Plans.pdf
PDF 9 MB Posted
- Solicitation number
- 0000039304
- Issued by
- Contra Costa County, Contra Costa Centre CDP, California
About this file
This is a set of architectural and engineering plans for an electric vehicle supply equipment (EVSE) Level II installation project submitted by the State of California Department of General Services (DGS) Real Estate Services Division in coordination with the Contra Costa County Department of General Services and the California Department of Public Health (CDPH). The project involves installing new EVSE charging infrastructure at 850 Marina Bay Parkway in Richmond, California. The scope of work includes the installation of 21 dual-port and single-port EVSE pedestals distributed across two areas (Area A with 11 chargers providing 20 charging spaces, and Area B with 10 chargers providing 20 charging spaces), along with associated electrical infrastructure including switchgear, panelboards, conduit systems, and grounding systems. The plans were approved by the Division of the State Architect (DSA) on September 11, 2025, with fire and panic approval from the Office of the State Fire Marshal dated May 5, 2025. The project number is 000000000012567, and SFM Application Number is 25-N-1087. The plans are at 95% completion for client review, dated February 13, 2025, with a civil expiration date of June 30, 2026.
The project encompasses comprehensive structural, electrical, and civil engineering design. The electrical work includes two main distribution areas fed from transformer banks (Area A from T-D4 12.47 KV-480/277V with a 3200-ampere bus, and Area B from MS-D4 480/277V with a 1200-ampere bus), with feeder schedules, panel schedules, voltage drop calculations, and load summaries specified for each area. Structural elements include transformer and panelboard foundations with reinforced concrete construction, anchor bolt specifications using ASTM standards, and permanent bollard and conduit installations. The site work includes demolition planning, improvement plans with accessible routes, ADA parking modifications, and parking space markings designating the new EV charging-only spaces. The design team includes a structural engineer (Ibrahim Shanah), civil engineer/designer (Chris Martinez), electrical engineer (Jon Alvarez), and electrical designer (Darsh Tanna), with overall project management by Ryan Allgood and Janelle Goulding from DGS. All work must comply with the 2021 California Building Code, relevant ASTM and ACI standards, and California Fire Code requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid_Package.pdf | ||
| Project_Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
850 MARINA BAY PARKWAY,
RICHMOND, CA 94804
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Ryan Allgood Phone 916-375-4115
RYAN.ALLGOOD@DGS.CA.GOV
JADT DT WP
EVSE LEVEL II
CDPH
CONTRA COSTA COUNTY
DEPARTMENT OF
GENERAL SERVICES
TITLE SHEET
E1.0
PROJECT LOCATION
CODES AND PREFERENCES SHEET INDEX
SYMBOLS AND ABBREVIATIONS
EVSE DESCRIPTION SCOPE OF WORK
EXISTING EVSE SPACES NEW EVSE SPACES
FLEET WORKPLACE WORKPLACEFLEET
0 02/13/25 95%CD CLIENT REVIEW
V1
000000000012567
TOTAL SHEET COUNT:14
SFM APPLICATION NUMBER: 25-N-1087
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
05/05/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1087
TEAM DIRECTORY:
ELECTRICAL ENGINEER: JON ALVAREZ: 916-214-8352
ELECTRICAL DESIGNER;DARSH TANNA-279-272-1838
CIVIL ENGINEER/DESIGNER:CHRIS MARTINEZ:714-337-2506
STRUCTURAL ENGINEER: IBRAHIM SHANAH:916-947-0505
E2.3 ELECTRICAL DETAILS
C1.0 DEMOLITION PLAN
DSA APPLICATION NUMBER: 02_123468
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-123468
09/11/2025
CDPH - Electric Vehicle Supply Equipment - Richmond
PROJECT NUMBER: 000000000012567; 05/15/26
Know what's below.
before you dig.Call
850 MARINA BAY PARKWAY,
RICHMOND, CA 94804
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Janelle Goulding Phone 916-823-7059
RYAN.ALLGOOD@DGS.CA.GOV
KKLG JA WP
EVSE LEVEL II
CDPH
CONTRA COSTA COUNTY
DEPARTMENT OF
GENERAL SERVICES
E1.1
N/A
N/A
480/277V SWITCHGEAR, NEMA 1 3Ø, 4W, 60HZ
(E) MS-D4
PB-EV AREA- A
NEMA 3R
800A, 208Y/120V, 3Ø, 4W, 60HZ
3200A BUS, 480/277V, 3Ø, 4W, 60HZ
EXIST.
LOAD
EXIST.
LOAD
EXIST.
LOAD
EXIST.
LOAD
350A 3P
800A
T-EV AREA-A
SINGLE LINE DIAGRAM
AREA "A"
PANEL SCHEDULE AREA- A
FEEDER SCHEDULE AREA- A
PROPOSED CHARGERS AREA -A
VOLTAGE DROP CALCUALTIONS AREA-A
LOAD SUMMARY
SINGLE LINE
DIAGRAM AND
SCHEDULES AREA-A
FED FROM TRANSFORMER BANK T-D4 12.47 KV-480/277V
3200A/3P
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
05/05/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1087
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-123468
09/11/2025
Know what's below.
before you dig.Call
850 MARINA BAY PARKWAY,
RICHMOND, CA 94804
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Janelle Goulding Phone 916-823-7059
RYAN.ALLGOOD@DGS.CA.GOV
KKLG JA WP
EVSE LEVEL II
CDPH
CONTRA COSTA COUNTY
DEPARTMENT OF
GENERAL SERVICES
E1.2
N/A
N/A
480/277V PANELBOARD, NEMA 1 3Ø, 4W, 60HZ
(E) DP-4
PB-EV AREA- B
NEMA 3R
800A, 208Y/120V, 3Ø, 4W, 60HZ
1200A BUS, 480/277V, 3Ø, 4W, 60HZ
EXIST.
LOAD
EXIST.
LOAD
EXIST.
LOAD
EXIST.
LOAD
350A 3P
800A
T-EV AREA-B
SINGLE LINE DIAGRAM
AREA "B"
PANEL SCHEDULE AREA- B
FEEDER SCHEDULE AREA- B
LOAD SUMMARY AREA- B
PROPOSED CHARGERS AREA- B
VOLTAGE DROP CALCULATIONS AREA- B
SINGLE LINE
DIAGRAM AND
SCHEDULES AREA-B
FED FROM MS-D4 480/277V, 3Ø, 4W, 60HZ
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
05/05/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1087
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-123468
09/11/2025
NO
PARKING
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARG ING
ONLY
EV
CHARGING
ONLY
EV
CHARG ING
ONLY
EV
CH ARGING
ON LY
EV
CHARG ING
ONLY
EV
CH ARGING
ON LY
EV
CHARG ING
ON LY
EV
CH ARGING
ON LY
EV
CHAR G ING
ONLY
EV
CHARGING
ONLY
EV
CHARG ING
ONLY
EV
CHARG ING
ONLY
EV
C HARG ING
ONLY
EV
CHARG ING
ONLY
EV
CHARG ING
ONLY
EV
CHARG ING
ONLY
EV
CHARG ING
ONLY
G
G G
G
G G
Know what's below.
before you dig. Call
850 MARINA BAY PARKWAY,
RICHMOND, CA 94804
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Ryan Allgood Phone 916-375-4115
RYAN.ALLGOOD@DGS.CA.GOV
JADT DT WP
EVSE LEVEL II
CDPH
CONTRA COSTA COUNTY
DEPARTMENT OF
GENERAL SERVICES
DRAWING LIMITS
LABORATORY D
CONT. TO
ELECTRICAL ROOM
MS-D4
E1.3
1/16'=1'-0"
V1
(TYP)
T-EV AREA-A
ELECTRICAL SITE
PLAN AREA-A
EVSE -1
1 & 2
EVSE -2
3 & 4
EVSE -3
5 & 6
EVSE -4
7 & 8
EVSE -5
9 & 10
EVSE -6
11 & 12
EVSE -7
13 & 14
EVSE -8
15 & 16
EVSE -9
17 & 18
EVSE -10
EVSE -11
NEW EVSE DUAL PORT PEDESTAL
PB-EV AREA-A
NEW EVSE SINGLE PORT PEDESTAL
000000000012567
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
05/05/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1087
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-123468
09/11/2025
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
G
G G
G
G G
NEW EVSE DUAL PORT PEDESTAL
PB-EV AREA-B
(TYP)
(TYP)
(TYP)
(TYP)
Know what's below.
before you dig. Call
850 MARINA BAY PARKWAY,
RICHMOND, CA 94804
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Ryan Allgood Phone 916-375-4115
RYAN.ALLGOOD@DGS.CA.GOV
JADT DT WP
EVSE LEVEL II
CDPH
CONTRA COSTA COUNTY
DEPARTMENT OF
GENERAL SERVICES
DRAWING LIMITS
OFFICE P
(E) PB
(E) PB
(E) U/G 3" SPARE CONDUIT
CONT. TO
ELECTRICAL ROOM
DP-4
E1.4
1/16'=1'-0"
V1
ELECTRICAL SITE PLAN
AREA - B
T-EV AREA-B
EVSE -12
21 & 22
EVSE -13
23 & 24
EVSE -14
25 & 26
EVSE -15
27 & 28
EVSE -16
29 & 30
EVSE -17
31 & 32
EVSE -18
33 & 34
EVSE -19
35 & 36
EVSE -20
37 & 38
EVSE -21
39 & 40
(TYP )
000000000012567
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
05/05/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1087
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-123468
09/11/2025
SPECIAL INSPECTIONS REQUIRED
CONCRETE CONSTRUCTION:
STEEL CONSTRUCTION:
GENERAL NOTES:
850 MARINA BAY PARKWAY,
RICHMOND, CA 94804
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Ryan Allgood Phone 916-375-4115
RYAN.ALLGOOD@DGS.CA.GOV
JADT DT WP
EVSE LEVEL II
CDPH
CONTRA COSTA COUNTY
DEPARTMENT OF
GENERAL SERVICES
E2.0
NONE
GENERAL NOTES
02/13/250 95%CD CLIENT REVIEW
V1
000000000012567
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
05/05/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1087
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-123468
09/11/2025
CONDUIT TRENCH HANDHOLES
PERMANENT BOLLARD
E2.1
NONE
ELECTRICAL DETAILS
850 MARINA BAY PARKWAY,
RICHMOND, CA 94804
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Ryan Allgood Phone 916-375-4115
RYAN.ALLGOOD@DGS.CA.GOV
JADT DT WP
EVSE LEVEL II
CDPH
CONTRA COSTA COUNTY
DEPARTMENT OF
GENERAL SERVICES
CONDUIT STUB-UP4' LONG WHEEL STOP
EVCS FLEET SIGNAGE
CONCRETE
CURB
EVSE PER
PLAN
PROPOSED OSHA
SAFETY GREEN 14120
STRIP
MIN. 12" HIGH WHITE LETTERS,
WITHIN 6" OF THE STALL
CENTERLINE AND ALIGNED AT THE
BOTTOM OF THE PARKING STALL
WHEELSTOP PER
PLAN
02/13/250 95%CD CLIENT REVIEW
V1
000000000012567
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
05/05/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1087
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-123468
09/11/2025
FLEET EVSE SIGNAGE
E2.2
NONE
ELECTRICAL DETAILS
850 MARINA BAY PARKWAY,
RICHMOND, CA 94804
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Ryan Allgood Phone 916-375-4115
RYAN.ALLGOOD@DGS.CA.GOV
JADT DT WP
EVSE LEVEL II
CDPH
CONTRA COSTA COUNTY
DEPARTMENT OF
GENERAL SERVICES
GROUND WELL
GROUND ROD CONNECTION
1" MIN., 2" MAX. FROM
SOIL. CONDUCTOR SHALL BE
CONTINUOUS; COORDINATE
WITH STRUCTURAL.
#4/0 AWG BARE COPPER.
SLAB CONSTRUCTION
(SEE STRUCTURAL DETAILS)
BARE COPPER CONDUCTOR
REFERENCE GROUND BUS
MAIN BUILDING
20 FEET MIN. #4/0
RIGID NON-METALLIC CONDUIT
BARRIER PROHIBITED
BED OR VAPOR
W/EARTH; DRY GRAVEL
IN DIRECT CONTACT
CONC. FOUNDATION
2" MIN
BOND TO GROUND RING 36" BELOW GRADE
UNLESS OTHERWISE NOTED. SEE DETAILS 7 AND 8
SHEET E06-600.
BOND TO GROUND RING
G G G G G G G
G
UFER GROUNDING ELECTRODE
EVSE WORKPLACE SIGNAGE
02/13/250 95%CD CLIENT REVIEW
V1
000000000012567
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
05/05/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1087
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-123468
09/11/2025
E2.3
NONE
ELECTRICAL DETAILS
850 MARINA BAY PARKWAY,
RICHMOND, CA 94804
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Ryan Allgood Phone 916-375-4115
RYAN.ALLGOOD@DGS.CA.GOV
JADT DT WP
EVSE LEVEL II
CDPH
CONTRA COSTA COUNTY
DEPARTMENT OF
GENERAL SERVICES
FIREWALL PENETRATION
Hilti Firestop Systems
System No. W-L-1054
SECTION A-A
W L
A
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 21, 2020
A
1A
2 1B
C
C
LA
SSIFIED
R
Classified by Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Ratings —1 and 2 Hr (See Items 1 and 3) F Ratings — 1 and 2 Hr (See Items 1 and 3)
T Rating — 0 Hr FT Rating — 0 Hr
L Rating (Without Movement) at Ambient — Less Than 1 CFM/sq ft
FH Ratings —1 and 2 Hr (See Items 1 and 3)
L Rating (Without Movement) at 400°F — Less Than 1 CFM/sq ft
FTH Rating — 0 Hr
M Rating (Movement) — See Table 1 FTH Rating — 0 Hr
L Rating at Ambient — Less Than 5.1 L/s/m2
L Rating at 204°C — Less Than 5.1 L/s/m2
Page: 1 of 2
1. Wall Assembly — The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC. For M Rating, steel studs to be min 3-5/8 in. (92 mm) wide. When steel studs are used and the diam of opening exceeds the width of stud cavity, the opening shall be framed on all sides using lengths of steel stud installed between the vertical studs and screw-attached to the steel studs at each end. The framed opening in the wall shall be 4 to 6 in. (102 to 152 mm) wider and 4 to 6 in. (102 to 152 mm) higher than the diam of the penetrating item such that, when the penetrating item is installed in the opening, a 2 to 3 in. (51 to 76 mm) clearance is present between the penetrating item and the framing on all four sides.
B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (122 cm) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 32-1/4 in. (819 mm) for steel stud walls. Max diam of opening is 14-1/2 in. (368 mm) for wood stud walls.
The F and FH Ratings of the firestop system are equal to the fire rating of the wall assembly. The M Rating is applicable only to 1 hr rated walls.
Hilti Firestop Systems Page: 2 of 2
W L
System No. W-L-1054
2. Through-Penetrants — One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space shall be min 0 in. to max 2-1/4 in. (57 mm). Pipe may be installed with continuous point contact. Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe — Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe.
C. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or 6 in. (152 mm) . diam steel conduit.
D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.
E. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) regular (or heavier) copper pipe.
3. Fill, Void or Cavity Material* — Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall.
At the point or continuous contact locations between pipe and wall, a min 1/2 in. (13 mm) diam bead of fill material shall be applied at the pipe wall interface on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE MAX Intumescent Sealant
Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.
January 21, 2020
Movement Direction
Penetrant Item
Nominal Penetrant Diameter
Annular
Space Movement Sealant Depth F-Rating L Rating with Movement
Y 2A, 2C* 2 in. Max 2-1/4 in. 5% 5/8 in. 1 hr N/A
Z 2A, 2C* 2 in. 2-1/4 in. 0.25 in. 5/8 in. 1 hr N/A
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
V1
000000000012567
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
05/05/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1087
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-123468
09/11/2025
P 1
850 MARINA
BAY PARKWAY
P
4 4
P1 1
DEMOLITION NOTES
DEMOLITION LEGEND
Know what's below.
before you dig.Call
850 MARINA BAY PARKWAY,
RICHMOND, CA 94804
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Ryan Allgood Phone 916-375-4115
RYAN.ALLGOOD@DGS.CA.GOV
JASWHSWHWP
EVSE LEVEL II
CDPH
CONTRA COSTA COUNTY
DEPARTMENT OF
GENERAL SERVICES
02/13/25 95% CD CLIENT REVIEW0
1''=10'
C1.0
DEMOLITION PLAN
N
CIVIL
EXP. 6-30-26
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-123468
09/11/2025
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans shall be available on the project site at all times.
05/05/25
OFFICE OF THE STATE FIRE MARSHAL
APPROVED FIRE AND PANIC ONLY
25-1087
CDPH - Electric Vehicle Supply Equipment - Richmond
PROJECT NUMBER: 000000000012567; 05/15/26
rallgood Rectangle
850 MARINA
BAY PARKWAY
NO
PARKING
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
CONSTRUCTION NOTES
PAVING LEGEND
NO
PARKING
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
Know what's below.
before you dig.Call
850 MARINA BAY PARKWAY,
RICHMOND, CA 94804
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Ryan Allgood Phone 916-375-4115
RYAN.ALLGOOD@DGS.CA.GOV
JASWHSWHWP
EVSE LEVEL II
CDPH
CONTRA COSTA COUNTY
DEPARTMENT OF
GENERAL SERVICES
02/13/25 95% CD CLIENT REVIEW0
1''=10'
C2.0
IMPROVEMENT PLAN
N
½” ¼”
ACCESSIBLE ROUTE SITE PLAN
850 MARINA BAY PARKWAY
LAB D
850 MARINA BAY
PARKWAY
OFFICE G
ADA PARKING SUMMARY TABLE
EXISTING: PROPOSED:
850 MARINA BAY
PARKWAY,
RICHMOND, CA 94804
EV ADA PARKING SUMMARY TABLE
PROPOSED:
850 MARINA BAY
PARKWAY,
RICHMOND, CA 94804
CIVIL
EXP. 6-30-26
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-123468
09/11/2025
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans shall be available on the project site at all times.
05/05/25
OFFICE OF THE STATE FIRE MARSHAL
APPROVED FIRE AND PANIC ONLY
25-1087
CDPH - Electric Vehicle Supply Equipment - Richmond
PROJECT NUMBER: 000000000012567; 05/15/26
N
NTS
C3.0
DETAILS
LC
EV
CHARGING
ONLY
EV
CHARGING
ONLY
9' min12' min
5' min
' m in fu ll re qu ire d le ng th o f ch ar gi ng s pa ce
EV
CHARGING
ONLY
NO
PARKING
EV
CHARGING
ONLY
850 MARINA BAY PARKWAY,
RICHMOND, CA 94804
State of California
Department of General Services Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105 West Sacramento, California 95605
Ryan Allgood Phone 916-375-4115
RYAN.ALLGOOD@DGS.CA.GOV
JASWHSWHWP
EVSE LEVEL II
CDPH
CONTRA COSTA COUNTY
DEPARTMENT OF
GENERAL SERVICES
02/13/25 95% CD CLIENT REVIEW0
EV
CHARGING
ONLY
NO
PARKING
CIVIL
EXP. 6-30-26
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-123468
09/11/2025
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans shall be available on the project site at all times.
05/05/25
OFFICE OF THE STATE FIRE MARSHAL
APPROVED FIRE AND PANIC ONLY
25-1087
CDPH - Electric Vehicle Supply Equipment - Richmond
PROJECT NUMBER: 000000000012567; 05/15/26
X-X
VII. REINFORCING STEEL:
1. REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615, GRADE 60.
2. REINFORCING STEEL FOR CAST-IN-PLACE NONPRESTRESSED CONCRETE MEMBERS SHALL HAVE THE
FOLLOWING CONCRETE COVER, SEE ACI 117 FOR TOLERANCES.
A. CONCRETE EXPOSED TO EARTH OR IN CONTACT WITH GROUND:
a. CAST AGAINST AND PERMANENTLY IN CONTACT WITH EARTH 3"
b. EXPOSED TO WEATHER OR IN CONTACT WITH EARTH (#5 AND SMALLER) 1-1/2"
c. EXPOSED TO WEATHER OR IN CONTACT WITH EARTH (#6 AND LARGER) 2"
B. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:
a. SLABS, JOISTS AND WALLS (#11 AND SMALLER) 3/4"
b. SLABS, JOISTS AND WALLS (#14 AND LARGER) 1-1/2"
c. BEAMS, COLUMNS AND PEDESTALS 1-1/2"
3. BAR SPLICES MAY BE DELETED AND CONTINUOUS REINFORCING USED AT CONTRACTORS OPTION. BAR SPLICES SHALL BE MADE AT POINTS OF MINIMUM STRESS. IN FRAMED BEAMS AND SLABS SPLICE TOP
BARS AT MID-SPAN, BOTTOM BARS OVER SUPPORTS.
4. ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE WITH ACI 318 AND THE
'MANUAL OF STANDARD PRACTICE' BY CRSI AS MODIFIED BY THE CONTRACT DOCUMENTS.
5. FIELD BENDING OF REINFORCEMENT SHALL NOT BE PERMITTED WITHOUT SEOR APPROVAL. ALL
REINFORCING BENDS SHALL BE MADE COLD.
IV. REINFORCED CONCRETE:
1. CONCRETE CONSTRUCTION SHALL CONFORM TO ACI 318 AND ACI 301 WITH MODIFICATIONS AS NOTED
ON THE CONTRACT DOCUMENTS.
2. CONCRETE MIXES SHALL BE DESIGNED BY A QUALIFIED TESTING LABORATORY AND BEAR THE WET SEAL OF A CIVIL ENGINEER LICENSED IN THE STATE OF THE PROJECT AND BE PROVIDED TO THE SEOR FOR REVIEW. EACH MIX DESIGN SHALL BEAR THE NAME OF THE PROJECT AND THE SPECIFIC USE.
3. CONCRETE MODULUS OF ELASTICITY SHALL MEET THE MINIMUM PROVIDED IN ACI 318 SECTION 19.2.2 FOR THE 28-DAY STRENGTH SPECIFIED BELOW. TEST SHALL BE IN ACCORDANCE WITH ASTM C469.
4. CONCRETE SHALL HAVE THE FOLLOWING ULTIMATE COMPRESSIVE STRENGTH AT 28 DAYS.
LOCATION STRENGTH, f'c CONCRETE TYPE
A. FOUNDATIONS 4,000 PSI* NORMAL WEIGHT
* INDICATES FOOTING DESIGNED FOR F'c = 2,500 PSI THEREFORE SPECIAL INSPECTIONS NOT
REQUIRED
1. PORTLAND CEMENT SHALL CONFORM TO ASTM C150, TYPE I OR II. CONCRETE EXPOSED TO SOILS
CONTAINING CORROSIVE ELEMENTS (SULFATES) SHALL COMPLY WITH CBC 1904.1.
2. FLY ASH MAY BE USED AS A SUBSTITUTE FOR PORTLAND CEMENT. WEIGHT OF FLY ASH SHALL NOT EXCEED 15% OF CEMENT WEIGHT. FLY ASH SHALL CONFORM TO ASTM C618 CLASS F AND LOSS OF
IGNITION SHALL BE LIMITED TO 2%.
3. MIXING OPERATIONS SHALL CONFORM TO ASTM C94.
4. ALL CONCRETE NOT IN CONTACT WITH EARTH TO HAVE FINISH AS SPECIFIED BY ARCHITECT OR AS
COVERED IN PROJECT SPECIFICATIONS. UNLESS OTHERWISE NOTED, NON-ARCHITECTURAL
CONCRETE COLUMNS AND WALLS SHALL HAVE 3/4”CHAMFERED CORNERS.
5. AGGREGATE FOR NORMALWEIGHT CONCRETE SHALL CONFORM TO ALL REQUIREMENTS AND TESTS
OF ASTM C33 AND PROJECT SPECIFICATIONS.
6. ALL CONCRETE SHALL BE REINFORCED. PROVIDE MINIMUM TEMPERATURE REINFORCEMENT AS REQUIRED BY ACI-318 IN ELEMENTS WHERE NO REINFORCEMENT IS INDICATED ON THE DRAWINGS.
7. DRY PACK OR GROUT UNDER BASE PLATES AND SILL PLATES SHALL BE 7000 PSI MIN AT 28 DAYS.
8. CONCRETE PLACEMENT SHALL CONFORM TO ACI 304 AND PROJECT SPECIFICATIONS. SANDBLAST ALL
CONCRETE SURFACES WHICH NEW CONCRETE WILL BE PLACED AGAINST.
9. TWO HOURS MUST ELAPSE BETWEEN END OF COLUMN OR WALL POURS AND THE BEGINNING OF
FLOOR POURS.
10. ALL REINFORCEMENT, ANCHOR BOLTS AND OTHER EMBEDDED ITEMS SHALL BE SECURELY HELD IN PLACE WHILE CONCRETE IS POURED. ADDITIONAL BARS TO BE PROVIDED BY THE CONTRACTOR FOR
SUPPORT AS NEEDED.
11. MECHANICAL, ELECTRICAL AND PLUMBING OPENINGS AND SLEEVES ARE SHOWN INDICATIVELY AND
SMALL OPENINGS AND SLEEVES ARE NOT SHOWN. SEE SLAB EDGE, MECHANICAL, ELECTRICAL,
PLUMBING AND OTHER TRADES FOR SIZE AND LOCATION OF ALL SLAB AND WALL OPENINGS AND SLEEVES. CONTRACTOR TO DEVELOP AND SUBMIT A SINGLE COORDINATION DRAWING COMBINING ALL TRADES INDICATING ALL SLAB OPENINGS AND SLEEVES PRIOR TO POURING CONCRETE FOR REVIEW
BY STRUCTURAL ENGINEER.
12. ALL PIPE AND CONDUIT OPENINGS SHALL BE SLEEVED AND CAST IN PLACE UNLESS OTHERWISE
NOTED. DO NOT SAWCUT, CORE OR CORE DRILL STRUCTURAL CONCRETE WITHOUT EXPLICIT
DIRECTION FROM THE STRUCTURAL ENGINEER. DRILL BITS THAT CAN CUT OR DAMAGE REINFORCING
ARE NOT PERMITTED TO BE USED ON STRUCTURAL CONCRETE.
13. CONDUITS AND PIPES SHALL NOT BE PERMITTED IN STRUCTURAL CONCRETE ELEMENTS UNLESS SPECIFICALLY REVIEWED BY THE STRUCTURAL ENGINEER. ALL CONDUITS TO BE EMBEDDED IN THE
STRUCTURAL CONCRETE SHALL BE SUBMITTED FOR STRUCTURAL REVIEW ON A SINGLE
COORDINATED CONDUIT DRAWING COMBINING ALL TRADES DEVELOPED AND COORDINATED BY THE
CONTRACTOR. COORDINATED CONDUITS/PIPES MUST BE PLACED IN ONE LAYER AVOIDING
CROSSOVER AND SPACED AT THE GREATER OF 3" OR 3 DIAMETERS. DRAWINGS SHALL SHOW STUB-UP LOCATIONS, BEND RADIUS AND DETAILS OF CONDUIT/PIPE INSTALLATION. ALL CONDUITS AND PIPES
SHALL BE INSTALLED PER THE REQUIREMENTS OF ACI 318 SECTIONS 20.7 AND 26.8.2.
A. ELECTRICAL CONDUIT SHALL BE RIGID STEEL CONDUIT OR FLEXIBLE PLASTIC CONDUIT. ALUMINUM
CONDUIT IS PROHIBITED. CONDUIT OUTSIDE DIAMETER SHALL NOT EXCEED 2" OR 1/6 SLAB
THICKNESS, WHICHEVER IS LESSER. CONDUIT SHALL BE FIRMLY CHAIRED AND TIED TO PREVENT
DISPLACEMENT DURING POURING.
II. DESIGN LOADS:
1. DEAD LOAD: EQUIPMENT SELF WEIGHT.
2. WIND LOAD
A. ULTIMATE DESIGN BASIC WIND SPEED V(ult) = 92 MPH
B. WIND IMPORTANCE FACTOR = 1.00
C. WIND EXPOSURE CATEGORY = C
3. SEISMIC LOAD
A. SITE CLASS = D (DEFAULT)
B. RISK CATEGORY = II
C. SEISMIC IMPORTANCE FACTOR = 1.00
D. MAPPED SPECTRAL RESPONSE
a. SHORT PERIOD SS = 1.896 g
b. 1-SECOND PERIOD S1 = 0.724 g
E. DESIGN SPECTRAL RESPONSE (5% DAMPED)
a. SHORT PERIOD SDS = 1.517 g
I. GENERAL NOTES:
1. ALL STRUCTURAL WORK SHALL CONFORM TO THE DRAWINGS, THE PROJECT SPECIFICATIONS, ALL
DRAWING NOTES, AND THE 2021 CALIFORNIA BUILDING CODE (CBC).
2. ALL APPLICABLE REFERENCE STANDARDS, AS MODIFIED BY THE BUILDING CODE, INCLUDE:
A. ASCE/SEI 7-16: MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
B. ACI 318-19: BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
C. AISC 360-16: SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
D. ACI 117-10: STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE
CONSTRUCTION AND MATERIAL
E. AISI SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL
MEMBERS, 2016
3. THE SCOPE OF WORK IS NOT SOLELY DEFINED BY THESE DOCUMENTS.
4. TYPICAL DETAILS APPLY THROUGHOUT THE PROJECT, EVEN IF NOT SPECIFICALLY REFERENCED IN PLANS OR DETAILS. DETAILS OF CONSTRUCTION NOT FULLY SHOWN OR NOTED ON THE DRAWINGS NOR CALLED OUT IN THE SPECIFICATIONS SHALL BE OF THE SAME SIZE AND CHARACTER AS FOR
SIMILAR CONDITIONS WHICH ARE SHOWN AND NOTED.
5. ALL FORCES INDICATED IN THE STRUCTURAL DRAWINGS ARE SERVICE LOADS AS DEFINED BY ASCE-7, UNLESS NOTED OTHERWISE.
6. DO NOT USE SCALED DIMENSIONS; USE ONLY WRITTEN DIMENSIONS. WHERE NO DIMENSION IS
PROVIDED, CONSULT THE ARCHITECT FOR CLARIFICATIONS BEFORE PROCEEDING WITH WORK.
7. SEE ARCHITECTURAL DRAWINGS FOR SITE POSITIONING AND PROJECT DATUM, REFERENCE IS (0'-0")
AS SHOWN ON ARCHITECTURAL DRAWINGS.
8. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE CONDITIONS OF THE JOB SITE
INCLUDING SAFETY OF PERSONS AND PROPERTY AND THE MEANS AND METHODS OF CONSTRUCTION.
9. STRUCTURAL ELEMENTS SHALL BE CENTERED ABOUT GRIDLINES OR DIMENSION LINES, UNLESS
OTHERWISE NOTED.
10. THE CONTRACTOR SHALL PROVIDE ENGINEERED DESIGNS OF TEMPORARY SHORING AND BRACING AND MAKE SAFE ALL FLOORS, ROOFS, WALLS, EXCAVATIONS AND ADJACENT PROPERTY AS PROJECT
CONDITIONS AND LOCAL BUILDING CODE REQUIRE.
11. ALL STRUCTURAL WORK SHALL BE COORDINATED WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, ETC. REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS NOT
SHOWN ON PLAN. DISCREPANCIES AND/OR INTERFERENCES SHALL BE REPORTED TO THE ARCHITECT
IMMEDIATELY.
12. OPENINGS SHALL NOT BE MADE IN ANY STRUCTURAL MEMBER UNLESS SPECIFICALLY SHOWN ON THE
STRUCTURAL DRAWINGS OR APPROVED BY THE STRUCTURAL ENGINEER.
13. DEFICIENT WORK AND WORK NOT IN CONFORMANCE WITH THE CONTRACT DOCUMENTS AS IDENTIFIED
BY THE ARCHITECT OR INSPECTOR SHALL BE REPAIRED AT THE CONTRACTOR'S EXPENSE.
CONTRACTOR SHALL COMPENSATE OWNER FOR SERVICES ARISING FROM DEFICIENT WORK.
14. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ANY REQUIRED DEWATERING OF THE SITE
DURING CONSTRUCTION.
15. THE CONTRACTOR SHALL PREPARE ENGINEERED DESIGN AND SHALL BE RESPONSIBLE FOR
CONFIRMING ADEQUACY OF AS BUILT STRUCTURE FOR ALL SURCHARGE LOADS RESULTING FROM
COMPACTION AS WELL AS CRANES TRUCKS, BULLDOZERS OR ANY OTHER CONSTRUCTION
EQUIPMENT. ENGINEERED DESIGNS SHALL BE PREPARED, SIGNED AND SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE JURISDICTION AND SUBMITTED TO ENGINEER OF RECORD FOR REVIEW.
16. THE STRUCTURAL COMPONENTS BY THEMSELVES ARE A NON-SELF-SUPPORTING STRUCTURE.
LATERAL FORCES DUE TO WIND, EARTHQUAKE, OR SOIL ARE CARRIED BY THE ROOF AND FLOOR DIAPHRAGMS TO THE LATERAL SYSTEM. CERTAIN ELEMENTS SHOWN ON THE STRUCTURAL DRAWINGS
(SUCH AS BRACING, ROOF AND FLOOR SLABS, AND CONCRETE IN COMPOSITE COLUMNS) ARE
REQUIRED FOR OVERALL OR LOCAL STABILITY OF OTHER ELEMENTS (SUCH AS BEAMS, COLUMNS, AND WALLS). IF DUE TO SEQUENCING OF CONSTRUCTION, THESE STABILITY ELEMENTS ARE NOT IN PLACE, THE CONTRACTOR SHALL RETAIN A STRUCTURAL ENGINEER LICENSED TO PERFORM THE WORK IN THE JURISDICTION WHERE THE PROJECT IS LOCATED, WHO SHALL INVESTIGATE WHERE TEMPORARY
SHORING/BRACING IS REQUIRED AND SHALL DESIGN THIS TEMPORARY SHORING/BRACING. THE
CONTRACTOR SHALL PROVIDE THIS SHORING/BRACING UNTIL THE REQUIRED STRUCTURAL ELEMENTS AND THEIR CONNECTIONS HAVE BEEN INSTALLED AND REACH THEIR FINAL DESIGN STRENGTHS.
17. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT WHEN PLACED ON FRAMED FLOORS OR ROOFS.
THE CONSTRUCTION MATERIAL LOAD SHALL NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT.
CONTRACTOR SHALL BE RESPONSIBLE FOR SHORING WHERE STRUCTURE IS NOT COMPLETE OR HAS
NOT ATTAINED DESIGN STRENGTH.
18. BUILDING TOLERANCES: STANDARD TOLERANCES SHALL BE BASED ON THE REQUIREMENTS OF THE AISC CODE OF STANDARD PRACTICE AND ACI 117, STANDARD SPECIFICATIONS FOR TOLERANCES FOR
CONCRETE CONSTRUCTION AND MATERIALS.
III. FOUNDATIONS:
1. FOUNDATION DESIGN CRITERIA ARE BASED ON CODE MINIMUM VALUES AS SPECIFIED IN CHAPTER 18
"SOILS AND FOUNDATIONS" OF THE 2021 CALIFORNIA BUILDING CODE (CBC).
2. FOOTINGS ARE DESIGNED BASED ON AN ALLOWABLE SOIL BEARING PRESSURE OF 1,500 PSF.
3. LATERAL BEARING PRESSURE FOR FOOTING DESIGN IS 100 PSF.
4. SOIL PREPARATION OF THE SITE SHALL FOLLOW THE RECOMMENDATIONS DESCRIBED IN CHAPTER 18 OF 2021 CBC. THIS INCLUDES REMOVAL OF EXISTING STRUCTURES/UTILITIES, REMOVAL OF EXISTING FILL WHERE DEEMED NECESSARY, PREPARATION OF THE SUBGRADE & COMPACTION, EXCAVATIONS
FOR NEW FOUNDATIONS & SLABS, AND BACKFILLING TO RETAINING WALLS.
5. FOUNDATIONS SHALL BEAR ON UNDISTURBED SOIL OR COMPACTED FILL MATERIAL 12 INHES IN DEPTH WITH THE IN-PLACE DRY DENSITY NOT LESS THAN 90 PERCENT OF THE MAXIMUM DRY DENSITY AT
OPTIMUM MOISTURE CONTENT DETERMINED IN ACCORDANCE WITH ASTM D1557.
6. LOCATION OF ALL UNDERGROUND UTILITIES SHALL BE VERIFIED PRIOR TO CONSTRUCTION OF FOUNDATION TO AVOID ANY INTERFERENCE. CONTRACTOR SHALL EXPOSE EXISTING UTILITY LINES IN THE IMMEDIATE AREA TO DETERMINE THEIR EXACT INVERT ELEVATION, SIZE AND LOCATION RELATIVE TO THE FOUNDATION. NOTIFY THE ENGINEER IMMEDIATELY OF ANY INTERFERENCE WITH PILES, FOOTINGS OR FOUNDATION WALLS.
7. CONTRACTOR SHALL PROVIDE FOR PROPER DEWATERING OF EXCAVATIONS FROM SURFACE WATER, GROUND WATER, AND SEEPAGE. WATER SHALL NOT BE ALLOWED TO STAND IN TRENCHES OR FORMS BEFORE OR AFTER CONCRETE IS PLACED, AND SHALL BE PUMPED OUT. IF BOTTOMS OF TRENCHES
BECOME SOFTENED DUE TO RAIN OR OTHER WATER BEFORE FOUNDATIONS ARE CAST, THE
CONTRACTOR SHALL, AT THEIR OWN EXPENSE, EXCAVATE THE SOFTENED MATERIAL AND REPLACE
WITH CONCRETE.
8. CONTRACTOR SHALL PROVIDE FOR THE DESIGN AND INSTALLATION OF ALL CRIBBING, SHEATHING AND SHORING REQUIRED TO SAFELY AND ADEQUATELY RETAIN THE EARTH BANKS AND ANY EXISTING
STRUCTURE.
9. EXCAVATIONS FOR FOOTINGS SHALL BE APPROVED BY THE GEOTECHNICAL ENGINEER PRIOR TO
PLACING OF CONCRETE AND REINFORCING. CONTRACTOR SHALL NOTIFY THE GEOTECHNICAL
ENGINEER WHEN THE EXCAVATIONS ARE READY FOR INSPECTION. THE GEOTECHNICAL ENGINEER
SHALL SUBMIT A LETTER OF COMPLIANCE TO THE OWNER.
10. ALL EXCAVATIONS SHALL BE PROPERLY BACKFILLED. DO NOT PLACE BACKFILL BEHIND RETAINING
WALLS BEFORE CONCRETE OR MASONRY HAS ATTAINED FULL DESIGN STRENGTH. CONTRACTOR
SHALL BRACE OR PROTECT ALL BUILDING WALLS BELOW GRADE FROM LATERAL LOADS UNTIL
ATTACHING FLOORS ARE COMPLETELY IN PLACE AND HAVE ATTAINED FULL DESIGN STRENGTH.
CONTRACTOR SHALL PROVIDE FOR DESIGNS, PERMITS AND INSTALLATION OF BRACING AND
PROTECTION.
VIII. ANCHOR RODS:
1. ANCHOR RODS SHALL BE ASTM F1554 GRADE 36 WITH CLASS 1A THREADS, UNLESS NOTED
OTHERWISE. FURNISH ANCHOR RODS PREFABRICATED WITH MATCHING DOUBLE HEAVY HEX NUTS
JAMMED AT THE END EMBEDDED IN CONCRETE. FURNISH HARDENED PLATE WASHERS, LOCK
WASHERS, AND MATCHING HEAVY HEX NUTS FOR SECURING THE BASE PLATE TO THE ANCHOR RODS.
A RIGID STEEL TEMPLATE SHALL BE USED TO LOCATE ANCHOR RODS WHILE PLACING CONCRETE.
2. HOOKED ANCHOR RODS SHALL NOT BE USED EXCEPT WHERE NOTED.
3. ANCHOR RODS SHALL HAVE SUFFICIENT LENGTH TO PROVIDE THE MINIMUM EMBEDMENT SHOWN ON THE DRAWINGS, MEASURED FROM THE FACE OF THE CONCRETE TO THE NEAR FACE OF THE DOUBLE NUT, WITH ADEQUATE EXTENSION AS REQUIRED TO RECEIVE THE BASE PLATE WITH FULL THREAD
PROJECTION FOR NUT INSTALLATION.
4. ANCHOR ROD INSTALLATION SHALL BE COORDINATED WITH REINFORCING AND FRAMEWORK.
5. LEVELING NUTS SHALL NOT BE USED EXCEPT AFTER EVALUATION BY THE CONTRACTOR'S ERECTION
ENGINEER.
6. AFTER BASE INSTALLATION, ANCHOR ROD NUTS SHALL BE INSTALLED TO A SNUG-TIGHT CONDITION.
7. NO HEATING OR BENDING OF THE ANCHOR RODS IS PERMITTED. HOLES IN THE BASE
MATERIAL SHALL NOT BE ENLARGED BY BURNING.
VI. MECHANICAL AND ADHESIVE ANCHORS:
1. ADHESIVE ANCHORS AND DOWELS INSTALLED INTO CONCRETE:
A. "SET-XP”BY SIMPSON STRONG TIE (ICC ESR-2508)
B. "HIT-HY 200 V3" BY HILTI, INC. (ICC ESR-3814) EQUIPMENT ANCHORAGE UON
C. "PURE110+BY DEWALT (ICC ESR-3298)
2. EXPANSION ANCHORS INSTALLED INTO CONCRETE:
A. "STRONG-BOLT 2" BY SIMPSON STRONG-TIE (ICC ESR-3037)
B. "KWIK BOLT TZ2 (KB-TZ2)”BY HILTI, INC. (ICC ESR-4266)
C. "POWER-STUD+SD2" BY DEWALT (ICC ESR-2502)
3. ADHESIVE ANCHORS: ASTM A36 THREADED RODS WITH ASTM A 563 GRADE A NUTS AND ANSI B18.22.1
TYPE A WASHERS, UNLESS OTHERWISE NOTED. ANCHORS DESIGNATED AS ASTM A193 GRADE B7
THREADED RODS TO USE ASTM A 563 GRADE DH HEAVY HEX NUTS AND ASTM F 436 WASHERS.
4. ADHESIVE DOWELS: ASTM A615 GRADE 60 REINFORCING STEEL.
5. ALL ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH ICC-ES REPORT AND MANUFACTURERS
RECOMMENDATIONS.
6. UNLESS OTHERWISE NOTED, PROVIDE MINIMUM EMBEDMENT OF ANCHORS PER ICC-ES REPORT &
MANUFACTURERS RECOMMENDATIONS.
7. CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO FABRICATING PLATES, MEMBERS, OR OTHER STEEL
ASSEMBLIES ATTACHED WITH MECHANICAL OR ADHESIVE ANCHORS.
8. PRIOR TO ALL DRILLING OR CORING, THE CONTRACTOR SHALL (1) VERIFY THE EXISTING CONCRETE OR MASONRY THICKNESS TO PREVENT DAMAGE TO THE OPPOSITE FACE OF CONCRETE AND MAINTAIN 1 -1 /2 ”CLEAR COVER U.N.O., AND (2) IDENTIFY EXISTING REINFORCING LOCATIONS BY PACHOMETER, PROBING, CHIPPING, ETC. TO AVOID DAMAGE EXISTING REINFORCING.
9. IF REINFORCEMENT IS ENCOUNTERED DURING DRILLING, ABANDON AND SHIFT THE HOLE LOCATION TO AVOID THE REINFORCEMENT. PROVIDE A MINIMUM OF 2 ANCHOR DIAMETERS OR 1 INCH, WHICHEVER IS
LARGER, OF SOUND CONCRETE BETWEEN THE DOWEL AND THE ABANDONED HOLE. FILL THE
ABANDONED HOLE WITH NON-SHRINK GROUT. IF THE ANCHOR OR DOWEL MAY NOT BE SHIFTED AS
NOTED ABOVE, THE ENGINEER WILL DETERMINE A NEW LOCATION.
10. ADHESIVE ANCHORS INSTALLED IN HORIZONTAL TO VERTICALLY OVERHEAD ORIENTATION TO SUPPORT SUSTAINED TENSION LOADS SHALL BE DONE BY A CERTIFIED ADHESIVE ANCHOR INSTALLER
(AAI) CERTIFIED THROUGH ACI/CRSI OR EQUIVALENT (ACI 318-14 17.8.2.2).
11. ADHESIVE ANCHORS MUST BE INSTALLED IN CONCRETE AGED A MINIMUM OF 21 DAYS (ACI 318-14 17.1.2).
SETTING INFORMATION SYM. UNITS
NOMINAL ANCHOR DIAMTER (IN.)
INSTALLATION TORQUE
CARBON STEEL
INSTALLATION TORQUE
STAINLESS STEEL
TINST
TINST
FT-LB
(Nm)
FT-LB
(Nm)
1/4 3/8 1/2 5/8 3/4
(5)
(41)
(68)
(54)
(149)
(8)
(41)
(54)
(81)
(169)
SLAB STEP/ DEPRESSION
SLOPE UP
SLOPE DOWN
RIDGE
VALLEY
REVISION NUMBER
ELEVATION
SECTION MARK
ELEVATION MARK
GRID BUBBLE
S301
S201
SLAB THICKNESS
CHANGE
DETAIL MARK
S501
THE INSPECTOR SHALL OBSERVE THESE FUNCTIONS ON A RANDOM BASIS.
OPERATIONS NEED NOT BE DELAYED PENDING OBSERVATIONS.
OBSERVE
THESE INSPECTIONS SHALL BE PERFORMED FOR EACH CONNECTION OR MEMBER,
AND COMPLETED PRIOR TO THE FINAL ACCEPTANCE OF THE ITEM.
PERFORM
SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS PRESENT CONTINUOUSLY
WHEN AND WHERE THE WORK TO BE INSPECTED IS BEING PERFORMED
CONTINUOUS
SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS INTERMITTENTLY PRESENT
WHERE THE WORK HAS BEEN OR IS BEING PERFORMED AND AT THE COMPLETION OF
WORK.
PERIODIC
A QUALIFIED PERSON EMPLOYED OR RETAINED BY AN APPROVED AGENCY AND
APPROVED BY THE BUILDING OFFICIAL AS HAVING THE COMPETENCE NECESSARY TO
INSPECT A PARTICULAR TYPE OF CONSTRUCTION REQUIRING SPECIAL INSPECTION.
SPECIAL
INSPECTOR
INSPECTION OF CONSTRUCTION REQUIRING THE EXPERTISE OF AN APPROVED
SPECIAL INSPECTOR IN ORDER TO ENSURE COMPLIANCE WITH THE BUILDING CODE
AND THE APPROVED CONSTRUCTION DOCUMENTS.
SPECIAL
INSPECTION
DEFINITIONS
REFERENCES
CODES/STANDARDS
SPECIAL INSPECTION AND TEST REQUIREMENTS
TYPE REQUIRED INSPECTIONS AND/OR TESTSFREQUENCY
INDICATES SPECIAL INSPECTION OF ITEM IS REQUIRED FOR THE WORK DEFINED IN
THE CONSTRUCTION DOCUMENTS FOR THIS PROJECT.
INSPECTION AND TESTING REQUIREMENTS ON THIS SHEET ARE IN ACCORDANCE
WITH SECTION 1705 OF THE 2021 CALIFORNIA BUILDING CODE (CBC). AND HAVE BEEN
IDENTIFIED AS A STATEMENT OF SPECIAL INSPECTIONS AS REQUIRED BY CBC
SECTION 1704.3. THE OWNER OR THE OWNER'S AUTHORIZED AGENT, OTHER THAN
THE CONTRACTOR, SHALL EMPLOY ONE OR MORE APPROVED AGENCIES TO
PROVIDE THE SPECIAL INSPECTIONS AND TESTS DURING CONSTRUCTION AS
REQUIRED BY CBC SECTION 1705 AND IDENTIFY THE APPROVED AGENCIES TO THE
BUILDING OFFICIAL. THESE SPECIAL INSPECTIONS AND TESTS ARE IN ADDITION TO
THE INSPECTIONS BY THE BUILDING OFFICIAL THAT ARE IDENTIFIED IN CBC SECTION
110. SPECIAL INSPECTORS SHALL BE QUALIFIED IN ACCORDANCE WITH CBC SECTION
1704.2.1, AND ALL OTHER APPLICABLE SECTIONS AND STANDARDS.
SPECIAL INSPECTIONS AND TESTS INDICATED ON THIS SHEET ARE FOR THE
STRUCTURAL WORK, SEE OTHER DISCIPLINES DRAWINGS AND SPECIFICATIONS FOR
REQUIRED NONSTRUCTURAL SPECIAL INSPECTIONS AND TESTS.
STATEMENT OF SPECIAL INSPECTIONS
CONCRETE CBC 1705.3
4. ANCHORS POST-INSTALLED
IN HARDENED CONCRETE
MEMBERS
INSPECT ALL OTHER MECHANICAL OR ADHESIVE ANCHORS THAT ARE NOT ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS - SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSUED BY AN APPROVED SOURCE IN ACCORDANCE WITH ACI318: 17.8.2 OR OTHER QUALIFICATION PROCEDURES.
PERIODIC ACI 318: 17.8.2
GENERAL NOTES ABBREVIATIONS
Ryan Allgood Phone 916-215-6663 Fax 916-376-6216 ryan.allgood@dgs.ca.gov
Issue
DateNo. Description
Project
Drawn
File Date
Supervisor
Sheet Title
Designed
Work Order
Sheet Number
Sheet ScaleReference North
DSA Building Number
Vault File Number
Checked
Client Agency
Address
X
C A D
F
IL
E
R Q P O N M L K J I H G F E D C B A
DEPARTMENT OF
GENERAL SERVICES
MRP JH DK AD
S/-001
GENERAL NOTES
850 MARINA BAY PARKWAY,
RICHMOND, CA 94804
# POUND
& AND
@ AT
AB ANCHOR BOLT
ACS ALL COMMON SIDES
ADDL ADDITIONAL
AESS ARCHITECTURALLY EXPOSED
STRUCTURAL STEEL
ALT ALTERNATE
ARCH,
ARCH'L
ARCHITECT, ARCHITECTURAL
BL BRICKLEDGE
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BN BOUNDARY NAILING
BO BOTTOM OF
BOB BOTTOM OF BEAM
BOD BOTTOM OF DECK
BOS BOTTOM OF STEEL
BOT, BOTT BOTTOM
BP BASE PLATE
BRBF BUCKLING RESTRAINED BRACED
FRAME
BRG BEARING
BTWN BETWEEN
C CHANNEL
CB CONCRETE BEAM
CC CARRIED COLUMN
CEN CENTER
CFMF COLD-FORMED METAL FRAMING
CIP CAST IN PLACE
CJ CONTROL JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECT, CONNECTION
CONT CONTINUOUS
CTR CENTERED
CWI CERTIFIED WELDING INSPECTOR
D, DIA DIAMETER
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DEF DEFORMED, DEFINITION
DEFL DEFLECTION
DET, DTL DETAIL
DIAG DIAGONAL
DN DOWN
DWG DRAWING
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATOR
EMB EMBED
EN EDGE NAILING
EOR ENGINEER OF RECORD
EOS EDGE OF SLAB
EQ EQUAL
EQ SPA EQUAL SPACE
ES EACH SIDE
EW EACH WAY
EXIST, (E) EXISTING
EXT EXTERIOR
FD FLOOR DRAIN
FDN, FNDN FOUNDATION
FF EL FINISH FLOOR ELEVATION
FN FIELD NAILING
FOA FACE OF ANGLE
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FT FEET
FTG FOOTING
Fy YIELD STRESS
GA GAGE, GUAGE
GALV GALVANIZED
GB GRADE BEAM
GLB GLUED-LAMINATED BEAM
GT GIRDER TRUSS
H, HORIZ HORIZONTAL
HC HOLLOW CORE
HI HIGH
HK HOOK
HSS HOLLOW STRUCTURAL STEEL
IN INCHES
INFO INFORMATION
INT INTERIOR
JST JOIST
JT JOINT
K KIPS
KB KNEE BRACE
L ANGLE
LB POUND
LF LINEAR FOOT
LG LENGTH
LLBB LONG LEG BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LO LOW
LT WT LIGHTWEIGHT
LVL LEVEL
MAX MAXIMUM
MC MOMENT CONNECTION
MCJ MASONRY CONTROL JOINT
MECH MECHANICAL
MEZZ MEZZANINE
MFR,
MANUF
MANUFACTURER
MID MIDDLE
MIL MILLIMETER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MTL METAL
N NORTH
NA NOT APPLICABLE
NDT NON-DESTRUCTIVE TESTING
NEW, (N) NEW
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OC ON CENTER
OH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OWSJ OPEN WEB STEEL JOIST
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
R RADIUS
REF REFER, REFERENCE
REINF REINFORCED, REINFORCEMENT
REM REMAINDER
REQ'D REQUIRED
REQ'MTS,
REQMTS
REQUIREMENTS
REV REVISION
SAD SEE ARCHITECTURAL DRAWINGS
SC SLIP CRITICAL
SCHED SCHEDULE
SCJ SAWN CONTROL JOINT
SECT SECTION
SF SQUARE FEET
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SOG SLAB ON GRADE
SPA SPACES, SPACING
SQ SQUARE
SSH SHORT SLOTTED HOLE
STD STANDARD
STL STEEL
STRUCT STRUCTURE, STRUCTURAL
SUPP SUPPORT
T&B TOP AND BOTTOM
TEMP TEMPORARY
THK THICK
TO TOP OF
TOC TOP OF CONCRETE
TOF TOP OF FOUNDATION
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOSC TOP OF STRUCTURAL CONCRETE
TOSL TOP OF SLAB
TOT TOTAL
TOW TOP OF WALL
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V, VERT VERTICAL
VIF VERIFY IN FIELD
W WIDE FLANGE
W/ WITH
W/O WITHOUT
WB WIND BRACE
WBBP WIND BRACE BASEPLATE
WHSS WELDED HEADED STEEL STUD
WP WORKING POINT, WORK POINT
WRT WITH RESPECT TO
WT WEIGHT
WWR WELDED-WIRE REINFORCEMENT
YD YARD
SYMBOLS
EVSE LEVEL II
CDPH CONTRA COSTA COUNTY
V1
09-30-622426
2-12-25
02/13/250 95%CD CLIENT REVIEW
V1
000000000012567
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
05/05/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1087
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-123468
09/11/2025
C
LR3"
TYP
3" CLR
1' 0"
TRANFORMER BY
OTHERS
FINISHED GRADE
SUBGRADE PER
GENERAL NOTES
(4) #4 EA WAY
TOP & BOT
WT = 1422 LBS,MAX
NOTE:
1. FOOTING MAY BE FLUSH WITH ADJACENT PAVING AS REQUIRED.
PAVING PER NOTE 1
1/2" DIA AB @ MFR LOCATION (4)
MIN TYP
CONTRACTOR'S ALT: 1/2" DIA
THREADED ROD W/ HITLI KB-TZ2
W/ 3 1/4" EMBED TYP
6" M
IN
TY
P
1.
5"
E M B
TYP
6" MIN
EQ EQ
24.67" x 31.44"
BRACKET PER MFR
PANEL BOARD
PER ELEC DWGS
WT = 220 LBS, MAX
UNISTRUT P1000
CHANNEL TYP
UNISTRUT P1026 ANGLE
W/ (2) 1/2" BOLT
W/ (2) P1006 SPRING NUT
TYP EA SIDE OF P1001
ELEVATION
1/2" DIA SS304 HILTI
KB-TZ2 W/ 2" EMB
UNISTRUT P1047
U-BRACKET TYP
W/ (3) 1/2" BOLT W/
(3) P1010 SPRING NUT
NWC TYP
UNISTRUT P2458-36 BRACE
W/ 1/2" BOLT & P1010
SPRING NUT EA END
3' - 9"
ALIGN HORIZONTAL
BACKING CHANNEL
W/ MFR PROVIDED
CONNECTION POINTS
AS REQUIRED
MB PER SECTION TYP
9 1/2"
TYP
3" 42" PER MFR
7' 6"
.0 0°
4' - 0"
SUBGRADE PER
GENERAL NOTES
8"
TYP
3" CLR
(4) #5 EA WAY
CENTERED IN CONC
TYP
6" MIN
3/8" DIA MB W/ OVERSIZE
PL WASHER TYP (4) TOT
AT MFR ANCHOR POINTS
3' - 4" MIN
7' 2"
P E R M
FR
8' 0"
M A X
6'
A
A
SECTION A-A
TYP
6" MIN
P1001 TYP (2) TOT
2" MIN
NOTE:
1. ALL EXPOSED STEEL SHALL BE HOT-DIPPED
GALVANIZED.
2. ALL STRUT SHALL BE UNISTRUT.
TY
P
2" M
A X
ANCHOR POINT
PER MFP TYP
(3) TOT
C
LR3"
TYP
3" CLR
M
IN
2' 0"
ELEVATION
SUBGRADE PER
GENERAL NOTES
(2) #5 EA WAY
FINISHED GRADE
5/8" DIA AB W/ 6"
EMBED @ MFR
LOCATION (3) MIN TYP
CONTRACTOR'S ALT:
5/8" DIA HILTI KB-TZ2
W/ 4 1/4" EMBED TYP
5-1/10"
4- 1/ 2"
1- 1/ 2"
DUAL PEDESTAL
CHARGER
WT = 168 LBS
5' 1/ 2"
9 5/8"
-3 /8 P E R M
FR
PLAN
6" MIN ALL AROUND
EQUIPMENT
BASE
9 5/8"
2' - 0" SQ
2' - 0"
2' 0"
6" MIN ALL AROUND
8' 3/ 4"
Ryan Allgood Phone 916-215-6663 Fax 916-376-6216 ryan.allgood@dgs.ca.gov
Issue
DateNo. Description
Project
Drawn
File Date
Supervisor
Sheet Title
Designed
Work Order
Sheet Number
Sheet ScaleReference North
DSA Building Number
Vault File Number
Checked
Client Agency
Address
X
C A D
F
IL
E
DEPARTMENT OF
GENERAL SERVICES
AD BM DK IS
S/-002
DETAILS
850 MARINA BAY PARKWAY,
RICHMOND, CA 94804
EVSE LEVEL II
CDPH CONTRA COSTA COUNTY
V1
NTS S/-002
7 TRANSFORMER FOUNDATION & ANCHORAGE
NTSS/-002
4 PANELBOARD SUPPORT FRAME AND ANCHORAGE
NTSS/-002
6 DUAL PEDESTAL CHARGER ANCHORAGE PLAN
09-30-622426
2-12-25
SINGLE AND DUAL PEDESTAL CHARGER ANCHORAGE PLAN
02/13/250 95%CD CLIENT REVIEW
V1
000000000012567
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
05/05/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1087
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
02-123468
09/11/2025
| 0001 E1.0 TITLE SHEET |
| 0002 E1.1 SINGLE LINE DIAGRAM AND SCHEDULES AREA-A |
| 0003 E1.4 ELECTRICAL SITE PLAN AREA - B |
| 0004 E1.2 SINGLE LINE DIAGRAM AND SCHEDULES AREA-B |
| 0005 E1.3 ELECTRICAL SITE PLAN AREA-A |
| 0006 E2.0 GENERAL NOTES |
| 0007 E2.1 ELECTRICAL DETAILS |
| 0008 E2.2 ELECTRICAL DETAILS |
| 0009 E2.3 ELECTRICAL DETAILS |
| 0010 C1.0 DEMOLITION PLAN |
| 0011 C2.0 IMPROVEMENT PLAN |
| 0012 C3.0 DETAILS |
| 0013 S/-001 GENERAL NOTES |
| 0014 S/-002 DETAILS |
File details come from the government source that posted it. Updated .