This document is a technical drawing for a pole base replacement detail. The drawing provides specifications for replacing an existing 30-foot aluminum light pole with a new concrete base foundation and grounding system. The project requires installation of a new 8-inch diameter by 10-foot-0-inch long copper-coated ground rod per code, along with a new concrete base utilizing a 5,000 PSI concrete mix with air-entrained reinforcing steel and rebar cage designed by a structural engineer. The drawing specifies anchor bolts per pole manufacturer requirements with leveling nuts positioned above and below the base plate.

The work includes reusing the existing pole structure while addressing existing conduit systems, both PVC and rigid steel, with adapter couplings and identification labels as needed. Additional specifications require a 2-piece bolt cover plate to be provided by VA, proper grounding rod installation, finished grade completion, and well-compacted undisturbed soil or select backfill. The drawing emphasizes compliance with construction safety requirements, proper mounting and leveling procedures, and identification of underground conduits with labels where required. The drawing scale is listed as N.T.S. (not to scale) with a reference date of 20260506.

View the file

Other files

File Type Posted
36C26326Q0712 0003.docx DOCX document
SF 30 MOD.pdf PDF
36C26326Q0712 0002_1.docx DOCX document
36C26326Q0712 0001_1.docx DOCX document
AMENDMENT.pdf PDF
RFQ 36C26326Q0712.pdf PDF
LPB-01 NORHT HALF LIGHT POLE BASE REPLACEMENT 20260506.pdf PDF
Wage Determination.pdf PDF
LPB-02 SOUTH HALF LIGHT POLE BASE REPLACEMENT 20260506.pdf PDF
36C26326Q0712_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AutoCAD SHX Text

AutoCAD SHX Text

POLE BASE REPLACEMENT DETAIL

AutoCAD SHX Text

SCALE: N.T.S

AutoCAD SHX Text GENERAL NOTES: 1. BACKFILL, CONCRETE, REINFORCING BACKFILL, CONCRETE, REINFORCING STEEL, & ANCHOR BOLTS ARE SHOWN FOR REFERENCE ONLY. 2. FOLLOW CONSTRUCTION SAFETY FOLLOW CONSTRUCTION SAFETY REQUIREMENTS. 3. FOLLOW MOUNTING AND LEVELING FOLLOW MOUNTING AND LEVELING TYPICAL CONSTRUCTION REQUIREMENTS. 4. IDENTIFY UNDERGROUND CONDUITS, IDENTIFY UNDERGROUND CONDUITS, IF REQUIRED LABELS ARE MISSING.

AutoCAD SHX Text

EXISTING 30'-0" ALUMINUM LIGHT POLE LIGHT FIXTURE TO BE REUSED

AutoCAD SHX Text 76 x 127mm (3"x5") EXISTING REINFORCED HAND HOLE WITH TAMPER RESISTANT SCREWS. PROVIDE IN-LINE SCREW-TYPE FUSE HOLDER(S) WITH FUSE(S). (ASUMED)

AutoCAD SHX Text

POLE GROUNDING ROD

AutoCAD SHX Text

2-PIECE BOLT COVER PLATE (VA PROVIDED)

AutoCAD SHX Text EXISTING PVC CONDUIT ADAPTER COUPLING (ASUMED) PROVIDE IDENTIFICATION LABEL IF MISSING

AutoCAD SHX Text

EXISTING PVC CONDUIT (ASUMED)

AutoCAD SHX Text

EXISTING RIGID STEEL CONDUIT (ASUMED)

AutoCAD SHX Text

UNDISTURBED SOIL OR SELECT BACKFILL WELL COMPACTED, SEE NOTE BELOW.

AutoCAD SHX Text

FINISHED GRADE

AutoCAD SHX Text ANCHOR BOLTS PER POLE MANUFACTURER'S REQUIREMENTS WITH LEVELING NUTS ABOVE & BELOW BASE PLATE

AutoCAD SHX Text

AutoCAD SHX Text (2'-6")

AutoCAD SHX Text (2'-0")

AutoCAD SHX Text 25mm (1") EXISTING CONDUIT WITH CAP (ASUMED) (APPROXIMATE LOCATION SHOWN ON SITE PLAN)

AutoCAD SHX Text NEW " DIAMETER X 10'-0" 58" DIAMETER X 10'-0" LONG COPPER COATED GROUND ROD. INSTALL AS PER CODE.

AutoCAD SHX Text NEW CONCRETE BASE REPLACEMENT 5,000 PSI CONCRETE MIX AIR ENTRAINED WITH REINFORCING STEEL REBAR CAGE, MIX DESIGN, CALCULATION BY STRUCTURAL ENGINEER.

AutoCAD SHX Text 2'

AutoCAD SHX Text 2'

AutoCAD SHX Text [609.6mm]

AutoCAD SHX Text 10'

AutoCAD SHX Text 10'

AutoCAD SHX Text [3048mm]GROUNDING ROD

AutoCAD SHX Text 762mm MIN

AutoCAD SHX Text (6'-0")

AutoCAD SHX Text (10'-0")

AutoCAD SHX Text

(2'-0" DIAMETER)

AutoCAD SHX Text

(GROUNDING ROD)