Plans.pdf
PDF 15 MB Posted
- Solicitation number
- 0000037384
- Issued by
- Tuolumne County, Tuolumne City CDP, California
About this file
This is a design and construction drawing package for the Moccasin Creek Hatchery Water Reuse Project, prepared by Stantec Consulting Services for the California Department of Fish and Wildlife in Moccasin, Tuolumne County. The project comprises a comprehensive water recirculation system including a reuse pump station with drum filters, seven submersible sewage pumps (6 required, 1 standby) with discharge capacities of 750 gallons per minute each, butterfly and check valves, piping systems, and associated infrastructure. The 27-sheet design package includes civil, structural, mechanical, and electrical drawings detailing the reuse pump station sump plan and sections, site piping plans, equipment schedules, process flow diagrams with design criteria specifying 30 cubic feet per second normal operations and 3 cubic feet per second reuse system capacity, and mechanical equipment specifications for basin-mounted drum filters with 3,000 gallons per minute capacity each. The drawings have undergone multiple revisions with the most recent pump station redesign dated April 11, 2025, and received Office of the State Fire Marshal approval for fire and panic systems on July 25, 2025.
The electrical scope includes 480-volt three-phase power distribution, a 200-kilowatt standby diesel generator, automatic transfer switch, two panelboards, control systems with programmable logic controllers and human-machine interface, alarm system with visual and audible signals, flow meters, level transmitters, and comprehensive conduit and raceways for site infrastructure. Construction work requires California A or B License certification and proof of fleet vehicle compliance with California Air Resources Board regulations. The project was re-advertised following failed bid openings on August 14, 2024, and October 9, 2024, with revised scope and updated drawings. Sealed bids are due January 6, 2026, at 2:00 P.M. at the Department of General Services Office of Business and Acquisition Services in West Sacramento, California, with contract number 25-287152 and project number 11551.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid_Package_Documents.pdf | ||
| Project_Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MOCCASIN CREEK
HATCHERY- WATER REUSE
2025.04.11
PROJECT NUMBER: 224202869
COUNT SHEET# SHEET TILE
GENERAL
1 G-1 LOCATION AND VICINITY MAPS, DRAWING INDEX
2 G-2 SYMBOLS AND ABBREVIATIONS
3 G-3 PROCESS FLOW DIAGRAM AND DESIGN CRITERIA
4 G-4 EQUIPMENT SCHEDULES
5 G-5 PIPE SCHEDULES
CIVIL
6 GC-1 CIVIL STANDARD DETAILS - 1
7 GC-2 CIVIL STANDARD DETAILS - 2
8 C-1 CIVIL SITE PLAN
9 C-2 SITE PIPING PLAN
STRUCTURAL
10 GS-1 STRUCTURAL NOTES - 1
11 GS-2 STRUCTURAL NOTES - 2
12 GS-3 STRUCTURAL STANDARD DETAILS - 1
13 GS-4 STRUCTURAL STANDARD DETAILS - 2
14 GS-5 STRUCTURAL STANDARD DETAILS - 3
15 S-1 REUSE PUMP STATION SUMP PLAN AND SECTION
16 S-2 REUSE PUMP STATION SECTIONS
MECHANICAL
17 GM-1 MECHANICAL STANDARD DETAILS
18 M-1 REUSE PUMP STATION PLAN AND ISOMETRIC
19 M-2 REUSE PUMP STATION SECTIONS
ELECTRICAL
20 GE-1 ELECTRICAL SYMBOLS - 1
21 GE-2 ELECTRICAL SYMBOLS - 2
22 GE-3 STANDARD ELECTRICAL DETAILS
23 GE-4 SINGLE-LINE DIAGRAM - 1
24 GE-5 CONDUIT DEVELOPMENT
25 GE-6 PANELBOARD SCHEDULES - REUSE STRUCTURE
26 E-1 ELECTRICAL PLAN DETAILS
27 E-2 ALARM SYSTEM DETAILS
PROJECT
LOCATION
LOCATION MAP
MOCCASIN
CREEK
HATCHERY
VICINITY MAP
TOTAL OF 27 SHEETS
ORIGINAL SHEET - ARCH D
A
B
C
D
V4 c u se rs d iy e ru sa lim e ts d c a c c d o c s\ st a n te c c o n su lt in g
_m o c c a si n
_h a tc h e ry p ro je c t fil e s\
.0 d e si g n
.7 d ra w in g s\ g e n e ra l\ m fh
-g
.0
.0
:3 :1
P
M
Permit/Seal
Drawing No.
ofRevision:
File Name: N/A
Title
Sheet:
YYYY.MM.DDDsgn. Chkd.Dwn.
2025.04.11
C lie n t/
P ro je c t
Project No.:
Scale:
M O
C C
A
SI
N C
R E E K
F
IS
H H
A
TC
H E R
Y
C A
LI
FO
R N
IA
D
E P
A R
TM
E N
T O
F
FI
SH
A
N D
W
IL
D
LI
FE
M O
C C
A
SI
N , C
A
LI
FO
R
N
IA
22402869
Is su e d
/R e vi si o n
B y
A p d
Y
Y
Y .M
M .D
D
Th e
C o n tr a c to r sh a ll v e rif y a n d b e r e sp o n si b le f o r a ll d im e n si o n s.
D O
N O
T sc a le t h e d ra w in g a n y e rr o rs o r o m is si o n s sh a ll b e r e p o rt e d t o St a n te c w ith o u t d e la y.
T h e
C o p y rig h ts t o a ll d e si g n s a n d d ra w in g s a re th e p ro p e rt y o f St a n te c
R e p ro d u c tio n o r u se f o r a n y p u rp o se o th e r th a n t h a t a u th o riz e d b y S ta n te c is f o rb id d e n
C o p yr ig h t R e se rv e d
St a n te c C o n su lt in g S e rv ic e s In c
T re a t B o u le v a rd S u it e
W a ln u t C re e k, C
-7
Te l:
(9
-1 w w w .s ta n te c
.c o m
4 51 2 3
D E
SI
G N
S U
B M
IT
TA
L
ST
N
D
E W
.1 .1
A
T
IT
LE
B
LO
C K
U P
D
TE
.0
.3
LOCATION AND VICINITY
MAPS, DRAWING INDEX
None
ARF DEW
G-1
D G
S R
E V
IE
W
C O
M M
E
TS
.0
.0
D E W
B
P U
M P
S
TA
TI
O
N R
E D
E
SI
G
.0
.1
D E W jr c^l fco(Qz — '------------- -"VO fofo 3*1
CO S
74231
EXP. 6/3&/2bZ5 /-S'\ Ua r>i
|^^^5/2V/Z®23
06/06/2025
CWS
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/25/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-2557
ISSUE DATE: OCTOBER 14, 2025
http://www.stantec.com
ORIGINAL SHEET - ARCH D
A
B
C
D
V4 c u se rs d iy e ru sa lim e ts d c a c c d o c s\ st a n te c c o n su lt in g
_m o c c a si n
_h a tc h e ry p ro je c t fil e s\
.0 d e si g n
.7 d ra w in g s\ g e n e ra l\ m fh
-g
.0
.0
:3
:3
P
M
Permit/Seal
Drawing No.
ofRevision:
File Name: N/A
Title
Sheet:
YYYY.MM.DDDsgn. Chkd.Dwn.
2025.04.11
C lie n t/
P ro je c t
Project No.:
Scale:
M O
C C
A
SI
N C
R E E K
F
IS
H H
A
TC
H E R
Y
C A
LI
FO
R N
IA
D
E P
A R
TM
E N
T O
F
FI
SH
A
N D
W
IL
D
LI
FE
M O
C C
A
SI
N , C
A
LI
FO
R
N
IA
22402869
A
O
SF
M S
TA
M
P B
LO
C
K U
P D
Is su e d
/R e vi si
Y
Y .M
M .D
D
Th e
C o n tr a c to r sh a ll v e rif y a n d b e r e sp o n si b le f o r a ll d im e n si o n s.
D O
N O
T sc a le t h e d ra w in g a n y e rr o rs o r o m is si o n s sh a ll b e r e p o rt e d t o St a n te c w ith o u t d e la y.
T h e
C o p y rig h ts t o a ll d e si g n s a n d d ra w in g s a re th e p ro p e rt y o f St a n te c
R e p ro d u c tio n o r u se f o r a n y p u rp o se o th e r th a n t h a t a u th o riz e d b y S ta n te c is f o rb id d e n
C o p yr ig h t R e se rv e d
St a n te c C o n su lt in g S e rv ic e s In c
T re a t B o u le v a rd S u it e
W a ln u t C re e k, -7
Te l:
(9
-1 w w w .s ta n te c
.c o m
4 51 2 3
.1
.1
D E
SI
G N
S U
B M
IT
.1
.1
EQUIPMENT DESIGNATOR
EQUIPMENT NUMBER
SLIDE GATE
(CAST IRON, ALUMINUM OR STAINLESS STEEL)
GATES
A
L
REFERENCE SYMBOLS
SEE EQUIPMENT SCHEDULE/SPECIFICATIONS
GENERAL SYMBOLOGY
MATERIAL SYMBOLOGY
VALVES
HAND / MANUAL OPERATOR
(ALSO SHOWN AS NO OPERATOR)
CHECK VALVE
BUTTERFLY VALVE
BALL VALVE
AIR VACUUM, AIR RELEASE, OR
AIR VACUUM AND AIR RELEASE ASSEMBLY
2-16
1-8
BFV-RS-05
4-12
C
0 /
MISCELLANEOUS
EQUIPMENT IDENTIFICATION
ROOM NUMBER
DOOR NUMBER
WINDOW NUMBER
ACCESSORY NUMBER
WALL TYPE NUMBER
SHEET KEY NOTES
COORDINATE POINT/
WORK POINT
ROUND OR DIAMETER
AT
ANGLE
CENTERLINE
NEW CONSTRUCTION
EXISTING (SCREENED)
FUTURE (PHANTOM)
EXISTING TO BE REMOVED OR DEMOLISHED
GRAVEL/DRAINROCK/AGGREGATE BASE, NEW
FINISHED GRADE
LUMBER/FRAMING - NOMINAL
CONCRETE (PLAN AND SECTION)
GROUT OR SAND (PLAN AND SECTION)
STEEL/METAL/FRP (SMALL SCALE SECTION)
GRATING (PLAN)
GRATING OR SOLID FRP GRATING (SECTION)
RAILING (PLAN)
REFERENCE SYMBOLS
SHEET ON WHICH
DETAIL IS SHOWN
DETAIL NUMBER
SHEET ON WHICH
DETAIL IS CALLED-OUT
SHEET ON WHICH
ELEVATION IS SHOWN
OR
DETAIL
C-302 C-302
DETAIL NUMBER
STANDARD DETAILS ARE LOCATED ON DISCIPLINE GENERAL
SHEETS, IN NUMERICAL ORDER
SECTION LETTER
SHEET ON WHICH
SECTION IS SHOWN
SHEET ON WHICH
SECTION IS CUT
SECTION
X-###
DETAIL#
X-###
SHEET ON WHICH
ELEVATION IS CALLED-OUT
ELEVATION
1A-3
ELEVATION NUMBER
X-###X-###
XX
A
D
C
B
1A-31A-3
INTERIOR ELEVATION IDENTIFICATION
STANDARD DETAIL IDENTIFICATION
DETAIL IDENTIFICATION
SECTION IDENTIFICATION
SCALE: #/#" = 1'-0"
SCALE: #/#" = 1'-0"
SCALE: #/#" = 1'-0"
SUB-TITLE
ELEVATION
1A-3
6A
SCALE: #/#" = 1'-0"
SCALE: #/#" = 1'-0"
NORTH ELEVATIONX
EXTERIOR ELEVATION IDENTIFICATION
N, S, E or W
NORTH ARROW
AREA DESIGNATOR
(IF APPLICABLE)
GRAVEL SURFACING, EXISTING
ASPHALT SURFACING, EXISTING
ASPHALT SURFACING, NEW
BM-# BENCHMARK
ABBREVIATIONS
AC ASPHALT
ALUM ALUMINUM
AVAR AIR VACUUM/AIR RELEASE
BFV BUTTERFLY VALVE
BLDG BUILDING
BM BENCHMARK
BMP BEST MANAGEMENT PRACTICE
BOL BOLLARD
CA/CAL CALIFORNIA
CBC CALIFORNIA BUILDING CODE
CDFW CA DEPT OF FISH AND WILDLIFE
CFS CUBIC FEET PER SECOND
CJ CONSTRUCTION JOINT
CL CENTERLINE
CLR CLEAR
CLSM CONTROLLED LOW STRENGTH MATERIAL
CMP CORRUGATED METAL PIPE
COL COLUMN
CONC CONCRETE
COTG CLEANOUT TO GRADE
DF DRUM FILTER
DI DUCTILE IRON
DIA DIAMETER
DO DISSOLVED OXYGEN
DP DIFFERENTIAL PRESSURE
DR DRAIN
(E) EXISTING
EA EACH
ECC ECCENTRIC
EF EACH FACE
EL ELEVATION
EMBED EMBEDMENT
EQN EQUATION
ES EXCLUSION SCREEN
ESC EROSION AND SEDIMENT CONTROL
EW EACH WAY
EXIST EXISTING
F FLANGE
FDN FOUNDATION
FF FINISH FLOOR
FH FIRE HYDRANT
FIG FIGURE
FM FLOW METER
FPT FEMALE PIPE THREAD
FRP FIBER-REINFORCED PLASTIC
FT FEET
FTG FOOTING
G GATE
GA GAUGE
GALV GALVANIZED
GB GRADE BREAK
GPM GALLON PER MINUTE
GS GAS SERVICE
H HEIGHT/HOIST
HB HOSE BIB
HDPE HIGH DENSITY POLYETHYLENE
HORZ/HORIZ HORIZONTAL
HP HORSEPOWER
HSS HOLLOW STRUCTURAL SECTION
HWY HIGHWAY
IBC INTERNATIONAL BUILDING CODE
IE INVERT ELEVATION
LB POUND
LG LONG
LHO LOW HEAD OXYGENATOR
LIT LEVEL INDICATING TRANSMITTER
LOX LIQUID OXYGEN
MBD MICRO BUBBLE DIFFUSER
MFR MANUFACTURER
MIN MINIMUM
MJ MECHANICAL JOINT
MP MEDIUM PRESSURE
MPH MILES PER HOUR
N/A NOT APPLICABLE
(N) NEW
NIC NOT IN CONTRACT
NO NUMBER
NTU NEPHELOMETRIC TURBIDITY UNIT
OC ON CENTER
OD OUTSIDE DIAMETER
OF OVERFLOW
P PUMP
PC POINT OF CURVATURE
PERF PERFORATED
PL PLATE
PP POWER POLE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT OF TANGENCY
PTFE POLYTETRAFLUOROETHYLENE
PVC POLYVINYL CHLORIDE PIPE
PVMT PAVEMENT
R REUSE
RB ROUND BAR
REINF REINFORCEMENT
REQ REQUIRED
RPS REUSE PUMP STATION
S SLOPE
SCH SCHEDULE
SFPUC SAN FRANCISCO PUBLIC UTILITIES COMMISSION
SHT SHEET
SIM SIMILAR
SQ SQUARE
SS STAINLESS STEEL
STA STATION
STD STANDARD
STRUC STRUCTURAL
STRUC STRUCTURE
SW SURFACE WATER
T&B TOP AND BOTTOM
TC TOP OF CURB
TDH TOTAL DYNAMIC HEAD
TF TAIL FLUME
THK THICK
TOC TOP OF CONCRETE
TW TOP OF WALL
TYP TYPICAL
UD UNDERDRAIN
UNO UNLESS NOTED OTHERWISE
µ MICRON
UTIL UTILITY
UV ULTRAVIOLET
UW UTILITY WATER
VLT VAULT
W WIDTH
W/ WITH
WM WATER METER
WS WATERSTOP
ENGINEER OF RECORD
Stantec Consulting Services, Inc.
2999 Oak Road, Suite 800 Walnut Creek CA 94597-7966
APPLICABLE CODES
Ryan Beck, State Project Director Professional Service Branch, Real Estate Services Division 707 Third Street, West Sacramento, CA 95605
·TITLE 19, CCR, PUBLIC SAFETY, SFM REGULATIONS
·2022 CALIFORNIA ADMINISTRATIVE CODE TITLE 24, PT 1
·2022 CALIFORNIA BUILDING CODE (CBC) TITLE 24, PT 2
·2022 CALIFORNIA ELECTRICAL CODE (CEC) TITLE 24, PT3
·2022 CALIFORNIA MECHANICAL CODE (CMC) TITLE 24, PT4
·2022 CALIFORNIA PLUMBING CODE (CPC) TITLE 24, PT 5
·2022 CALIFORNIA ENERGY CODE CCR TITLE 24, PT 6
·2022 CALIFORNIA FIRE CODE (CFC) CCR, PT 9
·2022 CALIFORNIA GREEN BUILDING STANDARDS TITLE 24, PT 11
·2022 CALIFORNIA REFERENCE STANDARDS TITLE 24, PT 12
·NFPA 13
·NFPA 14
·NFPA 17A
·NFPA 20
·NFPA 24
·NFPA 72
·NFPA 2001
CONTACTS LIST
DEPARTMENT OF GENERAL SERVICES
SYMBOLS AND
ABBREVIATIONS
None
ARF DEW CWC
G-2
D G
S R
E V
IE
W
C O
M M
E
.0
.0
O
SF
M C
O M
M E N
T U
P D
.0
.2
D E W
AUTOMATIC SPRINKLER SYSTEMS W/ CA AMENDMENTS
STANDPIPE SYSTEMS W/ CA AMENDMENTS
WET CHEMICAL SYSTEMS
STATIONARY PUMPS
PRIVATE FIRE MAINS W/ CA AMENDMENTS
NATIONAL FIRE ALARM CODE W/ CA AMENDMENTS
CLEAN AGENT FIRE EXTINGUISHING SYSTEMS W/ CA
AMENDMENTS
2022 EDITION
2022 EDITION
2022 EDITION
2022 EDITION
2022 EDITION
2022 EDITION
2022 EDITION
REFERENCE CODE SECTION FOR NFPA STANDARDS ARE IN 2022 CBC CHAPTER
35 OR 2022 CFC CHAPTER 80. SEE CHAPTER 35 FOR THE STATE OF CALIFORNIA
AMENDMENTS TO NFPA STANDARDS.
D E W
B
P U
M P
S
TA
TI
O
N R
E D
E
SI
.0
.1
D E W jr c^l fco(Qz — '------------- -"VO fofo 3*1
CO S
74231
EXP. 6/3&/2bZ5 /-S'\ Ua r>i
|^^^5/2V/Z®23
06/06/2025
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/25/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-2557
ORIGINAL SHEET - ARCH D
B
C
D
V4 c u se rs d iy e ru sa lim e ts d c a c c d o c s\ st a n te c c o n su lt in g
_m o c c a si n
_h a tc h e ry p ro je c t fil e s\
.0 d e si g n
.7 d ra w in g s\ g e n e ra l\ m fh
-g
.0
.0
:3
:4
P M
Permit/Seal
Drawing No.
ofRevision:
File Name: N/A
Title
Sheet:
YYYY.MM.DDDsgn. Chkd.Dwn.
2025.04.11
C lie n t/
P ro je c t
Project No.:
Scale:
M O
C C
A
SI
N C
R E E K
F
IS
H H
A
TC
H E R
Y
C A
LI
FO
R N
IA
D
E P
A R
TM
E N
T O
F
FI
SH
A
N D
W
IL
D
LI
FE
M O
C C
A
SI
N , C
A
LI
FO
R
N
IA
22402869
A
O
SF
M S
TA
M
P B
LO
C
K U
P D e d
/R e vi si
Y
Y .M
M .D
D
Th e
C o n tr a c to r sh a ll v e rif y a n d b e r e sp o n si b le f o r a ll d im e n si o n s.
D O
N O
T sc a le t h e d ra w in g a n y e rr o rs o r o m is si o n s sh a ll b e r e p o rt e d t o St a n te c w ith o u t d e la y.
T h e
C o p y rig h ts t o a ll d e si g n s a n d d ra w in g s a re th e p ro p e rt y o f St a n te c
R e p ro d u c tio n o r u se f o r a n y p u rp o se o th e r th a n t h a t a u th o riz e d b y S ta n te c is f o rb id d e n
C o p yr ig h t R e se rv e d
St a n te c C o n su lt in g S e rv ic e s In c
T re a t B o u le v a rd S u it e
W a ln u t C re e k, -7
Te l:
(9
-1 w w w .s ta n te c
.c o m
4 51 2 3
.1
.1
D E
SI
G N
S U
B M
IT
.1
.1
.0
.3
B
A D
D
IT
IV
E B
ID
IT
E M
N O
S
POND SERIES A
POND SERIES B
POND SERIES C
POND SERIES D
POND SERIES E
POND SERIES F
POND SERIES G
POND SERIES H
SETTLING POND
TO MOCCASIN
CREEK
TO MOCCASIN
CREEK
PIPELINE FROM
MOCCASIN
RESERVOIR
DISTRIBUTION
BOX
HATCHERY
BUILDING
BROOD HOLDING
ROUND TANKS
EMERGENCY
PUMP
STATION
MOCCASIN
CREEK
H E
A D
F L U
M E
T A
IL
F
L U
M E
DRUM
FILTERS
REUSE
PUMPS
REUSE PUMP STATION
LEGEND:
EXISTING GAS CONTROL
COLUMN (TYP 4)
DESIGN CRITERIA
DESCRIPTION VALUE UNITS COMMENTS
WATER SUPPLY
NORMAL OPERATIONS 30 CFS
REUSE SYSTEM OPERATION 3 CFS
FRESH WATER MAKEUP FROM
RESERVOIR
10 CFS REUSE
REUSE TREATMENT DRUM FILTERS
SYSTEM CAPACITY 13 CFS
NO OF UNITS 2 EA BASIN MOUNTED
DRUM FILTER CAPACITY, EA 3,000 GPM
FILTER OPENING, MAX 40 µM
MAXIMUM TOTAL SUSPENDED SOLIDS 25 MG/L
REUSE PUMPS NOTE: USE EXISTING PUMPS
CAPACITY, TOTAL 4,500 GPM
CAPACITY, EA 750 GPM
TOTAL NO. OF PUMPS REQUIRED 6
TOTAL NO. OF PUMPS INSTALLED 7
TOTAL DISCHARGE HEAD, MAX 40 FT
WATER
VAULT
OVERFLOW
M
FLOW
METER
(EXISTING
NIC)
SUMP
PROCESS WATER, NEW
DRAIN, EXISTING
DRAIN, NEW
PROCESS WATER, EXISTING
WASTE EFFLUENT / SOLIDS
SUMP
FLOW DIRECTION
PROCESS FLOW DIAGRAM
AND DESIGN CRITERIA
NONE
DEW DEW CWC
G-3
D G
S R
E V
IE
W
C O
M M
E
.0
.0
D E W
C
P U
M P
S
TA
TI
O
N R
E D
E
SI
.0
.1
D E W
VALVE
VAULT
jr c^l fco(Qz — '------------- -"VO fofo 3*1
CO S
74231
EXP. 6/3&/2bZ5 /-S'\ Ua r>i
|^^^5/2V/Z®23
06/06/2025
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/25/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-2557
B
C
D
V4 c u se rs d iy e ru sa lim e ts d c a c c d o c s\ st a n te c c o n su lt in g
_m o c c a si n
_h a tc h e ry p ro je c t fil e s\
.0 d e si g n
.7 d ra w in g s\ g e n e ra l\ m fh
-g
.0
.0
:3
:5
P M
Permit/Seal
Drawing No.
ofRevision:
File Name: N/A
Title
Sheet:
YYYY.MM.DDDsgn. Chkd.Dwn.
2025.04.11
C lie n t/
P ro je c t
Project No.:
Scale:
M O
C C
A
SI
N C
R E E K
F
IS
H H
A
TC
H E R
Y
C A
LI
FO
R N
IA
D
E P
A R
TM
E N
T O
F
FI
SH
A
N D
W
IL
D
LI
FE
M O
C C
A
SI
N , C
A
LI
FO
R
N
IA
22402869
A
O
SF
M S
TA
M
P B
LO
C
K U
P D e d
/R e vi si
Y
Y .M
M .D
D
Th e
C o n tr a c to r sh a ll v e rif y a n d b e r e sp o n si b le f o r a ll d im e n si o n s.
D O
N O
T sc a le t h e d ra w in g a n y e rr o rs o r o m is si o n s sh a ll b e r e p o rt e d t o St a n te c w ith o u t d e la y.
T h e
C o p y rig h ts t o a ll d e si g n s a n d d ra w in g s a re th e p ro p e rt y o f St a n te c
R e p ro d u c tio n o r u se f o r a n y p u rp o se o th e r th a n t h a t a u th o riz e d b y S ta n te c is f o rb id d e n
C o p yr ig h t R e se rv e d
St a n te c C o n su lt in g S e rv ic e s In c
T re a t B o u le v a rd S u it e
W a ln u t C re e k, -7
Te l:
(9
-1 w w w .s ta n te c
.c o m
4 51 2 3
.1
.1
D E
SI
G N
S U
B M
IT
.1
.1
.0
.3
B
A D
D
IT
IV
E B
ID
IT
E M
N O
GATE SCHEDULE
EQUIPMENT
NUMBER DESCRIPTION LOCATION MATERIAL TYPE SIZE (W x H) OPERATOR SEATING HEAD
UNSEATING
HEAD REMARKS
G-1 REUSE PUMP STATION SUPPLY GATE TAIL FLUME ALUMINUM SLIDE 24" X 24" MANUAL, HAND CRANK 5' 5' NON-SELF CONTAINED, MOUNT FLUSH TO FLOOR
PUMP SCHEDULE
PUMP
NO LOCATION SERVICE TYPE FLOW (GPM) @ TDH (FT) HP VOLTAGE/PHASE REMARKS
P-1 REUSE PUMP STATION RACEWAY EFFLUENT SUBMERSIBLE SEWAGE PUMPS 750 @ 40 15 480/3 INSTALL EXISTING PUMP, CONTRACTOR TO PROCURE AND INSTALL QUICK DISCONNECT AND GUIDE RAIL SYSTEM
P-2 REUSE PUMP STATION RACEWAY EFFLUENT SUBMERSIBLE SEWAGE PUMPS 750 @ 40 15 480/3 INSTALL EXISTING PUMP, CONTRACTOR TO PROCURE AND INSTALL QUICK DISCONNECT AND GUIDE RAIL SYSTEM
P-3 REUSE PUMP STATION RACEWAY EFFLUENT SUBMERSIBLE SEWAGE PUMPS 750 @ 40 15 480/3 INSTALL EXISTING PUMP, CONTRACTOR TO PROCURE AND INSTALL QUICK DISCONNECT AND GUIDE RAIL SYSTEM
P-4 REUSE PUMP STATION RACEWAY EFFLUENT SUBMERSIBLE SEWAGE PUMPS 750 @ 40 15 480/3 INSTALL EXISTING PUMP, CONTRACTOR TO PROCURE AND INSTALL QUICK DISCONNECT AND GUIDE RAIL SYSTEM
P-5 REUSE PUMP STATION RACEWAY EFFLUENT SUBMERSIBLE SEWAGE PUMPS 750 @ 40 15 480/3 INSTALL EXISTING PUMP, CONTRACTOR TO PROCURE AND INSTALL QUICK DISCONNECT AND GUIDE RAIL SYSTEM
P-6 REUSE PUMP STATION RACEWAY EFFLUENT SUBMERSIBLE SEWAGE PUMPS 750 @ 40 15 480/3 INSTALL EXISTING PUMP, CONTRACTOR TO PROCURE AND INSTALL QUICK DISCONNECT AND GUIDE RAIL SYSTEM
P-7 REUSE PUMP STATION RACEWAY EFFLUENT SUBMERSIBLE SEWAGE PUMPS 750 @ 40 15 480/3 INSTALL EXISTING PUMP, CONTRACTOR TO PROCURE AND INSTALL QUICK DISCONNECT AND GUIDE RAIL SYSTEM
VALVE SCHEDULE (6" AND LARGER)
EQUIPMENT
NUMBER DESCRIPTION TYPE SIZE CONNECTION OPERATOR REMARKS
BFV-RPS-1 REUSE PUMP 1 DISCHARGE ISOLATION BUTTERFLY 6-INCH FL X FL MANUAL, LEVER-ARM INSTALL EXISTING VALVE
BFV-RPS-2 REUSE PUMP 2 DISCHARGE ISOLATION BUTTERFLY 6-INCH FL X FL MANUAL, LEVER-ARM INSTALL EXISTING VALVE
BFV-RPS-3 REUSE PUMP 3 DISCHARGE ISOLATION BUTTERFLY 6-INCH FL X FL MANUAL, LEVER-ARM INSTALL EXISTING VALVE
BFV-RPS-4 REUSE PUMP 4 DISCHARGE ISOLATION BUTTERFLY 6-INCH FL X FL MANUAL, LEVER-ARM INSTALL EXISTING VALVE
BFV-RPS-5 REUSE PUMP 5 DISCHARGE ISOLATION BUTTERFLY 6-INCH FL X FL MANUAL, LEVER-ARM INSTALL EXISTING VALVE
BFV-RPS-6 REUSE PUMP 6 DISCHARGE ISOLATION BUTTERFLY 6-INCH FL X FL MANUAL, LEVER-ARM INSTALL EXISTING VALVE
BFV-RPS-7 REUSE PUMP 7 DISCHARGE ISOLATION BUTTERFLY 6-INCH FL X FL MANUAL, LEVER-ARM INSTALL EXISTING VALVE
CV-RPS-1 REUSE PUMP 1 DISCHARGE CHECK CHECK 6-INCH FL X FL N/A INSTALL EXISTING VALVE
CV-RPS-2 REUSE PUMP 2 DISCHARGE CHECK CHECK 6-INCH FL X FL N/A INSTALL EXISTING VALVE
CV-RPS-3 REUSE PUMP 3 DISCHARGE CHECK CHECK 6-INCH FL X FL N/A INSTALL EXISTING VALVE
CV-RPS-4 REUSE PUMP 4 DISCHARGE CHECK CHECK 6-INCH FL X FL N/A INSTALL EXISTING VALVE
CV-RPS-5 REUSE PUMP 5 DISCHARGE CHECK CHECK 6-INCH FL X FL N/A INSTALL EXISTING VALVE
CV-RPS-6 REUSE PUMP 6 DISCHARGE CHECK CHECK 6-INCH FL X FL N/A INSTALL EXISTING VALVE
CV-RPS-7 REUSE PUMP 7 DISCHARGE CHECK CHECK 6-INCH FL X FL N/A INSTALL EXISTING VALVE
EQUIPMENT SCHEDULES
DEW DEW CWS
G-4
D G
S R
E V
IE
W
C O
M M
E
.0
.0
D E W
C
P U
M P
S
TA
TI
O
N R
E D
E
SI
.0
.1
D E W
MECHANICAL EQUIPMENT SCHEDULE
EQUIPMENT
NUMBER LOCATION SERVICE TYPE CAPACITY REMARKS
DF-RPS-1 REUSE PUMP STATION RACEWAY EFFLUENT MICROSCREEN DRUM FILTER 3,000 GPM BASIN MOUNTED WITH BACKWASH CLEANING SYSTEM AND OVERFLOW WEIR
DF-RPS-2 REUSE PUMP STATION RACEWAY EFFLUENT MICROSCREEN DRUM FILTER 3,000 GPM BASIN MOUNTED WITH BACKWASH CLEANING SYSTEM AND OVERFLOW WEIR jr c^l fco(Qz — '------------- -"VO fofo 3*1
CO S
74231
EXP. 6/3&/2bZ5 /-S'\ Ua r>i
|^^^5/2V/Z®23
06/06/2025
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/25/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-2557
B
C
D
V4 c u se rs d iy e ru sa lim e ts d c a c c d o c s\ st a n te c c o n su lt in g
_m o c c a si n
_h a tc h e ry p ro je c t fil e s\
.0 d e si g n
.7 d ra w in g s\ g e n e ra l\ m fh
-g
.0
.0
:3
:2
P M
Permit/Seal
Drawing No.
ofRevision:
File Name: N/A
Title
Sheet:
YYYY.MM.DDDsgn. Chkd.Dwn.
2025.04.11
C lie n t/
P ro je c t
Project No.:
Scale:
M O
C C
A
SI
N C
R E E K
F
IS
H H
A
TC
H E R
Y
C A
LI
FO
R N
IA
D
E P
A R
TM
E N
T O
F
FI
SH
A
N D
W
IL
D
LI
FE
M O
C C
A
SI
N , C
A
LI
FO
R
N
IA
22402869
A
O
SF
M S
TA
M
P B
LO
C
K U
P D e d
/R e vi si
Y
Y .M
M .D
D
Th e
C o n tr a c to r sh a ll v e rif y a n d b e r e sp o n si b le f o r a ll d im e n si o n s.
D O
N O
T sc a le t h e d ra w in g a n y e rr o rs o r o m is si o n s sh a ll b e r e p o rt e d t o St a n te c w ith o u t d e la y.
T h e
C o p y rig h ts t o a ll d e si g n s a n d d ra w in g s a re th e p ro p e rt y o f St a n te c
R e p ro d u c tio n o r u se f o r a n y p u rp o se o th e r th a n t h a t a u th o riz e d b y S ta n te c is f o rb id d e n
C o p yr ig h t R e se rv e d
St a n te c C o n su lt in g S e rv ic e s In c
T re a t B o u le v a rd S u it e
W a ln u t C re e k, -7
Te l:
(9
-1 w w w .s ta n te c
.c o m
4 51 2 3
.1
.1
D E
SI
G N
S U
B M
IT
.1
.1
G H K I
CS01
DI01
PE05
PV01
PV05
SS01
PV03
GROUP
NO
POLYETHYLENE, PRESSURE PIPE, AWWA C906.
STAINLESS STEEL, TYPE 316L, ASTM A312, SCH 40S.
STEEL, ASTM A53, SCH 40, THREADED OR WELDED, BLACK
OR GALVANIZED
POLYVINYL CHLORIDE (PVC), GRAVITY SEWER PIPE, ASTM D3034, BELL AND SPIGOT.
POLYVINYL CHLORIDE (PVC), ASTM D1785, SCH 80, TYPE I.
POLYETHYLENE THERMAL BUTT-FUSED JOINTS, FLANGED JOINTS AT VALVES AND TRANSITIONS.
PVC, ANSI/ASTM D3034, BELL AND/OR SPIGOT.
AS INDICATED ON DRAWINGS.
VALVES, 6" AND SMALLER FITTINGS
PIPING MATERIAL SCHEDULE
PIPE
BRONZE, THREADED, GATE: CRANE 428 UB OR STOCKHAM B-105. GLOBE: STOCKHAM B-37. CHECK:
CRANE 37 OR STOCKHAM B-319Y. IRON PLUG VALVE: NORDSTROM FIG 142 OR 143. ECC PLUG:
DEZURIK PEC, CAST IRON OR MILLIKEN 603E. BALL: JAMESBURY FIG 351 OR WATTS #B-6080.
LUBRICATED PLUG VALVE (FOR CONDENSATE ONLY): NORDSTROM FIG 114 OR 115.
DUCTILE IRON, ANSI A21.51, (AWWA C151), ENDS BELL AND SPIGOT, MECHANICAL
JOINTS OR 125 PSI FLANGED. (TYPICAL SERVICE - WATER LINES).
POLYVINYL CHLORIDE (PVC), PRESSURE PIPE , AWWA C900, WITH BELL
AND SPIGOT JOINTS.
SHEET KEYNOTES
2 1/2" AND SMALLER, MALLEABLE IRON, ASME B16.3, THREADED, BANDED, 150 PSI OR STEEL, ASME B16.9, BUTT-WELDED. 3" AND LARGER, CAST IRON, ASME B16.1, 125 PSI FLANGED OR MECHANICAL
COUPLING.
DUCTILE IRON AWWA C110, BELL AND SPIGOT JOINTS (RESTRAINED OR NON-RESTRAINED),
MECHANICAL COUPLINGS, ASME B16.1 FLANGES, OR MECHANICAL JOINTS.
STAINLESS STEEL, TYPE 316L, THREADED, WELDED SLIP-ON FLANGE ASME B16.3, OR SOCKET WELDED
FITTINGS SCH 40S. (THREADED JOINTS NOT ALLOWED FOR OXYGEN SERVICE)
PVC, SCH 80, TYPE I, SOCKET SOLVENT WELD JOINTS, ASTM D2467. SOLVENT SHALL BE COMPATIBLE
WITH FLUID SERVICE.
GATE: AWWA C500, O-RING SEALS, MECHANICAL JOINT ENDS, CLOW F-5065. BUTTERFLY: AWWA. ECC
PLUG DEZURIK PEC, CAST IRON OR MILLIKEN 603E. BALL: PRATT OR APCO-WILLAMETTE.
PVC, BALL, DIAPHRAGM, BUTTERFLY, OR LIFT CHECK: NIBCO/CHEMTROL, MCCANNA-MARPAC,
OR GEORGE FISCHER SLOANE.
GATE: AWWA C500, O-RING SEALS, MECHANICAL JOINT ENDS, CLOW F-5065. BUTTERFLY: AWWA.
ECCENTRIC PLUG DEZURIK PEC, CAST IRON OR MILLIKEN 603E. BALL: PRATT OR APCO-WILLAMETTE.
SAME AS GROUP DI01.
STAINLESS STEEL, TYPE 316, BALL, FLANGED: CONTROMATICS SERIES 2801 OR JAMESBURY SERIES
7150. CHECK: LADISH 5275 OR CRANE FIG 377 OR AS SHOWN ON DRAWINGS.
G. PROPRIETARY NAMES HAVE BEEN QUOTED FOR IDENTIFICATION PURPOSES
ONLY. SUBSTITUTIONS WILL BE PERMITTED SUBJECT TO PROVISIONS OF
THE SPECIFICATIONS.
H. FOR VALVES 8" AND LARGER, SEE VALVE SCHEDULE. FOR SPECIAL VALVES,
SEE SPECIFICATIONS. FOR PIPE LINING AND COATING, SEE
SPECIFICATIONS.
I. PIPE MATERIALS SHALL BE PER THE REFERENCE STANDARDS AS MODIFIED
BY THE CONTRACT SPECIFICATIONS.
DUCTILE IRON FITTINGS, 125 PSI, FOR PVC PIPE, AWWA C110 CEMENT MORTAR LINED, AWWA
C104.
F L U
ID
A B B R E V
IA
T
IO
N
DR DRAIN
D
FUNCTION
THIS LIST INCLUDES SOME LINES
NOT USED IN THIS PROJECT F E
A4" DIA AND SMALLER 6" DIA AND LARGER 4" DIA AND SMALLER 6" DIA AND LARGER
EXPOSED PIPING BURIED PIPING
PIPING MATERIALS (SEE GENERAL NOTES AT THE RIGHT AND PIPE MATERIAL SHEET)
CU01, PV01 PV01, PV03, PV05 DI01 CU01, PV01, PV05CU01, PV01, PV05
TEST
MEDIUM
MINIMUM
TEST
PRESSURE
(PSI)
LEAKAGE
ALLOWANCE
FIELD TEST REQUIREMENTS
WATER (a)
B C
#" XXX (##)
MATERIAL GROUP NUMBER
FLUID ABBREVIATIONPIPE DIAMETER
GENERAL SHEET NOTES
TYPICAL PIPE DESIGNATION:
1. ALTHOUGH SEVERAL PIPE MATERIAL GROUPS MAY BE LISTED ON THIS SHEET
FOR A GIVEN FLUID SERVICE, CONTRACTOR SHALL PROVIDE ONLY THE PIPE
MATERIAL GROUP SHOWN ON THE DRAWINGS AND SPECIFIED FOR THAT FLUID
SERVICE.
2. CHANGE IN PIPING MATERIAL GROUP NUMBER IS INDICATED THUS:
LEAKAGE ALLOWANCE IS AS FOLLOWS:
(a) PIPES SO DESIGNATED SHALL SHOW ZERO LEAKAGE.
(b) PIPES SO DESIGNATED SHALL SHOW ZERO LEAKAGE FOR UNBURIED PIPE AND
NOT MORE THAN 0.02 GALLON PER HOUR PER INCH DIAMETER PER 100 FEET OF
BURIED PIPE.
A.
B. FOR FIELD TEST PROCEDURES AND ADDITIONAL TEST REQUIREMENTS, SEE
PIPING SECTION OF SPECIFICATIONS.
C. NO SUBSTITUTIONS UNLESS ACCEPTED BY THE ENGINEER PER THE
SPECIFICATIONS.
D. PIPING GROUP NUMBER SHOWN THUS * SHALL BE INSULATED. SEE PIPING
SECTION OF SPECIFICATIONS FOR INSULATING MATERIALS.
SURFACE WATER
R -- --DI01, PV01, PV03, PE05 WATER (a)DI01, PV03
SW 125 WATER
UD 50 WATER -
REUSE WATER 125
DI01, PV01 CS08, DI01, PV01,
PV03
DI01, PV01,
CU01(a) PV03, (b)
DI01, PV01,
CU01
PV06 PV06
DI01, PV01,
CU01
PV06 PV06 UNDERDRAIN
OF OVERFLOW CS08, DI01, PV03PV01, CS01 DI01, PV03, PV05 -- 25 (a)WATER
E. FOR PIPE LINING AND COATING, SEE SPECIFICATIONS.
F. EXPOSED PIPING SHALL BE PAINTED IN ACCORDANCE WITH SPECIFICATIONS.
COLORS TO BE SELECTED BY ENGINEER.
CU01 COPPER, ASTM B88, TYPE K, SOFT TEMPERED WHERE BURIED, HARD TEMPERED WHERE EXPOSED. BRONZE, SILVER SOLDER JOINT, GLOBE: CRANE #1310 OR STOCKHAM B-14T. CHECK: CRANE #1342 OR 36, OR
STOCKHAM B-309Y OR B-345. GATE: CRANE #426 OR STOCKHAM B-104 OR B-105.
WROUGHT COPPER OR CAST BRONZE, ASME B16.22, SILVER SOLDER JOINT, 150 PSI, OR COMPRESSION FITTINGS.
PV06
PVC, BELL AND/OR SPIGOT.POLYVINYL CHLORIDE, CORRUGATED, GRAVITY SEWER PIPE, ASTM F794 AND F949, BELL AND SPIGOT, PERFORATED (FOR STRUCTURE UNDERDRAIN), NON-PERFORATED (FOR STRUCTURE UNDERDRAIN
COLLECTOR).
UW 125 WATER
SS01,CS01,DI01,CU01(a)
PV03,(b)
CS01, DI01, SS01,
PV01, CU01
CS01, DI01,
SS01, PV01
CS01, DI01, SS01,
PV01, CU01
CS01, DI01,
PV03
UTILITY WATER
(NON-POTABLE WATER)
PIPE SCHEDULES
DEW DEW
G-5
D G
S R
E V
IE
W
C O
M M
E
.0
.0
D E W
B
P U
M P
S
TA
TI
O
N R
E D
E
SI
.0
.1
D E W jr c^l fco(Qz — '------------- -"VO fofo 3*1
CO S
74231
EXP. 6/3&/2bZ5 /-S'\ Ua r>i
|^^^5/2V/Z®23
06/06/2025
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/25/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-2557
B
C
D
V4 c u se rs d iy e ru sa lim e ts d c a c c d o c s\ st a n te c c o n su lt in g
_m o c c a si n
_h a tc h e ry p ro je c t fil e s\
.0 d e si g n
.7 d ra w in g s\ c iv il\ g c
.0
.0
:2
:2
P M
Permit/Seal
Drawing No.
ofRevision:
File Name: N/A
Title
Sheet:
YYYY.MM.DDDsgn. Chkd.Dwn.
2025.04.11
C lie n t/
P ro je c t
Project No.:
Scale:
M O
C C
A
SI
N C
R E E K
F
IS
H H
A
TC
H E R
Y
C A
LI
FO
R N
IA
D
E P
A R
TM
E N
T O
F
FI
SH
A
N D
W
IL
D
LI
FE
M O
C C
A
SI
N , C
A
LI
FO
R
N
IA
22402869
A
O
SF
M S
TA
M
P B
LO
C
K U
P D e d
/R e vi si
Y
Y .M
M .D
D
Th e
C o n tr a c to r sh a ll v e rif y a n d b e r e sp o n si b le f o r a ll d im e n si o n s.
D O
N O
T sc a le t h e d ra w in g a n y e rr o rs o r o m is si o n s sh a ll b e r e p o rt e d t o St a n te c w ith o u t d e la y.
T h e
C o p y rig h ts t o a ll d e si g n s a n d d ra w in g s a re th e p ro p e rt y o f St a n te c
R e p ro d u c tio n o r u se f o r a n y p u rp o se o th e r th a n t h a t a u th o riz e d b y S ta n te c is f o rb id d e n
C o p yr ig h t R e se rv e d
St a n te c C o n su lt in g S e rv ic e s In c
T re a t B o u le v a rd S u it e
W a ln u t C re e k, -7
Te l:
(9
-1 w w w .s ta n te c
.c o m
4 51 2 3
.1
.1
D E
SI
G N
S U
B M
IT
.1
.1
C
C D
FW
C
O M
M E N
TS
IN
C O
R P
O R
A
.0
.3
B
D
SA
C O
M M
E N
TS
IN
C O
R P
O R
A
TE
D ST
.0
.0
REV 110112
SEE PLANS2'-0"
GRAVEL ROAD SECTION
C-132
SEE PLANS
4" AGGREGATE BASE COURSE
SYMMETRICAL CL
OVEREXCAVATE EXISTING GRADE
12" MINIMUM. PROOF ROLL AND
BACKFILL WITH STRUCTURAL FILL
REV 110112
8'-0"
FABRIC OVERLAY
MIRIFI 140N
OR EQUAL
AC PAVEMENT -
GRAVEL TRANSITION
C-133
NEW GRAVEL ROAD
AND SUBGRADE
(WHERE SHOWN)
SUBGRADE PREPARATION
AS INDICATED
KEY-IN NEW BASE
AND SUBGRADE TO
EXISTING GRAVEL ROAD
(WHERE SHOWN)
NEW OR EXISTING
GRAVEL ROAD
NEW AC
PAVEMENT
2x6 CONSTRUCTION
HEART REDWOOD
OR CEDAR
HEADER
2 1/2" BASE COURSE AC
(AR 16,000)
NOTES:
V A
R
IA
B L E
"2
6"
2'-10" (MIN)
REV 110112
CLEANOUT TO GRADE (COTG)
L
L
SQUARE PAVEMENT
CONCRETE
WYE BRANCH
CONCRETE PLUG
INVERT ELEVATION
SEWER MAIN STATION
SEWER MAIN
C
C
CAST IRON FRAME AND COVER
C-302
1/2" CAST IRON CAP WITH
FINGER HOLE IN CENTER
1. IF IN UNIMPROVED AREA TOP SHALL BE 6" ABOVE GRADE.
2. SEE PLAN FOR STATION AND INVERT ELEVATION.
PIPE AND FITTINGS SHALL BE OF THE SAME
MATERIAL AS THE MAIN LINE SEWER.
45° BEND
(MIN)
REV 110112
INTERNAL BRACING
AT CORNER AND GATE
GATE POST
SET IN CONC
DESIGNED BY AN ENGINEER. OTHERS
SHALL BE 12" OR 5 X POST DIAMETER,
WHICHEVER IS GREATER
DIAGONAL
BRACE
3/8" TRUSS ROD
ASSEMBLY (TYP)
1. SEE SPECS FOR FENCE MATERIAL,
COATINGS, AND INSTALLATION
REQUIREMENTS.
2. GATE TO BE INSTALLED WITH KEEPER
TO SECURE IN OPEN POSITION.
3. GATES LESS THAN 8'-0" IN WIDTH
SHALL BE SINGLE LEAF.
4. SEE SPECIFICATIONS FOR CLEARANCES
IN SNOW REGIONS.
DIAGONAL
BRACE
GATE POST
SET IN CONC
GATE
FRAMEGATE
FRAME
LOCKING
DEVICEFOR
PADLOCK
CONTINUOUS NO 7
GALV STL TENSION WIRE
BUILDING
SIDEWALK
SIDEWALK
TOP RAIL
4" DIA GATE POST
(AS SHOWN ON PLANS)
3 ROWS OF
2 STRAND
BARBED WIRE
LOCKING DEVICE
FOR PADLOCK
S E
E S
P E
C
IF
IC
A
T
IO
N S
C-101
(B O
T T
O M
O F
F T
G T
O B
E S
E T
B E
L O
W F
R O
S T
L
IN
E
(AS SHOWN ON PLANS)
(4'-0" MIN)
(S E
E N
O T
E
(S E
E N
O T
E
NOTES:
X X
X X
X X
X X X X
X X X X
X X X X
X
X
X
X X X X
X X X X
X X X X
X
X
X
(M
IN
GATE WIDTH
GATE WIDTH
H E
IG
H
T T
O M
A T
C H
F E
N C
E
/2
C L R
M
IN
/ 2
C L R
M
IN
SINGLE LEAF PEDESTRIAN GATE
C-103
CIVIL
STANDARD DETAILS -1
ARF DEW CWS
GC-1
D G
S R
E V
IE
W
C O
M M
E
.0
.0
D E W
D
P U
M P
S
TA
TI
O
N R
E D
E
SI
.0
.1
D E W jr c^l fco(Qz — '------------- -"VO fofo 3*1
CO S
74231
EXP. 6/3&/2bZ5 /-S'\ Ua r>i
|^^^5/2V/Z®23
06/06/2025
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/25/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-2557
E N
O T E
T R
E N
C H
Z O
N E
T R
E N
C H
Z O
N E
T R
E N
C H
Z O
N E
E M
B E D
M E N
T
E M
B E D
M E N
T
C-601
S E E S
P E C
S S E E S
P E C
S
S E E S
P E C
S
TOP OF
PIPE (OD)
TRENCH
BOTTOM
1'-6" FINAL
BACKFILL
SEE SPECS
1'-6" FINAL
BACKFILL
SEE SPECS
1'-6" FINAL
BACKFILL
SEE SPECS
TOP OF
PIPE (OD)
TOP OF
PIPE (OD)
TRENCH
BOTTOM
10" BEDDING
SEE SPECS
TRENCH
BOTTOM
10" BEDDING
SEE SPECS
10" BEDDING
SEE SPECS
1. 6" MIN FOR PIPE DIAMETER < 24"
12" MIN FOR PIPE DIAMETER > 24"
2. MAX TRENCH WIDTH @ TOP OF PIPE:
OD + 36" FOR, 18" & LARGER PIPE OD
OD + 24" FOR LESS THAN 18"
3. MIN TRENCH BOTTOM WIDTH =
OD + 24" FOR MECHANICAL COMPACTION
A. FLEXIBLE PIPE REFERS TO ALL STEEL, DUCTILE-IRON, AND PLASTIC PIPES.
B. TYPICAL TRENCH SECTIONS (I, II AND III) ARE TO BE USED ONLY WHERE STABLE,
COMPACT SOIL CONDITIONS EXIST. IF BOULDERS OR LARGE OBSTRUCTIONS ARE
ENCOUNTERED, TRENCH SECTIONS MAY BE DEEPER OR WIDER THAN SHOWN.
THE ENGINEER SHALL BE ADVISED SHOULD THIS OCCUR.
C. THE NEED FOR PROTECTIVE SYSTEMS AND EXCAVATION SLOPES SHALL BE DETERMINED
CONSIDERING APPLICABLE LOCAL, STATE AND FEDERAL (OSHA) SAFETY STANDARDS AND
REGULATIONS, AND GEOTECHNICAL CONSULTANTS' RECOMMENDATIONS.
D. PROTECTIVE SYSTEMS SHALL BE DESIGNED AND BUILT IN ACCORDANCE WITH
THE APPLICABLE LOCAL, STATE AND FEDERAL (OSHA) SAFETY STANDARDS AND
REGULATIONS.
E. SUPPORTING DOCUMENTATION SHALL BE SUBMITTED TO THE ENGINEER
REGARDING PIPE DESIGN AND COMPLIANCE WITH APPLICABLE LOCAL, STATE
AND FEDERAL (OSHA) SAFETY STANDARDS.
F. UNSUPPORTED VERTICAL AND/OR SLOPING TRENCH WALL SLOPES SHALL NOT
BE STEEPER THAN ALLOWED BY APPLICABLE LOCAL, STATE AND FEDERAL (OSHA)
SAFETY STANDARDS AND REGULATIONS, UNLESS SUPPORTING DOCUMENTATION
IS SUBMITTED, ACCORDING TO AFOREMENTIONED SAFETY STANDARDS.
G. TRENCH SECTIONS OTHER THAN THE TYPICAL SECTIONS SHOWN MAY BE
UTILIZED PROVIDED THEY COMPLY WITH APPLICABLE LOCAL, STATE AND
FEDERAL (OSHA) SAFETY STANDARDS AND REGULATIONS. DOCUMENTATION
SUPPORTING THIS COMPLIANCE AND PIPE DESIGN CALCULATIONS SHALL BE
SUBMITTED TO THE ENGINEER.
H. IF OVER-EXCAVATION DUE TO POOR FOUNDATION MATERIAL IS ORDERED BY THE
ENGINEER, THE BACKFILL MATERIAL SHALL BE ACCORDING TO THE EARTHWORK
SECTION OF THE SPECIFICATIONS ARTICLE ENTITLED, "FILL AND BACKFILL MATERIAL
REQUIREMENTS."
I. IF DURING CONSTRUCTION, THE WATER TABLE IS DISCOVERED TO BE ABOVE THE
TRENCH BOTTOM, THE ENGINEER SHALL BE NOTIFIED, AND APPROPRIATE DEWATERING
SHALL BE IMPLEMENTED TO LOWER THE WATER LEVEL BELOW THE TRENCH BOTTOM.
THE BACKFILL MATERIAL SHALL BE ACCORDING TO THE EARTHWORK SECTIONS OF THE
SPECIFICATIONS, OR AS ORDERED BY THE ENGINEER.
TRENCH SECTION - TYPE I TRENCH SECTION - TYPE II TRENCH SECTION - TYPE III
NOTES:
TRENCH SECTION
FLEXIBLE PIPE
E M
B E D
M E N
T T R
E N
C H
D E P T H
P
IP
E Z
O N
E B
A C K F
IL
L
NOTE 3 NOTE 3
NOTE 2
NOTE 3
P
IP
E Z
O N
E B
A C K F
IL
L
P
IP
E Z
O N
E B
A C K F
IL
L
T R
E N
C H
D E P T H
T R
E N
C H
D E P T H
NOTE 2
S E E N
O T E
S E E N
O T E
REV 110112
S E E S
P E C
S S E E S
P E C
S
S E E S
P E C
S
S E E S
P E
E S
P E C
S
S E E S
P E C
S
3/8" TIE RODS
THRUST DIRECTION
PLUG OR CAP
75%
100% 100% OF TEE
100%
50% 50% 50% 50%
100%
75%
75%
75% 75%
75% OF TEE (TYP)
100%
=9.4 SQ FT=
4 19
623 878
27 15
478 244
PIPE SIZE SIDE THRUST-lb PIPE SIZE SIDE THRUST-lb
12 278
35 14
24 1150
C-605
3/8" TIE RODS
PLANS
2-#5 BARS
BEARING AREA
FIGURE (100%) AT THRUST BLOCK INDICATES
PERCENT OF TOTAL THRUST TO BE APPLIED
FOR BEARING AREA
100% OF
TEE
UNDISTURBED
EARTH (TYP)
75% OF TEE
(TYP)
CARDBOARD
SEPARATOR
PIPE
SIZE
DEAD END
OR TEE
90°
ELBOW
45°
ELBOW
THRUST PER PSI OF WATER
PRESSURE AT VARIOUS FITTINGS
SIDE THRUST PERM 100 PSI PRESSURE
PER DEGREE OF DEFLECTION
100% OF
90° ELL
VALVE IF SHOWN
ON PLAN
5° MAX
DEFLECTION/JOINT
FOR PIPES 3" - 12"
& 3° MAX 14" - 24"
MULTIPLY THRUST BY DEGREE OF DEFLECTION
TO OBTAIN TOTAL THRUST
8-INCH 90° ELBOW, PRESSURE=200 PSF
FROM TABLE: THRUST = 94 X 200 = 18,800 lb
ASSUME BEARING STRENGTH OF SOIL = 2000 PSF
BEARING AREA REQUIRED
FOR THRUST BLOCK
18,800
WEIGHT OF CONCRETE
TO RESIST 100% OF
TOTAL THRUST
1. IN USING THE ABOVE TABLES, USE THE MAXIMUM
INTERNAL PRESSURE ANTICIPATED (i.e. HYDROSTATIC
TEST PRESSURE) POSSIBLE SURGE PRESSURE DUE
TO PUMP SHUT-OFF, ETC.
2. SEE SOILS REPORT FOR BEARING STRENGTH OF SOIL
IN THE ABSENCE OF A SOILS REPORT AN AVERAGE
SOIL (SPADABLE MEDIUM CLAY) CAN BE ASSUMED TO
HAVE A BEARING STRENGTH OF 2000 PSF
3. WITH SOLVENT WELDED JOINTS
4. USE LIGHTWEIGHT CONCRETE FOR HILL THRUST BLOCK.
5. CONCRETE FOR THRUST BLOCKS TO BE 2000 PSI.
22 1/2°
ELBOW
NOTE:
NOTE:
VERTICAL BEND
DEAD-ENDVALVE
CURVE THRUST BLOCKING
EXAMPLE:
NOTES:
LENGTH
18" 18"
REV 110112
CONCRETE THRUST BLOCKS
SS BACKING
RING
SS BOLT
150 LBS FLANGE
1. FOR STEEL PIPE, FABRICATE TO MATCH THE SAME
ID AS HDPE PIPE.
2. PIPE SHALL BE INSTALLED SUCH THAT ID OF BOTH PIPES
ARE FLUSH AT THE JOINT.
NOTES:
PVC/STEEL PIPE
AS SPECIFIED
GRIND 1/4"
RADIUS ON
STEEL PIPE
HDPE PIPE
AS SPECIFIED
C-900
HDPE FLANGED CONNECTION
1.4D
.5 D
8"
2"
9"
D
D
9" D 8"
T Y P
" (T
Y P
.5 D M
IN
REV 110112
C-220
C-210
C-221
TRASH RACK #4 @ 9"
DRAIN PIPE
#4 @ 9" (TYP)
FLOW
(SIDE ENTRANCE) FLOW
FILTER FABRIC #4 @ 9"
U N O
(TYP)
FOR PIPE LOCATION &
SIZE SEE PLAN
EXTEND TO
1.5 D ABOVE
CHANNEL INVERT
EXTEND TO 1.5D
ABOVE CHANNEL
INVERT
(HEADWALL
ENTRANCE/EXIT)
APPROX EXTENSION
OF RIP-RAP
#4 @ 9"
(TYP EACH SIDE)
TYPICAL GRADING PLAN
TYPICAL PLAN
DETAIL PLAN
TYPICAL DETAIL PLAN & SECTION
LARGE DRAIN PIPE
INLET AND OUTLET
TRANSITION TO
REQ'D CHANNEL
SECTION (SEE
PLAN)
LC DRAINAGE DITCH
SLOPE 1:1 OR
AS INDICATED
5/8" HOLE FOR 1/2"
ADH ANCHOR
WITH NUT & WASHER
(TYP EACH CORNER
AND @ 18" MAX
SPACING TOP)
PLAN
ELEVATION
1 1/2"x3/8" STEEL
BARS @ 3/4" OC WITH
3/8" BANDING BAR ALL
AROUND, SEAL WELDS,
GALVANIZE AFTER
FABRICATION
TRASH RACK
REV 110112
C-221
ORIGINAL SHEET - ARCH D
A
B
C
D
V4 c u se rs d iy e ru sa lim e ts d c a c c d o c s\ st a n te c c o n su lt in g
_m o c c a si n
_h a tc h e ry p ro je c t fil e s\
.0 d e si g n
.7 d ra w in g s\ c iv il\ g c
.0
.0
:1
:3
P
M
Permit/Seal
Drawing No.
ofRevision:
File Name: N/A
Title
Sheet:
YYYY.MM.DDDsgn. Chkd.Dwn.
2025.04.11
C lie n t/
P ro je c t
Project No.:
Scale:
M O
C C
A
SI
N C
R E E K
F
IS
H H
A
TC
H E R
Y
C A
LI
FO
R N
IA
D
E P
A R
TM
E N
T O
F
FI
SH
A
N D
W
IL
D
LI
FE
M O
C C
A
SI
N , C
A
LI
FO
R
N
IA
22402869
A
O
SF
M S
TA
M
P B
LO
C
K U
P D e d
/R e vi si
Y
Y .M
M .D
D
Th e
C o n tr a c to r sh a ll v e rif y a n d b e r e sp o n si b le f o r a ll d im e n si o n s.
D O
N O
T sc a le t h e d ra w in g a n y e rr o rs o r o m is si o n s sh a ll b e r e p o rt e d t o St a n te c w ith o u t d e la y.
T h e
C o p y rig h ts t o a ll d e si g n s a n d d ra w in g s a re th e p ro p e rt y o f St a n te c
R e p ro d u c tio n o r u se f o r a n y p u rp o se o th e r th a n t h a t a u th o riz e d b y S ta n te c is f o rb id d e n
C o p yr ig h t R e se rv e d
St a n te c C o n su lt in g S e rv ic e s In c
T re a t B o u le v a rd S u it e
W a ln u t C re e k, -7
Te l:
(9
-1 w w w .s ta n te c
.c o m
4 51 2 3
.1
.1
D E
SI
G N
S U
B M
IT
.1
.1
CIVIL
STANDARD DETAILS -2
ARF DEW XXX
GC-2
D G
S R
E V
IE
W
C O
M M
E
.0
.0
D E W
B
P U
M P
S
TA
TI
O
N R
E D
E
SI
.0
.1
D E W jr c^l fco(Qz — '------------- -"VO fofo 3*1
CO S
74231
EXP. 6/3&/2bZ5 /-S'\ Ua r>i
|^^^5/2V/Z®23
06/06/2025
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/25/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-2557
STRUCTURAL WORK POINTS
POINT#
WP1
WP2
NORTHING
2118841.78
2118823.44
EASTING
6617005.29
6617020.90
DESCRIPTION
REUSE STRUCTURE (SW) CORNER
REUSE STRUCTURE (SE) CORNER
STRUCTURAL WORK POINTS
POINT#
WP1
WP2
NORTHING
2118841.78
2118823.44
EASTING
6617005.29
6617020.90
DESCRIPTION
REUSE STRUCTURE (SW) CORNER
REUSE STRUCTURE (SE) CORNER
ORIGINAL SHEET - ARCH D
A
B
C
D
V4 c u se rs d iy e ru sa lim e ts d c a c c d o c s\ st a n te c c o n su lt in g
_m o c c a si n
_h a tc h e ry p ro je c t fil e s\
.0 d e si g n
.7 d ra w in g s\ c iv il\ c
.0
.0
:1
:2
P M
Permit/Seal
Drawing No.
ofRevision:
File Name: N/A
Title
Sheet:
YYYY.MM.DDDsgn. Chkd.Dwn.
2025.04.11
C lie n t/
P ro je c t
Project No.:
Scale:
M O
C C
A
SI
N C
R E E K
F
IS
H H
A
TC
H E R
Y
C A
LI
FO
R N
IA
D
E P
A R
TM
E N
T O
F
FI
SH
A
N D
W
IL
D
LI
FE
M O
C C
A
SI
N , C
A
LI
FO
R
N
IA
22402869
A
O
SF
M S
TA
M
P B
LO
C
K U
P D e d
/R e vi si
Y
Y .M
M .D
D
Th e
C o n tr a c to r sh a ll v e rif y a n d b e r e sp o n si b le f o r a ll d im e n si o n s.
D O
N O
T sc a le t h e d ra w in g a n y e rr o rs o r o m is si o n s sh a ll b e r e p o rt e d t o St a n te c w ith o u t d e la y.
T h e
C o p y rig h ts t o a ll d e si g n s a n d d ra w in g s a re th e p ro p e rt y o f St a n te c
R e p ro d u c tio n o r u se f o r a n y p u rp o se o th e r th a n t h a t a u th o riz e d b y S ta n te c is f o rb id d e n
C o p yr ig h t R e se rv e d
St a n te c C o n su lt in g S e rv ic e s In c
T re a t B o u le v a rd S u it e
W a ln u t C re e k, -7
Te l:
(9
-1 w w w .s ta n te c
.c o m
4 51 2 3
.1
.1
D E
SI
G N
S U
B M
IT
.1
.1
0 40 80
SCALE IN FEET
HATCHERY
BUILDING
DISTRIBUTION
BOX
HEAD
FLUME
EXISTING GAS
CONTROL COLUMNS (TYP 4)
CHAINLINK
FENCE
SETTLING
POND
PREDATOR
FENCE
GARAGE/OFFICE
RESTROOMS
FREEZER
BUILDING
POND SERIES A
POND SERIES B
POND SERIES C
POND SERIES D
POND SERIES E
POND SERIES F
POND SERIES G
POND SERIES H
BENCHMARKS
NUMBER NORTHING EASTING ELEVATION DESCRIPTION
BM-1 2118227.9320 6617804.4970 931.51
4" BRASS DISK, STAMPED " SAN FRANSICO
H.H.WS. STA, ELEV 926.99"
BM-2 2118596.0810 6617583.1660 909.30 1" IRON PIPE W/ YELLOW CAP PLS 8008
GENERAL SHEET NOTES
1. SITE SURVEY WAS PERFORMED IN DECEMBER,2018 BY
LEE INC. HORIZONTAL AND VERTICAL DATUMS ARE
DEFINED BY BENCHMARK BM-1 LOCATED ON
MOCCASIN DAM BASED ON INFORMATION FOR THIS
BENCHMARK PROVIDED BY SAN FRANCISCO PUBLIC
UTILITIES COMMISSION. ELEVATIONS ARE SHOWN IN
THE HETCH HETCHY DATUM.
2. CONTRACTOR SHALL MAINTAIN PUBLIC ACCESS TO
AREAS TO BE DEFINED BY HATCHERY STAFF
THROUGHOUT THE DURATION OF CONSTRUCTION.
3. ALL STRUCTURE COORDINATES ARE TO THE OUTSIDE
CORNER OF COLUMN OR STRUCTURE UNO.
4. PRIOR TO EXCAVATION IN THE VICINITY OF ANY
UNDERGROUND UTILITIES, INCLUDING ALL DOMESTIC
WATER, PROCESS WATER, SEWER, STORM DRAIN,
BURIED ELECTRICAL POWER, COMMUNICATIONS
LINES, OR OTHERS, CONTRACTOR SHALL POTHOLE TO
DETERMINE LOCATION OF UTILITIES. TAKE ALL
NECESSARY PRECAUTIONS TO PROTECT
UNDERGROUND UTILITIES FROM DAMAGE.
EXISTING
SPILLWAY
MOCCASIN
CREEK
GARAGE
CARPORTS
(TYP 2)
FEED STORAGE
BINS (TYP 6)
VEHICLE
GATE
GRAVEL
ACCESS
ROAD
VEHICLE
GATE
(EXISTING)
VEHICLE
GATE
(EXISTING)
FLOOD PROTECTION
BERM
VEHICLE
GATE
PROTECT
EXISTING 18" HDPE PIPE
SEE SHEET C-2
UNUSED
CONCRETE PONDS
(TYP 3)
CREST OF
MOCCASIN DAM,
APPROX
FUEL TANKS
ON CONCRETE PAD
WATER
VAULT
HANDICAPPED
PARKING SPACES
T A
IL
F L U
M E
REUSE PUMP STATION
PEDESTRIAN
GATE
EXISTING
LEGEND
ASPHALT SURFACING, EXISTING
GRAVEL SURFACE,EXISTING
BIRD PREDATOR FENCE, EXISTING
CHAIN LINK FENCE, NEW,
CHAIN LINK FENCE, EXISTING
ASPHALT SURFACING, NEW
BM-1
EMERGENCY
PUMP STATION
BM-2
HB
HB
CAL TRANS ROW
HB
HB
GARAGE
WARDEN
OFFICE/SHOP
RETAIN AND PROTECT
EXISTING ELECTRICAL
PANELS
SETTLING POND
BYPASS OUTFALL
SETTLING POND
OUTFALL
18" CMP
VEHICLE
GATE
(EXISTING)
CA H
W
Y 1
STEPS
UTILITY WATER,
SEE M-1
WP1 WP2
FLOW METER,
(EXISTING)
REPLACE EXISTING ASPHALT
AROUND REUSE PUMP
STATION WITH GRAVEL
SURFACING, MATCH
EXISTING GRADES AND
SLOPES
C-1
CIVIL SITE PLAN
CWSDEW ARF
1"=40'
5. THE CONTRACTOR SHALL PROPERLY DISPOSE OFF
SITE OF ALL DEBRIS FROM DEMOLITION AT
CONTRACTORS EXPENSE UNO.
6. AT COMPLETION OF CONSTRUCTION, CONTRACTOR
SHALL RESTORE ASPHALT PAVING AND GRAVEL
SURFACING IN ALL WORK AREAS AND AT ANY
LOCATIONS DAMAGED BY CONSTRUCTION, INCLUDING
HATCHERY ACCESS ROAD.
7. RESTORE ALL EXISTING GRAVEL SURFACING AT
COMPLETION OF CONSTRUCTION, SEE DETAIL C-132
ON SHEET GC-1.
8. REPLACE EXISTING ASPHALT AROUND REUSE PUMP
STATION WITH GRAVEL SURFACING, SEE DETAIL C-132
ON SHEET GC-1.
9. SEE SHEET C-2 FOR TABLE OF CONSTRUCTION
WORKPOINTS.
10. PROVIDE 3' MIN COVER OVER UTILITY WATER PIPE.
GENERAL SHEET NOTES (CONTINUED)
D G
S R
E V
IE
W
C O
M M
E
.0
.0
B
P U
M P
S
TA
TI
O
N R
E D
E
SI
.0
.1
D E W
C-2
4" DR (PV01)
0.5% SLOPE,
APPROX 250 LF
DAYLIGHT DRAIN
PIPE IN EXISTING
DITCH ALONG N SIDE
OF ENTRY ROAD,
APPROX IE 865.00
TEE AT CONNECTION
TO EXISTING PIPE
2" TEE W/ BLIND FLANGE
FOR FUTURE CONNECTION
2" UW (PV01)
SEE NOTE 10
jr c^l fco(Qz — '------------- -"VO fofo 3*1
CO S
74231
EXP. 6/3&/2bZ5 /-S'\ Ua r>i
|^^^5/2V/Z®23
06/06/2025
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/25/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-2557
8" 2'-6"
8"
9"
9"
0'-8"
1'-6" 9"
ORIGINAL SHEET - ARCH D
A
B
C
D
V4 c u se rs d iy e ru sa lim e ts d c a c c d o c s\ st a n te c c o n su lt in g
_m o c c a si n
_h a tc h e ry p ro je c t fil e s\
.0 d e si g n
.7 d ra w in g s\ c iv il\ c
.0
.0
:2
:0
P
M
Permit/Seal
Drawing No.
ofRevision:
File Name: N/A
Title
Sheet:
YYYY.MM.DDDsgn. Chkd.Dwn.
2025.04.11
C lie n t/
P ro je c t
Project No.:
Scale:
M O
C C
A
SI
N C
R E E K
F
IS
H H
A
TC
H E R
Y
C A
LI
FO
R N
IA
D
E P
A R
TM
E N
T O
F
FI
SH
A
N D
W
IL
D
LI
FE
M O
C C
A
SI
N , C
A
LI
FO
R
N
IA
22402869
A
O
SF
M S
TA
M
P B
LO
C
K U
P D e d
/R e vi si
Y
Y .M
M .D
D
Th e
C o n tr a c to r sh a ll v e rif y a n d b e r e sp o n si b le f o r a ll d im e n si o n s.
D O
N O
T sc a le t h e d ra w in g a n y e rr o rs o r o m is si o n s sh a ll b e r e p o rt e d t o St a n te c w ith o u t d e la y.
T h e
C o p y rig h ts t o a ll d e si g n s a n d d ra w in g s a re th e p ro p e rt y o f St a n te c
R e p ro d u c tio n o r u se f o r a n y p u rp o se o th e r th a n t h a t a u th o riz e d b y S ta n te c is f o rb id d e n
C o p yr ig h t R e se rv e d
St a n te c C o n su lt in g S e rv ic e s In c
T re a t B o u le v a rd S u it e
W a ln u t C re e k, -7
Te l:
(9
-1 w w w .s ta n te c
.c o m
4 51 2 3
.1
.1
D E
SI
G N
S U
B M
IT
.1
.1
GENERAL SHEET NOTES
1. CONTRACTOR SHALL PROTECT AND REUSE EXISTING EXPOSED
HDPE PIPE AS PART OF NEW REUSE SUPPLY PIPING. TOTAL
LENGTH OF EXISTING PIPE IS APPROXIMATELY 600 FEET.
CONTRACTOR TO EVALUATE CONDITION AND SUPPLEMENT AND
REPLACE PIPE AS NECESSARY FOR A COMPLETE INSTALLATION.
2. A 4" EXISTING DOMESTIC WATER LINE IS BURIED IN THE GRAVEL
ROAD AND TO THE WEST OF THE REUSE PUMP STATION.
CONTRACTOR SHALL POTHOLE TO LOCATE WATER LINE
PROTECT PIPELINE AND MAINTAIN CONTINUOUS SERVICE
THROUGHOUT CONSTRUCTION. REROUTE EXISTING HDPE
DOMESTIC WATER LINE IF NEEDED TO AVOID NEW WORK.
COORDINATE OUTAGE WITH HATCHERY STAFF.
3. FOR PIPING, STRAIGHT SLOPES SHALL BE MAINTAINED BETWEEN
INVERT ELEVATIONS SHOWN OR SPECIFIED.
4. PIPE DIAMETERS SHOWN ARE NOMINAL DIAMETERS. SEE
SPECIFICATION FOR DETERMINATION OF WALL INSIDE DIAMETER,
WALL THICKNESS, AND PRESSURE RATING.
5. LOCATE BURIED UTILITY PIPE AND EXTEND TO REUSE PUMP
STATION, SEE SHEET M-1.
6. PROVIDE THRUST BLOCKS AT ALL FITTINGS ON PUMPED REUSE
WATER PIPELINE. AT CONTRACTOR'S OPTION, MECHANICAL JOINT
RESTRAINT MAY BE PROVIDED IN PLACE OF THRUST BLOCKS,
EBARA IRON SERIES 2000PV, OR EQUAL.
7. PIPES SHALL BE INSTALLED IN ACCORDANCE WITH STANDARD
DETAILS C-601 AND C-605.
8. INSTALL SLIDE GATE FLUSH TO FLOOR.
9. FOLLOWING CONSTRUCTION RESTORE/REPLACE FENCE GATES
AND DAMAGED OR RELOCATED EXISTING FENCES.
10. CORE DRILL WALL FOR PIPE PENETRATION THROUGH EXISTING
DRAIN CHANNEL. PRIOR TO CORE DRILLING, CONTRACTOR SHALL
LOCATE THE REBAR IN THE WALL AND VERIFY CORE DRILL
LOCATIONS WITH ENGINEER. FOLLOWING INSTALLATION, FILL
ANNULAR SPACE AROUND PIPE WITH NON-SHRINK GROUT FOR A
WATER TIGHT SEAL.
24" DR ( PV05)
. G-1
SECTION
SCALE: 1/2" = 1'-0"C-2
B
TO REUSE
PUMP STATION
MANUAL
HAND
CRANK
GRAVEL
SURFACING
INSTALL GATE FLUSH TO FLOOR
PER MFR RECOMMENDATIONS
DRILL & EPOXY #5@6" OC
EACH FACE HORIZ. INTO (E)
WALL & VERT. INTO (E) FOUNDATION
DETAIL
SCALE: 1/2" = 1'-0"C-2
EL 867.5±
24" DR ( PV05)
EXISTING TAIL
FLUME WALL
REMOVE 48" ± LENGTH OF EXISTING WALL & INSTALL
(N)24" PIPE & GATE INTO RECAST CONC
GREENSTREAK CJ1020
WATERSTOP ADHERED
CONTINUOUSLY TO SIDE WALL,
FOUNDATION & SIDE WALL
.G-1
24" SLIDE GATE
GREENSTREAK CJ1020 WATERSTOP ADHERED
CONTINUOUSLY AROUND (N) 24"Ø PIPE
FLANGE MOUNT SLIDE GATE TO
NEW CONCRETE ON SIDES
C-2
B
C-2
SITE PIPING PLAN
CWSDEW ARF
AS SHOWN
D G
S R
E V
IE
W
C O
M M
E
.0
.0
REUSE PUMP STATION AREA ENLARGED PLAN
SCALE: 1" = 10'C-2
REUSE
PUMP
STATION
4" HDPE EXISTING DOMESTIC
WATER LINE, SEE NOTE 2
EXISTING
FENCE GATE
LOW HEADLOSS RUBBER
CHECK VALVE, IE 867.75
EXISTING STEPS
12'-0"
18" R ( PE05)
EXISTING
VEHICLE GATE
SEE NOTE 8
EXISTING
FENCE
POWER
POLE
G-1
COTG C-302
2" UW (PV01)
NEW GRAVEL
SURFACING, APPROX
5227 SQ FT. REMOVE
EXISTING ASPHALT
PREDATOR FENCE
(EXISTING)
EXISTING 18" HDPE
PIPE
10'-0"
FLOW METER MOUNTED TO
EXPOSED PIPE, PROTECT AND RETAIN
FL X FL SLEEVE COUPLING
AT CONNECTION TO
EXISTING EXPOSED HDPE
PIPE
SLOPE PIPE BETWEEN
FITTINGS TO TRANSITION
ELEVATION
6" DR ( PV03)
24" OF ( PV05) SEE NOTE 10
6"X4" TEE (TYP)
S=2%
C-2
TRANSFORMER ,
SERVICE ENCLOSURE.AND ATS ENCLOSURE
(EXISTING, APPROX LOCATION) SEE SFPUC
REFERENCE DRAWING
4" DR (PV01)
FLEX COUPLING
24" OF (PV05)
6" DR (PV05)
FILTER FABRIC
SECTION
SCALE: 1/2' = 1'-0" C-2
A
A C-2
IE 865.65
WSE 867.50
M-112 PIPE THIMBLE,
TYP
EL 865.40
M-112 PIPE THIMBLE,
TYP
FOR STRUCTURAL
DETAILS, REFERENCE
STANDARD DETAIL C-220
TRASHRACK PER
STD DETAIL C-221
FLEX COUPLING (TYP)
IE 865.65
C-2
STOPLOGS BY OWNER (TYP)
IE 868.60
TOC 869.00
OUTFALL STRUCTURE PLAN
SCALE: 1/2' = 1'-0"C-2
LOW HEADLOSS
RUBBER CHECK VALVE
DRUM FILTER
BACKWASH
IE 867.5
IE 865.65
WSE 870.3±
SLEEVE
COUPLING
24" DR ( PV05)
2" TEE W/ BLIND FLANGE
FOR FUTURE CONNECTION
EXISTING 16'
FENCE GATE,
SEE NOTE 9
SEE NOTE 10
jr c^l fco(Qz — '------------- -"VO fofo 3*1
CO S
74231
EXP. 6/3&/2bZ5 /-S'\ Ua r>i
|^^^5/2V/Z®23
06/06/2025
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/25/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-2557
B
C
D
V4 c u se rs d iy e ru sa lim e ts d c a c c d o c s\ st a n te c c o n su lt in g
_m o c c a si n
_h a tc h e ry p ro je c t fil e s\
.0 d e si g n
.7 d ra w in g s\ st ru c tu ra l\ m fh
-g s0
.0
.0
:3
:2
P M
Permit/Seal
Drawing No.
ofRevision:
File Name: N/A
Title
Sheet:
YYYY.MM.DDDsgn. Chkd. Dwn.
2025.04.11
C lie n t/
P ro je c t
Project No.:
Scale:
M O
C C
A
SI
N C
R E E K
F
IS
H H
A
TC
H E R
Y
C A
LI
FO
R N
IA
D
E P
A R
TM
E N
T O
F
FI
SH
A
N D
W
IL
D
LI
FE
M O
C C
A
SI
N , C
A
LI
FO
R
N
IA
22402869
A
O
SF
M S
TA
M
P B
LO
C
K U
P D e d
/R e vi si
Y
Y .M
M .D
D
Th e
C o n tr a c to r sh a ll v e rif y a n d b e r e sp o n si b le f o r a ll d im e n si o n s.
D O
N O
T sc a le t h e d ra w in g a n y e rr o rs o r o m is si o n s sh a ll b e r e p o rt e d t o St a n te c w ith o u t d e la y.
T h e
C o p y rig h ts t o a ll d e si g n s a n d d ra w in g s a re th e p ro p e rt y o f St a n te c
R e p ro d u c tio n o r u se f o r a n y p u rp o se o th e r th a n t h a t a u th o riz e d b y S ta n te c is f o rb id d e n
C o p yr ig h t R e se rv e d
St a n te c C o n su lt in g S e rv ic e s In c
T re a t B o u le v a rd S u it e
W a ln u t C re e k, -7
Te l:
(9
-1 w w w .s ta n te c
.c o m
4 51 2 3
.1
.1
D E
SI
G N
S U
B M
IT
.1
.1
D E W
.0
.3
B
O
SF
M C
O M
M E N
TS
IN
C O
R P
O R
A
ALL CONSTRUCTION JOINTS, SHALL BE ROUGH AND THOROUGHLY
CLEANED FOR BOND.
LOCATION OF ALL CONSTRUCTION JOINTS SHALL BE AS SHOWN ON THE
DRAWINGS OR APPROVED BY THE ENGINEER. ALL CONSTRUCTION JOINTS
LOCATED ON THE DRAWINGS, OR REQUIRED FOR CONSTRUCTION BUT NOT
SHOWN ON THE DRAWINGS, SHALL HAVE A 6" FLATSTRIP WATERSTOP IF
IN CONTACT WITH WATER. IN ADDITION, JOINTS IN ALL SLABS COVERED
WITH WATER SHALL HAVE BOTH A 6" FLATSTRIP WATERSTOP AND A
SEALANT GROOVE.
DOWELS, PIPE, WATERSTOPS AND OTHER INSTALLED MATERIALS AND
ACCESSORIES SHALL BE HELD SECURELY IN POSITION WHILE
CONCRETE IS BEING PLACED.
UNLESS OTHERWISE INDICATED, ASIDE FROM NORMAL ACCESSORIES
USED TO HOLD REINFORCING BARS FIRMLY IN POSITION, THE
FOLLOWING SHALL BE ADDED:
+/- 3/8 INCH FOR MEMBERS WITH DEPTH D </= 8 INCHES
+/- 1/2 INCH FOR MEMBERS WITH DEPTH D > 8 INCHES
STEEL CONSTRUCTION SHALL CONFORM TO THE SPECIFICATIONS AND STANDARDS AS
CONTAINED IN THE SIXTEENTH EDITION OF THE AISC STEEL CONSTRUCTION MANUAL.
STRUCTURAL WIDE FLANGE SHAPES AND CHANNEL SHALL BE STEEL MEETING ASTM
A-992 SPECIFICATIONS.
OTHER SHAPES, BARS, PLATES AND SHEETS SHALL BE OF STEEL MEETING ASTM A-36
SPECIFICATIONS.
PIPE, PIPE COLUMNS, AND BOLLARDS SHALL BE OF STEEL MEETING ASTM
A-53, TYPE E OR S, GRADE B STANDARD WEIGHT, UNO.
HSS SHALL BE OF STEEL MEETING ASTM A-500 GRADE B.
STEEL JOISTS, BEAMS, AND GIRDERS SHALL NOT BE RELOCATED WITHOUT APPROVAL BY THE
ENGINEER.
ALL WELDING SHALL BE BY THE SHIELDED ARC METHOD AND SHALL CONFORM TO AWS CODE
FOR ARC AND GAS WELDING IN BUILDING CONSTRUCTION. QUALIFICATIONS OF WELDERS
SHALL BE IN ACCORDANCE WITH THE SPECIFICATIONS FOR STANDARD QUALIFICATION
PROCEDURE OF THE AWS.
ALL GRATINGS SHALL BE GALVANIZED STEEL, AND RAILINGS SHALL BE ALUMINUM.
UNLESS OTHERWISE NOTED OR SPECIFIED, ALL STRUCTURAL CONCRETE
SHALL DEVELOP A MINIMUM COMPRESSIVE STRENGTH OF 4500 PSI
IN 28 DAYS.
REINFORCEMENT STEEL SHALL BE DEFORMED BARS CONFORMING IN
QUALITY TO THE REQUIREMENTS OF ASTM A-615, "SPECIFICATIONS FOR
DEFORMED BILLET-STEEL BARS FOR CONCRETE REINFORCEMENT",
GRADE 60.
COLUMN SPIRALS SHALL CONFORM TO ASTM A-615, "DEFORMED AND
PLAIN BILLET-STEEL BARS FOR CONCRETE REINFORCEMENT, GRADE 60
OR ASTM A-82 "STEEL WIRE, PLAIN, FOR CONCRETE REINFORCEMENT".
ALL DETAILING, FABRICATION AND PLACING OF REINFORCING BARS,
UNLESS OTHERWISE INDICATED, SHALL BE IN ACCORDANCE WITH
ACI-315, "MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED
CONCRETE STRUCTURES", LATEST EDITION.
TOLERANCES IN PLACING REINFORCEMENT SHALL BE:
IN SLABS #5 RISER BARS AT 36 INCHES OC MAXIMUM TO
SUPPORT TOP REINFORCING BARS.
IN WALLS WITH 2 CURTAINS #3 U OR Z SHAPE SPACERS
AT 6 FEET OC EACH WAY.
A)
B)
ALL GROUT SHALL BE NON-SHRINK GROUT, UNLESS INDICATED OTHERWISE.
UNLESS OTHERWISE SHOWN CONCRETE WALLS AND SLABS SHALL BE
REINFORCED AS FOLLOWS: #4@12" EW , CENTER OF 6" SECTIONS; #5@12"
EW, CENTER OF 8" SECTIONS; #4 @ 12" EW EF OF 10" SECTIONS; #5@12"
EW EF OF 12" AND THICKER SECTIONS.
FOR CONCRETE PLACED AGAINST EARTH
(SEE CONSTRUCTION JOINT DETAILS FOR
THIN SLABS-ON-GRADE, BOTTOM COVER
MAY BE LESS THAN 3" IF SO INDICATED)
FOR SURFACES IN CONTACT WITH WATER OR WEATHER
AND FORMED SURFACES IN CONTACT WITH EARTH
WHEN FILLING THE STRUCTURES WITH WATER FOR THE TEST REQUIRED
IN THE SPECIFICATIONS, ALL VARIOUS BASINS LOCATED IN THE SAME
STRUCTURE SHALL BE FILLED SIMULTANEOUSLY AT THE SAME RATE IN
ORDER TO KEEP THE SAME LEVEL IN EACH BASIN.
DETAILS ON GS SHEETS ARE PART OF STANTEC'S STRUCTURAL STANDARD
DETAILS.
THESE DETAILS ARE TO BE USED WHEN REFERRED TO OR WHEN NO
OTHER MORE RESTRICTIVE OR…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .