Plans.pdf
PDF 12 MB Posted
- Solicitation number
- 0000037557
- Issued by
- San Luis Obispo County, San Luis Obispo City, California
About this file
This construction plan document pertains to electric vehicle supply equipment (EVSE) installation at Caltrans District 5 Office in San Luis Obispo County, California, as part of a state project (Project 13813) being managed by the California Department of General Services, Office of Sustainability. The project consists of installing one new panelboard and associated electrical feeders to support six electric vehicle charging station (EVCS) ports within the District 5 Office parking lot, specifically three dual-port Level 3 DC fast charging pedestals capable of 50,000 volts-amperes each, designed exclusively for designated fleet vehicles. The scope includes structural and civil work necessary to support the installation, including concrete foundations for the charging pedestals, bollard installation, sign post installation, underground conduit burial, pull boxes, and site restoration. The project area encompasses 2,500 square feet of exterior work, with all work required to comply with 2022 California Building Code, California Electrical Code, California Fire Code, and applicable NFPA standards. The construction drawings indicate third-party testing is required for all new feeder conductors, minimum 72-hour notice is required for any facility disruptions, and all EVCS final terminations will be performed by the state vendor rather than the construction contractor. The project received California State Fire Marshal approval on October 3, 2025, with final approval confirmed on December 19, 2025.
The project is being bid exclusively to small business and micro-business contractors certified through the California Department of General Services, with bids submitted electronically to Pavan.Randhawa@dgs.ca.gov prior to February 4, 2025 at 2:00 p.m. A Class C-10 contractor license is required to bid, and contractors must provide valid Certificates of Reported Compliance for any fleet vehicles subject to California Air Resources Board In-Use Off-Road Diesel-Fueled Fleet Regulations. Contractors must also provide all labor, materials, and services necessary for complete system installation and operational testing, including site work such as saw cutting, trenching, backfilling, and lot surface restoration. The EVCS equipment and final installation connections will be provided by a state-designated vendor and are not the contractor's responsibility, though the contractor must provide all supporting infrastructure shown on the construction documents.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Project_Manual.pdf | ||
| Bid_Package.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROACTIVE ENGINEERING CONSULTANTS
27051 TOWNE CENTRE DRIVE, SUITE 270
FOOTHILL RANCH, CA 92610
(949) 716-7460
CONTACT: FELIX GONZALEZ
SOLID ROCK STRUCTURAL SOLUTIONS
1501 QUAIL STREET, SUITE 150
NEWPORT BEACH, CA 92660
(949) 418-6722
CONTACT: ROBERT J. FECAROTTA
Caltrans District 5 Office
EVSE Installation
100% Construction Drawings
LOCATION MAP
NOT TO SCALE
INDEX OF DRAWINGS
SCOPE OF WORK
THE SCOPE OF THIS PROJECT CONSISTS OF THE INSTALLATION OF THE ELECTRIC
VEHICLE SUPPLY EQUIPMENT (EVSE) TO PROVIDE POWER TO (6) ELECTRIC VEHICLE
CHARGING STATION (EVCS) PORTS WITHIN THE DISTRICT 5 OFFICE. SEE EVCS NOTE
ON THIS SHEET.
THE ELECTRIC VEHICLE SUPPLY EQUIPMENT IS MADE UP OF (1) NEW PANELBOARD AS
WELL AS NEW FEEDERS TO THE EVCS PORTS LOCATIONS AS SHOWN ON THESE
PLANS. PROJECT INCLUDES STRUCTURAL AND CIVIL WORK EFFORT/S NECESSARY TO
SUPPORT THIS PROJECT. SEE SHEET E1.00 FOR A SUMMARY OF THE EVCS PORTS.
ALL EVSE INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE
INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC
SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO COMPLY
WITH CBC 11B-228.3.2 ACCESS REQUIREMENTS.
ALTHOUGH THE CONTRACTOR MAY NOT PROCURE OR PERFORM THE FINAL
INSTALLATION OF THE EVSE, SUCH WORK IS WITHIN THE PERMIT SCOPE AND MAY BE
PERFORMED BY OTHERS.
ALL WORK PERTAINING TO AND ALL MATERIALS SUPPLIED FOR EXECUTING AND
COMPLETING THIS CONTRACT SHALL COMPLY WITH PROVISIONS SPECIFIED IN THE
CONTRACT DOCUMENTS AND WITH ALL APPLICABLE LAWS, REGULATIONS AND
ORDINANCES GOVERNING WORK INCLUDING, BUT NOT NECESSARILY LIMITED TO
THOSE OF THE APPLICABLE CODES LISTED ON SHEET E0.01.
SHEET COUNT DWG. NO. DESCRIPTION
1 OF 12 T0.01 TITLE SHEET, LOCATION MAP, GENERAL NOTES &
SHEET INDEX
2 OF 12 E0.01 SYMBOLS, DESIGNATION AND ABBREVIATIONS
3 OF 12 E1.00 SITE PLAN
4 OF 12 E2.00 POWER PLAN
5 OF 12 E4.00 ELECTRICAL DETAILS
6 OF 12 E5.00 SINGLE LINE DIAGRAM & SCHEDULES
7 OF 12 C1 TITLE SHEET
8 OF 12 C2 SITE PLAN
9 OF 12 S0.01 GENERAL NOTES
10 OF 12 S0.02 SPECIAL INSPECTION TABLES, ABBREVIATIONS
AND SYMBOLS
11 OF 12 S1.01 PLANS
12 OF 12 S1.02 PLANS AND DETAILS
1. THE ARRANGEMENT OF THE EQUIPMENT, ELECTRICAL DEVICES, ETC. SHOWN ON THESE DRAWINGS IS GENERAL AND IS SHOWN TO IDENTIFY THE GENERAL INTENT OF THE PROJECT. ALL DETAILS AND ARRANGEMENTS SHALL BE VERIFIED PRIOR TO THE START OF WORK. THE DRAWINGS ARE NOT INTENDED TO SHOW EXACT DIMENSIONS/LOCATIONS.
2. CODE COMPLIANCE: ALL WORK SHALL CONFORM TO BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE CODES, STANDARDS, AND ORDINANCE AS SET FORTH BY THE AUTHORITIES HAVING JURISDICTION AND THEIR LATEST ADOPTED EDITIONS (IN EFFECT AT THE TIME OF THE BUILDING PERMIT APPLICATION) OF THE FOLLOWING PUBLICATIONS:
· CALIFORNIA CODE OF REGULATIONS TITLE 24: INCLUDES 2022 CALIFORNIA ELECTRICAL CODE, 2022 CALIFORNIA FIRE
CODE, 2022 CALIFORNIA BUILDING CODE, APPLICABLE YEARS OF NFPA ETC. WITH CALIFORNIA AND OTHER LOCAL
AMENDMENTS AS APPLICABLE.
· 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN.
3. SAFETY: THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO MAINTAIN ALL EQUIPMENT IN A SAFE AND RESPONSIBLE MANNER. KEEP DEAD FRONT EQUIPMENTS IN PLACE WHILE ENERGIZED. CONDUCT ALL CONSTRUCTION OPERATIONS IN A SAFE MANNER FOR EMPLOYEES AS WELL AS OTHER WORK PERSONS OR ANYONE VISITING THE JOB SITE. PROVIDE BARRIERS, FLAGS, TAPE, ETC. AS REQUIRED FOR SAFETY. THE CONTRACTOR SHALL HOLD ALL PARTIES HARMLESS OF
NEGLIGENT PRACTICES, WHICH MAY CAUSE INJURY TO OTHERS ON OR NEAR THE JOB SITE.
4. FIRE RATED ASSEMBLIES SHALL MAINTAIN RATINGS AS SPECIFIED IN THE CALIFORNIA BUILDING CODE, CHAPTER 7. ALL ASSEMBLIES TO BE PENETRATED SHALL BE INSTALLED WITH APPLICABLE THROUGH-PENETRATION FIRESTOP SYSTEM AS DETERMINED BY UL CLASSIFICATION. BEFORE CONSTRUCTION, VERIFY AND COMPLY WITH REQUIREMENTS.
5. PROVIDE THIRD-PARTY TESTING FOR ALL NEW FEEDER CONDUCTORS. BRANCH CIRCUITS ARE NOT REQUIRED TO BE
TESTED BY THIRD-PARTY. REFER TO PROJECT SPECIFICATIONS FOR MORE INFORMATION.
FOR EXISTING BUILDINGS:
1. ASBESTOS/LEAD PAINT: IF DURING THE COURSE OF WORK THE CONTRACTOR OBSERVES THE EXISTENCE OF ASBESTOS/LEAD PAINT, ASBESTOS BEARING MATERIALS, THE CONTRACTOR SHALL IMMEDIATELY TERMINATE FURTHER WORK ON THE PROJECT AND NOTIFY THE OWNER OF THE CONDITIONS. THE OWNER WILL, AFTER CONSULTATION WITH
THE OWNER'S REPRESENTATIVE, DETERMINE A FURTHER COURSE OF ACTION.
2. ANY DEMOLITION WORK SHOWN WAS PREPARED FOR THE CONVENIENCE OF THE CONTRACTOR. THE ENGINEER DOES NOT REPRESENT THAT ALL ITEMS WHICH MAY REQUIRE DEMOLITION HAVE BEEN SHOWN. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO CAREFULLY EXAMINE THE SITE AND CONTRACT DOCUMENTS AND TO PERFORM ALL DEMOLITION AND RECONSTRUCTION WHICH MAY BE REQUIRED FOR THE PROPER EXECUTION AND
COMPLETION OF THE WORK.
3. EXISTING CONDITIONS: INFORMATION SHOWN FOR EXISTING CONDITIONS WAS PRIMARILY GAINED FROM "AS-BUILT" DRAWINGS AND/OR LIMITED FIELD INVESTIGATION. BEFORE BID, VISIT SITE TO VERIFY EXISTING CONDITIONS AND MAKE
ALLOWANCE FOR VARIATION FROM THAT SHOWN.
4. CLOSELY COORDINATE OUTAGE AND FACILITY DISRUPTION TIME WITH OWNER. MINIMUM 72-HOURS NOTICE IS REQUIRED
BEFORE ANY CIRCUIT SHUTDOWN OR DISRUPTION OF FACILITY PERSONNEL FUNCTIONING.
GENERAL NOTES
OFFICE OF SUSTAINABILITY, DGS
707 3RD STREET, 4TH FLOOR
WEST SACRAMENTO, CA 95606
(279) 946-8547
STEVEN PIEPENHAGEN
BUILDING INFORMATION
EVCS NOTE:
ELECTRICAL VEHICLE CHARGING STATION
(EVCS) SHALL BE PROVIDED BY THE STATE
(DEPARTMENT OF GENERAL SERVICES), AND
INSTALLED BY THE CURRENT STATE ELECTRIC
VEHICLE CHARGING STATION VENDOR. ALL
FINAL TERMINATIONS AND/OR SPLICING FOR
THE EVCS SHALL BE THE RESPONSIBILITY AND
PERFORMED BY THE STATE VENDOR.
PROJECT TEAM
PROJECT DIRECTOR
STRUCTURAL ENGINEERCIVIL ENGINEER
ELECTRICAL ENGINEER
GOSS ENGINEERING, INC.
255 EAST RINCON STREET, SUITE 301,
CORONA, CA 92879
(951) 340-1977
CONTACT: ED BURTCH
R
CALL 811 BEFORE YOU DIG.
DGS PROJECT NUMBER: 000000000013813
ARC-FLASH NOTE:
ALL NEW ELECTRICAL SWITCHBOARDS, PANELBOARDS,
EQUIPMENT/DEVICES AND SUCH, SHALL BE PROVIDED WITH AN
ARC-FLASH HAZARD WARNING LABEL/MARKING, IN COMPLIANCE TO
THE REQUIREMENTS OF THE LATEST CEC 110.16. THE LABELS
SHALL BE GENERATED BY THE DESIGN TEAM AND INSTALLED BY
THE ELECTRICAL CONTRACTOR.
PROJECT
LOCATION
CONSTRUCTION TYPE: N/A*
OCCUPANCY CLASSIFICATION: N/A*
OCCUPANCY LOAD: N/A*
ACTUAL BUILDING HEIGHT: N/A*
BUILDING AREA (SQ. FT.) N/A*
AREA OF PROJECT (SQ. FT.) 2,500 SQ. FT.
SEPARATED OR NON-SEPARATED USE: N/A*
ALLOWABLE AREA: N/A*
AREA INCREASED: NONE
HEIGHT INCREASED: NONE
FIRE SPRINKLERS: N/A*
FIRE ALARM: N/A*
OTHER FIRE PROTECTION SYSTEMS: N/A*
SMOKE CONTROL SYSTEM: N/A*
YEAR CONSTRUCTED: N/A*
HIGH FIRE SEVERITY ZONE: N/A*
SEISMIC JOINTS: N/A*
EMERGENCY RESPONDER RADIO COVERAGE: N/A*
*NOT APPLICABLE, ALL WORK IS EXTERIOR.
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
H ig u e ra
S tr e e t, S a n L u is O b is p o C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t O ff ic e E V S E I n s ta lla ti o n
125-01-02.69
08/28/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B
R L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3159-C
95% CD SubmittalEB06/04/2025 1
100% CD SubmittalEB08/28/2025 2
TITLE SHEET, LOCATION
MAP, GENERAL NOTES &
SHEET INDEX
T0.01
H
IG
U E R
A S
T
M
AD
O
NNA
RD.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3159
DOT D5 - Electric Vehicle Supply Equipment
PROJECT NUMBER: 000000000013813; 12/19/25
http://www.gossengineering.com
ABBREVIATIONS
ANNOTATION SYMBOLS
LEGEND
WIRING SYSTEM ABOVE FLOOR
LEVEL
WIRING SYSTEM IN OR UNDER
FLOOR OR CONCEALED IN OR
BEHIND STRUCTURE OR EQUIPMENT
CONDUIT STUB ENDING WITH CAP
E0.1
REMOVE/RELOCATE/DEMOLISH
EXISTING
CIRCUIT BREAKER
DISCONNECT SWITCH (FUSED),
HORSE POWER RATED
SURFACE MOUNTED PANELBOARD
277V/480V
DISCONNECT SWITCH (NON-FUSED)
ELECTRICAL
SYMBOL
DESCRIPTION
F
SHEET WHERE DETAIL
IS DRAWN
OCCURRENCE
DETAIL IDENTIFICATION
(TYP.)
DETAIL
RECONSTRUCTION KEY NOTE
DEMOLITION KEY NOTE
REVISION
REVISED AREA
REVISION TAG
A AMPERE
ADA AMERICAN DISABILITIES ACT
AC ALTERNATING CURRENT
AF AMPERE FRAME
AS AMPERE SWITCH
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING CAPACITY
AT AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BKR BREAKER
BLDG BUILDING
C CONDUIT
CB CIRCUIT BREAKER
CEC CALIFORNIA ELECTRICAL CODE
CKT CIRCUIT
CO CONDUIT ONLY
DB DISTRIBUTION BOARD
DISC DISCONNECT
DIST DISTRIBUTION
DP DISTRIBUTION PANEL
DWG DRAWING
E EXISTING TO REMAIN
EEOR ELECTRICAL ENGINEER ON RECORD
EG EQUIPMENT GROUND
ELEC ELECTRICAL
EHH ELECTRICAL HAND HOLE
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
EV ELECTRIC VEHICLE
EVCS ELECTRIC VEHICLE CHARGING STATION
EVSE ELECTRIC VEHICLE SUPPLY EQUIPMENT
F FUSE, FUSED
FLA FULL LOAD AMPERES
GRD GROUND
GALV GALVANIZE, GALVANIZED
GFCI GROUND FAULT CIRCUIT INTERRUPTER
JB JUNCTION BOX
KA THOUSAND AMPERES
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT-AMPERE
KW KILOWATT
LCL LONG CONTINUOUS LOAD
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM THOUSAND CIRCULAR MILS
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MIN MINIMUM
MLO MAIN LUGS ONLY
MTD MOUNTED
MTR MOTOR
NEC NATIONAL ELECTRIC CODE
NF NON-FUSED
NIC NOT IN CONTRACT
P POLE, POLES
PF POWER FACTOR
PNL PANEL
PRI PRIMARY
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
PH PHASE
Ø PHASE
R REMOVE
RR REMOVE AND RELOCATE
RL RELOCATED
RECEPT RECEPTACLE
RGS RIGID GALVANIZED STEEL CONDUIT
SEC SECONDARY
SUSP SUSPEND, SUSPENDED
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TYP. TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLT, VOLTS
VA VOLT-AMPERES
WT WATERTIGHT
W WATT OR WIRE
WP WEATHER PROOF
XFMR TRANSFORMER
Y WYE CONNECTION
MISCELLANEOUS
LINE TYPES
JUNCTION BOX WITH COVER
(MINIMUM 4" SQUARE OR AS
REQUIRED)
CONCRETE BOLLARD
DUAL PORT PEDESTAL MOUNT
ELECTRIC VEHICLE CHARGING STATION
T
TRANSFORMER. "F" DENOTES FRONT
OF TRANSFORMER.
UNDERGROUND PULL BOX
POST AND SIGNAGE
WHEELSTOP
SURFACE MOUNTED JUNCTION BOX
WITH COVER
(MINIMUM 4" SQUARE OR AS
REQUIRED)
ELECTRICAL GENERAL NOTES
PB
APPLICABLE CODES
J
J
PB SURFACE-MOUNTED PULL BOX
F
FENCE
2022 CALIFORNIA BUILDING CODE (CBC) PART 2, VOLUMES
1 AND 2, TITLE 24
(BASED ON 2021 INTERNATIONAL BUILDING CODE)
2022 CALIFORNIA ELECTRIC CODE (CEC) PART 3, TITLE 24
(BASED ON 2020 NATIONAL ELECTRIC CODE)
2022 CALIFORNIA FIRE CODE (CFC) PART 9, TITLE 24
(BASED ON 2021 INTERNATIONAL FIRE CODE)
2022 CALIFORNIA ENERGY CODE PART 6, TITLE 24
2022 CALIFORNIA REFERENCED STANDARD CODE PART 12,
TITLE 24
TITLE 19, PUBLIC SAFETY, STATE FIRE MARSHAL
REGULATIONS
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
PARTIAL LIST OF APPLICABLE NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA) STANDARDS
NFPA 72, 2022 EDITION - NATIONAL FIRE ALARM AND
SIGNALING CODE (AMENDED BY CSFM)
NFPA 80, 2019 EDITION - FIRE DOORS AND OTHER OPENING
PROTECTIVES
REFER TO 2022 CBC CHAPTER 35 FOR ADDITIONAL
STANDARDS NOT PROVIDED ON THIS LIST
1. CONTRACTOR SHALL PERFORM INSTALLATION WORK IN CONFORMANCE WITH THE 2022 EDITION OF THE CALIFORNIA ELECTRICAL CODE (CEC) AND ALL APPLICABLE CODES, ORDINANCES, AND REGULATIONS.
2. CONDUIT ROUTING AND EQUIPMENT LOCATION AS SHOWN ON THE ELECTRICAL POWER PLAN ARE DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL VERIFY FEASIBILITY OF THE INSTALLATION BEFORE COMMENCING THE JOB. ANY OBSERVATIONS TO THE EXECUTION OF THE WORK SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER OF RECORD IMMEDIATELY.
3. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER CONSTRUCTION TRADES. CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE OF ANY UNRESOLVED ISSUES THAT MAY DELAY INSTALLATION OF
WORK.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING PROPER WORKING SPACE PER CALIFORNIA
ELECTRICAL CODE (CEC), PARAGRAPH 110-26.
5. CONTRACTOR SHALL PROVIDE NECESSARY HARDWARE AND SUPPORTS AS REQUIRED FOR ELECTRICAL CONDUIT/WIRE NOT SCHEDULED FOR DEMOLITION PER CALIFORNIA ELECTRICAL CODE (CEC), PARAGRAPH 110-12.
6. THE SEISMIC BRACING AND ANCHORAGE OF ELECTRICAL CONDUITS SHALL BE IN ACCORDANCE WITH THE
CALIFORNIA BUILDING CODE, CHAPTER 16.
7. CONNECTIONS TO VIBRATING EQUIPMENT AND SEISMIC SEPARATIONS:
· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN DRY INTERIOR LOCATIONS.
· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN AREAS EXPOSED TO WEATHER, DAMP LOCATIONS, CONNECTIONS TO TRANSFORMER ENCLOSURES, AND FINAL CONNECTIONS TO MOTORS.
PROVIDE A SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTOR IN FLEXIBLE CONDUIT RUNS.
MAXIMUM LENGTH SHALL BE SIX FEET UNLESS OTHERWISE NOTED.
8. WHENEVER A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE, EQUIPMENT DEVICES, CIRCUIT BREAKERS, GROUND FAULT PROTECTION SYSTEMS, ETC. (ALL MATERIALS), ARISES ON THE DRAWINGS OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE AND OPERABLE SYSTEMS.
9. ARC-FLASH LABELS SHALL BE PROVIDED FOR THE CONTRACTOR TO INSTALL ON NEW LOW VOLTAGE (480 V, 208 V, 120 V) SYSTEMS REPRESENTED ON THE PROJECT DRAWINGS. THIS INCLUDES SWITCHBOARDS, PANEL BOARDS, TRANSFORMERS, DISCONNECT SWITCHES AND OTHER REQUIRED ELECTRICAL EQUIPMENT. THESE LABELS SERVE AS A GUIDE TO ASSIST THE EMPLOYEES AND OTHERS IN THE SELECTION OF PROPER PERSONAL
PROTECTIVE EQUIPMENT WHEN WORKING AROUND EXPOSED AND ENERGIZED CONDUCTORS.
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
H ig u e ra
S tr e e t, S a n L u is O b is p o C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t O ff ic e E V S E I n s ta lla ti o n
125-01-02.69
08/28/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3159-C
95% CD SubmittalEB06/04/2025 1
100% CD SubmittalEB08/28/2025 2
SYMBOLS,
DESIGNATION AND
ABBREVIATIONS
E0.01
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3159
DOT D5 - Electric Vehicle Supply Equipment
SCALE
SITE PLAN 1
1/16" = 1'-0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
H ig u e ra
S tr e e t, S a n L u is O b is p o C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t O ff ic e E V S E I n s ta lla ti o n
125-01-02.69
08/28/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RI C
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3159-C
95% CD SubmittalEB06/04/2025 1
100% CD SubmittalEB08/28/2025 2
SITE PLAN
E1.00
E2.00
EVCS SUMMARY
LOCATION PARKING TYPE SHEET EXISTING EVCS SPACES NEW EVCS SPACES
PARKING LOT
*FLEET E2.00 (0) (6) LEVEL 3 DCFC
TOTAL FLEET PORTS: (6) LEVEL 3 DCFC
* NOTE:
FLEET EVCS INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO COMPLY WITH CBC
11B-228.3.2 ACCESS REQUIREMENTS.
(E) DISTRIBUTION
BOARD "DMB"
AREA OF WORK
(E) UTILITY
TRANSFORMER
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3159
DOT D5 - Electric Vehicle Supply Equipment
(E) DISTRIBUTION
BOARD "DMB"
4'-0"
(TYP.)
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
EVCS-3
1'-0"
(TYP.)1'-0"
(TYP.)
PANELBOARD "EVH"
(E) ASPHALT
PAVEMENT
(E) CONCRETE
CURB
(E) CONCRETE
WALKWAY
(E) LANDSCAPE
AREA
PB
PB
EVCS-2
(E) CONCRETE
CURB
(E) CHILLER
YARD
12(TYP.)
9(TYP.)
2 7
2"C - 3#4
& 1#8 GRD.
(2 SETS) 2"C - 3#4
& 1#8 GRD.
(3 SETS) 2"C - 3#4
& 1#8 GRD.
10(TYP.)
11 (TYP.)
EVCS-1 1
2 (TYP. OF 3)
7 14
SCALE
POWER PLAN 1
1/4"=1'=0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
H ig u e ra
S tr e e t, S a n L u is O b is p o C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t O ff ic e E V S E I n s ta lla ti o n
125-01-02.69
08/28/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3159-C
95% CD SubmittalEB06/04/2025 1
100% CD SubmittalEB08/28/2025 2
POWER PLAN
E2.00
SHEET NOTES:
DUAL PORT PEDESTAL MOUNTED DCFC EVCS
WITH 50,000VA. PROVIDE 10'-0" OF FEEDER WIRE
(3#4 + 1#8 GRD) COILED UP AT EVCS STUB-UP
LOCATION FOR FINAL EVCS INSTALLATION.
PROVIDE MULE TAPE ROUTED THROUGH
CONDUIT FROM NEAREST PULLBOX TO EVCS
STUB-UP. SEE DETAIL #1 ON SHEET E4.00.
SEE DETAIL #6 SHEET E4.00 FOR ELECTRIC
EQUIPMENT RGS CONDUIT STUB-UP DETAIL.
PROVIDE 13" X 24" X DEPTH AS REQUIRED
CONCRETE PULLBOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #4
SHEET E4.00 FOR UNDERGROUND PULL-BOX
DETAIL.
PROVIDE 11" X 17" X DEPTH AS REQUIRED
CONCRETE PULLBOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #4
SHEET E4.00 FOR UNDERGROUND PULL-BOX
DETAIL.
SEE DETAIL #5 SHEET E4.00 FOR UNDERGROUND
CONDUIT BURIAL DETAIL. PROVIDE NON-NATIVE
SOIL FOR BACKFILLING. NATIVE SOIL MAY BE
USED IF MOISTURE LEVELS ARE ACCEPTABLE
AND IF 90% COMPACTION IS ACHIEVED.
PROVIDE 100A-3P NEMA-3R DISCONNECT
SWITCH (NON-FUSED).
SEE SINGLE LINE DIAGRAM #1 SHEET E5.00 FOR
MORE INFORMATION.
PROVIDE WALL PENETRATION THROUGH
EXISTING NON-RATED WOOD WALL AND FENCE
TO ROUTE CONDUIT TO PANELBOARD.
EXISTING WHEELSTOP SHALL REMAIN AND BE
PROTECTED IN PLACE.
NEW 4" DIA. CONCRETE BOLLARD. REFER TO
DETAIL #7 ON SHEET E4.00.
NEW SIGN POST AND FOOTING. REFER TO CIVIL
DRAWINGS FOR MORE INFORMATION. EXISTING
SIGNAGE SHALL BE REUSED.
EXISTING STRIPING SHALL REMAIN AND BE
PROTECTED IN PLACE.
EXISTING MEMORIAL TREE SHALL REMAIN AND
BE PROTECTED IN PLACE.
MOUNT RGS CONDUIT TO EXISTING WOOD WALL.
GENERAL NOTES:
1. ELECTRICAL ENGINEERING FOR THIS PROJECT
IS BASED ON A FIELD VISIT OF THE ELECTRICAL
SYSTEM. IN CASE OF ANY DISCREPANCIES WITH
EXISTING FIELD CONDITIONS, ELECTRICAL
CONTRACTOR SHALL VERIFY THE EXACT
DIFFERENCES AND NOTIFY THE ELECTRICAL
ENGINEER FOR POSSIBLE REVISION TO THESE
DOCUMENTS.
2. ANY ELECTRICAL AND/OR SIGNAL UTILITY
SHUTDOWNS WITHIN THE AREA OF WORK SHALL
BE COORDINATED AND SCHEDULED IN ADVANCE
WITH THE SITE'S REPRESENTATIVE.
3. ELECTRIC VEHICLE CHARGING STATION/S
(EVCS) SHALL BE PROVIDED, INSTALLED AND
CONNECTED BY STATE VENDOR.
4. PROVIDE MINIMUM OF 1'-0" CLEARANCE BEHIND
ALL PEDESTAL MOUNTED CHARGERS FOR
SERVICING. CONTRACTOR SHALL FIELD VERIFY
ALL DISTANCES PRIOR TO BID.
5. EXISTING VEGETATION TO BE REMOVED,
PROTECTED AND RESTORED AFTER
CONSTRUCTION.
6. REMOVE AND REPLACE IN-GROUND
LANDSCAPING AND IRRIGATION IMPROVEMENTS
AFFECTED IN WORK.
7. PROJECT WAS PREVIOUSLY IN CONSTRUCTION.
DEMOLISH ABANDONED CONDUITS AND
EQUIPMENT THAT IS WITHIN THE AREA OF
WORK.
PROPOSED EV CHARGERS
EVCS #
WALL/PEDESTAL
MOUNT EVCS
SINGLE/DUAL
EVCS
CHARGE PORT #
FULL LOAD
AMPS
VOLTAGE
CHARGE PORT
TYPE
1 PEDESTAL DUAL 60 480V-3PH FLEET
2 PEDESTAL DUAL 60 480V-3PH FLEET
3 PEDESTAL DUAL 60 480V-3PH FLEET
NOTES:
· (3) DUAL PORT EVCS SHALL SERVE (6) FLEET PARKING STALLS
· FLEET EVCS INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS
SHALL NOT BE REQUIRED TO COMPLY WITH CBC 11B-228.3.2 ACCESS REQUIREMENTS.
1 2
1 2
1 2
R
CALL 811 BEFORE YOU DIG.
LEGEND:
EXISTING
NEW
NEW UNDERGROUND
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3159
DOT D5 - Electric Vehicle Supply Equipment
NOT USED 8
N.T.S.
SCALE
NOT USED 9
N.T.S.
SCALE
EMERGENCY SHUT-OFF LABEL DETAIL 2
N.T.S.
4"
3"
RED BACKGROUND
WITH WHITE LETTERING
RED STRIPING
WHITE STRIPING
1'-0"
GRADE LEVEL
2'-0"
MIN.
ELECTRICAL
WARNING TAPE
3" CLEAN SAND
BEDDING
NOTE:
1. PER CEC 300.5 NO CONCRETE CASING IS REQUIRED IF PVC CONDUIT IS USED 2'-0" BELOW GRADE LEVEL. SEE POWER PLAN
FOR MORE INFORMATION.
2. EXISTING SOIL MAY BE USED AS BACKFILL IF MOISTURE LEVELS ARE ACCEPTABLE.
1" MIN. SPACING. SHALL BE EQUAL
TO THE LARGEST CONDUIT SIZE
FOR MULTIPLE CONDUIT RUNS.
3" CLEAN SAND
BEDDING
SCALE
UNDERGROUND PULLBOX DETAIL 4
N.T.S.
NEW BACKFILL
90% COMPACTION
(SEE NOTE 2)
GRAVEL
BASE
ELECTRICAL
CONDUIT(S)
(IN/OUT)
CONCRETE STEEL
REINFORCED
BOLT DOWN LID
12" DEEP REINFORCED
CONCRETE NON-TRAFFIC
PULLBOX
(EXTEND AS REQUIRED)
FINISH GRADE
COMPACTED
BACKFILL
(TYPICAL)
ELECTRICAL
CONDUIT(S)
(IN/OUT)
2'-0"
MIN.
NOTE:
1. LABEL SHALL BE PROVIDED FOR ALL NEW EV CHARGING STATIONS SHOWN ON THESE DRAWINGS. LABEL SHALL
CORRESPOND WITH CHARGER NUMBER AND THE ASSOCIATED PANELBOARD PROVIDING POWER.
2. SEE BELOW FOR LABEL SPECIFICATIONS:
· MATERIAL: THERMAL PRINTED ON REFLECTIVE RED OUTDOOR LABEL STOCK (MEETS ASTMD 4956-99)
· COLOR: WHITE TEXT ON RED BACKGROUND WITH RED AND WHITE ALTERNATING STRIPES
· DAMAGE RESISTANT FROM COMMON CHEMICALS AND SOLVENTS.
· MINIMUM SERVICE TEMPERATURE: -40 DEG FAHRENHEIT
· MAXIMUM SERVICE TEMPERATURE: 180 DEG FAHRENHEIT
· APPLICATION TEMPERATURE: 50 DEG FAHRENHEIT
· FILM THICKNESS: 5.5 MIL
· ADHESIVE THICKNESS: 1 MIL
SCALE
UNDERGROUND CONDUIT BURIAL DETAIL 5
N.T.S.
NOTE:
REFER TO SHEET NOTES ON POWER
PLANS FOR SPECIFIC PULLBOX
DIMENSIONS.
CONDUIT/S PER PLAN
SCALE
BOLLARD DETAIL 6
N.T.S.
6"
MIN.
STEEL COUPLING WITH
THREADED PLUG
FINISH GRADE
PVC CONDUIT
TRANSITION
COUPLING
CONTINUOUS RIGID GALVANIZED
STEEL CONDUIT WRAPPED AROUND
WITH 10 MIL. BLACK ELECTRICAL
PLASTIC INSULATING TAPE TO 6"
ABOVE FINISH GRADE
CONTINUOUS RIGID
GALVANIZED STEEL
CONDUIT
BEND RADIUS
R = 10 x DIA. OF CONDUIT
(MINIMUM)
PROVIDE BUSHING
WHEN PULLING
CONDUCTORS
SCALE
ELECTRICAL EQUIPMENT RGS CONDUIT STUB-UP DETAIL 3
N.T.S.
SCALE
DUAL PORT PEDESTAL ELECTRIC VEHICLE CHARGING STATION 1
N.T.S.
NOTE:
1. FOR EVCS INFORMATION - REFER TO INSTALLATION INSTRUCTIONS PER MANUFACTURER.
2. DUAL PORT CHARGING STATION SHALL BE PROVIDED AND INSTALLED BY CURRENT STATE VENDOR. CONTRACTOR SHALL PROVIDE INFRASTRUCTURE NECESSARY TO SUPPORT THE CHARGER AS SHOWN ON THESE DRAWINGS.
3. PROVIDE FISH TAPE FROM EVCS STUB-UP BACK TO PANELBOARD "EVH".
FINISH GRADE
DUAL PORT DCFC
EV CHARGING STATION
(50,000VA)
NEW CONCRETE EVCS
FOOTING. SEE STRUCTURAL
DRAWINGS FOR MORE
INFORMATION.
3'-0"
PROVIDE LABEL IDENTIFYING
SHUT-OFF LOCATION ON THE FRONT
OF UNIT. LABEL SHALL CORRESPOND
TO CHARGER NUMBER. REFER TO
DETAIL #2 ON THIS SHEET.
PROVIDE 5'-0" OF
1" LIQUIDTIGHT FLEXIBLE
METAL CONDUIT WITH
3#4 & 1#8 GRD. FOR FINAL
CONNECTION
DISCONNECT SWITCH
NON-FUSED, NEMA-3R
SCALE
NOT USED 7
N.T.S.
FRONT
INCOMING 2" PVC
CONDUIT WITH 3#4 &
1#8 GRD. FROM
PULLBOX
4'-0"
CONCRETE CAP
STEEL PIPE AND FOOTING
PER STRUCTURAL
DRAWINGS
FIELD PRIME STEEL BOLLARDS
WITH 2 COATS OF ZINC-RICH
PRIMER. PAINT BOLLARDS WITH 2
COATS OF INDUSTRIAL YELLOW
ENAMEL.
3'-0"
7'-6"
2" A.F.G.
3" MIN.
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
H ig u e ra
S tr e e t, S a n L u is O b is p o C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t O ff ic e E V S E I n s ta lla ti o n
125-01-02.69
08/28/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3159-C
95% CD SubmittalEB06/04/2025 1
100% CD SubmittalEB08/28/2025 2
ELECTRICAL
DETAILS
E4.00
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3159
DOT D5 - Electric Vehicle Supply Equipment
SINGLE LINE DIAGRAM 1
N.T.S.
LEGEND:
EXISTING
NEW
SHEET NOTES:
PROVIDE NEW CIRCUIT BREAKER. SIZE AS
SHOWN. MATCH TO EXISTING MAKE, MODEL AND
AIC RATING. MODIFY "DMB" FACE PLATE TO
ACCOMODATE THE NEW CIRCUIT BREAKER.
200A 3P
600A BUS
200A 3P
(E)
(E F E E D
E R
(E F E E D
E R
M
500A 3P
(E) DISTRIBUTION BOARD "DMB"
600A, 480Y/277V-3Ø,4W
NEMA-3R, 22,000 AIC
(E F E E D
E R
(E F E E D
E R
250A 3P
(E)
CHILLER 1
(E)
CHILLER 2
(E)
CHILL WATER
PUMP
(E)
120 XFMR
PANEL
"EVH"
IF=21,341A
2 1/2"C - 4#250 KCMil
& 1#4 GRD.
L: ~10'-0"
%V.D.: NEGL.
15A 2P
(E) FEEDER INCOMING SERVICE FROM
PACIFIC GAS & ELECTRIC
(PG&E)
SPACE
1 2 3 4 5 6
(GENERAL ELECTRIC AV-LINE SWITCHBOARD)
250A 3P
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
H ig u e ra
S tr e e t, S a n L u is O b is p o C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t O ff ic e E V S E I n s ta lla ti o n
125-01-02.69
08/28/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3159-C
95% CD SubmittalEB06/04/2025 1
100% CD SubmittalEB08/28/2025 2
SINGLE LINE
DIAGRAM &
SCHEDULES
E5.00
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3159
DOT D5 - Electric Vehicle Supply Equipment
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
F L E E T
O N L Y
PB
PB
TITLE SHEET
C1
AM
OM/FG
As Noted
25.063
FG
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
H ig u e ra
S tr e e t, S a n L u is O b is p o C A
As Noted
C a lt ra n s D is tr ic t O ff ic e
E V S E I n s ta lla ti o n
08/15/2025
V1
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 25-S-3159-C
95% CD Submittal06/04/2025 1
100% CD SubmittalFG08/15/2025 2
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3159
DOT D5 - Electric Vehicle Supply Equipment
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
PB
PB
SITE PLAN
C2
R
CALL 811 BEFORE YOU DIG.
CONSTRUCTION NOTES
AM
OM/FG
As Noted
25.063
FG
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
H ig u e ra
S tr e e t, S a n L u is O b is p o C A
As Noted
C a lt ra n s D is tr ic t O ff ic e
E V S E I n s ta lla ti o n
08/15/2025
V1
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 25-S-3159-C
95% CD Submittal06/04/2025 1
100% CD SubmittalFG08/15/2025 2
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3159
DOT D5 - Electric Vehicle Supply Equipment
1. ALL WORK SHALL CONFORM TO THE MINIMUM STANDARDS OF THE FOLLOWING CODES:
2022 CALIFORNIA BUILDING CODE AND LATEST REVISIONS
REFERRED TO HERE AS "THE CODE", AND ANY OTHER REGULATING AGENCIES WHICH HAVE AUTHORITY OVER ANY PORTION OF THE WORK, INCLUDING THE STATE OF CALIFORNIA DIVISION OF INDUSTRIAL
SAFETY, AND THOSE CODES & STANDARDS LISTED IN THESE NOTES AND SPECIFICATIONS.
2. SEISMIC ANALYSIS PER CHAPTER 16 OF THE CODE UTILIZING THE FOLLOWING PROCEDURE:
- THE EQUIVALENT LATERAL FORCE ANALYSIS
RISK CATEGORY = II
IMPORTANCE FACTOR = 1.0
SS = 1.048
S1 = 0.387
SITE CLASS = D (DEFAULT)
SDS = 0.755
GROUND MOTION USED:
- CODE DESIGN RESPONSE SPECTRUM
SEISMIC DESIGN LOAD (NON-STRUCTURAL COMPONENT)
FP (HORIZONTAL FORCE)
FV (VERTICAL FORCE)
EV = 0.2 SDS WP
WP = COMPONENT WEIGHT
h = AVERAGE ROOF HEIGHT, FEET z = HEIGHT OF COMPONENT ATTACHMENT POINT, FEET
SDS = DESIGN SPECTRAL ACCELERATION
IP = COMPONENT IMPORTANCE FACTOR, PER ASCE 7-16 SECTION 13.1.3 = 1.0
ap = AMPLIFICATION FACTOR, PER ASCE 7-16 TABLE 13.5-1 AND TABLE 13.6.-1
RP = COMPONENT RESPONSE FACTOR, PER ASCE 7-16 TABLE 13.5-1 AND TABLE 13.6.-1
3. WIND ANALYSIS PER CHAPTER 16 OF THE CODE
RISK CATEGORY = II
BASIC WIND SPEED = 92 mph
WIND EXPOSURE = C
DESIGN CRITERIA
Fp = 0.4ap SDS
Rp
Ip{ } { 1 + 2 Wp z h } Fp MIN = 0.3 SDS IP WP
Fp MAX = 1.6 SDS IP WP
1. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO STARTING CONSTRUCTION. THE ARCHITECT
SHALL BE NOTIFIED OF ANY DISCREPANCIES OR INCONSISTENCIES.
2. ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION OF ALL DRAWINGS AND SPECIFICATIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES THAT OCCUR SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO START OF CONSTRUCTION SO THAT A CLARIFICATION CAN BE
ISSUED. ANY WORK PERFORMED IN CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY CODE
REQUIREMENTS SHALL BE CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE AND AT NO
EXPENSE TO THE OWNER OR ARCHITECT.
3. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
4. SEE ARCHITECTURAL DRAWINGS FOR THE FOLLOWING:
SIZE AND LOCATION OF ALL DOOR AND WINDOW OPENINGS, EXCEPT AS NOTED.
SIZE AND LOCATION OF ALL INTERIOR AND EXTERIOR NON-BEARING PARTITIONS.
SIZE AND LOCATION OF ALL CONCRETE CURBS, EQUIPMENT PADS, PITS, FLOOR DRAINS, SLOPES, DEPRESSED AREAS, CHANGE IN LEVEL, CHAMFERS, GROOVES, INSERTS, ETC.
SIZE AND LOCATION OF ALL FLOOR AND ROOF OPENINGS EXCEPT AS SHOWN.
FLOOR AND ROOF FINISHES.
DIMENSIONS NOT SHOWN ON STRUCTURAL DRAWINGS.
5. SEE MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR THE FOLLOWING:
PIPE RUNS, SLEEVES, HANGERS, TRENCHES, WALL AND SLAB OPENINGS, ETC., EXCEPT AS SHOWN OR
NOTED. ELECTRICAL CONDUIT RUNS, BOXES, OUTLETS IN WALLS AND SLABS.
CONCRETE INSERTS FOR ELECTRICAL, MECHANICAL OR PLUMBING FIXTURES.
SIZE AND LOCATION OF MACHINE OR EQUIPMENT BASES, ANCHOR BOLTS FOR MOTOR MOUNTS.
6. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE.
THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL
INCLUDE, BUT NOT BE LIMITED TO, BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION
EQUIPMENT, ETC. OBSERVATION VISITS TO THE SITE BY THE STRUCTURAL ENGINEER SHALL NOT INCLUDE
INSPECTION OF THE ABOVE ITEMS.
7. OPENINGS, POCKETS, ETC., LARGER THAN 6" SHALL NOT BE PLACED IN CONCRETE SLABS, DECKS, WALLS, UNLESS SPECIALLY DETAILED ON THE STRUCTURAL DRAWINGS. NOTIFY THE STRUCTURAL ENGINEER WHEN
DRAWINGS BY OTHERS SHOW OPENINGS, POCKETS, ETC., LARGER THAN 6" NOT SHOWN ON THE
STRUCTURAL DRAWINGS, BUT WHICH ARE LOCATED IN STRUCTURAL MEMBERS. FOR ANY FURTHER
RESTRICTIONS ON OPENINGS IN STRUCTURAL ELEMENTS, SEE APPLICABLE SECTIONS BELOW.
8. ASTM SPECIFICATIONS ON THE DRAWINGS SHALL BE OF THE LATEST REVISION.
9. CONTRACTOR SHALL INVESTIGATE SITE DURING CLEARING AND EARTHWORK OPERATIONS FOR FILLED EXCAVATIONS OR BURIED STRUCTURES, SUCH AS CESSPOOLS, CISTERNS, FOUNDATIONS, ETC. IF ANY
SUCH STRUCTURES ARE FOUND, STRUCTURAL ENGINEER SHALL BE NOTIFIED IMMEDIATELY.
10. CONSTRUCTION MATERIAL SHALL BE SPREAD OUT IF PLACED ON FRAMED ROOF OR FLOOR. LOAD SHALL
NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT. PROVIDE ADEQUATE SHORING AND/OR
BRACING WHERE STRUCTURE HAS NOT ATTAINED DESIGN STRENGTH.
11. THE LOCATION OF EXISTING UNDERGROUND UTILITIES SHOWN ON THE DRAWINGS, IF ANY, ARE APPROXIMATE. THE CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL EXISTING UNDERGROUND UTILITIES AND COORDINATING WITH THE REQUIREMENTS OF THIS PROJECT. THE CONTRACTOR SHALL EXERCISE
EXTREME CAUTION IN EXCAVATING AND TRENCHING ON THE SITE. THE CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE ARCHITECT IF ANY CONDITIONS ARE DISCOVERED THAT REQUIRES FURTHER
COORDINATION.
THE CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE THAT OCCURS DUE TO NOT FULLY LOCATING
EXISTING UTILITIES.
12. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO EXISTING CONDITIONS IS BASED ON AVAILABLE KNOWLEDGE OF EXISTING STRUCTURE. CONTRACTOR SHALL VERIFY IN FIELD ALL EXISTING CONDITIONS RELATIVE TO THE SCOPE OF THIS PROJECT. WHERE ACTUAL CONDITIONS ARE NOT IN ACCORDANCE WITH THE DRAWINGS PROVIDED, THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY.
CONTRACTOR SHALL ALIGN FOR SUFFICIENT BUDGET AND SCHEDULE CONTINGENCY TO ADDRESS
EXISTING HIDDEN CONDITIONS.
13. ALL DEMOLITION SHALL BE PERFORMED IN SUCH A WAY AS NOT TO DAMAGE THE EXISTING STRUCTURAL ELEMENTS THAT ARE TO REMAIN IN THE FINISHED STRUCTURE. ANY PORTIONS OF STRUCTURE TO REMAIN THAT ARE DAMAGED DURING DEMOLITION SHALL BE REPLACED AT NO ADDITIONAL COST. EXISTING STRUCTURAL ELEMENTS SHALL BE PROTECTED TO THE FULLEST EXTENT POSSIBLE, IN ORDER TO MITIGATE DAMAGE. CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF ALL EXISTING STRUCTURAL
ELEMENTS THAT ARE NECESSARY FOR THE COMPLETION OF ALL NEW WORK.
GENERAL
1. FOUNDATION DESIGN BASED ON 2022 CBC CODE MINIMUM VALUES.
2. FOOTINGS ARE DESIGNED BASED ON THE FOLLOWING INFORMATION:
W = FOOTING WIDTH
D = FOOTING DEPTH BELOW ADJACENT GRADE
ALLOWABLE BEARING *
WALL FTGS = 1500 PSF (MAX)
ISOLATED FTGS = 1500 PSF (MAX)
PASSIVE EARTH PRESSURE **
PASSIVE EARTH PRESSURE = 100 PCF (EFP) , 1500 PSF (MAX)
FOOTINGS SHALL BEAR ON FIRM NATURAL SOILS. MINIMUM DEPTH OF FOOTINGS BELOW LOWEST
ADJACENT FINAL GRADE SHALL BE 1'-0". MINIMUM WIDTH OF FOOTING SHALL BE 1'-0".
* VALUES MAY BE INCREASED BY 1/3 FOR WIND OR SEISMIC LOAD CASES
** PASSIVE PRESSURE AND FRICTION MAY BE COMBINED WITHOUT A REDUCTION
3. CONTRACTOR TO PROVIDE FOR DE-WATERING OF EXCAVATIONS FROM EITHER SURFACE WATER, GROUND WATER OR SEEPAGE, IF REQUIRED.
4. CONTRACTOR SHALL PROVIDE FOR DESIGN AND INSTALLATION OF ALL CRIBBING, SHEATHING AND SHORING REQUIRED AND SHALL BE SOLELY RESPONSIBLE FOR ALL EXCAVATION PROCEDURES INCLUDING LAGGING, SHORING AND PROTECTION OF ADJACENT PROPERTY, STRUCTURES, STREETS AND UTILITIES IN
ACCORDANCE WITH ALL NATIONAL, STATE AND LOCAL SAFETY ORDINANCES.
5. EXCAVATION FOR FOOTINGS SHALL BE APPROVED BY THE INSPECTOR OR SOILS ENGINEER PRIOR TO
PLACING THE CONCRETE AND REINFORCING. CONTRACTOR TO NOTIFY THE INSPECTOR WHEN
INSPECTION OF EXCAVATION IS READY. INSPECTOR TO SUBMIT LETTER OF COMPLIANCE.
6. ALL EXCAVATIONS SHALL BE PROPERLY BACKFILLED. DO NOT PLACE BACKFILL BEHIND RETAINING WALLS BEFORE CONCRETE OR GROUT HAS ATTAINED FULL DESIGN STRENGTH. CONTRACTOR SHALL BRACE OR PROTECT ALL BUILDING AND PIT WALLS BELOW GRADE FROM LATERAL LOADS UNTIL ATTACHING FLOORS ARE COMPLETELY IN PLACE AND HAVE ATTAINED FULL STRENGTH. CONTRACTOR SHALL PROVIDE FOR
DESIGN, PERMITS, AND INSTALLATION OF SUCH BRACING.
7. FOUNDATIONS SHALL BE PLACED AND ESTIMATED ACCORDING TO DEPTHS SHOWN ON DRAWINGS.
SHOULD SOIL ENCOUNTERED AT THESE DEPTHS NOT BE APPROVED BY THE INSPECTOR OR SOILS
ENGINEER, FOUNDATION ELEVATIONS WILL BE ALTERED BY CHANGE ORDER.
8. FOOTING BACKFILL AND UTILITY TRENCH BACKFILL WITHIN BUILDING AREA SHALL BE MECHANICALLY COMPACTED IN LAYERS IN ACCORDANCE WITH THE SOILS REPORT AND APPROVED BY THE SOILS ENGINEER. FLOODING WILL NOT BE PERMITTED. ALL FILLS USED TO SUPPORT FOUNDATIONS SHALL BE INSPECTED BY THE SOILS ENGINEER REPRESENTATIVE PER CODE SECTION 1705.6 AND TABLE 1705.6.
9. ALL ABANDONED FOOTINGS, UTILITIES, ETC., SHALL BE REMOVED UNLESS NOTED OTHERWISE. NEW
FOOTINGS MUST EXTEND INTO UNDISTURBED SOILS.
10. SLABS ON GRADE SHALL BE SUPPORTED ON NATURAL GRADE OR COMPACTED FILL AS PER THE
RECOMMENDATIONS OF THE SOILS REPORT.
FOUNDATION
1. REINFORCING BARS SHALL CONFORM TO THE REQUIREMENTS OF CHAPTER 19 & 21 OF THE CODE, ASTM
A615, GRADE 60 UNO.
2. BARS SHALL BE CLEAN OF RUST, GREASE, OR OTHER MATERIALS LIKELY TO IMPAIR BOND. ALL
REINFORCING BAR BENDS SHALL BE MADE COLD.
3. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185. WWF SHALL BE SUPPORTED ON APPROVED
CHAIRS.
4. REINFORCING BAR SPLICES SHALL BE MADE AS INDICATED ON THE DRAWINGS. LAP ALL HORIZONTAL BARS AT CORNERS AND INTERSECTIONS. STAGGER ALL SPLICES UNLESS NOTED OTHERWISE ON PLANS.
5. ALL BARS SHALL BE MARKED SO THEIR IDENTIFICATION CAN BE MADE WHEN THE FINAL IN-PLACE
INSPECTION IS MADE.
6. WHERE WELDING OF REINFORCING IS APPROVED BY THE STRUCTURAL ENGINEER, IT SHALL BE DONE BY
AWS CERTIFIED WELDERS USING FILLER MATERIAL TO MATCH MATERIAL STRENGTHS. WELDING
PROCEDURES SHALL CONFORM TO THE REQUIREMENTS OF STRUCTURAL WELDING CODE- REINFORCING STEEL", AWS-D1.4, LATEST REVISION. REINFORCING BARS TO BE WELDED SHALL CONFORM TO THE
REQUIREMENTS OF ASTM A706.
7. BARS IN SLABS SHALL BE SECURELY SUPPORTED ON WELL-CURED CONCRETE BLOCKS OR APPROVED METAL
CHAIRS, PRIOR TO PLACING CONCRETE.
8. REINFORCING STEEL SHALL BE DETAILED IN ACCORDANCE WITH THE "A.C.I. MANUAL OF STANDARD
PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES", LATEST EDITION.
9. COMPLETE AND DETAILED REINFORCING PLACEMENT DRAWINGS SHALL BE PREPARED AND SUBMITTED TO THE ARCHITECT FOR APPROVAL BY THE STRUCTURAL ENGINEER PRIOR TO FABRICATION IN ACCORDANCE WITH THE SPECIFICATIONS AND APPLICABLE CODES. THESE DRAWINGS SHALL BE AVAILABLE ON THE JOB
SITE PRIOR TO PLACING OF CONCRETE.
10. MILL TEST REPORTS FOR GRADE 60 BARS SHALL BE SUBMITTED PRIOR TO PLACEMENT OF CONCRETE.
11. PROVIDE INSPECTION OF CONCRETE PER SPECIAL INSPECTION NOTES SECTION. INSPECTION SHALL BE SCHEDULED SO THAT PLACEMENT OF REINFORCING STEEL, CONDUIT, SLEEVES, AND EMBEDDED ITEMS
MAY BE CORRECTED PRIOR TO PLACEMENT OF OVERLYING GRIDS OR REINFORCING STEEL.
12. ALL GRADE 60 REINFORCING STEEL SHALL BE CLEARLY MARKED TO DIFFERENTIATE THEM FROM GRADE 40
REINFORCING STEEL IF CONCURRENTLY ON SITE.
13. CONCRETE PROTECTION FOR REINFORCEMENT:
No. 6 THROUGH No. 18 BARS
1-1/2
NOT EXPOSED
TO WEATHER
OR IN CONTACT
WITH GROUND
SLABS, JOISTS
AND WALLS
BEAMS,
COLUMNS,
PEDESTALS, AND
TENSION TIES
PRIMARY
REINFORCEMENT,
STIRRUPS, TIES,
SPIRALS, AND
HOOPS
ALL No. 5 BAR, W31 OR
D31 WIRE, AND
SMALLER
1-1/2 No. 14 AND No. 18
BARS
3/4 No. 11 BAR AND
SMALLER
CONCRETE
EXPOSURE
MEMBER REINFORCEMENT
CAST-IN-PLACE NONPRESTRESSED CONCRETE MEMBERS
MIN COVER,
IN.
CAST AGAINST AND
PERMANENTLY IN
CONTACT WITH
GROUND
ALL ALL 3
EXPOSED TO
WEATHER OR IN
CONTACT WITH
GROUND
1-1/2
REINFORCING STEEL (FOR CONCRETE AND MASONRY)
1. ALL CONCRETE CONSTRUCTION SHALL CONFORM WITH CHAPTER 19 OF THE CODE AND WITH THE
PROVISIONS OF ACI 318, LATEST EDITION.
2. REINFORCED CONCRETE IS DESIGNED BY THE "ULTIMATE STRENGTH DESIGN METHOD".
3. CONCRETE MIXES SHALL BE DESIGNED BY THE APPROVED TESTING LABORATORY AND APPROVED BY THE STRUCTURAL ENGINEER. THE COMPRESSIVE STRENGTH OF THE CONCRETE SHALL BE PROPORTIONED
BASED ON CHAPTER 19 OF THE CODE.
4. SCHEDULE OF STRUCTURAL CONCRETE 28-DAY STRENGTH AND TYPES:
5. AGGREGATE FOR HARDROCK CONCRETE SHALL CONFORM TO ALL REQUIREMENTS AND TESTS OF ASTM C33 AND PROJECT SPECIFICATIONS. EXCEPTIONS MAY BE USED ONLY WITH PERMISSION OF THE
STRUCTURAL ENGINEER.
6. AGGREGATE FOR LIGHT WEIGHT (115 PCF) CONCRETE SHALL BE EXPANDED SHALE CONFORMING TO ASTM C330 AND PROJECT SPECIFICATIONS. EXCEPTIONS MAY BE USED ONLY WITH PERMISSION OF THE
STRUCTURAL ENGINEER.
7. CONCRETE MIXING OPERATION, ETC. SHALL CONFORM TO ASTM C94.
8. PLACEMENT OF CONCRETE SHALL CONFORM TO THE CODE AND PROJECT SPECIFICATIONS. CLEAN AND ROUGHEN TO 1/4" AMPLITUDE ALL CONCRETE SURFACES AGAINST WHICH NEW CONCRETE IS TO BE
PLACED.
9. ALL REINFORCING BARS, ANCHOR BOLTS AND OTHER CONCRETE INSERTS SHALL BE WELL SECURED IN
POSITION PRIOR TO PLACING CONCRETE.
10. PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL OPENINGS IN CONCRETE BEFORE PLACING. DO NOT CUT ANY REINFORCING WHICH MAY CONFLICT. CORING IN CONCRETE IS NOT PERMITTED. NOTIFY THE STRUCTURAL ENGINEER IN ADVANCE OF CONDITIONS NOT SHOWN ON THE DRAWINGS. SEE THESE DRAWINGS FOR ADDITIONAL RESTRICTIONS ON THE PLACEMENT OF OPENINGS IN SLABS AND WALLS.
11. PIPES LARGER THAN 1-1/2" DIAMETER SHALL NOT BE EMBEDDED IN STRUCTURAL CONCRETE EXCEPT WHERE SPECIFICALLY APPROVED BY STRUCTURAL ENGINEER. PIPES SHALL NOT DISPLACE OR INTERRUPT REINFORCING BARS, SPACE EMBEDDED PIPES AND SLEEVES AT A MINIMUM OF 3 DIAMETERS ON CENTER.
12. CONCRETE FILL OVER METAL DECK SHALL BE SCREEDED TO A CONSTANT THICKNESS AS SPECIFIED IN THE
DECKING SCHEDULE.
13. ALL CONCRETE MIX DESIGNS SHALL BE SIGNED AND SEALED BY A CIVIL ENGINEER REGISTERED IN THE
STATE IN WHICH THE PROJECT IS LOCATED.
EXPOSURE
CLASSES
LOCATION
F S W C
MIN
STRENGTH
f'c (PSI)
MAX WATER/
CEMENT
RATIO
CEMENT
TYPE
(ASTM C150)
DENSITY
ALL CONCRETE
FOOTINGS
F0 S0 W0 C1 4000 PSI 0.50 II/V 150 PCF
CONCRETE
1. STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED BY AN APPROVED AND LICENSED FABRICATOR IN ACCORDANCE WITH THE AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS (LATEST
EDITION), AND WITH CHAPTERS 17 AND 22 OF THE CODE.
2. ALL STRUCTURAL STEEL SHALL CONFORM TO THE ASTM DESIGNATION AS INDICATED BELOW (UNO):
WF & WT SHAPES A992
ANGLES, CHANNELS, PLATES, BARS,
CONNECTION PLATES, AND MISC A36
PIPE SECTIONS A53, GRADE B
HSS SECTIONS A500, GRADE C
BOLTS F3125, GRADE A325
TWIST-OFF TYPE BOLTS F3125, GRADE F1852
BOLTS IN CONCRETE F1554 GR 36 OR
F1554 GR 55 S1 (WELDABLE)
3. THE STRUCTURAL STEEL FABRICATOR SHALL FURNISH SHOP DRAWINGS OF ALL STEEL TO THE ARCHITECT FOR ARCHITECT'S AND STRUCTURAL ENGINEER'S REVIEW AND APPROVAL BEFORE FABRICATION.
4. BOLT HOLES USED IN STEEL SHALL BE 1/16" LARGER IN DIAMETER THAN NOMINAL SIZE OF BOLT USED, EXCEPT AS NOTED.
5. ALL STRUCTURAL STEEL SURFACES THAT ARE ENCASED IN CONCRETE, MASONRY OR SPRAY ON
FIREPROOFING, OR ARE ENCASED BY BUILDING FINISH, SHALL BE LEFT UNPAINTED.
6. ALL WELDING IS TO BE DONE BY CERTIFIED WELDERS USING FILLER METALS TO MATCH MATERIAL STRENGTH (UNO). ALL WELDS SHALL BE IN CONFORMITY WITH THE PROJECT SPECIFICATIONS AND THE CODE FOR WELDING IN BUILDING CONSTRUCTION (AWS D1.1 LATEST REVISION) OF THE AMERICAN WELDING SOCIETY. SEE SPECIAL INSPECTIONS SECTION FOR WELDING INSPECTION REQUIREMENTS. USE
OF E70T-4 WIRE IS NOT PERMITTED.
7. WHERE FABRICATION OF STRUCTURAL, LOAD-BEARING OR LATERAL LOAD-RESISTING MEMBERS OR ASSEMBLIES IS BEING CONDUCTED ON THE PREMISES OF FABRICATOR'S SHOP, SPECIAL INSPECTION OF THE FABRICATED ITEMS SHALL BE PERFORMED DURING FABRICATION, EXCEPT WHERE THE FABRICATOR HAS BEEN APPROVED TO PERFORM WORK WITHOUT SPECIAL INSPECTIONS IN ACCORDANCE WITH SECTION
1704.2.5.1 OF THE CODE.
8. WELD LENGTHS CALLED FOR ON PLANS ARE THE NET EFFECTIVE LENGTH REQUIRED. WHERE FILLET WELD SYMBOL IS GIVEN WITHOUT INDICATION OF SIZE, USE MINIMUM SIZE WELDS AS SPECIFIED IN AISC 360-16 SECTION J2.2b.
9. ALL EXPOSED STRUCTURAL STEEL AND MISCELLANEOUS METAL SHALL BE HOT DIP GALVANIZED AFTER
FABRICATION UNO.
10. THE SPECIAL INSPECTIONS FOR STEEL ELEMENTS OF BUILDINGS AND STRUCTURES SHALL BE AS REQUIRED
BY SECTION 1705.2 OF THE CODE AND CONSTRUCTION DOCUMENTS.
EXCEPTIONS:
SPECIAL INSPECTIONS OF THE STEEL FABRICATION PROCESS SHALL NOT BE REQUIRED WHERE THE FABRICATION PROCESS FOR THE ENTIRE BUILDING OR STRUCTURE DOES NOT INCLUDE ANY WELDING, THERMAL CUTTING OR HEATING OPERATION OF ANY KIND. IN SUCH CASES, THE FABRICATOR SHALL BE REQUIRED TO SUBMIT A DETAILED PROCEDURE FOR MATERIAL CONTROL THAT DEMONSTRATES THE FABRICATOR'S ABILITY TO MAINTAIN SUITABLE RECORDS AND PROCEDURES SUCH THAT, AT ANY TIME DURING THE FABRICATION PROCESS, THE MATERIAL SPECIFICATION AND GRADE FOR THE MAIN STRESS- CARRYING ELEMENTS ARE CAPABLE OF BEING DETERMINED. MILL TEST REPORTS SHALL BE IDENTIFIABLE TO
THE MAIN STRESS-CARRYING ELEMENTS WHERE REQUIRED BY THE APPROVED CONSTRUCTION
DOCUMENTS.
11. ALL SPLICES IN HEAVY SHAPES SHALL COMPLY WITH AISC 360-16 SECTION J1.5.
12. WELD ACCESS HOLES SHALL COMPLY WITH AISC 360-16 SECTION J1.6.
13. ALL WELD MATERIAL SHALL COMPLY WITH AISC 360-16 SECTION J2.6.
14. THE THERMAL CUTTING OF ALL MEMBERS SHALL COMPLY WITH AISC 360-16 SECTION M2.2.
15. NON-DESTRUCTIVE ULTRASONIC TESTING SHALL BE REQUIRED ON 100% OF CJP GROOVE WELDS IN
MATERIAL 5/16" THICK AND GREATER.
16. COORDINATE STRUCTURAL STEEL REQUIRED FOR ELEVATOR INSTALLATION AND OPERATION IN ADDITION
TO WHAT IS SHOWN ON DRAWINGS WITH ELEVATOR MANUFACTURER.
STRUCTURAL STEEL
1. ANCHOR DIAMETER REFERS TO THE ANCHOR SIZE AND NOT THE DIAMETER OF THE DRILLED HOLE.
2. ALL ANCHORS SHOULD MEET THE MINIMUM EMBEDMENT, EDGE DISTANCE, SPACING AND SLAB
THICKNESS CRITERIA ESTABLISHED BY THE RELEVANT ICC-ES EVALUATION REPORT.
3. ACCEPTABLE MANUFACTURERS FOR EXPANSION ANCHORS ARE AS FOLLOWS:
CONCRETE:
HILTI KWIK BOLT TZ2 (KB-TZ2) (ICC ESR-4266)
SIMPSON STRONG-BOLT 2 (ICC ESR-3037)
4. DO NOT LOCATE EXPANSION ANCHORS CLOSER TO EDGE OF CONCRETE/MASONRY OR TO
CONTROL/CONSTRUCTION JOINTS THAN THE MINIMUM EDGE DISTANCE SPECIFIED IN THE ICC REPORT, UNO.
5. WHEN INSTALLING DRILLED-IN ANCHORS IN EXISTING NON-PRESTRESSED REINFORCED CONCRETE, USE
CARE AND CAUTION TO AVOID CUTTING OR DAMAGING THE EXISTING REINFORCING BARS.
6. IT IS NOT ACCEPTABLE TO SUBSTITUTE ANY CAST-IN-PLACE BOLTS/RODS/ ANCHORS FOR EXPANSION
ANCHORS WITHOUT PRIOR APPROVAL FROM THE STRUCTURAL ENGINEER OF RECORD.
7. USE HOT DIP GALVANIZED OR STAINLESS STEEL ANCHORS WHEN EXPANSION ANCHORS ARE EXPOSED
TO WEATHER OR IN A DAMP ENVIRONMENT.
8. SPECIAL INSPECTION SHALL BE PROVIDED PER THE ICC-ER REPORT NOTED ABOVE.
EXPANSION ANCHORS
1501 Quail St., Ste 150, Newport Beach, CA 92660
O: 949.418.6722 www.srssinc.com
Drawn by:
Job No.:
PA / PM:
Description of RevisionsBy Date#
Sheet Title/Number
Scale:
Date:
REVISIONS
As Noted
V1
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 00−0−0000−C
255 East Rincon St., Suite 301
Corona, CA 92879
P 951.340.1977 | F 951.340.1090 www.gossengineering.com
24-S-4152-C
A u to d e s k D o c s:
G
O S S E n g in e e ri n g /2
G o s s D
O T D
S
L O
D is tr ic t O ff ic e R v t2
.r v t
/1
/2
:4 :0
P
M
C a lt ra n s D is tr ic t O ff ic e E V S E I n s ta lla ti o n
H ig u e ra
S tr e e t, S a n L u is
O b is p o C
A
06/04/2025
RR
AKZ
25065
GENERAL NOTES
S0.01
SHEET INDEX
S0.01 GENERAL NOTES
S0.02 SPECIAL INSPECTION TABLES,
ABBREVIATIONS AND SYMBOLS
S1.01 PLANS
S1.02 PLANS AND DETAILS
1 06/04/2024 RR 95% CD Submittal
2 08/15/2025 AKZ 100% CD Submittal
N
I
R
No. 4306 Exp. 12/31/2
G
T
R E
TAT
S
S
E OFILACFO
UCTURA
R
L
R
S T E
RE
D P L
OFESSIONA
N E R
AI
EN
G
I
O B
E R
T
JA
ME FE
C
A R
O T
R
S
T A5
CSFM APPLICATION NUMBER: 25-S-3159-C
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3159
DOT D5 - Electric Vehicle Supply Equipment
PROJECT NUMBER: 000000000013813; 12/19/25
http://www.srssinc.com
DETAIL NUMBER
SHEET NUMBER
CALLOUT REFERENCE
SECTION REFERENCE
PLAN NORTH
ELEVATION REFERENCE
CLOUD AND REVISIONS
GRID SYSTEM
DETAIL REFERENCE
NORTH SYMBOL
S-1.1
SHEET
A
SHEET
SHEET
CONCRETE CONSTRUCTION (CBC TABLE 1705.3)
SPECIAL INSPECTIONS AND TESTS
X
X
X
X
X
X
X
X
X
X
X
ITEMS REQUIRING SPECIAL INSPECTION
1. INSPECT REINFORCEMENT, INCLUDING PRESTRESSING TENDONS, AND
VERIFY PLACEMENT.
3. INSPECT ANCHORS CAST IN CONCRETE.
5. VERIFY USE OF REQUIRED DESIGN MIX.
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH
TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE
TEMPERATURE OF THE CONCRETE.
7. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER
APPLICATION TECHNIQUES.
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND
TECHNIQUES.
9. INSPECT PRESTRESSED CONCRETE FOR:
10. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS.
11. VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF
TENDONS IN POST-TENSIONED CONCRETE AND PRIOR TO REMOVAL OF
SHORES AND FORMS FROM BEAMS AND STRUCTURAL SLABS.
12. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE
CONCRETE MEMBER BEING FORMED.
a. APPLICATION OF PRESTRESSING FORCES; AND
b. GROUTING OF BONDED PRESTRESSING TENDONS.
PERIODICCONTINUOUS
THE OWNER SHALL PROVIDE FOR A SPECIAL INSPECTOR(S) WHO WILL PROVIDE SPECIAL INSPECTIONS OF THE CONSTRUCTION AS PRESCRIBED BY THE CODE AND THE CONSTRUCTION DOCUMENTS. IN NO CASE SHALL THE REQUIREMENTS IN THE CONSTRUCTION DOCUMENTS PROVIDE FOR ANY LESS THAN THE MINIMUM REQUIREMENTS OF THE CODE OR ANY OTHER GOVERNING AUTHORITY. ANY SUCH DISCREPANCY SHALL BE
BROUGHT TO THE IMMEDIATE ATTENTION OF THE ENGINEER.
THE SPECIAL INSPECTOR SHALL BE QUALIFIED BY THE CITY OF SAN LUIS OBISPO TO PROVIDE INSPECTIONS OF THE SPECIFIC CONSTRUCTION OR OPERATION REQUIRED. PROOF OF SUCH QUALIFICATION SHALL BE
PROVIDED TO THE ENGINEER PRIOR TO THE START OF INSPECTIONS.
THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE BUILDING OFFICIAL, THE ENGINEER, ARCHITECT AND THE CONTRACTOR IN A TIMELY MANNER. ALL DISCREPANCIES BETWEEN THE INSPECTORS WORK AND THE CONTRACT DOCUMENTS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION, THEN, IF NOT CORRECTED, TO THE ENGINEER, ARCHITECT AND THE BUILDING OFFICIAL. THE SPECIAL INSPECTOR SHALL KEEP RECORDS SUCH THAT ALL CONCERNED PARTIES CAN IDENTIFY THE OUTSTANDING WORK THAT NEEDS CORRECTION AND SUCH THAT CORRECTED WORK IS
RECORDED IN A TIMELY MANNER.
THE SPECIAL INSPECTOR SHALL SUBMIT A FINAL SIGNED REPORT STATING THAT THE WORK REQUIRING SPECIAL INSPECTION WAS, TO THE BEST OF THE INSPECTOR'S KNOWLEDGE, IN GENERAL CONFORMANCE WITH THE APPROVED PLANS AND SPECIFICATIONS AND THE APPLICABLE WORKMANSHIP PROVISIONS OF THE CODE. IF NON-CONFORMING WORK REMAINS, THEN THIS WORK SHALL BE ITEMIZED AND NOTED IN THE REPORT.
THE CONTRACTOR SHALL PROVIDE ACCESS TO THE WORK REQUIRING SPECIAL INSPECTION. THE CONTRACTOR SHALL PROVIDE A DESIGNATED AREA, ON SITE, FOR THE SPECIAL INSPECTOR TO RECEIVE CORRESPONDENCE AND AN AREA TO LEAVE CORRESPONDENCE FOR THE BUILDING OFFICIAL AND THE CONTRACTOR. THE CONTRACTOR SHALL DESIGNATE A QUALITY CONTROL INDIVIDUAL THAT SHALL ACT AS THE MAIN POINT OF CONTACT FOR THE INSPECTOR, ENGINEER AND ARCHITECT REGARDING INSPECTIONS
ISSUES.
A PRE-INSPECTION MEETING SHALL BE HELD AND ORGANIZED BY THE…