PLANS.pdf

PDF 2 MB Posted

Attached to
Ames Generator Replacement
Solicitation number
645-DOTRFB-3180-2027
Issued by
Story County, Iowa

About this file

Summary

This document comprises electrical engineering plans and specifications prepared by the Iowa Department of Transportation for the Ames Generator Replacement project located at 800 Lincoln Way, Ames, Iowa 50010 (Project Number 2240014950). The plans include a cover sheet, electrical general information, electrical site plan, basement plan, and electrical one-line diagram with schedules. The project involves removing an existing 500 kW, 625 kVA generator and installing a new 250 kW, 313 kVA generator with associated infrastructure modifications, including installation of a new natural gas line and generator connection cabinet. Work is to comply with the National Electrical Code and all applicable state and local codes. The contractor is responsible for all labor, materials, permits, inspections, and equipment necessary for a complete and operational system. All work must be coordinated with other trades, and the contractor shall maintain daily site cleanliness and follow specifications for demolition, fire-rated wall penetrations, electrical panel updates, and system coordination with existing fire alarm, security, and communication systems.

The contract requires the contractor to provide a typed updated circuit directory card for all affected electrical panels and properly indicate spare breakers. Key electrical modifications include reusing an existing 20-ampere, three-phase circuit for the generator heater and battery charger; rerouting circuits from the existing panel to a new panel; and coordinating new power and lighting circuits from the first floor of an adjacent building. The natural gas service requires contractor coordination with Alliant Energy for new meter installation and sizing, with the contractor responsible for all utility fees. The generator specifications indicate a 100 percent load demand of 3,180 cubic feet per hour at 7-11 inches of water column pressure, with supply sizing calculated at 4,770 cubic feet per hour. A Trystar TMTS-1 or equivalent generator connection cabinet rated at 400 amperes, three-phase, four-wire at 480 volts and NEMA 3R enclosure is required. The engineer will conduct periodic site observations to verify work compliance with contract documents, though this observation is not continuous or exhaustive.

View the file

Other files

File Type Posted
1463661-event.pdf PDF
PROJECT MANUAL.pdf PDF
A201-2017 Template.pdf PDF
A101-2017 - for RFB FINAL.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SEAL

A P

P R

O V

E D

B Y

D R

A W

N B

Y

IS

S

U E

D F

O R

IS

S

U E

D A

T E

P R

O J E

C T

N U

M B

E R

F

IE

L D

B O

O K

BA D E

FC G

H

BA D E FC G H

Autodesk Revit 2024Autodesk Revit 2024

/3

/2

:5 :1

P

M

A u to d e s k D o c s /I D

O T

A m e s G e n e ra to r

W O

/2

A m e s G e n e ra to r

W O

.r v t

IF

C

K J B

B F

G

-0

-3

G000

ID

O

T

A M

E S

G E

N E

R A

T O

R R

E P

L A

C E

M E

N T

IO

W

A D

E P

A R

T M

E N

T O

F T

R A

N S

P O

R T

A T

IO

N

L

IN

C

O L N

W A

Y A

M E

S

IO

W

A

.7

.0

S

H

IV

E -H

A T

T E

R Y

.C O

M

Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010

PROJECT

LOCATION

C O

V E

R S

H E

E T

AMES GENERATOR REPLACMENT

800 Lincoln Way

Ames, IA 50010Ames, IA 50010

PROJECT:2240014950

SHEET LIST

G000 COVER SHEET

E000 E100 E200 E300

ELECTRICAL GENERAL INFORMATION

ELECTRICAL SITE PLAN

BASEMENT PLAN

ELECTRICAL ONE-LINE & SCHEDULES

PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL:

PRINTED OR TYPED NAME

SIGNATURE

MY LICENSE RENEWAL DATE IS DECEMBER 31,

DATE

LICENSE NUMBER

I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS

PREPARED BY ME OR UNDER MY DIRECT SUPERVISION AND THAT I

AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS

OF THE STATE OF IOWA.

Kevin J. Bruxvoort

E-SHEETS

19927

ELECTRICAL ENGINEER

LINCOLN WAY

S G

R A

N D

A V

E

1. ALL WORK SHALL BE IN CONFORMANCE WITH THE NATIONAL

ELECTRICAL CODE - LATEST EDITION ADOPTED BY THE STATE,

THE STATE AMENDMENTS, LOCAL/MUNICIPAL CODES AND

ORDINANCES, AND THE AUTHORITY HAVING JURISDICTION.

THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE

WITH THE ADAAG (AMERICANS WITH DISABILITIES ACT

ACCESSIBILITY GUIDELINES).

2. IT IS THE INTENT OF THESE DOCUMENTS TO COMPLY WITH

THE APPLICABLE CODES. WHERE DISCREPANCIES OCCUR,

NOTIFY THE ENGINEER/ARCHITECT IN WRITING FOR

INTERPRETATION. CORRECT ANY INSTALLATION THAT FAILS

TO COMPLY WITH THE CODES AND STANDARDS AT NO

ADDITIONAL COST TO THE OWNER.

3. CONTRACTOR SHALL PROVIDE ALL WORK NECESSARY

INCLUDING ALL LABOR, MATERIALS, PERMITS, TAXES, FEES,

INSPECTIONS, HARDWARE, AND COST FOR INSTALLATION FOR

A COMPLETE AND OPERATIONAL SYSTEM.

4. ALL MATERIALS FURNISHED BY THE CONTRACTOR SHALL BE

NEW, COMPLETE WITH MANUFACTURER’S GUARANTEE OR

WARRANTY AND SHALL BE LISTED BY A NATIONALLY

RECOGNIZED TESTING LABORATORY (NRTL).

5. COORDINATE ELECTRICAL INSTALLATION WITH ALL TRADES

PRIOR TO INSTALLATION. IF ELECTRICAL WORK INSTALLED

INTERFERES WITH OTHER TRADES AFTER INSTALLATION, THE

CONTRACTOR SHALL MAKE ALL NECESSARY CHANGES TO

CORRECT THE CONDITION AT NO ADDITIONAL COST TO THE

OWNER.

6. ALL ELECTRICAL PANELS WITH ANY BRANCH CIRCUIT/LOAD

REVISIONS (DEMOLITION OR NEW WORK) SHALL HAVE A NEW

TYPED UPDATED CIRCUIT DIRECTORY CARD INSTALLED INSIDE

THE DOOR OF THE ELECTRICAL PANEL. THE CONTRACTOR

SHALL VERIFY THAT ALL UNUSED CIRCUIT BREAKERS ARE

TURNED ‘OFF’ AND PROPERLY INDICATED AS ‘SPARE’ ON THE

NEW CIRCUIT DIRECTORY CARD. THE CONTRACTOR SHALL

INSTALL FILLER PLATES WHERE BREAKERS ARE REMOVED AS

PART OF THIS PROJECT OR HAVE BEEN REMOVED

PREVIOUSLY.

7. NO ENERGIZED CONDUCTORS SHALL BE EXPOSED AT

ANYTIME EXCEPT WHEN THE IMMEDIATE AREA IS UNDER THE

SUPERVISION OF A QUALIFIED ELECTRICIAN.

8. WHERE CONDUIT IS SURFACE MOUNTED TO A WALL AND RUN

VERTICALLY DOWN TO A SWITCH/OUTLET BOX, UTILIZE 1-HOLE

OR 2-HOLE CONDUIT STRAPS.

9. PENETRATIONS THROUGH FIRE RATED WALLS BY DIVISION 26

CONTRACTOR SHALL BE SEALED WITH APPROPRIATE FIRE

PROOFING MATERIAL TO RESTORE FIRE RATING.

10. THE CONTRACTOR SHALL KEEP THE WORK AREA CLEAN OF

ALL DEBRIS ON A DAILY BASIS. ALL NEW MATERIALS AWAITING

INSTALLATION SHALL BE KEPT IN AREAS DESIGNATED BY THE

OWNER.

11. THESE DRAWINGS SHALL NOT BE SCALED TO OBTAIN

DIMENSIONS. IF THE DIMENSIONS CANNOT BE DETERMINED

BY THE INFORMATION GIVEN, CONTRACTOR SHALL CONTACT

THE ENGINEER FOR ADDITIONAL INFORMATION.

12. PERIODIC SITE OBSERVATION BY THE ENGINEER IS SOLELY

FOR THE PURPOSE OF DETERMINING IF THE WORK OF THE

CONTRACTOR IS PROCEEDING IN ACCORDANCE WITH THE

CONTRACT DOCUMENTS. THIS LIMITED SITE OBSERVATION

SHOULD NOT BE CONSTRUED AS EXHAUSTIVE OR

CONTINUOUS TO CHECK THE QUALITY OR QUANTITY OF THE

WORK, BUT RATHER PERIODIC IN AN EFFORT TO GUARD THE

OWNER AGAINST DEFECTS OR DEFICIENCIES IN THE WORK OF

THE CONTRACTOR.

13. THE INFORMATION CONTAINED ON THE ELECTRICAL

DRAWINGS IS IN ITSELF INCOMPLETE AND VOID UNLESS USED

IN CONJUNCTION WITH ALL OTHER DISCIPLINE DRAWINGS,

THE SPECIFICATIONS, TRADE PRACTICES, OR APPLICABLE

STANDARDS, CODES, ETC., AND SHALL BE CONSIDERED THE

CONTRACT DOCUMENTS AND WITH ALL THEREIN BY

REFERENCE, WHICH THE CONTRACTOR CERTIFIES

KNOWLEDGE OF BY SIGNING THE CONTRACT.

14. CONTRACTOR IS TO ASSUME FULL RESPONSIBILITY,

UNRELIEVED BY REVIEW OF SHOP DRAWINGS OR PERIODIC

OBSERVATION OF CONSTRUCTION, FOR COMPLIANCE WITH

THE CONTRACT DOCUMENTS, FOR DIMENSIONS TO BE

CONFIRMED AND CORRELATED ON THE JOB SITE AND

BETWEEN INDIVIDUAL DRAWINGS OR SETS OF DRAWINGS FOR

FABRICATION PROCESSES AND CONSTRUCTION TECHNIQUES

(INCLUDING EXCAVATION, SHORING, SCAFFOLDING, BRACING,

ERECTION, FORM WORK, ETC.), FOR COORDINATION OF THE

VARIOUS TRADES, AND FOR SAFE CONDITIONS ON THE JOB

SITE. VARIATIONS IN FIELD CONDITIONS RELATIVE TO THE

CONTRACT DOCUMENTS SHALL BE REPORTED TO THE

ENGINEER AS SOON AS THEY ARE FOUND. WORK SHALL NOT

PROGRESS UNTIL WRITTEN PERMISSION FROM THE ENGINEER

IS OBTAINED.

ELECTRICAL

1. LIGHT LINES INDICATE EXISTING WALLS AND EQUIPMENT TO

REMAIN. DASHED LINES INDICATE WALLS, EQUIPMENT, AND

ELECTRICAL ITEMS TO BE REMOVED.

2. COORDINATE PATCHING REQUIREMENTS FOR UNUSED

OPENINGS WITH THE GENERAL CONTRACTOR. GENERAL

CONTRACTOR SHALL PATCH ALL UNUSED OPENINGS.

PATCHWORK SHALL MATCH MATERIALS, FINISH, AND TEXTURE

OF ADJACENT SURFACES.

3. FIRE ALARM - REMOVE EXISTING CEILING MOUNTED DEVICES

TO PERMIT REMOVAL OF CEILING. WALL MOUNTED

NOTIFICATION DEVICES SHALL BE DEMOLISHED. COORDINATE

WORK WITH PROJECT PHASING TO MAINTAIN FIRE ALARM

SYSTEM PROTECTION OF SPACES AT ALL TIMES. INCLUDE

COSTS OF ALL TEMPORARY DEVICES IN THE BID.

4. SECURITY/SURVEILLANCE - EXISTING DEVICES TO BE

REMOVED BY SYSTEMS VENDOR. CONTRACTOR SHALL

REMOVE ASSOCIATED CABLING, ROUGH-IN, AND POWER

WIRING. PRIOR TO ANY DEMOLITION IDENTIFY AND PROTECT

CABLING REQUIRED TO MAINTAIN THE SYSTEM IN AREAS THAT

WILL NOT BE REMODELED.

5. COORDINATE DISPOSAL OF ALL ITEMS NOT REQUESTED AS

SALVAGE BY THE OWNER.

6. TELEPHONE AND DATA HORIZONTAL CABLING SHALL BE

REMOVED COMPLETELY BACK TO THE FIRST REMAINING

DISTRIBUTION FRAME. PROTECT FIBER OPTIC AND COPPER

TRUNK CABLING SERVING DISTRIBUTION RACKS.

7. LIGHTING FIXTURES AND CONTROLS - REMOVE EXISTING

LIGHT FIXTURES, WALL SWITCHES, OCCUPANCY SENSORS,

AND ASSOCIATED WIRING. VERIFY AND MAINTAIN

CONNECTION TO EXISTING LIGHTING THAT WILL NOT BE

REMOVED BUT ARE ON COMMON CIRCUITS WITH ITEMS TO BE

REMOVED.

8. DISCONNECT OUTLETS, WIRING, AND OTHER NOTED

EQUIPMENT TO PERMIT DEMOLITION OF WALLS. VERIFY AND

MAINTAIN CONNECTION TO EXISTING OUTLETS THAT WILL NOT

BE REMOVED BUT ARE ON COMMON CIRCUITS WITH ITEMS TO

BE REMOVED.

9. DRAWINGS DO NOT IDENTIFY ALL OUTLETS, SWITCHES,

CABLING, OR EQUIPMENT TO BE REMOVED. CONTRACTOR

SHALL BECOME FAMILIAR WITH THE SITE PRIOR TO BIDDING

AND INCLUDE LABOR AND MATERIAL NECESSARY FOR

REQUIRED DEMOLITION IN THEIR BID.

10. WIRING SHALL BE REMOVED BACK TO SERVING PANEL.

INSTALLATION OF NEW CONDUCTORS IN EXISTING CONDUITS

WILL BE PERMITTED AS DESCRIBED IN THE DIVISION 26

SPECIFICATIONS.

11. HVAC EQUIPMENT NOTED FOR REMOVAL IS FOR REFERENCE

ONLY. THE ELECTRICAL CONTRACTOR SHALL REVIEW THE

MECHANICAL SYSTEMS DEMOLITION PLANS AND INCLUDE ALL

LABOR AND MATERIAL NECESSARY TO FACILITATE REMOVAL

OF EQUIPMENT AS SHOWN ON THOSE DRAWINGS. THIS SHALL

INCLUDE ALL ITEMS NOTED ON EITHER THE PLUMBING OR

MECHANICAL SERIES OF DRAWINGS.

ELECTRICAL DEMOLITION

ELECTRICAL ABBREVIATIONS

A

A

AC

ACB

AF

AFF

AL

ALT

AM

AS

AT

APPROX

ATC

ATS

AUTO

AUX

AWG

B

BAS

BD

BRKR

BLDG

B/M

BUZ

C

C

CAB

CB

CCTV

CKT

CL

CLG

COMM

CONN

CONC

COND

CONTR

CP

CPT

CR

CT

CU

D

DC

DIA

DIAG

DIM

DISC

DIV

DN

DP

DT

DWG

E

EC

EL

ELEC

EMER

EMT

ENG

EPO

ETM

EWC

EXH

EXIST

F

F

FA

FACP

FC

FDR

FF

FHP

FL

FLEX

FLR

FLUOR

FREQ

AMPERE

ABOVE COUNTER/ALTERNATING CURRENT

AIR CIRCUIT BREAKER

AMPERE RATING OF FUSE

ABOVE FINISHED FLOOR

ALUMINUM

ALTERNATE

AMMETER

AMMETER SWITCH

AMPERE TRIP RATING

APPROXIMATELY

AUTOMATIC TEMPERATURE CONTROL

AUTOMATIC TRANSFER SWITCH

AUTOMATIC

AUXILIARY

AMERICAN WIRE GAUGE

BUILDING AUTOMATION SYSTEM

BUS DUCT

BREAKER

BUILDING

BILL OF MATERIALS

BUZZER

CONTRACTOR

CABINET

CIRCUIT BREAKER

CLOSED CIRCUIT TELEVISION

CIRCUIT

CENTERLINE

CEILING

COMMUNICATIONS CONNECT, CONNECTED,

CONNECTOR

CONCRETE

CONDUCTOR

CONTRACTOR

CONTROL PANEL

CONTROL POWER TRANSFORMER

CONTROL RELAY

CURRENT TRANSFORMER

COPPER

DIRECT CURRENT

DIAMETER

DIAGRAM

DIMMER CONTROL

DISCONNECT

DIVISION

DOWN

DOUBLE POLE

DOUBLE THROW

DRAWING

ELECTRICAL CONTRACTOR

ELEVATION

ELECTRICAL

EMERGENCY

ELECTRICAL METALLIC TUBING

ENGINEER

EMERGENCY POWER OFF

ELAPSED (RUN) TIME METER

ELECTRIC WATER COOLER

EXHAUST

EXISTING

FUSE

FIRE ALARM

FIRE ALARM CONTROL PANEL

FOOTCANDLE

FEEDER

FURNITURE FEED

FRACTIONAL HORSEPOWER

FLOODLIGHT

FLEXIBLE, FLEXIBLE CONDUIT

FLOOR

FLUORESCENT

FREQUENCY

G

GC

GEC

GEN

GFI

GFP

GND

GR

GW

H

HGT

HH

HID

HP

HPS

HTR

HZ

I

IMC

INCAND

INTCONN

J

JB

JCT

K

K

KCMIL

KV

KVA

KVAR

KW

KWH

L

LG

LIM

LPS

LTG

LV

LVSS

M

MAN

MATL

MC

MCC

MCP

MFR

MH

MIC

MLO

MTG

MTR

MTS

MVA

MVAR

MW

MWH

N

NC

NF

NIC

NEC

NEMA

NO

NTS

O

OCB

OPR

OL

GENERAL CONTRACTOR

GROUNDING ELECTRODE CONDUCTOR

GENERATOR

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT PROTECTOR

GROUND, GROUNDING CONDUCTOR

GROUND ROD

GROUND WELL

HEIGHT

HANDHOLE

HIGH INTENSITY DISCHARGE

HORSEPOWER

HIGH PRESSURE SODIUM

HEATER

HERTZ, FREQUENCY IN CYCLES PER SECOND

INTERMEDIATE METALLIC CONDUIT

INCANDESCENT

INTERCONNECTION

JUNCTION BOX

JUNCTION

KEY OPERATED

THOUSAND CIRCULAR MILS

KILOVOLT

KILOVOLT-AMPERE

KILOVOLT-AMPERE REACTIVE

KILOWATT

KILOWATT-HOUR

LENGTH

LIMIT

LOW PRESSURE SODIUM

LIGHT, LIGHTING

LOW VOLTAGE

LOW VOLTAGE SURGE SUPPRESSION

MANUAL

MATERIAL

MECHANICAL CONTRACTOR

MOTOR CONTROL CENTER

MOTOR CIRCUIT PROTECTOR

MANUFACTURER

MANHOLE

MICROPHONE

MAIN LUGS ONLY

MOUNT, MOUNTED, MOUNTING

MOTOR

MANUAL TRANSFER SWITCH

MEGAVOLT-AMPERE

MEGAVOLT-AMPERE REACTIVE

MEGAWATT

MEGAWATT-HOUR

NORMALLY CLOSED

NON-FUSED

NOT IN CONTRACT

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NORMALLY OPEN

NOT TO SCALE

OIL CIRCUIT BREAKER

OPERATOR, OPERATED

THERMAL OVERLOAD PROTECTION

P

P

PB

PC

PF

PFM

PNL

PRI

PS

PT

PVC

PWR

R

R

RC

RECPT

REF

REQD

RGS

S

SA

SCHD

SCHM

SP

SPKR

ST

STA

STBY

SUBSTA

SW

SWBD

SWGR

SYNC

SYS

T

T/

TB

TC

TCC

TDCD

TDCE

TDOD

TDOE

TEL

TEMP

TERM

TSTAT

TV

TYP

U

UG

UNO

UNG

UPS

V

V

VA

VAR

VERT

VFD

VM

VS

W

W W/ W/O

WH

WP

X

XDCR

XFMR

XFR

XMIT

XP

PILOT

LIGHT PUSHBUTTON

PHOTOCELL

POWER FACTOR

POWER FACTOR METER

PANEL

PRIMARY

PRESSURE SWITCH

POTENTIAL TRANSFORMER

POLVINYLCHLORIDE, PVC CONDUIT

POWER

RELAY

REMOTE CONTROL

RECEPTACLE

REFER, REFERENCE

REQUIRED

RIGID GALVANIZED STEEL CONDUIT

SURGE ARRESTER

SCHEDULE

SCHEMATIC

SINGLE POLE

LOUDSPEAKER

SINGLE THROW

STATION

STANDBY

SUBSTATION

SWITCH

SWITCHBOARD

SWITCHGEAR

SYNCHRONIZE, (ING), (ACTION)

SYSTEM

TOP OF

TERMINAL BOARD

TIMECLOCK

TEMPERATURE CONTROL CONTRACTOR

TIME DELAY CLOSE ON DENERGIZATION

TIME DELAY CLOSE ON ENERGIZATION

TIME DELAY OPEN ON DENERGIZATION

TIME DELAY OPEN ON ENERGIZATION

TELEPHONE

TEMPERATURE

TERMINAL

THERMOSTAT

TELEVISION

TYPICAL

UNDERGROUND

UNLESS NOTED OTHERWISE

UNGROUNDED

UNINTERRUPTIBLE POWER SUPPLY

VOLTS

VOLT-AMPERE

VOLT-AMPERE REACTIVE

VERTICAL

VARIABLE FREQUENCY DRIVE

VOLTMETER

VOLTMETER SWITCH

WATTS

WITH

WITHOUT

WATT-HOUR

WEATHERPROOF

TRANSDUCER

TRANSFORMER

TRANSFER

TRANSMIT, TRANSMITTER

EXPLOSION PROOF

UC

OS

LS

S

FS

TS

FB

B

L

L S

FACP

FARP

NAC

EVAC

FTR

FSCP

HVA

TCVR

T R

DR

FR

ARCR

ASCP

ARCM

E

HH

J

TV

N

NCM

NC ANNUN

NCC

K

D

OS

M

T

SURFACE CYLINDER

RECESSED DOWNLIGHT

WALL MOUNTED LIGHT

FLOOD LIGHT

POLE MOUNTED LIGHT

SURFACE LIGHT

SUSPENDED LINEAR

(+ DENOTES POWERED FROM)

RECESSED LINEAR

INDUSTRIAL STRIP LIGHT

TRACK AND TRACK LIGHT

EMERGENCY LIGHT

EXIT SIGN

LIGHT FIXTURE ON EMERGENCY CIRCUIT

SINGLE POLE SWITCH

3-WAY SWITCH

4-WAY SWITCH

KEYED SWITCH

DIMMER SWITCH

OCCUPANCY SENSOR SWITCH

MOMENTARY CONTACT SWITCH

TIMER SWITCH

PUSH BUTTON

DURESS PUSH BUTTON, UNDER COUNTER

DUPLEX RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

FLOOR BOX

DUPLEX RECEPTACLE - CEILING MOUNTED

CLOCK

OCCUPANCY SENSOR

LIGHT LEVEL SENSOR

EXTERIOR PHOTOCELL

SECURITY CAMERA

CONDUIT CONCEALED IN WALL OR OVERHEAD

CONDUIT CONCEALED BELOW FLOOR

CONDUIT TRANSITION UP

CONDUIT TRANSITION DOWN

CONDUIT STUBBED OUT

BRANCH CIRCUIT HOME RUN

CABLE TRAY (TYPE DENOTED)

CONDUIT SLEEVE (SIZE DENOTED)

VOICE/DATA OUTLET (WALL OR CEILING MOUNT)

# - QUANTITY OF RJ-45 JACKS/CABLES.

ONE, UNLESS SHOWN OTHERWISE

W - DENOTES WALL PHONE

WIRELESS ACCESS POINT (WALL OR CEILING MOUNT)

# - QUANTITY OF RJ-45 JACKS/CABLES.

ONE, UNLESS SHOWN OTHERWISE

TELEVISION OUTLET (WALL OR CEILING MOUNT)

SPEAKER (WALL OR CEILING MOUNT)

INTERCOM STATION

KEYNOTE (SEE SCHEDULE)E#

SPRINKLER FLOW SWITCH

SPRINKLER VALVE TAMPER SWITCH

DUCT SMOKE DETECTOR

LINEAR HEAT DETECTOR

REMOTE TEST/STATUS STATION

AUDIO NOTIFICATION DEVICE - CEILING MOUNTED

B = BELL

C = CHIME

H = HORN

S = SPEAKER

AUDIO NOTIFICATION DEVICE - WALL MOUNTED

B = BELL

C = CHIME

H = HORN

S = SPEAKER

VISUAL NOTIFICATION DEVICE - CEILING MOUNTED

VISUAL NOTIFICATION DEVICE - WALL MOUNTED

AUDIO/VISUAL NOTIFICATION DEVICE -

CEILING MOUNTED

B = BELL

C = CHIME

H = HORN

S = SPEAKER

AUDIO/VISUAL NOTIFICATION DEVICE -

WALL MOUNTED

B = BELL

C = CHIME

H = HORN

S = SPEAKER

FIRE ALARM CONTROL PANEL

FIRE ALARM RELAY PANEL

NAC POWER SUPPLY

VOICE EVACUATION PANEL

FIRE ALARM TRANSPONDER

FIRE SUPPRESSION CONTROL PANEL

HVAC PRESSURIZATION PANEL

FIRE ALARM TRANSCEIVER PANEL

BEAM SMOKE DETECTOR

T = TRANSMITTER/RECEIVER

R = REFLECTOR

DOOR HOLDER/HOLD OPEN

SMOKE DAMPER RELEASE

FIRE ALARM SHUT DOWN RELAY

SMOKE DETECTOR

HEAT DETECTOR

AREA OF REFUGE - CALL STATION

AIR SAMPLING CONTROL PANEL

AREA OF REFUGE - MASTER

FIREFIGHTER PHONE

EMERGENCY EXIT SIGN

SPECIAL RECEPTACLE

(CEILING, WALL, AND FLOOR MOUNTED)

BOLLARD

DIRECT POWER CONNECTION -

WALL AND EQUIPMENT

HANDHOLE

JUNCTION BOX

SYMBOL DESCRIPTION

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

SYMBOL DESCRIPTION

SYMBOL DESCRIPTION

SYMBOL DESCRIPTION

PENDANT LIGHT

SIMPLEX RECEPTACLE

SPLIT DUPLEX RECEPTACLE

DUPLEX RECEPTACLE ON EMERGENCY CIRCUIT

DUPLEX RECEPTACLE PLUG LOAD CONTROL

DOUBLE DUPLEX RECEPTACLE ON EMERGENCY CIRCUIT

MOTION DETECTOR (TYPE DENOTED)

DOOR SIGNAL - APARTMENT UNIT

BUZZER

D

BELL

CHIME

NURSE CALL SINGLE PATIENT STATION

37 PIN BED INTERFACE RECEPTACLE

AUXILIARY ALARM STATION, TWO JACK

EMERGENCY PULL CORD STATION

STAFF TERMINAL, TOUCHSCREEN

DUTY STATION

NURSE CALL DOME LIGHT

NURSE CALL MASTER STATION

NURSE CALL EQUIPMENT CABINET

NURSE CALL ANNUNCIATOR PANEL

STAFF ASSIST

CODE BLUE STATION

NURSE CALL STAFF STATION

CARD READER

SYMBOL DESCRIPTION

LIGHTING/CONTROLS

GENERAL POWER

COMMUNICATION/DATA

SECURITY

NURSE CALL

FIRE ALARM

ELECTRICAL SYMBOLS LEGEND

0000 SPECIALTY EQUIPMENT TAG

PL SINGLE POLE SWITCH WITH PILOT LIGHT

DOUBLE DUPLEX RECEPTACLE PLUG LOAD CONTROL

C

EXAMPLE RECEPTACLE TAG

##" - MOUNTING HEIGHT AS INDICATED.

IF OMITTED, 18" OR ABOVE COUNTER

XX - INDICATES RECEPTACLE CONFIGURATION:

GROUND CONNECTION - EXOTHERMIC WELD

GROUND CONNECTION TO STEEL OR STRUCTURE

STATIC GROUND RECEPTACLE (TYPE DENOTED)

GROUND ROD (PLAN VIEW)

LIGHTNING PROTECTION AIR TERMINAL

LIGHTNING PROTECTION CONDUCTOR SPLICE

SYMBOL DESCRIPTION

GROUNDING

XX

AC

GFI

HZ

IG

OC

USB

WP

XP

ABOVE COUNTER (COORDINATE HEIGHT)

GROUND FAULT CIRCUIT INTERRUPTER

HORIZONTALLY MOUNTED

ISOLATED GROUND

OCCUPANCY CONTROLLED

INTEGRAL USB CHARGER

WEATHERPROOF

EXPLOSION PROOF

XX

XX

FIRE ALARM - CONTINUED

MANUAL PULL STATION

GROUND BAR

ANN FIRE ALARM REMOTE ANNUNCIATOR

KEYPAD

REQUEST TO EXIT

SURFACE MOUNTED RECEPTACLE, VARIES PER TYPE

F

L S

L

B

P

RX

J

E

N

B

A

S

D

T

DH

TV

S

E

J

IC

CR

IR

MD

C

DESCRIPTIONSYMBOL

P C

WT WALL MOUNTED TOUCHPAD

# LIGHTING CONTROL DENOTATION

TROFFER LIGHT

POWER - CONTINUED

R

VFD

SURFACE RACEWAY

BRANCH PANEL WITH CLEARANCE

(SURFACE OR RECESS MOUNTED)

ELECTRICAL EQUIPMENT (SWITCHBOARD,

DISTRIBUTION PANEL)

SPECIAL CABINET

TRANSFORMER

DISCONNECT SWITCH

VARIABLE FREQUENCY DRIVE

RELAY

RECEPTACLE ON DROP CORD (DUPLEX SHOWN)

RECEPTACLE ON CORD REEL (DUPLEX SHOWN)

J

BUS DUCT WITH PLUG IN DISCONNECT (FUSED)

ENCLOSED CIRCUIT BREAKER

J UNDERFLOOR RACEWAY SYSTEM

FUSED DISCONNECT SWITCH

P POWER POLE

COMBINATION MOTOR STARTER

EMERGENCY POWER OFF

MX MOTOR HORSEPOWER RATED SWITCH

PUSH BUTTON

POKE-THROUGH FLOOR BOXFB

WB WALL BOX

SURFACE MOUNTED DEVICE

(J-BOX SHOWN AS EXAMPLE)

J

SEAL

A P

P R

O V

E D

B Y

D R

A W

N B

Y

IS

S

U E

D F

O R

IS

S

U E

D A

T E

P R

O J E

C T

N U

M B

E R

F

IE

L D

B O

O K

BA D E

FC G

H

BA D E FC G H

Autodesk Revit 2024Autodesk Revit 2024

/3

/2

:5 :1

P

M

A u to d e s k D o c s /I D

O T

A m e s G e n e ra to r

W O

/2

A m e s G e n e ra to r

W O

.r v t

E L E

C T

R

IC

A L

G E

N E

R A

L

IN

F O

R M

A T

IO

N

IF

C

K J B

B F

G

-0

-3

E000

ID

O

T

A M

E S

G E

N E

R A

T O

R R

E P

L A

C E

M E

N T

IO

W

A D

E P

A R

T M

E N

T O

F T

R A

N S

P O

R T

A T

IO

N

L

IN

C

O L N

W A

Y A

M E

S

IO

W

A

.7

.0

S

H

IV

E -H

A T

T E

R Y

.C O

M

EE

E01

GENERATOR CONNECTION CABINET

E02

POWER CIRCUIT

POWER CIRCUIT

LIGHTING CIRCUIT

M01

M02

PANEL EB-25

PANEL EB-27

EDP-1

SEAL

A P

P R

O V

E D

B Y

D R

A W

N B

Y

IS

S

U E

D F

O R

IS

S

U E

D A

T E

P R

O J E

C T

N U

M B

E R

F

IE

L D

B O

O K

BA D E

FC G

H

BA D E FC G H

Autodesk Revit 2024Autodesk Revit 2024

/3

/2

:5 :1

P

M

A u to d e s k D o c s /I D

O T

A m e s G e n e ra to r

W O

/2

A m e s G e n e ra to r

W O

.r v t

E L E

C T

R

IC

A L

S

IT

E P

L A

N

IF

C

K J B

B F

G

-0

-3

E100

ID

O

T

A M

E S

G E

N E

R A

T O

R R

E P

L A

C E

M E

N T

IO

W

A D

E P

A R

T M

E N

T O

F T

R A

N S

P O

R T

A T

IO

N

L

IN

C

O L N

W A

Y A

M E

S

IO

W

A

.7

.0

S

H

IV

E -H

A T

T E

R Y

.C O

M

NORTH

1" = 20'-0"A6

ELECTRICAL SITE PLAN

30'

KEYNOTES

KEY NOTE

E01 APPROXIMATE ROUTING OF NEW NATURAL GAS LINE. CONTRACTOR

SHALL DIRECT BORE FROM EXISTING METER LOCATION TO NEW

GENERATOR.

E02 REMOVE EXISTING GENERATOR FUEL MONITORING CABINET. INSTALL

GENERATOR CONNECTION CABINET AT THE TOP OF STAIR LANDING

ON CONCRETE

M01 CONTRACTOR SHALL FIELD VERIFY ROUTING TO GET NEW NATRUAL

GAS LINE TO NEW GENERATOR.

M02 EXISTING GAS METER LOCATION.

GENERATOR FUEL

MONITORING

CABINET

LOCATION FOR GENERATOR

CONNECTION CABINET

BOILER

ROOM

ELEVATOR

EQUIPMENT

JANITOR/STORAGE

WRR

MRR

SET-UP

ROOM

CONFERENCE

NORTH

EQUIPMENT

ROOM

SOUTH

EQUIPMENT

ROOM

VAULTBREAK

ROOM

TUNNEL

LOBBY

E

BOILER

ROOM

ELEVATOR

EQUIPMENT

JANITOR/STORAGE

WRR

MRR

SET-UP

ROOM

CONFERENCE

NORTH

EQUIPMENT

ROOM

SOUTH

EQUIPMENT

ROOM

VAULTBREAK

ROOM

TUNNEL

LOBBY

EDP

480V

PANEL

GENERATOR

ATS

TRANSFORMER

CAFE MDP

UTILITY DISCONNECT

ATS

CAFE DISCONNECT

U P

S

MAINTENACE

BYPASS

PANEL R

GEN-1

250 KW

313 KVA

480V 3P/4W

TRANSFORMER

LE

PANEL LE

MDP

UPS

UPS OUTPUT

PANEL

PANEL PA

E05

ELEVATOR

PANEL EB

E06 E08

E07

EXISTING GENERATOR

EXHAUST UP

2" NATURAL GAS TO

GERERATOR. SEE

SCHEMATIC

M01

M03

NOTE:

RECONNECT EXISTING CONTROLS FOR

FANS/DAMPERS ASSOCIATED WITH THE

GENERATOR SO SEQUENCE MATCHES

HOW GENERATOR OPERATES TODAY.

E12

GENERATOR

PANEL

GENERATOR

UPS

TRANSFORMER

CAFE

UTILITY DISCONNECT

ATS

CAFE DISCONNECT

MDP

EDP

U P

S

EXISTING GENERATOR

500 KW

625 KVA

480V 3P/4W

700 GAL

FUEL TANK

MDP

TRANSFORMER

LE

PANEL EB

PANEL LE

E04

PANEL PB

UPS

MAINTENACE

BYPASS PANEL R

UPS OUTPUT PANEL

SEAL

A P

P R

O V

E D

B Y

D R

A W

N B

Y

IS

S

U E

D F

O R

IS

S

U E

D A

T E

P R

O J E

C T

N U

M B

E R

F

IE

L D

B O

O K

BA D E

FC G

H

BA D E FC G H

Autodesk Revit 2024Autodesk Revit 2024

/3

/2

:5 :1

P

M

A u to d e s k D o c s /I D

O T

A m e s G e n e ra to r

W O

/2

A m e s G e n e ra to r

W O

.r v t

B A

S E

M E

N T

P L

A N

IF

C

K J B

B F

G

-0

-3

E200

ID

O

T

A M

E S

G E

N E

R A

T O

R R

E P

L A

C E

M E

N T

IO

W

A D

E P

A R

T M

E N

T O

F T

R A

N S

P O

R T

A T

IO

N

L

IN

C

O L N

W A

Y A

M E

S

IO

W

A

.7

.0

S

H

IV

E -H

A T

T E

R Y

.C O

M

NORTH

1/8" = 1'-0"E6

BASEMENT RENOVATION PLAN

12'0

NORTH

1/8" = 1'-0"B6

BASEMENT DEMOLITION PLAN

12'

KEYNOTES

KEY NOTE

E04 REMOVE EXISTING PANEL EB. PANEL TO BE REPLACE WITH NEW

PANEL. EXISTING LOADS TO BE FED FROM NEW PANEL.

E05 REUSE EXISTING 20A/3P CIRCUIT TO FEED GENERATOR HEATER AND

BATTERY CHARGER.

E06 CIRCUIT ELEVATOR TO NEW BREAKER IN EXISTING PANEL EDP.

MATCH EXISTING CONDUIT, WIRE AND BREAKER SIZE.

E07 CIRCUIT (2) POWER CIRCUITS ON FIRST FLOOR IN THE BUILDING TO

THE NORTH WEST. REFER TO E100 FOR LOCATION OF THE CIRCUITS.

COORDINATE EXACT LOCATION WITH OWNER PRIOR TO ROUGH-IN.

CIRCUIT WITH #8 CONDUCTORS.

E08 CIRCUIT (1) LIGHTING CIRCUITS ON FIRST FLOOR IN THE BUILDING TO

THE NORTH WEST. REFER TO E100 FOR LOCATION OF THE CIRCUITS.

COORDINATE EXACT LOCATION WITH OWNER PRIOR TO ROUGH-IN.

CIRCUIT WITH #10 CONDUCTORS.

E12 REMOVE EXISTING REMOTE RADIATOR FOR THE EXISTING

GENERATOR. FURNISH AND INSTALL NEW REMOTE RADIATOR FOR

THE GENERATOR. REUSE EXISTING REMOTE RADIATOR MOUNTING

BRACKET AND FAN. FURNISH AND INSTALL NEW PIPING BETWEEN

REMOTE RADIATOR AND GENERATOR.

M01 CONTRACTOR SHALL FIELD VERIFY ROUTING TO GET NEW NATRUAL

GAS LINE TO NEW GENERATOR.

M03 CONNECT NEW GENERATOR TO EXISTING EXHAUST PIPING WITH

FLEXIBLE CONNECTION PROVIDED WITH GENERATOR. MODIFY

EXISTING PIPING/INSULATION AS REQUIRED TO REMOVE EXISTING

EXHAUST AND INSTALL NEW. PIPING/INSULATION/JACKETING TO

MATCH EXISTING.

EXISTING

MDP

EXISTING

GENERATOR

PANEL

EXISTING

UTILITY

DISCONNECT

ATS

EXISTING

GENERATOR

ATS

GEN-1

GENERATOR

CONNECTION

CABINET

FEEDER SCHEDULE

ALL FEEDERS TYPE THHN/THWN-2 ALUMINUM UNLESS NOTED OTHERWISE

4-500KCIM, 2#2G, 3" CA

TAG FEEDER, GROUND, AND CONDUIT SIZE AMPS

400A

A

E09

NEW GAS SERVICE ENTRANCE (2 PSI)

CONTRACTOR TO COORD REQUIREMENTS WITH ALLIANT

ENERGY. CONTRACTOR SHALL BE RESPONSIBLE FOR

FILING AND PAYING ALL UTILITY FEES FOR NEW

SERVICE/METER INSTALLATION

METER

ALL PRESSURE REGULATORS SHALL HAVE

RELIEF VENT PIPING ROUTED TO A SAFE

OUTDOOR LOCATION

(OR ARE RATED NOT TO BE VENTED)

NATURAL GAS METER

UTILITY PROVIDED REGULATOR. ALL REGULATORS

DOWNSTREAM FROM HERE SHALL BE CONTRACTOR

PROVIDED

LOAD ON EXISTING METER IS UNKNOWN.

CONTRACTOR SHALL VERIFY CONNECTED

LOAD AND COORDINATE WITH UTILITY

COMPANY FOR NEW METER SIZING

1 1/4"

RECONNECT TO

EXISTING GAS

PIPING

INSTALL/SET REGULATOR TO

EXISTING SERVICE PRESSURE

SURVING THE BUIDLING

2"

INSTALL PRESSURE REDUCING REGULATOR LEAVING

APPROX. 10' BETWEEN REGULATOR AND GENERATOR

AND OVERSIZE PIPE ON LOW PRESSURE SIDE OF

REGULATOR ACCORDING TO GENERATOR'S WRITTEN

INSTRUCTIONS.

CONNECT TO NEW GENERATOR

100% LOAD = 3180 CFH @ 7-11" WC

PER GENERAC USE 1.5X FOR

SUPPLY SIZING: 4770 CFH

SEAL

A P

P R

O V

E D

B Y

D R

A W

N B

Y

IS

S

U E

D F

O R

IS

S

U E

D A

T E

P R

O J E

C T

N U

M B

E R

F

IE

L D

B O

O K

BA D E

FC G

H

BA D E FC G H

Autodesk Revit 2024Autodesk Revit 2024

/3

/2

:5 :1

P

M

A u to d e s k D o c s /I D

O T

A m e s G e n e ra to r

W O

/2

A m e s G e n e ra to r

W O

.r v t

E L E

C T

R

IC

A L

O N

S C

H E

D U

L E

S

IF

C

K J B

B F

G

-0

-3

E300

ID

O

T

A M

E S

G E

N E

R A

T O

R R

E P

L A

C E

M E

N T

IO

W

A D

E P

A R

T M

E N

T O

F T

R A

N S

P O

R T

A T

IO

N

L

IN

C

O L N

W A

Y A

M E

S

IO

W

A

.7

.0

S

H

IV

E -H

A T

T E

R Y

.C O

M

NOT TO SCALEA6

ELECTRICAL ONE-LINE DIAGRAM

NOTES:

ESTIMATED DEMAND CURRENT: 0.0 A

CONNECTED CURRENT: 0.0 A

ESTIMATED DEMAND: 0.0 VA

SPEC 0 VA 0% 0 VA CONNECTED LOAD: 0.0 VA

LOAD CLASSIFICATION

CONNECTED

LOAD (VA)

DEMAND FACTOR

ESTIMATED

DEMAND (VA)

PANEL TOTALS

TOTAL AMPS: 0.0 A 0.0 A 0.0 A

TOTAL LOAD: 0.0 VA 0.0 VA 0.0 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 0.0 / 0.0 30

POWER CIRCUIT 1 20 A 27 0.0 / 0.0 28

POWER CIRCUIT 1 20 A 25 0.0 / 0.0 26

20 A 3 -- EXISTING LOAD

EXISTING LOAD -- 1 20 A 23 0.0 / 0.0 24 20 A 1 -- EXISTING LOAD

EXISTING LOAD -- 1 20 A 21 0.0 / 0.0 22 20 A 1 -- EXISTING LOAD

EXISTING LOAD -- 1 20 A 19 0.0 / 0.0 20 20 A 1 -- EXISTING LOAD

EXISTING LOAD -- 1 20 A 17 0.0 / 0.0 18 20 A 1 -- EXISTING LOAD

EXISTING LOAD -- 1 20 A 15 0.0 / 0.0 16 20 A 1 -- EXISTING LOAD

EXISTING LOAD -- 1 20 A 13 0.0 / 0.0 14 20 A 1 -- EXISTING LOAD

EXISTING LOAD -- 1 20 A 11 0.0 / 0.0 12 20 A 1 -- EXISTING LOAD

EXISTING LOAD -- 1 20 A 9 0.0 / 0.0 10 20 A 1 -- EXISTING LOAD

EXISTING LOAD -- 1 20 A 7 0.0 / 0.0 8 20 A 1 -- EXISTING LOAD

EXISTING LOAD -- 1 20 A 5 0.0 / 0.0 6 20 A 1 -- EXISTING LOAD

EXISTING LOAD -- 1 20 A 3 0.0 / 0.0 4 20 A 1 -- EXISTING LOAD

EXISTING LOAD -- 1 20 A 1 0.0 / 0.0 2 20 A 1 -- EXISTING LOAD

L O

A D

N O

T E

P O

L E

B K

R

C K

T

A B C

C K

T

B K

R

P O

L E

N O

T E

L O

A D

FED FROM: FEED:

ROOM: ENCLOSURE: NEMA 1

MOUNTING: SURFACE

PANEL EB

208Y/120 3 4 100 AMPS 70 A

22,000 AMPS

SYMMETRICAL

BRANCH PANEL NAME VOLTAGE PHASE WIRE BUS SIZE MAIN OCP AIC RATING

KEYNOTES

KEY NOTE

E09 GENERATOR CONNECTION CABINET TO BE TRYSTAR TMTS-1 OR

EQUAL. NEMA 3R, 400A, 3P 4W, 480 VOLT.

012" = 1'-0"A3

NATURAL GAS SCHEMATIC

1.5"

-L

IN

E

S