PLANS.pdf
PDF 2 MB Posted
- Attached to
- Ames Generator Replacement
- Solicitation number
- 645-DOTRFB-3180-2027
- Issued by
- Story County, Iowa
About this file
Summary
This document comprises electrical engineering plans and specifications prepared by the Iowa Department of Transportation for the Ames Generator Replacement project located at 800 Lincoln Way, Ames, Iowa 50010 (Project Number 2240014950). The plans include a cover sheet, electrical general information, electrical site plan, basement plan, and electrical one-line diagram with schedules. The project involves removing an existing 500 kW, 625 kVA generator and installing a new 250 kW, 313 kVA generator with associated infrastructure modifications, including installation of a new natural gas line and generator connection cabinet. Work is to comply with the National Electrical Code and all applicable state and local codes. The contractor is responsible for all labor, materials, permits, inspections, and equipment necessary for a complete and operational system. All work must be coordinated with other trades, and the contractor shall maintain daily site cleanliness and follow specifications for demolition, fire-rated wall penetrations, electrical panel updates, and system coordination with existing fire alarm, security, and communication systems.
The contract requires the contractor to provide a typed updated circuit directory card for all affected electrical panels and properly indicate spare breakers. Key electrical modifications include reusing an existing 20-ampere, three-phase circuit for the generator heater and battery charger; rerouting circuits from the existing panel to a new panel; and coordinating new power and lighting circuits from the first floor of an adjacent building. The natural gas service requires contractor coordination with Alliant Energy for new meter installation and sizing, with the contractor responsible for all utility fees. The generator specifications indicate a 100 percent load demand of 3,180 cubic feet per hour at 7-11 inches of water column pressure, with supply sizing calculated at 4,770 cubic feet per hour. A Trystar TMTS-1 or equivalent generator connection cabinet rated at 400 amperes, three-phase, four-wire at 480 volts and NEMA 3R enclosure is required. The engineer will conduct periodic site observations to verify work compliance with contract documents, though this observation is not continuous or exhaustive.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1463661-event.pdf | ||
| PROJECT MANUAL.pdf | ||
| A201-2017 Template.pdf | ||
| A101-2017 - for RFB FINAL.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SEAL
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2024Autodesk Revit 2024
/3
/2
:5 :1
P
M
A u to d e s k D o c s /I D
O T
A m e s G e n e ra to r
W O
/2
A m e s G e n e ra to r
W O
.r v t
IF
C
K J B
B F
G
-0
-3
G000
ID
O
T
A M
E S
G E
N E
R A
T O
R R
E P
L A
C E
M E
N T
IO
W
A D
E P
A R
T M
E N
T O
F T
R A
N S
P O
R T
A T
IO
N
L
IN
C
O L N
W A
Y A
M E
S
IO
W
A
.7
.0
S
H
IV
E -H
A T
T E
R Y
.C O
M
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
PROJECT
LOCATION
C O
V E
R S
H E
E T
AMES GENERATOR REPLACMENT
800 Lincoln Way
Ames, IA 50010Ames, IA 50010
PROJECT:2240014950
SHEET LIST
G000 COVER SHEET
E000 E100 E200 E300
ELECTRICAL GENERAL INFORMATION
ELECTRICAL SITE PLAN
BASEMENT PLAN
ELECTRICAL ONE-LINE & SCHEDULES
PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL:
PRINTED OR TYPED NAME
SIGNATURE
MY LICENSE RENEWAL DATE IS DECEMBER 31,
DATE
LICENSE NUMBER
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS
OF THE STATE OF IOWA.
Kevin J. Bruxvoort
E-SHEETS
19927
ELECTRICAL ENGINEER
LINCOLN WAY
S G
R A
N D
A V
E
1. ALL WORK SHALL BE IN CONFORMANCE WITH THE NATIONAL
ELECTRICAL CODE - LATEST EDITION ADOPTED BY THE STATE,
THE STATE AMENDMENTS, LOCAL/MUNICIPAL CODES AND
ORDINANCES, AND THE AUTHORITY HAVING JURISDICTION.
THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE
WITH THE ADAAG (AMERICANS WITH DISABILITIES ACT
ACCESSIBILITY GUIDELINES).
2. IT IS THE INTENT OF THESE DOCUMENTS TO COMPLY WITH
THE APPLICABLE CODES. WHERE DISCREPANCIES OCCUR,
NOTIFY THE ENGINEER/ARCHITECT IN WRITING FOR
INTERPRETATION. CORRECT ANY INSTALLATION THAT FAILS
TO COMPLY WITH THE CODES AND STANDARDS AT NO
ADDITIONAL COST TO THE OWNER.
3. CONTRACTOR SHALL PROVIDE ALL WORK NECESSARY
INCLUDING ALL LABOR, MATERIALS, PERMITS, TAXES, FEES,
INSPECTIONS, HARDWARE, AND COST FOR INSTALLATION FOR
A COMPLETE AND OPERATIONAL SYSTEM.
4. ALL MATERIALS FURNISHED BY THE CONTRACTOR SHALL BE
NEW, COMPLETE WITH MANUFACTURER’S GUARANTEE OR
WARRANTY AND SHALL BE LISTED BY A NATIONALLY
RECOGNIZED TESTING LABORATORY (NRTL).
5. COORDINATE ELECTRICAL INSTALLATION WITH ALL TRADES
PRIOR TO INSTALLATION. IF ELECTRICAL WORK INSTALLED
INTERFERES WITH OTHER TRADES AFTER INSTALLATION, THE
CONTRACTOR SHALL MAKE ALL NECESSARY CHANGES TO
CORRECT THE CONDITION AT NO ADDITIONAL COST TO THE
OWNER.
6. ALL ELECTRICAL PANELS WITH ANY BRANCH CIRCUIT/LOAD
REVISIONS (DEMOLITION OR NEW WORK) SHALL HAVE A NEW
TYPED UPDATED CIRCUIT DIRECTORY CARD INSTALLED INSIDE
THE DOOR OF THE ELECTRICAL PANEL. THE CONTRACTOR
SHALL VERIFY THAT ALL UNUSED CIRCUIT BREAKERS ARE
TURNED ‘OFF’ AND PROPERLY INDICATED AS ‘SPARE’ ON THE
NEW CIRCUIT DIRECTORY CARD. THE CONTRACTOR SHALL
INSTALL FILLER PLATES WHERE BREAKERS ARE REMOVED AS
PART OF THIS PROJECT OR HAVE BEEN REMOVED
PREVIOUSLY.
7. NO ENERGIZED CONDUCTORS SHALL BE EXPOSED AT
ANYTIME EXCEPT WHEN THE IMMEDIATE AREA IS UNDER THE
SUPERVISION OF A QUALIFIED ELECTRICIAN.
8. WHERE CONDUIT IS SURFACE MOUNTED TO A WALL AND RUN
VERTICALLY DOWN TO A SWITCH/OUTLET BOX, UTILIZE 1-HOLE
OR 2-HOLE CONDUIT STRAPS.
9. PENETRATIONS THROUGH FIRE RATED WALLS BY DIVISION 26
CONTRACTOR SHALL BE SEALED WITH APPROPRIATE FIRE
PROOFING MATERIAL TO RESTORE FIRE RATING.
10. THE CONTRACTOR SHALL KEEP THE WORK AREA CLEAN OF
ALL DEBRIS ON A DAILY BASIS. ALL NEW MATERIALS AWAITING
INSTALLATION SHALL BE KEPT IN AREAS DESIGNATED BY THE
OWNER.
11. THESE DRAWINGS SHALL NOT BE SCALED TO OBTAIN
DIMENSIONS. IF THE DIMENSIONS CANNOT BE DETERMINED
BY THE INFORMATION GIVEN, CONTRACTOR SHALL CONTACT
THE ENGINEER FOR ADDITIONAL INFORMATION.
12. PERIODIC SITE OBSERVATION BY THE ENGINEER IS SOLELY
FOR THE PURPOSE OF DETERMINING IF THE WORK OF THE
CONTRACTOR IS PROCEEDING IN ACCORDANCE WITH THE
CONTRACT DOCUMENTS. THIS LIMITED SITE OBSERVATION
SHOULD NOT BE CONSTRUED AS EXHAUSTIVE OR
CONTINUOUS TO CHECK THE QUALITY OR QUANTITY OF THE
WORK, BUT RATHER PERIODIC IN AN EFFORT TO GUARD THE
OWNER AGAINST DEFECTS OR DEFICIENCIES IN THE WORK OF
THE CONTRACTOR.
13. THE INFORMATION CONTAINED ON THE ELECTRICAL
DRAWINGS IS IN ITSELF INCOMPLETE AND VOID UNLESS USED
IN CONJUNCTION WITH ALL OTHER DISCIPLINE DRAWINGS,
THE SPECIFICATIONS, TRADE PRACTICES, OR APPLICABLE
STANDARDS, CODES, ETC., AND SHALL BE CONSIDERED THE
CONTRACT DOCUMENTS AND WITH ALL THEREIN BY
REFERENCE, WHICH THE CONTRACTOR CERTIFIES
KNOWLEDGE OF BY SIGNING THE CONTRACT.
14. CONTRACTOR IS TO ASSUME FULL RESPONSIBILITY,
UNRELIEVED BY REVIEW OF SHOP DRAWINGS OR PERIODIC
OBSERVATION OF CONSTRUCTION, FOR COMPLIANCE WITH
THE CONTRACT DOCUMENTS, FOR DIMENSIONS TO BE
CONFIRMED AND CORRELATED ON THE JOB SITE AND
BETWEEN INDIVIDUAL DRAWINGS OR SETS OF DRAWINGS FOR
FABRICATION PROCESSES AND CONSTRUCTION TECHNIQUES
(INCLUDING EXCAVATION, SHORING, SCAFFOLDING, BRACING,
ERECTION, FORM WORK, ETC.), FOR COORDINATION OF THE
VARIOUS TRADES, AND FOR SAFE CONDITIONS ON THE JOB
SITE. VARIATIONS IN FIELD CONDITIONS RELATIVE TO THE
CONTRACT DOCUMENTS SHALL BE REPORTED TO THE
ENGINEER AS SOON AS THEY ARE FOUND. WORK SHALL NOT
PROGRESS UNTIL WRITTEN PERMISSION FROM THE ENGINEER
IS OBTAINED.
ELECTRICAL
1. LIGHT LINES INDICATE EXISTING WALLS AND EQUIPMENT TO
REMAIN. DASHED LINES INDICATE WALLS, EQUIPMENT, AND
ELECTRICAL ITEMS TO BE REMOVED.
2. COORDINATE PATCHING REQUIREMENTS FOR UNUSED
OPENINGS WITH THE GENERAL CONTRACTOR. GENERAL
CONTRACTOR SHALL PATCH ALL UNUSED OPENINGS.
PATCHWORK SHALL MATCH MATERIALS, FINISH, AND TEXTURE
OF ADJACENT SURFACES.
3. FIRE ALARM - REMOVE EXISTING CEILING MOUNTED DEVICES
TO PERMIT REMOVAL OF CEILING. WALL MOUNTED
NOTIFICATION DEVICES SHALL BE DEMOLISHED. COORDINATE
WORK WITH PROJECT PHASING TO MAINTAIN FIRE ALARM
SYSTEM PROTECTION OF SPACES AT ALL TIMES. INCLUDE
COSTS OF ALL TEMPORARY DEVICES IN THE BID.
4. SECURITY/SURVEILLANCE - EXISTING DEVICES TO BE
REMOVED BY SYSTEMS VENDOR. CONTRACTOR SHALL
REMOVE ASSOCIATED CABLING, ROUGH-IN, AND POWER
WIRING. PRIOR TO ANY DEMOLITION IDENTIFY AND PROTECT
CABLING REQUIRED TO MAINTAIN THE SYSTEM IN AREAS THAT
WILL NOT BE REMODELED.
5. COORDINATE DISPOSAL OF ALL ITEMS NOT REQUESTED AS
SALVAGE BY THE OWNER.
6. TELEPHONE AND DATA HORIZONTAL CABLING SHALL BE
REMOVED COMPLETELY BACK TO THE FIRST REMAINING
DISTRIBUTION FRAME. PROTECT FIBER OPTIC AND COPPER
TRUNK CABLING SERVING DISTRIBUTION RACKS.
7. LIGHTING FIXTURES AND CONTROLS - REMOVE EXISTING
LIGHT FIXTURES, WALL SWITCHES, OCCUPANCY SENSORS,
AND ASSOCIATED WIRING. VERIFY AND MAINTAIN
CONNECTION TO EXISTING LIGHTING THAT WILL NOT BE
REMOVED BUT ARE ON COMMON CIRCUITS WITH ITEMS TO BE
REMOVED.
8. DISCONNECT OUTLETS, WIRING, AND OTHER NOTED
EQUIPMENT TO PERMIT DEMOLITION OF WALLS. VERIFY AND
MAINTAIN CONNECTION TO EXISTING OUTLETS THAT WILL NOT
BE REMOVED BUT ARE ON COMMON CIRCUITS WITH ITEMS TO
BE REMOVED.
9. DRAWINGS DO NOT IDENTIFY ALL OUTLETS, SWITCHES,
CABLING, OR EQUIPMENT TO BE REMOVED. CONTRACTOR
SHALL BECOME FAMILIAR WITH THE SITE PRIOR TO BIDDING
AND INCLUDE LABOR AND MATERIAL NECESSARY FOR
REQUIRED DEMOLITION IN THEIR BID.
10. WIRING SHALL BE REMOVED BACK TO SERVING PANEL.
INSTALLATION OF NEW CONDUCTORS IN EXISTING CONDUITS
WILL BE PERMITTED AS DESCRIBED IN THE DIVISION 26
SPECIFICATIONS.
11. HVAC EQUIPMENT NOTED FOR REMOVAL IS FOR REFERENCE
ONLY. THE ELECTRICAL CONTRACTOR SHALL REVIEW THE
MECHANICAL SYSTEMS DEMOLITION PLANS AND INCLUDE ALL
LABOR AND MATERIAL NECESSARY TO FACILITATE REMOVAL
OF EQUIPMENT AS SHOWN ON THOSE DRAWINGS. THIS SHALL
INCLUDE ALL ITEMS NOTED ON EITHER THE PLUMBING OR
MECHANICAL SERIES OF DRAWINGS.
ELECTRICAL DEMOLITION
ELECTRICAL ABBREVIATIONS
A
A
AC
ACB
AF
AFF
AL
ALT
AM
AS
AT
APPROX
ATC
ATS
AUTO
AUX
AWG
B
BAS
BD
BRKR
BLDG
B/M
BUZ
C
C
CAB
CB
CCTV
CKT
CL
CLG
COMM
CONN
CONC
COND
CONTR
CP
CPT
CR
CT
CU
D
DC
DIA
DIAG
DIM
DISC
DIV
DN
DP
DT
DWG
E
EC
EL
ELEC
EMER
EMT
ENG
EPO
ETM
EWC
EXH
EXIST
F
F
FA
FACP
FC
FDR
FF
FHP
FL
FLEX
FLR
FLUOR
FREQ
AMPERE
ABOVE COUNTER/ALTERNATING CURRENT
AIR CIRCUIT BREAKER
AMPERE RATING OF FUSE
ABOVE FINISHED FLOOR
ALUMINUM
ALTERNATE
AMMETER
AMMETER SWITCH
AMPERE TRIP RATING
APPROXIMATELY
AUTOMATIC TEMPERATURE CONTROL
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AUXILIARY
AMERICAN WIRE GAUGE
BUILDING AUTOMATION SYSTEM
BUS DUCT
BREAKER
BUILDING
BILL OF MATERIALS
BUZZER
CONTRACTOR
CABINET
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CENTERLINE
CEILING
COMMUNICATIONS CONNECT, CONNECTED,
CONNECTOR
CONCRETE
CONDUCTOR
CONTRACTOR
CONTROL PANEL
CONTROL POWER TRANSFORMER
CONTROL RELAY
CURRENT TRANSFORMER
COPPER
DIRECT CURRENT
DIAMETER
DIAGRAM
DIMMER CONTROL
DISCONNECT
DIVISION
DOWN
DOUBLE POLE
DOUBLE THROW
DRAWING
ELECTRICAL CONTRACTOR
ELEVATION
ELECTRICAL
EMERGENCY
ELECTRICAL METALLIC TUBING
ENGINEER
EMERGENCY POWER OFF
ELAPSED (RUN) TIME METER
ELECTRIC WATER COOLER
EXHAUST
EXISTING
FUSE
FIRE ALARM
FIRE ALARM CONTROL PANEL
FOOTCANDLE
FEEDER
FURNITURE FEED
FRACTIONAL HORSEPOWER
FLOODLIGHT
FLEXIBLE, FLEXIBLE CONDUIT
FLOOR
FLUORESCENT
FREQUENCY
G
GC
GEC
GEN
GFI
GFP
GND
GR
GW
H
HGT
HH
HID
HP
HPS
HTR
HZ
I
IMC
INCAND
INTCONN
J
JB
JCT
K
K
KCMIL
KV
KVA
KVAR
KW
KWH
L
LG
LIM
LPS
LTG
LV
LVSS
M
MAN
MATL
MC
MCC
MCP
MFR
MH
MIC
MLO
MTG
MTR
MTS
MVA
MVAR
MW
MWH
N
NC
NF
NIC
NEC
NEMA
NO
NTS
O
OCB
OPR
OL
GENERAL CONTRACTOR
GROUNDING ELECTRODE CONDUCTOR
GENERATOR
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT PROTECTOR
GROUND, GROUNDING CONDUCTOR
GROUND ROD
GROUND WELL
HEIGHT
HANDHOLE
HIGH INTENSITY DISCHARGE
HORSEPOWER
HIGH PRESSURE SODIUM
HEATER
HERTZ, FREQUENCY IN CYCLES PER SECOND
INTERMEDIATE METALLIC CONDUIT
INCANDESCENT
INTERCONNECTION
JUNCTION BOX
JUNCTION
KEY OPERATED
THOUSAND CIRCULAR MILS
KILOVOLT
KILOVOLT-AMPERE
KILOVOLT-AMPERE REACTIVE
KILOWATT
KILOWATT-HOUR
LENGTH
LIMIT
LOW PRESSURE SODIUM
LIGHT, LIGHTING
LOW VOLTAGE
LOW VOLTAGE SURGE SUPPRESSION
MANUAL
MATERIAL
MECHANICAL CONTRACTOR
MOTOR CONTROL CENTER
MOTOR CIRCUIT PROTECTOR
MANUFACTURER
MANHOLE
MICROPHONE
MAIN LUGS ONLY
MOUNT, MOUNTED, MOUNTING
MOTOR
MANUAL TRANSFER SWITCH
MEGAVOLT-AMPERE
MEGAVOLT-AMPERE REACTIVE
MEGAWATT
MEGAWATT-HOUR
NORMALLY CLOSED
NON-FUSED
NOT IN CONTRACT
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NORMALLY OPEN
NOT TO SCALE
OIL CIRCUIT BREAKER
OPERATOR, OPERATED
THERMAL OVERLOAD PROTECTION
P
P
PB
PC
PF
PFM
PNL
PRI
PS
PT
PVC
PWR
R
R
RC
RECPT
REF
REQD
RGS
S
SA
SCHD
SCHM
SP
SPKR
ST
STA
STBY
SUBSTA
SW
SWBD
SWGR
SYNC
SYS
T
T/
TB
TC
TCC
TDCD
TDCE
TDOD
TDOE
TEL
TEMP
TERM
TSTAT
TV
TYP
U
UG
UNO
UNG
UPS
V
V
VA
VAR
VERT
VFD
VM
VS
W
W W/ W/O
WH
WP
X
XDCR
XFMR
XFR
XMIT
XP
PILOT
LIGHT PUSHBUTTON
PHOTOCELL
POWER FACTOR
POWER FACTOR METER
PANEL
PRIMARY
PRESSURE SWITCH
POTENTIAL TRANSFORMER
POLVINYLCHLORIDE, PVC CONDUIT
POWER
RELAY
REMOTE CONTROL
RECEPTACLE
REFER, REFERENCE
REQUIRED
RIGID GALVANIZED STEEL CONDUIT
SURGE ARRESTER
SCHEDULE
SCHEMATIC
SINGLE POLE
LOUDSPEAKER
SINGLE THROW
STATION
STANDBY
SUBSTATION
SWITCH
SWITCHBOARD
SWITCHGEAR
SYNCHRONIZE, (ING), (ACTION)
SYSTEM
TOP OF
TERMINAL BOARD
TIMECLOCK
TEMPERATURE CONTROL CONTRACTOR
TIME DELAY CLOSE ON DENERGIZATION
TIME DELAY CLOSE ON ENERGIZATION
TIME DELAY OPEN ON DENERGIZATION
TIME DELAY OPEN ON ENERGIZATION
TELEPHONE
TEMPERATURE
TERMINAL
THERMOSTAT
TELEVISION
TYPICAL
UNDERGROUND
UNLESS NOTED OTHERWISE
UNGROUNDED
UNINTERRUPTIBLE POWER SUPPLY
VOLTS
VOLT-AMPERE
VOLT-AMPERE REACTIVE
VERTICAL
VARIABLE FREQUENCY DRIVE
VOLTMETER
VOLTMETER SWITCH
WATTS
WITH
WITHOUT
WATT-HOUR
WEATHERPROOF
TRANSDUCER
TRANSFORMER
TRANSFER
TRANSMIT, TRANSMITTER
EXPLOSION PROOF
UC
OS
LS
S
FS
TS
FB
B
L
L S
FACP
FARP
NAC
EVAC
FTR
FSCP
HVA
TCVR
T R
DR
FR
ARCR
ASCP
ARCM
E
HH
J
TV
N
NCM
NC ANNUN
NCC
K
D
OS
M
T
SURFACE CYLINDER
RECESSED DOWNLIGHT
WALL MOUNTED LIGHT
FLOOD LIGHT
POLE MOUNTED LIGHT
SURFACE LIGHT
SUSPENDED LINEAR
(+ DENOTES POWERED FROM)
RECESSED LINEAR
INDUSTRIAL STRIP LIGHT
TRACK AND TRACK LIGHT
EMERGENCY LIGHT
EXIT SIGN
LIGHT FIXTURE ON EMERGENCY CIRCUIT
SINGLE POLE SWITCH
3-WAY SWITCH
4-WAY SWITCH
KEYED SWITCH
DIMMER SWITCH
OCCUPANCY SENSOR SWITCH
MOMENTARY CONTACT SWITCH
TIMER SWITCH
PUSH BUTTON
DURESS PUSH BUTTON, UNDER COUNTER
DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
FLOOR BOX
DUPLEX RECEPTACLE - CEILING MOUNTED
CLOCK
OCCUPANCY SENSOR
LIGHT LEVEL SENSOR
EXTERIOR PHOTOCELL
SECURITY CAMERA
CONDUIT CONCEALED IN WALL OR OVERHEAD
CONDUIT CONCEALED BELOW FLOOR
CONDUIT TRANSITION UP
CONDUIT TRANSITION DOWN
CONDUIT STUBBED OUT
BRANCH CIRCUIT HOME RUN
CABLE TRAY (TYPE DENOTED)
CONDUIT SLEEVE (SIZE DENOTED)
VOICE/DATA OUTLET (WALL OR CEILING MOUNT)
# - QUANTITY OF RJ-45 JACKS/CABLES.
ONE, UNLESS SHOWN OTHERWISE
W - DENOTES WALL PHONE
WIRELESS ACCESS POINT (WALL OR CEILING MOUNT)
# - QUANTITY OF RJ-45 JACKS/CABLES.
ONE, UNLESS SHOWN OTHERWISE
TELEVISION OUTLET (WALL OR CEILING MOUNT)
SPEAKER (WALL OR CEILING MOUNT)
INTERCOM STATION
KEYNOTE (SEE SCHEDULE)E#
SPRINKLER FLOW SWITCH
SPRINKLER VALVE TAMPER SWITCH
DUCT SMOKE DETECTOR
LINEAR HEAT DETECTOR
REMOTE TEST/STATUS STATION
AUDIO NOTIFICATION DEVICE - CEILING MOUNTED
B = BELL
C = CHIME
H = HORN
S = SPEAKER
AUDIO NOTIFICATION DEVICE - WALL MOUNTED
B = BELL
C = CHIME
H = HORN
S = SPEAKER
VISUAL NOTIFICATION DEVICE - CEILING MOUNTED
VISUAL NOTIFICATION DEVICE - WALL MOUNTED
AUDIO/VISUAL NOTIFICATION DEVICE -
CEILING MOUNTED
B = BELL
C = CHIME
H = HORN
S = SPEAKER
AUDIO/VISUAL NOTIFICATION DEVICE -
WALL MOUNTED
B = BELL
C = CHIME
H = HORN
S = SPEAKER
FIRE ALARM CONTROL PANEL
FIRE ALARM RELAY PANEL
NAC POWER SUPPLY
VOICE EVACUATION PANEL
FIRE ALARM TRANSPONDER
FIRE SUPPRESSION CONTROL PANEL
HVAC PRESSURIZATION PANEL
FIRE ALARM TRANSCEIVER PANEL
BEAM SMOKE DETECTOR
T = TRANSMITTER/RECEIVER
R = REFLECTOR
DOOR HOLDER/HOLD OPEN
SMOKE DAMPER RELEASE
FIRE ALARM SHUT DOWN RELAY
SMOKE DETECTOR
HEAT DETECTOR
AREA OF REFUGE - CALL STATION
AIR SAMPLING CONTROL PANEL
AREA OF REFUGE - MASTER
FIREFIGHTER PHONE
EMERGENCY EXIT SIGN
SPECIAL RECEPTACLE
(CEILING, WALL, AND FLOOR MOUNTED)
BOLLARD
DIRECT POWER CONNECTION -
WALL AND EQUIPMENT
HANDHOLE
JUNCTION BOX
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
PENDANT LIGHT
SIMPLEX RECEPTACLE
SPLIT DUPLEX RECEPTACLE
DUPLEX RECEPTACLE ON EMERGENCY CIRCUIT
DUPLEX RECEPTACLE PLUG LOAD CONTROL
DOUBLE DUPLEX RECEPTACLE ON EMERGENCY CIRCUIT
MOTION DETECTOR (TYPE DENOTED)
DOOR SIGNAL - APARTMENT UNIT
BUZZER
D
BELL
CHIME
NURSE CALL SINGLE PATIENT STATION
37 PIN BED INTERFACE RECEPTACLE
AUXILIARY ALARM STATION, TWO JACK
EMERGENCY PULL CORD STATION
STAFF TERMINAL, TOUCHSCREEN
DUTY STATION
NURSE CALL DOME LIGHT
NURSE CALL MASTER STATION
NURSE CALL EQUIPMENT CABINET
NURSE CALL ANNUNCIATOR PANEL
STAFF ASSIST
CODE BLUE STATION
NURSE CALL STAFF STATION
CARD READER
SYMBOL DESCRIPTION
LIGHTING/CONTROLS
GENERAL POWER
COMMUNICATION/DATA
SECURITY
NURSE CALL
FIRE ALARM
ELECTRICAL SYMBOLS LEGEND
0000 SPECIALTY EQUIPMENT TAG
PL SINGLE POLE SWITCH WITH PILOT LIGHT
DOUBLE DUPLEX RECEPTACLE PLUG LOAD CONTROL
C
EXAMPLE RECEPTACLE TAG
##" - MOUNTING HEIGHT AS INDICATED.
IF OMITTED, 18" OR ABOVE COUNTER
XX - INDICATES RECEPTACLE CONFIGURATION:
GROUND CONNECTION - EXOTHERMIC WELD
GROUND CONNECTION TO STEEL OR STRUCTURE
STATIC GROUND RECEPTACLE (TYPE DENOTED)
GROUND ROD (PLAN VIEW)
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION CONDUCTOR SPLICE
SYMBOL DESCRIPTION
GROUNDING
XX
AC
GFI
HZ
IG
OC
USB
WP
XP
ABOVE COUNTER (COORDINATE HEIGHT)
GROUND FAULT CIRCUIT INTERRUPTER
HORIZONTALLY MOUNTED
ISOLATED GROUND
OCCUPANCY CONTROLLED
INTEGRAL USB CHARGER
WEATHERPROOF
EXPLOSION PROOF
XX
XX
FIRE ALARM - CONTINUED
MANUAL PULL STATION
GROUND BAR
ANN FIRE ALARM REMOTE ANNUNCIATOR
KEYPAD
REQUEST TO EXIT
SURFACE MOUNTED RECEPTACLE, VARIES PER TYPE
F
L S
L
B
P
RX
J
E
N
B
A
S
D
T
DH
TV
S
E
J
IC
CR
IR
MD
C
DESCRIPTIONSYMBOL
P C
WT WALL MOUNTED TOUCHPAD
# LIGHTING CONTROL DENOTATION
TROFFER LIGHT
POWER - CONTINUED
R
VFD
SURFACE RACEWAY
BRANCH PANEL WITH CLEARANCE
(SURFACE OR RECESS MOUNTED)
ELECTRICAL EQUIPMENT (SWITCHBOARD,
DISTRIBUTION PANEL)
SPECIAL CABINET
TRANSFORMER
DISCONNECT SWITCH
VARIABLE FREQUENCY DRIVE
RELAY
RECEPTACLE ON DROP CORD (DUPLEX SHOWN)
RECEPTACLE ON CORD REEL (DUPLEX SHOWN)
J
BUS DUCT WITH PLUG IN DISCONNECT (FUSED)
ENCLOSED CIRCUIT BREAKER
J UNDERFLOOR RACEWAY SYSTEM
FUSED DISCONNECT SWITCH
P POWER POLE
COMBINATION MOTOR STARTER
EMERGENCY POWER OFF
MX MOTOR HORSEPOWER RATED SWITCH
PUSH BUTTON
POKE-THROUGH FLOOR BOXFB
WB WALL BOX
SURFACE MOUNTED DEVICE
(J-BOX SHOWN AS EXAMPLE)
J
SEAL
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2024Autodesk Revit 2024
/3
/2
:5 :1
P
M
A u to d e s k D o c s /I D
O T
A m e s G e n e ra to r
W O
/2
A m e s G e n e ra to r
W O
.r v t
E L E
C T
R
IC
A L
G E
N E
R A
L
IN
F O
R M
A T
IO
N
IF
C
K J B
B F
G
-0
-3
E000
ID
O
T
A M
E S
G E
N E
R A
T O
R R
E P
L A
C E
M E
N T
IO
W
A D
E P
A R
T M
E N
T O
F T
R A
N S
P O
R T
A T
IO
N
L
IN
C
O L N
W A
Y A
M E
S
IO
W
A
.7
.0
S
H
IV
E -H
A T
T E
R Y
.C O
M
EE
E01
GENERATOR CONNECTION CABINET
E02
POWER CIRCUIT
POWER CIRCUIT
LIGHTING CIRCUIT
M01
M02
PANEL EB-25
PANEL EB-27
EDP-1
SEAL
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2024Autodesk Revit 2024
/3
/2
:5 :1
P
M
A u to d e s k D o c s /I D
O T
A m e s G e n e ra to r
W O
/2
A m e s G e n e ra to r
W O
.r v t
E L E
C T
R
IC
A L
S
IT
E P
L A
N
IF
C
K J B
B F
G
-0
-3
E100
ID
O
T
A M
E S
G E
N E
R A
T O
R R
E P
L A
C E
M E
N T
IO
W
A D
E P
A R
T M
E N
T O
F T
R A
N S
P O
R T
A T
IO
N
L
IN
C
O L N
W A
Y A
M E
S
IO
W
A
.7
.0
S
H
IV
E -H
A T
T E
R Y
.C O
M
NORTH
1" = 20'-0"A6
ELECTRICAL SITE PLAN
30'
KEYNOTES
KEY NOTE
E01 APPROXIMATE ROUTING OF NEW NATURAL GAS LINE. CONTRACTOR
SHALL DIRECT BORE FROM EXISTING METER LOCATION TO NEW
GENERATOR.
E02 REMOVE EXISTING GENERATOR FUEL MONITORING CABINET. INSTALL
GENERATOR CONNECTION CABINET AT THE TOP OF STAIR LANDING
ON CONCRETE
M01 CONTRACTOR SHALL FIELD VERIFY ROUTING TO GET NEW NATRUAL
GAS LINE TO NEW GENERATOR.
M02 EXISTING GAS METER LOCATION.
GENERATOR FUEL
MONITORING
CABINET
LOCATION FOR GENERATOR
CONNECTION CABINET
BOILER
ROOM
ELEVATOR
EQUIPMENT
JANITOR/STORAGE
WRR
MRR
SET-UP
ROOM
CONFERENCE
NORTH
EQUIPMENT
ROOM
SOUTH
EQUIPMENT
ROOM
VAULTBREAK
ROOM
TUNNEL
LOBBY
E
BOILER
ROOM
ELEVATOR
EQUIPMENT
JANITOR/STORAGE
WRR
MRR
SET-UP
ROOM
CONFERENCE
NORTH
EQUIPMENT
ROOM
SOUTH
EQUIPMENT
ROOM
VAULTBREAK
ROOM
TUNNEL
LOBBY
EDP
480V
PANEL
GENERATOR
ATS
TRANSFORMER
CAFE MDP
UTILITY DISCONNECT
ATS
CAFE DISCONNECT
U P
S
MAINTENACE
BYPASS
PANEL R
GEN-1
250 KW
313 KVA
480V 3P/4W
TRANSFORMER
LE
PANEL LE
MDP
UPS
UPS OUTPUT
PANEL
PANEL PA
E05
ELEVATOR
PANEL EB
E06 E08
E07
EXISTING GENERATOR
EXHAUST UP
2" NATURAL GAS TO
GERERATOR. SEE
SCHEMATIC
M01
M03
NOTE:
RECONNECT EXISTING CONTROLS FOR
FANS/DAMPERS ASSOCIATED WITH THE
GENERATOR SO SEQUENCE MATCHES
HOW GENERATOR OPERATES TODAY.
E12
GENERATOR
PANEL
GENERATOR
UPS
TRANSFORMER
CAFE
UTILITY DISCONNECT
ATS
CAFE DISCONNECT
MDP
EDP
U P
S
EXISTING GENERATOR
500 KW
625 KVA
480V 3P/4W
700 GAL
FUEL TANK
MDP
TRANSFORMER
LE
PANEL EB
PANEL LE
E04
PANEL PB
UPS
MAINTENACE
BYPASS PANEL R
UPS OUTPUT PANEL
SEAL
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2024Autodesk Revit 2024
/3
/2
:5 :1
P
M
A u to d e s k D o c s /I D
O T
A m e s G e n e ra to r
W O
/2
A m e s G e n e ra to r
W O
.r v t
B A
S E
M E
N T
P L
A N
IF
C
K J B
B F
G
-0
-3
E200
ID
O
T
A M
E S
G E
N E
R A
T O
R R
E P
L A
C E
M E
N T
IO
W
A D
E P
A R
T M
E N
T O
F T
R A
N S
P O
R T
A T
IO
N
L
IN
C
O L N
W A
Y A
M E
S
IO
W
A
.7
.0
S
H
IV
E -H
A T
T E
R Y
.C O
M
NORTH
1/8" = 1'-0"E6
BASEMENT RENOVATION PLAN
12'0
NORTH
1/8" = 1'-0"B6
BASEMENT DEMOLITION PLAN
12'
KEYNOTES
KEY NOTE
E04 REMOVE EXISTING PANEL EB. PANEL TO BE REPLACE WITH NEW
PANEL. EXISTING LOADS TO BE FED FROM NEW PANEL.
E05 REUSE EXISTING 20A/3P CIRCUIT TO FEED GENERATOR HEATER AND
BATTERY CHARGER.
E06 CIRCUIT ELEVATOR TO NEW BREAKER IN EXISTING PANEL EDP.
MATCH EXISTING CONDUIT, WIRE AND BREAKER SIZE.
E07 CIRCUIT (2) POWER CIRCUITS ON FIRST FLOOR IN THE BUILDING TO
THE NORTH WEST. REFER TO E100 FOR LOCATION OF THE CIRCUITS.
COORDINATE EXACT LOCATION WITH OWNER PRIOR TO ROUGH-IN.
CIRCUIT WITH #8 CONDUCTORS.
E08 CIRCUIT (1) LIGHTING CIRCUITS ON FIRST FLOOR IN THE BUILDING TO
THE NORTH WEST. REFER TO E100 FOR LOCATION OF THE CIRCUITS.
COORDINATE EXACT LOCATION WITH OWNER PRIOR TO ROUGH-IN.
CIRCUIT WITH #10 CONDUCTORS.
E12 REMOVE EXISTING REMOTE RADIATOR FOR THE EXISTING
GENERATOR. FURNISH AND INSTALL NEW REMOTE RADIATOR FOR
THE GENERATOR. REUSE EXISTING REMOTE RADIATOR MOUNTING
BRACKET AND FAN. FURNISH AND INSTALL NEW PIPING BETWEEN
REMOTE RADIATOR AND GENERATOR.
M01 CONTRACTOR SHALL FIELD VERIFY ROUTING TO GET NEW NATRUAL
GAS LINE TO NEW GENERATOR.
M03 CONNECT NEW GENERATOR TO EXISTING EXHAUST PIPING WITH
FLEXIBLE CONNECTION PROVIDED WITH GENERATOR. MODIFY
EXISTING PIPING/INSULATION AS REQUIRED TO REMOVE EXISTING
EXHAUST AND INSTALL NEW. PIPING/INSULATION/JACKETING TO
MATCH EXISTING.
EXISTING
MDP
EXISTING
GENERATOR
PANEL
EXISTING
UTILITY
DISCONNECT
ATS
EXISTING
GENERATOR
ATS
GEN-1
GENERATOR
CONNECTION
CABINET
FEEDER SCHEDULE
ALL FEEDERS TYPE THHN/THWN-2 ALUMINUM UNLESS NOTED OTHERWISE
4-500KCIM, 2#2G, 3" CA
TAG FEEDER, GROUND, AND CONDUIT SIZE AMPS
400A
A
E09
NEW GAS SERVICE ENTRANCE (2 PSI)
CONTRACTOR TO COORD REQUIREMENTS WITH ALLIANT
ENERGY. CONTRACTOR SHALL BE RESPONSIBLE FOR
FILING AND PAYING ALL UTILITY FEES FOR NEW
SERVICE/METER INSTALLATION
METER
ALL PRESSURE REGULATORS SHALL HAVE
RELIEF VENT PIPING ROUTED TO A SAFE
OUTDOOR LOCATION
(OR ARE RATED NOT TO BE VENTED)
NATURAL GAS METER
UTILITY PROVIDED REGULATOR. ALL REGULATORS
DOWNSTREAM FROM HERE SHALL BE CONTRACTOR
PROVIDED
LOAD ON EXISTING METER IS UNKNOWN.
CONTRACTOR SHALL VERIFY CONNECTED
LOAD AND COORDINATE WITH UTILITY
COMPANY FOR NEW METER SIZING
1 1/4"
RECONNECT TO
EXISTING GAS
PIPING
INSTALL/SET REGULATOR TO
EXISTING SERVICE PRESSURE
SURVING THE BUIDLING
2"
INSTALL PRESSURE REDUCING REGULATOR LEAVING
APPROX. 10' BETWEEN REGULATOR AND GENERATOR
AND OVERSIZE PIPE ON LOW PRESSURE SIDE OF
REGULATOR ACCORDING TO GENERATOR'S WRITTEN
INSTRUCTIONS.
CONNECT TO NEW GENERATOR
100% LOAD = 3180 CFH @ 7-11" WC
PER GENERAC USE 1.5X FOR
SUPPLY SIZING: 4770 CFH
SEAL
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2024Autodesk Revit 2024
/3
/2
:5 :1
P
M
A u to d e s k D o c s /I D
O T
A m e s G e n e ra to r
W O
/2
A m e s G e n e ra to r
W O
.r v t
E L E
C T
R
IC
A L
O N
S C
H E
D U
L E
S
IF
C
K J B
B F
G
-0
-3
E300
ID
O
T
A M
E S
G E
N E
R A
T O
R R
E P
L A
C E
M E
N T
IO
W
A D
E P
A R
T M
E N
T O
F T
R A
N S
P O
R T
A T
IO
N
L
IN
C
O L N
W A
Y A
M E
S
IO
W
A
.7
.0
S
H
IV
E -H
A T
T E
R Y
.C O
M
NOT TO SCALEA6
ELECTRICAL ONE-LINE DIAGRAM
NOTES:
ESTIMATED DEMAND CURRENT: 0.0 A
CONNECTED CURRENT: 0.0 A
ESTIMATED DEMAND: 0.0 VA
SPEC 0 VA 0% 0 VA CONNECTED LOAD: 0.0 VA
LOAD CLASSIFICATION
CONNECTED
LOAD (VA)
DEMAND FACTOR
ESTIMATED
DEMAND (VA)
PANEL TOTALS
TOTAL AMPS: 0.0 A 0.0 A 0.0 A
TOTAL LOAD: 0.0 VA 0.0 VA 0.0 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 0.0 / 0.0 30
POWER CIRCUIT 1 20 A 27 0.0 / 0.0 28
POWER CIRCUIT 1 20 A 25 0.0 / 0.0 26
20 A 3 -- EXISTING LOAD
EXISTING LOAD -- 1 20 A 23 0.0 / 0.0 24 20 A 1 -- EXISTING LOAD
EXISTING LOAD -- 1 20 A 21 0.0 / 0.0 22 20 A 1 -- EXISTING LOAD
EXISTING LOAD -- 1 20 A 19 0.0 / 0.0 20 20 A 1 -- EXISTING LOAD
EXISTING LOAD -- 1 20 A 17 0.0 / 0.0 18 20 A 1 -- EXISTING LOAD
EXISTING LOAD -- 1 20 A 15 0.0 / 0.0 16 20 A 1 -- EXISTING LOAD
EXISTING LOAD -- 1 20 A 13 0.0 / 0.0 14 20 A 1 -- EXISTING LOAD
EXISTING LOAD -- 1 20 A 11 0.0 / 0.0 12 20 A 1 -- EXISTING LOAD
EXISTING LOAD -- 1 20 A 9 0.0 / 0.0 10 20 A 1 -- EXISTING LOAD
EXISTING LOAD -- 1 20 A 7 0.0 / 0.0 8 20 A 1 -- EXISTING LOAD
EXISTING LOAD -- 1 20 A 5 0.0 / 0.0 6 20 A 1 -- EXISTING LOAD
EXISTING LOAD -- 1 20 A 3 0.0 / 0.0 4 20 A 1 -- EXISTING LOAD
EXISTING LOAD -- 1 20 A 1 0.0 / 0.0 2 20 A 1 -- EXISTING LOAD
L O
A D
N O
T E
P O
L E
B K
R
C K
T
A B C
C K
T
B K
R
P O
L E
N O
T E
L O
A D
FED FROM: FEED:
ROOM: ENCLOSURE: NEMA 1
MOUNTING: SURFACE
PANEL EB
208Y/120 3 4 100 AMPS 70 A
22,000 AMPS
SYMMETRICAL
BRANCH PANEL NAME VOLTAGE PHASE WIRE BUS SIZE MAIN OCP AIC RATING
KEYNOTES
KEY NOTE
E09 GENERATOR CONNECTION CABINET TO BE TRYSTAR TMTS-1 OR
EQUAL. NEMA 3R, 400A, 3P 4W, 480 VOLT.
012" = 1'-0"A3
NATURAL GAS SCHEMATIC
1.5"
-L
IN
E