This is an electrical site plan document for the State of Hawaii's boat lift improvements project at Pier 1 in Hilo Harbor (Project P50217). The plans detail the installation of electrical infrastructure to support a new pre-engineered elevator boat lift structure, including partial electrical site plans, enlarged electrical details, equipment specifications, and duct encasement requirements. The project encompasses trenching for electrical conduits, installation of electrical connections for the boat lift system, and coordination with existing electrical panels and transformer equipment. Key electrical components specified include a 3-phase 200-amp equipment enclosure, a 15KVA dry-type transformer rated 240X480V to 120/240V, disconnect switches rated at 2-pole 30-amp and 2-pole 20-amp, and multiple junction boxes constructed from 6-inch square by 4-inch deep and 12-inch square by 6-inch deep NEMA 4X 316 stainless steel enclosures. The plans establish detailed duct and wire schedules for various utility lines, including primary/secondary electric, control/instrumentation, and telecommunications conduits, with specific minimum separation requirements and concrete encasement specifications. Equipment racks are designed using 1-5/8 inch 316 stainless steel C-channels and brackets, fabricated to nominal 24 by 36-inch dimensions and adjustable based on final requirements.

The estimated construction cost for the overall boat lift improvements project ranges from $350,000 to $450,000. Each boat lift track will be mounted on a concrete pile cap supported by micropiles below, with restoration of asphalt concrete pavement, chain link fencing, gates, and miscellaneous site elements included in the scope. The electrical plans were certified by Adobe Acrobat Sign on April 16, 2026, indicating these are final construction documents ready for bidding and implementation.

View the file

Other files

File Type Posted
Specifications-FINAL SPECIFICATIONS w NTB P50217.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

for 04/16/2026 https://stateofhawaii.na1.adobesign.com/verifier?tx=CBJCHBCAABAAYfahrmarr1AISKp4qVz-ALv2hRY2_cxV

SCALE: 1"=10'

PARTIAL ELECTRICAL SITE PLAN

10' 5' 0 10' 20' 30'

SCALE: 1"=10'

GRAPHIC SCALE

SCALE: NOT TO SCALE

ENLARGED ELECTRICAL PLAN 1

SCALE: NOT TO SCALE

ENLARGED ELECTRICAL PLAN 2

EQUIPMENT FURNISHED BY

BOAT LIFT MANUFACTURER,

INSTALLED BY ELECTRICAL

NOTE(S):

PANEL SCHEDULE

NO SCALE

PC INDICATES PROVIDE PULLCORD.

ALL CONCRETE ENCASED DUCTS SHALL BE SCHEDULE 40 PVC.

DESTINATION/USE/DESCRIPTIONWIRE SIZEDUCT SIZENO.

DUCT AND WIRE SCHEDULE

SIG = INSTRUMENTATION OR ANTENNA CABLE

TEL = UTILITY CO. TELEPHONE

PWR = PRIMARY OR SECONDARY ELECTRIC

CTL = CONTROL

ELEC = UTILITY CO. PRIMARY OR SECONDARY ELECTRIC

CTL/SIG - CTL/SIG = 1 1/2"

PWR - PWR = 1 1/2"

TEL - PWR = 3"

ELEC - PWR = 3"

DUCTLINE.

ENCASEMENT AROUND

MINIMUM OF 3" CONCRETE

ELEC - ELEC = 1 1/2"

ELEC - TEL = 3"

TEL - TEL = 1 1/2"

ELEC - CTL/SIG = 3"

TEL - CTL/SIG = 1 1/2"

PWR - CTL/SIG = 3"

NOTES:

1.

2.

DUCT SECTION DETAILS

LINE.

3.

2.

1.

BACKFILL AROUND WATER

PROVIDE ONLY TYPE "B"

AROUND DUCTLINES.

PROVIDE CONCRETE ENCASEMENT

DUCTLINES AND WATER LINE.

6" MINIMUM SEPARATION BETWEEN

WATER LINE, PROVIDE THE FOLLOWING:

WHERE DUCTLINE CROSSES OVER

(TYP)

DIMENSION REQUIREMENTS

SEE NOTES BELOW FOR MINIMUM

SEE CIVIL DRAWINGS FOR

BACKFILL AND RESTORATION

DUCT COMPLEMENTS

DETAILS FOR

SEE DUCT SECTION

TYPICAL DUCT SECTION

2#12, 1#12 GND1" BOAT LIFT

3"3"

3" 3"

A

REQUIREMENTS

3P200A

EXIST EQUIPMENT ENCLOSURE

JB 1

6"SQ X 4"D,

NEMA 4X 316 SS

DISCONNECT SWITCH

2P30A, NEMA 4X 316 SS

2P20A

ONE-LINE DIAGRAM

SCALE: NONE

3/4"C, 2#12, 1#12 GND

EXIST PANEL P4 (PARTIAL)

480Y/277V, 3PH, 4W

EXIST PANEL 2A (PARTIAL)

120/240V, 1PH, 3W, 10KAIC

EATON

CAT. NO. BR4242L225S4XG

EXIST DRY-TYPE TRANSFORMER

15KVA, 240X480V - 120/240V

JB 2

6"SQ X 4"D,

NEMA 4X 316 SS

1"C, 2#12, 1#12 GND

TYPICAL EQUIPMENT RACK DETAIL

NOT TO SCALE

36" NOMINAL,

ADJUST WIDTH

AS REQUIRED

C-CHANNEL, 1-5/8",

316 STAINLESS STEEL,

TYPICAL

C-CHANNEL, 1-5/8"

BACK-TO-BACK,

316 STAINLESS STEEL

U SHAPED BRACKET,

5-HOLE,

316 STAINLESS STEEL

8-HOLE POST BRACKET,

316 STAINLESS STEEL

C-CHANNEL, 1-5/8"

BACK-TO-BACK,

316 STAINLESS STEEL

C-CHANNEL, 1-5/8",

316 STAINLESS STEEL,

TYPICAL

U SHAPED BRACKET,

5-HOLE,

316 STAINLESS STEEL

8-HOLE POST BRACKET,

316 STAINLESS STEEL

FINISHED GRADEFINISHED GRADE

JB 3

12"SQ X 6"D,

NEMA 4X 316 SS

JB 3

12"SQ X 6"D,

NEMA 4X 316 SS

JB 3

12"SQ X 6"D,

NEMA 4X 316 SS

TO EQUIPMENT

ENCLOSURE

TO CONTROL PANEL

CONTROL PANEL

E

E

BOAT LIFT MOTOR

1 EQUIPMENT FURNISHED BY

BOAT LIFT MANUFACTURER,

INSTALLED BY ELECTRICAL

NOTE(S):

2026-04-16T23:57:32+0000
Certified by Adobe Acrobat Sign