PREFABRICATED BUILDING REQUIREMENTS
INTENDED USE
The Wisconsin Air National Guard (WI ANG) requires a portable building at the Hardwood Bombing range to effectively, efficiently, and safely control military aircraft operating on the bombing range. The building will be placed on a pad and will have access to electrical power and communications fiber.
STRUCTURAL REQUIREMENTS
1. 36 ft. Long x 14 ft. Wide (504 sq. ft.)
2. Must be sided with steel siding on all sides & roof
a. Color: Alternating red & white (IAW AFMAN 13-212,4.17 Range Safety)
3. Roof must over hang 12 inches on all sides
a. Metal soffits
4. Building will be divided into two rooms
a. Main room is to be 24 ft. x 14 ft.
b. Secondary room is to be 12 ft. x 14 ft.
c. Interior dividing wall must be built with 2 x 6 inch boards & insulated for sound proofing
i. Wall must go from floor to ceiling
ii. Interior wall must have a solid core door dividing the two rooms
5. All exterior and interior walls will be insulated to the standard commercial code.
6. Exterior door must be steel and painted to match color pattern of exterior
a. Door must open into the room
7. Two exterior LED lights
8. Three interior ceiling fans with lights
a. Two located in main area of building
b. One located in smaller area of building
i. All fans must be large enough to adequately distribute air in room
9. Countertops located in control room
a. Formica countertops
i. Standard commercial height
10. Interior walls & ceiling are to be finished with wood tongue and groove car siding
11. Interior Floors are to be covered in prefinished tongue and groove wood
a. Floor must be insulated
12. 8 dual pane windows, minimum of 36 inches High x 30 inches wide
a. White adjustable minim vinyl mini blinds on all windows
13. Four (4) Skylights in roof
a. 22 ½ in. x 46 ½ in. Fixed self-flashed skylight with tempered Low-E3 Glass and Classica sand manual light filtering blind or equivalent.
14. One (1) Vinyl patio door in exterior of Control Room
a. Interior shades
b. Standard 72” X 80” in dimension
15. Building requires 200 amp breaker panel
a. Building will use standard lights and electrical outlets
16. Wall mounted Air Conditioning & Heating unit is required for each room
a. Separate PTAC type units
17. Building must be mounted on 4 x 4 x 6 skids
a. Treated or composite material
18. Must allow for antenna cables to be run inside from exterior
19. Building is to be electrically wired IAW commercial standards
COMMUNICATIONS FIBER/ HARDWARE REQUIREMENTS
1. CAT6 Cable runs from the cabinet to each Communication outlet
a. Communication cabinet will be located under countertop
b. Two (2) per outlet in Break Room
c. Four (4) per outlet in Control Room
d. Cables should terminate on a 24 port patch panel
e. Jacks
i. Panduit Mini-Com T6 Part# CJ688TGBU
f. Wall Plate
i. Panduit 4 Port faceplate Part# CFPSL4IWY
g. Patch Panel
i. Panduit CAT6 24 Port Part# DP24688TGY