Plans.pdf
PDF 14 MB Posted
- Attached to
- Project 13672. DOT D9 EVSE. Contract 25-324068
- Solicitation number
- 0000039769
- Issued by
- Inyo County, Kern County, Inyokern CDP, California
About this file
This is a 100% construction drawings document prepared for the California Department of Transportation (Caltrans) District 9 Bishop Equipment Shop Electric Vehicle Supply Equipment (EVSE) Installation project, with structural and electrical engineering support from KPFF and Goss Engineering. The project comprises the installation of EVSE infrastructure to provide power to four electric vehicle charging station (EVCS) ports within the Bishop Equipment Shop parking lot. The major work components include installation of one new 75-kilowatt-ampere transformer, one new 250-ampere panelboard, new feeders to EVCS port locations, and all associated electrical, civil, and structural work necessary to support the charging system. The project scope also includes required saw cutting, trenching, backfilling, and restoration of the affected parking lot surface. The construction drawings include site plans, power plans, electrical details, single-line diagrams, civil site plans, and structural anchorage details across 14 sheets, with construction type V-B occupancy classification and a building area of 12,800 square feet. All work must conform to the 2022 California Building Code, California Electrical Code, California Fire Code, and applicable NFPA standards, with special attention to fire-rated assemblies, through-penetration firestop systems, arc-flash hazard warnings, and third-party testing of all new feeder conductors.
The EVCS infrastructure is comprised of two dual-port pedestal-type electric vehicle charging stations—one with 19,200 volts-amperes per port and one with 12,000 volts-amperes per port—both designed for fleet-only use and not available to the general public, therefore exempt from certain Americans with Disabilities Act accessibility requirements under California Building Code Section 11B-228.3.2. The electrical vehicle charging stations will be provided, installed, and connected by the State Vendor, with the contractor responsible for providing all infrastructure necessary to support the chargers, including conduit, wiring, panelboard connections, and equipment anchorage. The project requires coordination with the existing main switchboard and includes demolition of an existing 20-ampere circuit breaker to be replaced with a new circuit breaker matching existing specifications. Special inspections are required for post-installed anchors, concrete construction verification, and structural welding in accordance with California Building Code Table 1705.2 and Table 1705.3, with the contractor responsible for providing access to work areas and designating a quality control point of contact for inspection coordination.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Project_Manual.pdf | ||
| Bid_Package_Documents.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Caltrans District 9 - Bishop Equipment Shop
EVSE Installation
100% Construction Drawings
1. THE ARRANGEMENT OF THE EQUIPMENT, ELECTRICAL DEVICES, ETC. SHOWN ON THESE DRAWINGS IS GENERAL AND IS SHOWN TO IDENTIFY THE GENERAL INTENT OF THE PROJECT. ALL DETAILS AND ARRANGEMENTS SHALL BE VERIFIED PRIOR TO THE START OF WORK. THE DRAWINGS ARE NOT INTENDED TO SHOW EXACT DIMENSIONS/LOCATIONS.
2. CODE COMPLIANCE: ALL WORK SHALL CONFORM TO BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE CODES, STANDARDS, AND ORDINANCE AS SET FORTH BY THE AUTHORITIES HAVING JURISDICTION AND THEIR LATEST ADOPTED EDITIONS (IN EFFECT AT THE TIME OF THE BUILDING PERMIT APPLICATION) OF THE FOLLOWING PUBLICATIONS:
· CALIFORNIA CODE OF REGULATIONS TITLE 24: INCLUDES 2022 CALIFORNIA ELECTRICAL CODE, 2022 CALIFORNIA FIRE
CODE, 2022 CALIFORNIA BUILDING CODE, APPLICABLE YEARS OF NFPA ETC. WITH CALIFORNIA AND OTHER LOCAL
AMENDMENTS AS APPLICABLE.
· 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN.
3. SAFETY: THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO MAINTAIN ALL EQUIPMENT IN A SAFE AND RESPONSIBLE MANNER. KEEP DEAD FRONT EQUIPMENTS IN PLACE WHILE ENERGIZED. CONDUCT ALL CONSTRUCTION OPERATIONS IN A SAFE MANNER FOR EMPLOYEES AS WELL AS OTHER WORK PERSONS OR ANYONE VISITING THE JOB SITE. PROVIDE BARRIERS, FLAGS, TAPE, ETC. AS REQUIRED FOR SAFETY. THE CONTRACTOR SHALL HOLD ALL PARTIES HARMLESS OF
NEGLIGENT PRACTICES, WHICH MAY CAUSE INJURY TO OTHERS ON OR NEAR THE JOB SITE.
4. FIRE RATED ASSEMBLIES SHALL MAINTAIN RATINGS AS SPECIFIED IN THE CALIFORNIA BUILDING CODE, CHAPTER 7. ALL ASSEMBLIES TO BE PENETRATED SHALL BE INSTALLED WITH APPLICABLE THROUGH-PENETRATION FIRESTOP SYSTEM AS DETERMINED BY UL CLASSIFICATION. BEFORE CONSTRUCTION, VERIFY AND COMPLY WITH REQUIREMENTS.
5. PROVIDE THIRD-PARTY TESTING FOR ALL NEW FEEDER CONDUCTORS. BRANCH CIRCUITS ARE NOT REQUIRED TO BE
TESTED BY THIRD-PARTY. REFER TO PROJECT SPECIFICATIONS FOR MORE INFORMATION.
FOR EXISTING BUILDINGS:
1. ASBESTOS/LEAD PAINT: IF DURING THE COURSE OF WORK THE CONTRACTOR OBSERVES THE EXISTENCE OF ASBESTOS/LEAD PAINT, ASBESTOS BEARING MATERIALS, THE CONTRACTOR SHALL IMMEDIATELY TERMINATE FURTHER WORK ON THE PROJECT AND NOTIFY THE OWNER OF THE CONDITIONS. THE OWNER WILL, AFTER CONSULTATION WITH
THE OWNER'S REPRESENTATIVE, DETERMINE A FURTHER COURSE OF ACTION.
2. ANY DEMOLITION WORK SHOWN WAS PREPARED FOR THE CONVENIENCE OF THE CONTRACTOR. THE ENGINEER DOES NOT REPRESENT THAT ALL ITEMS WHICH MAY REQUIRE DEMOLITION HAVE BEEN SHOWN. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO CAREFULLY EXAMINE THE SITE AND CONTRACT DOCUMENTS AND TO PERFORM ALL DEMOLITION AND RECONSTRUCTION WHICH MAY BE REQUIRED FOR THE PROPER EXECUTION AND
COMPLETION OF THE WORK.
3. EXISTING CONDITIONS: INFORMATION SHOWN FOR EXISTING CONDITIONS WAS PRIMARILY GAINED FROM "AS-BUILT" DRAWINGS AND/OR LIMITED FIELD INVESTIGATION. BEFORE BID, VISIT SITE TO VERIFY EXISTING CONDITIONS AND MAKE
ALLOWANCE FOR VARIATION FROM THAT SHOWN.
4. CLOSELY COORDINATE OUTAGE AND FACILITY DISRUPTION TIME WITH OWNER. MINIMUM 72-HOURS NOTICE IS REQUIRED
BEFORE ANY CIRCUIT SHUTDOWN OR DISRUPTION OF FACILITY PERSONNEL FUNCTIONING.
GENERAL NOTES
BUILDING INFORMATION
LOCATION MAP
NOT TO SCALE
INDEX OF DRAWINGS
SCOPE OF WORK
THE SCOPE OF THIS PROJECT CONSISTS OF THE INSTALLATION OF THE ELECTRIC
VEHICLE SUPPLY EQUIPMENT (EVSE) TO PROVIDE POWER TO (4) ELECTRIC VEHICLE
CHARGING STATION (EVCS) PORTS WITHIN THE BISHOP EQUIPMENT SHOP. SEE EVCS
NOTE ON THIS SHEET.
THE ELECTRIC VEHICLE SUPPLY EQUIPMENT IS MADE UP OF (1) NEW TRANSFORMER,
(1) NEW PANELBOARD AS WELL AS NEW FEEDERS TO THE EVCS PORTS LOCATIONS
AS SHOWN ON THESE PLANS. PROJECT INCLUDES STRUCTURAL AND CIVIL WORK
EFFORT/S NECESSARY TO SUPPORT THIS PROJECT. SEE SHEET E1.00 FOR A
SUMMARY OF THE EVCS PORTS.
ALL EVSE INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE
INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC
SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO COMPLY
WITH CBC 11B-228.3.2 ACCESS REQUIREMENTS.
ALTHOUGH THE CONTRACTOR MAY NOT PROCURE OR PERFORM THE FINAL
INSTALLATION OF THE EVSE, SUCH WORK IS IN THE PERMIT SCOPE AND MAY BE
PERFORMED BY OTHERS.
ALL WORK PERTAINING TO AND ALL MATERIALS SUPPLIED FOR EXECUTING AND
COMPLETING THIS CONTRACT SHALL COMPLY WITH PROVISIONS SPECIFIED IN THE
CONTRACT DOCUMENTS AND WITH ALL APPLICABLE LAWS, REGULATIONS AND
ORDINANCES GOVERNING WORK INCLUDING, BUT NOT NECESSARILY LIMITED TO
THOSE OF THE APPLICABLE CODES LISTED ON SHEET E0.01.
CONSTRUCTION TYPE: V-B
OCCUPANCY CLASSIFICATION: S-1
OCCUPANCY LOAD: 40
ACTUAL BUILDING HEIGHT: 25 FT.
BUILDING AREA (SQ. FT.) 12,800 SQ. FT.
AREA OF PROJECT (SQ. FT.) 3,500 SQ. FT.
SEPARATED OR NON-SEPARATED USE: NON-SEPARATED
ALLOWABLE AREA: 36,000 SQ. FT.
AREA INCREASED: NONE
HEIGHT INCREASED: NONE
FIRE SPRINKLERS: YES
FIRE ALARM: YES
OTHER FIRE PROTECTION SYSTEMS: NO
SMOKE CONTROL SYSTEM: NO
YEAR CONSTRUCTED: 1958
HIGH FIRE SEVERITY ZONE: NO
SEISMIC JOINTS: NO
EMERGENCY RESPONDER RADIO COVERAGE: YES
SHEET COUNT DWG. NO. DESCRIPTION
1 OF 14 T0.01 TITLE SHEET, LOCATION MAP, GENERAL NOTES &
SHEET INDEX
2 OF 14 E0.01 SYMBOLS, DESIGNATION AND ABBREVIATIONS
3 OF 14 E1.00 SITE PLAN
4 OF 14 E2.00 POWER PLANS
5 OF 14 E4.00 ELECTRICAL DETAILS
6 OF 14 E5.00 SINGLE LINE DIAGRAM & SCHEDULES
7 OF 14 C-001 CIVIL TITLE SHEET
8 OF 14 C-140 CIVIL SITE PLAN
9 OF 14 C-500 CIVIL DETAILS
10 OF 14 S-001 GENERAL NOTES
11 OF 14 S-002 SPECIAL INSPECTION TABLES
12 OF 14 S-101 PLANS
13 OF 14 S-102 EQUIPMENT ANCHORAGE DETAILS
14 OF 14 S-103 EQUIPMENT ANCHORAGE DETAILS
EVCS NOTE:
ELECTRICAL VEHICLE CHARGING STATION
(EVCS) SHALL BE PROVIDED BY THE STATE
(DEPARTMENT OF GENERAL SERVICES), AND
INSTALLED BY THE CURRENT STATE ELECTRIC
VEHICLE CHARGING STATION VENDOR. ALL
FINAL TERMINATIONS AND/OR SPLICING FOR
THE EVCS SHALL BE THE RESPONSIBILITY AND
PERFORMED BY THE STATE VENDOR.
PROJECT TEAMPROJECT TEAM
KPFF
140 NEWPORT CENTER DRIVE, SUITE 100
NEWPORT BEACH, CA 92660
(949) 478-8800
CONTANT: ALI KHAMSI
KPFF
18400 VON KARMAN AVE., SUITE 600
IRVINE, CA 92612
(949) 252-1022
CONTACT: CHRISTOPHER DOMINAS
PROJECT DIRECTOR
STRUCTURAL ENGINEERCIVIL ENGINEER
ELECTRICAL ENGINEER
GOSS ENGINEERING, INC.
255 EAST RINCON ST., SUITE 301,
CORONA, CA. 92879
(951) 340-1977
CONTACT: ED BURTCH
OFFICE OF SUSTAINABILITY, DGS
707 3RD STREET, 4TH FLOOR
WEST SACRAMENTO, CA 95606
(279) 782-3872
CONTACT: ANN WATSON
R
CALL 811 BEFORE YOU DIG.
DGS PROJECT NUMBER: 000000000013672
ARC-FLASH NOTE:
ALL NEW ELECTRICAL SWITCHBOARDS, PANELBOARDS,
EQUIPMENT/DEVICES AND SUCH, SHALL BE PROVIDED WITH AN
ARC-FLASH HAZARD WARNING LABEL/MARKING, IN COMPLIANCE TO
THE REQUIREMENTS OF THE LATEST CEC 110.16. THE LABELS
SHALL BE GENERATED BY THE DESIGN TEAM AND INSTALLED BY
THE ELECTRICAL CONTRACTOR.
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
J a y S tr e e t, B is h o p C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
B is h o p E q u ip m e n t S h o p
E V S E I n s ta lla ti o n
124-01-01.24
04/29/2025
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RI C
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4391-C
95% CD SubmittalEB03/24/20251
100% CD SubmittalEB04/29/20252
TITLE SHEET, LOCATION
MAP, GENERAL NOTES &
SHEET INDEX
T0.01
PROJECT
LOCATION
S M
A
IN
S T
E. JAY ST.W. JAY ST.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
06/18/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4391
DOT D9 - Electric Vehicle Supply Equipment - Bishop Equipment Shop
PROJECT NUMBER: 000000000013672; 07/10/26
Issue Date: 7/10/2026 http://www.gossengineering.com
ABBREVIATIONS
ANNOTATION SYMBOLS
LEGEND
WIRING SYSTEM ABOVE FLOOR
LEVEL, CONCEALED IN WALL OR
ABOVE CEILING UON
WIRING SYSTEM IN OR UNDER
FLOOR OR CONCEALED IN OR
BEHIND STRUCTURE OR EQUIPMENT
CONDUIT STUB ENDING WITH CAP
E0.1
REMOVE/RELOCATE/DEMOLISH
EXISTING
FUSE
RECESSED PANELBOARD 120V/208V
SWITCH
COMBINATION MOTOR
STARTER/DISCONNECT SWITCH
(NUMBER INDICATES STARTER SIZE)
DISCONNECT SWITCH (FUSED),
HORSE POWER RATED
SURFACE MOUNTED PANELBOARD
277V/480V
DISTRIBUTION BOARD
FUSED DISCONNECT SWITCH
RECESSED PANELBOARD 277V/480V
SURFACE MOUNTED PANELBOARD
120V/208V
DISCONNECT SWITCH (NON-FUSED)
ELECTRICAL
SYMBOL
DESCRIPTION
F
SHEET WHERE DETAIL
IS DRAWN
OCCURRENCE
DETAIL IDENTIFICATION
(TYP.)
DETAIL
RECONSTRUCTION KEY NOTE
DEMOLITION KEY NOTE
REVISION
REVISED AREA
REVISION TAG
A AMPERE
ADA AMERICAN DISABILITIES ACT
AC ALTERNATING CURRENT
AF AMPERE FRAME
AS AMPERE SWITCH
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING CAPACITY
ANN ANNUNCIATOR
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO-VISUAL
AWG AMERICAN WIRE GAUGE
BKR BREAKER
BLDG BUILDING
C CONDUIT
CB CIRCUIT BREAKER
CATV CABLE TELEVISION
CEC CALIFORNIA ELECTRICAL CODE
CKT CIRCUIT
CLG CEILING
CO CONDUIT ONLY
COMM COMMUNICATIONS
COMP COMPUTER
DB DISTRIBUTION BOARD
DISC DISCONNECT
DIST DISTRIBUTION
DL DOUBLE LUG
DP DISTRIBUTION PANEL
DWG DRAWING
E EXISTING TO REMAIN
EEOR ELECTRICAL ENGINEER ON RECORD
EG EQUIPMENT GROUND
ELEC ELECTRICAL
EMH ELECTRICAL MAN HOLE
EHH ELECTRICAL HAND HOLE
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
EV ELECTRIC VEHICLE
EVCS ELECTRIC VEHICLE CHARGING STATION
EVSE ELECTRIC VEHICLE SUPPLY EQUIPMENT
F FUSE, FUSED
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPERES
GRD GROUND
GALV GALVANIZE, GALVANIZED
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HPF HEAT PUMP HIGH POWER FACTOR
HPS HIGH PRESSURE SODIUM
JB JUNCTION BOX
KA THOUSAND AMPERES
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT-AMPERE
KW KILOWATT
LCL LONG CONTINUOUS LOAD
LTG LIGHTING
MC METAL CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM THOUSAND CIRCULAR MILS
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MH METAL HALIDE
MIN MINIMUM
MLO MAIN LUGS ONLY
MTD MOUNTED
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
NEC NATIONAL ELECTRIC CODE
NF NON-FUSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NC NORMALLY CLOSED
P POLE, POLES
PF POWER FACTOR
PNL PANEL
PRI PRIMARY
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
PH PHASE
Ø PHASE
R REMOVE
RR REMOVE AND RELOCATE
RL RELOCATED
RECEPT RECEPTACLE
RGS RIGID GALVANIZED STEEL CONDUIT
SEC SECONDARY
SUSP SUSPEND, SUSPENDED
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TBB TELECOMMUNICATIONS BACKBOARD
TMH TELECOMMUNICATIONS MAN HOLE
THH TELECOMMUNICATIONS HAND HOLE
TYP. TYPICAL
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
UON UNLESS OTHERWISE NOTED
V VOLT, VOLTS
VA VOLT-AMPERES
VAV VARIABLE AIR VOLUME
WT WATERTIGHT
W WATT OR WIRE
WP WEATHER PROOF
XFMR TRANSFORMER
Y WYE CONNECTION
MISCELLANEOUS
LINE TYPES
JUNCTION BOX WITH COVER
(MINIMUM 4" SQUARE OR AS
REQUIRED)
CONCRETE BOLLARD
SINGLE PORT PEDESTAL TYPE
ELECTRIC VEHICLE CHARGING STATION
DUAL PORT PEDESTAL TYPE
ELECTRIC VEHICLE CHARGING STATION
T
TRANSFORMER. "F" DENOTES FRONT
OF TRANSFORMER.
DIGITAL MULTI-METERDMM
UNDERGROUND PULL BOX
POST AND SIGNAGE
WHEELSTOP
SURFACE MOUNTED JUNCTION BOX
WITH COVER
(MINIMUM 4" SQUARE OR AS
REQUIRED)
ELECTRICAL GENERAL NOTES
PB
APPLICABLE CODES
J
J
PB SURFACE-MOUNTED PULL BOX
F
FENCE
2022 CALIFORNIA BUILDING CODE (CBC) PART 2, VOLUMES
1 AND 2, TITLE 24
(BASED ON 2021 INTERNATIONAL BUILDING CODE)
2022 CALIFORNIA ELECTRIC CODE (CEC) PART 3, TITLE 24
(BASED ON 2020 NATIONAL ELECTRIC CODE)
2022 CALIFORNIA FIRE CODE (CFC) PART 9, TITLE 24
(BASED ON 2021 INTERNATIONAL FIRE CODE)
2022 CALIFORNIA ENERGY CODE PART 6, TITLE 24
2022 CALIFORNIA REFERENCED STANDARD CODE PART 12,
TITLE 24
TITLE 19, PUBLIC SAFETY, STATE FIRE MARSHAL
REGULATIONS
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
PARTIAL LIST OF APPLICABLE NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA) STANDARDS
NFPA 72, 2022 EDITION - NATIONAL FIRE ALARM AND
SIGNALING CODE (AMENDED BY CSFM)
NFPA 80, 2019 EDITION - FIRE DOORS AND OTHER OPENING
PROTECTIVES
REFER TO 2022 CBC CHAPTER 35 FOR ADDITIONAL
STANDARDS NOT PROVIDED ON THIS LIST
1. CONTRACTOR SHALL PERFORM INSTALLATION WORK IN CONFORMANCE WITH THE 2022 EDITION OF THE CALIFORNIA ELECTRICAL CODE (CEC) AND ALL APPLICABLE CODES, ORDINANCES, AND REGULATIONS.
2. CONDUIT ROUTING AND EQUIPMENT LOCATION AS SHOWN ON THE ELECTRICAL POWER PLAN ARE DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL VERIFY FEASIBILITY OF THE INSTALLATION BEFORE COMMENCING THE JOB. ANY OBSERVATIONS TO THE EXECUTION OF THE WORK SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER OF RECORD IMMEDIATELY.
3. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER CONSTRUCTION TRADES. CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE OF ANY UNRESOLVED ISSUES THAT MAY DELAY INSTALLATION OF
WORK.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING PROPER WORKING SPACE PER CALIFORNIA
ELECTRICAL CODE (CEC), PARAGRAPH 110-26.
5. CONTRACTOR SHALL PROVIDE NECESSARY HARDWARE AND SUPPORTS AS REQUIRED FOR ELECTRICAL CONDUIT/WIRE NOT SCHEDULED FOR DEMOLITION PER CALIFORNIA ELECTRICAL CODE (CEC), PARAGRAPH 110-12.
6. THE SEISMIC BRACING AND ANCHORAGE OF ELECTRICAL CONDUITS SHALL BE IN ACCORDANCE WITH THE
CALIFORNIA BUILDING CODE, CHAPTER 16.
7. CONNECTIONS TO VIBRATING EQUIPMENT AND SEISMIC SEPARATIONS:
· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN DRY INTERIOR LOCATIONS.
· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN AREAS EXPOSED TO WEATHER, DAMP LOCATIONS, CONNECTIONS TO TRANSFORMER ENCLOSURES, AND FINAL CONNECTIONS TO MOTORS.
PROVIDE A SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTOR IN FLEXIBLE CONDUIT RUNS.
MAXIMUM LENGTH SHALL BE SIX FEET UNLESS OTHERWISE NOTED.
8. WHENEVER A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE, EQUIPMENT DEVICES, CIRCUIT BREAKERS, GROUND FAULT PROTECTION SYSTEMS, ETC. (ALL MATERIALS), ARISES ON THE DRAWINGS OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE AND OPERABLE SYSTEMS.
9. ARC-FLASH LABELS SHALL BE PROVIDED FOR THE CONTRACTOR TO INSTALL ON NEW LOW VOLTAGE (480 V, 208 V, 120 V) SYSTEMS REPRESENTED ON THE PROJECT DRAWINGS. THIS INCLUDES SWITCHBOARDS, PANEL BOARDS, TRANSFORMERS, DISCONNECT SWITCHES AND OTHER REQUIRED ELECTRICAL EQUIPMENT. THESE LABELS SERVE AS A GUIDE TO ASSIST THE EMPLOYEES AND OTHERS IN THE SELECTION OF PROPER PERSONAL
PROTECTIVE EQUIPMENT WHEN WORKING AROUND EXPOSED AND ENERGIZED CONDUCTORS.
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
J a y S tr e e t, B is h o p C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
B is h o p E q u ip m e n t S h o p
E V S E I n s ta lla ti o n
124-01-01.24
04/29/2025
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4391-C
95% CD SubmittalEB03/24/20251
100% CD SubmittalEB04/29/20252
SYMBOLS,
DESIGNATION AND
ABBREVIATIONS
E0.01
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
06/18/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4391
DOT D9 - Electric Vehicle Supply Equipment - Bishop Equipment Shop
PROJECT NUMBER: 000000000013672; 07/10/26
Issue Date 7/10/2026
SCALE
SITE PLAN 1
1/32" = 1'-0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
J a y S tr e e t, B is h o p C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic h o p E q u ip m e n t S h o p
E V S E I n s ta lla ti o n
124-01-01.24
04/29/2025
V1
255 East Rincon St., Suite 301
Corona, CA 92879
P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B
R L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4391-C
95% CD SubmittalEB03/24/20251
100% CD SubmittalEB04/29/20252
SITE PLAN
E1.00
E2.00
EVCS SUMMARY
LOCATION PARKING TYPE SHEET EXISTING EVCS SPACES NEW EVCS SPACES
PARKING LOT
*FLEET E2.00 (0) LEVEL 2 (4) LEVEL 2
TOTAL FLEET PORTS: (4) LEVEL 2
* NOTE:
FLEET EVCS INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE INTENDED FOR USE BY A DESIGNATED VEHICLE
OR DRIVER; THEREFORE, PER CBC SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO COMPLY WITH CBC
11B-228.3.2 ACCESS REQUIREMENTS.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
06/18/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4391
DOT D9 - Electric Vehicle Supply Equipment - Bishop Equipment Shop PROJECT NUMBER: 000000000013672; 07/10/26 Issue Date 7/10/2026
(E) MAIN SWITCHBOARD 'MSB'
(E) FENCE
EVCS-2
L: ~55'-0" %V.D.: 0.50%
J
3"C - 3#4/0
& 1#4 GRD.
& (1) 3" SPARE CONDUIT
11 3
(2 SETS) 1 1/2"C - 4#2
& 1#6 GRD.
8" BETWEEN BOLLARD
AND EVCS FOOTING
(TYP.)
9 (TYP.)
J
3"C - 3#4/0
& 1#4 GRD.
& (1) 3" SPARE CONDUIT
11 8
PB-1
PB-2
PB
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
10'-0"
(TYP.)
18'-0"
(TYP.)
3'-0"
(TYP.)
1'-0"
(TYP.)
T
PB
EVCS-1 51
1 1/2"C - 4#2
& 1#6 GRD.
DISCONNECT SWITCH 6 11
TRANSFORMER
'TEV'
3"C - 3#4/0
& 1#4 GRD.
3 11
(1) 3" SPARE
CONDUIT
11 15
(2) SETS 1 1/2"C - 4#2
& 1#6 GRD.
9(TYP.)
PB-3 14
7 6 11
PANELBOARD 'PB-EV'11 6
PB4'-0" (TYP. BETWEEN
BOLLARDS)
T
PB
3'-0" (TYP.)
1'-0"
(TYP.)
3'-0"
MIN.
SCALE
POWER PLAN 1
1/8"=1'=0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
J a y S tr e e t, B is h o p C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic h o p E q u ip m e n t S h o p
E V S E I n s ta lla ti o n
124-01-01.24
04/29/2025
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4391-C
95% CD SubmittalEB03/24/20251
100% CD SubmittalEB04/29/20252
POWER PLANS
E2.00
R
CALL 811 BEFORE YOU DIG.
LEGEND:
EXISTING
NEW
NEW UNDERGROUND
SHEET NOTES:
DUAL PORT PEDESTAL TYPE EVCS WITH
19,200VA PER PORT. PROVIDE 10'-0" OF FEEDER
WIRE (4#2 + 1#6 GRD) COILED UP AT EVCS
STUB-UP LOCATION FOR FINAL EVCS
INSTALLATION. PROVIDE MULE TAPE ROUTED
THROUGH CONDUIT FROM THE PANELBOARD TO
EVCS STUB-UP. SEE DETAIL #1 ON SHEET E4.00.
DUAL PORT PEDESTAL TYPE EVCS WITH
12,000VA PER PORT. PROVIDE 10'-0" OF FEEDER
WIRE (4#2 + 1#6 GRD) COILED UP AT EVCS
STUB-UP LOCATION FOR FINAL EVCS
INSTALLATION. PROVIDE MULE TAPE ROUTED
THROUGH CONDUIT FROM THE PANELBOARD TO
EVCS STUB-UP. SEE DETAIL #1 ON SHEET E4.00.
SEE DETAIL #2 SHEET E4.00 FOR UNDERGROUND
CONDUIT BURIAL DETAIL BELOW ASPHALT
PAVEMENT. FOR ALL ROUTING THROUGH
TRAFFIC CROSSINGS PROVIDE SCHEDULE 80
PVC UNDERGROUND CONDUIT.
PROVIDE 11" X 17" X DEPTH AS REQUIRED
CONCRETE PULLBOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #3
SHEET E4.00 FOR UNDERGROUND PULL-BOX
DETAIL.
SEE DETAIL #4 SHEET E4.00 FOR EV CHARGING
STATION PVC CONDUIT STUB-UP DETAIL.
SEE DETAIL #5 SHEET E4.00 FOR ELECTRIC
EQUIPMENT RGS CONDUIT STUB-UP DETAIL.
SEE DETAILS #7 & #8 SHEET E4.00 FOR
TRANSFORMER GROUND ROD AND
GROUND-WELL DETAILS.
SURFACE MOUNT CONDUIT ALONG EXISTING
BUILDING WALL. PAINT CONDUITS TO MATCH
EXISTING SURFACE.
NEW 4" DIA. CONCRETE BOLLARD. REFER TO
CIVIL AND STRUCTURAL DRAWINGS FOR MORE
INFORMATION.
PROVIDE 30" X 30" X 8" NEMA-3R PULLBOX PB-2.
SEE SINGLE LINE DIAGRAM #1 SHEET E5.00 FOR
MORE INFORMATION.
PENETRATION THROUGH NON-RATED WOOD
FRAME WALL WALL. PROVIDE 30" X 30" X 8"
NEMA-3R PULLBOX PB-1 TO TRANSITION
THROUGH WALL.
11'-6" X 3'-6" ELECTRICAL EQUIPMENT CONCRETE
PAD. REFER TO STRUCTURAL DRAWINGS FOR
ADDITIONAL INFORMATION.
PROVIDE 17" X 30" X DEPTH AS REQUIRED
CONCRETE PULLBOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #3
SHEET E4.00 FOR UNDERGROUND PULL-BOX
DETAIL.
TERMINATE 3" SPARE CONDUIT IN PULLBOX AND
CAP. PROVIDE PULL TAPE AND LABEL "SPARE
FOR FUTURE EVCS".
GENERAL NOTES:
1. ELECTRICAL ENGINEERING FOR THIS PROJECT
IS BASED ON A FIELD VISIT OF THE ELECTRICAL
SYSTEM. IN CASE OF ANY DISCREPANCIES WITH
EXISTING FIELD CONDITIONS, ELECTRICAL
CONTRACTOR SHALL VERIFY THE EXACT
DIFFERENCES AND NOTIFY THE ELECTRICAL
ENGINEER FOR POSSIBLE REVISION TO THESE
DOCUMENTS.
2. ANY ELECTRICAL AND/OR SIGNAL UTILITY
SHUTDOWNS WITHIN THE AREA OF WORK SHALL
BE COORDINATED AND SCHEDULED IN ADVANCE
WITH THE SITE'S REPRESENTATIVE.
3. ELECTRIC VEHICLE CHARGING STATION/S
(EVCS) SHALL BE PROVIDED, INSTALLED AND
CONNECTED BY STATE VENDOR.
4. PROVIDE MINIMUM OF 1'-0" CLEARANCE BEHIND
ALL PEDESTAL MOUNTED CHARGERS FOR
SERVICING. CONTRACTOR SHALL FIELD VERIFY
ALL DISTANCES PRIOR TO BID.
PROPOSED EV CHARGERS
EVCS #
WALL/PEDESTAL
MOUNT EVCS
SINGLE/DUAL
EVCS
CHARGE PORT #
POWER SELECT
(FLA)
VOLTAGE
POWER SHARE
(Y / N/A)
CHARGE PORT
TYPE
1 PEDESTAL DUAL 80 208V-1PH N/A FLEET
2 PEDESTAL DUAL 50 208V-1PH N/A FLEET
NOTES:
1. (2) DUAL PORT EVCS SHALL SERVE (4) FLEET PARKING STALLS
2. (FLA) STANDS FOR FULL LOAD AMPS
3. (Y) STANDS FOR, YES WILL BE REQUIRED; (N/A) STANDS FOR, NOT APPLICABLE
1 2
1 2
SCALE
ENLARGED EQUIPMENT PLAN 2
1/4"=1'=0"
E2.00
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
06/18/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4391
DOT D9 - Electric Vehicle Supply Equipment - Bishop Equipment Shop
PROJECT NUMBER: 000000000013672; 07/10/26
Issue Date 7/10/2026
DUAL PORT PEDESTAL ELECTRIC VEHICLE CHARGING STATION 1
N.T.S.
NEW CONCRETE EVCS
FOOTING. SEE STRUCTURAL
DRAWINGS FOR MORE
INFORMATION.
FRONT
ELEVATION
SIDE
ELEVATION
4'-0"
MAX.
FINISH GRADE
DUAL PORT PEDESTAL
EV CHARGING STATION
PROVIDE 1'-6" PVC CONDUIT
STUB-UP WITH CONDUIT
PLUG AND GROUNDING
BUSHING. REFER TO
CONDUIT STUB UP DETAIL #4
ON THIS SHEET.
PROVIDE LABEL IDENTIFYING
SHUT-OFF LOCATION. LABEL SHALL
CORRESPOND TO CHARGER NUMBER.
REFER TO DETAIL #6 ON THIS SHEET.
6"
MIN.
STEEL COUPLING WITH
THREADED PLUG
FINISH GRADE
PVC CONDUIT
TRANSITION
COUPLING
CONTINUOUS RIGID GALVANIZED
STEEL CONDUIT WRAPPED AROUND
WITH 40 MIL. BLACK ELECTRICAL
PLASTIC INSULATING TAPE TO 6"
ABOVE FINISH GRADE
CONTINUOUS RIGID
GALVANIZED STEEL
CONDUIT
BEND RADIUS
R = 10 x DIA. OF CONDUIT
(MINIMUM)
PROVIDE BUSHING
WHEN PULLING
CONDUCTORS
SCALE
ELECTRICAL EQUIPMENT RGS CONDUIT STUB-UP DETAIL 5
N.T.S.
SCALE
EV CHARGING STATION PVC CONDUIT STUB-UP DETAIL 4
N.T.S.
1'-6"
MIN.
FINISH GRADE
PVC CONDUIT
COUPLING
PVC CONDUIT
BEND RADIUS
R = 10 x DIA. OF CONDUIT
(MINIMUM)
PROVIDE BUSHING
WHEN PULLING
CONDUCTORS
PVC COUPLING WITH
THREADED PLUG
PVC CONDUIT
1'-0"
MIN.
2'-0"
MIN.
3" CLEAN SAND
BEDDING
NOTE:
1. PER CEC 300.5 NO CONCRETE CASING IS REQUIRED IF SCHEDULE 80 PVC IS USED 2'-0"
BELOW GRADE LEVEL. SEE POWER PLAN FOR MORE INFORMATION
1" MIN. SPACING. SHALL BE EQUAL
TO THE LARGEST CONDUIT SIZE
FOR MULTIPLE CONDUIT RUNS.
3" CLEAN SAND
BEDDING
NEW ASPHALT PAVEMENT
EXISTING ASPHALT PAVEMENT
EXISTING BASE
CRUSHED AGGREGATE BASE
RECOMPACTED TO 95%
RLATIVE COMPACTION
MATCH
EXISTING +1"
MATCH
EXISTING
+1"
ELECTRICAL
WARNING TAPE
NATIVE BACKFILL
95% COMPACTION
SCALE
UNDERGROUND CONDUIT BURIAL DETAIL (ASPHALT PAVEMENT) 2
N.T.S.
CONDUIT/S PER PLAN
SCALE
UNDERGROUND PULLBOX DETAIL 3
N.T.S.
GRAVEL
BASE
ELECTRICAL CONDUITS
(IN/OUT)
CONCRETE STEEL
REINFORCED
BOLT DOWN LID
NATIVE BACKFILL
95% COMPACTION
12" DEEP REINFORCED
CONCRETE NON-TRAFFIC
PULLBOX
(EXTEND AS REQUIRED)
FINISH GRADE
BASE
(TYPICAL)
AC PAVEMENT
(TYPICAL)
2'-0"
MIN.
NOTE:
REFER TO SHEET NOTES ON POWER
PLANS FOR SPECIFIC PULLBOX
DIMENSIONS.
SCALE
EMERGENCY SHUT-OFF LABEL DETAIL 6
N.T.S.
4"
3"
RED BACKGROUND
WITH WHITE LETTERING
RED STRIPING
WHITE STRIPING
NOTE:
1. LABEL SHALL BE PROVIDED FOR ALL NEW EV CHARGING STATIONS SHOWN ON THESE DRAWINGS. LABEL SHALL
CORRESPOND WITH CHARGER NUMBER AND THE ASSOCIATED PANELBOARD PROVIDING POWER.
2. SEE BELOW FOR LABEL SPECIFICATIONS:
· MATERIAL: THERMAL PRINTED ON REFLECTIVE RED OUTDOOR LABEL STOCK (MEETS ASTMD 4956-99)
· COLOR: WHITE TEXT ON RED BACKGROUND WITH RED AND WHITE ALTERNATING STRIPES
· DAMAGE RESISTANT FROM COMMON CHEMICALS AND SOLVENTS.
· MINIMUM SERVICE TEMPERATURE: -40 DEG FAHRENHEIT
· MAXIMUM SERVICE TEMPERATURE: 180 DEG FAHRENHEIT
· APPLICATION TEMPERATURE: 50 DEG FAHRENHEIT
· FILM THICKNESS: 5.5 MIL
· ADHESIVE THICKNESS: 1 MIL
NOTE:
1. FOR PEDESTAL TYPE EVCS INFORMATION - REFER TO INSTALLATION INSTRUCTIONS PER MANUFACTURER.
2. DUAL PORT CHARGING STATION SHALL BE PROVIDED AND INSTALLED BY CURRENT STATE VENDOR. CONTRACTOR SHALL PROVIDE INFRASTRUCTURE NECESSARY TO SUPPORT THE CHARGER AS SHOWN ON THESE DRAWINGS.
3. PROVIDE MULE TAPE FROM EVCS STUB-UP BACK TO PANELBOARD.
1 1/2" PVC CONDUIT
4#2 & 1#6 GRD.
WITH MULE TAPE BACK
TO PANELBOARD
1#2 BARE COPPER GROUND
WIRE FOR GROUND RING.
3/4"Ø X 10'-0"L
COPPER GROUND ROD
WELD TO COPPER
GROUND ROD BY
EXOTHERMIC PROCESS
SCALE
CONNECTION TO GROUND ROD DETAIL 9
N.T.S.
NOTE:
ALL GROUNDING SHALL BE IN
ACCORDANCE WITH
CALIFORNIA ELECTRICAL CODE,
CEC 2022, ARTICLE 250
SCALE
GROUND-WELL DETAIL 8
N.T.S.
G R O U N D
COVER SHALL HAVE CAST
LETTERING "GROUND"
1 CUBIC FT.
MIN. 3/4" GRAVEL
3/4"Ø X 10'-0"L
COPPER GROUND
ROD
PRE-CAST CONCRETE
BOX 10"W x 17"L x 12"D
OPEN BOTTOM
1#2 GROUNDING WIRE
CONNECTED TO
EQUIPMENT
GROUND ROD CLAMP
NOTE:
ALL GROUNDING SHALL BE IN
ACCORDANCE WITH
CALIFORNIA ELECTRICAL CODE,
CEC 2022, ARTICLE 250
SCALE
GROUND RING DETAIL 7
N.T.S.
G R O U N D
G R O U N D
GROUND-WELL
(SEE DETAIL #8 ON THIS SHEET)
PAD MOUNTED
TRANSFORMER
GROUND-WELL
(SEE DETAIL #8 ON THIS SHEET) DISCONNECT SWITCH ON
STRUCTURAL SUPPORTS
REFER TO STRUCTURAL
DRAWINGS FOR EQUIPMENT
PAD INFORMATION
1#2 BARE COPPER GROUND
WIRE FOR GROUND RING.
(TYP.)
PANELBOARD MOUNTED
ON STRUCTURAL
SUPPORTS
PROVIDE EXOTHERMIC WELDING
FOR CONNECTIONS BELOW GRADE.
(TYP.)
NOTE:
1. THE GROUND RING SHALL BE INSTALLED NOT LESS THAN 30" BELOW FINISH SURFACE PER NEC 250.53.
1#2 BARE COPPER GROUND WIRE
CONNECTING TRANSFORMER AND
GROUND ROD.
EQUIPMENT GROUNDING
CONNECTION
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
J a y S tr e e t, B is h o p C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
B is h o p E q u ip m e n t S h o p
E V S E I n s ta lla ti o n
124-01-01.24
04/29/2025
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4391-C
95% CD SubmittalEB03/24/20251
100% CD SubmittalEB04/29/20252
ELECTRICAL
DETAILS
E4.00
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
06/18/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4391
DOT D9 - Electric Vehicle Supply Equipment - Bishop Equipment Shop
SINGLE LINE DIAGRAM 1
N.T.S.
LEGEND:
EXISTING
NEW
SHEET NOTES:
DEMOLISH EXISTING SPARE 20A-3P CIRCUIT
BREAKER AND REPLACE WITH NEW CIRCUIT
BREAKER. SIZE AS SHOWN. MATCH TO EXISTING
MAKE, MODEL AND AIC RATING.
PROVIDE SPARE 3" CONDUIT WITH PULL TAPE
AND CAP IN PULLBOX PB-3. LABEL CONDUIT AS
"SPARE FOR FUTURE EVCS". SEE POWER PLANS
FOR MORE INFORMATION.
SEE GROUNDING DETAILS ON SHEET E4.00.
PANELBOARD SHALL REMAIN UNLOCKED
UNLESS SERVICING THE ELECTRICAL
EQUIPMENT.
EV CHARGER DISCONNECTS SHALL BE
LOCKABLE CIRCUIT BREAKER TYPE.
1,000A BUS
(E)
M
INCOMING 12KV SERVICE
FROM SOUTHERN
CALIFORNIA EDISON
2,000A 3P
SERVICE DISCONNECT - EQUIPMENT SHOP 9
2,000A, 240D/120V, 3Ø, 4W
NEMA-3R, 65,000 AIC
(SQUARE-D QED POWER STYLE SWITCHBOARD)
MAIN SWITCHBOARD MSB'
2,000A, 240D/120V, 3Ø, 4W
NEMA-1, 65,000 AIC (SQUARE-D QED POWER STYLE SWITCHBOARD)
TRANSFORMER
500KVA
12KV-240D/120V , 3Ø, 4W
%Z =4.00%
NEMA-3R
(E)
20A 2P
(E F E E D
E R
20A 3P
(E F E E D
E R
20A 3P
225A 3P
(E F E E D
E R
225A 2P
(E F E E D
E R
50A 2P
(E F E E D
E R
20A 3P
(E F E E D
E R
20A 3P
(E F E E D
E R
50A 3P
(E F E E D
E R
(E)
PANEL
'P'
50A 3P
(E F E E D
E R
20A 3P
(E F E E D
E R
150A 3P
(E F E E D
E R
(E)
PANEL
'W'
(E)
MILL
(E)
ARC
WELDER
(E)
DOORS
(E)
DRILL
PRESS
(E)
LOAD
(E)
RECEPT
(E)
PANELS
'H' & 'G'
(E)
PARKING
LOT
LIGHTS
(E)
UNIT
HEATERS
2-7
SPARE
225A 3P
15 16 17 18 19 20 21 22 23 24 25 26 27
TRANSFORMER 'TEV'
75KVA
240V-208Y/120V 3Ø, 4W %Z =3.36%
NEMA-3R
DISC. SWITCH
200A-3P
WP
4"C - 4#250
& 1#4 GRD.
L: ~10'-0"
%V.D.: NEGL.
3"C - 3#4/0
& 1#4 GRD.
L: ~150'-0"
%V.D.: 1.46%
1#2 TO
GROUND ROD
IF=7,467A
IF=2,809A
3"C - 3#4/0
& 1#4 GRD.
L: ~10'-0"
%V.D.: NEGL.
PANEL
'PB-EV'
IF=2,775A
250A-3P
PB-1
PB-2
PB-3
4 5
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
J a y S tr e e t, B is h o p C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
B is h o p E q u ip m e n t S h o p
E V S E I n s ta lla ti o n
124-01-01.24
04/29/2025
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4391-C
95% CD SubmittalEB03/24/20251
100% CD SubmittalEB04/29/20252
SINGLE LINE
DIAGRAM &
SCHEDULES
E5.00
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
06/18/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4391
DOT D9 - Electric Vehicle Supply Equipment - Bishop Equipment Shop
CALTRANS DISTRICT 8 BISHOP EQUIPMENT SHOP
EVSE INSTALLATION
100% CONSTRUCTION DRAWINGS
CIVIL TITLE SHEET
C-001
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
J a y S tr e e t, B is h o p C A
RC
JP
As Noted
C a lt ra n s D is tr ic h o p E q u ip m e n t S h o p
E V S E I n s ta lla ti o n
2400052
04/29/2025
V1
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 24-S-4391-C
95% CD Submittal--03/24/20251
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
140 Newport Center Drive, Suite 100
Newport Beach, CA 92660
O: 949.478.8800 www.kpff.com
100% CD Submittal--04/29/20252
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
06/18/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4391
DOT D9 - Electric Vehicle Supply Equipment - Bishop Equipment Shop PROJECT NUMBER: 000000000013672; 07/10/26 Issue Date 7/10/2026 http://www.kpff.com
EXISTING BUILDING
(TO REMAIN)
E A S T J
A Y S
T R
E E T
EXISTING
BUILDING
TO REMAIN
J J
PB
E V
F
LE
E T
O N
LY
E V
F
LE
E T
O N
LY
E V
F
LE
E T
O N
LY
E V
F
LE
E T
O N
LY
T
PB
CIVIL SITE PLAN
C-140
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
J a y S tr e e t, B is h o p C A
RC
JP
As Noted
C a lt ra n s D is tr ic h o p E q u ip m e n t S h o p
E V S E I n s ta lla ti o n
2400052
04/29/2025
V1
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 24-S-4391-C
95% CD Submittal--03/24/20251
255 East Rincon St., Suite 301
Corona, CA 92879
P 951.340.1977 | F 951.340.1090 www.gossengineering.com
140 Newport Center Drive, Suite 100
Newport Beach, CA 92660
O: 949.478.8800 www.kpff.com
100% CD Submittal--04/29/20252
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
06/18/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4391
DOT D9 - Electric Vehicle Supply Equipment - Bishop Equipment Shop PROJECT NUMBER: 000000000013672; 07/10/26 Issue Date 7/10/2026
CIVIL DETAILS
C-500
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
J a y S tr e e t, B is h o p C A
RC
JP
As Noted
C a lt ra n s D is tr ic h o p E q u ip m e n t S h o p
E V S E I n s ta lla ti o n
2400052
04/29/2025
V1
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 24-S-4391-C
95% CD Submittal--03/24/20251
255 East Rincon St., Suite 301
Corona, CA 92879
P 951.340.1977 | F 951.340.1090 www.gossengineering.com
140 Newport Center Drive, Suite 100
Newport Beach, CA 92660
O: 949.478.8800 www.kpff.com
100% CD Submittal--04/29/20252
E V
F
LE
E T
O N
LY
E V
F
LE
E T
O N
LY
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
06/18/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4391
DOT D9 - Electric Vehicle Supply Equipment - Bishop Equipment Shop PROJECT NUMBER: 000000000013672; 07/10/26 Issue Date: 7/10/2026
STRUCTURAL NOTES
GENERAL
1. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO STARTING
CONSTRUCTION. THE ARCHITECT SHALL BE NOTIFIED OF ANY DISCREPANCIES OR
INCONSISTENCIES.
2. ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION OF ALL
DRAWINGS AND SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION. ANY
DISCREPANCIES THAT OCCUR SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT PRIOR TO START OF CONSTRUCTION SO THAT A CLARIFICATION CAN BE
ISSUED. ANY WORK PERFORMED IN CONFLICT WITH THE CONTRACT DOCUMENTS OR
ANY CODE REQUIREMENTS SHALL BE CORRECTED BY THE CONTRACTOR AT THEIR
OWN EXPENSE AND AT NO EXPENSE TO THE OWNER OR ARCHITECT.
3. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES
AND TYPICAL DETAILS. WHERE NO DETAILS ARE GIVEN, CONSTRUCTION SHALL BE AS
SHOWN FOR SIMILAR WORK.
4. SEE ARCHITECTURAL DRAWINGS FOR THE FOLLOWING:
SIZE AND LOCATION OF ALL DOOR AND WINDOW OPENINGS, EXCEPT AS NOTED.
SIZE AND LOCATION OF ALL INTERIOR AND EXTERIOR NON-BEARING PARTITIONS.
SIZE AND LOCATION OF ALL CONCRETE CURBS, EQUIPMENT PADS, PITS, FLOOR
DRAINS, SLOPES, DEPRESSED AREAS, CHANGE IN LEVEL, CHAMFERS, GROOVES,
INSERTS, ETC.
SIZE AND LOCATION OF ALL FLOOR AND ROOF OPENINGS EXCEPT AS SHOWN.
FLOOR AND ROOF FINISHES.
DIMENSIONS NOT SHOWN ON STRUCTURAL DRAWINGS.
5. SEE MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR THE FOLLOWING:
PIPE RUNS, SLEEVES, HANGERS, TRENCHES, WALL AND SLAB OPENINGS, ETC., EXCEPT
AS SHOWN OR NOTED.
ELECTRICAL CONDUIT RUNS, BOXES, OUTLETS IN WALLS AND SLABS.
CONCRETE INSERTS FOR ELECTRICAL, MECHANICAL OR PLUMBING FIXTURES.
SIZE AND LOCATION OF MACHINE OR EQUIPMENT BASES, ANCHOR BOLTS FOR MOTOR
MOUNTS.
6. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE
FINISHED STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE
CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE
STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE
LIMITED TO, BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC.
OBSERVATION VISITS TO THE SITE BY THE STRUCTURAL ENGINEER SHALL NOT
INCLUDE INSPECTION OF THE ABOVE ITEMS.
7. ASTM SPECIFICATIONS ON THE DRAWINGS SHALL BE OF THE LATEST REVISION.
8. CONSTRUCTION MATERIAL SHALL BE SPREAD OUT IF PLACED ON FRAMED ROOF OR
FLOOR. LOAD SHALL NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT.
PROVIDE ADEQUATE SHORING AND/OR BRACING WHERE STRUCTURE HAS NOT
ATTAINED DESIGN STRENGTH.
9. THE LOCATION OF EXISTING UNDERGROUND UTILITIES SHOWN ON THE DRAWINGS, IF
ANY, ARE APPROXIMATE. THE CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL
EXISTING UNDERGROUND UTILITIES AND COORDINATING WITH THE REQUIREMENTS OF
THIS PROJECT. THE CONTRACTOR SHALL EXERCISE EXTREME CAUTION IN
EXCAVATING AND TRENCHING ON THE SITE. THE CONTRACTOR SHALL IMMEDIATELY
NOTIFY THE ARCHITECT IF ANY CONDITIONS ARE DISCOVERED THAT REQUIRES
FURTHER COORDINATION.
THE CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE THAT OCCURS DUE TO NOT
FULLY LOCATING EXISTING UTILITIES.
10. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO EXISTING CONDITIONS IS
BASED ON AVAILABLE KNOWLEDGE OF EXISTING STRUCTURE. CONTRACTOR SHALL
VERIFY IN FIELD ALL EXISTING CONDITIONS RELATIVE TO THE SCOPE OF THIS
PROJECT. WHERE ACTUAL CONDITIONS ARE NOT IN ACCORDANCE WITH THE
DRAWINGS PROVIDED, THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY.
CONTRACTOR SHALL ALIGN FOR SUFFICIENT BUDGET AND SCHEDULE CONTINGENCY
TO ADDRESS EXISTING HIDDEN CONDITIONS.
11. ALL DEMOLITION SHALL BE PERFORMED IN SUCH A WAY AS NOT TO DAMAGE THE
EXISTING STRUCTURAL ELEMENTS THAT ARE TO REMAIN IN THE FINISHED STRUCTURE.
ANY PORTIONS OF STRUCTURE TO REMAIN THAT ARE DAMAGED DURING DEMOLITION
SHALL BE REPLACED AT NO ADDITIONAL COST. EXISTING STRUCTURAL ELEMENTS
SHALL BE PROTECTED TO THE FULLEST EXTENT POSSIBLE, IN ORDER TO MITIGATE
DAMAGE. CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF ALL
EXISTING STRUCTURAL ELEMENTS THAT ARE NECESSARY FOR THE COMPLETION OF
ALL NEW WORK.
12. NOTICE TO THE CONTRACTOR/ BUILDER/ INSTALLER/ SUB-CONTRACTOR/
OWNER-BUILDER: BY USING THIS PERMITTED CONSTRUCTION DRAWINGS FOR
CONSTRUCTION/INSTALLATION OF THE WORK SPECIFIED HEREIN, YOU ACKNOWLEDGE
AND ARE AWARE OF THE REQUIREMENTS OF CITY OF SAN DIEGO FOR SPECIAL
INSPECTIONS, STRUCTURAL OBSERVATIONS, CONSTRUCTION MATERIAL TESTING AND
OFF-SITE FABRICATION OF BUILDING COMPONENTS, CONTAINED IN THE STATEMENT
OF SPECIAL INSPECTIONS AND, AS REQUIRED BY THE CALIFORNIA CONSTRUCTION
CODES.
DESIGN CRITERIA
1. ALL WORK SHALL CONFORM TO THE MINIMUM STANDARDS OF THE FOLLOWING CODES:
2022 CALIFORNIA BUILDING CODE AND LATEST REVISIONS
REFERRED TO HERE AS "THE CODE", AND ANY OTHER REGULATING AGENCIES WHICH
HAVE AUTHORITY OVER ANY PORTION OF THE WORK, INCLUDING THE STATE OF
CALIFORNIA DIVISION OF INDUSTRIAL SAFETY, AND THOSE CODES & STANDARDS LISTED
IN THESE NOTES AND SPECIFICATIONS.
2. SEISMIC ANALYSIS PER CHAPTER 16A OF THE CODE UTILIZING THE FOLLOWING
PROCEDURE:
RISK CATEGORY = II
IMPORTANCE FACTOR = 1.0
SS = 1.542
S1 = 0.525
SITE CLASS = D (DEFAULT)
SDS = 1.234
SD1 = 0.494
GROUND MOTION USED:
- CODE DESIGN RESPONSE SPECTRUM
SEISMIC DESIGN LOAD (NON-STRUCTURAL COMPONENT)
Fp (HORIZONTAL FORCE)
Fp = 0.4a p S DS
R p
I p
1 + 2 W P z h
Fp MIN = 0.3 SDS IP WP
Fp MAX = 1.6 SDS IP WP
Fv (VERTICAL FORCE)
Ev = 0.2 SDS WP
W P = COMPONENT WEIGHT
h = AVERAGE ROOF HEIGHT, FEET z = HEIGHT OF COMPONENT ATTACHMENT POINT, FEET
S DS= DESIGN SPECTRAL ACCELERATION
I P = COMPONENT IMPORTANCE FACTOR, PER ASCE 7-16 SECTION 13.1.3 = 1.0
a p = AMPLIFICATION FACTOR, PER ASCE 7-16 TABLE 13.5-1 AND TABLE 13.6.-1 R p = COMPONENT RESPONSE FACTOR, PER ASCE 7-16 TABLE 13.5-1 AND TABLE 13.6.-1
CONCRETE
1. ALL CONCRETE CONSTRUCTION SHALL CONFORM WITH CHAPTER 19 OF THE CODE
AND WITH THE PROVISIONS OF ACI 318, LATEST EDITION.
2. REINFORCED CONCRETE IS DESIGNED BY THE "ULTIMATE STRENGTH DESIGN
METHOD".
3. CONCRETE MIXES SHALL BE DESIGNED BY THE APPROVED TESTING LABORATORY
AND APPROVED BY THE STRUCTURAL ENGINEER. THE COMPRESSIVE STRENGTH OF
THE CONCRETE SHALL BE PROPORTIONED BASED ON CHAPTER 19A OF THE CODE.
4. SCHEDULE OF STRUCTURAL CONCRETE 28-DAY STRENGTH AND TYPES:
LOCATION
EXPOSURE
CLASSES
F S W C
MIN
STRENGTH
f'c (PSI)
MAX WATER/
CEMENT
RATIO
CEMENT
TYPE
(ASTM C150)
DENSITY
ALL CONCRETE
FOOTINGS
F0 S0 W0 C1 4000 PSI 0.50 II/V 150 PCF
5. AGGREGATE FOR HARDROCK CONCRETE SHALL CONFORM TO ALL REQUIREMENTS
AND TESTS OF ASTM C 33 AND PROJECT SPECIFICATIONS. EXCEPTIONS MAY BE
USED ONLY WITH PERMISSION OF THE STRUCTURAL ENGINEER.
6. AGGREGATE FOR LIGHT WEIGHT (110PCF) CONCRETE SHALL BE EXPANDED SHALE
CONFORMING TO ASTM C 330 AND PROJECT SPECIFICATIONS. EXCEPTIONS MAY BE
USED ONLY WITH PERMISSION OF THE STRUCTURAL ENGINEER.
7. CONCRETE MIXING OPERATION, ETC. SHALL CONFORM TO ASTM C 94.
8. PLACEMENT OF CONCRETE SHALL CONFORM TO THE CODE AND PROJECT
SPECIFICATIONS. CLEAN AND ROUGHEN TO 1/4" AMPLITUDE ALL CONCRETE
SURFACES AGAINST WHICH NEW CONCRETE IS TO BE PLACED.
9. ALL REINFORCING BARS, ANCHOR BOLTS AND OTHER CONCRETE INSERTS SHALL BE
WELL SECURED IN POSITION PRIOR TO PLACING CONCRETE.
10. PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL OPENINGS IN CONCRETE
BEFORE PLACING. DO NOT CUT ANY REINFORCING WHICH MAY CONFLICT. CORING IN
CONCRETE IS NOT PERMITTED. NOTIFY THE STRUCTURAL ENGINEER IN ADVANCE OF
CONDITIONS NOT SHOWN ON THE DRAWINGS. SEE THESE DRAWINGS FOR
ADDITIONAL RESTRICTIONS ON THE PLACEMENT OF OPENINGS IN SLABS AND WALLS.
11. PIPES LARGER THAN 1-1/2" DIAMETER SHALL NOT BE EMBEDDED IN STRUCTURAL
CONCRETE EXCEPT WHERE SPECIFICALLY APPROVED BY STRUCTURAL ENGINEER.
PIPES SHALL NOT DISPLACE OR INTERRUPT REINFORCING BARS, SPACE EMBEDDED
PIPES AND SLEEVES AT A MINIMUM OF 3 DIAMETERS ON CENTER.
12. CONCRETE FILL OVER METAL DECK SHALL BE SCREEDED TO A CONSTANT
THICKNESS AS SPECIFIED IN THE DECKING SCHEDULE.
3. WIND ANALYSIS PER CHAPTER 16A OF THE CODE
RISK CATEGORY = II
BASIC WIND SPEED = 96 mph
WIND EXPOSURE = C
SHEET INDEX
S-001 GENERAL NOTES
S-002 SPECIAL INSPECTION TABLES
S-101 PLANS
S-102 EQUIPMENT ANCHORAGE DETAILS
S-103 EQUIPMENT ANCHORAGE DETAILS
HILTI KB-TZ2 IN CONCRETE
SYMBOL UNITS
NOMINAL ANCHOR DIAMETER (IN)
1/4 3/8 1/2 5/8 3/4
NOMINAL BIT DIAMETER do in 1/4 3/8 1/2 5/8 3/4
EFFECTIVE MIN.
EMBEDMENT
hef in 1 1/2 1 1/2 2 2 1/2 1 1/2 2 2 1/2 3 1/4 2 3/4 3 1/4 4 3 1/4 3 3/4 4 3/4
NOMINAL EMBEDMENT hnom in 1 3/4 1 7/8 2 1/2 3 2 2 1/2 3 3 3/4 3 1/4 3 3/4 4 1/2 4 4 1/2 5 1/2
MINIMUM HOLE DEPTH ho in 2 2 2 3/4 3 1/4 2 1/4 2 3/4 3 1/4 4 1/4 3 3/4 4 1/4 4 3/4 4 1/4 4 3/4 5 3/4
FIXTURE HOLE DIAMETER dh in 5/16 7/16 9/16 11/16 13/16
MINIMUM CONCRETE
THICKNESS hmin in 3 1/4 3 1/4 4 5 3 1/2 4 5 5 1/2 5 5 1/2 6 5 1/2 6 8
HILTI KB-TZ2 - CARBON STEEL
SYMBOL UNITS
NOMINAL ANCHOR DIAMETER (IN)
1/4 3/8 1/2 5/8 3/4
EFFECTIVE MIN.
EMBEDMENT
hef in 1 1/2 1 1/2 2 2 1/2 1 1/2 2 2 1/2 3 1/4 2 3/4 3 1/4 4 3 1/4 3 3/4 4 3/4
INSTALLATION TORQUE Tinst ft-lb 4 30 50 40 110
MINIMUM EDGE
DISTANCE1
cmin in 1 1/2 5 2 1/2 2 1/2 8 2 3/4 2 3/4 2 1/4 4 1/2 3 1/2 2 3/4 5 4 3 1/2
MINIMUM SPACING 1 smin in 1 1/2 5 2 1/4 2 12 3 1/2 3 2 4 1/2 2 3/4 2 1/4 4 1/2 3 3/4 3 3/4
1 REFER TO ESR-4266, TABLE 3 FOR SPACING REQUIREMENTS FOR c min AND EDGE DISTANCE REQUIREMENTS FOR s min.
HILTI KB-TZ2 - STAINLESS STEEL
SYMBOL UNITS
NOMINAL ANCHOR DIAMETER (IN)
1/4 3/8 1/2 5/8 3/4
EFFECTIVE MIN.
EMBEDMENT
hef in 1 1/2 1 1/2 2 2 1/2 1 1/2 2 2 1/2 3 1/4 2 3/4 3 1/4 4 3 1/4 3 3/4 4 3/4
INSTALLATION TORQUE Tinst ft-lb 6 30 40 60 125
MINIMUM EDGE
DISTANCE1 cmin in 1 1/2 5 2 1/2 2 1/2 N/A 2 3/4 2 1/2 2 1/4 4 3 1/4 2 1/4 5 4 3 3/4
MINIMUM SPACING 1 smin in 1 1/2 5 2 1/4 2 1/4 N/A 2 3/4 2 1/2 2 5 1/2 2 3/4 3 5 4 4
1 REFER TO ESR-4266, TABLE 3 FOR SPACING REQUIREMENTS FOR c min AND EDGE DISTANCE REQUIREMENTS FOR s min.
STRUCTURAL STEEL
1. STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED BY AN
APPROVED AND LICENSED FABRICATOR IN ACCORDANCE WITH THE AISC
SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL
STEEL FOR BUILDINGS (LATEST EDITION), AND WITH CHAPTERS 17A AND 22A OF THE
CODE.
2. ALL STRUCTURAL STEEL SHALL CONFORM TO THE ASTM DESIGNATION AS INDICATED
BELOW (UNO):
ANGLES, CHANNELS, PLATES, BARS,
CONNECTION PLATES, AND MISC A36 (UNO)
HSS SECTIONS A500, GRADE C
BOLTS A325 (UNO)
3. THE STRUCTURAL STEEL FABRICATOR SHALL FURNISH SHOP DRAWINGS OF ALL STEEL
TO THE ARCHITECT FOR ARCHITECT'S AND STRUCTURAL ENGINEER'S REVIEW AND
APPROVAL BEFORE FABRICATION.
4. BOLT HOLES USED IN STEEL SHALL BE 1/16" LARGER IN DIAMETER THAN NOMINAL SIZE
OF BOLT USED, EXCEPT AS NOTED.
5. ALL WELDING IS TO BE DONE BY CERTIFIED WELDERS USING FILLER METALS TO
MATCH MATERIAL STRENGTH (UNO). ALL WELDS SHALL BE IN CONFORMITY WITH THE
PROJECT SPECIFICATIONS AND THE CODE FOR WELDING IN BUILDING CONSTRUCTION
(AWS D1.1 LATEST REVISION) OF THE AMERICAN WELDING SOCIETY. SEE SPECIAL
INSPECTIONS SECTION FOR WELDING INSPECTION REQUIREMENTS. USE OF E70T-4
WIRE IS NOT PERMITTED.
6. WHERE FABRICATION OF STRUCTURAL LOAD-BEARING MEMBERS AND ASSEMBLIES IS
BEING PERFORMED ON THE PREMISES OF FABRICATOR'S SHOP, SPECIAL INSPECTION
OF THE FABRICATED ITEMS SHALL BE REQUIRED.
7. SPECIAL INSPECTIONS ARE NOT REQUIRED WHERE THE WORK IS DONE ON THE
PREMISES OF A FABRICATOR REGISTERED AND APPROVED TO PERFORM SUCH WORK
WITHOUT SPECIAL INSPECTION BY AN APPROVED SPECIAL INSPECTION AGENCY.
APPROVAL SHALL BE BASED ON SECTION 1704A.2.5 OF THE CODE. AT COMPLETION OF
FABRICATION, THE APPROVED FABRICATOR SHALL SUBMIT A CERTIFICATE OF
COMPLIANCE TO THE BUILDING OFFICIAL STATING THAT THE WORK WAS PERFORMED
IN ACCORDANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS.
8. WELD LENGTHS CALLED FOR ON PLANS ARE THE NET EFFECTIVE LENGTH REQUIRED.
WHERE FILLET WELD SYMBOL IS GIVEN WITHOUT INDICATION OF SIZE, USE MINIMUM
SIZE WELDS AS SPECIFIED IN AISC 360-10 SECTION J2.2b.
9. ALL EXPOSED STRUCTURAL STEEL AND MISCELLANEOUS METAL SHALL BE HOT DIP
GALVANIZED AFTER FABRICATION UNO.
10. BEAM COPES AND WELD ACCESS HOLES SHALL COMPLY WITH AISC 360-10 SECTION
J1.6.
11. ALL WELD MATERIAL SHALL COMPLY WITH AISC 360-10 SECTION J2.6.
12. THE THERMAL CUTTING OF ALL MEMBERS SHALL COMPLY WITH AISC 360-10 SECTION
M2.2.
13. NON-DESTRUCTIVE ULTRASONIC TESTING SHALL BE REQUIRED ON 100% OF CJP
GROOVE WELDS IN MATERIAL 5/16" THICK AND GREATER.
FOUNDATION
1. ALLOWABLE SOIL PRESSURE AND LATERAL EARTH PRESSURE BASED ON CODE
PRESCRIBED VALUES IN ACCORDANCE WITH CHAPTER 18A TABLE 1806.2 OF THE
CODE.
2. FOOTINGS ARE DESIGNED BASED ON THE FOLLOWING INFORMATION:
ALLOWABLE BEARING *
1,500 PSF
3. CONTRACTOR TO PROVIDE FOR DE-WATERING OF EXCAVATIONS FROM EITHER
SURFACE WATER, GROUND WATER OR SEEPAGE, IF REQUIRED.
4. CONTRACTOR SHALL PROVIDE FOR DESIGN AND INSTALLATION OF ALL CRIBBING,
SHEATHING AND SHORING REQUIRED AND SHALL BE SOLELY RESPONSIBLE FOR
ALL EXCAVATION PROCEDURES INCLUDING LAGGING, SHORING AND PROTECTION
OF ADJACENT PROPERTY, STRUCTURES, STREETS AND UTILITIES IN ACCORDANCE
WITH ALL NATIONAL, STATE AND LOCAL SAFETY ORDINANCES.
5. EXCAVATION FOR FOOTINGS SHALL BE APPROVED BY THE INSPECTOR OR SOILS
ENGINEER PRIOR TO PLACING THE CONCRETE AND REINFORCING. CONTRACTOR
TO NOTIFY THE INSPECTOR WHEN INSPECTION OF EXCAVATION IS READY.
INSPECTOR TO SUBMIT LETTER OF COMPLIANCE.
6. ALL EXCAVATIONS SHALL BE PROPERLY BACKFILLED. DO NOT PLACE BACKFILL
BEHIND RETAINING WALLS BEFORE CONCRETE OR GROUT HAS ATTAINED FULL
DESIGN STRENGTH. CONTRACTOR SHALL BRACE OR PROTECT ALL BUILDING AND
PIT WALLS BELOW GRADE FROM LATERAL LOADS UNTIL ATTACHING FLOORS ARE
COMPLETELY IN PLACE AND HAVE ATTAINED FULL STRENGTH. CONTRACTOR
SHALL PROVIDE FOR DESIGN, PERMITS, AND INSTALLATION OF SUCH BRACING.
7. FOUNDATIONS SHALL BE PLACED AND ESTIMATED ACCORDING TO DEPTHS
SHOWN ON DRAWINGS. SHOULD SOIL ENCOUNTERED AT THESE DEPTHS NOT BE
APPROVED BY THE INSPECTOR OR SOILS ENGINEER, FOUNDATION ELEVATIONS
WILL BE ALTERED BY CHANGE ORDER.
8. FOOTING BACKFILL AND UTILITY TRENCH BACKFILL WITHIN BUILDING AREA SHALL
BE MECHANICALLY COMPACTED IN LAYERS IN ACCORDANCE WITH THE SOILS
REPORT AND APPROVED BY THE SOILS ENGINEER. FLOODING WILL NOT BE
PERMITTED. ALL FILLS USED TO SUPPORT FOUNDATIONS SHALL BE INSPECTED BY
THE SOILS ENGINEER REPRESENTATIVE PER CODE SECTION 1705A.6 AND TABLE
1705.6
9. ALL ABANDONED FOOTINGS, UTILITIES, ETC., SHALL BE REMOVED UNLESS NOTED
OTHERWISE. NEW FOOTINGS MUST EXTEND INTO UNDISTURBED SOILS.
10. SLABS ON GRADE SHALL BE SUPPORTED ON NATURAL GRADE OR COMPACTED
FILL AS PER THE RECOMMENDATIONS OF THE SOILS REPORT.
REINFORCING STEEL (FOR CONCRETE AND MASONRY)
1. REINFORCING BARS SHALL CONFORM TO THE REQUIREMENTS OF CHAPTER 19 & 21
OF THE CODE, ASTM A615, GRADE 60 UNO.
2. BARS SHALL BE CLEAN OF RUST, GREASE, OR OTHER MATERIALS LIKELY TO IMPAIR
BOND. ALL REINFORCING BAR BENDS SHALL BE MADE COLD.
3. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185. WWF SHALL BE
SUPPORTED ON APPROVED CHAIRS.
4. REINFORCING BAR SPLICES SHALL BE MADE AS INDICATED ON THE DRAWINGS. LAP
ALL HORIZONTAL BARS AT CORNERS AND INTERSECTIONS. STAGGER ALL SPLICES
UNLESS NOTED OTHERWISE ON PLANS.
5. ALL BARS SHALL BE MARKED SO THEIR IDENTIFICATION CAN BE MADE WHEN THE
FINAL IN-PLACE INSPECTION IS MADE.
6. WHERE WELDING OF REINFORCING IS APPROVED BY THE STRUCTURAL ENGINEER,
IT SHALL BE DONE BY AWS CERTIFIED WELDERS USING FILLER MATERIAL TO
MATCH MATERIAL STRENGTHS. WELDING PROCEDURES SHALL CONFORM TO THE
REQUIREMENTS OF STRUCTURAL WELDING CODE- REINFORCING STEEL",
AWS-D1.4, LATEST REVISION. REINFORCING BARS TO BE WELDED SHALL CONFORM
TO THE REQUIREMENTS OF ASTM A706.
7. BARS IN SLABS SHALL BE SECURELY SUPPORTED ON WELL-CURED CONCRETE
BLOCKS OR APPROVED METAL CHAIRS, PRIOR TO PLACING CONCRETE.
8. REINFORCING STEEL SHALL BE DETAILED IN ACCORDANCE WITH THE "A.C.I.
MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE
STRUCTURES", LATEST EDITION.
9. COMPLETE AND DETAILED REINFORCING PLACEMENT DRAWINGS SHALL BE
PREPARED AND SUBMITTED TO THE ARCHITECT FOR APPROVAL BY THE
STRUCTURAL ENGINEER PRIOR TO FABRICATION IN ACCORDANCE WITH THE
SPECIFICATIONS AND APPLICABLE CODES. THESE DRAWINGS SHALL BE AVAILABLE
ON THE JOB SITE PRIOR TO PLACING OF CONCRETE.
10. MILL TEST REPORTS FOR GRADE 60 BARS SHALL BE SUBMITTED PRIOR TO
PLACEMENT OF CONCRETE.
11. PROVIDE INSPECTION OF CONCRETE PER SPECIAL INSPECTION NOTES SECTION.
INSPECTION SHALL BE SCHEDULED SO THAT PLACEMENT OF REINFORCING STEEL,
CONDUIT, SLEEVES, AND EMBEDDED ITEMS MAY BE CORRECTED PRIOR TO
PLACEMENT OF OVERLYING GRIDS OR REINFORCING STEEL.
12. ALL GRADE 60 REINFORCING STEEL SHALL BE CLEARLY MARKED TO
DIFFERENTIATE THEM FROM GRADE 40 REINFORCING STEEL IF CONCURRENTLY ON
SITE.
13. CONCRETE PROTECTION FOR REINFORCEMENT:
CONCRETE
EXPOSURE
MEMBER REINFORCEMENT
MIN COVER,
IN.
EXPOSED TO
WEATHER OR IN
CONTACT WITH
GROUND
No. 6 THROUGH No.
18 BARS
NOT EXPOSED
TO WEATHER OR
IN CONTACT
WITH GROUND
SLABS, JOISTS
AND WALLS
BEAMS,
COLUMNS,
PEDESTALS, AND
TENSION TIES
PRIMARY REINFORCEMENT,
STIRRUPS, TIES, SPIRALS,
AND HOOPS
CAST-IN-PLACE NONPRESTRESSED CONCRETE MEMBERS
ALL
No. 5 BAR, W31 OR D31
WIRE, AND SMALLER
1-1/2No. 14 AND No. 18 BARS
1-1/2
CAST AGAINST AND
PERMANENTLY IN
CONTACT WITH
GROUND
ALL ALL 3
3/4No. 11 BAR AND SMALLER
1-1/2
EXPANSION ANCHORS
1. ANCHOR DIAMETER REFERS TO THE ANCHOR SIZE AND NOT THE DIAMETER
OF THE DRILLED HOLE.
2. ALL ANCHORS SHOULD MEET THE MINIMUM EMBEDMENT, EDGE DISTANCE,
SPACING AND SLAB THICKNESS CRITERIA ESTABLISHED BY THE RELEVANT
ICC-ES EVALUATION REPORT.
3. ACCEPTABLE MANUFACTURERS FOR EXPANSION ANCHORS ARE AS FOLLOWS:
CONCRETE MASONRY UNITS (CMU):
HILTI KWIK BOLT TZ2 (KB-TZ2) (ICC ESR-4561).
SIMPSON WEDGE-ALL (ICC ESR-1396).
CONCRETE:
HILTI KWIK BOLT TZ2 (KB-TZ2) (ICC ESR-4266).
SIMPSON STRONG-BOLT 2 (ICC ESR-3037).
4. DO NOT LOCATE EXPANSION ANCHORS CLOSER TO EDGE OF
CONCRETE/MASONRY OR TO CONTROL/CONSTRUCTION JOINTS THAN THE
MIN…