Plans Bid 2901-20636.pdf
PDF 6 MB Posted
- Attached to
- PW Prequal Bid 2901-RELAY of WATER MAINS in HAVERFORD AVE (S. R. 3018) & GSI in W. GIRARD AVE
- Solicitation number
- B2727512
- Issued by
- Pennsylvania
About this file
This is a project plan document for the Water Main Relay Project in Philadelphia, prepared for the Philadelphia Water Department. The project involves the replacement and installation of water mains across four primary corridors: Haverford Avenue (State Route 3018), Girard Avenue, Stiles Street, and 63rd Street (State Route 3015). The scope includes abandoning existing 12-inch water mains and installing new 8-inch and 12-inch ductile iron water mains with a minimum 4-foot cover depth throughout the project area. Additionally, the project incorporates green stormwater infrastructure (GSI) elements, including stormwater storage trenches, green inlets, distribution pipes, and underdrains, with a fully lined storage trench system (1559-01) to be replaced along Girard Avenue. The plans contain detailed cross-sections, specifications for pipe materials, depths, and connections, and coordination requirements with other concurrent PWD work projects and utility providers including PECO (electrical lines) and SEPTA (trolley catenary lines).
Critical project requirements include maintaining a minimum 5-foot-6-inch cover for all water mains crossing SEPTA trolley tracks and exercising caution around electrified PECO aerial lines present in the project corridors. The document specifies coordination with existing infrastructure, including fire stations, sewer laterals, and observation wells integrated into the stormwater system design. Contractors must address geomembrane liner installations, watertight pipe connections, and proper inlet protection throughout construction. The solicitation is for pre-qualification only, with an estimated project value exceeding $5,000,000, and approved sellers will receive formal invitation to a closed bid solicitation. All work must conform to current Philadelphia Streets Department standards for city streets and Pennsylvania Department of Transportation (PennDOT) standards for state routes.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N S
IM
PS
O N
S T
N
4T H
S T
W
YN
N
EW
O O
D R
D
N
3R D
S T
N
5T H
S T
M
AR
LY
N
R D
N
0T H
S T
N
2N D
S T
N H
IR
ST
S T
N
3R D
S T
(S .R
. 3
5)
N F
EL
TO
N S
T
N R
O
BI
N
SO
N S
T
N
1S T
ST
N
4T H
S T
N F
EL
TO
N S
T
N
2N D
S T
N E
D G
EW
O
O D
S T
N
1S T
ST
N R
O
BI
N
SO
N S
T
N G
R O
SS
S
T
N
0T H
S T
N S
AL
FO
R D
S T
(S .R
. 3
5)
WORK NO. W-20636-DG
WATER MAIN RELAY PROJECT
HAVERFORD AVE. (S.R. 3018), GIRARD AVE., STILES
ST., AND 63RD ST. (S.R. 3015)
A
A
A
A
I I
I
IIIIIIII
X X
X X
X
X X
X
I I
I
I
I X
X
I
IIIIIIIIIIIII
I
I I I I
I
I
I
I
I
X X
IIIIIIIIIIII
I I
I I
I
I
I
I
I
I
I
I
I
I I I I I I I
I I I I I
I
I I I I
I I I I I I I I I I I
IIII
I
I I
I I
I I
I I
X X X X X X X X X
X X
I I I I I I I
I
IIII
I
X
6' -3
PROPOSED PECO 21"X22" DUCT
(4) 5" PVC, 4'-0"± COV.
4' -1
1"
SECTION A-A
15'-6"
PROPOSED 12" WATER MAIN,
4'-0" COV. (TO BE ABANDONED)
(SEE SPECS)
A
A
A
A
6' -3
PROPOSED PECO 21"X22" DUCT
(4) 5" PVC, 4'-0"± COV.
4' -1
1"
PROPOSED 8" DUCTILE IRON WATER MAIN, 4'-0" COV.
PROPOSED 12" DUCTILE IRON
WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(TO BE ABANDONED)
13'-0"
'-6
(SEE SPECS)
(SEE SPECS)
(SEE SPECS)
(SEE SPECS)
(TO BE ABANDONED)
'-2
HAVERFORD AVENUE (S.R. 3018)
M A
TC
H
LI
E
E
E T
W -3
B B
N . F
EL
TO
N S
T.
MATCH LINE SEE SHEET W-11
AA
N . 6
3R D
T.
(S
.R . 3
5)
NOTE:
CAUTION - ELECTRIFIED AERIAL PECO LINES AND SEPTA
CATENARY LINES EXIST IN 63RD STREET AND HAVERFORD
AVENUE. SEE SPECIFICATIONS FOR REQUIREMENTS.
PROVIDE 5'-6" COVER MINIMUM FOR ALL WATER MAINS
CROSSING SEPTA TROLLEY TRACKS.
B
B
B
B
X
X X X X X X X X X X X X X X
X X
X X
X X
X
X X
X X
X X
X X X X
X X
X X
X X
X X
X X X
X
X X
X
X X
XXX
X
X
X
X
X
X
X
X X
X X
X X X
X
X
X
X
X
X
X
X
I
I
I
I
I
I
I I
I I
II
I
I
I
I
I
I
I
I
I
I
I I I I I
I I I
I
I
I I
MAIN, 4'-0" COV., BY OTHERS
(UNDER PWD WORK NO. W-20579-D)
7'-8"12'-0"
PROPOSED STORMWATER BUMPOUT, BY OTHERS
(UNDER PWD WORK NO. S-50372-RDG)
PROPOSED 8" DUCTILE IRON WATER MAIN,
4'-0" COV., BY OTHERS
(UNDER PWD WORK NO. S-50372-RDG)
15'-0"
SUPPORT & PROTECT EXISTING VALVE
DURING WATER MAIN INSTALLATION
PROPOSED 8" DUCTILE IRON
WATER MAIN, 4'-0" COV.
PROPOSED 8" DUCTILE IRON
WATER MAIN
PROPOSED 12" DUCTILE IRON
WATER MAIN, 4'-0" COV.PROPOSED 8" DUCTILE IRON
WATER MAIN, 4'-0" COV.
PROPOSED 12" DUCTILE IRON
WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(SEE SPECS)
PROPOSED 8" DUCTILE IRON WATER MAIN,
4'-0" COV.
SECTION B-B
9'-0"
PROPOSED 12" WATER
MAIN, 4'-0" COV.
(TO BE ABANDONED)
(SEE SPECS)
B
B
B
B
PROPOSED 8" DUCTILE IRON WATER
MAIN, 4'-0" COV., BY OTHERS
(UNDER PWD WORK NO. W-20579-D)
7'-8"12'-0"
PROPOSED STORMWATER BUMPOUT, BY OTHERS
(UNDER PWD WORK NO. S-50372-RDG)
PROPOSED 8" DUCTILE IRON WATER MAIN,
4'-0" COV., BY OTHERS
(UNDER PWD WORK NO. S-50372-RDG)
PROPOSED 8" DUCTILE IRON WATER MAIN,
4'-0" COV., BY OTHERS
(UNDER PWD WORK NO. W-20673-D)
15'-0"
SUPPORT & PROTECT EXISTING VALVE
DURING WATER MAIN INSTALLATION
PROPOSED 8" DUCTILE IRON
WATER MAIN, 4'-0" COV.
PROPOSED 8" DUCTILE IRON
WATER MAIN
PROPOSED 12" DUCTILE IRON
WATER MAIN, 4'-0" COV.PROPOSED 8" DUCTILE IRON
WATER MAIN, 4'-0" COV.
PROPOSED 12" DUCTILE IRON
WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(TO BE ABANDONED)
(TO BE ABANDONED)
5'-0"
9' -0
'-6
9' -0
(SEE SPECS)
(SEE SPECS)
9'-6"
PROPOSED 8" DUCTILE IRON WATER MAIN,
4'-0" COV.
HAVERFORD AVENUE (S.R. 3018)
N . 6
2N D
S T.
M
AT
CH
NE
SE
S
HE
ET
W
-4 C
C
B B
M A
E
E T
W -2
N . R
O B
IN
SO
N S
T.
W. THOMPSON ST.
NOTE:
CAUTION - ELECTRIFIED AERIAL PECO LINES AND SEPTA
CATENARY LINES EXIST IN 62ND STREET AND HAVERFORD
AVENUE. SEE SPECIFICATIONS FOR REQUIREMENTS.
NOTE:
COORDINATE ALL WORK IN ROBINSON ST. NORTH OF
HAVERFORD AVE. WITH THE PROPOSED UNDER PWD WORK NO.
W-20579-D. (SEE SPECIFICATIONS)
NOTE:
C
C
C
C
X
X X X X X X X X X X X X X X
X
X
X
X
X
X
X
X
X
X
X
I I I I
I
I
I
I
I
IIIIIIIIII
I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I I I I I I I I I I I I I
I I I I I I
I
X X
'-6
9' -0
'-0
'-0
SECTION C-C
(TO BE ABANDONED)
9'-0"
PROPOSED 12" WATER
MAIN, 4'-0" COV.
(SEE SPECS)
C
C
C
C
(TO BE ABANDONED)
PROPOSED 12" DUCTILE IRON WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(RECONNECT)
(TO BE ABANDONED)
'-6
9' -0
'-0
(SEE SPECS)
PROPOSED 8" DUCTILE IRON
WATER MAIN, 4'-0" COV.
'-0
HAVERFORD AVENUE (S.R. 3018)
N. 61ST ST.
C C
M A
E
E T
W -3
D D
M A
E
E T
W -5
NOTE: FOR SECTION OF HAVERFORD AVENUE BETWEEN N. 61ST
STREET AND W. GIRARD AVENUE SEE SHEET W-5.
NOTE:
CAUTION - ELECTRIFIED AERIAL PECO LINES AND SEPTA
CATENARY LINES EXIST IN 61ST STREET AND HAVERFORD
AVENUE. SEE SPECIFICATIONS FOR REQUIREMENTS.
W. T
HOMPSON ST. NOTE:
SEE SPECIFICATIONS RELATIVE TO WORK IN THE VICINITY OF
THE PFD - FIRE STATION ENGINE 41/ LADDER 24/ MEDIC 23.
NOTE:
D
D
D
IIII
I
I I I I
X
X
X
X
X
X
X
I
I I
I I
I
I I
I
I
IIIIIIIIIIIIIII
I
I I I I I I I I I I I I I I I I I I I I I I
I I
I I
I I
I I
I I
I
I I
I I
I
I
I I
I I
I I
I I
I I
I I
I
I
I
I
I
I
I
I
I
I
IIIIIIIIIIII
I I
I
IIIIIIIII
I I
I
I
I
I
I
I
I
I
I I
I I
I I
I I
I
I
I I I I I I I I I I
5'-0"
PROPO
WATE
(UNDEPROPOSED 12" DUCTILE IRON
WATER MAIN, 4'-0" COV.
(SEE SPECS)
(TO BE ABANDONED)
(TO BE ABANDONED BY OTHERS
UNDER PWD WORK NO. S-41160-RD)
SECTION D-D
12'-0"
PROPOSED 12" WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(SEE SPECS)
D
D
D
D
5'-0"
PROPOSED 8" DUCTILE IRON
WATER MAIN, 4'-0" COV., BY OTHERS
(UNDER PWD WORK NO. S-41160-RD)
PROPOSED 12" DUCTILE
IRON WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
PROPOSED 12" DUCTILE IRON
WATER MAIN, 4'-0" COV.
'-0
(SEE SPECS)
(TO BE ABANDONED)
(TO BE ABANDONED BY OTHERS
UNDER PWD WORK NO. S-41160-RD)
HAVERFORD AVENUE (S.R. 3018)
D
M A
E
E T
W -4
W. G
IRARD AVE. N. 60TH ST.
NOTE:
CAUTION - ELECTRIFIED AERIAL PECO LINES AND SEPTA
CATENARY LINES EXIST IN 63RD STREET AND HAVERFORD
AVENUE. SEE SPECIFICATIONS FOR REQUIREMENTS.
PROVIDE 5'-6" COVER MINIMUM FOR ALL WATER MAINS
SECTION E-E
7'-0"
PROPOSED 8" WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
I I
I
I
I
I
I I
I I
I
I
I I
E
E
E
E I
I I
I
I
I
I I
I I
I
I
I I
X
X
I
I I
I
I
II
X X
X X
I
I
I I
I I
I
I
I
I I
I
I I
I
I I
I I
I
I
II
II
IIIII
I
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
PROPOSED 8" DUCTILE IRON WATER
MAIN, 4'-0" COV., BY OTHERS
(UNDER PWD WORK NO. S-50372-RDG)
PROPOSED 8" DUCTILE IRON WATER
MAIN, 4'-0" COV., BY OTHERS
(UNDER PWD WORK NO. S-50372-RDG)
PROPOSED STORMWATER STORAGE
TRENCH, BY OTHERS
(UNDER PWD WORK NO. S-50372-RDG)
PROPOSED 24" DIA. R.C.P., BY OTHERS
(UNDER PWD WORK NO. S-50372-RDG)
12'-0"
15'-0"
PROPOSED 8" DUCTILE IRON
WATER MAIN, 4'-0" COV.
PROPOSED 8" DUCTILE IRON WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(TO BE ABANDONED)
7' -0
15'-0"
15'-0"
STILES STREET
N . F
EL
TO
N S
T.
N . 6
2N D
S T.
NOTE:
CAUTION - ELECTRIFIED AERIAL PECO LINES AND SEPTA
CATENARY LINES EXIST IN 63RD STREET AND HAVERFORD
AVENUE. SEE SPECIFICATIONS FOR REQUIREMENTS.
FF
I I I I I I I I I
I
X X
I I I I I
I I
I I I I I I I I I I I I
I I
I
I
I
I I
I
I
IIIIIIIIIIIIIIIIII
I
II
I I
I
X
I I I I
X
IIIIIIIIII
I
I I
I I I
X X
X X X X
12'-6"
'-0
'-0
SECTION F-F
(TO BE ABANDONED)
12'-0"
PROPOSED 8" WATER MAIN, 4'-0" COV.
(SEE SPECS)
F
F
F
F
PROPOSED 8" DUCTILE IRON
WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(TO BE ABANDONED)
PROPOSED 8" DUCTILE IRON WATER MAIN, 4'-0" COV.
(SEE SPECS)
(SEE SPECS)
(SEE SPECS)
GIRARD AVENUE
N . 6
5T H
S T.
M A
E
E T
W -8
E
N . S
IM
PS
O N
S T.
E
NOTE:
CAUTION - ELECTRIFIED AERIAL PECO LINES AND SEPTA
CATENARY LINES EXIST IN 63RD STREET AND HAVERFORD
AVENUE. SEE SPECIFICATIONS FOR REQUIREMENTS.
FULLY LINED STORAGE TRENCH 1559-01
(TO BE REPLACED)
G
G
G
G
I
IIIII
I
X X X X X X X X X X X X X X X
X
I
I
I I I
I
I
I
X
X
X X
X
X
I
I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I
I I
I I
I I
I I
XXXXXXXX
I
IIIIIII
I
I
I
I
I
I
I
IIIIIIII
I
I I I
I I
I I
I
I
IIIIIIIIIIII
I
I
I
I
IIIIIIIIIIIII
I
IIIIIIIIIIII
I I
I
I
I
I I
I
I I
I
I I
I I I
I
I
I
I I
I
IIIIIIIIIIIIIIIIIII
I
I
I I I I I I
I I
I I
I
I
I
I I I I I I I I I I I I I I I
I
I I
I
PROPOSED 8" DUCTILE IRON
WATER MAIN, 4'-0" COV.PROPOSED 8" DUCTILE IRON WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(TO BE ABANDONED)
(TO BE ABANDONED)
(SEE SPECS) (SEE SPECS)
SECTION G-G
PROPOSED 8" WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(SEE SPECS)14'-0"
5' -6
9'-2"
4' -6
4'-7" 5'-11"
PROPOSED STORMWATER 8" HDPE
PROPOSED STORMWATER 12" PP PIPE
11"
FULLY LINED STORAGE TRENCH 1559-01
(TO BE REPLACED)
G
G
G
G
PROPOSED 8" DUCTILE IRON
WATER MAIN, 4'-0" COV.
PROPOSED 8" DUCTILE IRON WATER MAIN, 4'-0" COV.
PROPOSED 8" DUCTILE IRON WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(TO BE ABANDONED)
(TO BE ABANDONED)
(TO BE ABANDONED)
13'-0"
'-0
'-0
'-0
(SEE SPECS) (SEE SPECS)
GIRARD AVENUE
N . 6
4T H
S T.
M A
E
E T
W -9
F F
N . G
R O
SS
S
T.
M A
E
E T
W -7
E E
NOTE:
CAUTION - ELECTRIFIED AERIAL PECO LINES AND SEPTA
CATENARY LINES EXIST IN 63RD STREET AND HAVERFORD
AVENUE. SEE SPECIFICATIONS FOR REQUIREMENTS.
HH
XXXXXXXXXXXXXX
X
X
X
I
I I I I I I I IXX
I I I I I I I I I
I
XXXXX
I I I I I I I I I I I I
I I
I
I I
IIIIIIIIII
I
I
IIIIIII
I
I
I
I
I
I
I
I
I
I I
I
I
I
I
I
I
IIIIIIIIIIIIIIIIIIIIIIIII
I
I I I I I I I I I I I I I I I I I I I I I I I
I I
I I
I I
I
I
I I I I I I I
I I
I I
I I
I
PROPOSED 8" DUCTILE IRON WATER
MAIN 4' 0" COV BY OTHERS
9'-3"
PROPOSED STORMWATER STORAGE
TRENCH, BY OTHERS
(UNDER PWD WORK NO. S-50372-RDG)
SECTION H-H
6'-6"
PROPOSED 8" WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(SEE SPECS)
H
H
H
H
PROPOSED 8" DUCTILE IRON WATER
MAIN, 4'-0" COV., BY OTHERS
(UNDER PWD WORK NO. S-50372-RDG)
9'-3"
PROPOSED STORMWATER STORAGE
TRENCH, BY OTHERS
(UNDER PWD WORK NO. S-50372-RDG)
PROPOSED STORMWATER STORAGE
TRENCH, BY OTHERS
(UNDER PWD WORK NO. S-50372-RDG)
PROPOSED 8" DUCTILE IRON WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(TO BE ABANDONED)
PROPOSED 8" DUCTILE IRON
WATER MAIN, 4'-0" COV.
PROPOSED 8" DUCTILE IRON
WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(TO BE ABANDONED)
13'-0"
13'-0"
5' -0
'-0
6' -6
(SEE SPECS)
(SEE SPECS)
(SEE SPECS)
(SEE SPECS)
(SEE SPECS)
(SEE SPECS)
6' -6
PROPOSED 8" DUCTILE IRON WATER MAIN, 4'-0" COV.
GIRARD AVENUE
N . 6
3R D
T.
. F
EL
TO
N S
T.
MATCH LINE SEE SHEET W-11
HH
MATCH LINE SEE SHEET W-10
GG
M A
E
E T
W -8
F F
(S .R
. 3
5)
NOTE:
CAUTION - ELECTRIFIED AERIAL PECO LINES AND SEPTA
CATENARY LINES EXIST IN 63RD STREET AND HAVERFORD
AVENUE. SEE SPECIFICATIONS FOR REQUIREMENTS.
J
J
J
J
I
I
IIIIIIII
II
IIII
I
XXXXXXX
I
I I I I I I I I
II
I I I
I
I
I
I
I
II
I I
I
I
I I
I
I I
IIII
X X
X
I
IIIIIIIIIII
I
I
IIII
II
IIIIIIIIII
X X
X
I I
I I
I I
I I
I I
I I I I
I
IIIIIIIII
I I
I I
I I
I I
I
I
X X X
X X
XX
X
XXXXXXX
14'-9"
(RECONNECT)
(SEE SPECS)
SECTION J-J
13'-0"
PROPOSED 8" WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(SEE SPECS)
J
J
J
J
I
I
IIIIIIII
II
IIII
I
XXXXXXX
I
I I I I I I I I
II
I I I
I
I
I I
I
II
I I
I I
I I
I
I I
IIII
X X
X
I
IIIIIIIIIII
I
I
IIII
II
IIIIIIIIII
X X
X
I
I
I
I I
I I
I I
I
I I I I
I
IIIIIIIII
I
I
I I
I
I I
I
I
I X X X
X X
XX
X
XXXXXXX
PROPOSED STORMWATER STORAGE TRENCH,
BY OTHERS (UNDER PWD WORK NO. S-50372-RDG)
14'-9"
PROPOSED 8" DUCTILE IRON WATER MAIN, 4'-0" COV.,
BY OTHERS (UNDER PWD WORK NO. S-50372-RDG)
(RECONNECT)
(TO BE ABANDONED)
PROPOSED 8" DUCTILE IRON WATER MAIN, 4'-0" COV.
'-0
(SEE SPECS)
(SEE SPECS)
'-0
63RD STREET (S.R. 3015)
C A
LL
O
W H
IL
L
ST
M A
E
E T
W -9
G G
NOTE:
CAUTION - ELECTRIFIED AERIAL PECO LINES AND SEPTA
CATENARY LINES EXIST IN 63RD STREET AND HAVERFORD
AVENUE. SEE SPECIFICATIONS FOR REQUIREMENTS.
KK
I I I
I
X X X X X X
I
I I I
X X
I
IIIIII
I I
IIIIIIIIII
I
I I I I I I I I I I I II
I
I
(TO BE ABANDONED) (SEE SPECS)
SECTION K-K
13'-0"
PROPOSED 8" WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(SEE SPECS)
(SEE SPECS)
K
K
K
K
PROPOSED 8" DUCTILE IRON WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
(TO BE ABANDONED)
'-0
(SEE SPECS)
(SEE SPECS)
63RD STREET (S.R. 3015)
M A
E
E T
W -2
A A
H
M A
E
E T
W -9
H
NOTE:
CAUTION - ELECTRIFIED AERIAL PECO LINES AND SEPTA
CATENARY LINES EXIST IN 63RD STREET AND HAVERFORD
AVENUE. SEE SPECIFICATIONS FOR REQUIREMENTS.
X
X X
X
X X
X
X
X
X X
X X X X X X X X X
X X
X
X
X X X X
X X X X X X X X X X X X X X X
X
X X
X
XXXXXXXX
I
I I
I I
I
I I
X
X
X X
X
X
I
I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I
I
I
I
I
I I
I I
XXX
IIIIII
I I
I
I
I
I
I I
I I
I
I
II
I
I
I
IIIIIIIIIIIII
I
IIIIIIIIIIII
I
I I
I
I I
I
I I
I
I I
I
I I I
I
I I
I
I
I
IIIIIIIIIIIIIIIIIII
I
I
I I
I I
I I
I I I I I I I I I I I I I I I I
I
16'-5"
9' -2
33'-10"10'-6"
8' -0
L
L
2' -9
5'
26'-1"
9' -2
5' -0
20'-0" TYP.
5' -1
1"
7'-3"
1' -4
6'
-1 0"
21'-3"
M
M
2'-2"
AASHTO #57 STONE PIPE BEDDING FOR
SUMPED UNDERDRAIN, BOTTOM ELEV. +133.60
6" DIA. V.C.P. SEWER LATERAL
8" SOLID PVC UNDERDRAIN @ 0.0% SLOPE
8" PERFORATED HDPE
UNDERDRAIN @ 0.0% SLOPE
8" PERFORATED HDPE
UNDERDRAIN @ 0.0% SLOPE
CLEANOUT (TYP.)
OBSERVATION WELL (TYP.)
4' OPEN MOUTH GRATE INLET
TC ELEV. +140.25
GRATE ELEV. +139.86
8" IN INV. ELEV. +134.10
CORED INTO INLET WITH 1/2" ORIFICE
15" INV. OUT ELEV. +132.97 TO SEWER
TOP OF STONE IN CARTWAY TO MATCH
BOTTOM OF CONCRETE ROAD BASE.
MAX ELEV. +139.93
12" PERFORATED PP
DISTRIBUTION PIPE @ 0.0% SLOPE
12" SOLID DI DISTRIBUTION
PIPE @ 0.0% SLOPE
4' GREEN HIGHWAY GRATE INLET
GRATE ELEV. +139.93
8" IN INV. ELEV. +137.42
12" OUT INV. ELEV. +136.93
SYSTEM 1559-01
1" = 20'-0" 1" = 5'-0"
12" PERFORATED PP
DISTRIBUTION PIPE @ 0.0% SLOPE
CLEAN WASHED AASHTO # 57
STONE WRAPPED IN GEOTEXTILE
AND GEOMEMBRANE AS INDICATED
ON PLAN AND SECTION
TOP ELEV. +139.93
BOTTOM ELEV. +134.43
3'x6' TREE PIT (TYP.)
25 LF OF 15" VCP LATERAL WITH 24"x15"
RCP WYE CONNECTION TO SEWER
(TO BE ABANDONED) 6"
M
IN
GEOMEMBRANE PIPE PENETRATION (TYP.)
CONTACT PWD CONSTRUCTION FOR
CONFIRMATION PRIOR TO MODIFYING
EXISTING SEWER LATERAL.
6" MIN.
PERFORATED PIPE
SOLID PIPE
CLEANOUT
OBSERVATON WELL
FLEXIBLE COUPLING
STORMWATER TRENCH
GEOMEMBRANE LINER
TREE PIT
4 FT. GREEN HIGHWAY GRATE INLET
4 FT. GREEN CITY INLET
4 FT. OPEN MOUTH GRATE INLET
4 FT. HIGHWAY GRATE INLET
CONCRETE APRON
DENOTES GREEN INLET
DENOTES 4' INLET
DENOTES INLET TO BE RECONNECTED TO
EXISTING PIPE
CURB RAMP
X C/R
LEGEND
(TO BE ABANDONED)
(TO BE ABANDONED)
(SEE SPECS)
PROPOSED 8" DUCTILE IRON
WATER MAIN, 4'-0" COV.
25 LF OF 15" VCP LATERAL WITH 24"x15"
RCP WYE CONNECTION TO SEWER
PROPOSED 8" DUCTILE IRON WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
33 LF OF 8" PERFORATED HDPE UNDERDRAIN
@ 0.0% SLOPE
14 LF OF 8" PERFORATED HDPE
UNDERDRAIN @ 0.0% SLOPE
32 LF OF 8" D.I. DISTRIBUTION PIPE @
0.5% SLOPE
12 LF OF 8" PVC SOLID UNDERDRAIN @ 0.0% SLOPE
12 LF OF 8" PVC SOLID
UNDERDRAIN @ 0.0%
SLOPE
SYSTEM 1559-01
5 2
397 8
33 LF OF 12"
PERFORATED PP
DISTRIBUTION PIPE
@ 0.0% SLOPE
12 LF OF 12" PERFORATED PP DISTRIBUTION
PIPE @ 0.0% SLOPE
21 3
3'x6' TREE PIT (TYP.)
FULLY LINED TREE TRENCH 1559-01-01
REPLACE FAI, TRAP, & PORTION
OF EXISTING LATERAL. ADJUST LATERAL 6" MIN.
BELOW PROPOSED 8" PVC UNDERDRAIN AND
RECONNECT TO EXISTING SAN. LATERAL. (2% MIN.
SLOPE. 1:1 MAX. SLOPE WITHOUT RISERS).
CONTACT PWD CONSTRUCTION FOR CONFIRMATION
PRIOR TO MODIFYING EXISTING SEWER LATERAL.
22.5° PIPE BEND
12 LF OF 12" DI SOLID DISTRIBUTION
PIPE @ 0.0% SLOPE
12" PP TO 12" DI FLEXIBLE COUPLING (TYP.)
45° PIPE BEND (TYP.)
N . 6
4T H
S T.
G R
O
SS
S T.
GIRARD AVENUE
NOTE:
WELDED PIPE BOOT SEAL MUST BE INSTALLED
AT ANY POINT WHERE A PIPE PENETRATES AN
IMPERMEABLE GEOMEMBRANE LINER
# COMPONENT ID COMPONENT TYPE PIPE LENGTH (FT)
1 G15590101-13-05 GREEN CITY INLET W/APRON N/A
2 G15590101-14-05 GREEN HIGHWAY GRATE INLET N/A
3 G15590101-20-05 DISTRIBUTION PIPE 57
4 G15590101-20-10 DISTRIBUTION PIPE 32
5 G15590101-21-05 UNDERDRAIN 71
6 G15590101-50-05 CLEANOUT N/A
7 G15590101-50-10 CLEANOUT N/A
8 G15590101-51-05 OBSERVATION WELL N/A
9 G15590101-51-10 OBSERVATION WELL N/A
10 G15590101-62-05 OMG INLET N/A
SYSTEM 1
SECTION L-L
PROPOSED 8" WATER MAIN, 4'-0" COV.
(TO BE ABANDONED)
14'-0"
8" PERFORATED HDPE
UNDERDRAIN @ 0.0% SLOPE
5' -6
9'-2" 4'-7"
GEOTEXTILE
AASHTO #57 STONE PIPE BEDDING
FOR SUMPED UNDERDRAIN,
BOTTOM ELEV. +133.60
CLEAN-WASHED AASHTO
#57 STONE
TOP ELEV. +139.93
BOTTOM ELEV. +134.43
FOLD GEOMEMBRANE LINER BENEATH
CONCRETE FOOTWAY (18" MIN.)
GEOMEMBRANE LINER
(TO BE REMOVED)
11"
12" PERFORATED PP DISTRIBUTION
PIPE @ 0.0% SLOPE
3'x6" TREE PIT (TYP.)
8'-0" 5'-0"
1'-6"
SET GEOMEMBRANE INTO CONCRETE BASE COURSE
(2" MIN. - 4" MAX.)
SECTION M-M
PROPOSED 8" WATER
MAIN, 4'-0" COV.
(TO BE ABANDONED)
14'-0"
8" PERFORATED HDPE
UNDERDRAIN @ 0.0% SLOPE
11" 4'-7"
12" PERFORATED PP
DISTRIBUTION PIPE @ 0.0% SLOPE
8" SOLID D.I. DISTRIBUTION
PIPE @ 0.5% SLOPE
4' GREEN CITY
INLET W/ APRON
TC EL. +140.70
GUTTER EL. +140.20
8" OUT INV. EL. +137.84
(TO BE REMOVED)
1' -1
6" M
IN
. 5'
-5
NOTES:
1. LOCATE PIPE OPENINGS TO PROVIDE MINIMUM 4" OF
CONCRETE BETWEEN TOP OF INLET BOX AND TOP OF
PIPE OPENING. (PENNDOT RC-46M). CURB ABOVE
INLET SHALL BE SUPPORTED WITH 2A STONE
BETWEEN TOP OF PIPE AND BOTTOM OF CURB.
CURB OUTSIDE OF INLET SHALL BE STANDARD
DEPTH.
2. FOOTWAY AND CARTWAY RESTORATION HAS BEEN
DRAWN FOR REFERENCE PURPOSES ONLY.
PAVEMENT RESTORATION QUANTITIES AND DESIGN
MUST CONFORM TO CURRENT PHILADELPHIA
STREETS DEPARTMENT STANDARDS FOR CITY
STREETS AND PENNDOT STANDARDS FOR STATE
ROUTES.
3. MINUMUM COVER FOR THERMOPLASTIC PIPE IN ROW
IS 2'.
4. PLUMBERS PLUG TO MAINTAIN WATERTIGHT SEAL
UNTIL CONSTRUCTION IS COMPLETE. PLUMBERS
PLUG TO BE REMOVED AT DIRECTION OF PWD.
PLUMBERS PLUG IS NOT TO EXTEND MORE THAN 2"
OUT FROM INLET WALL.
5. ALL JOINTS, ADJUSTMENTS, AND PIPE CONNECTIONS
MUST BE WATERTIGHT.
1" MIN. CLEARANCE
SEAL WITH
NON-SHRINK GROUT
STANDARD PWD OMG
FRAME & GRATE
FOOTWAY
TO SMP
2'-0"
8"
3'-0"
PROPOSED BOND
BREAKER TAPE
OR APPROVED EQUAL
CARTWAY
SEE NOTE 1
3' -6
" M
IN
8'
-0 " M
AX
"M
IN
SU
M
P
4' - 9 14"
PLUMBERS PLUG
SEE NOTE 4
6"
7" STANDARD
PENNDOT
PRECAST
CONCRETE
INLET BOX
MATCH EXISTING CURB
AND FOOTWAY
PROPOSED EXPANSION JOINT
6" MIN. OFFSET FROM CATCH BASIN
PERMANENT INLET
PROTECTION
SEE SPECIFICATIONS
B
B
6" MIN.
A
CURB PLACED ON TOP OF CATCH BASIN
A
SECTION B-B
SECTION A-A
PLAN
10'-0" CURB RESTORATION (TYP.)
SEE NOTE 3
2" MAX.
STANDARD CURB
6"
GREEN INLET MARKER LOCATION
SEE SPECIFICATIONS
SECTION B-B
FOOTWAY
CARTWAY
SE
E
NO
TE
CONCRETE APRON
SEE COMPONENT DETAIL
TO SMP
2" MAX.
1" MIN.
CLEARANCE
SEAL WITH
NON-SHRINK
GROUT
PLUMBER'S PLUG
WITH
WATERTIGHT SEAL
SEE NOTE 6
SEE NOTE 1
NOTES:
1. LOCATE PIPE OPENINGS TO PROVIDE
MIN. 4" OF CONCRETE BETWEEN TOP OF
INLET BOX AND TOP OF PIPE OPENING
(PENNDOT RC-46M).
2. OPEN MOUTH AT CURB FORMED IN TOP
OF INLET BOX.
3. MODIFIED PWD CITY INLET TOP SLAB.
OUTER DIMENSIONS REDUCED TO
MATCH PENNDOT BOX.
4. FOOTWAY AND CARTWAY RESTORATION
HAS BEEN DRAWN FOR REFERENCE
PURPOSES ONLY. PAVEMENT
RESTORATION QUANTITIES AND DESIGN
MUST CONFORM TO CURRENT
PHILADELPHIA STREETS DEPARTMENT
STANDARDS FOR CITY STREETS AND
PENNDOT STANDARDS FOR STATE
ROUTES.
5. MIN. COVER FOR THERMOPLASTIC PIPE
IN ROW IS 2'.
6. PLUMBERS PLUG TO MAINTAIN
WATERTIGHT SEAL UNTIL
CONSTRUCTION IS COMPLETE. PLUG TO
BE REMOVED AT DIRECTION OF PWD.
PLUG NOT TO EXTEND MORE THAN 2"
OUT FROM INLET WALL.
7. ALL JOINTS, ADJUSTMENTS, AND PIPE
CONNECTIONS MUST BE WATERTIGHT.
8. INSTALL PERMANENT INLET PROTECTION
PER SPECIFICATIONS.
A A
PLAN
B
B
TO
S
M P
CONCRETE APRON
SEE COMPONENT DETAIL
SECTION A-A
MATCH
EXISTING CURB
MATCH EXISTING
FOOTWAY
2'-0"
3'-0" 3'
-6 " M
IN
8' -0
" M
AX
" M
IN
SU
M
P
4' - 9 14" 6"
STANDARD
PENNDOT
PRECAST
CONCRETE
INLET BOX
7"
GREEN INLET MARKER
LOCATION
SEE SPECIFICATIONS
3" MIN.
6" MAX.
THROAT
WEED BARRIER SEE
SPECIFICATIONS SEE NOTE 3
NON-WOVEN GEOTEXTILE,
TOPS AND SIDES
FIRMLY PACKED SOIL PEDESTAL
SCARIFY SUBGRADE WHERE PLANTING
SOIL MEETS UNDISTURBED SOIL
NOTES:
1. TREE TO BE INSTALLED BY OTHERS
2. PLANTING SOIL SHALL BE A MINIMUM DEPTH OF 3'-0" UNLESS
OTHERWISE SPECIFIED.
3. INCLUDE STEEL WIRE STAPLES , SIX (6) INCHES LONG PER
MANUFACTURER SPECIFICATIONS.
4. EXTENTS OF STONE STORAGE AND SAND LAYER CAN VARY.
SCARIFY SOIL HORIZON WHERE
PLANTING SOIL MEETS UNDISTURBED
SOIL TO DEPTH OF SOIL PEDESTAL
CLEAN WASHED AASHTO
NO.57 STONE SEE NOTE 4
DISTRIBUTION PIPE
UNDISTURBED SOIL
3' -0
" M
IN
SE
E
NO
TE
PLANTING SOIL
6" SAND LAYER
6" GEOTEXTILE TUCK (TYP.)
STANDARD PENNDOT
PRECAST CONCRETE
INLET BOX
GREEN HIGHWAY GRATE INLET WITH
PROTECTION
TREE PIT IN STORMWATER TRENCH
(WITHOUT TREE)
GREEN CITY INLET
NOTES:
1. TO BE SET IN PWD INLET WITH RECESSED CONTROL
STRUCTURE.
2. ORIFICE SHOULD NOT BE DRILLED PRIOR TO AUTHORIZATION
BY PWD. PWD WILL REVIEW THE RESULTS OF THE DOUBLE
RING INFILTROMETER TESTS CONDUCTED AFTER SMP
EXCAVATION AND WILL CONFIRM ORIFICE DIMENSIONS.
HDPE TO PVC
FITTING
WATERTIGHT
BOOT COLLAR SEE
SPECIFICATIONS
SLOW RELEASE ORIFICE
INLET WALL
THREADED 8" PVC END
PLUG WITH NUT
12" CORED OPENING
INLET WALLDRILLED ORIFICE OPENING
(DIMENSION VARIES, SEE
NOTE 2)
THREADED PVC END
PLUG WITH NUT
DETAIL OF TRAP CONNECTION
1. 8" X 6" PVC WYE JOINT FOR INLINE
SECTION OR 8" 45° BEND AND 8" TO 6"
PVC REDUCER FOR END SECTION.
2. CONCRETE COLLAR TO BE POURED
SINGULARLY IN SOIL/GRASS OR
MONOLITHICALLY WITH FOOTWAY. THE
CONCRETE COLLAR MUST HAVE STONE
FOOTING. EXPANSION JOINT OR CAULK
MAY BE USED.
3. STORMWATER SOIL AND STONE SUBBASE
SURROUNDING CLEANOUT RISER MUST
BE COMPACTED TO ENSURE NO LATERAL
MOVEMENT PRIOR TO PLACEMENT OF
CONCRETE COLLAR.
4. PLACE THREE (3) LENGTHS OF REBAR
EVENLY SPACED AROUND COLLAR, AND 3"
FROM OUTER EDGE.
EXPANSION JOINT
(CONTINUOUS AROUND FRAME)
USED AS NECESSARY
6" PVC
45° BEND
PROPOSED 8" UNDERDRAIN /
DISTRIBUTION PIPE (TYP.)
CONCRETE COLLAR
SEE NOTE 2
CLEANOUT IN FOOTWAY
SURFACE
RESTORATION
(VARIES)
PHILADELPHIA WATER
CLEANOUT FRAME
PHILADELPHIA WATER
CLEANOUT COVER
SEE COMPONENT DETAILS
CLEANOUT
STANDARD PWD
TRAP
UNDERDRAIN
PIPE
UNDERDRAIN
PIPE
STANDARD PWD TRAP AND
CONNECTION TO SEWER
OUTLET PIPE
INVERT
UNDERDRAIN
INVERT
7-1/2" MIN.
SECTION B-B SECTION A-A
FROM SMP
B
B
A A
NOTES:
1. ALL CONCRETE COMPONENTS, INLET GRATE AND FRAME, INLET TRAP,
AND CONNECTION TO SEWER SHALL BE PWD STANDARD CONSTRUCTION.
2. HIGHWAY INLET DEPICTED; DESIGN IS GENERALLY APPLICABLE TO ALL
PWD STANDARD INLETS.
3. TOTAL EXTENSION OF UNDERDRAIN AND CAP ASSEMBLY INTO INLET TO
BE 2" FROM INLET WALL TO END OF CAP.
4. ALL JOINTS, ADJUSTMENTS, AND PIPE CONNECTIONS MUST BE
WATERTIGHT.
STANDARD PWD PRECAST
INLET BOX
UNDERDRAIN
EXTENSION
SEE NOTE 3
UNDERDRAIN
EXTENSION
SEE NOTE 3
PLAN
SLOW RELEASE
ORIFICE
SEE COMPONENT
DETAIL
SLOW RELEASE
ORIFICE
SEE COMPONENT
DETAIL
SLOW RELEASE ORIFICE
SEE COMPONENT DETAIL
WATERTIGHT
BOOT COLLAR
SEE SPECIFICATIONS
WATERTIGHT
BOOT COLLAR
SEE SPECIFICATIONS
STANDARD INLET WITH UNDERDRAIN CONNECTION
DEPRESS GUTTER 2" FROM PROJECTED GUTTER LINE AT OPENING PLAN
NOTES
1. MAXIMUM SLOPE OF APRON PARALLEL TO CURB IS 7H:1V
(15.0%), 12H:1V (8.5%) IS PREFERRED.
2. MAXIMUM SLOPE OF APRON PERPENDICULAR TO CURB
IS 7H:1V (15.0%), 12H:1V (8.5%) IS PREFERRED.
3. CONCRETE APRON THICKNESS TO MATCH BOTTOM OF
EXISTING CONCRETE BASE COURSE.
4. CONCRETE BASE COURSE MINIMUM THICKNESS IS 8" ON
CITY STREETS AND 10" ON STATE ROUTES.
SEAL JOINTS ON
ALL SIDES
2'-0"
2- 0"
2'-0" INLET OPENING (VARIES)
INLET TYPE VARIES
DEPRESS GUTTER
2" AT OPENING
EXISTING PAVEMENT
SECTION
MAXIMUM SLOPE 15.0%
SEE NOTES 1 AND 2
EDGE OF CONCRETE APRON 14" BELOW EDGE
OF PAVEMENT TO ENSURE POSITIVE DRAINAGE
EDGE OF CONCRETE APRON AT LEAST 14" ABOVE EDGE
OF INLET BOX TO ENSURE POSITIVE DRAINAGE
CONCRETE APRON
INLET OPENING FOR PIPE CONNECTION
WATERTIGHT BATTEN BAR (SEE
COMPONENT DETAIL)
GEOMEMBRANE LINER
(SEE PLAN AND SECTION FOR EXTENTS)
CONCRETE INLET CATCH BASIN
CAULK SEALANT
PIPE
A
A
EDGE OF INLET CATCH BASIN
(SIZE VARIES)
4" MIN
IF ANNULAR SPACE BETWEEN PIPE AND PIPE OPENING IS
GREATER THAN 1/2", FILL WITH NON-SHRINK GROUT
1/4" x 2-1/4" ANCHOR BOLT WITH WASHER AND NUT
MAX SPACING 8" O.C.
1/4" THICK SOLID NEOPRENE OR NITRILE PAD WITH TIGHT
BUTT-JOINTS
1/8" THICK BY 2" WIDE ALUMINUM BATTEN BAR
GEOMEMBRANE
PIPE WALL
ELEVATION VIEW OF INLET
SECTION A-A
GEOMEMBRANE PIPE PENETRATION AT INLET
1. THIS DETAIL APPLIES TO ALL PIPE PENETRATIONS THROUGH GEOMEMBRANE LINER. SEE PLANS
FOR LOCATION, PIPE SIZE, PIPE MATERIAL, AND PIPE ANGLE.
2. WELD CONNECTING PIPE BOOT TO SKIRT NOT NECESSARY IF PREFABRICATED.
3. FOR CORRUGATED PIPE, INSERT PIPE ADAPTERS TO CREATE SMOOTH SURFACE FOR CLAMPS.
GEOTEXTILE
CONTINUOUS EXTRUSION
WELD HOLDING PIPE BOOT
SKIRT TO MAIN LINER
PIPE BOOT
BACKFILL
GEOMEMBRANE
LINER
SOLID PIPE
AASHTO #57
STONE
GASKET/SEALANT
(SEE NOTE 3)
OUTER CAULK
BEAD
STAINLESS STEEL
CLAMPS
BOOT SLEEVE
PIPE WALL
(HDPE SHOWN)
GEOTEXTILE
SECTION
END VIEW
EXTRUSION WELD
(SEE NOTE 2)
CONTINUOUS STRIP OF NEOPRENE RUBBER
CUSHION BETWEEN CLAMP AND BOOT LINER
" M
IN
18" MIN
NOTES:
1. WELL COVER SHALL BE SECURED IN CONCRETE SURROUND (1'-4" TOTAL
DIAMETER) IF WELL IS NOT OTHERWISE SECURED BY SURFACE RESTORATION.
2. FOR OBSERVATION WELLS LOCATED WITHIN SURFACE SMPs, PVC CAP SHALL
EXTEND 3" ABOVE MAXIMUM PONDING DEPTH.
3. OBSERVATION WELLS LOCATED IN UNPAVED AREAS (NO SURFACE SMPs) SHALL
BE FLUSH WITH FINISHED GRADE.
4. OBSERVATION WELLS AREA TO BE LOCATED AS SHOWN ON PLANS.
5. FOR OBSERVATION WELLS LOCATED IN UNPAVED AREAS, PLACE THREE (3)
LENGTHS OF REBAR EVENLY SPACED AROUND COLLAR, AND 3" FROM OUTER
EDGE.
DUCTILE IRON BOLTED
OBSERVATION WELL COVER WITH
GRAY IRON FRAME, EAST JORDAN
IRON WORKS PRODUCT #00157024
OR APPROVED EQUAL
PVC CAP
FINISHED GRADE
BENTONITE/CEMENT SEAL
WITH WELL COVER
4" PVC SCHEDULE 40 PIPE
4" PVC SLOTTED WELL SCREEN 0.01
SLOT SIZE WITH PVC CAP. ATLANTIC
SCREEN AND MANUFACTURING INC.
ITEM #OES40400 OR APPROVED EQUAL
UNDISTURBED EARTH
SMP STONE
BACKFILL AS PER SPECIFICATIONS
OBSERVATION WELL IN PAVED AREA
SLOTTED WELL SCREEN SHALL
EXTEND FOR ENTIRE DEPTH
BOTTOM OF TRENCH
PVC CAP WITH PRIMER AND
SOLVENT CEMENT
6" MIN.
6"
SURFACE RESTORATION (VARIES)
VARIES: TYPICAL TO INVERT OF
SMP OR DESIGNATED
OBSERVATION DEPTH
GEOMEMBRANE LINER
3x3 8/8 WWM, PLACED IN
BOTTOM THIRD OF
CONCRETE RING
6" CONCRETE RING 2500 PSI
6" COMPACTED 2A STONE
6"
OBSERVATION WELL IN UNPAVED AREA
PVC CAP
6" 6"
HEIGHT VARIES
SEE NOTES 2 AND 3 ℄
PROTECTIVE CASING
SEE SPECIFICATIONS
1" (MIN.)
2"
5/8" DIAMETER REBAR (12"
LENGTH, TYP.)
SEE NOTE 5
1 4"
4"
2"
1"
CONCEALED PICKHOLE DETAIL
16"
16"1
4" 16"
SECTION A-A
2"
3 8"
Ø5 8"Ø11
4"
16"
PLAN
A A
B
B
SECTION B-B
2"
2"
10 7 16"
1'-21 2"
4"
4"
2"
3 8"
Ø5 8"
Ø11 4"
81 2" 10 1 2"
1' -2
1 2"
4"4"
16" DEEP
BOLT RECESS
2"
1"
R1 3 16"
1' -0
3 4"
SEE SPECIFICATIONS
FOR PRODUCT
NUMBER
NOTES:
1. BOLTS SHALL BE STAINLESS
STEEL AND LUBRICATED
PRIOR TO INSTALLATION.
A A
PLAN
SECTION B-B
B
B
SEE SPECIFICATIONS
FOR PRODUCT NUMBER
5/8" ENGRAVED LETTERS
(1) CONCEALED TYPE
SPECIAL PICK HOLE
(SEE DETAIL BELOW)
CUSTOM ENGRAVED
LOGO DESIGN
PWD CLEANOUT FRAME
PWD CLEANOUT LID
OBSERVATION WELL IN LINED TRENCH
GEOMEMBRANE PIPE PENETRATION
File details come from the government source that posted it. Updated .