Pictures of the doors.docx
DOCX document 439 KB Posted
- Attached to
- MSHA Dorm Room Doors ABA Renovation Federal contract opportunity
- Solicitation number
- 1605C4-26-R-00023
About this file
This is a technical specification document for dorm room door replacement and modification work at MSHA facilities. The project requires replacing two door frames and doors in rooms B11 and B13 to meet ADA accessibility guidelines. The current doors provide only 29 inches of clearance, but ADA compliance mandates a minimum clear opening width of 32 inches when the door is open 90 degrees, measured between the face of the door and the opposite stop per Section 404.2.3 of the ADA Standards. The dormitory features 8-inch concrete walls with rough room door openings of 36.25 inches.
The door frames and doors must be fire-rated for a minimum of 60 minutes. Automatic door openers will be integrated into the existing access control system and operated by PIV cards programmed through the dormitory registration desk Lenel system. Dedicated power circuits for the automatic openers must be installed from the main dorm hallway to the B hallway stairwell serving both rooms, spanning approximately 175 feet through drop leaf ceiling and concrete wall construction. The electrical system consists of a General Electric Type NLAB Style 5 panel rated at 225 amps, 120/208 volts, 3-phase. The solicitation number is 1605C4-26-R-00023, issued by the Department of Labor Office of the Assistant Secretary for Administration and Management. A site survey is recommended prior to work commencement.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| A19 - 1605C4-26-R-00023 - Sol.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Replace two door frames and doors for rooms B11 & B13, to meet ADA guidelines. The current doors only provide a clearance of 29”. The dormitory is constructed of 8” concrete walls, the rough room door openings are 36.25”. See below attached figures 1, 2 & 3.
Must meet the following requirement
Minimum clear opening width: For accessible entrances, doorways must have a minimum clear opening of 32 inches (815 mm) when the door is open 90°, measured between the face of the door and the opposite stop ADA Compliance.
The doors frame and doors must be fire rated for at least 60 minutes.
Section 404.2.3 of the ADA Standards (and the ICC A117.1) - Measuring from the end of the door to the face of the stop ADA Compliance, mandates a minimum clear opening width of 32 inches for accessible doorways
Automatic openers will be integrated into the access control system operated by PIV cards; access keycards are programmed by dormitory registration desk Lenel system.
Dedicated power circuit(s) for automatic door openers will be installed from the main dorm hallway to stairwell of B hallway for rooms B11 and B13. Total distance approximately +175’ consisting of drop leaf ceiling and concrete walls.
The electrical panel General Electric:
Type: NLAB Style: 5
AMP: 225
Volt: 120/208 Ph 3
Figure 1
Figure 2
Figure 3
NOTE: A site survey is recommended.
image1.jpeg image2.jpeg image3.jpeg