Plan Sheets.pdf

PDF 422 KB Posted

Attached to
ESB Solar Project - Hermiston Maintenance Station
Solicitation number
S-73000-00002623
Issued by
Union County, Oregon

About this file

The document appears to be a set of plan sheets for an electrical system design related to a solar photovoltaic (PV) project at the Hermiston Maintenance Station in Oregon. The project is being managed by the Oregon Department of Transportation (ODOT) and is located at 1840 S Hwy 395 in Hermiston, Oregon. The key details in the plan sheets include a site plan showing the location of the PV array, first floor electrical plan, single line diagrams for the PV system, and associated electrical symbols and notes. The PV array will consist of 72 monocrystalline solar modules with a total capacity of 26kW and is expected to generate 35MWh per year. The PV system will be interconnected to the main electrical distribution panel in the facility.

The document does not provide specifics on pricing, funding sources, or other contractual terms. However, it does indicate that the PV system is part of a larger scope of work to achieve net-zero energy requirements for the facility. Contractors will be required to coordinate their PV system shop drawings with the ODOT structural engineer prior to finalizing the design.

View the file

Other files

File Type Posted
RFCQ 35229.docx DOCX document
Specifications~8.pdf PDF
OregonBuys Vendor Solicitation Response~13.pdf PDF
OB Bid S-44300-00002624 RFA 5383 Amendment 1.pdf PDF
Hermiston Maintenance Station Photo.pdf PDF
RFCQ 35229 Attachments A-D.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRAWN BY

CHECKED BY

JOB NO.

DATE

SHEET NUMBER

REVISIONS

SHEET TITLE

EXPIRES: 06/30/22

O D

O T

H e rm is to n

S H w y

H e rm is to n

O

R

2020-0475

01/15/2021

E0.1

LMK

JRS

SYMBOL LIST AND

GENERAL NOTES -

ELECTRICAL

E0.1 SYMBOL LIST AND GENERAL NOTES - ELECTRICAL

E1.1 SITE PLAN – ELECTRICAL

E3.1 FIRST FLOOR PLAN – ELECTRICAL

E5.1 SINGLE LINE DIAGRAMS - ELECTRICAL

SHEET INDEX

Abbreviations

AFC ABOVE FINISHED CEILING

AFF ABOVE FINISHED FLOOR

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

AWG AMERICAN WIRE GAUGE

A AMPERES, AMBER

AHJ AUTHORITY HAVING JURISDICTION

AIC AVAILABLE INTERRUPTING CAPACITY

BAS BUILDING AUTOMATION SYSTEM

CA CABLE

CAT CATEGORY

CLG CEILING

C CONDUIT, CLOSE, CONTROL

COORD COORDINATE

CU COPPER

dB DECIBEL

(X) DEMOLISH

DTL DETAIL

DIA DIAMETER

DIM DIMENSION

DIV DIVISION

DN DOWN

DWG DRAWING

EA EACH

EMT ELECTRICAL METALLIC TUBING

EL ELEVATION

E EMERGENCY

EF EXHAUST FAN

(E) EXISTING

FA FIRE ALARM

FMC FLEXIBLE METAL CONDUIT

FT FOOT, FEET

FBO FURNISHED BY OTHERS

G, GND GROUND

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFI GROUND FAULT INTERRUPTER

GFP GROUND FAULT PROTECTION

HT HEIGHT

ID IDENTIFICATION

IN INCH, INCHES

IEEE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS

IG ISOLATED GROUND

KV KILOVOLT

KVA KILOVOLT AMPERES

KW KILOWATT

LED LIGHT EMITTING DIODE

LFMC LIQUIDTIGHT FLEXIBLE METAL CONDUIT

LV LOW VOLTAGE

MOCP MAXIMUM OVERCURRENT PROTECTION

MIN MINIMUM

MCA MINIMUM CIRCUIT AMPS

MISC MISCELLANEOUS

MCC MOTOR CONTROL CENTER

MT, MTD MOUNT, MOUNTED

NEC NATIONAL ELECTRIC CODE

NESC NATIONAL ELECTRIC SAFETY CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

N NEUTRAL

N/A NOT APPLICABLE

N.I.C. NOT IN CONTRACT

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED, CONTRACTOR INSTALLED

PNL PANEL

PH PHASE

PVC POLY-VINYL-CHLORIDE

PWR POWER

QTY QUANTITY

(R) RELOCATE

RFI REQUEST FOR INFORMATION

REQD REQUIRED

RMC RIGID METAL CONDUIT

RM ROOM

SHT SHEET

STD STANDARD

SPD SURGE PROTECTION DEVICE

SWBD SWITCHBOARD

TBD TO BE DETERMINED

XFMR TRANSFORMER

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR

TYP TYPICAL

UL UNDERWRITERS LABORATORIES

UPS UNINTERRUPTIBLE POWER SUPPLY

UON UNLESS OTHERWISE NOTED

V VOLTS, VOLTAGE

WP WEATHERPROOF

W/ WITH

W/O WITHOUT

DRY TYPE TRANSFORMER

FLUSH WALL MOUNTED BRANCH PANEL

GROUND BAR

MAIN DISTRIBUTION PANEL / SUB DISTRIBUTION PANEL

Raceways

CONDUIT CONCEALED IN WALL OR CEILING SPACE

CONDUIT ROUTED BELOW FLOOR / GRADE

CONDUIT ELLED DOWN

CONDUIT ELLED UP

CONDUIT/WIRING CONTINUATION

CONDUIT/WIRING STUBBED OUT WITH END CAP OR INSULATED

PLASTIC BUSHING

FLEXIBLE CONDUIT

Switches and Receptacles

DUPLEX RECEPTACLE (MULTIPLE LETTERS INDICATE MULTIPLE

OPTIONS)

A = ABOVE COUNTER

B = CLOCK HANGER

C = FLUSH CEILING MOUNTED

E = EMERGENCY

F = ARC FAULT PROTECTED BY BREAKER IN PANEL

G = GROUND FAULT CIRCUIT INTERRUPTER

H = HOSPITAL GRADE

K = CHILD RESISTANT COVER

L = ISOLATED GROUND

P = PENDANT MOUNTED WITH CORD GRIPS. VERIFY PENDANT

LENGTH

R1 = HALF SWITCHED BY OCCUPANCY SENSOR RELAY

R2 = FULLY SWITCHED BY OCCUPANCY SENSOR RELAY

S = SPLIT WIRED

T = TAMPER RESISTANT SHUTTERED RECEPTACLE

U = USB PORT(S)

W = WEATHERPROOF CONTINUOUS USE COVER, GFCI PROTECTED,

WITH WEATHER-RESISTANT RECEPTACLE

DUPLEX RECEPTACLE, FLUSH FLOOR

DOUBLE DUPLEX RECEPTACLE, FLUSH FLOOR

DOUBLE DUPLEX RECEPTACLE. SEE LETTER CODE LIST AT DUPLEX

RECEPTACLE FOR OPTIONS

EQUIPMENT ELECTRICAL CONNECTION

SPECIAL PURPOSE RECEPTACLE. LETTER CODE DENOTES

RECEPTACLE CONFIGURATION

LX-XXR = NEMA CONFIGURATION TWIST-LOCK RECEPTACLE

X-XXR = NEMA CONFIGURATION STRAIGHT BLADE RECEPTACLE

P = PENDANT MOUNT WITH CORD GRIPS. VERIFY PENDANT LENGTH

X = COORDINATE RECEPTACLE CONFIGURATION WITH EQUIPMENT

BEING SUPPLIED

CEILING MOUNTED OCCUPANCY SENSOR

P = PASSIVE INFRARED

D = DUAL TECHNOLOGY

U = ULTRASONIC, 360 DEG RANGE

H = ULTRASONIC, HALLWAY PATTERN

v (LOWERCASE) = VACANCY CONTROL DESIGNATION

WALL MOUNTED OCCUPANCY SENSOR

P = PASSIVE INFRARED

D = DUAL TECHNOLOGY

v (LOWERCASE) = VACANCY CONTROL DESIGNATION

WALL MOUNTED OCCUPANCY SENSOR/SWITCH

S = PASSIVE INFRARED WITH INTEGRAL "OFF" SWITCH

T = DUAL RELAY PASSIVE INFRARED WITH TWO INTEGRAL "OFF"

SWITCHES

D = PASSIVE INFRARED WITH INTEGRAL DIMMER TO OFF.

v (LOWERCASE) = VACANCY CONTROL DESIGNATION

MULTIPLE CHANNEL SURFACE METAL RECEPTACLE RACEWAY

WITH LOW VOLTAGE DIVIDERS, LENGTH AND RECEPTACLES AS

INDICATED

PHOTO ELECTRIC SWITCH

D = CONTINUOUS DIMMING PHOTOCELL

S = SWITCHED PHOTOCELL

SINGLE POLE SWITCH

2 = DOUBLE POLE SWITCH

3 = THREE-WAY SWITCH

4 = FOUR-WAY SWITCH

a THRU z (LOWERCASE) = LUMINAIRE CONTROL DESIGNATION

D = DIMMER

F = FAN SPEED CONTROL

K = KEY OPERATED SWITCH

L = LIGHTED HANDLE

M = MANUAL MOTOR STARTER WITH THERMAL OVERLOAD

P = SWITCH WITH PILOT LIGHT

S = SENTRY SWITCH

T = INTERVAL TIMER

W = WEATHERPROOF SWITCH

V = LOW VOLTAGE SWITCH

Telecommunications

RACEWAY ONLY DATA/TELEPHONE OUTLET. PROVIDE DOUBLE

GANG BACK BOX AND SINGLE GANG ADAPTER PLATE WITH 1" C.

AND PULLSTRING TO ACCESSIBLE CEILING SPACE.

(MULTIPLE LETTERS INDICATE MULTIPLE OPTIONS)

A = ABOVE COUNTER

C = CEILING MOUNTED ABOVE ACCESSIBLE CEILING

F = FLUSH CEILING MOUNTED

R = SURFACE MOUNTED ON RACEWAY

RACEWAY ONLY TELEPHONE OUTLET. PROVIDE DOUBLE GANG

BACK BOX AND SINGLE GANG ADAPTER PLATE WITH 3/4" C. AND

PULLSTRING TO ACCESSIBLE CEILING SPACE. SEE LETTER CODE

LIST AT DATA/TELEPHONE OUTLET FOR OPTIONS.

Connections / Equipment

COMBINATION ADJUSTABLE FREQUENCY DRIVE WITH SAFETY

DISCONNECT SWITCH

COMBINATION MOTOR STARTER/FUSED DISCONNECT SWITCH

HEAVY DUTY FUSED DISCONNECT SWITCH

MOTOR CONNECTION

NON-FUSED DISCONNECT SWITCH

TRANSFORMER

FIRE SMOKE DAMPER

SMOKE DAMPER

CEILING MOUNTED JUNCTION BOX

FLOOR MOUNTED JUNCTION BOX

WALL-MOUNTED JUNCTION BOX

General

DETAIL NUMBER AND SHEET LOCATION

EQUIPMENT IDENTIFICATION

KEYED NOTE

DEMOLISH

EXISTING WORK

NEW WORK

Lighting

COMBINATION EXIT SIGN CEILING MOUNTED AND DUAL HEAD

EMERGENCY EGRESS LIGHTING WITH BATTERY PACK. ARROW(S)

INDICATES DIRECTION IF SHOWN

COMBINATION EXIT SIGN WALL MOUNTED AND DUAL HEAD

EMERGENCY EGRESS LIGHTING WITH BATTERY PACK. ARROW(S)

INDICATES DIRECTION IF SHOWN

EXIT SIGN CEILING MOUNTED, ARROW(S) INDICATES DIRECTION IF

SHOWN

EXIT SIGN WALL MOUNTED, ARROW(S) INDICATES DIRECTION IF

SHOWN

RECESSED 1' X 4' LUMINAIRE

RECESSED 1' X 4' LUMINAIRE CONNECTED TO EMERGENCY/LIFE

SAFETY CIRCUIT OR WITH INTEGRAL EMERGENCY BATTERY

CONNECTED TO UNSWITCHED CIRCUIT

RECESSED 2' X 2' LUMINAIRE

RECESSED 2' X 2' LUMINAIRE CONNECTED TO EMERGENCY/LIFE

SAFETY CIRCUIT OR WITH INTEGRAL EMERGENCY BATTERY

CONNECTED TO UNSWITCHED CIRCUIT

RECESSED 2' X 4' LUMINAIRE

RECESSED 2' X 4' LUMINAIRE CONNECTED TO EMERGENCY/LIFE

SAFETY CIRCUIT OR WITH INTEGRAL EMERGENCY BATTERY

CONNECTED TO UNSWITCHED CIRCUIT

RECESSED LUMINAIRE

RECESSED LUMINAIRE CONNECTED TO EMERGENCY/LIFE SAFETY

CIRCUIT

SURFACE MOUNTED 2' X 2' LUMINAIRE CONNECTED TO

EMERGENCY/LIFE SAFETY CIRCUIT OR WITH INTEGRAL

EMERGENCY BATTERY CONNECTED TO UNSWITCHED CIRCUIT

SURFACE MOUNTED 2' X 4' LUMINAIRE

SURFACE MOUNTED 2' X 4' LUMINAIRE CONNECTED TO

EMERGENCY/LIFE SAFETY CIRCUIT OR WITH INTEGRAL

EMERGENCY BATTERY CONNECTED TO UNSWITCHED CIRCUIT

SURFACE OR PENDANT MOUNTED 1' X 4' LUMINAIRE

SURFACE OR PENDANT MOUNTED 1' X 4' LUMINAIRE CONNECTED

TO EMERGENCY/LIFE SAFETY CIRCUIT OR WITH INTEGRAL

EMERGENCY BATTERY CONNECTED TO UNSWITCHED CIRCUIT

SURFACE OR PENDANT MOUNTED LUMINAIRE CONNECTED TO

EMERGENCY/LIFE SAFETY CIRCUIT OR WITH INTEGRAL

EMERGENCY BATTERY CONNECTED TO UNSWITCHED CIRCUIT

SURFACE OR PENDANT MOUNTED STRIPLIGHT

WALL MOUNTED 6" WIDE LUMINAIRE

WALL MOUNTED 6" WIDE LUMINAIRE CONNECTED TO

EMERGENCY/LIFE SAFETY CIRCUIT OR WITH INTEGRAL

EMERGENCY BATTERY CONNECTED TO UNSWITCHED CIRCUIT

WALL MOUNTED 12" WIDE LUMINAIRE

WALL MOUNTED 12" WIDE LUMINAIRE CONNECTED TO

EMERGENCY/LIFE SAFETY CIRCUIT OR WITH INTEGRAL

EMERGENCY BATTERY CONNECTED TO UNSWITCHED CIRCUIT

WALL MOUNTED LUMINAIRE

WALL MOUNTED LUMINAIRE CONNECTED TO EMERGENCY/LIFE

SAFETY CIRCUIT OR WITH INTEGRAL EMERGENCY BATTERY

CONNECTED TO UNSWITCHED CIRCUIT

Miscellaneous

BRANCH CIRCUIT WIRING. ARROW INDICATES HOME RUN TO

PANEL WITH CIRCUITS AS NOTED. WIRE SIZE IS #12 AWG MINIMUM

UNLESS NOTED OTHERWISE. SHORT TICK MARKS INDICATE PHASE

CONDUCTORS. LONG TICK MARKS INDICATE NEUTRAL

CONDUCTORS. A SINGLE CURVED TICK MARK INDICATES

INSULATED GREEN GROUND CONDUCTOR. SECOND CURVED TICK

MARK INDICATES "ISOLATED GROUND" (GREEN INSULATION WITH

YELLOW STRIPE) CONDUCTOR.

BRANCH PANEL

CIRCUIT BREAKER

ELECTRICAL SYMBOL LIST

NOTE: This is a standard symbol list and not all items listed may be used.

PROJECT

CONTACT

www.interfaceengineering.com

Lauren Krueger

2020-0475

100 SW Main Street, Suite 1600 Portland, OR 97204

TEL 503.382.2266

S

(72) 360W

MONOCRYSTALLINE

MODULES, 5 DEGREE TILT,

224 DEGREE AZIMUTH, 26kW, 35MWh/YEAR

REQUIRED 3'-0"

SETBACK FROM EDGE

OF ROOF, TYPICAL

3'-1"

DRAWN BY

CHECKED BY

JOB NO.

DATE

SHEET NUMBER

REVISIONS

SHEET TITLE

EXPIRES: 06/30/22

O D

O T

H e rm is to n

S H w y

H e rm is to n

O

R

2020-0475

01/15/2021

E1.1

LMK

JRS

SITE PLAN –

ELECTRICAL

PROJECT

CONTACT

www.interfaceengineering.com

Lauren Krueger

2020-0475

100 SW Main Street, Suite 1600 Portland, OR 97204

TEL 503.382.2266

A. REFER TO SPEC SECTION 263100 FOR DESIGN/BUILD

REQUIREMENTS FOR PV SYSTEM. LAYOUT SHOWN ON ELECTRICAL

PLANS FOR REFERENCE ONLY. COORDINATE PV SHOP DRAWING

LAYOUT WITH ODOT STRUCTURAL PRIOR TO PRODUCING SHOP

DRAWINGS FOR RACK SUPPORTS OF PV SYSTEM.

B. EXISTING STANDING SEAM METAL ROOF INSTALLED IN AUGUST,

2020. CONTRACT DOCUMENT AVAILABLE FROM OWNER. CONDUIT

IS NOT PERMITTED TO PENETRATE THE ROOF. CONDUIT SHOULD

ENTER THE SIDE OF THE BUILDING AND BE SEALED AS REQUIRED

TO PREVENT WATER INTRUSION.

0' 4' 8' 16'

1/8" = 1'-0"

1 SITE PLAN - ELECTRICAL

GENERAL SHEET NOTES

SHEET KEYNOTES

1. WASH BAY ROOF AREA IS OFF LIMITS FOR PV ARRAY.

2. PV PANELS WITHIN THIS AREA ARE INCLUDED UNDER CURRENT

CONTRACT. REMAINDER OF PANELS ARE SHOWN FOR REFERENCE

ONLY AS FUTURE ARRAY REQUIRED TO ACHIEVE NET-ZERO ENERGY

REQUIREMENTS.

3. PANEL TILT TO MATCH EXISTING ROOF SLOPE.

N O R T H

UP

DN

WOMEN

HALL

MEETING

OFFICE

GREASE BAY

REPAIR BAY

REPAIR WASH

MEN

EQUIPMENT

STORAGE

TRUCK STORAGE

WASH BAY

OIL & LUBE

OFFICE

STORAGE

STOR.

STOR.

STOR.

M

(N) UTILITY

METER

MAIN DISTRIBUTION PANEL 'MDP'

(E) PANEL

PANEL 'PV'

PV MAIN DISCONNECT

PV INVERTERS

PENETRATE

SIDE OF

BUILDING AND

ROUTE TO PV

ARRAY

DRAWN BY

CHECKED BY

JOB NO.

DATE

SHEET NUMBER

REVISIONS

SHEET TITLE

EXPIRES: 06/30/22

O D

O T

H e rm is to n

S H w y

H e rm is to n

O

R

2020-0475

01/15/2021

E3.1

LMK

JRS

FIRST FLOOR PLAN –

ELECTRICAL

0' 4' 8' 16'

1/8" = 1'-0"

1 LEVEL 1 POWER PLAN

PROJECT

CONTACT

www.interfaceengineering.com

Lauren Krueger

2020-0475

100 SW Main Street, Suite 1600 Portland, OR 97204

TEL 503.382.2266

SHEET KEYNOTES

1. PROVIDE PHOTOVOLTAIC INVERTER. SEE SINGLE LINE

DIAGRAM ON SHEET E5.1 FOR ADDITIONAL INFORMATION.

2. MOUNT NEW METER TO SIDE OF PANEL ENCLOSURE.

N O

R T

H

DC

AC

DC

AC

600 AMP BUS

240/120 VOLT, 1 PHASE, 3 WIRE

SOLAR PV COMBINER PANELBOARD (PV)

2P

70A

2P

70A

INTEGRAL

AC

DISCONNECT

INTEGRAL

DC

DISCONNECT

INTEGRATED

COMMUNICATIONS

GATEWAY

TO ETHERNET

CAT6E INTEGRAL

AC

DISCONNECT

INTEGRAL

DC

DISCONNECT

#8 CU

GND.,

TYP.

INTEGRATED DC

FUSES, TYP.

TYP.

2P

80A

PV

INVERTER,

'INV-1',

12.5kW

PV

INVERTER,

'INV-2',

12.5kW

TO ETHERNET

CAT6E

2P

80A

TO GROUND,

TYP.

PROVISIONS FOR FUTURE PV

ADDITION FOR NET ZERO ENERGY

TYP.

TYP.

MODULE TECHNOLOGY CONNECTOR:

(RAPID SHUTDOWN/MONITORING)

AVAILABLE FAULT CURRENT: 2123A

240/120 VOLT, 1 PHASE, 3 WIRE

REQUIREMENTS

POWER COMPANY

METER BASE PER

PULL WIRE

1-1/2"C. WITH

MAIN DISTRIBUTION PANEL (MDP)

TERMINAL

CABINET

TRANSF./

CURRENT

UTILITY

TRANSFORMER

T

M

1. PV INVERTERS ARE 1-PHASE AND LOCATED AS SHOWN

ON FLOOR PLAN. BASIS OF DESIGN: FRONIUS PRIMO

12.5-1 208-240.

2. SEE FINAL SHOP DRAWINGS FOR PV MODULE COUNT,

CONDUIT/CONDUCTOR SIZES AND ROOFTOP

PLACEMENT.

3. PV MODULE BASIS OF DESIGN: TRINASOLAR

TSM-360DD14A.18(II).

4. PROVIDE LOCKABLE DISCONNECT IN NEMA 3R

ENCLOSURE IF UTILITY REQUIRES METER TO BE

LOCATED OUTSIDE. PROVIDE ENGRAVED LABEL ON

DISCONNECT WITH WHITE LETTERING ON RED

BACKGROUND: "PV SYSTEM DISCONNECT". CONFIRM

WITH UTILITY IF DISCONNECT CAN BE OMITTED AND

BREAKER INTEGRAL TO 'MDP' MAY FUNCTION AS PV

MAIN DISCONNECT.

5. PROVIDE POWER/ENERGY SUBMETER FOR PV SYSTEM.

6. MODULE TECHNOLOGY CONNECTOR: PROVIDE

CONNECTOR FOR MODULE-BY-MODULE MONITORING,

OPTIMIZATION (TO DIMINISH EFFECTS OF PV MODULE

SHADING ON STRING), AND RAPID SHUTDOWN FOR NEC

ARTICLE 690.12 COMPLIANCE, SUCH THAT WHEN AC

POWER IS CUT TO THE INVERTER, THE INVERTER AND

MODULE TECHNOLOGY COMMUNICATE, CAUSING THE

DC OUTPUT OF THE PANELS TO BE DE-

ENERGIZED. TIGO TS4-O SERIES MODULE

TECHNOLOGY CONNECTOR OR APPROVED EQUAL.

7. DEMOLISH EXISTING FEEDER TO EXISTING PANEL.

REFEED FROM NEW SERVICE MAIN DISTRIBUTION

PANEL 'MDP'.

903 903

2P

80A

2P

80A

SPACE SPACE SPACE SPACE

NEUT. BUS

3P

GFI

400A

FULL LENGTH

800 AMP BUSGROUND BUS

SPD

#3 CU

PROTECTION DEVICE

INTEGRAL SURGE

2P

600A

F4

MM 5

GFP

600AS

600AF

SHEET KEYNOTES

2 3

2P 400A

(E)PANEL

400C

SHORT CIRCUIT CURRENT RATING: 22KAIC

NEMA 3R

AVAILABLE FAULT CURRENT: 2100A

SHORT CIRCUIT CURRENT RATING: 10KAIC

#3 CU,

CONNECT TO

EXISTING

GROUNDING

ELECTRODE

SYSTEM

DRAWN BY

CHECKED BY

JOB NO.

DATE

SHEET NUMBER

REVISIONS

SHEET TITLE

EXPIRES: 06/30/22

O D

O T

H e rm is to n

S H w y

H e rm is to n

O

R

2020-0475

01/15/2021

E5.1

LMK

JRS

SINGLE LINE DIAGRAMS

- ELECTRICAL

PROJECT

CONTACT

www.interfaceengineering.com

Lauren Krueger

2020-0475

100 SW Main Street, Suite 1600 Portland, OR 97204

TEL 503.382.2266

0' 4' 8' 16'

NO SCALE

1 PV ONE-LINE POWER DIAGRAM

A,C,S,X A=Aluminum C=Conduit only S=Service secondary X=Seperately derived system

FEEDER SCHEDULE

400C TWO 3" DIAMETER EMPTY CONDUIT WITH PULL CORD

903 3 #2 CU, 1 #8 CU GND., IN 1 1/4" C.

4003 2 SETS OF (3 #3/0 CU, 1 #2 CU GND., IN 2" C.)

5003 2 SETS OF (3 -250 kcmil CU, 1 #2 CU GND., IN 2 1/2" C.)

Disclaimer: Interface Engineering, Inc. has contacted the utilities but has not received in writing the final requirements from the [power utility] [telephone utility] [CATV utility]. These drawings indicate our best estimation of their requirements. [Prior to bid] [Prior to any construction] contact the utilities and obtain in writing their requirements.

2. All service installation work shall be in strict compliance with the requirements of the serving utilities.

1. Contact and coordinate all requirements and responsibilities with serving utility companies prior to submitting bid.

Notes:

Reported Fault Current at Transformer 2123A

Electric Room Door Lock Box (obtain from power company)

N/A N/A

Meter X

Meter Base X

C/T's X

C/T Enclosure X

Secondary Conductors X

Secondary Conduit X

Transformer Connections N/A N/A

Bollards N/A N/A

Transformer Pad / Vault N/A N/A

Transformer N/A N/A

Trenching and Backfill X

Primary Conductors X

Primary Conduit X Power Utility:

Tami Sinor Umatilla Electric Cooperative 750 W. Elm Ave.

Hermiston, OR 97838 Phone:(541) 564-4365 Fax: (541) 564-4345

Contractor Utility Contacts:

Division of Responsibility Incoming Electrical Service

Sheets
E0.1 - SYMBOL LIST AND GENERAL NOTES - ELECTRICAL
E1.1 - SITE PLAN – ELECTRICAL
E3.1 - FIRST FLOOR PLAN – ELECTRICAL
E5.1 - SINGLE LINE DIAGRAMS - ELECTRICAL