Plans.pdf

PDF 16 MB Posted

Attached to
Project 13979. DOT D8 EVSE. Contract 25-311717
Solicitation number
0000039137
Issued by
Riverside County, Lake Riverside CDP, Riverside City, California

About this file

This is a design and permitting document for the Department of Transportation (DOT) Blythe Maintenance Station Charging Station project located at 431 S Broadway, Blythe, California 92225, in Riverside County. The project involves the installation of two dual-port Level 2 electric vehicle charging stations with Power Share capability (ChargePoint CP6021B model) and associated electrical infrastructure to support an electric vehicle fleet of four stalls. The scope of work includes installation of two 80-ampere dual-port chargers, two 100-ampere circuit breakers on separate electrical panels (Panel B and Panel C), 100-ampere safety switch disconnects, underground and above-ground conduit systems, concrete pads, bollards, wheel stops, and parking stall striping marked for EV charging only. The project has received State Fire Marshal approval (Permit #24-4163) as of January 6, 2025, with a project completion date of May 1, 2026. The design was prepared by C2 Group, with civil engineer Jason Paquette (License C 79782) and electrical engineer Henry Perez providing technical oversight. Project management is handled by Ann Watson, Project Director for the Office of Sustainability, Department of General Services.

The electrical infrastructure modifications include installation of a 100-ampere two-pole branch circuit breaker in the existing 150-ampere (120/240-volt), single-phase Distribution Panel C and replacement of the existing 150-ampere main breaker with a fully rated 150-ampere unit, as well as installation of a 100-ampere two-pole branch circuit breaker in the existing 400-ampere (120/240-volt), single-phase Switchboard Panel B. The design specifications require two-inch PVC conduit runs with number 3 AWG copper conductors and number 8 AWG copper ground conductors, concrete pads with 3,000 PSI minimum strength, and compliance with 2022 California Building Code, California Electrical Code, and Fire Code standards. Load calculations demonstrate that both the 150-ampere Panel C (with existing peak demand of 38.80 amperes requiring 48.50 amperes at 125 percent and new load of 100 amperes) and the 400-ampere Panel B (with existing peak demand of 92.1 amperes requiring 115.13 amperes at 125 percent and new load of 100 amperes) have adequate capacity for the additional charger loads. The chargers are designated for use by authorized fleet or designated electric vehicles only and are not available to the general public, thereby exempting the project from accessibility improvement requirements under CBC 11B-202.4 Exception 10.

View the file

Other files

File Type Posted
Bid_Package_Documents.pdf PDF
Project_Manual.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

date designed detailed checked

no. by descriptiondate ckd

8340 JUNIPER CREEK LN

SAN DIEGO, CA 92126

(619) 880-9797 project contract

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G

H drawing sheet of 14 rev.

sheets

I

/3

/2

:5

:2

A

M B

Y P A M

S M

IT

T H

C O

P Y R

IG

H

T

C

G

R O

U P file:

DEPARTMENT OF TRANSPORTATION

BLYTHE MAINTENANCE STATION

CHARGING STATION

431 S BROADWAY

BLYTHE, CA 92225

RIVERSIDE COUNTY

DGS_DOT BLYTHE STATION - BTM.DWG

0 ISSUE FOR PERMITTING

MM

MM

JP

10/14/2024

07/9/2024 JPMM

V2

1 ISSUE FOR PERMITTING09/30/2024 JPMM

2 SFM SUBMITTAL10/14/2024 JPMM

3 SFM COMMENTS12/24/2024 JPMM

COVER SHEET

C-1.0

LI

C

EN

SE

D PROFESSIONAL ENGINEER

STATE OF CALIFORNIAC I VI L

JA

SON PAQUETTE

C 79782 Exp. 9/30/26

N

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/06/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-4163

DOT D8 - Electric Vehicle Supply Equipment - Blythe Maintenance Station

PROJECT NUMBER: 000000000013979; 05/01/26

AutoCAD SHX Text: DECEMBER 2024 AutoCAD SHX Text: APN 848-132-002 AutoCAD SHX Text: REFERENCES: (SURVEY) SURVEY PREPARED BY C2 GROUP DATED 03/18/2024 AutoCAD SHX Text: BASIS OF BEARING: CALIFORNIA STATE PLANE COORDINATE SYSTEM NAD 83 (2011), ZONE 6, US FOOT, 2010.00 EPOCH AutoCAD SHX Text: LOCATION MAP NTS AutoCAD SHX Text: PROPOSED MODIFICATION MAP NTS AutoCAD SHX Text: CONTACTS AutoCAD SHX Text: ENGINEERING MANAGER: JASON PAQUETTE, PE C2 GROUP 8340 JUNIPER CREEK LN SAN DIEGO, CA 92126 JASONP@C2GROUP.US (619) 518-1101 AutoCAD SHX Text: ELECTRICAL ENGINEER: HENRY PEREZ, PE C2 GROUP 8340 JUNIPER CREEK LN SAN DIEGO, CA 92126 HENRYP@C2GROUP.US (619) 807-5952 AutoCAD SHX Text: PROJECT MANAGER: ANN WATSON, PROJECT DIRECTOR OFFICE OF SUSTAINABILITY DEPARTMENT OF GENERAL SERVICES DIRECT: (279) 782-3872 ANN.WATSON@DGS.CA.GOV AutoCAD SHX Text: DESIGNER: MARK MANINGAS C2 GROUP 8340 JUNIPER CREEK LN SAN DIEGO, CA 92126 MARKMA@C2GROUP.US (619) 813-2547 AutoCAD SHX Text: DEPARTMENT OF TRANSPORTATION BLYTHE MAINTENANCE STATION BLYTHE, CALIFORNIA SFM PERMIT #:24-4163 AutoCAD SHX Text: NO DRAWINGS: TITLE: DRAWINGS: TITLE: TITLE: 1 C-1.0 COVER SHEET C-1.0 COVER SHEET COVER SHEET 2 C-2.0 NOTES C-2.0 NOTES NOTES 3 C-3.0 STRUCTURAL NOTES C-3.0 STRUCTURAL NOTES STRUCTURAL NOTES 4 C-4.0 OVERALL SITE PLAN C-4.0 OVERALL SITE PLAN OVERALL SITE PLAN 5 C-5.0 SITE PLAN C-5.0 SITE PLAN SITE PLAN 6 C-5.1 SITE PLAN C-5.1 SITE PLAN SITE PLAN 7 C-6.0 DETAILS C-6.0 DETAILS DETAILS 8 E-1.0 ELECTRICAL PLAN E-1.0 ELECTRICAL PLAN ELECTRICAL PLAN 9 E-1.1 ELECTRICAL PLAN E-1.1 ELECTRICAL PLAN ELECTRICAL PLAN 10 E-2.0 ONE-LINE DIAGRAM E-2.0 ONE-LINE DIAGRAM ONE-LINE DIAGRAM 11 E-3.0 GROUNDING DETAILS E-3.0 GROUNDING DETAILS GROUNDING DETAILS 12 E-4.0 ELECTRICAL DETAILS E-4.0 ELECTRICAL DETAILS ELECTRICAL DETAILS 13 R-1.0 REFERENCE R-1.0 REFERENCE REFERENCE 14 R-2.0 REFERENCE R-2.0 REFERENCE REFERENCE AutoCAD SHX Text: APPLICABLE CODES 2022 CALIFORNIA ADMINISTRATIVE CODE (CAC), PART 1, TITLE 24 CCR* 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 CCR (2021 INTERNATIONAL BUILDING CODE, VOL. 1 & 2, AND 2022 CALIFORNIA AMENDMENTS) 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 CCR (2020 NATIONAL ELECTRICAL CODE AND 2022 CALIFORNIA AMENDMENTS) 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 CCR (2019 IAPMO UNIFORM MECHANICAL CODE AND 2022 CALIFORNIA AMENDMENTS) 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 CCR (2021 IAPMO UNIFORM PLUMBING CODE AND 2022 CALIFORNIA AMENDMENTS) 2022 CALIFORNIA ENERGY CODE (CEC), PART 6, TITLE 24 CCR 2022 CALIFORNIA FIRE CODE (CFC), PART 9, TITLE 24 CCR (2021 INTERNATIONAL FIRE CODE AND 2022 CALIFORNIA AMENDMENTS) 2022 CALIFORNIA EXISTING BUILDING CODE (CEBC), PART 10, TITLE 24 CCR (2021 INTERNATIONAL EXISTING BUILDING CODE AND 2022 CALIFORNIA AMENDMENTS) 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), PART 11, TITLE 24 CCR 2022 CALIFORNIA REFERENCED STANDARDS CODE, PART 12, TITLE 24 CCR TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS FOR A COMPLETE LIST OF APPLICABLE STANDARDS, INCLUDING CALIFORNIA AMENDMENTS TO THE NFPA STANDARDS, REFER TO CBC CHAPTER 35 AND CFC CHAPTER 80. 2010 AMERICANS WITH DISABILITIES ACT (ADA) STANDARDS FOR ACCESSIBLE DESIGN.AMERICANS WITH DISABILITIES ACT (ADA) STANDARDS FOR ACCESSIBLE DESIGN.

AutoCAD SHX Text: PROJECT DESCRIPTION: INSTALLATION OF (2) DUAL-PORT LEVEL 2 (POWER SHARE) CHARGERS AND (2) 100A CIRCUIT BREAKER ON EACH PANEL. THE SCOPE OF WORK DOES NOT REQUIRE ACCESSIBILITY IMPROVEMENTS TO COMPLY WITH CBC 11B-202.4 EXCEPTION 10. ALL EVSE INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER. TOTAL EV FLEET STALL COUNT: 4 AutoCAD SHX Text: MODIFICATION LOCATION AutoCAD SHX Text: PROJECT LOCATION detailed checked

no. by descriptiondate ckd

8340 JUNIPER CREEK LN

SAN DIEGO, CA 92126

(619) 880-9797 project contract

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G

H drawing sheet of 14 rev.

sheets

I

/3

/2

:5

:3

A

M B

Y P A M

S M

IT

T H

C O

P Y R

IG

H

T

C

G

R O

U P file:

DEPARTMENT OF TRANSPORTATION

BLYTHE MAINTENANCE STATION

CHARGING STATION

431 S BROADWAY

BLYTHE, CA 92225

RIVERSIDE COUNTY

DGS_DOT BLYTHE STATION - BTM.DWG

0 ISSUE FOR PERMITTING

MM

MM

JP

10/14/2024

07/9/2024 JPMM

V2

1 ISSUE FOR PERMITTING09/30/2024 JPMM

2 SFM SUBMITTAL10/14/2024 JPMM

3 SFM COMMENTS12/24/2024 JPMM

NOTES

C-2.0

LI

C

EN

SE

D PROFESSIONAL ENGINEER

STATE OF CALIFORNIAC I VI L

JA

SON PAQUETTE

C 79782 Exp. 9/30/26

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/06/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-4163

DOT D8 - Electric Vehicle Supply Equipment - Blythe Maintenance Station

PROJECT NUMBER: 000000000013979; 05/01/26

AutoCAD SHX Text: CONSTRUCTION NOTES:

AutoCAD SHX Text: 1. CONTRACTOR SHALL CONFORM TO PERTINENT LOCAL, STATE, AND FEDERAL CONTRACTOR SHALL CONFORM TO PERTINENT LOCAL, STATE, AND FEDERAL CODES, REQUIREMENTS, AND STANDARDS. 2. ALL PRODUCTS SHALL BE INSTALLED IN ACCORDANCE WITH THE ALL PRODUCTS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S OR SUPPLIER'S INSTRUCTIONS OR RECOMMENDATIONS. 3. CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFE AND HEALTHFUL CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFE AND HEALTHFUL PERFORMANCE OF WORK BY EACH OF ITS EMPLOYEES, VENDORS OR SUPPORT PERSONNEL ENTERING THE PROJECT AREA. 4. ANY INSPECTION BY OWNER OR ENGINEER SHALL NOT IN ANY WAY RELIEVE ANY INSPECTION BY OWNER OR ENGINEER SHALL NOT IN ANY WAY RELIEVE CONTRACTOR FROM FULL CONFORMANCE WITH APPLICABLE CODES AND JURISDICTIONAL REQUIREMENTS. 5. CONTRACTOR SHALL BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, CONTRACTOR SHALL BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, AND SEQUENCES, AND TO CARRY OUT WORK IN ACCORDANCE WITH CONTRACT DOCUMENTS. 6. CONTRACTOR SHALL BE RESPONSIBLE FOR COSTS AND REPAIRS OF FAULTY CONTRACTOR SHALL BE RESPONSIBLE FOR COSTS AND REPAIRS OF FAULTY CONSTRUCTION AND DAMAGES TO EXISTING FACILITIES NOT INTENDED TO BE DAMAGED OR DEMOLISHED, WHICH ARE CAUSED BY CONTRACTOR, VENDORS AND SUPPORT PERSONNEL. THIS RESPONSIBILITY APPLIES TO FACILITIES WHETHER OR NOT SHOWN ON THESE DRAWINGS. 7. CONTRACTOR SHALL SATISFY AS TO THE ACTUAL FIELD CONDITIONS PRIOR TO CONTRACTOR SHALL SATISFY AS TO THE ACTUAL FIELD CONDITIONS PRIOR TO BID AND PRIOR TO WORK. NO CLAIM SHALL BE MADE AGAINST ENGINEER FOR DISCREPANCIES BETWEEN CONDITIONS REPRESENTED ON THESE DRAWINGS AND ACTUAL. 8. NO CONSTRUCTION ACTIVITIES SHALL TAKE PLACE OUTSIDE OF THE PROJECT NO CONSTRUCTION ACTIVITIES SHALL TAKE PLACE OUTSIDE OF THE PROJECT BOUNDARIES. THE PROJECT BOUNDARIES MEANS AREAS WHERE OWNER HAS RIGHTS TO CONSTRUCT THE PROJECT. CONTRACTOR SHALL NOT ACCESS THE SITE OUTSIDE OF LEGAL RIGHT-OF-WAY ACCESS. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY TEMPORARY CONSTRUCTION EASEMENTS, AS NECESSARY, FOLLOWING LOCAL REQUIREMENTS. 9. UNDERGROUND UTILITY INFORMATION IS BASED ON LIMITED DATA. THERE MAY UNDERGROUND UTILITY INFORMATION IS BASED ON LIMITED DATA. THERE MAY BE EXISTING UTILITIES WHICH ARE NOT SHOWN ON THESE DRAWINGS. 10. CONTRACTOR SHALL BE RESPONSIBLE TO CONTACT CALIFORNIA 811 THREE (3) CONTRACTOR SHALL BE RESPONSIBLE TO CONTACT CALIFORNIA 811 THREE (3) WORKING DAYS BEFORE DIGGING. 11. IN THE EVENT THAT HISTORIC OR PREHISTORIC SURFACE OR SUBSURFACE IN THE EVENT THAT HISTORIC OR PREHISTORIC SURFACE OR SUBSURFACE OBJECTS ARE ENCOUNTERED DURING THE PROJECT ACTIVITIES, CONTRACTOR MUST DISCONTINUE WORK IN THE IMMEDIATE AREA, AND AN ARCHAEOLOGIST MUST BE CONSULTED TO EVALUATE THE NATURE AND SIGNIFICANCE OF THE MATERIAL. 12. SOIL SHALL BE WETTED AS APPROPRIATE FOR DUST CONTROL. CONTRACTOR SOIL SHALL BE WETTED AS APPROPRIATE FOR DUST CONTROL. CONTRACTOR SHALL BE RESPONSIBLE TO COMPLY WITH JURISDICTIONAL AIR QUALITY REQUIREMENTS. 13. CONTRACTOR SHALL BE RESPONSIBLE FOR DUST CONTROL, EROSION CONTROL, CONTRACTOR SHALL BE RESPONSIBLE FOR DUST CONTROL, EROSION CONTROL, BEST MANAGEMENT PRACTICES, AND DRAINAGE DURING CONSTRUCTION, IN COMPLIANCE WITH JURISDICTIONAL STANDARDS, AND SUBJECT TO ENGINEER'S APPROVAL. 14. CONTRACTOR SHALL KEEP SITE ACCESSES CLEAN AT ALL TIMES. CONTRACTOR SHALL KEEP SITE ACCESSES CLEAN AT ALL TIMES. 15. FINAL STABILIZATION OF GROUND SURFACES AT PROJECT COMPLETION SHALL FINAL STABILIZATION OF GROUND SURFACES AT PROJECT COMPLETION SHALL MEET JURISDICTIONAL STANDARDS, AND SHALL BE SUBJECT TO ENGINEER'S APPROVAL. 16. CONTRACTOR SHALL BE RESPONSIBLE FOR THE PREPARATION, UPDATES, AND CONTRACTOR SHALL BE RESPONSIBLE FOR THE PREPARATION, UPDATES, AND MAINTENANCE OF A STORM WATER POLLUTION PREVENTION PLAN (SWPPP), IN CONFORMANCE WITH CALIFORNIA REQUIREMENTS. 17. CONTRACTOR SHALL BE RESPONSIBLE FOR PERFORMING/PROVIDING BEST CONTRACTOR SHALL BE RESPONSIBLE FOR PERFORMING/PROVIDING BEST MANAGEMENT PRACTICES (BMP) TO MINIMIZE POLLUTANTS IN STORMWATER RUNOFF TO THE GREATEST EXTENT PRACTICAL, CONTRACTOR SHALL REMOVE THE BMP'S INTENDED TO BE REMOVED AT PROJECT COMPLETION. 18. CONTRACTOR SHALL BE RESPONSIBLE FOR TRAFFIC CONTROL AS NECESSARY. CONTRACTOR SHALL BE RESPONSIBLE FOR TRAFFIC CONTROL AS NECESSARY. 19. CONTRACTOR SHALL COORDINATE WITH AND OBTAIN APPROVALS FROM CONTRACTOR SHALL COORDINATE WITH AND OBTAIN APPROVALS FROM ENGINEER PRIOR TO ANY DESIGN CHANGES, SIGNIFICANT ADJUSTMENTS OR VARIATIONS FROM THE DRAWINGS. 20. FINISHED GRADING AND PAVING SHALL SURFACE/GRAVITY DRAIN AWAY FROM FINISHED GRADING AND PAVING SHALL SURFACE/GRAVITY DRAIN AWAY FROM FOUNDATIONS/FACILITIES, AND SHALL NOT "POND" OR RETAIN RAIN WATER. 21. CONTRACTOR SHALL KEEP PROJECT AREA NEAT, CLEAN, AND ORDERLY DURING CONTRACTOR SHALL KEEP PROJECT AREA NEAT, CLEAN, AND ORDERLY DURING CONSTRUCTION, AND SHALL MAKE THE PROJECT AREA NEAT AND CLEAN AT PROJECT COMPLETION. 22. UNLESS NOTED OTHERWISE, PROPOSED ELEVATIONS AND CONTOURS SHOWN ARE UNLESS NOTED OTHERWISE, PROPOSED ELEVATIONS AND CONTOURS SHOWN ARE TO TOP OF FINISHED GRADE. CONTRACTOR SHALL GRADE TO SUBGRADE AND GRADE TO DRAIN, PROOF ROLL WITH LOADED DUMP TRUCK OR APPROVED EQUIPMENT AND THEN HYDROMULCH FOR SITE STABILIZATION. 23. GRADE SHALL SLOPE UNIFORMLY, AT CONSTANT SLOPE, BETWEEN THE DESIGN GRADE SHALL SLOPE UNIFORMLY, AT CONSTANT SLOPE, BETWEEN THE DESIGN SPOT ELEVATIONS SHOWN ON THESE DRAWINGS. 24. WORK WHICH DOES NOT MEET THE HORIZONTAL LOCATIONS, LINES, SLOPES, WORK WHICH DOES NOT MEET THE HORIZONTAL LOCATIONS, LINES, SLOPES, AND ELEVATIONS WITHIN SPECIFIED OR REASONABLE TOLERANCES, AS SHOWN ON THESE DRAWINGS, SHALL BE SUBJECT TO REPLACEMENT AT CONTRACTOR'S EXPENSE. 25. ALL WORK SHALL BE IN COMPLIANCE OF THE PROJECT TECHNICAL ALL WORK SHALL BE IN COMPLIANCE OF THE PROJECT TECHNICAL SPECIFICATIONS.

AutoCAD SHX Text: ABBREVIATIONS:

AutoCAD SHX Text: AFF ABOVE FINISH FLOOR ABOVE FINISH FLOOR AC ASPHALT CONCRETE ASPHALT CONCRETE BOC BACK OF CURB BACK OF CURB C RUNOFF COEFFICIENT RUNOFF COEFFICIENT CBC CALIFORNIA BUILDING CODE CALIFORNIA BUILDING CODE CBSC CALIFORNIA BUILDING STANDARD CODE CALIFORNIA BUILDING STANDARD CODE CONC CONCRETE CONCRETE COR CORNER CORNER CF CUBIC FEET CUBIC FEET CLR CLEAR, CLEARANCE CLEAR, CLEARANCE DCFC DIRECT CURRENT FAST CHARGER DIRECT CURRENT FAST CHARGER DIA DIAMETER DIAMETER DTL DETAIL DETAIL DGS DEPARTMENT OF GENERAL SERVICES DEPARTMENT OF GENERAL SERVICES DWG DRAWING DRAWING E EAST; EASTING EAST; EASTING EG EXISTING GRADE EXISTING GRADE EMT ELECTRIC METALLIC TUBING ELECTRIC METALLIC TUBING EVCS ELECTRIC VEHICLE CHARGING STATIONS ELECTRIC VEHICLE CHARGING STATIONS ES EXISTING SURFACE EXISTING SURFACE EX EXISTING EXISTING FOC FACE OF CURB FACE OF CURB FG FINISH GROUND FINISH GROUND FPS FEET PER SECOND FEET PER SECOND FS FINISH SURFACE FINISH SURFACE HVAC HEATING, VENTILATION, AND AIR CONDITIONING HEATING, VENTILATION, AND AIR CONDITIONING IBC INTERNATIONAL BUILDING CODE INTERNATIONAL BUILDING CODE IN INCHES INCHES MCB MAIN CIRCUIT BREAKER MAIN CIRCUIT BREAKER N NORTH; NORTHING NORTH; NORTHING QTY QUANTITY QUANTITY PED PEDESTAL PEDESTAL PG PROPOSED GRADE PROPOSED GRADE PI POINT OF INTERSECTION POINT OF INTERSECTION PVC POLY VINYL CHLORIDE POLY VINYL CHLORIDE R RADIUS RADIUS RMC RIGID METAL CONDUIT RIGID METAL CONDUIT SDG&E SAN DIEGO GAS & ELECTRIC SAN DIEGO GAS & ELECTRIC SEC SECTION SECTION SF SQUARE FEET SQUARE FEET SW SIDEWALK SIDEWALK TC TOP OF CURB TOP OF CURB T&D TRANSMISSION & DISTRIBUTION TRANSMISSION & DISTRIBUTION V VOLUME VOLUME W WEST WEST W/ WITH WITH AutoCAD SHX Text: ARC FLASH NOTE TO CONTRACTOR: THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING EXISTING ARC FLASH HAZARD ANALYSIS DOCUMENTATION AND PERFORMING A NEW ARC FLASH HAZARD ANALYSIS IN ACCORDANCE WITH 2021 EDITION OF NFPA 70E. THE CONTRACTOR SHALL PERFORM ALL WORK IN ACCORDANCE WITH THE 2021 EDITION OF NFPA 70E, INCLUDING BUT NOT LIMITED TO, LOCKOUT/TAGOUT REQUIREMENTS. ALL NEW PANEL BOARDS AND DRY-TYPE TRANSFORMERS SHALL BE MARKED TO WARN QUALIFIED PERSONS OF POTENTIAL ARC FLASH HAZARDS IN ACCORDANCE WITH NEC 110.16. ARC-FLASH ASSESSMENT STUDY AND ARC FLASH HAZARD WARNING LABELS SHALL BE SUBMITTED TO THE ELECTRICAL ENGINEER OF RECORD FOR REVIEW AND APPROVAL.

detailed checked

no. by descriptiondate ckd

8340 JUNIPER CREEK LN

SAN DIEGO, CA 92126

(619) 880-9797 project contract

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G

H drawing sheet of 14 rev.

sheets

I

/3

/2

:5

:3

A

M B

Y P A M

S M

IT

T H

C O

P Y R

IG

H

T

C

G

R O

U P file:

431 S BROADWAY

BLYTHE, CA 92225

RIVERSIDE COUNTY

DGS_DOT BLYTHE STATION - BTM.DWG

0 ISSUE FOR PERMITTING

MM

MM

JP

10/14/2024

07/9/2024 JPMM

V2

1 ISSUE FOR PERMITTING09/30/2024 JPMM

2 SFM SUBMITTAL10/14/2024 JPMM

3 SFM COMMENTS12/24/2024 JPMM

DEPARTMENT OF TRANSPORTATION

BLYTHE MAINTENANCE STATION

CHARGING STATION

STRUCTURAL NOTES

C-3.0

LI

C

EN

SE

D PROFESSIONAL ENGINEER

STATE OF CALIFORNIAC I VI L

JA

SON PAQUETTE

C 79782 Exp. 9/30/26

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/06/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-4163

DOT D8 - Electric Vehicle Supply Equipment - Blythe Maintenance Station

PROJECT NUMBER: 000000000013979; 05/01/26

AutoCAD SHX Text: DESIGN LOADS: PER 2021 IBC & 2022 CBSC : PER 2021 IBC & 2022 CBSC 1603.1.4 - WIND DESIGN CRITERIA: ULTIMATE DESIGN WIND SPEED, Vult ............................................. 99 MPH 99 MPH RISK CATEGORY ...................................................................... II II WIND EXPOSURE ....................................................................... EXPOSURE C EXPOSURE C 1603.1.5 - EARTHQUAKE DESIGN CRITERIA: RISK CATEGORY ...................................................................... II II SEISMIC IMPORTANCE FACTOR, I ................................................ 1.00 E ................................................ 1.00 1.00 SPECTRAL ACCELERATION, S .................................................... 0.29 g S .................................................... 0.29 g 0.29 g SPECTRAL ACCELERATION, S .................................................... 0.15 g 1 .................................................... 0.15 g 0.15 g SITE CLASS ............................................................................... D D SPECTRAL RESPONSE COEFFICIENT, S ........................................ 0.30 g DS ........................................ 0.30 g 0.30 g SEISMIC DESIGN CATEGORY ............................................................. CATEGORY DCATEGORY D AutoCAD SHX Text: FOUNDATIONS: : 1. SOIL CHARACTERISTICS HAVE BEEN ASSUMED PER THE 2022 CBSC SECTION 1806 PRESUMPTIVE LOAD-BEARING SOIL CHARACTERISTICS HAVE BEEN ASSUMED PER THE 2022 CBSC SECTION 1806 PRESUMPTIVE LOAD-BEARING VALUES OF SOILS CONSISTENT WITH SAND, SILTY SAND, CLAYEY SAND, SILTY GRAVEL AND CLAYEY GRAVEL (SW, SP, SM, SC, GM AND SOIL TYPES. THE CONTRACTOR SHALL VERIFY THE PRESUMED SOIL TYPES PRIOR TO CONSTRUCTION AND NOTIFY THE ENGINEER OF NON-CONFORMING IN-SITU CONDITIONS IF PRESENT BEFORE PROCEEDING. 2. ALL FOUNDATIONS TO BEAR ON UNDISTURBED NATIVE MATERIAL, OR GRANULAR COMPACTED FILL. ALL FOUNDATIONS TO BEAR ON UNDISTURBED NATIVE MATERIAL, OR GRANULAR COMPACTED FILL. 3. SOIL DESIGN CRITERIA, PER 2022 CBSC SECTION 1806: SOIL DESIGN CRITERIA, PER 2022 CBSC SECTION 1806: 3.1. SOIL BEARING - 1,500 PSF SOIL BEARING - 1,500 PSF 3.2. 1/3 INCREASE ALLOWED FOR SHORT TERM LOADS 1/3 INCREASE ALLOWED FOR SHORT TERM LOADS 3.3. SOIL PROFILE - D SOIL PROFILE - D 3.4. FRICTION COEFFICIENT - 0.25FRICTION COEFFICIENT - 0.25 AutoCAD SHX Text: JOB SITE CONDITIONS AND SAFETY: : 1. CONTRACTOR AGREES THAT THEY SHALL ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE CONDITIONS CONTRACTOR AGREES THAT THEY SHALL ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION OF THIS PROJECT, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY; THAT THIS REQUIREMENT SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS; AND THAT THE CONTRACTOR SHALL DEFEND, INDEMNIFY, AND HOLD THE ENGINEER AND IT'S REPRESENTATIVE HARMLESS FROM ANY AND ALL LIABILITY, REAL OR ALLEGED, IN CONNECTION WITH THE PERFORMANCE OF WORK ON THIS PROJECT, EXCEPTING FOR LIABILITY ARISING FROM THE SOLE NEGLIGENCE OF THE ENGINEER.

AutoCAD SHX Text: GENERAL STRUCTURAL NOTES: : 1. THESE NOTES ARE GENERAL IN NATURE AND ARE INTENDED TO SET MINIMUM STANDARDS FOR CONSTRUCTION. THE THESE NOTES ARE GENERAL IN NATURE AND ARE INTENDED TO SET MINIMUM STANDARDS FOR CONSTRUCTION. THE CONTRACTOR SHALL BE COMPLETELY FAMILIAR WITH THE CONTRACT DOCUMENTS AND HAVE A COPY OF THEM ON SITE AT ALL TIMES. 2. FOR ANY PORTION OF THE CONSTRUCTION WHICH THE CONTRACTOR IS UNABLE TO ASCERTAIN THE REQUIRED FOR ANY PORTION OF THE CONSTRUCTION WHICH THE CONTRACTOR IS UNABLE TO ASCERTAIN THE REQUIRED CONSTRUCTION OR WHERE CONFLICTS EXIST, IT IS THE CONTRACTOR'S RESPONSIBILITY TO REQUEST ADDITIONAL INFORMATION (RFIs) AND/OR CLARIFICATIONS BEFORE CONSTRUCTION. 3. ALL WORK SHALL BE IN STRICT CONFORMANCE WITH THE 2021 INTERNATIONAL BUILDING CODE (IBC) AS AMENDED BY ALL WORK SHALL BE IN STRICT CONFORMANCE WITH THE 2021 INTERNATIONAL BUILDING CODE (IBC) AS AMENDED BY THE 2022 CALIFORNIA BUILDING STANDARDS CODE (CBSC). 4. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND ELEVATIONS BEFORE CONSTRUCTION. THE ARCHITECT AND THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND ELEVATIONS BEFORE CONSTRUCTION. THE ARCHITECT AND ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES OR INCONSISTENCIES. 5. THE CONTRACTOR, CONTRACTORS AND SUPPLIERS SHALL ENSURE COORDINATION OF CONTRACTOR THE CONTRACTOR, CONTRACTORS AND SUPPLIERS SHALL ENSURE COORDINATION OF CONTRACTOR SUPPLIED/DESIGNED ELEMENTS AND DEFERRED SUBMITTALS WITH ALL DESIGN DISCIPLINES WITHIN THE CONSTRUCTION SET. COORDINATION SHALL IDENTIFY AND RECONCILE CONFLICTS BETWEEN THE CONTRACTOR SUPPLIED/DESIGNED ELEMENTS AND THE CONSTRUCTION DRAWINGS PRIOR TO FABRICATION AND DELIVERY TO THE PROJECT SITE. THE PROJECT ENGINEER SHALL BE NOTIFIED IF CONFLICTS EXIST. 6. THE CONTRACT STRUCTURAL DRAWINGS REPRESENT THE FINISHED STRUCTURE. METHODS, PROCEDURES, AND THE CONTRACT STRUCTURAL DRAWINGS REPRESENT THE FINISHED STRUCTURE. METHODS, PROCEDURES, AND SEQUENCE OF CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO MAINTAIN AND ENSURE THE INTEGRITY OF THE STRUCTURE AT ALL STAGES OF CONSTRUCTION. 7. CONSTRUCTION LOADS SHALL NOT EXCEED THE DESIGN LIVE LOAD FOR THE STRUCTURE. PROVIDE SHORING AND/OR CONSTRUCTION LOADS SHALL NOT EXCEED THE DESIGN LIVE LOAD FOR THE STRUCTURE. PROVIDE SHORING AND/OR BRACING WHERE LOADS EXCEED DESIGN CAPACITY AND WHERE STRUCTURES HAVE NOT ATTAINED DESIGN STRENGTH. 8. CLADDING, WATERPROOFING, AND ARCHITECTURAL FEATURES ARE OUTSIDE THE STRUCTURAL SCOPE OF WORK. ANY CLADDING, WATERPROOFING, AND ARCHITECTURAL FEATURES ARE OUTSIDE THE STRUCTURAL SCOPE OF WORK. ANY DEPICTION OF SUCH FEATURES ON THE STRUCTURAL DRAWINGS ARE NOT INTENDED TO BE USED FOR CONSTRUCTION. REPRESENTATION OF SUCH FEATURES ON THESE DRAWINGS MAY OR MAY NOT BE ACCURATE.

AutoCAD SHX Text: CONCRETE: : 1. ALL CONCRETE SHALL BE HARD ROCK CONCRETE MEETING REQUIREMENTS OF ACI-301, "SPECIFICATIONS FOR ALL CONCRETE SHALL BE HARD ROCK CONCRETE MEETING REQUIREMENTS OF ACI-301, "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS". MIX PROPORTIONS SHALL BE PER ACI-301, METHOD 2 OR THE ALTERNATE PROCEDURE. SUBMIT MIX DESIGN FOR REVIEW BY STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO CONSTRUCTION. 2. STRUCTURAL CONCRETE SHALL ATTAIN THE FOLLOWING MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS: STRUCTURAL CONCRETE SHALL ATTAIN THE FOLLOWING MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS: TYPE f'c SLUMP w/c AIR f'c SLUMP w/c AIR SLUMP w/c AIR w/c AIR AIR FOOTINGS 3,000 1-4" 0.45 6% 3,000 1-4" 0.45 6% 1-4" 0.45 6% 0.45 6% 6% 3. ALL CONCRETE EXPOSED TO WEATHER SHALL CONTAIN 6% (±) 1% AIR ENTRAINMENT BY VOLUME. AIR ENTRAINMENT ALL CONCRETE EXPOSED TO WEATHER SHALL CONTAIN 6% (±) 1% AIR ENTRAINMENT BY VOLUME. AIR ENTRAINMENT SHALL BE IN CONFORMANCE WITH ASTM C260 AND C494. 4. COLD WEATHER PLACEMENT SHALL CONFORM TO ACI-306. HOT WEATHER PLACEMENT SHALL CONFORM TO ACI-305. COLD WEATHER PLACEMENT SHALL CONFORM TO ACI-306. HOT WEATHER PLACEMENT SHALL CONFORM TO ACI-305. MECHANICALLY VIBRATE ALL FORMED CONCRETE. DO NOT OVER-VIBRATE. PLACE CONCRETE MONOLITHICALLY BETWEEN CONSTRUCTION OR CONTROL JOINTS. PROTECT ALL CONCRETE FROM PREMATURE DRYING. 5. CHAMFER ALL EXTERIOR CORNERS 1/2" UNLESS SHOWN OTHERWISE. CHAMFER ALL EXTERIOR CORNERS 1/2" UNLESS SHOWN OTHERWISE. 6. SLUMP LIMITS MAY BE INCREASED BY ADDITION OF ADMIXTURES PROVIDED THAT THE WATER/CEMENT RATIO OF THE SLUMP LIMITS MAY BE INCREASED BY ADDITION OF ADMIXTURES PROVIDED THAT THE WATER/CEMENT RATIO OF THE ORIGINAL MIX DESIGN IS NOT EXCEEDED. WATER REDUCING ADMIXTURE SHALL BE IN CONFORMANCE WITH ASTM494, USED IN CONFORMANCE WITH MANUFACTURER'S INSTRUCTIONS. SUBMIT ADMIXTURES TO ENGINEER FOR REVIEW PRIOR TO CONSTRUCTION. 7. CEMENT SHALL BY TYPE II/V IN CONFORMANCE WITH ASTM C150. AGGREGATES SHALL BE IN CONFORMANCE WITH CEMENT SHALL BY TYPE II/V IN CONFORMANCE WITH ASTM C150. AGGREGATES SHALL BE IN CONFORMANCE WITH ASTM C33 AND USE CRUSHED (NOT ROUND) GRAVEL OR STONE. COARSE AGGREGATES SHALL NOT EXCEED 3/4". WATER SHALL BE CLEAN AND POTABLE. 8. REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60. GRADE 40 MAY BE USED FOR #3 AND SMALLER REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60. GRADE 40 MAY BE USED FOR #3 AND SMALLER TIES AND STIRRUPS. DETAIL AND PLACE ACCORDING TO ACI MANUAL SP-66. 9. UNLESS OTHERWISE NOTED, MINIMUM COVER SHALL BE 1 1/2" FOR #5 AND SMALLER BARS, 2" FOR #6 AND LARGER UNLESS OTHERWISE NOTED, MINIMUM COVER SHALL BE 1 1/2" FOR #5 AND SMALLER BARS, 2" FOR #6 AND LARGER BARS AND 3" WHEN POURED AGAINST EARTH. SUPPORT REINFORCEMENT WITH APPROVED CHAIRS, SPACERS, OR TIES. 10. PROVIDE MINIMUM 48 BAR DIAMETERS AT SPLICES. NO MORE THAN 50% OF REINFORCING SHALL BE SPLICED AT ANY PROVIDE MINIMUM 48 BAR DIAMETERS AT SPLICES. NO MORE THAN 50% OF REINFORCING SHALL BE SPLICED AT ANY LOCATION. UNLESS OTHERWISE NOTED, BEND ALL HORIZONTAL REINFORCING A MINIMUM OF 2'-0" AT CORNERS AND WALL/FOOTING INTERSECTIONS WITH MIN. EMBEDMENT BEYOND INTERFACE PER DEVELOPMENT LENGTH SPECIFIED IN ACI 318. 11. FORMWORK SHALL BE IN ACCORDANCE WITH ACI-347 "GUIDE TO FORMWORK FOR CONCRETE". FORMS SHALL BE FORMWORK SHALL BE IN ACCORDANCE WITH ACI-347 "GUIDE TO FORMWORK FOR CONCRETE". FORMS SHALL BE DESIGNED BY THE CONTRACTOR. BRACING SHALL BE PROVIDED AS REQUIRED OR UNTIL THE CONCRETE HAS REACHED ITS SPECIFIED 28-DAY STRENGTH. ALL SHORING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. FORMWORK, SUPPORTS, AND SHORING SHALL PROVIDE FINISHED CONCRETE SURFACES AT ALL FACES: LEVEL, PLUMB, AND TRUE TO DIMENSIONS AND ELEVATIONS SHOWN IN THE DRAWINGS. 12. SPECIAL INSPECTIONS: OWNER WILL ENGAGE A QUALIFIED SPECIAL INSPECTOR TESTING AGENCY. TESTING AGENCY SPECIAL INSPECTIONS: OWNER WILL ENGAGE A QUALIFIED SPECIAL INSPECTOR TESTING AGENCY. TESTING AGENCY WILL TEST COMPACTION OF SOIL IN PLACE ACCORDING TO ASTM D1556, ASTM D2167, ASTM D2937, AND ASTM D6938, AS APPLICABLE.

X

X X X X X X

X X X X X X X X X X XX

X X X X X X X X X X X X X X X X X X X

E E E E E

O H

E

E V

C H

A R

G I N

G

O N L Y

E V

C H

A R

G

IN

G

O N L Y

EV

CHARGING

ONLY

EV

CHARGING

ONLY

date designed detailed checked

no. by descriptiondate ckd

8340 JUNIPER CREEK LN

SAN DIEGO, CA 92126

(619) 880-9797 project contract

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G

H drawing sheet of 14 rev.

sheets

I

/3

/2

:5

:4

A

M B

Y P A M

S M

IT

T H

C O

P Y R

IG

H

T

C

G

R O

U P file:

431 S BROADWAY

BLYTHE, CA 92225

RIVERSIDE COUNTY

DGS_DOT BLYTHE STATION - BTM.DWG

0 ISSUE FOR PERMITTING

MM

MM

JP

10/14/2024

07/9/2024 JPMM

V2

1 ISSUE FOR PERMITTING09/30/2024 JPMM

2 SFM SUBMITTAL10/14/2024 JPMM

3 SFM COMMENTS12/24/2024 JPMM

DEPARTMENT OF TRANSPORTATION

BLYTHE MAINTENANCE STATION

CHARGING STATION

OVERALL SITE PLAN

C-4.0

LI

C

EN

SE

D PROFESSIONAL ENGINEER

STATE OF CALIFORNIAC I VI L

JA

SON PAQUETTE

C 79782 Exp. 9/30/26

20 20

1"=20'

10 4000

N

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/06/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-4163

DOT D8 - Electric Vehicle Supply Equipment - Blythe Maintenance Station

PROJECT NUMBER: 000000000013979; 05/01/26

AutoCAD SHX Text: EXISTING BUILDING AutoCAD SHX Text: EXISTING BUILDING AutoCAD SHX Text: EXISTING CANOPY GARAGE AutoCAD SHX Text: EXISTING VEHICLE WASHPAD AutoCAD SHX Text: EXISTING BUILDING AutoCAD SHX Text: LEGEND:

AutoCAD SHX Text: EXISTING PARKING STALL STRIPING AutoCAD SHX Text: PROPOSED BOLLARD AutoCAD SHX Text: PROPOSED TRENCH CONDUIT AutoCAD SHX Text: EXISTING SIGN AutoCAD SHX Text: EXISTING STREET LIGHT AutoCAD SHX Text: EXISTING BUILDING COLUMN AutoCAD SHX Text: NOTES: : 1. CONTRACTOR SHALL PROTECT EXISTING INFRASTRUCTURE IN PLACE WITHIN THE LIMITS OF WORK, AND RETURN CONTRACTOR SHALL PROTECT EXISTING INFRASTRUCTURE IN PLACE WITHIN THE LIMITS OF WORK, AND RETURN ALL DISTURBED FACILITIES TO THE SAME OR BETTER THAN THE EXISTING CONDITION. 2. INSTALLATION OF ALL CHARGEPOINT LEVEL 2 CHARGERS AND PEDESTALS, EVSE INFORMATION IS PROVIDED INSTALLATION OF ALL CHARGEPOINT LEVEL 2 CHARGERS AND PEDESTALS, EVSE INFORMATION IS PROVIDED FOR REFERENCE ONLY. CHARGER AND PEDESTALS TO BE INSTALLED BY OTHERS.

AutoCAD SHX Text: EXISTING CONCRETE PAVEMENT TO BE REPLACED AutoCAD SHX Text: EXISTING AC PAVEMENT TO BE REPLACED AutoCAD SHX Text: EXISTING BUILDING OVERHANG AutoCAD SHX Text: EXISTING BUILDING FOOTPRINT AutoCAD SHX Text: EXISTING CONCRETE PAVEMENT AutoCAD SHX Text: EXISTING BOLLARD AutoCAD SHX Text: EXISTING SWITCHBOARD AutoCAD SHX Text: EXISTING DISTRIBUTION PANEL AutoCAD SHX Text: EXISTING DECOMPOSED GRAVEL TO BE REPLACED AutoCAD SHX Text: PROPOSED DUAL-PORT LEVEL 2 CHARGER STATION AutoCAD SHX Text: PROPOSED PARKING STALL STRIPING AutoCAD SHX Text: PROPOSED ABOVEGROUND CONDUIT AutoCAD SHX Text: PROPOSED UNDERGROUND CONDUIT AutoCAD SHX Text: PROPOSED JUNCTION BOX AutoCAD SHX Text: SEE DETAIL ON SHEET C-5.0 & E-1.0 AutoCAD SHX Text: SEE DETAIL ON SHEET C-5.1 & E-1.1 AutoCAD SHX Text: S BROADWAY AutoCAD SHX Text: 1. OCCUPANCY GROUPS AND VARIED USES: 8. OCCUPANCY GROUPS AND VARIED USES: 8. 2. BUILDING CONSTRUCTION TYPE: METAL BUILDING CONSTRUCTION TYPE: METAL 3. NUMBER OF STORIES: ONE NUMBER OF STORIES: ONE 4. BUILDING AREA IN SQUARE FEET: 1598 SF BUILDING AREA IN SQUARE FEET: 1598 SF 5. AREA OF THE PROJECT IN SQUARE FEET: 1900 SF AREA OF THE PROJECT IN SQUARE FEET: 1900 SF 6. SEPARATED, NON-SEPARATED, ACCESSORY USE: SEPARATED SEPARATED, NON-SEPARATED, ACCESSORY USE: SEPARATED 7. ALLOWABLE AREA: N/A ALLOWABLE AREA: N/A 8. AREA INCREASE: O SF AREA INCREASE: O SF 9. HEIGHT INCREASE: 0 FT HEIGHT INCREASE: 0 FT 10. FIRE SPRINKLERS (TYPE, FULL, PARTIAL): N/A (OUTSIDE THE FIRE SPRINKLERS (TYPE, FULL, PARTIAL): N/A (OUTSIDE THE BUILDING) 11. FIRE ALARM (TYPE): NO FIRE ALARM (TYPE): NO 12. OTHER FIRE PROTECTION SYSTEM: NO OTHER FIRE PROTECTION SYSTEM: NO 13. SMOKE CONTROL SYSTEM: NO SMOKE CONTROL SYSTEM: NO 14. OCCUPANT LOAD FOR ENTIRE BUILDING: 8 OCCUPANT LOAD FOR ENTIRE BUILDING: 8 15. OCCUPANT LOAD FOR EACH FLOOR: 8 OCCUPANT LOAD FOR EACH FLOOR: 8 16. YEAR BUILDING WAS CONSTRUCTED: 1990 YEAR BUILDING WAS CONSTRUCTED: 1990 17. HIGH FIRE HAZARD SEVERITY ZONE: NO HIGH FIRE HAZARD SEVERITY ZONE: NO 18. SEISMIC JOINTS AND LOCATIONS: NO SEISMIC JOINTS AND LOCATIONS: NO 19. EMERGENCY RESPONDER RADIO COVERAGE: YESEMERGENCY RESPONDER RADIO COVERAGE: YES AutoCAD SHX Text: NONSTRUCTURAL PROVISIONS-BUILDING ANALYSIS:

E V

C H

A R

G

IN

G

O N

L Y

E V

C H

A R

G

IN

G

O N

L Y date designed detailed checked

no. by descriptiondate ckd

8340 JUNIPER CREEK LN

SAN DIEGO, CA 92126

(619) 880-9797 project contract

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G

H drawing sheet of 14 rev.

sheets

I

/3

/2

:5

:4

A

M B

Y P A M

S M

IT

T H

C O

P Y R

IG

H

T

C

G

R O

U P file:

DEPARTMENT OF TRANSPORTATION

BLYTHE MAINTENANCE STATION

CHARGING STATION

431 S BROADWAY

BLYTHE, CA 92225

RIVERSIDE COUNTY

DGS_DOT BLYTHE STATION - BTM.DWG

0 ISSUE FOR PERMITTING

MM

MM

JP

10/14/2024

07/9/2024 JPMM

V2

1 ISSUE FOR PERMITTING09/30/2024 JPMM

2 SFM SUBMITTAL10/14/2024 JPMM

3 SFM COMMENTS12/24/2024 JPMM

SITE PLAN

C-5.0

LI

C

EN

SE

D PROFESSIONAL ENGINEER

STATE OF CALIFORNIAC I VI L

JA

SON PAQUETTE

C 79782 Exp. 9/30/26

1"=5'

2.5 00 5 105

N

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/06/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-4163

DOT D8 - Electric Vehicle Supply Equipment - Blythe Maintenance Station

PROJECT NUMBER: 000000000013979; 05/01/26

AutoCAD SHX Text: PROPOSED LEVEL 2 CHARGER 80A DUAL-PORT PEDESTAL WITH POWER SHARE [CHARGEPOINT CP6021B] AutoCAD SHX Text: 1 AutoCAD SHX Text: E-4.0 AutoCAD SHX Text: INSTALL 100A 2-POLE BRANCH CIRCUIT BREAKER & REPLACE EXISTING 150A MAIN BREAKER WITH FULLY RATED 150A MAIN BREAKER IN EXISTING 150A (120/240V), 1-PHASE DISTRIBUTION PANEL "C" AutoCAD SHX Text: PROPOSED 8"x8"x6" JUNCTION BOX OR EQUIVALENT. QTY 2 AutoCAD SHX Text: PROPOSED BOLLARD AutoCAD SHX Text: 1 AutoCAD SHX Text: C-6.0 AutoCAD SHX Text: EXISTING CONCRETE SWALE AutoCAD SHX Text: EXISTING BUILDING AutoCAD SHX Text: EXISTING BUILDING AutoCAD SHX Text: EXISTING CANOPY GARAGE AutoCAD SHX Text: LEVEL 2 CHARGER NOTE: POWER SHARE ALLOWS A DUAL-PORT STATION TO SHARE POWER FROM A SINGLE CIRCUIT ACROSS TWO PORTS, ADJUSTING POWER DEPENDING ON WHETHER ONE OR BOTH ARE CHARGING. STANDARD WIRING USES AN INDEPENDENT CIRCUIT FOR EACH PORT. POWER SHARE CAN BE USED IN COMBINATION WITH POWER SELECT.

AutoCAD SHX Text: PROPOSED PARKING SIGN AutoCAD SHX Text: 2 AutoCAD SHX Text: C-6.0 AutoCAD SHX Text: PROPOSED WHEEL STOP AutoCAD SHX Text: 3 AutoCAD SHX Text: C-6.0 AutoCAD SHX Text: 2 AutoCAD SHX Text: E-4.0 AutoCAD SHX Text: PROPOSED 100A (120/240V), 1-PHASE SAFETY SWITCH DISCONNECT AutoCAD SHX Text: CONSTRUCTION NOTES: : REMOVE AND REPLACE EXISTING AC PAVEMENT WHERE TRENCHING IS REQUIRED FOR THE INSTALLATION OF CONDUIT PER DETAILS ON SHEET E-1.0. SEE DETAILS ON SHEET C-6.0 FOR TRENCH SECTION. REMOVE AND REPLACE EXISTING CONCRETE SWALE WHERE TRENCHING IS REQUIRED FOR THE INSTALLATION OF CONDUIT PER DETAILS ON SHEET E-1.0. SEE DETAILS ON SHEET C-6.0 FOR TRENCH SECTION. REMOVE EXISTING AC PAVEMENT FOR THE INSTALLATION OF LEVEL 2 CHARGER AND CONCRETE BASE. SEE DETAIL 1 ON SHEET E-4.0. WALL CORING FOR THE INSTALLATION OF JUNCTION BOXES. REMOVE EXISTING AC PAVEMENT FOR THE INSTALLATION OF SAFETY SWITCH DISCONNECT ON H-FRAME. SEE DETAIL 2 ON SHEET E-4.0. REMOVE AND REPLACE EXISTING STRIPING FOR EV STALL 1 THROUGH 4. STRIPING SHALL BE (OSHA SAFETY GREEN-14120) SURFACE MARKING SHALL BE WHITE LETTERS A MINIMUM OF 12 INCHES IN HEIGHT, THE CENTERLINE OF THE TEXT SHALL BE A MAXIMUM OF 6 INCHES FROM CENTERLINE OF THE VEHICLE SPACE AND IT'S LOWER SIDE ALIGNED WITH THE END OF THE PARKING SPACE LENGTH.

AutoCAD SHX Text: 1A AutoCAD SHX Text: 1B AutoCAD SHX Text: 2 AutoCAD SHX Text: 3 AutoCAD SHX Text: 4 AutoCAD SHX Text: 5 AutoCAD SHX Text: 6 AutoCAD SHX Text: NOTES: : 1. RUN 48" OF WIRING ABOVE THE CONDUIT (FOR L2'S PEDESTAL), AS THE HOOK UPS ARE IN THE TOP "HEAD" RUN 48" OF WIRING ABOVE THE CONDUIT (FOR L2'S PEDESTAL), AS THE HOOK UPS ARE IN THE TOP "HEAD" OF THE PEDESTAL UNIT. 2. DO NOT EXTEND THE CONDUIT FORE THAN 9" ABOVE THE PAD. DO NOT EXTEND THE CONDUIT FORE THAN 9" ABOVE THE PAD. 3. INSTALLATION OF ALL CHARGEPOINT CP6000 LEVEL 2 CHARGERS AND PEDESTALS, EVSE INFORMATION IS INSTALLATION OF ALL CHARGEPOINT CP6000 LEVEL 2 CHARGERS AND PEDESTALS, EVSE INFORMATION IS PROVIDED FOR REFERENCE ONLY. CHARGER AND PEDESTALS TO BE INSTALLED BY OTHERS. 4. CONTRACTOR TO PROVIDE EMERGENCY SHUT OFF LABELS PER SPECIFICATION SECTION 26 05 53-2.2G. CONTRACTOR TO PROVIDE EMERGENCY SHUT OFF LABELS PER SPECIFICATION SECTION 26 05 53-2.2G. 5. SEE C-4.0 FOR LEGEND.SEE C-4.0 FOR LEGEND.

X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

E E E E E E E E E E E E E E E E E

E E E E E

E

E

E

EV

CHARGING

ONLY

EV

CHARGING

ONLY

date designed detailed checked

no. by descriptiondate ckd

8340 JUNIPER CREEK LN

SAN DIEGO, CA 92126

(619) 880-9797 project contract

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G

H drawing sheet of 14 rev.

sheets

I

/3

/2

:5

:5

A

M B

Y P A M

S M

IT

T H

C O

P Y R

IG

H

T

C

G

R O

U P file:

DEPARTMENT OF TRANSPORTATION

BLYTHE MAINTENANCE STATION

CHARGING STATION

431 S BROADWAY

BLYTHE, CA 92225

RIVERSIDE COUNTY

DGS_DOT BLYTHE STATION - BTM.DWG

0 ISSUE FOR PERMITTING

MM

MM

JP

10/14/2024

07/9/2024 JPMM

V2

1 ISSUE FOR PERMITTING09/30/2024 JPMM

2 SFM SUBMITTAL10/14/2024 JPMM

3 SFM COMMENTS12/24/2024 JPMM

SITE PLAN

C-5.1

LI

C

EN

SE

D PROFESSIONAL ENGINEER

STATE OF CALIFORNIAC I VI L

JA

SON PAQUETTE

C 79782 Exp. 9/30/26

1"=5'

2.5 00 5 105

N

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/06/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-4163

DOT D8 - Electric Vehicle Supply Equipment - Blythe Maintenance Station

PROJECT NUMBER: 000000000013979; 05/01/26

AutoCAD SHX Text: LEVEL 2 CHARGER NOTE: POWER SHARE ALLOWS A DUAL-PORT STATION TO SHARE POWER FROM A SINGLE CIRCUIT ACROSS TWO PORTS, ADJUSTING POWER DEPENDING ON WHETHER ONE OR BOTH ARE CHARGING. STANDARD WIRING USES AN INDEPENDENT CIRCUIT FOR EACH PORT. POWER SHARE CAN BE USED IN COMBINATION WITH POWER SELECT.

AutoCAD SHX Text: PROPOSED LEVEL 2 CHARGER 80A DUAL-PORT PEDESTAL WITH POWER SHARE [CHARGEPOINT CP6021B] AutoCAD SHX Text: 1 AutoCAD SHX Text: E-4.0 AutoCAD SHX Text: INSTALL 100A 2-POLE BRANCH CIRCUIT BREAKER IN EXISTING 400A (120/240V), 1-PHASE SWITCHBOARD ON PANEL "B" AutoCAD SHX Text: PROPOSED BOLLARD AutoCAD SHX Text: EXISTING VEHICLE WASHPAD AutoCAD SHX Text: EXISTING GENERATOR AutoCAD SHX Text: EXISTING SHED AutoCAD SHX Text: EXISTING ELECTRICAL HANDHOLE AutoCAD SHX Text: PROPOSED PARKING SIGN AutoCAD SHX Text: 2 AutoCAD SHX Text: C-6.0 AutoCAD SHX Text: 1 AutoCAD SHX Text: C-5.0 AutoCAD SHX Text: PROPOSED WHEELSTOP AutoCAD SHX Text: 2 AutoCAD SHX Text: C-6.0 AutoCAD SHX Text: 2 AutoCAD SHX Text: E-4.0 AutoCAD SHX Text: PROPOSED 100A (120/240V), 1-PHASE SAFETY SWITCH DISCONNECT AutoCAD SHX Text: CONSTRUCTION NOTES: : REMOVE AND REPLACE EXISTING CONCRETE PAVEMENT WHERE TRENCHING IS REQUIRED FOR THE INSTALLATION OF CONDUIT PER DETAILS ON SHEET E-1.0. SEE DETAILS ON SHEET C-6.0 FOR TRENCH SECTION. REMOVE AND REPLACE EXISTING DECOMPOSED GRAVEL WHERE TRENCHING IS REQUIRED FOR THE INSTALLATION OF CONDUIT PER DETAILS ON SHEET E-1.0. SEE DETAILS ON SHEET C-6.0 FOR TRENCH SECTION. REMOVE EXISTING AC PAVEMENT FOR THE INSTALLATION OF LEVEL 2 CHARGER AND CONCRETE BASE. SEE DETAIL 1 ON SHEET E-4.0. REMOVE EXISTING AC PAVEMENT FOR THE INSTALLATION OF SAFETY SWITCH DISCONNECT ON H-FRAME. SEE DETAIL 2 ON SHEET E-4.0. REMOVE AND REPLACE EXISTING STRIPING FOR EV STALL 1 THROUGH 4. STRIPING SHALL BE (OSHA SAFETY GREEN-14120) SURFACE MARKING SHALL BE WHITE LETTERS A MINIMUM OF 12 INCHES IN HEIGHT, THE CENTERLINE OF THE TEXT SHALL BE A MAXIMUM OF 6 INCHES FROM CENTERLINE OF THE VEHICLE SPACE AND IT'S LOWER SIDE ALIGNED WITH THE END OF THE PARKING SPACE LENGTH.

AutoCAD SHX Text: 1A AutoCAD SHX Text: 1B AutoCAD SHX Text: 2 AutoCAD SHX Text: 4 AutoCAD SHX Text: 5 AutoCAD SHX Text: 6 AutoCAD SHX Text: NOTES: : 1. RUN 48" OF WIRING ABOVE THE CONDUIT (FOR L2'S PEDESTAL), AS THE HOOK UPS ARE IN THE TOP "HEAD" RUN 48" OF WIRING ABOVE THE CONDUIT (FOR L2'S PEDESTAL), AS THE HOOK UPS ARE IN THE TOP "HEAD" OF THE PEDESTAL UNIT. 2. DO NOT EXTEND THE CONDUIT FORE THAN 9" ABOVE THE PAD. DO NOT EXTEND THE CONDUIT FORE THAN 9" ABOVE THE PAD. 3. INSTALLATION OF ALL CHARGEPOINT CP6000 LEVEL 2 CHARGERS AND PEDESTALS, EVSE INFORMATION IS INSTALLATION OF ALL CHARGEPOINT CP6000 LEVEL 2 CHARGERS AND PEDESTALS, EVSE INFORMATION IS PROVIDED FOR REFERENCE ONLY. CHARGER AND PEDESTALS TO BE INSTALLED BY OTHERS. 4. CONTRACTOR TO PROVIDE EMERGENCY SHUT OFF LABELS PER SPECIFICATION SECTION 26 05 53-2.2G. CONTRACTOR TO PROVIDE EMERGENCY SHUT OFF LABELS PER SPECIFICATION SECTION 26 05 53-2.2G. 5. SEE C-4.0 FOR LEGEND.SEE C-4.0 FOR LEGEND.

detailed checked

no. by descriptiondate ckd

8340 JUNIPER CREEK LN

SAN DIEGO, CA 92126

(619) 880-9797 project contract

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G

H drawing sheet of 14 rev.

sheets

I

/3

/2

:5

:5

A

M B

Y P A M

S M

IT

T H

C O

P Y R

IG

H

T

C

G

R O

U P file:

DEPARTMENT OF TRANSPORTATION

BLYTHE MAINTENANCE STATION

CHARGING STATION

431 S BROADWAY

BLYTHE, CA 92225

RIVERSIDE COUNTY

DGS_DOT BLYTHE STATION - BTM.DWG

0 ISSUE FOR PERMITTING

MM

MM

JP

10/14/2024

07/9/2024 JPMM

V2

1 ISSUE FOR PERMITTING09/30/2024 JPMM

2 SFM SUBMITTAL10/14/2024 JPMM

3 SFM COMMENTS12/24/2024 JPMM

DETAILS

C-6.0

LI

C

EN

SE

D PROFESSIONAL ENGINEER

STATE OF CALIFORNIAC I VI L

JA

SON PAQUETTE

C 79782 Exp. 9/30/26

AUTHORIZED

FLEET OR

DESIGNATED

ELECTRIC

VEHICLES

ONLY

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

01/06/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-4163

DOT D8 - Electric Vehicle Supply Equipment - Blythe Maintenance Station

PROJECT NUMBER: 000000000013979; 05/01/26

AutoCAD SHX Text: NOTES: : 1. ASPHALT AND BASE MATERIAL SHALL COMPLY WITH CALTRANS OR LOCAL JURISDICTION SPEC. FOR HMA ASPHALT AND BASE MATERIAL SHALL COMPLY WITH CALTRANS OR LOCAL JURISDICTION SPEC. FOR HMA SURFACE COURSE AND CLASS 2 AGGREGATE BASE. 2. ANY EXCAVATION LEFT OPEN NEEDS TO BE FENCED, BARRICADED, OR TRENCH PLATED TO ENSURE THE ANY EXCAVATION LEFT OPEN NEEDS TO BE FENCED, BARRICADED, OR TRENCH PLATED TO ENSURE THE SAFETY OF THE GENERAL PUBLIC. 3. ANY PAVEMENT DAMAGE DURING CONSTRUCTION SHALL BE REPAIRED OR REPLACED BY THE SUBCONTRACTOR ANY PAVEMENT DAMAGE DURING CONSTRUCTION SHALL BE REPAIRED OR REPLACED BY THE SUBCONTRACTOR TO PRE CONSTRUCTION CONDITIONS OR BETTER. 4. TOTAL CONDUIT COVER IS REQUIRED TO BE 2'-0" MIN. OR 6" BELOW FROST LINE PER LOCAL JURISDICTION TOTAL CONDUIT COVER IS REQUIRED TO BE 2'-0" MIN. OR 6" BELOW FROST LINE PER LOCAL JURISDICTION REQUIREMENTS, IF THE FROST LINE EXCEED 2'-0". 5. EXACT NUMBER OF CONDUITS SHALL BE DETERMINED BY SHEET E1.0, EXACT CONDUIT PLACEMENT IN TRENCH EXACT NUMBER OF CONDUITS SHALL BE DETERMINED BY SHEET E1.0, EXACT CONDUIT PLACEMENT IN TRENCH SHALL BE DETERMINED BY THE SUBCONTRACTOR IN THE FIELD BASED ON PHYSICAL MEASUREMENTS AND JURISDICTIONAL REQUIREMENTS. 6. CLEAN GRANULAR BACKFILL SHALL BE PLACED IN LOOSE, LEVEL LIFTS NOT TO EXCEED 6-INCHES THICKNESS. CLEAN GRANULAR BACKFILL SHALL BE PLACED IN LOOSE, LEVEL LIFTS NOT TO EXCEED 6-INCHES THICKNESS. 7. COMPACTION SHALL BE BY MECHANICAL VIBRATORY PLATE COMPACTORS UNLESS OTHERWISE SPECIFIED. COMPACTION SHALL BE BY MECHANICAL VIBRATORY PLATE COMPACTORS UNLESS OTHERWISE SPECIFIED. 8. COMPACT TO THE SAME DENSITY AS THE UNDISTURBED SOIL. COMPACT EACH LAYER UNTIL THERE IS NO COMPACT TO THE SAME DENSITY AS THE UNDISTURBED SOIL. COMPACT EACH LAYER UNTIL THERE IS NO EVIDENCE OF CONSOLIDATION. 9. FINAL LIFT BENEATH PAVEMENTS SHALL BE COMPACTED A MINIMUM OF FOUR COMPLETE PASSES. FINAL LIFT BENEATH PAVEMENTS SHALL BE COMPACTED A MINIMUM OF FOUR COMPLETE PASSES. 10. CONTROLLED LOW STRENGTH MATERIAL (CLSM) MAY BE USED IN PLACE OF CLEAN GRANULAR CONTROLLED LOW STRENGTH MATERIAL (CLSM) MAY BE USED IN PLACE OF CLEAN GRANULAR BACKFILL. CLSM SHALL CONFORM TO THE REQUIREMENTS OF THE DOT STANDARD SPECIFICATIONS. 11. SHADE MATERIAL SHALL NOT CONTAIN ROCKS LARGER THAN 1-1/2 INCHES IN THEIR GREATEST DIMENSION SHADE MATERIAL SHALL NOT CONTAIN ROCKS LARGER THAN 1-1/2 INCHES IN THEIR GREATEST DIMENSION AND SHALL CONFORM TO SCE SERVICE REQUIREMENTS. 12. ALL UTILITY CROSSINGS SHALL PROVIDE A MINIMUM OF 12 INCHES CLEAR VERTICAL SEPARATION FROM THE ALL UTILITY CROSSINGS SHALL PROVIDE A MINIMUM OF 12 INCHES CLEAR VERTICAL SEPARATION FROM THE SDG&E ELECTRIC FACILITIES. 13. APPLY SLURRY COAT IN A UNIFORM THICKNESS IN ACCORDANCE WITH ASTM D3910 AND ALLOW TO CURE FOR APPLY SLURRY COAT IN A UNIFORM THICKNESS IN ACCORDANCE WITH ASTM D3910 AND ALLOW TO CURE FOR A MIN. OF 5 DAYS. ROLL SLURRY SEAL TO REMOVE RIDGES AND PROVIDE A UNIFORM, SMOOTH SURFACE. 14. DIRECT BURIED UTILITY TRENCH BACK FILL SHALL COMPLY WITH THE FOLLOWING SPECIFICATIONS: DIRECT BURIED UTILITY TRENCH BACK FILL SHALL COMPLY WITH THE FOLLOWING SPECIFICATIONS: -SECTION 31 20 00, EARTH MOVING -SECTION 26 05 43, UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS -SECTION 32 12 16, ASPHALT PAVING -SECTION 03 30 00, CAST-IN-PLACE CONCRETE AutoCAD SHX Text: PAVEMENT TRENCH DETAIL NOT TO SCALE AutoCAD SHX Text: SOIL TRENCH DETAIL NOT TO SCALE AutoCAD SHX Text: CONCRETE TRENCH DETAIL NOT TO SCALE AutoCAD SHX Text: SAW CUT EXISTING ASPHALT ON SITE AutoCAD SHX Text: EXISTING AC PAVEMENT AutoCAD SHX Text: CAUTION TAPE @ 1/2 DEPTH AutoCAD SHX Text: ASPHALT SURFACE AutoCAD SHX Text: ASPHALT BASE AutoCAD SHX Text: EXISTING AC PAVEMENT AutoCAD SHX Text: MATERIAL NOT TO CONTAIN ROCKS LARGER THAN 3" DIAMETER WITHIN THE FIRST 6" OF BACKFILL PLACED AutoCAD SHX Text: 3" CLEAN SAND BEDDING TO BE PLACED BELOW, SIDE & TOP OF CONDUIT PER ASTM C33/C33M; FINE AGGREGATE AutoCAD SHX Text: FIXED BOLLARD DETAIL NOT TO SCALE AutoCAD SHX Text: 1 AutoCAD SHX Text: - AutoCAD SHX Text: 1. CONCRETE SHALL COMPLY WRITTEN SPECIFICATION. MINIMUM CONCRETE STRENGTH SHALL BE 3,000 CONCRETE SHALL COMPLY WRITTEN SPECIFICATION. MINIMUM CONCRETE STRENGTH SHALL BE 3,000 PSI. 2. CONCRETE REINFORCEMENT SHALL COMPLY WITH WRITTEN SPECIFICATION. CONCRETE REINFORCEMENT SHALL COMPLY WITH WRITTEN SPECIFICATION. 3. ANY PAVEMENT DAMAGE DURING CONSTRUCTION SHALL BE REPAIRED OR REPLACED BY THE ANY PAVEMENT DAMAGE DURING CONSTRUCTION SHALL BE REPAIRED OR REPLACED BY THE SUBCONTRACTOR TO PRE CONSTRUCTION CONDITIONS OR BETTER. 4. TOTAL CONDUIT COVER IS REQUIRED TO BE 2'-0" MIN. OR 6" BELOW FROST LINE PER LOCAL TOTAL CONDUIT COVER IS REQUIRED TO BE 2'-0" MIN. OR 6" BELOW FROST LINE PER LOCAL JURISDICTION REQUIREMENTS, IF THE FROST LINE EXCEED 2'-0". 5. EXACT NUMBER OF CONDUITS SHALL BE DETERMINED BY SHEET E1.0 & E1.1, EXACT CONDUIT EXACT NUMBER OF CONDUITS SHALL BE DETERMINED BY SHEET E1.0 & E1.1, EXACT CONDUIT PLACEMENT IN TRENCH SHALL BE DETERMINED BY THE SUBCONTRACTOR IN THE FIELD BASED ON PHYSICAL MEASUREMENTS AND JURISDICTIONAL REQUIREMENTS. 6. CLEAN GRANULAR BACKFILL SHALL BE PLACED IN LOOSE, LEVEL LIFTS NOT TO EXCEED 6-INCHES CLEAN GRANULAR BACKFILL SHALL BE PLACED IN LOOSE, LEVEL LIFTS NOT TO EXCEED 6-INCHES THICKNESS. 7. COMPACTION SHALL BE BY MECHANICAL VIBRATORY PLATE COMPACTORS UNLESS OTHERWISE COMPACTION SHALL BE BY MECHANICAL VIBRATORY PLATE COMPACTORS UNLESS OTHERWISE SPECIFIED. 8. COMPACT TO THE SAME DENSITY AS THE UNDISTURBED SOIL. COMPACT EACH LAYER UNTIL THERE COMPACT TO THE SAME DENSITY AS THE UNDISTURBED SOIL. COMPACT EACH LAYER UNTIL THERE IS NO EVIDENCE OF CONSOLIDATION. 9. FINAL LIFT BENEATH PAVEMENTS SHALL BE COMPACTED A MINIMUM OF FOUR COMPLETE PASSES. FINAL LIFT BENEATH PAVEMENTS SHALL BE COMPACTED A MINIMUM OF FOUR COMPLETE PASSES. 10. CONTROLLED LOW STRENGTH MATERIAL (CLSM) MAY BE USED IN PLACE OF CLEAN GRANULAR CONTROLLED LOW STRENGTH MATERIAL (CLSM) MAY BE USED IN PLACE OF CLEAN GRANULAR BACKFILL. CLSM SHALL CONFORM TO THE REQUIREMENTS OF THE DOT STANDARD SPECIFICATIONS. 11. SHADE MATERIAL SHALL NOT CONTAIN ROCKS LARGER THAN 1-1/2 INCHES IN THEIR GREATEST SHADE MATERIAL SHALL NOT CONTAIN ROCKS LARGER THAN 1-1/2 INCHES IN THEIR GREATEST DIMENSION AND SHALL CONFORM TO SCE SERVICE REQUIREMENTS. 12. ALL UTILITY CROSSINGS SHALL PROVIDE A MINIMUM OF 12 INCHES CLEAR VERTICAL SEPARATION ALL UTILITY CROSSINGS SHALL PROVIDE A MINIMUM OF 12 INCHES CLEAR VERTICAL SEPARATION FROM THE SCE ELECTRIC FACILITIES. 13. APPLY SLURRY COAT IN A UNIFORM THICKNESS IN ACCORDANCE WITH ASTM D3910 AND ALLOW TO APPLY SLURRY COAT IN A UNIFORM THICKNESS IN ACCORDANCE WITH ASTM D3910 AND ALLOW TO CURE FOR A MIN. OF 5 DAYS. ROLL SLURRY SEAL TO REMOVE RIDGES AND PROVIDE A UNIFORM, SMOOTH SURFACE. 14. DIRECT BURIED UTILITY TRENCH BACK FILL SHALL COMPLY WITH THE FOLLOWING SPECIFICATIONS: DIRECT BURIED UTILITY TRENCH BACK FILL SHALL COMPLY WITH THE FOLLOWING SPECIFICATIONS: -SECTION 31 20 00, EARTH MOVING -SECTION 26 05 43, UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS -SECTION 32 12 16, ASPHALT PAVING -SECTION 03 30 00, CAST-IN-PLACE CONCRETE AutoCAD SHX Text: NOTES:

AutoCAD SHX Text: SAW CUT EXISTING CONCRETE AutoCAD SHX Text: EXISTING CONCRETE PAVEMENT AutoCAD SHX Text: CAUTION TAPE @ 1/2 DEPTH AutoCAD SHX Text: CONCRETE SURFACE-MATCH EXISTING CONCRETE SECTION AutoCAD SHX Text: CONCRETE BASE AutoCAD SHX Text: EXISTING AC PAVEMENT AutoCAD SHX Text: MATERIAL NOT TO CONTAIN ROCKS LARGER THAN 3" DIAMETER WITHIN THE FIRST 6" OF BACKFILL PLACED AutoCAD SHX Text: 3" CLEAN SAND BEDDING TO BE PLACED BELOW, SIDE & TOP OF CONDUIT PER ASTM C33/C33M; FINE AGGREGATE AutoCAD SHX Text: NATIVE MATERIAL AutoCAD SHX Text: NATIVE BACKFILL OR ACCEPTABLE MATERIAL AutoCAD SHX Text: UNDISTURBED SOIL (TYP) AutoCAD SHX Text: EXISTING GRADE AutoCAD SHX Text: 3" CLEAN SAND BEDDING TO BE PLACED BELOW, SIDE & TOP OF CONDUIT PER ASTM C33/C33M; FINE AGGREGATE AutoCAD SHX Text: MATERIAL NOT TO CONTAIN ROCKS LARGER THAN 3" DIAMETER WITHIN THE FIRST 6" OF BACKFILL PLACED AutoCAD SHX Text: SHADE AutoCAD SHX Text: WARNING TAPE @ 12" BELOW FINISHED GRADE AutoCAD SHX Text: NOTES: 1. ANY EXCAVATION LEFT OPEN NEEDS TO BE FENCED, BARRICADED, OR COVERED W/ TRAFFIC RATED TRENCH PLATING TO ENSURE THE SAFETY OF THE GENERAL PUBLIC. 2. ANY LANDSCAPE DAMAGE DURING CONSTRUCTION SHALL BE REPAIRED OR REPLACED BY THE CONTRACTOR TO PRE CONSTRUCTION CONDITIONS OR BETTER. CONSTRUCTION CONDITIONS OR BETTER. 3. TOTAL CONDUIT COVER IS REQUIRED TO BE 2'-0" MIN. OR 6" BELOW FROST LINE PER LOCAL JURISDICTION TOTAL CONDUIT COVER IS REQUIRED TO BE 2'-0" MIN. OR 6" BELOW FROST LINE PER LOCAL JURISDICTION REQUIREMENTS, IF THE FROST LINE EXCEED 2'-0". 4. EXACT NUMBER OF CONDUITS SHALL BE DETERMINED BY SHEET E-1.0, EXACT CONDUIT PLACEMENT IN EXACT NUMBER OF CONDUITS SHALL BE DETERMINED BY SHEET E-1.0, EXACT CONDUIT PLACEMENT IN TRENCH SHALL BE DETERMINED BY THE CONTRACTOR IN THE FIELD BASED ON PHYSICAL MEASUREMENTS AND JURISDICTIONAL REQUIREMENTS. 5. CLEAN GRANULAR BACKFILL SHALL BE PLACED IN LOOSE, LEVEL LIFTS NOT TO EXCEED 6-INCHES CLEAN GRANULAR BACKFILL SHALL BE PLACED IN LOOSE, LEVEL LIFTS NOT TO EXCEED 6-INCHES THICKNESS. 6. COMPACTION SHALL BE BY MECHANICAL VIBRATORY PLATE COMPACTORS UNLESS OTHERWISE SPECIFIED. COMPACTION SHALL BE BY MECHANICAL VIBRATORY PLATE COMPACTORS UNLESS OTHERWISE SPECIFIED. 7. COMPACT TO THE SAME DENSITY AS THE UNDISTURBED SOIL. COMPACT EACH LAYER UNTIL THERE IS NO COMPACT TO THE SAME DENSITY AS THE UNDISTURBED SOIL. COMPACT EACH LAYER UNTIL THERE IS NO EVIDENCE OF CONSOLIDATION. 8. FINAL LIFT BENEATH PAVEMENTS SHALL BE COMPACTED A MINIMUM OF FOUR COMPLETE PASSES. FINAL LIFT BENEATH PAVEMENTS SHALL BE COMPACTED A MINIMUM OF FOUR COMPLETE PASSES. 9. CONTROLLED LOW STRENGTH MATERIAL (CLSM) MAY BE USED IN PLACE OF GRANULAR BACKFILL. CLSM CONTROLLED LOW STRENGTH MATERIAL (CLSM) MAY BE USED IN PLACE OF GRANULAR BACKFILL. CLSM SHALL CONFORM TO THE REQUIREMENTS OF THE PROJECT SPECIFICATIONS. 10. SHADE MATERIAL SHALL NOT CONTAIN ROCKS LARGER THAN 1-1/2 INCHES IN THEIR GREATEST DIMENSION. SHADE MATERIAL SHALL NOT CONTAIN ROCKS LARGER THAN 1-1/2 INCHES IN THEIR GREATEST DIMENSION. 11. ALL UTILITY CROSSINGS SHALL PROVIDE A MINIMUM OF 12 INCHES CLEAR VERTICAL SEPARATION FROM THE ALL UTILITY CROSSINGS SHALL PROVIDE A MINIMUM OF 12 INCHES CLEAR VERTICAL SEPARATION FROM THE SCE ELECTRIC FACILITIES. 12.

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .