPARENT, THESE SHALL BE BROUGHT TO THE ATTENTION
OF THE ARCHITECT/ ENGINEER PRIOR TO CONSTRUCTION OF
ANYTHING AFFECTED SO THAT CLARIFICATION OR REDESIGN
MAY OCCUR.
GENERAL NOTES
DENOTES PERMANENT SEEDING. ALL DISTURBED AREAS NOT PAVED OR GRAVELED SHALL
BE RESTORED. PLACE TOPSOIL SURFACE, SALV, 3 INCH, MDOT SEEDING, MIXTURE TUF
APPLIED AT A RATE OF 220 LB/ACRE, FERTILIZER, CHEMICAL NUTRIENT, CL A APPLIED AT A
RATE OF 228 LB/ACRE; MULCH AT A RATE OF 2 TON/ACRE AND MULCH ANCHORING.
(APPLIES TO ENTIRE PROJECT)
DENOTES TEMPORARY SILT FENCE. SILT FENCE SHALL BE INSTALLED AT CREEK
CROSSINGS, ADJACENT TO ALL WETLANDS AND SURFACE WATERS, AND OTHER
LOCATIONS AS DIRECTED BY THE ENGINEER. EACH SILT FENCE SHALL BE INSTALLED
GENERALLY ALONG THE SAME CONTOUR ELEVATION.
SOIL EROSION & SEDIMENTATION CONTROL NOTES
1 ALL CONSTRUCTION METHODS SHALL BE DONE IN COMPLIANCE WITH MDOT-EGLE. THE
OWNER SHALL BE RESPONSIBLE FOR OBTAINING A "SOIL EROSION PERMIT" FROM THE
COUNTY AND A "PERMIT BY RULE/NOTICE OF COVERAGE" FROM EGLE, IF APPLICABLE, PRIOR
TO START OF CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING
WITH ALL REQUIREMENTS OF THE COUNTY "SOIL EROSION PERMIT" AND FOR ALL CERTIFIED
STORM WATER INSPECTION SERVICE REQUIRED BY THE "PERMIT BY RULE." EROSION
CONTROL MEASURES SHOWN ON THE PLANS ARE THE MINIMUM REQUIREMENTS AND SHALL
NOT RELIEVE THE CONTRACTOR'S RESPONSIBILITY FOR PROVIDING ALL REQUIRED EROSION
CONTROL MEASURES.
2. AVOID UNNECESSARY DISTURBING OR REMOVING OF EXISTING VEGETATED TOPSOIL OR
EARTH COVER, THESE COVER AREAS ACT AS SEDIMENT FILTERS.
3. ALL TEMPORARY SOIL EROSION PROTECTION SHALL REMAIN IN PLACE UNTIL REMOVAL IS
REQUIRED FOR FINAL CLEAN UP AND APPROVAL.
4. GEOTEXTILE SILT FENCE SHALL BE INSTALLED AS REQUIRED WHEN CROSSING CREEKS OR
WHEN ADJACENT TO WETLANDS OR SURFACE WATER BODIES TO PREVENT SILTATION AND
ELSEWHERE AS DIRECTED BY THE ENGINEER. SEEDING AND/OR SODDING SHALL BE
INSTALLED ON CREEK BANKS IMMEDIATELY AFTER CONSTRUCTION TO PREVENT EROSION.
5. MAINTENANCE, CLEANING, AND REMOVAL OF THE VARIOUS SEDIMENT CONTROL MEASURES
SHALL BE INCLUDED IN THE VARIOUS EROSION CONTROL ITEMS.
NUMBER IN CIRCLE REFERS TO NUMBERED DETAILS ON MDOT STANDARD PLAN R-96-D, SOIL
EROSION & SEDIMENTATION CONTROL MEASURES. "P" DENOTES PERMANENT MEASURE AND
"T" DENOTES TEMPORARY MEASURE. SOIL EROSION CONTROL PLANS DENOTE MINIMUM
EROSION MEASURES REQUIRED AS DESCRIBED BELOW.
3P
26T
DENOTES INLET PROTECTION FABRIC DROP. SHALL BE INSTALLED AT EXISTING AND
PROPOSED STORM SEWER INLETS TO PROVIDE SETTLING AND FILTERING OF SILT LADEN
WATER PRIOR TO ENTRY INTO THE DRAINAGE SYSTEM.
29T
A
NOTE:
MANHOLE SHALL BE
CONSTRUCTED IN
ACCORDANCE WITH ASTM
SPECIFICATION C-478
PRECAST REINFORCED
CONCRETE BARREL
SECTIONS
PRECAST REINFORCED
CONCRETE CONE SECTION
(FLAT TOP TO BE USED FOR
LIMITED DEPTH APPLICATIONS)
SEE PLAN FOR COVER
PRECAST CONCRETE
ADJUSTING RINGS
(2 MAX, 8" MAX)
V A
R
IE
S
S E
E P
LA
N
SEE PLAN 5"5"
2' S
U M
P
CATCH BASIN DETAIL
NOT TO SCALE
D
ALL UTILITIES AS SHOWN ARE APPROXIMATE LOCATIONS DERIVED
FROM ACTUAL MEASUREMENTS AND AVAILABLE RECORDS. THEY
SHOULD NOT BE INTERPRETED TO BE EXACT LOCATION NOR
SHOULD IT BE ASSUMED THAT THEY ARE THE ONLY UTILITIES IN THE
AREA. FIELD WORK PERFORMED BY: H & S ENGINEERING
1. ALL WORK SHALL CONFORM TO ALL LOCAL, STATE AND FEDERAL LAWS, RULES AND REGULATIONS
IN FORCE AT TIME OF CONSTRUCTION.
2. ALL WORK SHALL CONFORM TO THE MICHIGAN HANDICAPPED ACCESSIBILITY CODE AND THE
AMERICANS WITH DISABILITIES ACT.
3. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PERMIT
COSTS, TAP FEES, METER DEPOSITS, PERMANENT UTILITY APPLICATIONS, BONDS, AND OTHER
FEES REQUIRED FOR PROPOSED WORK.
4. CONTACT "MISS DIG" AT 1-800-482-7171 FOR LOCATION OF UNDERGROUND UTILITIES A MINIMUM
OF 48 HOURS BEFORE COMMENCING EXCAVATION WORK. THIS DOES NOT RELIEVE THE
CONTRACTOR OF THE RESPONSIBILITY OF NOTIFYING UTILITY OWNERS WHO ARE NOT PART OF
THE "MISS DIG" ALERT SYSTEM. THE CONTRACTOR SHALL CONDUCT HIS OPERATIONS IN A
MANNER AS TO ENSURE THAT THOSE UTILITIES NOT REQUIRING RELOCATION WILL NOT BE
DISTURBED.
5. MANHOLE AND CATCH BASIN STRUCTURES SHALL BE PRECAST AND HAVE A MAXIMUM OF 2
ADJUSTING RINGS FOR FINISH GRADE ADJUSTMENT.
6. DEMOLISH & REMOVE ALL EXISTING SITE FEATURES AS REQUIRED.
1. SOILS EXPOSED IN THE BASE OF ALL SATISFACTORY FOUNDATION EXCAVATIONS SHOULD BE
PROTECTED AGAINST ANY DETRIMENTAL CHANGES IN CONDITION SUCH AS FROM DISTURBANCE,
RAIN AND FREEZING. SURFACE RUN-OFF WATER SHOULD BE DRAINED AWAY FROM THE
EXCAVATION AND NOT ALLOWED TO POND. IF POSSIBLE, ALL FOOTING CONCRETE SHOULD BE
POURED THE SAME DAY THE EXCAVATION IS MADE. IF THIS IS NOT PRACTICAL, THE FOOTING
EXCAVATIONS SHOULD BE ADEQUATELY PROTECTED.
2. REMOVE ALL SUBGRADE GRADE MATERIAL THAT MAY BE SOFTENED BY RAINS, FREEZING, OR
CONSTRUCTION TRAFFIC, ETC. AND REPLACE WITH COMPACTED GRANULAR FILL.
3. THE CONTRACTOR SHALL INSTALL A PEDESTRIAN FENCE AROUND ALL EXCAVATIONS TO BE LEFT
OPEN OVERNIGHT AS REQUIRED.
4. EXTERIOR CONCRETE SHALL HAVE A COMPRESSIVE STRENGTH OF 4000 PSI AND SHALL HAVE
LIMESTONE AGGREGATE AND SHALL HAVE 4 - 6 % AIR ENTRAINMENT WITH A BROOM FINISH.
5. EXPANSION JOINTS IN CONCRETE PAVEMENT AND WALLS SHALL BE 1/2" ASPHALT IMPREGNATED FULL DEPTH 40' O.C. MAXIMUM & AT SIDEWALK INTERSECTIONS. CRACK CONTROL SCORING AT
SIDEWALK WIDTH DIMENSION AND @ 10'-0" O.C. IN DRIVES.
SITE MATERIALS & CONSTRUCTION NOTES:
GENERAL CONSTRUCTION NOTES
1. ALL WORK SHALL CONFORM TO ALL LOCAL, STATE AND FEDERAL LAWS, RULES AND REGULATIONS IN
FORCE AT TIME OF CONSTRUCTION.
2. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PERMIT COSTS, TAP FEES, METER DEPOSITS, PERMANENT UTILITY APPLICATIONS, BONDS, AND OTHER FEES
REQUIRED FOR PROPOSED WORK. THIS SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO THOSE
REQUIRED BY THE CITY OF PORTAGE
3. CONTACT "811" AT 1-800-482-7171 FOR LOCATION OF UNDERGROUND UTILITIES A MINIMUM OF 48
HOURS BEFORE COMMENCING EXCAVATION WORK. THIS DOES NOT RELIEVE THE CONTRACTOR OF
THE RESPONSIBILITY OF NOTIFYING UTILITY OWNERS WHO ARE NOT PART OF THE "811" ALERT SYSTEM. THE CONTRACTOR SHALL CONDUCT HIS OPERATIONS IN A MANNER AS TO ENSURE THAT
THOSE UTILITIES NOT REQUIRING RELOCATION WILL NOT BE DISTURBED.
4. DEMOLISH & REMOVE ALL EXISTING SITE FEATURES AS REQUIRED.
5. MATCH EXISTING GRADES AROUND PERIMETER WITH SLOPES AS SHOWN.
6. ALL SPOT ELEVATIONS ARE TOP OF PAVEMENT GRADES AT EDGE OF METAL (EOM) UNLESS
OTHERWISE NOTED.
7. ALL SOIL EROSION CONTROL MEASURES SHALL BE IN PLACE PRIOR TO MASS GRADING.
8. ALL EXCAVATION SHALL BE IN ACCORDANCE WITH THE TECHNICAL SPECIFICATIONS AND
GEOTECHNICAL REPORT.
9. ALL EXISTING ELEVATIONS ARE TO BE VERIFIED AND ACCEPTED AS SHOWN PRIOR TO
COMMENCEMENT OF WORK.
10. CONTRACTOR SHALL TAKE PRECAUTIONS TO AVOID TRACKING SOIL ONTO ADJACENT ROADWAYS.
CONTRACTOR SHALL SWEEP IMMEDIATELY IF OCCURS.
11. ANY DISTURBED AREA WHICH WILL BE LEFT UNWORKED 15 DAYS OR LONGER MUST BE SEEDED TO
ESTABLISH VEGETATION FOR TEMPORARY STABILIZATION. BASINS TO BE SEEDED AND MULCH
BLANKETS APPLIED IMMEDIATELY TO PROVIDE A STABLE BASE AND AVOID EXCESSIVE EROSION.
GRADING NOTES
GROUND SURFACE EJIW 1410
3' M
A X
THREADED PLUG CAP
UNLESS OTHERWISE
SPECIFIED
SIZE OF PIPE AS
SHOWN ON PLANS GRAVEL FILL (WITHIN OPENING
AROUND PIPE END SECTION)
CONCRETE REINFORCED
FOOTING
GRADE 35S OR PRECAST
REINFORCED SECTION
UNLESS OTHERWISE
SPECIFIED
CONCRETE ADJUSTING
RING GRADE35S, CONC.
REINF. BATTER BLOCKS
AND MORTAR, OR
REINF. PRECAST
MANHOLE SECTION.
(2) 45° (1
8 BEND)
PIPE SECTION
6" MINIMUM COMPACTED (98%)
SAND SUB-BASE (MDOT CLASS II)
OR AS RECOMMENDED BY
GEOTECHNICAL
ENGINEER
6" (4" CONCRETE WHEN
REPLACING SIDEWALK)-4,000 P.S.I.
NON-REINFORCED
CONCRETE TOPSOIL
ACCEPTABLE COMPACTED SUB-BASE (AS
RECOMMENDED BY GEOTECHNICAL ENGINEER)
1.0' MIN.
CLEANOUT DETAIL
NOT TO SCALE
CONC. PAVEMENT SECTION
NOT TO SCALE
S
T
A
F M
I C
H
I
G
A
N
L
S
D
P
O
F
E S S I
O
L
R
RELOCATE WATER
SERVICE HERE3'
A C
O S
0K
T R
E N
C H
D R
A
IN
WHY CONNECTION
TO 24" STORM PIPE
WHY CONNECTION
TO 24" STORM PIPE
Civil Engineers & Surveying
MICHIGAN | INDIANA | ILLINOIS | OHIO
AR Engineering www.arengineeringllc.com
269.250.5991 PHONE | 866.569.0604 FAX
ADJUST ELECTRIC LINES
AS NECESSARY FOR
UTILITY INSTALLATION
-2
.0
G
AA 301
AA 301
B
AA 301
C
AA 301
D
AA 301
A B C D E
AA 301
32' - 0"
8' - 0" 8' - 0" 8' - 0" 8' - 0"
24" x 10" FOOTING AT
END WALL COLUMNS
(TYP.) - U.N.O.
36" x 12"
FOOTING AT
OVERHEAD DOOR
(TYP.) - U.N.O.
24" x 10"
FOOTING AT END
WALL COLUMNS
(TYP.) - U.N.O.
24" X 10"
FOOTING
(TYP.) - U.N.O.
14"Ø CONCRETE
PIERS WITH (6)
VERTICAL #5 BARS
AND 4# STIRRUPS
AT 12" O.C.
36" x 12" FOOTING
AT OVERHEAD DOOR
(TYP.) - U.N.O.
36" x 12" FOOTING
AT OVERHEAD DOOR
(TYP.) - U.N.O.
24" X 10"
FOOTING
(TYP.) - U.N.O.
/4
/4
/2
/2
/4
/4
AA 301
A
AA 301
B
AA 301
C
AA 301
D
AA 301
A B C D E
AA 301
(2) 1 3/4" x 9 1/2" LVL
CARRIERS ON EACH SIDE
OF POSTS AT OVERHEAD
DOORS (TYP.)
(2) 2x10
CONTINUOUS
CARRIERS ON
EACH SIDE OF
POSTS (TYP.)
(2) 2x10
CONTINUOUS
CARRIERS ON
EACH SIDE OF
POSTS (TYP.)
(2) 1 3/4" x 9 1/2" LVL
CARRIERS ON EACH SIDE
OF POSTS AT OVERHEAD
DOORS (TYP.)
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
X
F O
U N
D A
T
IO
N A
N D
F R
A M
IN
G
P L A
N
-2
.0
A A
M A
Y
P O
R T
A G
E
N O
R T
H E
R N
H
IG
H S
C H
O O
L
S T
O R
A G
E B
A R
N S
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
1/8" = 1'-0"
FOUNDATION PLAN
1/8" = 1'-0"
FRAMING PLAN
GENERAL NOTES
1. REFER TO CODE COMPLIANCE PLAN FOR WALL RATING LINES.
2. REFER TO FLOOR FINISH PLANS FOR INTERIOR ELEVATION CALLOUTS.
3. REFER TO SHEET A 501 FOR WALL AND CEILING ACCESS PANEL INFORMATION.
OHSF
SEE SCHED.
S E E S
C H E D U
LE
SEE SCHEDULE
S E E S
C H E D U
LE
2" TYP. SEE SCHED. 2" TYP.
S E E S
C H E D U
LE
T Y P
AA 301
A
AA 301
B
AA 301
C
AA 301
D
AA 301
A B C D E
101A
8' - 0" 8' - 0" 8' - 0" 8' - 0"
AA 301
6x6 TREATED
POST - (TYP.)
U.N.O.
6x6 TREATED
POST - (TYP.)
U.N.O.
6x6 TREATED
POST - (TYP.)
U.N.O.
6x6 TREATED
POST - (TYP.)
U.N.O.
STORAGE
101C
101B
101D
/2
32' - 10 1/2"
/4
/4
/2
/4
/4
AA 301
A
AA 301
B
AA 301
C
AA 301
D
AA 301
A B C D E
AA 301
/1
P
IT
C H E
N G
IN
E E R E D
T R U S S E S
A T
O
.C
/2
LINE OF BUILDING BELOW LINE OF BUILDING BELOW
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
X
F
IR
S T
F L O
O R
P L A
N
R O
O F
F R
A M
IN
G
P L A
N A
N D
D O
O R
S C
H E
D U
L E
-2
.0
A A
M A
Y
P O
R T
A G
E
N O
R T
H E
R N
H
IG
H S
C H
O O
L
S T
O R
A G
E B
A R
N S
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
DOOR SCHEDULE - BUILDING A
NUMBER
ROOM
NAME
FIRE RATING DOOR SIZE FRAME DETAILS
GLASS
ACCESS CONTROLS
HDWR.
SET
REMARKS
DOOR ROOM DOOR FRAME TYPE MAT FIN WIDTH HEIGHT ELEV MAT FIN HEAD JAMB SILL
A-PHO
NE
BARRIER-
FREE
CARD
READER
ELEC. LOCK
HDWR.
MAG
HOLD
101A 101 STORAGE - - F STL FACTORY FINISH 3' - 0" 7' - 2" 1 HM PAINT - - - - No No No No No 1.0 -
101B 101 STORAGE - - OHS STL FACTORY FINISH 12' - 0" 10' - 0" - STL - 5 / AA 301 - - - No No No No No 2.0 -
101C 101 STORAGE - - OHS STL FACTORY FINISH 12' - 0" 10' - 0" - STL - 5 / AA 301 - - - No No No No No 2.0 -
101D 101 STORAGE - - F STL FACTORY FINISH 3' - 0" 7' - 2" 1 HM PAINT - - - - No No No No No - -
1/4" = 1'-0"
DOOR TYPES
1/4" = 1'-0"
FRAME ELEVATION
1/8" = 1'-0"
FIRST FLOOR PLAN
1/8" = 1'-0"
ROOF FRAMING PLAN
FIRST FLOOR
100' - 0"
ABCDE
TRUSS BEARING - BLDG A
112' - 0"
AA 301
FOOTING
96' - 6"
4" 12"
4"
12"
STEEL SIDING 1 -
FABRAL GRANDRIB 3
OR EQUAL
STEEL SIDING
OUTSIDE CORNER
GUTTER
STEEL SIDING 2 -
FABRAL GRANDRIB
3 OR EQUAL
FIRST FLOOR
100' - 0"
AA 301
1 2 3 4 5 6 7 8 9
TRUSS BEARING - BLDG A
112' - 0"
FOOTING
96' - 6"
STEEL SIDING 2 -
FABRAL GRANDRIB
3 OR EQUAL
ASPHALT SHINGLES
STEEL SIDNG
OUTSIDE CORNER
GUTTER
STEEL DOWNSPOUT
RIDGE VENT
STEEL SIDING 1 -
FABRAL GRANDRIB
3 OR EQUAL
FIRST FLOOR
100' - 0"
A B C D E
TRUSS BEARING - BLDG A
112' - 0"
AA 301
FOOTING
96' - 6"
4"
12" 4"
12"
STEEL SIDING 2 -
FABRAL GRANDRIB
3 OR EQUAL
STEEL SIDING
OUTSIDE CORNER
STEEL SIDING 1 -
FABRAL GRANDRIB
3 OR EQUAL
FIRST FLOOR
100' - 0"
AA 301
123456789
TRUSS BEARING - BLDG A
112' - 0"
FOOTING
96' - 6"
STEEL SIDING 2 -
FABRAL GRANDRIB
3 OR EQUAL
ASPHALT SHINGLES
STEEL SIDING
OUTSIDE CORNER
STEEL DOWNSPOUT
GUTTER
RIDGE VENT
STEEL SIDING 1 -
FABRAL GRANDRIB
3 OR EQUAL
FIRST FLOOR
100' - 0"
A B C D E
TRUSS BEARING - BLDG A
112' - 0"
AA 301
FOOTING
96' - 6"
4"
12" 4"
12"
AA 301
AA 301
FIRST FLOOR
100' - 0"
AA 301
1 2 3 4 5 6 7 8 9
TRUSS BEARING - BLDG A
112' - 0"
FOOTING
96' - 6"
ASPHALT SHINGLES, COLOR:
EXTERIOR ELEVATION KEY
STEEL SIDING 1, COLOR:
STEEL SIDING 2, COLOR:
FIRST FLOOR
100' - 0"
A
TRUSS BEARING - BLDG A
112' - 0"
ENGINEERED WOOD
TRUSSES AT 2' O.C.
METAL GUTTERS
METAL FASCIA
2X6 SUB FASCIA
VENTED SOFFIT PANELS
2X4 GIRTS AT 24" O.C.
STEEL SIDING 1 -
FABRAL GRANDRIB
6X6 TREATED POST
(2) ROWS OF TREATED
2X6 T&G SKIRT BOARDS
6" CONCRETE SLAB WITH
TURNED DOWN EDGE
4" COMPACT SAND
'F' CHANNEL
(2) 2x10 CONTINUOUS
CARRIERS ON EACH
SIDE OF POSTS
3/4" SHEATHING
ASPHALT SHINGLES ON
ICE AND WATER SHIELD
HEMMED TRIM BETWEEN
STEEL SIDING 1 AND 2
STEEL SIDING 2 -
FABRAL GRANDRIB
A
TRUSS BEARING - BLDG A
112' - 0"
STEEL GUTTERS
2X6 SUB FASCIA
METAL FASCIA
VENTED SOFFIT PANELS
(2) 1 3/4" X 9 1/2"
LVL - BOTH SIDES
STEEL SIDING -
FABRAL GRANDRIB
F CHANNEL
J CHANNEL
2X6 NAILERS
STEEL TRIM BY SIDING MANUF.
ENGINEERED WOOD
TRUSSES AT 24" O.C.
6X6 TREATED POST
OVERHEAD DOOR
3/4" SHEATHING
ASPHALT SHINGLES ON
ICE AND WATER SHIELD
TRUSS NOTE FOR BUILDING B:
SISSOR TRUSSES IN LEIU OF
STANDARD TRUSSES
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
X
E X
T E
R
IO
R E
L E
V A
T
IO
N S
B
U
IL
D
IN
G S
E C
T
IO
N S
D V
IE
W
A N
D W
A L
L S
E C
T
IO
N S
-2
.0
A A
M A
Y
P O
R T
A G
E
N O
R T
H E
R N
H
IG
H S
C H
O O
L
S T
O R
A G
E B
A R
N S
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
1/8" = 1'-0"AA 301
A NORTH ELEVATION
1/8" = 1'-0"AA 301
B WEST ELEVATION
1/8" = 1'-0"AA 301
C SOUTH ELEVATION
1/8" = 1'-0"AA 301
D EAST ELEVATION
1/8" = 1'-0"AA 301
1 BUILDING SECTION
1/8" = 1'-0"AA 301
2 BUILDING SECTION
1/2" = 1'-0"AA 301
4 WALL SECTION
1 1/2" = 1'-0"AA 301
5 WALL DETAIL
3D VIEW
F G H IAB 301
A
AB 301
B
AB 301
D
AB 301
C
6' - 8" 6' - 8" 6' - 8"
20' - 0"
24" x 10"
FOOTING AT
END WALL
COLUMNS
(TYP.) - U.N.O.
36" x 12"
FOOTING AT
OVERHEAD DOOR
(TYP.) - U.N.O.
24" x 10"
FOOTING AT END
WALL COLUMNS
(TYP.) - U.N.O.
24" X 10"
FOOTING
(TYP.) - U.N.O.
14"Ø CONCRETE
PIERS WITH (6)
VERTICAL #5 BARS
AND 4# STIRRUPS
AT 12" O.C.
AB 301
AB 301
36" x 12"
FOOTING AT
OVERHEAD DOOR
(TYP.) - U.N.O.
/4
/4
/2
/2
/4
/4
F G H IAB 301
A
AB 301
B
AB 301
D
AB 301
C
(2) 1 3/4" x 9 1/2" LVL
CARRIERS ON EACH SIDE
OF POSTS AT OVERHEAD
DOORS (TYP.)
(2) 2x10
CONTINUOUS
CARRIERS ON
EACH SIDE OF
POSTS (TYP.)
(2) 2x10
CONTINUOUS
CARRIERS ON
EACH SIDE OF
POSTS (TYP.)
AB 301
AB 301
(2) 1 3/4" x 9 1/2" LVL
CARRIERS ON EACH SIDE
OF POSTS AT OVERHEAD
DOORS (TYP.)
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
X
F O
U N
D A
T
IO
N A
N D
F R
A M
IN
G
P L A
N
-2
.0
A B
M A
Y
P O
R T
A G
E
N O
R T
H E
R N
H
IG
H S
C H
O O
L
S T
O R
A G
E B
A R
N S
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
1/8" = 1'-0"
FOUNDATION PLAN
1/8" = 1'-0"
FRAMING PLAN
F G H I
6' - 8" 6' - 8" 6' - 8"
20' - 10 1/2"
6x6 TREATED
POST - (TYP.)
U.N.O.
6x6 TREATED
POST - (TYP.)
U.N.O.
6x6 TREATED
POST - (TYP.)
U.N.O.
STORAGE
AB 301
A
AB 301
B
AB 301
D
AB 301
C
AB 301
AB 301
102A
102C
102B
/2
/4
/4
/2
/2
/4
/4
F G H IAB 301
A
AB 301
B
AB 301
D
AB 301
C
AB 301
AB 301
/1
P
IT
C H E
N G
IN
E E R E D
T R U S S E S
A T
O
.C
LINE OF BUILDING BELOW
OHSF
SEE SCHED.
S E E S
C H E D U
LE
SEE SCHEDULE
S E E S
C H E D U
LE
2" TYP. SEE SCHED. 2" TYP.
S E E S
C H E D U
LE
T Y P
GENERAL NOTES
1. REFER TO CODE COMPLIANCE PLAN FOR WALL RATING LINES.
2. REFER TO FLOOR FINISH PLANS FOR INTERIOR ELEVATION CALLOUTS.
3. REFER TO SHEET A 501 FOR WALL AND CEILING ACCESS PANEL INFORMATION.
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
X
F
IR
S T
F L O
O R
P L A
N
R O
O F
F R
A M
IN
G
P L A
N A
N D
D O
O R
S C
H E
D U
L E
-2
.0
A B
M A
Y
P O
R T
A G
E
N O
R T
H E
R N
H
IG
H S
C H
O O
L
S T
O R
A G
E B
A R
N S
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
1/8" = 1'-0"
FIRST FLOOR PLAN
1/8" = 1'-0"
ROOF FRAMING PLAN
DOOR SCHEDULE - BUILDING B
NUMBER
ROOM
NAME
FIRE RATING DOOR SIZE FRAME DETAILS
GLASS
ACCESS CONTROLS
HDWR.
SET
REMARKS
DOOR ROOM DOOR FRAME TYPE MAT FIN WIDTH HEIGHT ELEV MAT FIN HEAD JAMB SILL
A-PHO
NE
BARRIER-
FREE
CARD
READER
ELEC. LOCK
HDWR.
MAG
HOLD
101E 102 STORAGE - - F STL FACTORY FINISH 3' - 0" 7' - 2" 1 HM PAINT - - - - No No No No No - -
102A 102 STORAGE - - F STL FACTORY FINISH 3' - 0" 7' - 2" 1 HM PAINT - - - - No No No No No 1.0 -
102B 102 STORAGE - - OHS STL FACTORY FINISH 12' - 0" 12' - 0" - STL - 5 / AB 301 - - - No No No No No 2.0 -
102C 102 STORAGE - - OHS STL FACTORY FINISH 12' - 0" 12' - 0" - STL - 5 / AB 301 - - - No No No No No 2.0 -
1/4" = 1'-0"
DOOR TYPES
1/4" = 1'-0"
FRAME ELEVATION
FIRST FLOOR
100' - 0"
FOOTING
96' - 6"
FGHI
AB 301
TRUSS BEARING - BLDG B
116' - 0"
6"
12"
6"
12"
STEEL SIDING 1 -
FABRAL GRANDRIB 3
OR EQUAL
STEEL SIDING
OUTSIDE CORNER
GUTTER
STEEL SIDING 2 -
FABRAL GRANDRIB
3 OR EQUAL
FIRST FLOOR
100' - 0"
1 2 3 4 5 6 7 8 9
FOOTING
96' - 6"
AB 30110
TRUSS BEARING - BLDG B
116' - 0"
11 12
STEEL SIDING 2 -
FABRAL GRANDRIB
3 OR EQUAL
ASPHALT SHINGLES
STEEL SIDNG
OUTSIDE CORNER
GUTTER
STEEL DOWNSPOUT
RIDGE VENT
STEEL SIDING 1 -
FABRAL GRANDRIB
3 OR EQUAL
FIRST FLOOR
100' - 0"
FOOTING
96' - 6"
F G H I
AB 301
TRUSS BEARING - BLDG B
116' - 0"
STEEL SIDING 1 -
FABRAL GRANDRIB 3
OR EQUAL
STEEL SIDING
OUTSIDE CORNER
GUTTER
STEEL SIDING 2 -
FABRAL GRANDRIB
3 OR EQUAL
6"
12"
6"
12"
FIRST FLOOR
100' - 0"
123456789
FOOTING
96' - 6"
AB 301
TRUSS BEARING - BLDG B
116' - 0"
STEEL SIDING 2 -
FABRAL GRANDRIB
3 OR EQUAL
ASPHALT SHINGLES
STEEL SIDNG
OUTSIDE CORNER
GUTTER
STEEL DOWNSPOUT
RIDGE VENT
STEEL SIDING 1 -
FABRAL GRANDRIB
3 OR EQUAL
ASPHALT SHINGLES, COLOR:
EXTERIOR ELEVATION KEY
STEEL SIDING 1, COLOR:
STEEL SIDING 2, COLOR:
FIRST FLOOR
100' - 0"
FOOTING
96' - 6"
F G H I
AB 301
TRUSS BEARING - BLDG B
116' - 0"
6"
12"
6"
12"
AA 301
OPP. HAND
AA 301
OPP. HAND
FIRST FLOOR
100' - 0"
1 2 3 4 5 6 7 8 9
FOOTING
96' - 6"
AB 301
TRUSS BEARING - BLDG B
116' - 0"
11 12
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
X
E X
T E
R
IO
R E
L E
V A
T
IO
N S
B
U
IL
D
IN
G S
E C
T
IO
N S
A
N D
D
V
IE
W
-2
.0
A B
M A
Y
P O
R T
A G
E
N O
R T
H E
R N
H
IG
H S
C H
O O
L
S T
O R
A G
E B
A R
N S
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
1/8" = 1'-0"AB 301
A NORTH ELEVATION
1/8" = 1'-0"AB 301
B WEST ELEVATION
1/8" = 1'-0"AB 301
C SOUTH ELEVATION
1/8" = 1'-0"AB 301
D EAST ELEVATION
3D VIEW
1/8" = 1'-0"AB 301
1 BUILDING SECTION
1/8" = 1'-0"AB 301
2 BUILDING SECTION
ELECTRIC VAULT
RIM = 888.55
AHU
BM
STM
STM
HH
A B C D E
STORAGE
A A A
A A A
A A A
A AA
RPA
RPA-1, 40", GFCI
RPA-1, 40"
RPA-1
, WP, 24"
RPA-3, 40"
RPA-5
, OVERHEAD DOOR, 120"
RPA-3, 40"
RPA-3, 40", GFCI
RPA-4
, OVERHEAD DOOR, 120"
RPA-2, 40", GFCI
RPA-2, 40"
RPA-2, 40"
B
RPA-6
B
RPA-6
RPA-3
, WP, 24"
STORAGE B
BUILDING
STORAGE A
BUILDING
MDP IN EXIST.
BUILDING
REMOVE POWER CONNECTION TO
EXISTING BUILDING. RETAIN EXISTING
100 AMP FEEDER TO FEED NEW PANEL
RPB. INTERCEPT FEED IN-GRADE AND RE-
ROUTE TO NEW PANEL. EXTEND EXISTING
FEEDER AS REQUIRED.
NEW FEEDER TO PANEL
RPA FROM PANEL RPB
NEW FEEDER TO PANEL
RPA FROM PANEL RPB
EXISTING HAND HOLE
EXISTING CONDUIT
UNDER PAVING
INTERCEPT EXISTING CONDUIT RUNNING UNDER
PAVING. PROVIDE NEW 18"X24" HAND HOLE
AND PROVIDE FEEDER TO PANEL RPA FROM
PANEL RPA. REFER TO ONE-LINE DIAGRAM
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z o o
M ic h ig
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s
M ic h ig a n
.4
.9
P H
O
.4
.5
F A
X
S T
O R
A G
E B
A R
N A
E L E
C T
R
IC
A L
P L A
N
-2
.0
E A
M A
Y
P O
R T
A G
E
N O
R T
H E
R N
H
IG
H S
C H
O O
L
S T
O R
A G
E B
A R
N S
P o rt a g e
M ic h ig a n
P O
R T
A G
E P
U B
L
IC
S C
H O
O L
S
1/8" = 1'-0"
STORAGE BARN A ELECTRICAL PLAN
1" = 20'-0"
ELECTRICAL SITE PLAN
GENERAL ELECTRICAL NOTES
ELECTRICAL KEYED NOTES
1 ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING
AND PATCHING REQUIRED FOR NEW WORK OR WHERE DEVICES ARE
REMOVED AND NOT REPLACED.
2 PATCH ALL PENETRATIONS AS REQUIRED TO MAINTAIN FIRE RATING.
3 ALL CONDUITS SHALL ENTER/EXIT THE BUILDING BELOW GRADE.
PROVIDE TRENCHING AND DIRECTIONAL BORING AS REQUIRED. CUT
AND PATCH AS REQUIRED. NO EXPOSED CONDUIT SHALL BE ALLOWED
ON EXTERIOR OF BUILDING.
4 ALL CONDUITS SHALL RUN AS NEAR TO DECK AS PERMITTED BY CODE.
SOME CONDUITS WILL BE EXPOSED AND SHALL BE RUN IN A NEAT
MANNER. MAINTAIN THE SAME SPACING WHEN CONDUITS ARE RUN
TOGETHER. CONCEAL JUNCTION BOXES OVER LAY-IN CEILING AND
USE EMT DROPS DOWN TO CLOUDS. LOCATE CONDUIT DROPS TO
CLOUDS AND CEILING ELEMENTS IN LEAST VISIBLE LOCATION.
1 CONNECT RECEPTACLE TO LOAD SIDE OF UPSTREAM GFCI
RECEPTACLE.
2 COORDINATE FINAL POWER CONNECTION WITH OVERHEAD DOOR
PROVIDER. MOUNT AND WIRE DOOR SWITCH AND ELECTRIC EYE(S) AT
BOTTOM OF DOOR.
NOTES:
TOTAL ESTIMATED DEMAND... 11 A
TOTAL CONNECTED LOAD (A): 11 A
TOTAL ESTIMATED DEMAND: 3950 VA
RECEPTACLE - 3300 VA 100.00% 3300 VA TOTAL CONNECTED LOAD: 3950 VA
LIGHTING - 650 VA 100.00% 650 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 9 A 13 A 12 A
ADDITIONAL FEED THRU LUGS LOAD (IF APPLICABLE): 0 VA 0 VA 0 A
TOTAL LOAD: 1080 VA 1470 VA 1400 VA
17 18
15 16
13 14
11 SPARE 20 1 0 0 1 20 SPARE 12
9 SPARE 20 1 0 0 1 20 SPARE 10
7 SPARE 20 1 0 0 1 20 SPARE 8
5 RECEPTACLE - STORAGE 101 20 1 750 650 1 20 LIGHTING - Room 101 6
3 RECEPTACLE - STORAGE 101 20 1 720 750 1 20 RECEPTACLE - STORAGE 101 4
1 RECEPTACLE - STORAGE 101 20 1 540 540 1 20 RECEPTACLE - STORAGE 101 2
CIRCUIT DESCRIPTION
TRIP
(A) POLES A B C POLES
TRIP
(A) CIRCUIT DESCRIPTION
ADDED ACCESSORIES: FEED-THRU LUGS... No I.C. RATING: 10 KAIC
LOCATION: STORAGE 101 / FIRST FLOOR AMPS: 60 A MB , ULSE RATED FED FROM: RPB
PANEL: RPA MOUNTING: SURFACE VOLTAGE: 208/120V, 3PH, 4W
PANELBOARD " RPA" LOAD SCHEDULE
F G H I
STORAGE
A A
A A
A A
A A
RPB
RPB-3, 40", GFCI
RPB-3, 40"
RPB-2, 40"
RPB-2, 40", GFCI
RPB-4
, OVERHEAD DOOR, 120"
RPB-1, 40", GFCI
RPB-1, 40"
RPB-5
, OVERHEAD DOOR, 120"
RPB-1, 40"
B
RPB6
B
RPB6
RPB-3
, WP, 24"
RPB-1
, WP, 24"
A A
RPB- 6
AA
2000/3
EXIST MDP
208/120V 3Ø, 4W
/3
RPB
PANEL
E X
IS
T C
H
IL
LE
R
E X
IS
T C
H
IL
LE
R
E X
IS
T M
C C
E X
IS
T A M
D P
E X
IS
T A H U
E X
IS
T R T U
E X
IS
T A H U
E X
IS
T S R
E X
IS
T
RPA
PANEL
60/3
4 #6, 1 #10G
1¼" PVC CONDUIT
MODIFY EXISTING FEEER. VERIFY AND
MATCH EXISTING WIRE SIZE. EXTEND
AS REQUIRED.
EXISTING PORTABLE BUILDING BREAKER IN
MDP. RELABEL STORAGE BUILDING PANEL RPB.
NEW SQAURE D NQOD
100 MAIN BREAKER
PANEL OR EQUAL. REFER
TO PANEL SCHEDULE.
NEW SQAURE D NQOD
60 MAIN BREAKER PANEL
OR EQUAL. REFER TO
PANEL SCHEDULE.
G R O
U N D
B U S
10' SPACING (TYP)
#3/0 Cu GND (TYP)
10'-0"
GROUND ROD
G R O
U N D
B U S
10' SPACING (TYP)
#3/0 Cu GND (TYP)
10'-0"
GROUND ROD
PROVIDE (3) 10'-0"
GROUND RODS SPACED 10'
APART AT EACH BUILDING
NOTES:
MOUNT DEVICES AT HEIGHTS INDICATED UNLESS INDICATED
OTHERWISE ON PLANS. HEIGHTS ARE TO BOTTOM OF DEVICE.
HH
SYMBOL DESCRIPTION MOUNTING HEIGHTS
RECEPTACLE SYMBOLS
POWER SYMBOLSLIGHTING SYMBOLS
SD
ELECTRICAL SYMBOLS
PANELBOARD
CIRCUIT BREAKER
72" TO TOP
DUPLEX RECEPTACLE - WITH GFI
DUPLEX RECEPTACLE - WET LOCATION ENCLOSURE WITH GFIWP
GFI
24"
16"
DUPLEX RECEPTACLE 16"
DIMMER SWITCH
WALL MTD. LIGHT FIXTURE
INDUSTRIAL LIGHT FIXTURE
FLUSH IN-GRADE HAND HOLE
PUSH-BUTTON STATION - 3 HOLE 40"
40"
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
E a s t
K a la m a z o o A v e n u e
S u it e
K a la m a z…