This is a set of 100% construction drawings and specifications for the Electric Vehicle Supply Equipment (EVSE) installation project at the Department of Water Resources Pearblossom O&M Center, prepared by Goss Engineering, Inc. in coordination with Proactive Engineering Consultants, MRP Planning Co., and the Office of Sustainability at the California Department of General Services. The project involves installation of EVSE infrastructure to provide power to 27 electric vehicle charging station (EVCS) ports across three facility locations: Water Ops Building (2 ports), O&M Center (10 ports), and Pumping Plant (3 ports). The scope includes three panelboards, two transformers, two disconnect switches, new feeder conduits, structural and civil work, and comprehensive electrical and fire safety systems. The project received approval from the Office of the State Fire Marshal on October 3, 2025, with the sealed bid deadline set for December 30, 2025, at 2:00 P.M. Bids are to be submitted to the DGS/OBAS Bid/Proposal Drop Box at 707 Third Street, West Sacramento, California. The project encompasses approximately 14,300 square feet of work area across the three locations and requires a C-10 contractor license. All charging stations are designated for authorized fleet vehicles only and are not available to the general public, with final EVCS installation and terminations to be performed by the State's designated electric vehicle charging station vendor.

The project requires compliance with the 2022 California Building Code, California Electrical Code, California Fire Code, and applicable NFPA standards. Third-party testing is required for all new feeder conductors, and special inspections are mandated for reinforcing steel, concrete placement, and post-installed anchorage per CBC Sections 1704 and 1705. The drawings include detailed fire safety plans identifying emergency access routes, fire extinguisher locations, fire hydrants, and emergency procedures at each facility location. Structural details encompass transformer and disconnect switch anchorage, bollard installation, panel board and digital multimeter mounting specifications, and rebar development length schedules. The project is funded by the State of California and administered under Contract 25-286288, Project 13263. Contractors must provide proof of valid Certificates of Reported Compliance (CRC) for any off-road diesel-fueled fleet vehicles used on the project. All work must maintain minimum 72-hour notice requirements for facility disruptions and coordinate closely with site operations to minimize impact to DWR personnel and operations.

View the file

Other files

File Type Posted
Project_Manual.pdf PDF
Bid_Package.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROACTIVE ENGINEERING CONSULTANTS

27051 TOWNE CENTRE DRIVE, SUITE 270

FOOTHILL RANCH, CA 92610

(949) 716-7460

CONTACT: FELIX GONZALEZ

MRP PLANNING CO.

130 CENTENNIAL WAY, UNIT C,

TUSTIN, CA 92780

(714) 923-8946

CONTACT: MIKE PAAR

Department of Water Resources

Pearblossom O&M Center EVSE Installation

100% Construction Drawings

LOCATION MAP

NOT TO SCALE

INDEX OF DRAWINGS

SCOPE OF WORK

THE SCOPE OF THIS PROJECT CONSISTS OF THE INSTALLATION OF THE ELECTRIC

VEHICLE SUPPLY EQUIPMENT (EVSE) TO PROVIDE POWER TO (27) ELECTRIC VEHICLE

CHARGING STATION (EVCS) PORTS WITHIN THE DWR PEARBLOSSOM O&M CENTER.

SEE EVCS NOTE ON THIS SHEET.

THE ELECTRIC VEHICLE SUPPLY EQUIPMENT IS MADE UP OF (3) PANELBOARDS, (2)

TRANSFORMERS AND (2) DISCONNECT SWITCHES AS WELL AS NEW FEEDERS TO THE

EVCS PORTS LOCATIONS AS SHOWN ON THESE PLANS. PROJECT INCLUDES

STRUCTURAL AND CIVIL WORK EFFORT/S NECESSARY TO SUPPORT THIS PROJECT.

SEE SHEET E1.00 FOR A SUMMARY OF THE EVCS PORTS.

ALL EVSE INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE

INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC

SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO COMPLY

WITH CBC 11B-228.3.2 ACCESS REQUIREMENTS.

ALTHOUGH THE CONTRACTOR MAY NOT PROCURE OR PERFORM THE FINAL

INSTALLATION OF THE EVSE, SUCH WORK IS WITHIN THE PERMIT SCOPE AND MAY BE

PERFORMED BY OTHERS.

ALL WORK PERTAINING TO AND ALL MATERIALS SUPPLIED FOR EXECUTING AND

COMPLETING THIS CONTRACT SHALL COMPLY WITH PROVISIONS SPECIFIED IN THE

CONTRACT DOCUMENTS AND WITH ALL APPLICABLE LAWS, REGULATIONS AND

ORDINANCES GOVERNING WORK INCLUDING, BUT NOT NECESSARILY LIMITED TO

THOSE OF THE APPLICABLE CODES LISTED ON SHEET E0.01.

SHEET COUNT DWG. NO. DESCRIPTION

1 OF 25 T0.01 TITLE SHEET, LOCATION MAP, GENERAL NOTES &

SHEET INDEX

2 OF 25 E0.01 SYMBOLS, DESIGNATION AND ABBREVIATIONS

3 OF 25 E0.02 SITE SAFETY PLAN

4 OF 25 E0.03 WATER OPS BUILDING SITE SAFETY PLANS

5 OF 25 E0.04 O&M CENTER SITE SAFETY PLANS

6 OF 25 E0.05 PUMPING PLANT SITE SAFETY PLANS

7 OF 25 E1.00 SITE PLAN

8 OF 25 E2.00 WATER OPS BUILDING POWER PLANS

9 OF 25 E2.01 O&M CENTER POWER PLANS

10 OF 25 E2.02 PUMPING PLANT POWER PLANS

11 OF 25 E4.00 ELECTRICAL DETAILS

12 OF 25 E4.01 ELECTRICAL DETAILS

13 OF 25 E5.00 SINGLE LINE DIAGRAMS

14 OF 25 E5.01 SINGLE LINE DIAGRAM

15 OF 25 E5.02 PANEL SCHEDULES

16 OF 25 C1 TITLE SHEET

17 OF 25 C2 SITE PLAN

18 OF 25 C3 SITE PLAN

19 OF 25 C4 SITE PLAN

20 OF 25 S0.01 GENERAL NOTES

21 OF 25 S0.02 SPECIAL INSPECTIONS

22 OF 25 S2.00 WATER OPS BUILDING ENLARGED EQUIPMENT

SUPPORT PLAN

23 OF 25 S2.01 O & M ENLARGED EQUIPMENT SUPPORT PLAN

24 OF 25 S2.02 WATER OPS BUILDING ENLARGED EQUIPMENT

SUPPORT PLAN

25 OF 25 S4.00 STRUCTURAL DETAILS

1. THE ARRANGEMENT OF THE EQUIPMENT, ELECTRICAL DEVICES, ETC. SHOWN ON THESE DRAWINGS IS GENERAL AND IS SHOWN TO IDENTIFY THE GENERAL INTENT OF THE PROJECT. ALL DETAILS AND ARRANGEMENTS SHALL BE VERIFIED PRIOR TO THE START OF WORK. THE DRAWINGS ARE NOT INTENDED TO SHOW EXACT DIMENSIONS/LOCATIONS.

2. CODE COMPLIANCE: ALL WORK SHALL CONFORM TO BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE CODES, STANDARDS, AND ORDINANCE AS SET FORTH BY THE AUTHORITIES HAVING JURISDICTION AND THEIR LATEST ADOPTED EDITIONS (IN EFFECT AT THE TIME OF THE BUILDING PERMIT APPLICATION) OF THE FOLLOWING PUBLICATIONS:

· CALIFORNIA CODE OF REGULATIONS TITLE 24: INCLUDES 2022 CALIFORNIA ELECTRICAL CODE, 2022 CALIFORNIA FIRE

CODE, 2022 CALIFORNIA BUILDING CODE, APPLICABLE YEARS OF NFPA ETC. WITH CALIFORNIA AND OTHER LOCAL

AMENDMENTS AS APPLICABLE.

· 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN.

3. SAFETY: THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO MAINTAIN ALL EQUIPMENT IN A SAFE AND RESPONSIBLE MANNER. KEEP DEAD FRONT EQUIPMENTS IN PLACE WHILE ENERGIZED. CONDUCT ALL CONSTRUCTION OPERATIONS IN A SAFE MANNER FOR EMPLOYEES AS WELL AS OTHER WORK PERSONS OR ANYONE VISITING THE JOB SITE. PROVIDE BARRIERS, FLAGS, TAPE, ETC. AS REQUIRED FOR SAFETY. THE CONTRACTOR SHALL HOLD ALL PARTIES HARMLESS OF

NEGLIGENT PRACTICES, WHICH MAY CAUSE INJURY TO OTHERS ON OR NEAR THE JOB SITE.

4. FIRE RATED ASSEMBLIES SHALL MAINTAIN RATINGS AS SPECIFIED IN THE CALIFORNIA BUILDING CODE, CHAPTER 7. ALL ASSEMBLIES TO BE PENETRATED SHALL BE INSTALLED WITH APPLICABLE THROUGH-PENETRATION FIRESTOP SYSTEM AS DETERMINED BY UL CLASSIFICATION. BEFORE CONSTRUCTION, VERIFY AND COMPLY WITH REQUIREMENTS.

5. PROVIDE THIRD-PARTY TESTING FOR ALL NEW FEEDER CONDUCTORS. BRANCH CIRCUITS ARE NOT REQUIRED TO BE

TESTED BY THIRD-PARTY. REFER TO PROJECT SPECIFICATIONS FOR MORE INFORMATION.

FOR EXISTING BUILDINGS:

1. ASBESTOS/LEAD PAINT: IF DURING THE COURSE OF WORK THE CONTRACTOR OBSERVES THE EXISTENCE OF ASBESTOS/LEAD PAINT, ASBESTOS BEARING MATERIALS, THE CONTRACTOR SHALL IMMEDIATELY TERMINATE FURTHER WORK ON THE PROJECT AND NOTIFY THE OWNER OF THE CONDITIONS. THE OWNER WILL, AFTER CONSULTATION WITH

THE OWNER'S REPRESENTATIVE, DETERMINE A FURTHER COURSE OF ACTION.

2. ANY DEMOLITION WORK SHOWN WAS PREPARED FOR THE CONVENIENCE OF THE CONTRACTOR. THE ENGINEER DOES NOT REPRESENT THAT ALL ITEMS WHICH MAY REQUIRE DEMOLITION HAVE BEEN SHOWN. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO CAREFULLY EXAMINE THE SITE AND CONTRACT DOCUMENTS AND TO PERFORM ALL DEMOLITION AND RECONSTRUCTION WHICH MAY BE REQUIRED FOR THE PROPER EXECUTION AND

COMPLETION OF THE WORK.

3. EXISTING CONDITIONS: INFORMATION SHOWN FOR EXISTING CONDITIONS WAS PRIMARILY GAINED FROM "AS-BUILT" DRAWINGS AND/OR LIMITED FIELD INVESTIGATION. BEFORE BID, VISIT SITE TO VERIFY EXISTING CONDITIONS AND MAKE

ALLOWANCE FOR VARIATION FROM THAT SHOWN.

4. CLOSELY COORDINATE OUTAGE AND FACILITY DISRUPTION TIME WITH OWNER. MINIMUM 72-HOURS NOTICE IS REQUIRED

BEFORE ANY CIRCUIT SHUTDOWN OR DISRUPTION OF FACILITY PERSONNEL FUNCTIONING.

GENERAL NOTES

EVCS NOTE:

ELECTRICAL VEHICLE CHARGING STATION

(EVCS) SHALL BE PROVIDED BY THE STATE

(DEPARTMENT OF GENERAL SERVICES), AND

INSTALLED BY THE CURRENT STATE ELECTRIC

VEHICLE CHARGING STATION VENDOR. ALL

FINAL TERMINATIONS AND/OR SPLICING FOR

THE EVCS SHALL BE THE RESPONSIBILITY AND

PERFORMED BY THE STATE VENDOR.

PROJECT TEAM

PROJECT DIRECTOR

STRUCTURAL ENGINEERCIVIL ENGINEER

ELECTRICAL ENGINEER

GOSS ENGINEERING, INC.

255 EAST RINCON STREET, SUITE 301,

CORONA, CA 92879

(951) 340-1977

CONTACT: ED BURTCH

R

CALL 811 BEFORE YOU DIG.

DGS PROJECT NUMBER: 000000000013263

ARC-FLASH NOTE:

ALL NEW ELECTRICAL SWITCHBOARDS, PANELBOARDS,

EQUIPMENT/DEVICES AND SUCH, SHALL BE PROVIDED WITH AN

ARC-FLASH HAZARD WARNING LABEL/MARKING, IN COMPLIANCE TO

THE REQUIREMENTS OF THE LATEST CEC 110.16. THE LABELS

SHALL BE GENERATED BY THE DESIGN TEAM AND INSTALLED BY

THE ELECTRICAL CONTRACTOR.

PROJECT

LOCATION

OFFICE OF SUSTAINABILITY, DGS

707 3RD STREET, 4TH FLOOR

WEST SACRAMENTO, CA 95606

(916) 823-7059

CONTACT: JANELLE GOULDING

OSFM APPLICATION NUMBERS:

PUMPING PLANT: 25-S-3435-C

WATER OPS BUILDING: 25-S-3997-C

O&M CENTER: 25-S-3998-C

Drawn by:

Job No.:

PA / PM:

Description of RevisionsByDate #

Sheet Title/Number

Scale:

Date:

REVISIONS

th

S tr e e t E a st

P e a rb lo ss o m

C A

E. Torres

E. Burtch

As Noted

D e p a rt m e n t o f W a te r R e s o u rc e s

P e a rb lo s s o m

O M

C e n te r E V S E I n s ta lla ti o n

125-01-02.65

09/29/2025

V2

255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com

DSA IDENTIFICATION STAMP:

CALOF I

G I

R E

NG

A

E

S

No. E17083

T

E

ET

S

AT

L

CE A

F

RIC

L

ORN

I

E

PR

RAET

RE

D D.D

OF ONA

B

R L

SSI

N E

RE

IW

D

U

T

HC

E

CSFM APPLICATION NUMBER: 25-S-3435-C

95% CD SubmittalEB05/28/2025 1

100% CD SubmittalEB09/02/2025 2

TITLE SHEET, LOCATION

MAP, GENERAL NOTES &

SHEET INDEX

T0.01

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/03/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3435

22 OF 25 S2.00 WATER OPS BUILDING

ENLARGED EQUIPMENT SUPPORT PLAN

23 OF 25 S2.01 O & M CENTER

ENLARGED EQUIPMENT SUPPORT PLAN

24 OF 25 S2.02 PUMPING PLANT

ENLARGED EQUIPMENT SUPPORT PLAN

25 OF 25 S4.00 STRUCTURAL DETAILS

CALOF I

G I

RE

NG

A

E

S

No. E17083

T E

ET

S

AT L CE A

F

R I C

L

ORNI

E

PR

RAET

RE

D D.D

OF ONA

B R L

SSI

NE

RE

IWD

U

T

HC

E

Exp. 9-30-27

Electric Vehicle Supply Equipment - Pearblossom O&M Center PN: 000000000013263, Date: 11/21/25 http://www.gossengineering.com

ABBREVIATIONS

ANNOTATION SYMBOLS

LEGEND

WIRING SYSTEM ABOVE FLOOR

LEVEL, CONCEALED IN WALL OR

ABOVE CEILING UON

WIRING SYSTEM IN OR UNDER

FLOOR OR CONCEALED IN OR

BEHIND STRUCTURE OR EQUIPMENT

CONDUIT STUB ENDING WITH CAP

E0.1

REMOVE/RELOCATE/DEMOLISH

EXISTING

FUSE

RECESSED PANELBOARD 120V/208V

SWITCH

COMBINATION MOTOR

STARTER/DISCONNECT SWITCH

(NUMBER INDICATES STARTER SIZE)

DISCONNECT SWITCH (FUSED),

HORSE POWER RATED

SURFACE MOUNTED PANELBOARD

277V/480V

DISTRIBUTION BOARD

FUSED DISCONNECT SWITCH

RECESSED PANELBOARD 277V/480V

SURFACE MOUNTED PANELBOARD

120V/208V

DISCONNECT SWITCH (NON-FUSED)

ELECTRICAL

SYMBOL

DESCRIPTION

F

SHEET WHERE DETAIL

IS DRAWN

OCCURRENCE

DETAIL IDENTIFICATION

(TYP.)

DETAIL

RECONSTRUCTION KEY NOTE

DEMOLITION KEY NOTE

REVISION

REVISED AREA

REVISION TAG

A AMPERE

ADA AMERICAN DISABILITIES ACT

AC ALTERNATING CURRENT

AF AMPERE FRAME

AS AMPERE SWITCH

AFC ABOVE FINISHED CEILING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIC AMPERE INTERRUPTING CAPACITY

ANN ANNUNCIATOR

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AV AUDIO-VISUAL

AWG AMERICAN WIRE GAUGE

BKR BREAKER

BLDG BUILDING

C CONDUIT

CB CIRCUIT BREAKER

CATV CABLE TELEVISION

CEC CALIFORNIA ELECTRICAL CODE

CKT CIRCUIT

CLG CEILING

CO CONDUIT ONLY

COMM COMMUNICATIONS

COMP COMPUTER

DB DISTRIBUTION BOARD

DISC DISCONNECT

DIST DISTRIBUTION

DL DOUBLE LUG

DP DISTRIBUTION PANEL

DWG DRAWING

E EXISTING TO REMAIN

EEOR ELECTRICAL ENGINEER ON RECORD

EG EQUIPMENT GROUND

ELEC ELECTRICAL

EMH ELECTRICAL MAN HOLE

EHH ELECTRICAL HAND HOLE

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

EV ELECTRIC VEHICLE

EVCS ELECTRIC VEHICLE CHARGING STATION

EVSE ELECTRIC VEHICLE SUPPLY EQUIPMENT

F FUSE, FUSED

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FLA FULL LOAD AMPERES

GRD GROUND

GALV GALVANIZE, GALVANIZED

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HPF HEAT PUMP HIGH POWER FACTOR

HPS HIGH PRESSURE SODIUM

JB JUNCTION BOX

KA THOUSAND AMPERES

KCMIL THOUSAND CIRCULAR MILS

KVA KILOVOLT-AMPERE

KW KILOWATT

LCL LONG CONTINUOUS LOAD

LTG LIGHTING

MC METAL CLAD CABLE

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCM THOUSAND CIRCULAR MILS

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MH METAL HALIDE

MIN MINIMUM

MLO MAIN LUGS ONLY

MTD MOUNTED

MTR MOTOR

MTS MANUAL TRANSFER SWITCH

NEC NATIONAL ELECTRIC CODE

NF NON-FUSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NC NORMALLY CLOSED

P POLE, POLES

PF POWER FACTOR

PNL PANEL

PRI PRIMARY

PVC POLYVINYL CHLORIDE CONDUIT

PWR POWER

PH PHASE

Ø PHASE

R REMOVE

RR REMOVE AND RELOCATE

RL RELOCATED

RECEPT RECEPTACLE

RGS RIGID GALVANIZED STEEL CONDUIT

RMC RIGID METALLIC CONDUIT

SEC SECONDARY

SUSP SUSPEND, SUSPENDED

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TBB TELECOMMUNICATIONS BACKBOARD

TMH TELECOMMUNICATIONS MAN HOLE

THH TELECOMMUNICATIONS HAND HOLE

TYP. TYPICAL

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION

UON UNLESS OTHERWISE NOTED

V VOLT, VOLTS

VA VOLT-AMPERES

VAV VARIABLE AIR VOLUME

WT WATERTIGHT

W WATT OR WIRE

WP WEATHER PROOF

XFMR TRANSFORMER

MISCELLANEOUS

LINE TYPES

JUNCTION BOX WITH COVER

(MINIMUM 4" SQUARE OR AS

REQUIRED)

CONCRETE BOLLARD

SINGLE PORT PEDESTAL TYPE

ELECTRIC VEHICLE CHARGING STATION

DUAL PORT PEDESTAL TYPE

ELECTRIC VEHICLE CHARGING STATION

T

TRANSFORMER. "F" DENOTES FRONT

OF TRANSFORMER.

DIGITAL MULTI-METERDMM

UNDERGROUND PULL BOX

POST AND SIGNAGE

WHEELSTOP

SURFACE MOUNTED JUNCTION BOX

WITH COVER

(MINIMUM 4" SQUARE OR AS

REQUIRED)

ELECTRICAL GENERAL NOTES

PB

APPLICABLE CODES

J

J

PB SURFACE-MOUNTED PULL BOX

F

FENCE

2022 CALIFORNIA BUILDING CODE (CBC) PART 2, VOLUMES

1 AND 2, TITLE 24

(BASED ON 2021 INTERNATIONAL BUILDING CODE)

2022 CALIFORNIA ELECTRIC CODE (CEC) PART 3, TITLE 24

(BASED ON 2020 NATIONAL ELECTRIC CODE)

2022 CALIFORNIA FIRE CODE (CFC) PART 9, TITLE 24

(BASED ON 2021 INTERNATIONAL FIRE CODE)

2022 CALIFORNIA ENERGY CODE PART 6, TITLE 24

2022 CALIFORNIA REFERENCED STANDARD CODE PART 12,

TITLE 24

TITLE 19, PUBLIC SAFETY, STATE FIRE MARSHAL

REGULATIONS

2010 ADA STANDARDS FOR ACCESSIBLE DESIGN

PARTIAL LIST OF APPLICABLE NATIONAL FIRE PROTECTION

ASSOCIATION (NFPA) STANDARDS

NFPA 72, 2022 EDITION - NATIONAL FIRE ALARM AND

SIGNALING CODE (AMENDED BY CSFM)

NFPA 80, 2019 EDITION - FIRE DOORS AND OTHER OPENING

PROTECTIVES

REFER TO 2022 CBC CHAPTER 35 FOR ADDITIONAL

STANDARDS NOT PROVIDED ON THIS LIST

1. CONTRACTOR SHALL PERFORM INSTALLATION WORK IN CONFORMANCE WITH THE 2022 EDITION OF THE CALIFORNIA ELECTRICAL CODE (CEC) AND ALL APPLICABLE CODES, ORDINANCES, AND REGULATIONS.

2. CONDUIT ROUTING AND EQUIPMENT LOCATION AS SHOWN ON THE ELECTRICAL POWER PLAN ARE DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL VERIFY FEASIBILITY OF THE INSTALLATION BEFORE COMMENCING THE JOB. ANY OBSERVATIONS TO THE EXECUTION OF THE WORK SHALL BE BROUGHT TO THE

ATTENTION OF THE ENGINEER OF RECORD IMMEDIATELY.

3. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER CONSTRUCTION TRADES. CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE OF ANY UNRESOLVED ISSUES THAT MAY DELAY INSTALLATION OF

WORK.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING PROPER WORKING SPACE PER CALIFORNIA

ELECTRICAL CODE (CEC), PARAGRAPH 110-26.

5. CONTRACTOR SHALL PROVIDE NECESSARY HARDWARE AND SUPPORTS AS REQUIRED FOR ELECTRICAL CONDUIT/WIRE NOT SCHEDULED FOR DEMOLITION PER CALIFORNIA ELECTRICAL CODE (CEC), PARAGRAPH 110-12.

6. THE SEISMIC BRACING AND ANCHORAGE OF ELECTRICAL CONDUITS SHALL BE IN ACCORDANCE WITH THE

CALIFORNIA BUILDING CODE, CHAPTER 16.

7. CONNECTIONS TO VIBRATING EQUIPMENT AND SEISMIC SEPARATIONS:

· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN DRY INTERIOR LOCATIONS.

· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN AREAS EXPOSED TO WEATHER, DAMP LOCATIONS, CONNECTIONS TO TRANSFORMER ENCLOSURES, AND FINAL CONNECTIONS TO MOTORS.

PROVIDE A SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTOR IN FLEXIBLE CONDUIT RUNS.

MAXIMUM LENGTH SHALL BE SIX FEET UNLESS OTHERWISE NOTED.

8. WHENEVER A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE, EQUIPMENT DEVICES, CIRCUIT BREAKERS, GROUND FAULT PROTECTION SYSTEMS, ETC. (ALL MATERIALS), ARISES ON THE DRAWINGS OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE

SPECIFICATIONS TO ENSURE COMPLETE AND OPERABLE SYSTEMS.

9. ARC-FLASH LABELS SHALL BE PROVIDED FOR THE CONTRACTOR TO INSTALL ON NEW LOW VOLTAGE (480 V, 208 V, 120 V) SYSTEMS REPRESENTED ON THE PROJECT DRAWINGS. THIS INCLUDES SWITCHBOARDS, PANEL BOARDS, TRANSFORMERS, DISCONNECT SWITCHES AND OTHER REQUIRED ELECTRICAL EQUIPMENT. THESE LABELS SERVE AS A GUIDE TO ASSIST THE EMPLOYEES AND OTHERS IN THE SELECTION OF PROPER PERSONAL

PROTECTIVE EQUIPMENT WHEN WORKING AROUND EXPOSED AND ENERGIZED CONDUCTORS.

Drawn by:

Job No.:

PA / PM:

Description of RevisionsByDate #

Sheet Title/Number

Scale:

Date:

REVISIONS

th

S tr e e t E a st

P e a rb lo ss o m

C A

E. Torres

E. Burtch

As Noted

D e p a rt m e n t o f W a te r R e s o u rc e s

P e a rb lo s s o m

O M

C e n te r E V S E I n s ta lla ti o n

125-01-02.65

09/29/2025

V2

255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com

DSA IDENTIFICATION STAMP:

CALOF I

G I

R E

NG

A

E

S

No. E17083

T

E

ET

S

AT

L

CE A

F

RIC

L

ORN

I

E

PR

RAET

RE

D D.D

OF ONA

B R

L

SSI

N E

RE

IW

D

U

T

HC

E

CSFM APPLICATION NUMBER: 25-S-3435-C

95% CD SubmittalEB05/28/2025 1

100% CD SubmittalEB09/02/2025 2

SYMBOLS,

DESIGNATION AND

ABBREVIATIONS

E0.01

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/03/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3435

CALOF I

G I

RE

NG

A

E

S

No. E17083

T E

ET

S

AT L CE A

F

R I C

L

ORNI

E

PR

RAET

RE

D D.D

OF ONA

B R L

SSI

NE

RE

IWD

U

T

HC

E

Exp. 9-30-27

Electric Vehicle Supply Equipment - Pearblossom O&M Center

FIRE SAFETY PLAN - CONSTRUCTION

1. NAME AND CONTACT INFORMATION OF SITE SAFETY DIRECTOR:

KEVIN PARGETT

ASSOCIATE SAFETY ENGINEER

SOUTHERN FIELD DIVISION

OFFICE: (661) 944-8577

CELL: (661) 383-3001

2. DOCUMENTATION OF THE TRAINING OF THE SITE SAFETY DIRECTOR AND FIRE WATCH PERSONNEL:

· FIRE EXTINGUISHER TRAINING

· ARC FLASH AWARENESS

· HAZARD ASSESSMENT & MITIGATION CSWP 1.06

· INJURY ILLNESS PREVENTION PLAN

· PERSONAL PROTECTIVE EQUIPMENT

· WORKPLACE SAFETY

· INCIDENT INVESTIGATION AWARENESS

· PROTECTIVE GROUNDING

· STANDARDIZED EMERGENCY MANAGEMENT SYSTEM (SEMS)

· NATIONAL EMERGENCY MANAGEMENT SYSTEM (NEMS)

3. PROCEDURES FOR REPORTING EMERGENCIES:

THIS INFORMATION WAS PROVIDED FROM THE SJFC EAP REDBOOK.

ANY FIRE WILL BE REPORTED TO THE OFFICE OF THE STATE FIRE MARSHAL. ANY FIRE ON STATE PROPERTY OR IN FACILITIES IS CONSIDERED A RESPONSE LEVEL SITUATION AND THE FIRE EVENT ACTIONS CHECKLIST OF THE EMERGENCY ACTION PLAN WILL BE FOLLOWED. THE AREA CONTROL CENTER (ACC) WILL BE NOTIFIED OF

AN INCIDENT. WHEN NOTIFYING ACC TRY TO DETERMINE AND DOCUMENT THE FOLLOWING:

1. TYPE AND TIME OF INCIDENT

2. LOCATION OF FIRE - EXTERNAL OR INTERNAL, DISTANCE FROM STRUCTURES, SIZE, PROXIMITY TO

POWER LINERS

3. WEATHER CONDITIONS, WIND SPEED/DIRECTION

4. INFORMATION ON INJURY OR FATALITY

5. EQUIPMENT AFFECTED

6. NAME AND CONTACT FOR PERSONNEL REPORTING

THE ACC WILL RECORD THE INFORMATION IN THE OPERATIONS LOG. THE ACC WILL THEN RUN THE EAP

CHECKLIST.

REFERENCES AND ORDERS THAT PERTAIN TO FIRES: STANDARD OPERATION ORDER (SOO) PC 600.36 REPORTING OF FIRES OR EXPLOSIONS. SJFD S00 18 PROTOCOL FOR ENTERING SJFD FACILITY WHEN SOKE IS

PRESENT. PLANT AND SITE-SPECIFIC CONTINGENCE PLANS.

4. FIRE DEPARTMENT VEHICLE ACCESS ROUTES:

SEE MAP ON SHEET E0.03.

CONSTRUCTION SITE SHALL BE READILY ACCESSIBLE BY FIRE DEPARTMENT APPARATUS BY MEANS OF ROADWAYS HAVING AN ALL-WEATHER DRIVING SERVICE OF NOT LESS THAN 20 FEET OF UNOBSTRUCTED WIDTH. THE ROADS SHALL WITHSTAND LIVE LOADS OF FIRE APPARATUS, AND HAVE A MINIMUM OF 13 FEED, 6 INCHES OF VERTICAL CLEARANCE. DEAD END FIRE ACCESS ROADS IN EXCESS OF 150 FEET IN LENGTH SHALL

BE PROVIDED WITH APPROVED TURNAROUNDS.

5. LOCATION OF FIRE PROTECTION EQUIPMENT, INCLUDING PORTABLE FIRE EXTINGUISHERS, STANDPIPES, FIRE

DEPARTMENT CONNECTIONS AND FIRE HYDRANTS:

SEE MAP ON PLANS.

6. SMOKING AND COOKING POLICIES, DESIGNATED AREAS TO BE USED WHERE APPROVED, AND SIGNAGE

LOCATIONS IN ACCORDANCE WITH SECTION 3305.8:

N/A (NO SMOKING OR COOKING ALLOWED ON PREMISES)

7. LOCATION AND SAFETY CONSIDERATIONS FOR TEMPORARY HEATING EQUIPMENT:

N/A (NO TEMPORARY HEATING EQUIPMENT FOR THIS PROJECT)

8. HOT WORK PERMIT PLAN:

N/A (NO HOT WORK FOR THIS PROJECT. ALL WELDING ON FENCING AND GATES SHALL BE SHOP FABRICATED

BEFORE INSTALLATION ON SITE).

9. PLANS FOR CONTROL OF COMBUSTIBLE WASTE MATERIAL:

ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIAL, SUCH AS WOOD, PLASTIC, INSULATION, PAINTS AND VARNISHES, ADHESIVES AND SEALANTS, DUST, AND DEBRIS SHALL BE REMOVED FROM THE WORK SITE AT THE END OF EACH WORK SHIFT OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS. MATERIALS SUSCEPTIBLE TO SPONTANEOUS IGNITION, SUCH AS OILY RAGS, SHALL BE STORED IN A LISTED DISPOSAL CONTAINER. YARD STORAGE OF EQUIPMENT TO BE INSTALLED OR COMBUSTIBLE CONSTRUCTION MATERIALS

SHALL NOT BE STORES CLOSER THEN 30 FEET FROM ANY STRUCTURE UNDER CONSTRUCTION OR

ALTERATION.

10. LOCATIONS AND METHODS FOR STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS AND OTHER

HAZARDOUS MATERIALS:

STORAGE - FLAMMABLE AND COMBUSTIBLE LIQUID STORAGE AREAS SHALL BE MAINTAINED CLEAR OF COMBUSTIBLE VEGETATION AND WASTE MATERIALS. SUCH STORAGE AREAS SHALL NOT BE USED FOR THE STORAGE OF COMBUSTIBLE MATERIALS. SMOKING AND OTHER SOURCES OF IGNITION SHALL BE PROHIBITED IN AREAS WHERE FLAMMABLE AND COMBUSTIBLE LIQUIDS ARE STORED OR USED. STORAGE OF CLASS I AND CLASS II LIQUIDS SHALL NOT EXCEED 60 GALLONS WITHIN 50 FEET OF THE STRUCTURE UNLESS APPROVED BY

KERN COUNTY FD.

TANKS - TANKS AND CONTAINERS FOR THE STORAGE OF LIQUIDS ABOVE GROUND SHALL BE CONSPICUOUSLY MARKED WITH THE NAME OF THE PRODUCT THEY CONTAIN AND THE WORDS: "FLAMMABLE--KEEP FIRE AND FLAME AWAY." TANKS SHALL BEAR THE ADDITIONAL MARKING: "KEEP 50 FEET FROM BUILDINGS." A. TANKS MORE THAN 100 GALLONS IN CAPACITY, WHICH ARE PERMANENTLY INSTALLED OR MOUNTED AND USED FOR THE STORAGE OF CLASS I, II OR III LIQUIDS, SHALL BE PROVIDED WITH A PLACARD IN ACCORDANCE WITH NFPA 704.B. PORTABLE FIRE EXTINGUISHERS WITH A MINIMUM RATING OF 20-B:C SHALL BE PROVIDED WITHIN 30 FEET

OF THE TANK.

HANDLING AT POINT OF FINAL USE - THE STORAGE, USE AND HANDLING OF FLAMMABLE AND COMBUSTIBLE LIQUIDS AT CONSTRUCTION SITES SHALL BE IN ACCORDANCE WITH CFC SECTION 5706.2. VENTILATION SHALL BE PROVIDED FOR OPERATIONS INVOLVING THE APPLICATION OF MATERIALS CONTAINING FLAMMABLE SOLVENTS. CLASS I AND CLASS II LIQUIDS SHALL BE KEPT IN APPROVED SAFETY CONTAINERS, LEAKAGE AND SPILLS - LEAKING VESSELS SHALL BE IMMEDIATELY REPAIRED OR TAKEN OUT OF SERVICE AND SPILLS SHALL BE CLEANED UP AND DISPOSED OF PROPERLY. PROVISIONS FOR SITE SECURITY.

APPLICABLE CODES

STANDARD ADMINISTRATIVE CODE:

· 2022 CALIFORNIA BUILDING CODE (CBC)

· 2022 CALIFORNIA ELECTRICAL CODE (CEC)

· 2022 CALIFORNIA MECHANICAL CODE (CMC)

· 2022 CALIFORNIA PLUMBING CODE (CPC)

· 2022 CALIFORNIA ENERGY CODE

· 2022 CALIFORNIA FIRE CODE

· 2022 CALIFORNIA GREEN BUILDING CODE

· 2022 CALIFORNIA REFERENCE STANDARD CODE

· CCR-TITLE 19 PUBLIC SAFETY: DIVISION 1 STATE FIRE MARSHAL

· 2016 NFPA 13 INSTALLATION OF FIRE SPRINKLER

· 2013 NFPA 14 INSTALLATION OF STANDPIPE AND HOSE SYSTEM

· 2016 NFPA 20 INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION

· 2016 NFPA 24 INSTALLATION OF PRIVATE FIRE SERVICES MAINS AND THEIR APPURTENANCE

· 2006 NFPA CALIFORNIA EDITION, INSPECTION, TESTING AND MAINTENANCE OF WATER BASED FIRE

PROTECTION SYSTEMS

· 2016 NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE "AS AMENDED BY CALIFORNIA" CSF

SCALE

FIRE ACCESS ROUTES 1

N.T.S.

LOCATION OF

SECONDARY ENTRANCE

WITH GUARD SHACK

LOCATION OF MAIN ENTRANCE

WITH GUARD SHACK AND KNOX

BOX FOR FIRE DEPARTMENT

ACCESS.

Drawn by:

Job No.:

PA / PM:

Description of RevisionsByDate #

Sheet Title/Number

Scale:

Date:

REVISIONS

th

S tr e e t E a st

P e a rb lo ss o m

C A

E. Torres

E. Burtch

As Noted

D e p a rt m e n t o f W a te r R e s o u rc e s

P e a rb lo s s o m

O M

C e n te r E V S E I n s ta lla ti o n

125-01-02.65

09/29/2025

V2

255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com

DSA IDENTIFICATION STAMP:

CALOF I

G I

R E

NG

A

E

S

No. E17083

T

E

ET

S

AT

L

CE A

F

RIC

L

ORN

I

E

PR

RAET

RE

D D.D

OF ONA

B R

L

SSI

N E

RE

IW

D

U

T

HC

E

CSFM APPLICATION NUMBER: 25-S-3435-C

95% CD SubmittalEB05/28/2025 1

100% CD SubmittalEB09/02/2025 2

SITE SAFETY

PLAN

E0.02

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/03/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3435

CALOF I

G I

RE

NG

A

E

S

No. E17083

T E

ET

S

AT L CE A

F

R I C

L

ORNI

E

PR

RAET

RE

D D.D

OF ONA

B R L

SSI

NE

RE

IWD

U

T

HC

E

Exp. 9-30-27

Electric Vehicle Supply Equipment - Pearblossom O&M Center

SCALE

WATER OPS BUILDING FIRE EXTINGUISHER LOCATIONS 2

N.T.S.

SCALE

WATER OPS BUILDING FIRE EXTINGUISHER LOCATIONS 1

N.T.S.

Drawn by:

Job No.:

PA / PM:

Description of RevisionsByDate #

Sheet Title/Number

Scale:

Date:

REVISIONS

th

S tr e e t E a st

P e a rb lo ss o m

C A

E. Torres

E. Burtch

As Noted

D e p a rt m e n t o f W a te r R e s o u rc e s

P e a rb lo s s o m

O M

C e n te r E V S E I n s ta lla ti o n

125-01-02.65

09/29/2025

V2

255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com

DSA IDENTIFICATION STAMP:

CALOF I

G I

R E

NG

A

E

S

No. E17083

T

E

ET

S

AT

L

CE A

F

RI C

L

ORN

I

E

PR

RAET

RE

D D.D

OF ONA

B R

L

SSI

N E

RE

IW

D

U

T

HC

E

CSFM APPLICATION NUMBER: 25-S-3435-C

95% CD SubmittalEB05/28/2025 1

100% CD SubmittalEB09/02/2025 2

WATER OPS BUILDING

SITE SAFETY PLANS

E0.03

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/03/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3435

CALOF I

G I

RE

NG

A

E

S

No. E17083

T E

ET

S

AT L CE A

F

R I C

L

ORNI

E

PR

RAET

RE

D D.D

OF ONA

B R L

SSI

NE

RE

IWD

U

T

HC

E

Exp. 9-30-27

Electric Vehicle Supply Equipment - Pearblossom O&M Center

O&M CENTER FIRE EXTINGUISHER AND FIRE ACCESS LOCATIONS 2

N.T.S.

SCALE

O&M CENTER FIRE EXTINGUISHER AND FIRE HYDRANT LOCATIONS 1

N.T.S.

Drawn by:

Job No.:

PA / PM:

Description of RevisionsByDate #

Sheet Title/Number

Scale:

Date:

REVISIONS

th

S tr e e t E a st

P e a rb lo ss o m

C A

E. Torres

E. Burtch

As Noted

D e p a rt m e n t o f W a te r R e s o u rc e s

P e a rb lo s s o m

O M

C e n te r E V S E I n s ta lla ti o n

125-01-02.65

09/29/2025

V2

255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com

DSA IDENTIFICATION STAMP:

CALOF I

G I

R E

NG

A

E

S

No. E17083

T

E

ET

S

AT

L

CE A

F

RI C

L

ORN

I

E

PR

RAET

RE

D D.D

OF ONA

B R

L

SSI

N E

RE

IW

D

U

T

HC

E

CSFM APPLICATION NUMBER: 25-S-3435-C

95% CD SubmittalEB05/28/2025 1

100% CD SubmittalEB09/02/2025 2

O&M CENTER

SITE SAFETY PLANS

E0.04

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/03/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3435

CALOF I

G I

RE

NG

A

E

S

No. E17083

T E

ET

S

AT L CE A

F

R I C

L

ORNI

E

PR

RAET

RE

D D.D

OF ONA

B R L

SSI

NE

RE

IWD

U

T

HC

E

Exp. 9-30-27

Electric Vehicle Supply Equipment - Pearblossom O&M Center

PUMPING PLANT FIRE ACCESS LOCATIONS 2

N.T.S.

SCALE

PUMPING PLANT FIRE EXTINGUISHER AND FIRE HYDRANT LOCATIONS 1

N.T.S.

Drawn by:

Job No.:

PA / PM:

Description of RevisionsByDate #

Sheet Title/Number

Scale:

Date:

REVISIONS

th

S tr e e t E a st

P e a rb lo ss o m

C A

E. Torres

E. Burtch

As Noted

D e p a rt m e n t o f W a te r R e s o u rc e s

P e a rb lo s s o m

O M

C e n te r E V S E I n s ta lla ti o n

125-01-02.65

09/29/2025

V2

255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com

DSA IDENTIFICATION STAMP:

CALOF I

G I

R E

NG

A

E

S

No. E17083

T

E

ET

S

AT

L

CE A

F

RI C

L

ORN

I

E

PR

RAET

RE

D D.D

OF ONA

B R

L

SSI

N E

RE

IW

D

U

T

HC

E

CSFM APPLICATION NUMBER: 25-S-3435-C

95% CD SubmittalEB05/28/2025 1

100% CD SubmittalEB09/02/2025 2

PUMPING PLANT

SITE SAFETY PLANS

E0.05

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/03/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3435

CALOF I

G I

RE

NG

A

E

S

No. E17083

T E

ET

S

AT L CE A

F

R I C

L

ORNI

E

PR

RAET

RE

D D.D

OF ONA

B R L

SSI

NE

RE

IWD

U

T

HC

E

Exp. 9-30-27

Electric Vehicle Supply Equipment - Pearblossom O&M Center

SITE PLAN 1

1/64" = 1'-0"

Drawn by:

Job No.:

PA / PM:

Description of RevisionsByDate #

Sheet Title/Number

Scale:

Date:

REVISIONS

th

S tr e e t E a st

P e a rb lo ss o m

C A

E. Torres

E. Burtch

As Noted

D e p a rt m e n t o f W a te r R e s o u rc e s

P e a rb lo s s o m

O M

C e n te r E V S E I n s ta lla ti o n

125-01-02.65

09/29/2025

V2

255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com

DSA IDENTIFICATION STAMP:

CALOF I

G I

R E

NG

A

E

S

No. E17083

T

E

ET

S

AT

L

CE A

F

RIC

L

ORN

I

E

PR

RAET

RE

D D.D

OF ONA

B R

L

SSI

N E

RE

IW

D

U

T

HC

E

CSFM APPLICATION NUMBER: 25-S-3435-C

95% CD SubmittalEB05/28/2025 1

100% CD SubmittalEB09/02/2025 2

SITE PLAN

E1.00

E2.00

E2.02

E2.01

PUMPING PLANT

O&M CENTER

WATER OPS

BUILDING

PROPOSED EV CHARGERS

EVCS #

WALL/PEDESTAL

MOUNT EVCS

SINGLE/DUAL

EVCS

CHARGE PORT #

POWER SELECT

(FLA)

VOLTAGE

POWER SHARE

(Y / N/A)

CHARGE PORT

TYPE

WATER OPS BUILDING

1 PEDESTAL DUAL 30 240V-1PH N/A FLEET

2 PEDESTAL DUAL 30 240V-1PH N/A FLEET

O&M CENTER

3 PEDESTAL DUAL 30 208V-1PH N/A FLEET

4 PEDESTAL DUAL 30 208V-1PH N/A FLEET

5 PEDESTAL DUAL 30 208V-1PH N/A FLEET

6 PEDESTAL SINGLE 30 208V-1PH N/A FLEET

7 PEDESTAL DUAL 30 208V-1PH N/A FLEET

8 PEDESTAL DUAL 30 208V-1PH N/A FLEET

9 PEDESTAL DUAL 30 208V-1PH N/A FLEET

10 PEDESTAL DUAL 30 208V-1PH N/A FLEET

11 PEDESTAL DUAL 30 208V-1PH N/A FLEET

12 PEDESTAL DUAL 30 208V-1PH N/A FLEET

PUMPING PLANT

13 PEDESTAL DUAL 30 208V-1PH N/A FLEET

14 PEDESTAL SINGLE 30 208V-1PH N/A FLEET

15 PEDESTAL SINGLE 30 208V-1PH N/A FLEET

NOTES:

· (12) DUAL PORT AND (3) SINGLE PORT EVCS SHALL SERVE (27) FLEET PARKING STALLS

· (FLA) STANDS FOR FULL LOAD AMPS

· (Y) STANDS FOR, YES WILL BE REQUIRED; (N/A) STANDS FOR, NOT APPLICABLE

NOTE FOR FLEET EVCS:

FLEET EVCS INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO

COMPLY WITH CBC 11B-228.3.2 ACCESS REQUIREMENTS.

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/03/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3435

CALOF I

G I

RE

NG

A

E

S

No. E17083

T E

ET

S

AT L CE A

F

R I C

L

ORNI

E

PR

RAET

RE

D D.D

OF ONA

B R L

SSI

NE

RE

IWD

U

T

HC

E

Exp. 9-30-27

Electric Vehicle Supply Equipment - Pearblossom O&M Center

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

(E) UTILITY POLE WITH METER

& DISCONNECT SWITCH

(E) SWITCHBOARD

PB

4 8

(E) ASPHALT

PAVEMENT

(E) ASPHALT

PAVEMENT

(E) VISITOR OVERLOOK

PARKING LOT (E) FENCE

(E) EDGE OF

ASPHALT PAVEMENT

(E) EDGE OF

ASPHALT PAVEMENT

2 8

2 8

PANELBOARD "EV-1"

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

APPROXIMATE LOCATION OF

(E) SEPTIC TANK

PANELBOARD "EV-1"

DIGITAL MULTI-METER

PB

4'-0"

(TYP.)

3'-0"

(TYP.)

1'-2" (TYP.)

EVCS-1 1 5 6 8

EVCS-2 1 5

1'-0"

(TYP.)

19'-0"

(TYP.)

9'-0"

(TYP.)

1"C - 4#6 & 1#8GRD.

(E) CONCRETE

12 (TYP.)

9 (TYP.)

11 (TYP.) 10 (TYP.)

2 TO (E) DISCONNECT

SWITCH

(E) ASPHALT

PAVEMENT

4'-0"

(TYP.)

(E) EDGE OF

ASPHALT PAVEMENT

(E) EDGE OF

ASPHALT PAVEMENT

2 8

SCALE

ENLARGED POWER PLAN 2

1/4"=1'=0"

Drawn by:

Job No.:

PA / PM:

Description of RevisionsByDate #

Sheet Title/Number

Scale:

Date:

REVISIONS

th

S tr e e t E a st

P e a rb lo ss o m

C A

E. Torres

E. Burtch

As Noted

D e p a rt m e n t o f W a te r R e s o u rc e s

P e a rb lo s s o m

O M

C e n te r E V S E I n s ta lla ti o n

125-01-02.65

09/29/2025

V2

255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com

DSA IDENTIFICATION STAMP:

CALOF I

G I

R E

NG

A

E

S

No. E17083

T

E

ET

S

AT

L

CE A

F

RIC

L

ORN

I

E

PR

RAET

RE

D D.D

OF ONA

B R

L

SSI

N E

RE

IW

D

U

T

HC

E

CSFM APPLICATION NUMBER: 25-S-3435-C

95% CD SubmittalEB05/28/2025 1

100% CD SubmittalEB09/02/2025 2

WATER OPS

BUILDING

POWER PLANS

E2.00

SHEET NOTES:

DUAL PORT PEDESTAL TYPE EVCS WITH 7,200VA

PER PORT. PROVIDE 10'-0" OF FEEDER WIRE (4#6

+ 1#8 GRD) COILED UP AT EVCS STUB-UP

LOCATION FOR FINAL EVCS INSTALLATION. SEE

DETAIL #1 ON SHEET E4.00.

SEE DETAIL #3 SHEET E4.00 FOR UNDERGROUND

CONDUIT BURIAL DETAIL. FOR ALL ROUTING

THROUGH TRAFFIC CROSSINGS PROVIDE

SCHEDULE 80 PVC UNDERGROUND CONDUIT.

PROVIDE 17" X 30" X DEPTH AS REQUIRED

CONCRETE PULL BOX WITH WEATHERPROOF

COVER ENGRAVED 'POWER'. SEE DETAIL #6

SHEET E4.00 FOR UNDERGROUND PULL BOX

DETAIL.

DEMOLISH AND REPLACE EXISTING FUSES IN

DISCONNECT SWITCH WITH NEW 200A FUSES.

SEE DETAIL #4 SHEET E4.00 FOR EV CHARGING

STATION PVC CONDUIT STUB-UP DETAIL.

SEE DETAIL #5 SHEET E4.00 FOR ELECTRIC

EQUIPMENT RGS CONDUIT STUB-UP DETAIL.

PROVIDE DIGITAL MULTI-METER IN NEMA-3R

ENCLOSURE FOR MONITORING PANEL "EV-1"

INCOMING FEEDERS. REFER TO DETAIL #7 ON

SHEET E4.00 FOR MORE INFORMATION.

SEE SINGLE LINE DIAGRAM #1 SHEET E5.00 FOR

MORE INFORMATION.

RELOCATED WHEELSTOP. REFER TO CIVIL

DRAWINGS FOR INSTALLATION INFORMATION.

NEW 4" DIA. CONCRETE BOLLARD. REFER TO

DETAIL #5 ON SHEET E4.01.

NEW SIGN AND POST. REFER TO CIVIL

DRAWINGS FOR MORE INFORMATION.

NEW STRIPING. REFER TO CIVIL DRAWINGS FOR

MORE INFORMATION.

VERIFY EXACT LOCATIONS OF SEPTIC TANK IN

FIELD PRIOR TO START OF WORK.

PROVIDE CONNECTION TO NEW GROUND ROD.

REFER TO DETAIL #9 ON SHEET E4.01.

GENERAL NOTES:

1. ELECTRICAL ENGINEERING FOR THIS PROJECT

IS BASED ON A FIELD VISIT OF THE ELECTRICAL

SYSTEM. IN CASE OF ANY DISCREPANCIES WITH

EXISTING FIELD CONDITIONS, ELECTRICAL

CONTRACTOR SHALL VERIFY THE EXACT

DIFFERENCES AND NOTIFY THE ELECTRICAL

ENGINEER FOR POSSIBLE REVISION TO THESE

DOCUMENTS.

2. ANY ELECTRICAL AND/OR SIGNAL UTILITY

SHUTDOWNS WITHIN THE AREA OF WORK SHALL

BE COORDINATED AND SCHEDULED IN ADVANCE

WITH THE SITE'S REPRESENTATIVE.

3. ELECTRIC VEHICLE CHARGING STATION/S

(EVCS) SHALL BE PROVIDED, INSTALLED AND

CONNECTED BY STATE VENDOR.

4. PROVIDE MINIMUM OF 1'-0" CLEARANCE BEHIND

ALL PEDESTAL MOUNTED CHARGERS FOR

SERVICING. CONTRACTOR SHALL FIELD VERIFY

ALL DISTANCES PRIOR TO BID.

5. EXISTING VEGETATION TO BE REMOVED,

PROTECTED AND RESTORED AFTER

CONSTRUCTION.

6. REMOVE AND REPLACE EXISTING IN-GROUND

LANDSCAPING AND IRRIGATION LINES

AFFECTED IN WORK.

R

CALL 811 BEFORE YOU DIG.

SCALE

WATER OPS BUILDING POWER PLAN 1

1/16"=1'=0"

2 TO PANEL "EV-1" & EV

CHARGING STATIONS

LEGEND:

EXISTING

NEW

NEW UNDERGROUND

BUILDING INFORMATION: WATER OPS BUILDING

CONSTRUCTION TYPE: N/A*

OCCUPANCY CLASSIFICATION: N/A*

OCCUPANCY LOAD: N/A*

ACTUAL BUILDING HEIGHT: N/A*

BUILDING AREA (SQ. FT.) N/A*

AREA OF PROJECT (SQ. FT.) 4,300 SQ. FT.

SEPARATED OR NON-SEPARATED USE: N/A*

ALLOWABLE AREA: N/A*

AREA INCREASED: NONE

HEIGHT INCREASED: NONE

FIRE SPRINKLERS: N/A*

FIRE ALARM: N/A*

OTHER FIRE PROTECTION SYSTEMS: N/A*

SMOKE CONTROL SYSTEM: N/A*

YEAR CONSTRUCTED: N/A*

HIGH FIRE SEVERITY ZONE: NO

SEISMIC JOINTS: NO

EMERGENCY RESPONDER RADIO COVERAGE: NO

*ALL WORK AT THE BUILDING IS EXTERIOR. NO INTERIOR WORK.

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/03/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3435

CALOF I

G I

RE

NG

A

E

S

No. E17083

T E

ET

S

AT L CE A

F

R I C

L

ORNI

E

PR

RAET

RE

D D.D

OF ONA

B R L

SSI

NE

RE

IWD

U

T

HC

E

Exp. 9-30-27

Electric Vehicle Supply Equipment - Pearblossom O&M Center

ONLY

EV

FLEET

ONLY EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

T

(E) ASPHALT

PAVEMENT

TO PANEL "EV-2" & EV

CHARGING STATIONS

PB

(E) CONCRETE

CURB

(E) GENERATOR

(E) MAIN SWITCHBOARD "MSS"

(E) M.V. TRANSFORMER

(E) ASPHALT

PAVEMENT

3 11

PB

PB

ENCLOSED CIRCUIT

BREAKER

19 (TYP.)

SEE GENERAL

NOTES 5 & 6

EV

FLEET

ONLY

EV

FLEET

ONLY EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

EV

FLEET

ONLY

T

PB

PB

PB

(E) ASPHALT

PAVEMENT

9'-0"

(TYP.)

20'-0"

(TYP.)

18'-0"

(TYP.)

9'-0"

(TYP.)

1'-0"

(TYP.)

3'-0"

(TYP.)

3'-0"

(TYP.)

4'-0"

(TYP.)

TRANSFORMER "TEV-2"

(E) CONCRETE

CURB

(E) AREA LIGHT

(E) EDGE OF

ASPHALT PAVEMENT

(E) CONCRETE

CURB

(E) ASPHALT

PAVEMENT

(E) LANDSCAPE

AREA

(E) CONCRETE

CURB

(E) STRIPING

(E) PULLBOX

DIGITAL MULTI-METER

PANELBOARD "EV-2"

TO MAIN

SWITCHBOARD "MSS"

8 11

9 11 8

3'-0"

(TYP.)

4'-0"

(TYP.)

1'-0"

(TYP.)

EVCS-12 1 7

1"C - 4#6

& 1#8GRD.

(2 SETS) 1"C - 4#6

& 1#8GRD.

(3 SETS) 1"C - 4#6

& 1#8GRD.

(5 SETS) 1"C - 4#6

& 1#8GRD.

(7 SETS) 1"C - 4#6

& 1#8GRD.

(9 SETS) 1"C - 4#6

& 1#8GRD.

EVCS-8 1 7

EVCS-6 1 7

EVCS-5 1 7

EVCS-37 2

EVCS-4

15 (TYP.)

14 (TYP.)

16 (TYP.)

17 (TYP.)

15(TYP.)

DISCONNECT SWITCH8 11

3'-0"

(TYP.)

PB

PB

EVCS-7 1 7

EVCS-9 1 7

EVCS-10 1 7

EVCS-11 1 7

SHEET NOTES:

DUAL PORT PEDESTAL TYPE EVCS WITH 7,200VA

PER PORT. PROVIDE 10'-0" OF FEEDER WIRE (4#6

+ 1#8 GRD) COILED UP AT EVCS STUB-UP

LOCATION FOR FINAL EVCS INSTALLATION. SEE

DETAIL #1 ON SHEET E4.00.

SINGLE PORT PEDESTAL TYPE EVCS WITH

7,200VA PER PORT. PROVIDE 10'-0" OF FEEDER

WIRE (2#6 + 1#10 GRD) COILED UP AT EVCS

STUB-UP LOCATION FOR FINAL EVCS

INSTALLATION. SEE DETAIL #2 ON SHEET E4.00.

SEE DETAIL #3 SHEET E4.00 FOR UNDERGROUND

CONDUIT BURIAL DETAIL. FOR ALL ROUTING

THROUGH TRAFFIC CROSSINGS PROVIDE

SCHEDULE 80 PVC UNDERGROUND CONDUIT.

PROVIDE 17" X 30" X DEPTH AS REQUIRED

CONCRETE PULL BOX WITH WEATHERPROOF

COVER ENGRAVED 'POWER'. SEE DETAIL #6

SHEET E4.00 FOR UNDERGROUND PULL BOX

DETAIL.

PROVIDE 13" X 24" X DEPTH AS REQUIRED

CONCRETE PULL BOX WITH WEATHERPROOF

COVER ENGRAVED 'POWER'. SEE DETAIL #6

SHEET E4.00 FOR UNDERGROUND PULL BOX

DETAIL.

PROVIDE 11" X 17" X DEPTH AS REQUIRED

CONCRETE PULL BOX WITH WEATHERPROOF

COVER ENGRAVED 'POWER'. SEE DETAIL #6

SHEET E4.00 FOR UNDERGROUND PULL BOX

DETAIL.

SEE DETAIL #4 SHEET E4.00 FOR EV CHARGING

STATION PVC CONDUIT STUB-UP DETAIL.

SEE DETAIL #5 SHEET E4.00 FOR ELECTRIC

EQUIPMENT RGS CONDUIT STUB-UP DETAIL.

SEE DETAILS #1, #2 & #3 SHEET E4.01 FOR

TRANSFORMER GROUNDING DETAILS.

PROVIDE DIGITAL MULTI-METER IN NEMA-3R

ENCLOSURE FOR MONITORING PANEL "EV-2"

FEEDERS. REFER TO DETAIL #7 ON SHEET E4.00

FOR MORE INFORMATION.

SEE SINGLE LINE DIAGRAM #2 SHEET E5.00 FOR

MORE INFORMATION.

PENETRATION THROUGH CMU CONCRETE WALL

WALL. PROVIDE 12" X 12" X 8" NEMA 3R PULL BOX

TO TRANSITION THROUGH WALL. REFER TO

DETAIL #6 ON SHEET E4.01.

PROVIDE 12" X 12" X 8" NEMA-3R PULL BOX.

RELOCATED WHEELSTOP. REFER TO CIVIL

DRAWINGS FOR INSTALLATION INFORMATION.

NEW 4" DIA. CONCRETE BOLLARD. REFER TO

DETAIL #5 ON SHEET E4.01.

NEW SIGN AND POST. REFER TO CIVIL

DRAWINGS FOR MORE INFORMATION.

REMOVE EXISTING STRIPING AND REPLACE

WITH NEW STRIPING. REFER TO CIVIL DRAWINGS

FOR MORE INFORMATION.

PENETRATION THROUGH CMU CONCRETE WALL

WALL FOR (2) 2" CONDUITS. PROVIDE 16" X 16" X

8" NEMA 3R PULL BOX TO TRANSITION THROUGH

WALL. REFER TO DETAIL #7 ON SHEET E4.01.

RGS CONDUIT SURFACE MOUNTED TO EXISTING

WALL. REFER TO DETAIL #8 ON SHEET E4.01.

EXISTING FOLIAGE TO REMAIN AND BE

PROTECTED IN PLACE.

LEGEND:

EXISTING

NEW

NEW UNDERGROUND

SCALE

ENLARGED POWER PLAN 2

3/16"=1'=0"

Drawn by:

Job No.:

PA / PM:

Description of RevisionsByDate #

Sheet Title/Number

Scale:

Date:

REVISIONS

th

S tr e e t E a st

P e a rb lo ss o m

C A

E. Torres

E. Burtch

As Noted

D e p a rt m e n t o f W a te r R e s o u rc e s

P e a rb lo s s o m

O M

C e n te r E V S E I n s ta lla ti o n

125-01-02.65

09/29/2025

V2

255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com

DSA IDENTIFICATION STAMP:

CALOF I

G I

R E

NG

A

E

S

No. E17083

T

E

ET

S

AT

L

CE A

F

RI C

L

ORN

I

E

PR

RAET

RE

D D.D

OF ONA

B R

L

SSI

N E

RE

IW

D

U

T

HC

E

CSFM APPLICATION NUMBER: 25-S-3435-C

95% CD SubmittalEB05/28/2025 1

100% CD SubmittalEB09/02/2025 2

O&M CENTER

POWER PLANS

E2.01

R

CALL 811 BEFORE YOU DIG.

SCALE

O&M CENTER POWER PLAN 1

3/32"=1'=0"

GENERAL NOTES:

1. ELECTRICAL ENGINEERING FOR THIS PROJECT

IS BASED ON A FIELD VISIT OF THE ELECTRICAL

SYSTEM. IN CASE OF ANY DISCREPANCIES WITH

EXISTING FIELD CONDITIONS, ELECTRICAL

CONTRACTOR SHALL VERIFY THE EXACT

DIFFERENCES AND NOTIFY THE ELECTRICAL

ENGINEER FOR POSSIBLE REVISION TO THESE

DOCUMENTS.

2. ANY ELECTRICAL AND/OR SIGNAL UTILITY

SHUTDOWNS WITHIN THE AREA OF WORK SHALL

BE COORDINATED AND SCHEDULED IN ADVANCE

WITH THE SITE'S REPRESENTATIVE.

3. ELECTRIC VEHICLE CHARGING STATION/S

(EVCS) SHALL BE PROVIDED, INSTALLED AND

CONNECTED BY STATE VENDOR.

4. PROVIDE MINIMUM OF 1'-0" CLEARANCE BEHIND

ALL PEDESTAL MOUNTED CHARGERS FOR

SERVICING. CONTRACTOR SHALL FIELD VERIFY

ALL DISTANCES PRIOR TO BID.

5. EXISTING FOLIAGE TO BE REMOVED,

PROTECTED AND RESTORED AFTER

CONSTRUCTION.

6. REMOVE AND REPLACE EXISTING IN-GROUND

FOLIAGE AND IRRIGATION LINES AFFECTED IN

WORK.

BUILDING INFORMATION: O&M CENTER

CONSTRUCTION TYPE: N/A*

OCCUPANCY CLASSIFICATION: N/A*

OCCUPANCY LOAD: N/A*

ACTUAL BUILDING HEIGHT: N/A*

BUILDING AREA (SQ. FT.) N/A*

AREA OF PROJECT (SQ. FT.) 8,500 SQ. FT.

SEPARATED OR NON-SEPARATED USE: N/A*

ALLOWABLE AREA: N/A*

AREA INCREASED: NONE

HEIGHT INCREASED: NONE

FIRE SPRINKLERS: N/A*

FIRE ALARM: N/A*

OTHER FIRE PROTECTION SYSTEMS: N/A*

SMOKE CONTROL SYSTEM: N/A*

YEAR CONSTRUCTED: N/A*

HIGH FIRE SEVERITY ZONE: NO

SEISMIC JOINTS: NO

EMERGENCY RESPONDER RADIO COVERAGE: NO

*ALL WORK AT THE BUILDING IS EXTERIOR. NO INTERIOR WORK.

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/03/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3435

CALOF I

G I

RE

NG

A

E

S

No. E17083

T E

ET

S

AT L CE A

F

R I C

L

ORNI

E

PR

RAET

RE

D D.D

OF ONA

B R L

SSI

NE

RE

IWD

U

T

HC

E

Exp. 9-30-27

Electric Vehicle Supply Equipment - Pearblossom O&M Center

E V

F L E E T

O N L Y

E V

F L E E T

O N L Y

E V

F L E E T

O N L Y

E V

F L E E T

O N L Y

T

(E) ROLL-UP GARAGE

DOOR

(E) ASPHALT

PAVEMENT

(E) LOUVER

(E) LOUVER

(E) MOTOR CONTROL

CENTER "PWB"

(E) EQUIPMENT

AREA

(E) LOUVER

(E) EQUIPMENT

(E) BOLLARD (E) BOLLARD

(E) HOSE BIB

PB

(E) AREA LIGHT

(E) CONDUIT

SUPPORT

(E) CONDUIT

SUPPORT

(E) CONDUIT

SUPPORT

(E) DRAINAGE

CHANNEL

(E) DRAINAGE

CHANNEL

(E) LOUVER

(E) LOUVER

PB

PB

PANELBOARD "EV-3"

TRANSFORMER

"TEV-3"

DIGITAL MULTI-METER

EVCS-13 7 1

EVCS-14 2 7

EVCS-15 2 7

1"C - 4#6 & 1#8GRD.

1"C - 2#6 & 1#10GRD.

1"C - 2#6 & 1#10GRD. 3

6 (TYP.)

11(TYP.)

10(TYP.)

12(TYP.)

13(TYP.)

9'-0"

(TYP.)

18'-0"

(TYP.)

3'-0" (TYP.)

1'-0" (TYP.)

1'-0" (TYP.)

(E) CONDUIT

SUPPORT

4'-0"

(TYP.)

(E) DRAINAGE

CHANNEL

SCALE

PUMPING PLANT POWER PLAN 1

1/4"=1'=0"

Drawn by:

Job No.:

PA / PM:

Description of RevisionsByDate #

Sheet Title/Number

Scale:

Date:

REVISIONS

th

S tr e e t E a st

P e a rb lo ss o m

C A

E. Torres

E. Burtch

As Noted

D e p a rt m e n t o f W a te r R e s o u rc e s

P e a rb lo s s o m

O M

C e n te r E V S E I n s ta lla ti o n

125-01-02.65

09/29/2025

V2

255 East Rincon St., Suite 301

Corona, CA 92879

P 951.340.1977 | F 951.340.1090 www.gossengineering.com

DSA IDENTIFICATION STAMP:

CALOF I

G I

R E

NG

A

E

S

No. E17083

T

E

ET

S

AT

L

CE A

F

RI C

L

ORN

I

E

PR

RAET

RE

D D.D

OF ONA

B

R L

SSI

N E

RE

IW

D

U

T

HC

E

CSFM APPLICATION NUMBER: 25-S-3435-C

95% CD SubmittalEB05/28/2025 1

100% CD SubmittalEB09/02/2025 2

PUMPING PLANT

POWER PLANS

E2.02

SHEET NOTES:

DUAL PORT PEDESTAL TYPE EVCS WITH 7,200VA

PER PORT. PROVIDE 10'-0" OF FEEDER WIRE (4#6

+ 1#8 GRD) COILED UP AT EVCS STUB-UP

LOCATION FOR FINAL EVCS INSTALLATION. SEE

DETAIL #1 ON SHEET E4.00.

SINGLE PORT PEDESTAL TYPE EVCS WITH

7,200VA PER PORT. PROVIDE 10'-0" OF FEEDER

WIRE (2#6 + 1#10 GRD) COILED UP AT EVCS

STUB-UP LOCATION FOR FINAL EVCS

INSTALLATION. SEE DETAIL #2 ON SHEET E4.00.

SEE DETAIL #3 SHEET E4.00 FOR UNDERGROUND

CONDUIT BURIAL DETAIL. FOR ALL ROUTING

THROUGH TRAFFIC CROSSINGS PROVIDE

SCHEDULE 80 PVC UNDERGROUND CONDUIT.

PENETRATION THROUGH CMU CONCRETE WALL

WALL. PROVIDE 10" X 10" X 8" NEMA 3R PULL BOX

TO TRANSITION THROUGH WALL. REFER TO

DETAIL #4 ON SHEET E4.01.

PROVIDE 10" X 10" X 8" NEMA-1 PULL BOX.

SURFACE MOUNTED CONDUIT SHALL BE

PAINTED TO MATCH EXISTING SURFACE.

SEE DETAIL #4 SHEET E4.00 FOR EV CHARGING

STATION PVC CONDUIT STUB-UP DETAIL.

PROVIDE DIGITAL MULTI-METER IN NEMA-1

ENCLOSURE FOR MONITORING PANEL "EV-3"

INCOMING FEEDERS. REFER TO DETAIL #7 ON

SHEET E4.00 FOR MORE INFORMATION.

SEE SINGLE LINE DIAGRAM #1 SHEET E5.01 FOR

MORE INFORMATION.

NEW STRIPING. REFER TO CIVIL DRAWINGS FOR

MORE INFORMATION.

NEW WHEELSTOP. REFER TO CIVIL DRAWINGS

FOR INSTALLATION INFORMATION.

NEW 4" DIA. CONCRETE BOLLARD. REFER TO

DETAIL #5 ON SHEET E4.01.

NEW SIGN AND POST. REFER TO CIVIL

DRAWINGS FOR MORE INFORMATION.

EMT CONDUIT SURFACE MOUNTED TO EXISTING

WALL. REFER TO DETAIL #8 ON SHEET E4.01.

R

CALL 811 BEFORE YOU DIG.

GENERAL NOTES:

1. ELECTRICAL ENGINEERING FOR THIS PROJECT

IS BASED ON A FIELD VISIT OF THE ELECTRICAL

SYSTEM. IN CASE OF ANY DISCREPANCIES WITH

EXISTING FIELD CONDITIONS, ELECTRICAL

CONTRACTOR SHALL VERIFY THE EXACT

DIFFERENCES AND NOTIFY THE ELECTRICAL

ENGINEER FOR POSSIBLE REVISION TO THESE

DOCUMENTS.

2. ANY ELECTRICAL AND/OR SIGNAL UTILITY

SHUTDOWNS WITHIN THE AREA OF WORK SHALL

BE COORDINATED AND SCHEDULED IN ADVANCE

WITH THE SITE'S REPRESENTATIVE.

3. ELECTRIC VEHICLE CHARGING STATION/S

(EVCS) SHALL BE PROVIDED, INSTALLED AND

CONNECTED BY STATE VENDOR.

4. PROVIDE MINIMUM OF 1'-0" CLEARANCE BEHIND

ALL PEDESTAL MOUNTED CHARGERS FOR

SERVICING. CONTRACTOR SHALL FIELD VERIFY

ALL DISTANCES PRIOR TO BID.

LEGEND:

EXISTING

NEW

NEW UNDERGROUND

BUILDING INFORMATION: PUMPING PLANT

EQUIPMENT BUILDING

CONSTRUCTION TYPE: II-A

OCCUPANCY CLASSIFICATION: F-1

OCCUPANCY LOAD: 11

ACTUAL BUILDING HEIGHT: 15 FT.

BUILDING AREA (SQ. FT.) 1,100 SQ. FT.

AREA OF PROJECT (SQ. FT.) 2,500 SQ. FT.

SEPARATED OR NON-SEPARATED USE: NON-SEPARATED

ALLOWABLE AREA: 25,000

AREA INCREASED: NONE

HEIGHT INCREASED: NONE

FIRE SPRINKLERS: NO

FIRE ALARM: YES

OTHER FIRE PROTECTION SYSTEMS: YES

SMOKE CONTROL SYSTEM: NO

YEAR CONSTRUCTED: 1973

HIGH FIRE SEVERITY ZONE: NO

SEISMIC JOINTS: NO

EMERGENCY RESPONDER RADIO COVERAGE: NO

PREVIOUS OSFM PROJECT NO: 22-S-4796-C

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/03/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3435

CALOF I

G I

RE

NG

A

E

S

No. E17083

T E

ET

S

AT L CE A

F

R I C

L

ORNI

E

PR

RAET

RE

D D.D

OF ONA

B R L

SSI

NE

RE

IWD

U

T

HC

E

Exp. 9-30-27

Electric Vehicle Supply Equipment - Pearblossom O&M Center

EMERGENCY SHUT-OFF LABEL DETAIL 8

N.T.S.

4"

3"

RED BACKGROUND

WITH WHITE LETTERING

RED STRIPING

WHITE STRIPING

6"

MIN.

STEEL COUPLING WITH

THREADED PLUG

FINISH GRADE

PVC CONDUIT

TRANSITION

COUPLING

CONTINUOUS RIGID GALVANIZED

STEEL CONDUIT WRAPPED AROUND

WITH 10 MIL. BLACK ELECTRICAL

PLASTIC INSULATING TAPE TO 6"

ABOVE FINISH GRADE

CONTINUOUS RIGID

GALVANIZED STEEL

CONDUIT

BEND RADIUS

R = 10 x DIA. OF CONDUIT

(MINIMUM)

PROVIDE BUSHING

WHEN PULLING

CONDUCTORS

NOTE:

1. LABEL SHALL BE PROVIDED FOR ALL NEW EV CHARGING STATIONS SHOWN ON THESE DRAWINGS. LABEL SHALL

CORRESPOND WITH CHARGER NUMBER AND THE ASSOCIATED PANELBOARD PROVIDING POWER.

2. SEE BELOW FOR LABEL SPECIFICATIONS:

· MATERIAL: THERMAL PRINTED ON REFLECTIVE RED OUTDOOR LABEL STOCK (MEETS ASTMD 4956-99)

· COLOR: WHITE TEXT ON RED BACKGROUND WITH RED AND WHITE ALTERNATING STRIPES

· DAMAGE RESISTANT FROM COMMON CHEMICALS AND SOLVENTS.

· MINIMUM SERVICE TEMPERATURE: -40 DEG FAHRENHEIT

· MAXIMUM SERVICE TEMPERATURE: 180 DEG FAHRENHEIT

· APPLICATION TEMPERATURE: 50 DEG FAHRENHEIT

· FILM THICKNESS: 5.5 MIL

· ADHESIVE THICKNESS: 1 MIL

SCALE

ELECTRICAL EQUIPMENT RGS CONDUIT STUB-UP DETAIL 5

N.T.S.

SCALE

UNDERGROUND CONDUIT BURIAL DETAIL 3

N.T.S.

3" OF SLURRY

BELOW

CONDUIT

1" MIN. SPACING. SHALL BE EQUAL

TO THE LARGEST CONDUIT SIZE

FOR MULTIPLE CONDUIT RUNS.

NEW ASPHALT PAVEMENT EXISTING ASPHALT PAVEMENT

EXISTING BASE

CRUSHED AGGREGATE BASE

RECOMPACTED TO 95%

RELATIVE COMPACTION

ELECTRICAL

WARNING TAPE

4 SACK SLURRY

1'-0"

MIN.

GRADE LEVEL

2'-0"

MIN.

ELECTRICAL

WARNING TAPE

3" CLEAN SAND

BEDDING

NOTE:

PER CEC 300.5 NO CONCRETE CASING IS

REQUIRED IF SCHEDULE 80 PVC IS USED

2'-0" BELOW GRADE LEVEL. SEE POWER

PLAN FOR MORE INFORMATION

1" MIN. SPACING. SHALL BE EQUAL

TO THE LARGEST CONDUIT SIZE

FOR MULTIPLE CONDUIT RUNS.

3" CLEAN SAND

BEDDING

NATIVE BACKFILL

90% COMPACTION

ASPHALT PAVEMENT

APPLICATION

NATIVE SOIL APPLICATION

CONDUIT/S PER PLAN

CONDUIT/S PER PLAN

SCALE

EV CHARGING STATION PVC CONDUIT STUB-UP DETAIL 4

N.T.S.

1'-6" MIN.

FINISH GRADE

PVC CONDUIT

COUPLING

PVC CONDUIT

BEND RADIUS

R = 10 x DIA. OF CONDUIT

(MINIMUM)

PROVIDE BUSHING

WHEN PULLING

CONDUCTORS

PVC COUPLING WITH

THREADED PLUG

PVC CONDUIT

1'-0"

MIN.

2'-0"

MIN.

MATCH

EXISTING +1"

MATCH

EXISTING

+1"

SCALE

DUAL PORT PEDESTAL ELECTRIC VEHICLE CHARGING STATION 1

N.T.S.

NEW CONCRETE EVCS

FOOTING. SEE STRUCTURAL

DRAWINGS FOR MORE

INFORMATION.

FRONT

ELEVATION

SIDE

ELEVATION

4'-0"

MAX.

FINISH GRADE

1" PVC CONDUIT

4#6 & 1#8 GRD.

DUAL PORT PEDESTAL

EV CHARGING STATION

(7,200VA PER PORT)

PROVIDE 1'-6" PVC CONDUIT

STUB-UP WITH CONDUIT

PLUG AND GROUNDING

BUSHING. REFER TO

CONDUIT STUB UP DETAIL #4

ON THIS SHEET.

PROVIDE LABEL IDENTIFYING

SHUT-OFF LOCATION. LABEL SHALL

CORRESPOND TO CHARGER NUMBER.

REFER TO DETAIL #8 ON THIS SHEET.

NOTE:

1. FOR PEDESTAL TYPE EVCS INFORMATION - REFER TO INSTALLATION INSTRUCTIONS PER MANUFACTURER.

2. DUAL PORT CHARGING STATION SHALL BE PROVIDED AND INSTALLED BY CURRENT STATE VENDOR. CONTRACTOR SHALL PROVIDE INFRASTRUCTURE NECESSARY TO SUPPORT THE CHARGER AS SHOWN ON THESE DRAWINGS.

SCALE

UNDERGROUND PULL BOX DETAIL 6

N.T.S.

GRAVEL

BASE

ELECTRICAL

CONDUIT(S)

(IN/OUT)

CONCRETE STEEL

REINFORCED

BOLT DOWN LID

12" DEEP REINFORCED

CONCRETE NON-TRAFFIC

PULL BOX

(EXTEND AS REQUIRED)

FINISH GRADE

COMPACTED

BACKFILL

(TYPICAL)

ELECTRICAL

CONDUIT(S)

(IN/OUT)

2'-0"

MIN.

NOTE:

REFER TO SHEET NOTES ON POWER

PLANS FOR SPECIFIC PULL BOX

DIMENSIONS.

SCALE

SINGLE PORT PEDESTAL ELECTRIC VEHICLE CHARGING STATION 2

N.T.S.

NEW CONCRETE EVCS

FOOTING. SEE STRUCTURAL

DRAWINGS FOR MORE

INFORMATION.

FRONT

ELEVATION

SIDE

ELEVATION

4'-0"

MAX.

FINISH GRADE

1" PVC CONDUIT

2#6 & 1#10 GRD.

SINGLE PORT PEDESTAL

EV CHARGING STATION

(7,200VA PER PORT)

PROVIDE 1'-6" PVC CONDUIT

STUB-UP WITH CONDUIT

PLUG AND GROUNDING

BUSHING. REFER TO

CONDUIT STUB UP DETAIL #4

ON THIS SHEET.

PROVIDE LABEL IDENTIFYING

SHUT-OFF LOCATION. LABEL SHALL

CORRESPOND TO CHARGER NUMBER.

REFER TO DETAIL #8 ON THIS SHEET.

NOTE:

1. FOR PEDESTAL TYPE EVCS INFORMATION - REFER TO INSTALLATION INSTRUCTIONS PER MANUFACTURER.

2. SINGLE PORT CHARGING STATION SHALL BE PROVIDED AND INSTALLED BY CURRENT STATE VENDOR. CONTRACTOR SHALL PROVIDE INFRASTRUCTURE NECESSARY TO SUPPORT THE CHARGER AS SHOWN ON THESE DRAWINGS.

VIN

I1 I2 I3 I4

DIGITAL MULTI-METER

WITH NEMA-3R

ENCLOSURE

3/4"C - 3#12

& 1#12 GRD.

PANELBOARD

SCALE

DIGITAL MULTI-METER DETAIL 7

N.T.S.

(TYP.)3

2" A.F.F.

2" A.F.F.

NOTES:

PROVIDE DIGITAL MULTI-METER WITH CAPABILITIES OF MONITORING

EVCS BRANCH CIRCUITS. METER SHALL BE CAPABLE OF

MONITORING KHW, MAX PEAK DEMAND AMPS AND VOLTAGE.

PROVIDE IN-LINE FUSES PER MANUFACTURER'S INSTALLATION

MANUAL.

PROVIDE CURRENT TRANSFORMERS TO MONITOR ALL EVCS BRANCH

CIRCUITS. REFER TO SINGLE LINE ON SHEET E5.00 FOR MORE

INFORMATION.

VERIFY POWER CONNECTIONS WITH MANUFACTURER'S

INSTALLATION MANUAL.

Drawn by:

Job No.:

PA / PM:

Description of RevisionsByDate #

Sheet Title/Number

Scale:

Date:

REVISIONS

th

S tr e e t E a st

P e a rb lo ss o m

C A

E. Torres

E. Burtch

As Noted

D e p a rt m e n t o f W a te r R e s o u rc e s

P e a rb lo s s o m

O M

C e n te r E V S E I n s ta lla ti o n

125-01-02.65

09/29/2025

V2

255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com

DSA IDENTIFICATION STAMP:

CALOF I

G I

R E

NG

A

E

S

No. E17083

T

E

ET

S

AT

L

CE A

F

RIC

L

ORN

I

E

PR

RAET

RE

D D.D

OF ONA

B R

L

SSI

N E

RE

IW

D

U

T

HC

E

CSFM APPLICATION NUMBER: 25-S-3435-C

95% CD SubmittalEB05/28/2025 1

100% CD SubmittalEB09/02/2025 2

ELECTRICAL

DETAILS

E4.00

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/03/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25…