Plans.pdf
PDF 21 MB Posted
- Solicitation number
- 0000037345
About this file
File Summary
This is a set of 100% construction drawings and specifications for the Electric Vehicle Supply Equipment (EVSE) installation project at the Department of Water Resources Pearblossom O&M Center, prepared by Goss Engineering, Inc. in coordination with Proactive Engineering Consultants, MRP Planning Co., and the Office of Sustainability at the California Department of General Services. The project involves installation of EVSE infrastructure to provide power to 27 electric vehicle charging station (EVCS) ports across three facility locations: Water Ops Building (2 ports), O&M Center (10 ports), and Pumping Plant (3 ports). The scope includes three panelboards, two transformers, two disconnect switches, new feeder conduits, structural and civil work, and comprehensive electrical and fire safety systems. The project received approval from the Office of the State Fire Marshal on October 3, 2025, with the sealed bid deadline set for December 30, 2025, at 2:00 P.M. Bids are to be submitted to the DGS/OBAS Bid/Proposal Drop Box at 707 Third Street, West Sacramento, California. The project encompasses approximately 14,300 square feet of work area across the three locations and requires a C-10 contractor license. All charging stations are designated for authorized fleet vehicles only and are not available to the general public, with final EVCS installation and terminations to be performed by the State's designated electric vehicle charging station vendor.
The project requires compliance with the 2022 California Building Code, California Electrical Code, California Fire Code, and applicable NFPA standards. Third-party testing is required for all new feeder conductors, and special inspections are mandated for reinforcing steel, concrete placement, and post-installed anchorage per CBC Sections 1704 and 1705. The drawings include detailed fire safety plans identifying emergency access routes, fire extinguisher locations, fire hydrants, and emergency procedures at each facility location. Structural details encompass transformer and disconnect switch anchorage, bollard installation, panel board and digital multimeter mounting specifications, and rebar development length schedules. The project is funded by the State of California and administered under Contract 25-286288, Project 13263. Contractors must provide proof of valid Certificates of Reported Compliance (CRC) for any off-road diesel-fueled fleet vehicles used on the project. All work must maintain minimum 72-hour notice requirements for facility disruptions and coordinate closely with site operations to minimize impact to DWR personnel and operations.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Project_Manual.pdf | ||
| Bid_Package.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROACTIVE ENGINEERING CONSULTANTS
27051 TOWNE CENTRE DRIVE, SUITE 270
FOOTHILL RANCH, CA 92610
(949) 716-7460
CONTACT: FELIX GONZALEZ
MRP PLANNING CO.
130 CENTENNIAL WAY, UNIT C,
TUSTIN, CA 92780
(714) 923-8946
CONTACT: MIKE PAAR
Department of Water Resources
Pearblossom O&M Center EVSE Installation
100% Construction Drawings
LOCATION MAP
NOT TO SCALE
INDEX OF DRAWINGS
SCOPE OF WORK
THE SCOPE OF THIS PROJECT CONSISTS OF THE INSTALLATION OF THE ELECTRIC
VEHICLE SUPPLY EQUIPMENT (EVSE) TO PROVIDE POWER TO (27) ELECTRIC VEHICLE
CHARGING STATION (EVCS) PORTS WITHIN THE DWR PEARBLOSSOM O&M CENTER.
SEE EVCS NOTE ON THIS SHEET.
THE ELECTRIC VEHICLE SUPPLY EQUIPMENT IS MADE UP OF (3) PANELBOARDS, (2)
TRANSFORMERS AND (2) DISCONNECT SWITCHES AS WELL AS NEW FEEDERS TO THE
EVCS PORTS LOCATIONS AS SHOWN ON THESE PLANS. PROJECT INCLUDES
STRUCTURAL AND CIVIL WORK EFFORT/S NECESSARY TO SUPPORT THIS PROJECT.
SEE SHEET E1.00 FOR A SUMMARY OF THE EVCS PORTS.
ALL EVSE INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE
INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC
SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO COMPLY
WITH CBC 11B-228.3.2 ACCESS REQUIREMENTS.
ALTHOUGH THE CONTRACTOR MAY NOT PROCURE OR PERFORM THE FINAL
INSTALLATION OF THE EVSE, SUCH WORK IS WITHIN THE PERMIT SCOPE AND MAY BE
PERFORMED BY OTHERS.
ALL WORK PERTAINING TO AND ALL MATERIALS SUPPLIED FOR EXECUTING AND
COMPLETING THIS CONTRACT SHALL COMPLY WITH PROVISIONS SPECIFIED IN THE
CONTRACT DOCUMENTS AND WITH ALL APPLICABLE LAWS, REGULATIONS AND
ORDINANCES GOVERNING WORK INCLUDING, BUT NOT NECESSARILY LIMITED TO
THOSE OF THE APPLICABLE CODES LISTED ON SHEET E0.01.
SHEET COUNT DWG. NO. DESCRIPTION
1 OF 25 T0.01 TITLE SHEET, LOCATION MAP, GENERAL NOTES &
SHEET INDEX
2 OF 25 E0.01 SYMBOLS, DESIGNATION AND ABBREVIATIONS
3 OF 25 E0.02 SITE SAFETY PLAN
4 OF 25 E0.03 WATER OPS BUILDING SITE SAFETY PLANS
5 OF 25 E0.04 O&M CENTER SITE SAFETY PLANS
6 OF 25 E0.05 PUMPING PLANT SITE SAFETY PLANS
7 OF 25 E1.00 SITE PLAN
8 OF 25 E2.00 WATER OPS BUILDING POWER PLANS
9 OF 25 E2.01 O&M CENTER POWER PLANS
10 OF 25 E2.02 PUMPING PLANT POWER PLANS
11 OF 25 E4.00 ELECTRICAL DETAILS
12 OF 25 E4.01 ELECTRICAL DETAILS
13 OF 25 E5.00 SINGLE LINE DIAGRAMS
14 OF 25 E5.01 SINGLE LINE DIAGRAM
15 OF 25 E5.02 PANEL SCHEDULES
16 OF 25 C1 TITLE SHEET
17 OF 25 C2 SITE PLAN
18 OF 25 C3 SITE PLAN
19 OF 25 C4 SITE PLAN
20 OF 25 S0.01 GENERAL NOTES
21 OF 25 S0.02 SPECIAL INSPECTIONS
22 OF 25 S2.00 WATER OPS BUILDING ENLARGED EQUIPMENT
SUPPORT PLAN
23 OF 25 S2.01 O & M ENLARGED EQUIPMENT SUPPORT PLAN
24 OF 25 S2.02 WATER OPS BUILDING ENLARGED EQUIPMENT
SUPPORT PLAN
25 OF 25 S4.00 STRUCTURAL DETAILS
1. THE ARRANGEMENT OF THE EQUIPMENT, ELECTRICAL DEVICES, ETC. SHOWN ON THESE DRAWINGS IS GENERAL AND IS SHOWN TO IDENTIFY THE GENERAL INTENT OF THE PROJECT. ALL DETAILS AND ARRANGEMENTS SHALL BE VERIFIED PRIOR TO THE START OF WORK. THE DRAWINGS ARE NOT INTENDED TO SHOW EXACT DIMENSIONS/LOCATIONS.
2. CODE COMPLIANCE: ALL WORK SHALL CONFORM TO BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE CODES, STANDARDS, AND ORDINANCE AS SET FORTH BY THE AUTHORITIES HAVING JURISDICTION AND THEIR LATEST ADOPTED EDITIONS (IN EFFECT AT THE TIME OF THE BUILDING PERMIT APPLICATION) OF THE FOLLOWING PUBLICATIONS:
· CALIFORNIA CODE OF REGULATIONS TITLE 24: INCLUDES 2022 CALIFORNIA ELECTRICAL CODE, 2022 CALIFORNIA FIRE
CODE, 2022 CALIFORNIA BUILDING CODE, APPLICABLE YEARS OF NFPA ETC. WITH CALIFORNIA AND OTHER LOCAL
AMENDMENTS AS APPLICABLE.
· 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN.
3. SAFETY: THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO MAINTAIN ALL EQUIPMENT IN A SAFE AND RESPONSIBLE MANNER. KEEP DEAD FRONT EQUIPMENTS IN PLACE WHILE ENERGIZED. CONDUCT ALL CONSTRUCTION OPERATIONS IN A SAFE MANNER FOR EMPLOYEES AS WELL AS OTHER WORK PERSONS OR ANYONE VISITING THE JOB SITE. PROVIDE BARRIERS, FLAGS, TAPE, ETC. AS REQUIRED FOR SAFETY. THE CONTRACTOR SHALL HOLD ALL PARTIES HARMLESS OF
NEGLIGENT PRACTICES, WHICH MAY CAUSE INJURY TO OTHERS ON OR NEAR THE JOB SITE.
4. FIRE RATED ASSEMBLIES SHALL MAINTAIN RATINGS AS SPECIFIED IN THE CALIFORNIA BUILDING CODE, CHAPTER 7. ALL ASSEMBLIES TO BE PENETRATED SHALL BE INSTALLED WITH APPLICABLE THROUGH-PENETRATION FIRESTOP SYSTEM AS DETERMINED BY UL CLASSIFICATION. BEFORE CONSTRUCTION, VERIFY AND COMPLY WITH REQUIREMENTS.
5. PROVIDE THIRD-PARTY TESTING FOR ALL NEW FEEDER CONDUCTORS. BRANCH CIRCUITS ARE NOT REQUIRED TO BE
TESTED BY THIRD-PARTY. REFER TO PROJECT SPECIFICATIONS FOR MORE INFORMATION.
FOR EXISTING BUILDINGS:
1. ASBESTOS/LEAD PAINT: IF DURING THE COURSE OF WORK THE CONTRACTOR OBSERVES THE EXISTENCE OF ASBESTOS/LEAD PAINT, ASBESTOS BEARING MATERIALS, THE CONTRACTOR SHALL IMMEDIATELY TERMINATE FURTHER WORK ON THE PROJECT AND NOTIFY THE OWNER OF THE CONDITIONS. THE OWNER WILL, AFTER CONSULTATION WITH
THE OWNER'S REPRESENTATIVE, DETERMINE A FURTHER COURSE OF ACTION.
2. ANY DEMOLITION WORK SHOWN WAS PREPARED FOR THE CONVENIENCE OF THE CONTRACTOR. THE ENGINEER DOES NOT REPRESENT THAT ALL ITEMS WHICH MAY REQUIRE DEMOLITION HAVE BEEN SHOWN. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO CAREFULLY EXAMINE THE SITE AND CONTRACT DOCUMENTS AND TO PERFORM ALL DEMOLITION AND RECONSTRUCTION WHICH MAY BE REQUIRED FOR THE PROPER EXECUTION AND
COMPLETION OF THE WORK.
3. EXISTING CONDITIONS: INFORMATION SHOWN FOR EXISTING CONDITIONS WAS PRIMARILY GAINED FROM "AS-BUILT" DRAWINGS AND/OR LIMITED FIELD INVESTIGATION. BEFORE BID, VISIT SITE TO VERIFY EXISTING CONDITIONS AND MAKE
ALLOWANCE FOR VARIATION FROM THAT SHOWN.
4. CLOSELY COORDINATE OUTAGE AND FACILITY DISRUPTION TIME WITH OWNER. MINIMUM 72-HOURS NOTICE IS REQUIRED
BEFORE ANY CIRCUIT SHUTDOWN OR DISRUPTION OF FACILITY PERSONNEL FUNCTIONING.
GENERAL NOTES
EVCS NOTE:
ELECTRICAL VEHICLE CHARGING STATION
(EVCS) SHALL BE PROVIDED BY THE STATE
(DEPARTMENT OF GENERAL SERVICES), AND
INSTALLED BY THE CURRENT STATE ELECTRIC
VEHICLE CHARGING STATION VENDOR. ALL
FINAL TERMINATIONS AND/OR SPLICING FOR
THE EVCS SHALL BE THE RESPONSIBILITY AND
PERFORMED BY THE STATE VENDOR.
PROJECT TEAM
PROJECT DIRECTOR
STRUCTURAL ENGINEERCIVIL ENGINEER
ELECTRICAL ENGINEER
GOSS ENGINEERING, INC.
255 EAST RINCON STREET, SUITE 301,
CORONA, CA 92879
(951) 340-1977
CONTACT: ED BURTCH
R
CALL 811 BEFORE YOU DIG.
DGS PROJECT NUMBER: 000000000013263
ARC-FLASH NOTE:
ALL NEW ELECTRICAL SWITCHBOARDS, PANELBOARDS,
EQUIPMENT/DEVICES AND SUCH, SHALL BE PROVIDED WITH AN
ARC-FLASH HAZARD WARNING LABEL/MARKING, IN COMPLIANCE TO
THE REQUIREMENTS OF THE LATEST CEC 110.16. THE LABELS
SHALL BE GENERATED BY THE DESIGN TEAM AND INSTALLED BY
THE ELECTRICAL CONTRACTOR.
PROJECT
LOCATION
OFFICE OF SUSTAINABILITY, DGS
707 3RD STREET, 4TH FLOOR
WEST SACRAMENTO, CA 95606
(916) 823-7059
CONTACT: JANELLE GOULDING
OSFM APPLICATION NUMBERS:
PUMPING PLANT: 25-S-3435-C
WATER OPS BUILDING: 25-S-3997-C
O&M CENTER: 25-S-3998-C
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
th
S tr e e t E a st
P e a rb lo ss o m
C A
E. Torres
E. Burtch
As Noted
D e p a rt m e n t o f W a te r R e s o u rc e s
P e a rb lo s s o m
O M
C e n te r E V S E I n s ta lla ti o n
125-01-02.65
09/29/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B
R L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3435-C
95% CD SubmittalEB05/28/2025 1
100% CD SubmittalEB09/02/2025 2
TITLE SHEET, LOCATION
MAP, GENERAL NOTES &
SHEET INDEX
T0.01
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3435
22 OF 25 S2.00 WATER OPS BUILDING
ENLARGED EQUIPMENT SUPPORT PLAN
23 OF 25 S2.01 O & M CENTER
ENLARGED EQUIPMENT SUPPORT PLAN
24 OF 25 S2.02 PUMPING PLANT
ENLARGED EQUIPMENT SUPPORT PLAN
25 OF 25 S4.00 STRUCTURAL DETAILS
CALOF I
G I
RE
NG
A
E
S
No. E17083
T E
ET
S
AT L CE A
F
R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
Exp. 9-30-27
Electric Vehicle Supply Equipment - Pearblossom O&M Center PN: 000000000013263, Date: 11/21/25 http://www.gossengineering.com
ABBREVIATIONS
ANNOTATION SYMBOLS
LEGEND
WIRING SYSTEM ABOVE FLOOR
LEVEL, CONCEALED IN WALL OR
ABOVE CEILING UON
WIRING SYSTEM IN OR UNDER
FLOOR OR CONCEALED IN OR
BEHIND STRUCTURE OR EQUIPMENT
CONDUIT STUB ENDING WITH CAP
E0.1
REMOVE/RELOCATE/DEMOLISH
EXISTING
FUSE
RECESSED PANELBOARD 120V/208V
SWITCH
COMBINATION MOTOR
STARTER/DISCONNECT SWITCH
(NUMBER INDICATES STARTER SIZE)
DISCONNECT SWITCH (FUSED),
HORSE POWER RATED
SURFACE MOUNTED PANELBOARD
277V/480V
DISTRIBUTION BOARD
FUSED DISCONNECT SWITCH
RECESSED PANELBOARD 277V/480V
SURFACE MOUNTED PANELBOARD
120V/208V
DISCONNECT SWITCH (NON-FUSED)
ELECTRICAL
SYMBOL
DESCRIPTION
F
SHEET WHERE DETAIL
IS DRAWN
OCCURRENCE
DETAIL IDENTIFICATION
(TYP.)
DETAIL
RECONSTRUCTION KEY NOTE
DEMOLITION KEY NOTE
REVISION
REVISED AREA
REVISION TAG
A AMPERE
ADA AMERICAN DISABILITIES ACT
AC ALTERNATING CURRENT
AF AMPERE FRAME
AS AMPERE SWITCH
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING CAPACITY
ANN ANNUNCIATOR
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO-VISUAL
AWG AMERICAN WIRE GAUGE
BKR BREAKER
BLDG BUILDING
C CONDUIT
CB CIRCUIT BREAKER
CATV CABLE TELEVISION
CEC CALIFORNIA ELECTRICAL CODE
CKT CIRCUIT
CLG CEILING
CO CONDUIT ONLY
COMM COMMUNICATIONS
COMP COMPUTER
DB DISTRIBUTION BOARD
DISC DISCONNECT
DIST DISTRIBUTION
DL DOUBLE LUG
DP DISTRIBUTION PANEL
DWG DRAWING
E EXISTING TO REMAIN
EEOR ELECTRICAL ENGINEER ON RECORD
EG EQUIPMENT GROUND
ELEC ELECTRICAL
EMH ELECTRICAL MAN HOLE
EHH ELECTRICAL HAND HOLE
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
EV ELECTRIC VEHICLE
EVCS ELECTRIC VEHICLE CHARGING STATION
EVSE ELECTRIC VEHICLE SUPPLY EQUIPMENT
F FUSE, FUSED
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPERES
GRD GROUND
GALV GALVANIZE, GALVANIZED
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HPF HEAT PUMP HIGH POWER FACTOR
HPS HIGH PRESSURE SODIUM
JB JUNCTION BOX
KA THOUSAND AMPERES
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT-AMPERE
KW KILOWATT
LCL LONG CONTINUOUS LOAD
LTG LIGHTING
MC METAL CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM THOUSAND CIRCULAR MILS
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MH METAL HALIDE
MIN MINIMUM
MLO MAIN LUGS ONLY
MTD MOUNTED
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
NEC NATIONAL ELECTRIC CODE
NF NON-FUSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NC NORMALLY CLOSED
P POLE, POLES
PF POWER FACTOR
PNL PANEL
PRI PRIMARY
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
PH PHASE
Ø PHASE
R REMOVE
RR REMOVE AND RELOCATE
RL RELOCATED
RECEPT RECEPTACLE
RGS RIGID GALVANIZED STEEL CONDUIT
RMC RIGID METALLIC CONDUIT
SEC SECONDARY
SUSP SUSPEND, SUSPENDED
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TBB TELECOMMUNICATIONS BACKBOARD
TMH TELECOMMUNICATIONS MAN HOLE
THH TELECOMMUNICATIONS HAND HOLE
TYP. TYPICAL
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
UON UNLESS OTHERWISE NOTED
V VOLT, VOLTS
VA VOLT-AMPERES
VAV VARIABLE AIR VOLUME
WT WATERTIGHT
W WATT OR WIRE
WP WEATHER PROOF
XFMR TRANSFORMER
MISCELLANEOUS
LINE TYPES
JUNCTION BOX WITH COVER
(MINIMUM 4" SQUARE OR AS
REQUIRED)
CONCRETE BOLLARD
SINGLE PORT PEDESTAL TYPE
ELECTRIC VEHICLE CHARGING STATION
DUAL PORT PEDESTAL TYPE
ELECTRIC VEHICLE CHARGING STATION
T
TRANSFORMER. "F" DENOTES FRONT
OF TRANSFORMER.
DIGITAL MULTI-METERDMM
UNDERGROUND PULL BOX
POST AND SIGNAGE
WHEELSTOP
SURFACE MOUNTED JUNCTION BOX
WITH COVER
(MINIMUM 4" SQUARE OR AS
REQUIRED)
ELECTRICAL GENERAL NOTES
PB
APPLICABLE CODES
J
J
PB SURFACE-MOUNTED PULL BOX
F
FENCE
2022 CALIFORNIA BUILDING CODE (CBC) PART 2, VOLUMES
1 AND 2, TITLE 24
(BASED ON 2021 INTERNATIONAL BUILDING CODE)
2022 CALIFORNIA ELECTRIC CODE (CEC) PART 3, TITLE 24
(BASED ON 2020 NATIONAL ELECTRIC CODE)
2022 CALIFORNIA FIRE CODE (CFC) PART 9, TITLE 24
(BASED ON 2021 INTERNATIONAL FIRE CODE)
2022 CALIFORNIA ENERGY CODE PART 6, TITLE 24
2022 CALIFORNIA REFERENCED STANDARD CODE PART 12,
TITLE 24
TITLE 19, PUBLIC SAFETY, STATE FIRE MARSHAL
REGULATIONS
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
PARTIAL LIST OF APPLICABLE NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA) STANDARDS
NFPA 72, 2022 EDITION - NATIONAL FIRE ALARM AND
SIGNALING CODE (AMENDED BY CSFM)
NFPA 80, 2019 EDITION - FIRE DOORS AND OTHER OPENING
PROTECTIVES
REFER TO 2022 CBC CHAPTER 35 FOR ADDITIONAL
STANDARDS NOT PROVIDED ON THIS LIST
1. CONTRACTOR SHALL PERFORM INSTALLATION WORK IN CONFORMANCE WITH THE 2022 EDITION OF THE CALIFORNIA ELECTRICAL CODE (CEC) AND ALL APPLICABLE CODES, ORDINANCES, AND REGULATIONS.
2. CONDUIT ROUTING AND EQUIPMENT LOCATION AS SHOWN ON THE ELECTRICAL POWER PLAN ARE DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL VERIFY FEASIBILITY OF THE INSTALLATION BEFORE COMMENCING THE JOB. ANY OBSERVATIONS TO THE EXECUTION OF THE WORK SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER OF RECORD IMMEDIATELY.
3. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER CONSTRUCTION TRADES. CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE OF ANY UNRESOLVED ISSUES THAT MAY DELAY INSTALLATION OF
WORK.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING PROPER WORKING SPACE PER CALIFORNIA
ELECTRICAL CODE (CEC), PARAGRAPH 110-26.
5. CONTRACTOR SHALL PROVIDE NECESSARY HARDWARE AND SUPPORTS AS REQUIRED FOR ELECTRICAL CONDUIT/WIRE NOT SCHEDULED FOR DEMOLITION PER CALIFORNIA ELECTRICAL CODE (CEC), PARAGRAPH 110-12.
6. THE SEISMIC BRACING AND ANCHORAGE OF ELECTRICAL CONDUITS SHALL BE IN ACCORDANCE WITH THE
CALIFORNIA BUILDING CODE, CHAPTER 16.
7. CONNECTIONS TO VIBRATING EQUIPMENT AND SEISMIC SEPARATIONS:
· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN DRY INTERIOR LOCATIONS.
· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN AREAS EXPOSED TO WEATHER, DAMP LOCATIONS, CONNECTIONS TO TRANSFORMER ENCLOSURES, AND FINAL CONNECTIONS TO MOTORS.
PROVIDE A SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTOR IN FLEXIBLE CONDUIT RUNS.
MAXIMUM LENGTH SHALL BE SIX FEET UNLESS OTHERWISE NOTED.
8. WHENEVER A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE, EQUIPMENT DEVICES, CIRCUIT BREAKERS, GROUND FAULT PROTECTION SYSTEMS, ETC. (ALL MATERIALS), ARISES ON THE DRAWINGS OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE AND OPERABLE SYSTEMS.
9. ARC-FLASH LABELS SHALL BE PROVIDED FOR THE CONTRACTOR TO INSTALL ON NEW LOW VOLTAGE (480 V, 208 V, 120 V) SYSTEMS REPRESENTED ON THE PROJECT DRAWINGS. THIS INCLUDES SWITCHBOARDS, PANEL BOARDS, TRANSFORMERS, DISCONNECT SWITCHES AND OTHER REQUIRED ELECTRICAL EQUIPMENT. THESE LABELS SERVE AS A GUIDE TO ASSIST THE EMPLOYEES AND OTHERS IN THE SELECTION OF PROPER PERSONAL
PROTECTIVE EQUIPMENT WHEN WORKING AROUND EXPOSED AND ENERGIZED CONDUCTORS.
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
th
S tr e e t E a st
P e a rb lo ss o m
C A
E. Torres
E. Burtch
As Noted
D e p a rt m e n t o f W a te r R e s o u rc e s
P e a rb lo s s o m
O M
C e n te r E V S E I n s ta lla ti o n
125-01-02.65
09/29/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3435-C
95% CD SubmittalEB05/28/2025 1
100% CD SubmittalEB09/02/2025 2
SYMBOLS,
DESIGNATION AND
ABBREVIATIONS
E0.01
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3435
CALOF I
G I
RE
NG
A
E
S
No. E17083
T E
ET
S
AT L CE A
F
R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
Exp. 9-30-27
Electric Vehicle Supply Equipment - Pearblossom O&M Center
FIRE SAFETY PLAN - CONSTRUCTION
1. NAME AND CONTACT INFORMATION OF SITE SAFETY DIRECTOR:
KEVIN PARGETT
ASSOCIATE SAFETY ENGINEER
SOUTHERN FIELD DIVISION
OFFICE: (661) 944-8577
CELL: (661) 383-3001
2. DOCUMENTATION OF THE TRAINING OF THE SITE SAFETY DIRECTOR AND FIRE WATCH PERSONNEL:
· FIRE EXTINGUISHER TRAINING
· ARC FLASH AWARENESS
· HAZARD ASSESSMENT & MITIGATION CSWP 1.06
· INJURY ILLNESS PREVENTION PLAN
· PERSONAL PROTECTIVE EQUIPMENT
· WORKPLACE SAFETY
· INCIDENT INVESTIGATION AWARENESS
· PROTECTIVE GROUNDING
· STANDARDIZED EMERGENCY MANAGEMENT SYSTEM (SEMS)
· NATIONAL EMERGENCY MANAGEMENT SYSTEM (NEMS)
3. PROCEDURES FOR REPORTING EMERGENCIES:
THIS INFORMATION WAS PROVIDED FROM THE SJFC EAP REDBOOK.
ANY FIRE WILL BE REPORTED TO THE OFFICE OF THE STATE FIRE MARSHAL. ANY FIRE ON STATE PROPERTY OR IN FACILITIES IS CONSIDERED A RESPONSE LEVEL SITUATION AND THE FIRE EVENT ACTIONS CHECKLIST OF THE EMERGENCY ACTION PLAN WILL BE FOLLOWED. THE AREA CONTROL CENTER (ACC) WILL BE NOTIFIED OF
AN INCIDENT. WHEN NOTIFYING ACC TRY TO DETERMINE AND DOCUMENT THE FOLLOWING:
1. TYPE AND TIME OF INCIDENT
2. LOCATION OF FIRE - EXTERNAL OR INTERNAL, DISTANCE FROM STRUCTURES, SIZE, PROXIMITY TO
POWER LINERS
3. WEATHER CONDITIONS, WIND SPEED/DIRECTION
4. INFORMATION ON INJURY OR FATALITY
5. EQUIPMENT AFFECTED
6. NAME AND CONTACT FOR PERSONNEL REPORTING
THE ACC WILL RECORD THE INFORMATION IN THE OPERATIONS LOG. THE ACC WILL THEN RUN THE EAP
CHECKLIST.
REFERENCES AND ORDERS THAT PERTAIN TO FIRES: STANDARD OPERATION ORDER (SOO) PC 600.36 REPORTING OF FIRES OR EXPLOSIONS. SJFD S00 18 PROTOCOL FOR ENTERING SJFD FACILITY WHEN SOKE IS
PRESENT. PLANT AND SITE-SPECIFIC CONTINGENCE PLANS.
4. FIRE DEPARTMENT VEHICLE ACCESS ROUTES:
SEE MAP ON SHEET E0.03.
CONSTRUCTION SITE SHALL BE READILY ACCESSIBLE BY FIRE DEPARTMENT APPARATUS BY MEANS OF ROADWAYS HAVING AN ALL-WEATHER DRIVING SERVICE OF NOT LESS THAN 20 FEET OF UNOBSTRUCTED WIDTH. THE ROADS SHALL WITHSTAND LIVE LOADS OF FIRE APPARATUS, AND HAVE A MINIMUM OF 13 FEED, 6 INCHES OF VERTICAL CLEARANCE. DEAD END FIRE ACCESS ROADS IN EXCESS OF 150 FEET IN LENGTH SHALL
BE PROVIDED WITH APPROVED TURNAROUNDS.
5. LOCATION OF FIRE PROTECTION EQUIPMENT, INCLUDING PORTABLE FIRE EXTINGUISHERS, STANDPIPES, FIRE
DEPARTMENT CONNECTIONS AND FIRE HYDRANTS:
SEE MAP ON PLANS.
6. SMOKING AND COOKING POLICIES, DESIGNATED AREAS TO BE USED WHERE APPROVED, AND SIGNAGE
LOCATIONS IN ACCORDANCE WITH SECTION 3305.8:
N/A (NO SMOKING OR COOKING ALLOWED ON PREMISES)
7. LOCATION AND SAFETY CONSIDERATIONS FOR TEMPORARY HEATING EQUIPMENT:
N/A (NO TEMPORARY HEATING EQUIPMENT FOR THIS PROJECT)
8. HOT WORK PERMIT PLAN:
N/A (NO HOT WORK FOR THIS PROJECT. ALL WELDING ON FENCING AND GATES SHALL BE SHOP FABRICATED
BEFORE INSTALLATION ON SITE).
9. PLANS FOR CONTROL OF COMBUSTIBLE WASTE MATERIAL:
ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIAL, SUCH AS WOOD, PLASTIC, INSULATION, PAINTS AND VARNISHES, ADHESIVES AND SEALANTS, DUST, AND DEBRIS SHALL BE REMOVED FROM THE WORK SITE AT THE END OF EACH WORK SHIFT OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS. MATERIALS SUSCEPTIBLE TO SPONTANEOUS IGNITION, SUCH AS OILY RAGS, SHALL BE STORED IN A LISTED DISPOSAL CONTAINER. YARD STORAGE OF EQUIPMENT TO BE INSTALLED OR COMBUSTIBLE CONSTRUCTION MATERIALS
SHALL NOT BE STORES CLOSER THEN 30 FEET FROM ANY STRUCTURE UNDER CONSTRUCTION OR
ALTERATION.
10. LOCATIONS AND METHODS FOR STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS AND OTHER
HAZARDOUS MATERIALS:
STORAGE - FLAMMABLE AND COMBUSTIBLE LIQUID STORAGE AREAS SHALL BE MAINTAINED CLEAR OF COMBUSTIBLE VEGETATION AND WASTE MATERIALS. SUCH STORAGE AREAS SHALL NOT BE USED FOR THE STORAGE OF COMBUSTIBLE MATERIALS. SMOKING AND OTHER SOURCES OF IGNITION SHALL BE PROHIBITED IN AREAS WHERE FLAMMABLE AND COMBUSTIBLE LIQUIDS ARE STORED OR USED. STORAGE OF CLASS I AND CLASS II LIQUIDS SHALL NOT EXCEED 60 GALLONS WITHIN 50 FEET OF THE STRUCTURE UNLESS APPROVED BY
KERN COUNTY FD.
TANKS - TANKS AND CONTAINERS FOR THE STORAGE OF LIQUIDS ABOVE GROUND SHALL BE CONSPICUOUSLY MARKED WITH THE NAME OF THE PRODUCT THEY CONTAIN AND THE WORDS: "FLAMMABLE--KEEP FIRE AND FLAME AWAY." TANKS SHALL BEAR THE ADDITIONAL MARKING: "KEEP 50 FEET FROM BUILDINGS." A. TANKS MORE THAN 100 GALLONS IN CAPACITY, WHICH ARE PERMANENTLY INSTALLED OR MOUNTED AND USED FOR THE STORAGE OF CLASS I, II OR III LIQUIDS, SHALL BE PROVIDED WITH A PLACARD IN ACCORDANCE WITH NFPA 704.B. PORTABLE FIRE EXTINGUISHERS WITH A MINIMUM RATING OF 20-B:C SHALL BE PROVIDED WITHIN 30 FEET
OF THE TANK.
HANDLING AT POINT OF FINAL USE - THE STORAGE, USE AND HANDLING OF FLAMMABLE AND COMBUSTIBLE LIQUIDS AT CONSTRUCTION SITES SHALL BE IN ACCORDANCE WITH CFC SECTION 5706.2. VENTILATION SHALL BE PROVIDED FOR OPERATIONS INVOLVING THE APPLICATION OF MATERIALS CONTAINING FLAMMABLE SOLVENTS. CLASS I AND CLASS II LIQUIDS SHALL BE KEPT IN APPROVED SAFETY CONTAINERS, LEAKAGE AND SPILLS - LEAKING VESSELS SHALL BE IMMEDIATELY REPAIRED OR TAKEN OUT OF SERVICE AND SPILLS SHALL BE CLEANED UP AND DISPOSED OF PROPERLY. PROVISIONS FOR SITE SECURITY.
APPLICABLE CODES
STANDARD ADMINISTRATIVE CODE:
· 2022 CALIFORNIA BUILDING CODE (CBC)
· 2022 CALIFORNIA ELECTRICAL CODE (CEC)
· 2022 CALIFORNIA MECHANICAL CODE (CMC)
· 2022 CALIFORNIA PLUMBING CODE (CPC)
· 2022 CALIFORNIA ENERGY CODE
· 2022 CALIFORNIA FIRE CODE
· 2022 CALIFORNIA GREEN BUILDING CODE
· 2022 CALIFORNIA REFERENCE STANDARD CODE
· CCR-TITLE 19 PUBLIC SAFETY: DIVISION 1 STATE FIRE MARSHAL
· 2016 NFPA 13 INSTALLATION OF FIRE SPRINKLER
· 2013 NFPA 14 INSTALLATION OF STANDPIPE AND HOSE SYSTEM
· 2016 NFPA 20 INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION
· 2016 NFPA 24 INSTALLATION OF PRIVATE FIRE SERVICES MAINS AND THEIR APPURTENANCE
· 2006 NFPA CALIFORNIA EDITION, INSPECTION, TESTING AND MAINTENANCE OF WATER BASED FIRE
PROTECTION SYSTEMS
· 2016 NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE "AS AMENDED BY CALIFORNIA" CSF
SCALE
FIRE ACCESS ROUTES 1
N.T.S.
LOCATION OF
SECONDARY ENTRANCE
WITH GUARD SHACK
LOCATION OF MAIN ENTRANCE
WITH GUARD SHACK AND KNOX
BOX FOR FIRE DEPARTMENT
ACCESS.
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
th
S tr e e t E a st
P e a rb lo ss o m
C A
E. Torres
E. Burtch
As Noted
D e p a rt m e n t o f W a te r R e s o u rc e s
P e a rb lo s s o m
O M
C e n te r E V S E I n s ta lla ti o n
125-01-02.65
09/29/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3435-C
95% CD SubmittalEB05/28/2025 1
100% CD SubmittalEB09/02/2025 2
SITE SAFETY
PLAN
E0.02
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3435
CALOF I
G I
RE
NG
A
E
S
No. E17083
T E
ET
S
AT L CE A
F
R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
Exp. 9-30-27
Electric Vehicle Supply Equipment - Pearblossom O&M Center
SCALE
WATER OPS BUILDING FIRE EXTINGUISHER LOCATIONS 2
N.T.S.
SCALE
WATER OPS BUILDING FIRE EXTINGUISHER LOCATIONS 1
N.T.S.
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
th
S tr e e t E a st
P e a rb lo ss o m
C A
E. Torres
E. Burtch
As Noted
D e p a rt m e n t o f W a te r R e s o u rc e s
P e a rb lo s s o m
O M
C e n te r E V S E I n s ta lla ti o n
125-01-02.65
09/29/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RI C
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3435-C
95% CD SubmittalEB05/28/2025 1
100% CD SubmittalEB09/02/2025 2
WATER OPS BUILDING
SITE SAFETY PLANS
E0.03
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3435
CALOF I
G I
RE
NG
A
E
S
No. E17083
T E
ET
S
AT L CE A
F
R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
Exp. 9-30-27
Electric Vehicle Supply Equipment - Pearblossom O&M Center
O&M CENTER FIRE EXTINGUISHER AND FIRE ACCESS LOCATIONS 2
N.T.S.
SCALE
O&M CENTER FIRE EXTINGUISHER AND FIRE HYDRANT LOCATIONS 1
N.T.S.
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
th
S tr e e t E a st
P e a rb lo ss o m
C A
E. Torres
E. Burtch
As Noted
D e p a rt m e n t o f W a te r R e s o u rc e s
P e a rb lo s s o m
O M
C e n te r E V S E I n s ta lla ti o n
125-01-02.65
09/29/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RI C
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3435-C
95% CD SubmittalEB05/28/2025 1
100% CD SubmittalEB09/02/2025 2
O&M CENTER
SITE SAFETY PLANS
E0.04
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3435
CALOF I
G I
RE
NG
A
E
S
No. E17083
T E
ET
S
AT L CE A
F
R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
Exp. 9-30-27
Electric Vehicle Supply Equipment - Pearblossom O&M Center
PUMPING PLANT FIRE ACCESS LOCATIONS 2
N.T.S.
SCALE
PUMPING PLANT FIRE EXTINGUISHER AND FIRE HYDRANT LOCATIONS 1
N.T.S.
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
th
S tr e e t E a st
P e a rb lo ss o m
C A
E. Torres
E. Burtch
As Noted
D e p a rt m e n t o f W a te r R e s o u rc e s
P e a rb lo s s o m
O M
C e n te r E V S E I n s ta lla ti o n
125-01-02.65
09/29/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RI C
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3435-C
95% CD SubmittalEB05/28/2025 1
100% CD SubmittalEB09/02/2025 2
PUMPING PLANT
SITE SAFETY PLANS
E0.05
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3435
CALOF I
G I
RE
NG
A
E
S
No. E17083
T E
ET
S
AT L CE A
F
R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
Exp. 9-30-27
Electric Vehicle Supply Equipment - Pearblossom O&M Center
SITE PLAN 1
1/64" = 1'-0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
th
S tr e e t E a st
P e a rb lo ss o m
C A
E. Torres
E. Burtch
As Noted
D e p a rt m e n t o f W a te r R e s o u rc e s
P e a rb lo s s o m
O M
C e n te r E V S E I n s ta lla ti o n
125-01-02.65
09/29/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3435-C
95% CD SubmittalEB05/28/2025 1
100% CD SubmittalEB09/02/2025 2
SITE PLAN
E1.00
E2.00
E2.02
E2.01
PUMPING PLANT
O&M CENTER
WATER OPS
BUILDING
PROPOSED EV CHARGERS
EVCS #
WALL/PEDESTAL
MOUNT EVCS
SINGLE/DUAL
EVCS
CHARGE PORT #
POWER SELECT
(FLA)
VOLTAGE
POWER SHARE
(Y / N/A)
CHARGE PORT
TYPE
WATER OPS BUILDING
1 PEDESTAL DUAL 30 240V-1PH N/A FLEET
2 PEDESTAL DUAL 30 240V-1PH N/A FLEET
O&M CENTER
3 PEDESTAL DUAL 30 208V-1PH N/A FLEET
4 PEDESTAL DUAL 30 208V-1PH N/A FLEET
5 PEDESTAL DUAL 30 208V-1PH N/A FLEET
6 PEDESTAL SINGLE 30 208V-1PH N/A FLEET
7 PEDESTAL DUAL 30 208V-1PH N/A FLEET
8 PEDESTAL DUAL 30 208V-1PH N/A FLEET
9 PEDESTAL DUAL 30 208V-1PH N/A FLEET
10 PEDESTAL DUAL 30 208V-1PH N/A FLEET
11 PEDESTAL DUAL 30 208V-1PH N/A FLEET
12 PEDESTAL DUAL 30 208V-1PH N/A FLEET
PUMPING PLANT
13 PEDESTAL DUAL 30 208V-1PH N/A FLEET
14 PEDESTAL SINGLE 30 208V-1PH N/A FLEET
15 PEDESTAL SINGLE 30 208V-1PH N/A FLEET
NOTES:
· (12) DUAL PORT AND (3) SINGLE PORT EVCS SHALL SERVE (27) FLEET PARKING STALLS
· (FLA) STANDS FOR FULL LOAD AMPS
· (Y) STANDS FOR, YES WILL BE REQUIRED; (N/A) STANDS FOR, NOT APPLICABLE
NOTE FOR FLEET EVCS:
FLEET EVCS INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO
COMPLY WITH CBC 11B-228.3.2 ACCESS REQUIREMENTS.
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3435
CALOF I
G I
RE
NG
A
E
S
No. E17083
T E
ET
S
AT L CE A
F
R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
Exp. 9-30-27
Electric Vehicle Supply Equipment - Pearblossom O&M Center
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
(E) UTILITY POLE WITH METER
& DISCONNECT SWITCH
(E) SWITCHBOARD
PB
4 8
(E) ASPHALT
PAVEMENT
(E) ASPHALT
PAVEMENT
(E) VISITOR OVERLOOK
PARKING LOT (E) FENCE
(E) EDGE OF
ASPHALT PAVEMENT
(E) EDGE OF
ASPHALT PAVEMENT
2 8
2 8
PANELBOARD "EV-1"
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
APPROXIMATE LOCATION OF
(E) SEPTIC TANK
PANELBOARD "EV-1"
DIGITAL MULTI-METER
PB
4'-0"
(TYP.)
3'-0"
(TYP.)
1'-2" (TYP.)
EVCS-1 1 5 6 8
EVCS-2 1 5
1'-0"
(TYP.)
19'-0"
(TYP.)
9'-0"
(TYP.)
1"C - 4#6 & 1#8GRD.
(E) CONCRETE
12 (TYP.)
9 (TYP.)
11 (TYP.) 10 (TYP.)
2 TO (E) DISCONNECT
SWITCH
(E) ASPHALT
PAVEMENT
4'-0"
(TYP.)
(E) EDGE OF
ASPHALT PAVEMENT
(E) EDGE OF
ASPHALT PAVEMENT
2 8
SCALE
ENLARGED POWER PLAN 2
1/4"=1'=0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
th
S tr e e t E a st
P e a rb lo ss o m
C A
E. Torres
E. Burtch
As Noted
D e p a rt m e n t o f W a te r R e s o u rc e s
P e a rb lo s s o m
O M
C e n te r E V S E I n s ta lla ti o n
125-01-02.65
09/29/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3435-C
95% CD SubmittalEB05/28/2025 1
100% CD SubmittalEB09/02/2025 2
WATER OPS
BUILDING
POWER PLANS
E2.00
SHEET NOTES:
DUAL PORT PEDESTAL TYPE EVCS WITH 7,200VA
PER PORT. PROVIDE 10'-0" OF FEEDER WIRE (4#6
+ 1#8 GRD) COILED UP AT EVCS STUB-UP
LOCATION FOR FINAL EVCS INSTALLATION. SEE
DETAIL #1 ON SHEET E4.00.
SEE DETAIL #3 SHEET E4.00 FOR UNDERGROUND
CONDUIT BURIAL DETAIL. FOR ALL ROUTING
THROUGH TRAFFIC CROSSINGS PROVIDE
SCHEDULE 80 PVC UNDERGROUND CONDUIT.
PROVIDE 17" X 30" X DEPTH AS REQUIRED
CONCRETE PULL BOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #6
SHEET E4.00 FOR UNDERGROUND PULL BOX
DETAIL.
DEMOLISH AND REPLACE EXISTING FUSES IN
DISCONNECT SWITCH WITH NEW 200A FUSES.
SEE DETAIL #4 SHEET E4.00 FOR EV CHARGING
STATION PVC CONDUIT STUB-UP DETAIL.
SEE DETAIL #5 SHEET E4.00 FOR ELECTRIC
EQUIPMENT RGS CONDUIT STUB-UP DETAIL.
PROVIDE DIGITAL MULTI-METER IN NEMA-3R
ENCLOSURE FOR MONITORING PANEL "EV-1"
INCOMING FEEDERS. REFER TO DETAIL #7 ON
SHEET E4.00 FOR MORE INFORMATION.
SEE SINGLE LINE DIAGRAM #1 SHEET E5.00 FOR
MORE INFORMATION.
RELOCATED WHEELSTOP. REFER TO CIVIL
DRAWINGS FOR INSTALLATION INFORMATION.
NEW 4" DIA. CONCRETE BOLLARD. REFER TO
DETAIL #5 ON SHEET E4.01.
NEW SIGN AND POST. REFER TO CIVIL
DRAWINGS FOR MORE INFORMATION.
NEW STRIPING. REFER TO CIVIL DRAWINGS FOR
MORE INFORMATION.
VERIFY EXACT LOCATIONS OF SEPTIC TANK IN
FIELD PRIOR TO START OF WORK.
PROVIDE CONNECTION TO NEW GROUND ROD.
REFER TO DETAIL #9 ON SHEET E4.01.
GENERAL NOTES:
1. ELECTRICAL ENGINEERING FOR THIS PROJECT
IS BASED ON A FIELD VISIT OF THE ELECTRICAL
SYSTEM. IN CASE OF ANY DISCREPANCIES WITH
EXISTING FIELD CONDITIONS, ELECTRICAL
CONTRACTOR SHALL VERIFY THE EXACT
DIFFERENCES AND NOTIFY THE ELECTRICAL
ENGINEER FOR POSSIBLE REVISION TO THESE
DOCUMENTS.
2. ANY ELECTRICAL AND/OR SIGNAL UTILITY
SHUTDOWNS WITHIN THE AREA OF WORK SHALL
BE COORDINATED AND SCHEDULED IN ADVANCE
WITH THE SITE'S REPRESENTATIVE.
3. ELECTRIC VEHICLE CHARGING STATION/S
(EVCS) SHALL BE PROVIDED, INSTALLED AND
CONNECTED BY STATE VENDOR.
4. PROVIDE MINIMUM OF 1'-0" CLEARANCE BEHIND
ALL PEDESTAL MOUNTED CHARGERS FOR
SERVICING. CONTRACTOR SHALL FIELD VERIFY
ALL DISTANCES PRIOR TO BID.
5. EXISTING VEGETATION TO BE REMOVED,
PROTECTED AND RESTORED AFTER
CONSTRUCTION.
6. REMOVE AND REPLACE EXISTING IN-GROUND
LANDSCAPING AND IRRIGATION LINES
AFFECTED IN WORK.
R
CALL 811 BEFORE YOU DIG.
SCALE
WATER OPS BUILDING POWER PLAN 1
1/16"=1'=0"
2 TO PANEL "EV-1" & EV
CHARGING STATIONS
LEGEND:
EXISTING
NEW
NEW UNDERGROUND
BUILDING INFORMATION: WATER OPS BUILDING
CONSTRUCTION TYPE: N/A*
OCCUPANCY CLASSIFICATION: N/A*
OCCUPANCY LOAD: N/A*
ACTUAL BUILDING HEIGHT: N/A*
BUILDING AREA (SQ. FT.) N/A*
AREA OF PROJECT (SQ. FT.) 4,300 SQ. FT.
SEPARATED OR NON-SEPARATED USE: N/A*
ALLOWABLE AREA: N/A*
AREA INCREASED: NONE
HEIGHT INCREASED: NONE
FIRE SPRINKLERS: N/A*
FIRE ALARM: N/A*
OTHER FIRE PROTECTION SYSTEMS: N/A*
SMOKE CONTROL SYSTEM: N/A*
YEAR CONSTRUCTED: N/A*
HIGH FIRE SEVERITY ZONE: NO
SEISMIC JOINTS: NO
EMERGENCY RESPONDER RADIO COVERAGE: NO
*ALL WORK AT THE BUILDING IS EXTERIOR. NO INTERIOR WORK.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3435
CALOF I
G I
RE
NG
A
E
S
No. E17083
T E
ET
S
AT L CE A
F
R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
Exp. 9-30-27
Electric Vehicle Supply Equipment - Pearblossom O&M Center
ONLY
EV
FLEET
ONLY EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
T
(E) ASPHALT
PAVEMENT
TO PANEL "EV-2" & EV
CHARGING STATIONS
PB
(E) CONCRETE
CURB
(E) GENERATOR
(E) MAIN SWITCHBOARD "MSS"
(E) M.V. TRANSFORMER
(E) ASPHALT
PAVEMENT
3 11
PB
PB
ENCLOSED CIRCUIT
BREAKER
19 (TYP.)
SEE GENERAL
NOTES 5 & 6
EV
FLEET
ONLY
EV
FLEET
ONLY EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
T
PB
PB
PB
(E) ASPHALT
PAVEMENT
9'-0"
(TYP.)
20'-0"
(TYP.)
18'-0"
(TYP.)
9'-0"
(TYP.)
1'-0"
(TYP.)
3'-0"
(TYP.)
3'-0"
(TYP.)
4'-0"
(TYP.)
TRANSFORMER "TEV-2"
(E) CONCRETE
CURB
(E) AREA LIGHT
(E) EDGE OF
ASPHALT PAVEMENT
(E) CONCRETE
CURB
(E) ASPHALT
PAVEMENT
(E) LANDSCAPE
AREA
(E) CONCRETE
CURB
(E) STRIPING
(E) PULLBOX
DIGITAL MULTI-METER
PANELBOARD "EV-2"
TO MAIN
SWITCHBOARD "MSS"
8 11
9 11 8
3'-0"
(TYP.)
4'-0"
(TYP.)
1'-0"
(TYP.)
EVCS-12 1 7
1"C - 4#6
& 1#8GRD.
(2 SETS) 1"C - 4#6
& 1#8GRD.
(3 SETS) 1"C - 4#6
& 1#8GRD.
(5 SETS) 1"C - 4#6
& 1#8GRD.
(7 SETS) 1"C - 4#6
& 1#8GRD.
(9 SETS) 1"C - 4#6
& 1#8GRD.
EVCS-8 1 7
EVCS-6 1 7
EVCS-5 1 7
EVCS-37 2
EVCS-4
15 (TYP.)
14 (TYP.)
16 (TYP.)
17 (TYP.)
15(TYP.)
DISCONNECT SWITCH8 11
3'-0"
(TYP.)
PB
PB
EVCS-7 1 7
EVCS-9 1 7
EVCS-10 1 7
EVCS-11 1 7
SHEET NOTES:
DUAL PORT PEDESTAL TYPE EVCS WITH 7,200VA
PER PORT. PROVIDE 10'-0" OF FEEDER WIRE (4#6
+ 1#8 GRD) COILED UP AT EVCS STUB-UP
LOCATION FOR FINAL EVCS INSTALLATION. SEE
DETAIL #1 ON SHEET E4.00.
SINGLE PORT PEDESTAL TYPE EVCS WITH
7,200VA PER PORT. PROVIDE 10'-0" OF FEEDER
WIRE (2#6 + 1#10 GRD) COILED UP AT EVCS
STUB-UP LOCATION FOR FINAL EVCS
INSTALLATION. SEE DETAIL #2 ON SHEET E4.00.
SEE DETAIL #3 SHEET E4.00 FOR UNDERGROUND
CONDUIT BURIAL DETAIL. FOR ALL ROUTING
THROUGH TRAFFIC CROSSINGS PROVIDE
SCHEDULE 80 PVC UNDERGROUND CONDUIT.
PROVIDE 17" X 30" X DEPTH AS REQUIRED
CONCRETE PULL BOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #6
SHEET E4.00 FOR UNDERGROUND PULL BOX
DETAIL.
PROVIDE 13" X 24" X DEPTH AS REQUIRED
CONCRETE PULL BOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #6
SHEET E4.00 FOR UNDERGROUND PULL BOX
DETAIL.
PROVIDE 11" X 17" X DEPTH AS REQUIRED
CONCRETE PULL BOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #6
SHEET E4.00 FOR UNDERGROUND PULL BOX
DETAIL.
SEE DETAIL #4 SHEET E4.00 FOR EV CHARGING
STATION PVC CONDUIT STUB-UP DETAIL.
SEE DETAIL #5 SHEET E4.00 FOR ELECTRIC
EQUIPMENT RGS CONDUIT STUB-UP DETAIL.
SEE DETAILS #1, #2 & #3 SHEET E4.01 FOR
TRANSFORMER GROUNDING DETAILS.
PROVIDE DIGITAL MULTI-METER IN NEMA-3R
ENCLOSURE FOR MONITORING PANEL "EV-2"
FEEDERS. REFER TO DETAIL #7 ON SHEET E4.00
FOR MORE INFORMATION.
SEE SINGLE LINE DIAGRAM #2 SHEET E5.00 FOR
MORE INFORMATION.
PENETRATION THROUGH CMU CONCRETE WALL
WALL. PROVIDE 12" X 12" X 8" NEMA 3R PULL BOX
TO TRANSITION THROUGH WALL. REFER TO
DETAIL #6 ON SHEET E4.01.
PROVIDE 12" X 12" X 8" NEMA-3R PULL BOX.
RELOCATED WHEELSTOP. REFER TO CIVIL
DRAWINGS FOR INSTALLATION INFORMATION.
NEW 4" DIA. CONCRETE BOLLARD. REFER TO
DETAIL #5 ON SHEET E4.01.
NEW SIGN AND POST. REFER TO CIVIL
DRAWINGS FOR MORE INFORMATION.
REMOVE EXISTING STRIPING AND REPLACE
WITH NEW STRIPING. REFER TO CIVIL DRAWINGS
FOR MORE INFORMATION.
PENETRATION THROUGH CMU CONCRETE WALL
WALL FOR (2) 2" CONDUITS. PROVIDE 16" X 16" X
8" NEMA 3R PULL BOX TO TRANSITION THROUGH
WALL. REFER TO DETAIL #7 ON SHEET E4.01.
RGS CONDUIT SURFACE MOUNTED TO EXISTING
WALL. REFER TO DETAIL #8 ON SHEET E4.01.
EXISTING FOLIAGE TO REMAIN AND BE
PROTECTED IN PLACE.
LEGEND:
EXISTING
NEW
NEW UNDERGROUND
SCALE
ENLARGED POWER PLAN 2
3/16"=1'=0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
th
S tr e e t E a st
P e a rb lo ss o m
C A
E. Torres
E. Burtch
As Noted
D e p a rt m e n t o f W a te r R e s o u rc e s
P e a rb lo s s o m
O M
C e n te r E V S E I n s ta lla ti o n
125-01-02.65
09/29/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RI C
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3435-C
95% CD SubmittalEB05/28/2025 1
100% CD SubmittalEB09/02/2025 2
O&M CENTER
POWER PLANS
E2.01
R
CALL 811 BEFORE YOU DIG.
SCALE
O&M CENTER POWER PLAN 1
3/32"=1'=0"
GENERAL NOTES:
1. ELECTRICAL ENGINEERING FOR THIS PROJECT
IS BASED ON A FIELD VISIT OF THE ELECTRICAL
SYSTEM. IN CASE OF ANY DISCREPANCIES WITH
EXISTING FIELD CONDITIONS, ELECTRICAL
CONTRACTOR SHALL VERIFY THE EXACT
DIFFERENCES AND NOTIFY THE ELECTRICAL
ENGINEER FOR POSSIBLE REVISION TO THESE
DOCUMENTS.
2. ANY ELECTRICAL AND/OR SIGNAL UTILITY
SHUTDOWNS WITHIN THE AREA OF WORK SHALL
BE COORDINATED AND SCHEDULED IN ADVANCE
WITH THE SITE'S REPRESENTATIVE.
3. ELECTRIC VEHICLE CHARGING STATION/S
(EVCS) SHALL BE PROVIDED, INSTALLED AND
CONNECTED BY STATE VENDOR.
4. PROVIDE MINIMUM OF 1'-0" CLEARANCE BEHIND
ALL PEDESTAL MOUNTED CHARGERS FOR
SERVICING. CONTRACTOR SHALL FIELD VERIFY
ALL DISTANCES PRIOR TO BID.
5. EXISTING FOLIAGE TO BE REMOVED,
PROTECTED AND RESTORED AFTER
CONSTRUCTION.
6. REMOVE AND REPLACE EXISTING IN-GROUND
FOLIAGE AND IRRIGATION LINES AFFECTED IN
WORK.
BUILDING INFORMATION: O&M CENTER
CONSTRUCTION TYPE: N/A*
OCCUPANCY CLASSIFICATION: N/A*
OCCUPANCY LOAD: N/A*
ACTUAL BUILDING HEIGHT: N/A*
BUILDING AREA (SQ. FT.) N/A*
AREA OF PROJECT (SQ. FT.) 8,500 SQ. FT.
SEPARATED OR NON-SEPARATED USE: N/A*
ALLOWABLE AREA: N/A*
AREA INCREASED: NONE
HEIGHT INCREASED: NONE
FIRE SPRINKLERS: N/A*
FIRE ALARM: N/A*
OTHER FIRE PROTECTION SYSTEMS: N/A*
SMOKE CONTROL SYSTEM: N/A*
YEAR CONSTRUCTED: N/A*
HIGH FIRE SEVERITY ZONE: NO
SEISMIC JOINTS: NO
EMERGENCY RESPONDER RADIO COVERAGE: NO
*ALL WORK AT THE BUILDING IS EXTERIOR. NO INTERIOR WORK.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3435
CALOF I
G I
RE
NG
A
E
S
No. E17083
T E
ET
S
AT L CE A
F
R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
Exp. 9-30-27
Electric Vehicle Supply Equipment - Pearblossom O&M Center
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
E V
F L E E T
O N L Y
T
(E) ROLL-UP GARAGE
DOOR
(E) ASPHALT
PAVEMENT
(E) LOUVER
(E) LOUVER
(E) MOTOR CONTROL
CENTER "PWB"
(E) EQUIPMENT
AREA
(E) LOUVER
(E) EQUIPMENT
(E) BOLLARD (E) BOLLARD
(E) HOSE BIB
PB
(E) AREA LIGHT
(E) CONDUIT
SUPPORT
(E) CONDUIT
SUPPORT
(E) CONDUIT
SUPPORT
(E) DRAINAGE
CHANNEL
(E) DRAINAGE
CHANNEL
(E) LOUVER
(E) LOUVER
PB
PB
PANELBOARD "EV-3"
TRANSFORMER
"TEV-3"
DIGITAL MULTI-METER
EVCS-13 7 1
EVCS-14 2 7
EVCS-15 2 7
1"C - 4#6 & 1#8GRD.
1"C - 2#6 & 1#10GRD.
1"C - 2#6 & 1#10GRD. 3
6 (TYP.)
11(TYP.)
10(TYP.)
12(TYP.)
13(TYP.)
9'-0"
(TYP.)
18'-0"
(TYP.)
3'-0" (TYP.)
1'-0" (TYP.)
1'-0" (TYP.)
(E) CONDUIT
SUPPORT
4'-0"
(TYP.)
(E) DRAINAGE
CHANNEL
SCALE
PUMPING PLANT POWER PLAN 1
1/4"=1'=0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
th
S tr e e t E a st
P e a rb lo ss o m
C A
E. Torres
E. Burtch
As Noted
D e p a rt m e n t o f W a te r R e s o u rc e s
P e a rb lo s s o m
O M
C e n te r E V S E I n s ta lla ti o n
125-01-02.65
09/29/2025
V2
255 East Rincon St., Suite 301
Corona, CA 92879
P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RI C
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B
R L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3435-C
95% CD SubmittalEB05/28/2025 1
100% CD SubmittalEB09/02/2025 2
PUMPING PLANT
POWER PLANS
E2.02
SHEET NOTES:
DUAL PORT PEDESTAL TYPE EVCS WITH 7,200VA
PER PORT. PROVIDE 10'-0" OF FEEDER WIRE (4#6
+ 1#8 GRD) COILED UP AT EVCS STUB-UP
LOCATION FOR FINAL EVCS INSTALLATION. SEE
DETAIL #1 ON SHEET E4.00.
SINGLE PORT PEDESTAL TYPE EVCS WITH
7,200VA PER PORT. PROVIDE 10'-0" OF FEEDER
WIRE (2#6 + 1#10 GRD) COILED UP AT EVCS
STUB-UP LOCATION FOR FINAL EVCS
INSTALLATION. SEE DETAIL #2 ON SHEET E4.00.
SEE DETAIL #3 SHEET E4.00 FOR UNDERGROUND
CONDUIT BURIAL DETAIL. FOR ALL ROUTING
THROUGH TRAFFIC CROSSINGS PROVIDE
SCHEDULE 80 PVC UNDERGROUND CONDUIT.
PENETRATION THROUGH CMU CONCRETE WALL
WALL. PROVIDE 10" X 10" X 8" NEMA 3R PULL BOX
TO TRANSITION THROUGH WALL. REFER TO
DETAIL #4 ON SHEET E4.01.
PROVIDE 10" X 10" X 8" NEMA-1 PULL BOX.
SURFACE MOUNTED CONDUIT SHALL BE
PAINTED TO MATCH EXISTING SURFACE.
SEE DETAIL #4 SHEET E4.00 FOR EV CHARGING
STATION PVC CONDUIT STUB-UP DETAIL.
PROVIDE DIGITAL MULTI-METER IN NEMA-1
ENCLOSURE FOR MONITORING PANEL "EV-3"
INCOMING FEEDERS. REFER TO DETAIL #7 ON
SHEET E4.00 FOR MORE INFORMATION.
SEE SINGLE LINE DIAGRAM #1 SHEET E5.01 FOR
MORE INFORMATION.
NEW STRIPING. REFER TO CIVIL DRAWINGS FOR
MORE INFORMATION.
NEW WHEELSTOP. REFER TO CIVIL DRAWINGS
FOR INSTALLATION INFORMATION.
NEW 4" DIA. CONCRETE BOLLARD. REFER TO
DETAIL #5 ON SHEET E4.01.
NEW SIGN AND POST. REFER TO CIVIL
DRAWINGS FOR MORE INFORMATION.
EMT CONDUIT SURFACE MOUNTED TO EXISTING
WALL. REFER TO DETAIL #8 ON SHEET E4.01.
R
CALL 811 BEFORE YOU DIG.
GENERAL NOTES:
1. ELECTRICAL ENGINEERING FOR THIS PROJECT
IS BASED ON A FIELD VISIT OF THE ELECTRICAL
SYSTEM. IN CASE OF ANY DISCREPANCIES WITH
EXISTING FIELD CONDITIONS, ELECTRICAL
CONTRACTOR SHALL VERIFY THE EXACT
DIFFERENCES AND NOTIFY THE ELECTRICAL
ENGINEER FOR POSSIBLE REVISION TO THESE
DOCUMENTS.
2. ANY ELECTRICAL AND/OR SIGNAL UTILITY
SHUTDOWNS WITHIN THE AREA OF WORK SHALL
BE COORDINATED AND SCHEDULED IN ADVANCE
WITH THE SITE'S REPRESENTATIVE.
3. ELECTRIC VEHICLE CHARGING STATION/S
(EVCS) SHALL BE PROVIDED, INSTALLED AND
CONNECTED BY STATE VENDOR.
4. PROVIDE MINIMUM OF 1'-0" CLEARANCE BEHIND
ALL PEDESTAL MOUNTED CHARGERS FOR
SERVICING. CONTRACTOR SHALL FIELD VERIFY
ALL DISTANCES PRIOR TO BID.
LEGEND:
EXISTING
NEW
NEW UNDERGROUND
BUILDING INFORMATION: PUMPING PLANT
EQUIPMENT BUILDING
CONSTRUCTION TYPE: II-A
OCCUPANCY CLASSIFICATION: F-1
OCCUPANCY LOAD: 11
ACTUAL BUILDING HEIGHT: 15 FT.
BUILDING AREA (SQ. FT.) 1,100 SQ. FT.
AREA OF PROJECT (SQ. FT.) 2,500 SQ. FT.
SEPARATED OR NON-SEPARATED USE: NON-SEPARATED
ALLOWABLE AREA: 25,000
AREA INCREASED: NONE
HEIGHT INCREASED: NONE
FIRE SPRINKLERS: NO
FIRE ALARM: YES
OTHER FIRE PROTECTION SYSTEMS: YES
SMOKE CONTROL SYSTEM: NO
YEAR CONSTRUCTED: 1973
HIGH FIRE SEVERITY ZONE: NO
SEISMIC JOINTS: NO
EMERGENCY RESPONDER RADIO COVERAGE: NO
PREVIOUS OSFM PROJECT NO: 22-S-4796-C
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3435
CALOF I
G I
RE
NG
A
E
S
No. E17083
T E
ET
S
AT L CE A
F
R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
Exp. 9-30-27
Electric Vehicle Supply Equipment - Pearblossom O&M Center
EMERGENCY SHUT-OFF LABEL DETAIL 8
N.T.S.
4"
3"
RED BACKGROUND
WITH WHITE LETTERING
RED STRIPING
WHITE STRIPING
6"
MIN.
STEEL COUPLING WITH
THREADED PLUG
FINISH GRADE
PVC CONDUIT
TRANSITION
COUPLING
CONTINUOUS RIGID GALVANIZED
STEEL CONDUIT WRAPPED AROUND
WITH 10 MIL. BLACK ELECTRICAL
PLASTIC INSULATING TAPE TO 6"
ABOVE FINISH GRADE
CONTINUOUS RIGID
GALVANIZED STEEL
CONDUIT
BEND RADIUS
R = 10 x DIA. OF CONDUIT
(MINIMUM)
PROVIDE BUSHING
WHEN PULLING
CONDUCTORS
NOTE:
1. LABEL SHALL BE PROVIDED FOR ALL NEW EV CHARGING STATIONS SHOWN ON THESE DRAWINGS. LABEL SHALL
CORRESPOND WITH CHARGER NUMBER AND THE ASSOCIATED PANELBOARD PROVIDING POWER.
2. SEE BELOW FOR LABEL SPECIFICATIONS:
· MATERIAL: THERMAL PRINTED ON REFLECTIVE RED OUTDOOR LABEL STOCK (MEETS ASTMD 4956-99)
· COLOR: WHITE TEXT ON RED BACKGROUND WITH RED AND WHITE ALTERNATING STRIPES
· DAMAGE RESISTANT FROM COMMON CHEMICALS AND SOLVENTS.
· MINIMUM SERVICE TEMPERATURE: -40 DEG FAHRENHEIT
· MAXIMUM SERVICE TEMPERATURE: 180 DEG FAHRENHEIT
· APPLICATION TEMPERATURE: 50 DEG FAHRENHEIT
· FILM THICKNESS: 5.5 MIL
· ADHESIVE THICKNESS: 1 MIL
SCALE
ELECTRICAL EQUIPMENT RGS CONDUIT STUB-UP DETAIL 5
N.T.S.
SCALE
UNDERGROUND CONDUIT BURIAL DETAIL 3
N.T.S.
3" OF SLURRY
BELOW
CONDUIT
1" MIN. SPACING. SHALL BE EQUAL
TO THE LARGEST CONDUIT SIZE
FOR MULTIPLE CONDUIT RUNS.
NEW ASPHALT PAVEMENT EXISTING ASPHALT PAVEMENT
EXISTING BASE
CRUSHED AGGREGATE BASE
RECOMPACTED TO 95%
RELATIVE COMPACTION
ELECTRICAL
WARNING TAPE
4 SACK SLURRY
1'-0"
MIN.
GRADE LEVEL
2'-0"
MIN.
ELECTRICAL
WARNING TAPE
3" CLEAN SAND
BEDDING
NOTE:
PER CEC 300.5 NO CONCRETE CASING IS
REQUIRED IF SCHEDULE 80 PVC IS USED
2'-0" BELOW GRADE LEVEL. SEE POWER
PLAN FOR MORE INFORMATION
1" MIN. SPACING. SHALL BE EQUAL
TO THE LARGEST CONDUIT SIZE
FOR MULTIPLE CONDUIT RUNS.
3" CLEAN SAND
BEDDING
NATIVE BACKFILL
90% COMPACTION
ASPHALT PAVEMENT
APPLICATION
NATIVE SOIL APPLICATION
CONDUIT/S PER PLAN
CONDUIT/S PER PLAN
SCALE
EV CHARGING STATION PVC CONDUIT STUB-UP DETAIL 4
N.T.S.
1'-6" MIN.
FINISH GRADE
PVC CONDUIT
COUPLING
PVC CONDUIT
BEND RADIUS
R = 10 x DIA. OF CONDUIT
(MINIMUM)
PROVIDE BUSHING
WHEN PULLING
CONDUCTORS
PVC COUPLING WITH
THREADED PLUG
PVC CONDUIT
1'-0"
MIN.
2'-0"
MIN.
MATCH
EXISTING +1"
MATCH
EXISTING
+1"
SCALE
DUAL PORT PEDESTAL ELECTRIC VEHICLE CHARGING STATION 1
N.T.S.
NEW CONCRETE EVCS
FOOTING. SEE STRUCTURAL
DRAWINGS FOR MORE
INFORMATION.
FRONT
ELEVATION
SIDE
ELEVATION
4'-0"
MAX.
FINISH GRADE
1" PVC CONDUIT
4#6 & 1#8 GRD.
DUAL PORT PEDESTAL
EV CHARGING STATION
(7,200VA PER PORT)
PROVIDE 1'-6" PVC CONDUIT
STUB-UP WITH CONDUIT
PLUG AND GROUNDING
BUSHING. REFER TO
CONDUIT STUB UP DETAIL #4
ON THIS SHEET.
PROVIDE LABEL IDENTIFYING
SHUT-OFF LOCATION. LABEL SHALL
CORRESPOND TO CHARGER NUMBER.
REFER TO DETAIL #8 ON THIS SHEET.
NOTE:
1. FOR PEDESTAL TYPE EVCS INFORMATION - REFER TO INSTALLATION INSTRUCTIONS PER MANUFACTURER.
2. DUAL PORT CHARGING STATION SHALL BE PROVIDED AND INSTALLED BY CURRENT STATE VENDOR. CONTRACTOR SHALL PROVIDE INFRASTRUCTURE NECESSARY TO SUPPORT THE CHARGER AS SHOWN ON THESE DRAWINGS.
SCALE
UNDERGROUND PULL BOX DETAIL 6
N.T.S.
GRAVEL
BASE
ELECTRICAL
CONDUIT(S)
(IN/OUT)
CONCRETE STEEL
REINFORCED
BOLT DOWN LID
12" DEEP REINFORCED
CONCRETE NON-TRAFFIC
PULL BOX
(EXTEND AS REQUIRED)
FINISH GRADE
COMPACTED
BACKFILL
(TYPICAL)
ELECTRICAL
CONDUIT(S)
(IN/OUT)
2'-0"
MIN.
NOTE:
REFER TO SHEET NOTES ON POWER
PLANS FOR SPECIFIC PULL BOX
DIMENSIONS.
SCALE
SINGLE PORT PEDESTAL ELECTRIC VEHICLE CHARGING STATION 2
N.T.S.
NEW CONCRETE EVCS
FOOTING. SEE STRUCTURAL
DRAWINGS FOR MORE
INFORMATION.
FRONT
ELEVATION
SIDE
ELEVATION
4'-0"
MAX.
FINISH GRADE
1" PVC CONDUIT
2#6 & 1#10 GRD.
SINGLE PORT PEDESTAL
EV CHARGING STATION
(7,200VA PER PORT)
PROVIDE 1'-6" PVC CONDUIT
STUB-UP WITH CONDUIT
PLUG AND GROUNDING
BUSHING. REFER TO
CONDUIT STUB UP DETAIL #4
ON THIS SHEET.
PROVIDE LABEL IDENTIFYING
SHUT-OFF LOCATION. LABEL SHALL
CORRESPOND TO CHARGER NUMBER.
REFER TO DETAIL #8 ON THIS SHEET.
NOTE:
1. FOR PEDESTAL TYPE EVCS INFORMATION - REFER TO INSTALLATION INSTRUCTIONS PER MANUFACTURER.
2. SINGLE PORT CHARGING STATION SHALL BE PROVIDED AND INSTALLED BY CURRENT STATE VENDOR. CONTRACTOR SHALL PROVIDE INFRASTRUCTURE NECESSARY TO SUPPORT THE CHARGER AS SHOWN ON THESE DRAWINGS.
VIN
I1 I2 I3 I4
DIGITAL MULTI-METER
WITH NEMA-3R
ENCLOSURE
3/4"C - 3#12
& 1#12 GRD.
PANELBOARD
SCALE
DIGITAL MULTI-METER DETAIL 7
N.T.S.
(TYP.)3
2" A.F.F.
2" A.F.F.
NOTES:
PROVIDE DIGITAL MULTI-METER WITH CAPABILITIES OF MONITORING
EVCS BRANCH CIRCUITS. METER SHALL BE CAPABLE OF
MONITORING KHW, MAX PEAK DEMAND AMPS AND VOLTAGE.
PROVIDE IN-LINE FUSES PER MANUFACTURER'S INSTALLATION
MANUAL.
PROVIDE CURRENT TRANSFORMERS TO MONITOR ALL EVCS BRANCH
CIRCUITS. REFER TO SINGLE LINE ON SHEET E5.00 FOR MORE
INFORMATION.
VERIFY POWER CONNECTIONS WITH MANUFACTURER'S
INSTALLATION MANUAL.
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
th
S tr e e t E a st
P e a rb lo ss o m
C A
E. Torres
E. Burtch
As Noted
D e p a rt m e n t o f W a te r R e s o u rc e s
P e a rb lo s s o m
O M
C e n te r E V S E I n s ta lla ti o n
125-01-02.65
09/29/2025
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
RE
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 25-S-3435-C
95% CD SubmittalEB05/28/2025 1
100% CD SubmittalEB09/02/2025 2
ELECTRICAL
DETAILS
E4.00
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/03/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25…