POLE BASE REPLACEMENT DET 1 - 20260506l.pdf
PDF 84 KB Posted
- Solicitation number
- 36C26326Q0712
About this file
This document is a technical drawing for a pole base replacement detail. The drawing provides specifications for replacing an existing 30-foot aluminum light pole with a new concrete base foundation and grounding system. The project requires installation of a new 8-inch diameter by 10-foot-0-inch long copper-coated ground rod per code, along with a new concrete base utilizing a 5,000 PSI concrete mix with air-entrained reinforcing steel and rebar cage designed by a structural engineer. The drawing specifies anchor bolts per pole manufacturer requirements with leveling nuts positioned above and below the base plate.
The work includes reusing the existing pole structure while addressing existing conduit systems, both PVC and rigid steel, with adapter couplings and identification labels as needed. Additional specifications require a 2-piece bolt cover plate to be provided by VA, proper grounding rod installation, finished grade completion, and well-compacted undisturbed soil or select backfill. The drawing emphasizes compliance with construction safety requirements, proper mounting and leveling procedures, and identification of underground conduits with labels where required. The drawing scale is listed as N.T.S. (not to scale) with a reference date of 20260506.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26326Q0712 0003.docx | DOCX document | |
| SF 30 MOD.pdf | ||
| 36C26326Q0712 0002_1.docx | DOCX document | |
| 36C26326Q0712 0001_1.docx | DOCX document | |
| AMENDMENT.pdf | ||
| RFQ 36C26326Q0712.pdf | ||
| LPB-01 NORHT HALF LIGHT POLE BASE REPLACEMENT 20260506.pdf | ||
| Wage Determination.pdf | ||
| LPB-02 SOUTH HALF LIGHT POLE BASE REPLACEMENT 20260506.pdf | ||
| 36C26326Q0712_1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AutoCAD SHX Text
AutoCAD SHX Text
POLE BASE REPLACEMENT DETAIL
AutoCAD SHX Text
SCALE: N.T.S
AutoCAD SHX Text GENERAL NOTES: 1. BACKFILL, CONCRETE, REINFORCING BACKFILL, CONCRETE, REINFORCING STEEL, & ANCHOR BOLTS ARE SHOWN FOR REFERENCE ONLY. 2. FOLLOW CONSTRUCTION SAFETY FOLLOW CONSTRUCTION SAFETY REQUIREMENTS. 3. FOLLOW MOUNTING AND LEVELING FOLLOW MOUNTING AND LEVELING TYPICAL CONSTRUCTION REQUIREMENTS. 4. IDENTIFY UNDERGROUND CONDUITS, IDENTIFY UNDERGROUND CONDUITS, IF REQUIRED LABELS ARE MISSING.
AutoCAD SHX Text
EXISTING 30'-0" ALUMINUM LIGHT POLE LIGHT FIXTURE TO BE REUSED
AutoCAD SHX Text 76 x 127mm (3"x5") EXISTING REINFORCED HAND HOLE WITH TAMPER RESISTANT SCREWS. PROVIDE IN-LINE SCREW-TYPE FUSE HOLDER(S) WITH FUSE(S). (ASUMED)
AutoCAD SHX Text
POLE GROUNDING ROD
AutoCAD SHX Text
2-PIECE BOLT COVER PLATE (VA PROVIDED)
AutoCAD SHX Text EXISTING PVC CONDUIT ADAPTER COUPLING (ASUMED) PROVIDE IDENTIFICATION LABEL IF MISSING
AutoCAD SHX Text
EXISTING PVC CONDUIT (ASUMED)
AutoCAD SHX Text
EXISTING RIGID STEEL CONDUIT (ASUMED)
AutoCAD SHX Text
UNDISTURBED SOIL OR SELECT BACKFILL WELL COMPACTED, SEE NOTE BELOW.
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text ANCHOR BOLTS PER POLE MANUFACTURER'S REQUIREMENTS WITH LEVELING NUTS ABOVE & BELOW BASE PLATE
AutoCAD SHX Text
AutoCAD SHX Text (2'-6")
AutoCAD SHX Text (2'-0")
AutoCAD SHX Text 25mm (1") EXISTING CONDUIT WITH CAP (ASUMED) (APPROXIMATE LOCATION SHOWN ON SITE PLAN)
AutoCAD SHX Text NEW " DIAMETER X 10'-0" 58" DIAMETER X 10'-0" LONG COPPER COATED GROUND ROD. INSTALL AS PER CODE.
AutoCAD SHX Text NEW CONCRETE BASE REPLACEMENT 5,000 PSI CONCRETE MIX AIR ENTRAINED WITH REINFORCING STEEL REBAR CAGE, MIX DESIGN, CALCULATION BY STRUCTURAL ENGINEER.
AutoCAD SHX Text 2'
AutoCAD SHX Text 2'
AutoCAD SHX Text [609.6mm]
AutoCAD SHX Text 10'
AutoCAD SHX Text 10'
AutoCAD SHX Text [3048mm]GROUNDING ROD
AutoCAD SHX Text 762mm MIN
AutoCAD SHX Text (6'-0")
AutoCAD SHX Text (10'-0")
AutoCAD SHX Text
(2'-0" DIAMETER)
AutoCAD SHX Text
(GROUNDING ROD)
AutoCAD SHX Text 20260506