PHCC 260-B3260-059 M23PH126 Project Drawings 2025-02-03.pdf

PDF 3 MB Posted

Attached to
Replace A. L. Philpott Roof at Patrick and Henry Community College PC#260-B3260-059 (M23PH126)
Solicitation number
87108
Issued by
Middlesex County, Virginia

About this file

This is a set of architectural and engineering drawings for a roof replacement project at Patrick & Henry Community College's A.L. Philpott Building in Martinsville, Virginia (State Project #PC#260-B3260-059/M23PH126), prepared by Spectrum Design architects and engineers. The project involves a Level 1 alteration to replace roofing components including insulation and membrane systems while maintaining the existing roof deck, with repairs/replacements only as indicated. The work area covers 39,708 SF across a single-story building constructed in 1982 with a 1993 addition. The construction documents are dated February 3, 2025 and must comply with multiple building codes including the 2024 Construction and Professional Services Manual, 2021 Virginia Building Codes, and 2022 National Electrical Code.

The building is classified as Risk Category II with specific structural design criteria including 30 PSF live roof load, 45 PSF ground snow load, and basic wind speed of 109 MPH. The work areas are designated as Business, Educational, and Factory occupancy types with Type IIB construction. The plans detail extensive roof system requirements including fully adhered FSM membrane over continuous base layer rigid insulation (R-30 minimum) and tapered roof insulation on continuous vapor barrier over the existing roof deck. The drawings include comprehensive details for roof drains, equipment curbs, wall terminations, ladder installations and other roofing components.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REPLACE A.L. PHILPOTT ROOF

MARTINSVILLE, VIRGINIA 24112

PLAZA SUITE 1 | 10 CHURCH AVENUE SE

ROANOKE, VA 24011-2104

540 . 342 . 6001

FAX: 540 . 342 . 6055

STATE PROJECT NUMBER: PC#260-B3260-059/M23PH126

FEBRUARY 3, 2025

www.spectrumpc.com

SPECTRUM PROJECT NO: 23112

C O

N

ST

R U

C

TI

O N

D O

C U

M

EN

TS

TITLE SHEETS

T001 COVER SHEET

R

EP

LA

C

E A.

L.

PH

IL

PO

TT

R

O O

F

COMMUNITY COLLEGE - MAIN CAMPUS

PATRICK & HENRY

PA

TR

IC

K

H

EN

R

Y C

O M

M U

N

IT

Y C

O

LL

EG

E

- M

AI

N C

AM

PU

S

ARCHITECTURAL

A030 STRUCTURAL ROOF DECK REPAIR NOTES AND ABBREVIATIONS

A150 PARTIAL ROOF PLAN, LEGEND, ROOF SCHEDULE, & GENERAL ROOF NOTES

A151 PARTIAL ROOF PLAN, & LEGEND

A152 ROOF DETAILS

INDEX OF DRAWINGS VICINITY MAP

CONSTRUCTION DOCUMENTS

VIRGINIA COMMUNITY COLLEGE SYSTEM

PATRIOT AVE

STATE ROUTE 371

KINGS MOUNTAIN ROAD

STATE ROUTE 174

PROJECT

LOCATION

CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL (CPSM) 2024,

REVISION 1 ISSUED 10/10/24

VIRGINIA UNIFORM STATEWIDE BUILDING CODE (VUSBC) 2021

VIRGINIA EXISTING BUILDING CODE (VEBC) 2021

ADA90-TITLE II (2010 ASAD CHAPTER 2 FOR SCOPING , ICC 117.1 - 2017

CHAPTERS 1 AND 3 THRU 11 FOR TECHNICAL REQUIREMENTS

2021 VIRGINIA MECHANICAL CODE

2021 VIRGINIA PLUMBING CODE

2022 NATIONAL ELECTRICAL CODE

NFPA 241-2019

2021 INTERNATIONAL FIRE CODE (IFC)

2021 VIRGINIA STATEWIDE FIRE PREVENTION CODE

APPLICABLE BUILDING CODES:

DESCRIPTION OF WORK:

LEVEL 1 ALTERATION: REPLACE ROOFING COMPONENTS

(INSULATION AND MEMBRANE) IN KIND WITH SIMILAR

UPDATED SYSTEMS. EXISTING ROOF DECK IS TO REMAIN

AND ONLY BE REPAIRED/ REPLACED AS INDICATED.

FIRE SAFETY AND BUILDING CODE NOTES

FE

BR

U

AR

Y 3, 02.03.25

KEY PLAN

WORK AREA USE GROUP: B (BUSINESS), E (EDUCATIONAL), F1

(MODERATE HAZARD FACTORY), F2 (LOW HAZARD FACTORY)

WORK AREA CONSTRUCTION TYPE: IIB

EXISTING BUILDiNG NUMBER OF STORIES - 1 STORY

EXISTING BUILDING HEIGHT = 19'-0"

WORK AREA SQUARE FOOTAGE = 39,708 SF

HIGH PERFORMANCE BUILDINGS ACT

COMPLIANCE STATEMENT

IN ACCORDANCE WITH THE HIGH PERFORMANCE BUILDINGS ACT, THE BUILDING IS EXEMPT FROM COMPLIANCE BECAUSE

THE COST OF THE RENOVATIONS DOES NOT EXCEED 50% OF THE VALUE OF THE BUILDING.

VECC COMPLIANCE PATH

IN ACCORDANCE WITH THE VIRGINIA ENERGY CONSERVATION CODE (VECC), THE BUILDING SHALL COMPLY WITH VECC

SECTIONS C402 THROUGH C405, AND C408.

PATRIOT AVE

STATE ROUTE 371

SP

EC

TR

U

M P

R O

JE

C

T N

U M

BE

R

T001

COVER SHEET

AN ASBESTOS INSPECTION WAS PERFORMED AND ACM WAS FOUND GENERALLY IN THE AREA

INDICATED. THE ASBESTOS INSPECTION REPORT IS INCLUDED AS AN APPENDIX TO THE

PROJECT SPECIFICATIONS. ASBESTOS-CONTAINING BUILDING MATERIALS SHALL NOT BE

DISTURBED IN THE WORK EXCEPT WHERE SPECIFICALLY INDICATED AND REQUIRED. WHERE

SUCH ACTIONS ARE REQUIRED, THE CONTRACTOR SHALL HAVE THE ACM REMOVED BY A

LICENSED ASBESTOS CONTRACTOR USING APPROVED PROCEDURES AS SPECIFIED. THE

WORK REQUIRED FOR ASBESTOS ABATEMENT IS PERMITTED WITHIN THE OVER ALL BUILDING

PERMIT ISSUED. THE ACM THAT IS TO REMAIN AND THE NEW NON ASBESTOS CONTAINING

MATERIAL SHALL BE LABELED ACCORDINGLY. THE ASBESTOS ABATEMENT CONTRACTOR

SHALL MARK UP THE AS-BUILT DRAWINGS RESULTING FROM ITS WORK TO INCLUDE AREAS

HERE ASBESTOS WAS ABATED, AREAS WHERE ASBESTOS WAS ENCAPSULATED, AND AREAS

WHERE ACM EXIST BUT WERE LEFT IN PLACE. THE GENERAL CONTRACTOR SHALL REVIEW

AND CERTIFY THE LOCATIONS WHERE ACM WAS ABATED, AREAS WHERE ACM WAS

ENCAPSULATED, AND AREAS WHERE ACM WAS LEFT IN PLACE AS MARKED ON THE AS-BUILT

DRAWINGS AND WILL PROVIDE THE DRAWINGS TO THE ARCHITECT.

ASBESTOS DISCLOSURE STATEMENT

LEAD DISCLOSURE STATEMENT

AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING COMPONENTS HAS BEEN CONDUCTED AND CAN BE FOUND IN THE PROJECT SPECIFICATIONS. THIS REPORT IS PROVIDED FOR THE CONTRACTOR'S USE AND MAY NOT BE ALL INCLUSIVE. IT IS THE CONTRACTORS RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS THEY PERTAIN TO EMPLOYEE EXPOSURES TO LEAD. ALL LEAD AND LEAD COATED BUILDING

COMPONENTS SHALL BE RECYCLED TO THE EXTENT POSSIBLE.

ORIGINAL BUILDING DATE - 1982

BUILDING ADDITION DATE - 1993

HAZARDOUS MATERIAL STATEMENTS

SPRINKLER:

FULLY SPRINKLERED

OCCUPANCY:

EXISTING OCCUPANCY: 544 OCCUPANTS - UNCHANGED

FIRE ALARM SYSTEM:

PROVIDED

645 PATRIOT AVENUE

UNLESS NOTED OTHERWISE, ALL DESIGN LOADS ARE BASED ON THE

FOLLOWING DATA IN ACCORDANCE WITH THE 2021 VCC (2021 IBC AS

AMENDED), 2021 VEBC (2021 IEBC AS AMENDED), ASCE 7-22 AND 2024

CPSM, REVISION 0 ISSUED 2/29/2024.

RISK CATEGORY II

LIVE LOADS

ROOF (UNREDUCIBLE) 30 PSF PER CPSM

SNOW LOADS

GROUND SNOW LOAD, Pg = 45 PSF, Pg(ASD) = 0.7(45) = 32 PSF EXPOSURE FACTOR, Ce = 1.0 THERMAL FACTOR, Ct =1.2 SLOPE FACTOR, Cs = 1.0

FLAT ROOF SNOW LOAD,

Pf = 0.7CeCtPg = 38 PSF, Pf(ASD) = 0.7(38) = 27 PSF

THE WORK ASSOCIATED WITH THIS PROJECT DOES NOT CAUSE ANY

ADDITIONAL DRIFTING OR SLIDING SNOW CONDITIONS.

WIND LOADS

BASIC DESIGN WIND SPEED, V = 109 MPH

ALLOWABLE STRESS DESIGN WIND SPEED, Vasd = 84 MPH MEAN BUILDING HEIGHT, h = 19 FT

EXPOSURE CATEGORY B

STRUCTURAL DESIGN CRITERIA:

STEEL DECK:

PATCH EXISTING OPENINGS IN STEEL DECK PRIOR TO REROOF.

OVERLAY EXISTING DECK PENETRATIONS w/ 22 GA (MIN) DECKING

MATCHING EXISTING PROFILE. NEW DECK SHALL OVERLAP THE

EXISTING DECK PENETRATIONS BUY A MINIMUM OF TWO FLUTES

ALONG THE SIDES AND SPAN TO CLOSEST STEEL JOIST BEYOND

THE ENDS OF THE PENETRATIONS. FASTEN TO EXIST STEEL JOISTS

w/ PDF'S SPACED AT 12" OC MAX THRU THE EXISTING DECK

WHERE APPLICABLE. FASTEN NEW DECK TO EXISTING DECK

ALONG THE SIDES WITH (2) ROWS OF #10 SCREWS @ 12" OC

STAGGERED ALONG THE TOP FLUTE.

STRUCTURAL ROOF DECK REPAIR

PATCH EXISTING ROOF DECK AS REQUIRED AND IN ACCORDANCE

WITH THE FOLLOWING: REFERENCE SHEET A150 AND A151

NOTE:

THE ABOVE PERTAINS TO LOCATIONS OF EXISTING ROOF MOUNTED

EQUIPMENT, EITHER PRESENT CURRENTLY TO BE REMOVED OR

REMOVED IN THE PAST. ANY DETERIORATED ROOF DECK SHALL BE

REPAIRED/REPLACED VIA UNIT PRICE, AS INDICATED IN PROJECT

BID FORM (DGS-30-220).

ANCHOR BOLT

ARCHITECTURAL

BLOCKING

BUILDING

ALUMINUM

ADDENDUM

CONTROL JOINT

CASEWORK

CONTRACTOR

CONTINUOUS

CONFERENCE

CEILING

DIAMETER

CONCRETE

CONCRETE MASONRY UNIT

ABOVE FINISH FLOOR

CJ

CONTR

CONT

CONF

CONC

CW

DIA

CMU

CLG

ARCH

BLKG

BLDG

ADD

AFF

ALUM

AB

EXPANSION BOLT

EXPANSION JOINT

ELEVATION

EQUIPMENT

EXTERIOR

EXISTING

ELEVATOR

ELECTRICAL

EQUAL

HIGH POINT

HOUR

GALVANIZED

FLOOR

GYPSUM WALL BOARD

FIRE RETARDANT TREATED

FLEXIBLE SHEET ROOFING

HIGH PERFORMANCE ARCH COATING

INSIDE DIAMETER

ISOLATION

JOINT

LOW POINT

INTERIOR

JANITOR

NOT TO SCALE

NOT IN CONTRACT

NOT APPLICABLE

MASONRY OPENING

MAINTENANCE

ON CENTER

METAL

MECHANICAL

MACHINE

LIMITS OF CONSTRUCTION

EJ

EL

FL

ID

MECH

MAINT

OC

NTS

MO

NIC

NA

MTL

MACH

ISOL

LOC

LP

JT

INT

HR

HP

EXIST

EQUIP

GALV

GWB

FRT, F.R.T.

EXT

EQ

ELEV

ELEC

EB

FSR

JAN

HIPAC

ROUGH OPENING

REFER

RECEPTION

ROOM

RADIUS

PLASTIC LAMINATE

OUTSIDE DIAMETER

TOP OF JOIST

SPECIFICATION

STEEL

TOILET

STRUCTURAL

STORAGE

SCHEDULED

SHEET

REFLECTED CEILING PLAN

WITH

TOP OF WALL

TOP OF STEEL

TOP OF MASONRY

VESTIBULE

TYPICAL

TRAINING

WITHOUT

WOOD

WHEELCHAIR

UNLESS OTHERWISE NOTED

R

W/, w/

WHL CHR

W/O

STRUCT

TOW

VEST

U.O.N.

TYP

TRN

TOS

TOM

TOJ

TLT

SCHED

RECPT

STL

STOR

SPEC

SHT

RE

RO

RM

RCP

OD

PLAM

WD

ARCHITECTURAL

ABBREVIATIONS

FIELD VERIFYF.V.

GENERALGEN

ADJACENTADJ

MECHANICAL, ELECTRICAL, PLUMBINGMEP

VERIFY IN FIELDV.I.F. / VIF

ALTERNATEALT

ACOUSTIC TILE/PANEL ACT/ACP

PRESSURE TREATEDP.T.

PAIRPR

FINISHEDFIN

REQUIREDREQ'D

NOT FOR

CONSTRUCTION

SHEET NUMBER:

STATE PROJECT NO.:

SHEET REVISIONS:

SHEET ISSUE DATE:

SHEET NAME:

DRAWN BY:CHECKED BY:

Spectrum Design Project No.:

PROJ. MGR.:

KEY PLAN:

PROJECT PHASE:

J:

\2

\2 .4

A rc h\

2_

A

0.

d w g

, P lo tt ed

B y:

d m cc a rt, P lo tte d:

J an

7,

- 7 :4

4a m

23112

COMMUNITY COLLEGE

a r c h i t e c t s e n g i n e e r s

Plaza Suite 1 10 Church Avenue, SE Roanoke, VA 24011 540.342.6001

SPECTRUMPC.COM

A030

GEG DCV DGM

CONSTRUCTION DOCUMENTS

02.03.2025

PATRICK & HENRY

02.03.25

71'-10 1/2"36'-0"

'-4

4' -8

65'-0"7'-0"

'-8

/1

6"

40'-8"

'-4

4' -8

4'-8"

RI

DG

E

RI

DG

E

14'-8"

7' -4

7' -2

7'-8"

ROOF 1

TEAR OFF TO

DECK

ROOF 2

TEAR OFF TO

DECK

ROOF 3

TEAR OFF TO

DECK

ROOF 4

TEAR OFF TO

DECK

PARTIAL ROOF PLAN

ROOF 5

REF A151 FOR CONT

VERTICAL TERM BAR

VERTICAL TERM BAR

REMOVE EXIST PITCH

POCKET

EXIST SLOPED STRUCTURE

1/4": 1'-0" (TYP)

EXIST SLOPED STRUCTURE

1/4": 1'-0" (TYP)

EXIST SLOPED STRUCTURE

1/4": 1'-0" (TYP)

EXIST SLOPED STRUCTURE

1/4": 1'-0" (TYP) EXIST SLOPED STRUCTURE

1/4": 1'-0" (TYP)

EXIST SLOPED STRUCTURE

1/4": 1'-0" (TYP)

CRICKET

PROVIDE PREFINISHED SURFACE APPLIED

ALUM COUNTERFLASHING @ VERT WALL

TERMINATION (REF DETAIL 6B/A152; TYP)

PROVIDE NEW ROOF LADDER. REF

DETAIL (TYP)

8' 4' 0 8' 16'

GRAPHIC SCALE: 1/8" = 1'-0"

TYP

A152

TYP

A152

TYP

A152

TYP

TYP

A152

TYP

A152

TYP

A152

LOW

A152

TYP

A152

SIM

A152

6A

TYP

A152

TYP

A152

TYP

A152

TYP

A152

TYP

A152

TYP

A152

A152

A152

SIM

A152

6A

SIM

A152

SIM

A152

EOS

SIM

A152

SIM

A152

6A

SIM

A152

SIM

A152

SIM

A152

SIM

A152

A152

A152

SIM

SIM

A152

SIM

SIM

A152

6A

SIM

A152

6A

SIM

A152

6A

A152

SIM

A152

TYP

A152

WALKWAY PADS

(TYP)

PROVIDE PREFINISHED

SURFACE APPLIED ALUM

COUNTERFLASHING @

VERT WALL TERMINATION

(REF DETAIL 6B/A152; TYP)

PROVIDE PREFINISHED

SURFACE APPLIED ALUM

COUNTERFLASHING @

VERT WALL TERMINATION

(REF DETAIL 6B/A152; TYP)

TYP

LOW

TYP

LOW

TYP

LOW

PROVIDE PREFINISHED

SURFACE APPLIED ALUM

COUNTERFLASHING @

VERT WALL TERMINATION

(REF DETAIL 6A/A152; TYP)

4" RD

4" RD

4" RD

2" RD

3" RD

3" RD

3" RD

3" RD

3" RD

2" RD

ROOF 5

REF A151 FOR CONT

EXIST

OVERFLOW TO

REMAIN (TYP)

4" RD

SIM

A152

6A

PROVIDE NON

PENETRATING SAFETY

GUARDRAIL (REF

SPECIFICATIONS (TYP)

PROVIDE NON

PENETRATING SAFETY

GUARDRAIL (REF

SPECIFICATIONS (TYP)

REMOVE EXIST

OVERFLOW AND

WALL MATERIALS

AS REQUIRED TO

PROVIDE NEW

4" H x 13" W

OVERFLOW

SCUPPER REF (TYP)

SIM

A152

6A

SIM

A152

6A

SIM

A152

6A

SIM

A152

6A

1488 SF

REMOVE EXISTING

WALL MATERIALS AS

REQ'D TOPROVIDE

NEW 4" H x 7" W

OVERFLOW SCUPPER

(TYP)

REMOVE EXISTING

WALL MATERIALS AS

REQ'D TO PROVIDE

NEW 4" H x 13" W

OVERFLOW SCUPPER

(TYP)

REMOVE

EXISTING

WALL

MATERIALS

AS REQ'D TO

PROVIDE NEW

4" H x 13" W

OVERFLOW

SCUPPER

(TYP)

REMOVE

EXISTING

WALL

MATERIALS

AS REQ'D TO

PROVIDE NEW

4" H x 13" W

OVERFLOW

SCUPPER

(TYP)

REMOVE EXISTING WALL

MATERIALS AS REQ'D TO

PROVIDE NEW 4" H x 13" W

OVERFLOW SCUPPER (TYP)

REMOVE EXISTING

WALL MATERIALS AS

REQ'D TO PROVIDE

NEW 4" H x 7" W

OVERFLOW SCUPPER

(TYP)

NOTES: 1. REFERENCE ROOF SCHEDULE (A150) FOR NEW ROOF COMPOSITION (TYP)

2. NEW EMERGENCY OVERFLOW SCUPPERS ARE TO BE PROVIDED AND SIZED AS NOTED ON ROOF PLANS.

PROVIDE AT SAME HEIGHT AFF FOR LEVEL APPEARANCE ON EXTERIOR ELEVATIONS (TYP)

CONTRACTOR IS RESPONSIBLE FOR COORDINATING

ROOFING ACTIVITIES WITH P&HCC.

ALL NEW METAL EDGING, FLASHINGS, AND TRIM TO BE ATTACHED

TO SUBSTRATE WITH A CONTINUOUS CONCEALED CLEAT SYSTEM.

FACE NAILING WILL NOT BE ACCEPTED AS A MEANS OF

ATTACHMENT.

METAL EDGE FLASHINGS ARE TO BE SHOP FABRICATED

WITH PREMADE CORNERS.

TAPERED POLYISOCYANURATE INSULATION; SLOPE TO BE 1/4" PER

FOOT @ CRICKETS). WITH APPROVAL OF AE THE STIPULATED SLOPE

MAY BE REDUCED IF EXISTING CONDITIONS WARRANT THE CHANGE.

NO STRUCTURAL MEMBERS SHALL BE CUT OR

MODIFIED UNLESS PRIOR WRITTEN APPROVAL FROM

ARCHITECT/ENGINEER HAS BEEN OBTAINED.

ALL NEW WORK SHALL COMPLY WITH 2021 VIRGINIA

UNIFORM STATEWIDE BUILDING CODE.

ALL BALLAST INCLUDING PRECAST PAVERS SHALL BE

COMPLETELY REMOVED FROM THE ROOF BY THE

CONTRACTOR AND PROPERLY DISPOSED OF OFF SITE

UNLESS NOTED OTHERWISE.

RAISE ROOFTOP EQUIPMENT, CONDUIT, PIPING, AND

STANDARDS INCLUDING MECHANICAL UNITS ETC. AS

NECESSARY TO ACCOMMODATE 8" MIN VERTICAL CURB

HEIGHT PER NRCA GUIDELINES WITH NEW INSULATION

THICKNESS AND CURBS PROVIDED.

CONTRACTOR SHALL IDENTIFY LOW PLACES IN ROOF DECK

FOLLOWING TEAR-OFF. LOW AREAS SHALL BE BUILT-UP WITH

POLYISOCYANURATE INSULATION PRIOR TO INSTALLATION OF

BASE LAYER INSULATION.

ROOF DRAINS ARE TO BE REMOVED AND REPLACED IN KIND WITH

NEW ROOF DRAINS (TYP U.O.N.). AT ROOF #2, EXISTING 3" ROOF

DRAINS ARE TO BE REMOVED AND REPLACED WITH NEW 4" ROOF

DRAINS (TYP). AT ROOFS #3 & #4, EXISTING 2" ROOF DRAINS ARE

TO BE REMOVED AND REPLACED WITH NEW 2" ROOF DRAINS.

CONNECT NEW ROOF DRAINS TO EXISTING RAIN LEADER PIPES

BELOW EXISTING ROOF DECK AND ABOVE EXISTING CEILINGS.

FIELD VERIFY EXISTING DRAIN AND PIPE SIZES (TYP). NEW ROOF

MEMBRANE IS TO BE FLASHED INTO NEW DRAIN SYSTEM AT NEW

ROOF DRAINS AND ALSO FLASHED IN AT NEW AND EXISTING

THROUGH WALL PARAPET OVERFLOW SCUPPERS. APPLIES TO

ALL ROOF DRAINS AND SCUPPERS (TYP).

EXISTING VENTS AND ROOF TOP EQUIPMENT ARE TO

REMAIN UNLESS OTHERWISE NOTED

EXISTING THROUGHWALL FLASHING AND COUNTERFLASHING IS

TO REMAIN FOR RE-USE AT VERT WALLS TO ROOF

TERMINATIONS. CONTRACTOR TO RAKE OUT SEALANT JOINTS,

CLEAN AND RE-SEAL IN ACCORDANCE WITH SPECIFICATIONS.

PIPE, CONDUIT AND DUCT SUPPORTS ARE TO BE ADJUSTED AS

REQUIRED AND RE-USED. PROVIDE NEW WALKWAY PADS AS

SHOWN (TYP)

GN-21

GN-19

GN-18

GN-17

GN-16

GN-15

GN-14

GN-13

GN-12

GN-7

GN-8

GN-9

GN-10

GN-11

SUBMIT SHOP DRAWINGS FOR THE PROPOSED FIXED HEIGHT AND

TAPERED INSULATION LAYOUT AREAS. INDICATE INSULATION AND

TAPERED INSULATION w/ BASE LAYER FOR APPROVAL. SEE

SPECIFICATIONS.

SQUARE FOOTAGE AND DIMENSIONS ARE APPROXIMATE.

CONTRACTOR SHALL FIELD VERIFY EXISTING SITE CONDITIONS AND

DIMENSIONS PRIOR TO ORDERING MATERIAL AND THE START OF

CONSTRUCTION.

DETAILS ARE BASED ON A FLEXIBLE SHEET MEMBRANE (F.S.M.)

SYSTEM OVER FIXED HEIGHT POLYISOCYANURATE INSULATION ON

SLOPED STRUCTURE (R 30 MIN AT DRAINS; TYP U.O.N.). AREAS

WHERE ADDITIONAL TAPERED INSULATION IS REQUIRED FOR

OPTIMAL DRAINAGE PATTERN ARE AS INDICATED AND AS

REQUIRED. SEAMS ARE TO BE AS SPECIFIED.

CONTRACTOR SHALL NOT SPOT LOAD ANY AREA OF ROOF IN

EXCESS OF 20 POUNDS/SQUARE FOOT (PSF) OR

WITHIN 6'-0" OF ROOF EDGE.

DEBRIS SHALL BE REMOVED FROM PROJECT DAILY BY CHUTE

HOIST OR OTHER DEVICE THAT WILL CONVEY DEBRIS IN A

CONTROLLED DESCENT TO GRADE

IF A CONFLICT BETWEEN THE DESIGN DOCUMENTS, DETAILS,

RECOMMENDATIONS OR MANUFACTURER SHALL ARISE, THE MORE

STRINGENT SHALL PREVAIL.

ALL EXIST NON-ALUMINUM, NON-COPPER ROOFTOP EQUIPMENT TO

REMAIN SHALL BE CLEANED, PRIMED, AND PAINTED, UNLESS

NOTED OTHERWISE. SEE SPECIFICATIONS, SECTION 099000.

GN-22 EXISTING METAL PARAPET COPING, EDGE METAL (EXCLUDING EXISTING

THROUGH WALL SCUPPERS), AND BLOCKING IS TO BE REMOVED IN ITS

ENTIRETY AND REPLACED WITH NEW AS REQUIRED FOR PROVIDING

NEW PARAPET DETAILS AS SHOWN (TYP U.O.N.)

ADJUST CRICKETS AROUND ROOFTOP EQUIPMENT AS NECESSARY WHERE

EQUIPMENT ENCROACHES INTO THE DRAINAGE FIELD VALLEYS AS REQUIRED TO

PROVIDE UNOBSTRUCTED POSITIVE DRAINAGE PATH TO ROOF DRAINS (TYP)

GN-23:

GN-24:

GN-25:

INSTALL ROOF DRAINS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.

COORDINATE FLASHING WORK WITH CONTRACTOR AND ROOF MATERIALS AND

SUBSTRATE. MAINTAIN INTEGRITY OF ROOFING MEMBRANE MATERIAL AND INSTALL AT

LOW POINTS OF SURFACE AREAS TO BE DRAINED.

ROOF DRAINS SHALL BE MADE WATERTIGHT WITH HYDRAULIC CEMENT GROUT

WHERE DRAIN RECEIVER MEETS ROOF DECK PRIOR TO INSULATION, ROOFING

MATERIAL AND FLASHING INSTALLATIONS.

FIELD VERIFY SIZES OF EXISTING RAIN LEADERS AND COORDINATE NEW ROOF

DRAIN OUTLET SIZES.

GN-26:

REMOVE NO MORE EXISTING ROOFING THAN WHAT CAN BE COVERED IN ONE DAY BY

NEW ROOFING SO THAT BUILDING INTERIOR REMAINS WATERTIGHT AND

WEATHERTIGHT THROUGHOUT CONSTRUCTION.

GN-27:

GN-20 EXISTING THROUGH WALL OVERFLOW SCUPPERS ARE TO REMAIN. IF ANY ARE

PARTIALLY BLOCKED BY NEW INSULATION HEIGHTS, PROVIDE 12":12" TAPERED

TRANSITION FROM TOP OF ADJACENT INSULATION TO BOTTOM OF SCUPPER SLEEVE

PRIOR TO EXTENDING MEMBRANE INTO SCUPPER INLET (REF DETAIL 6/A152 SIM; TYP).

NEW THROUGH WALL OVERFLOW SCUPPERS ARE TO BE PROVIDED WHERE SHOWN

(TYP; REF ROOF PLANS 1/ A150, A151, AND DETAILS 6 & 6A/A152)

GN-28: PROVIDE NON PENETRATING GUARDRAIL PROTECTION AT ALL SERVICEABLE ROOF TOP

EQUIPMENT THAT IS LESS THAN 10'-0" FROM THE ROOF EDGE WHERE SHOWN ON ROOF

PLANS. FIELD VERIFY REQUIRED LOCATIONS (TYP).

GN-29: FOR FIRE HAZARDS DURING DEMOLITION AND CONSTRUCTION THE PROVISIONS OF

THE 2021 INTERNATIONAL FIRE CODE (CHAPTER 33) ARE TO BE STRICTLY OBSERVED

AS WELL AS VCC SECTION 3302.3 AND VEBC SECTIONS 1201.5 AND 1210.7 (TYP).

GN-30: COMPLIANCE WITH NFPA-241-2019 IS REQUIRED FOR CONDITIONS NOT COVERED BY

THE IFC; IFC SECTION 3301.1 (TYP).

GN-31: THE REQUIREMENTS OF THE VEBC AND THE INTERNATIONAL FIRE CODE (IFC) SHALL BE

STRICTLY OBSERVED TO SAFEGUARD AGAINST ALL FIRE HAZARDS ATTENDANT UPON

CONSTRUCTION OPERATIONS. VEBC SECTION 1204.2 & VCC SECTION 3309.2 (TYP).

FULLY ADHERED FSM OVER TAPERED AND/OR FIXED HEIGHT POLYISOCYANURATE INSUL

(WHERE INDICATED) OVER CONTINUOUS VAPOR BARRIER ON ROOF DECK (TYP)

THE ROOF DESIGN IS BASED ON A FULLY ADHERED FLEXIBLE SHEET MEMBRANE (F.S.M.) SYSTEM OVER FIXED HEIGHT AND/OR TAPERED (1/4" : 1'-0" TYP U.O.N.)

POLYISOCYANURATE INSULATION ON CONTINUOUS BASE LAYER (R:30 MINIMUM AT DRAINS TYP U.O.N.) OVER VAPOR BARRIER ON ROOF DECK AND

STRUCTURE (TYP U.O.N.)

FULLY ADHERED FSM ROOF ON RIGID INSULATION

BALLASTED FSM ROOF ON RIGID INSULATION

TEAR OFF ROOF

MATERIALS TO ROOF DECK

TEAR OFF ROOF

MATERIALS TO ROOF DECK

TEAR OFF ROOF

MATERIALS TO ROOF DECK

TEAR OFF ROOF

MATERIALS TO ROOF DECK

TEAR OFF ROOF

MATERIALS TO ROOF DECK

FULLY ADHERED FSM ROOF ON RIGID INSULATION

FULLY ADHERED FSM ROOF ON RIGID INSULATION

FULLY ADHERED FSM ROOF ON RIGID INSULATION

FULLY ADHERED FSM OVER TAPERED AND/OR FIXED HEIGHT POLYISOCYANURATE INSUL

(WHERE INDICATED) OVER CONTINUOUS VAPOR BARRIER ON ROOF DECK (TYP)

FULLY ADHERED FSM OVER TAPERED AND/OR FIXED HEIGHT POLYISOCYANURATE INSUL

(1 1/2" DEPTH AT ROOF DRAIN) OVER CONTINUOUS VAPOR BARRIER ON ROOF DECK (TYP)

FULLY ADHERED FSM OVER TAPERED AND/OR FIXED HEIGHT POLYISOCYANURATE INSUL

(WHERE INDICATED) OVER CONTINUOUS VAPOR BARRIER ON ROOF DECK (TYP)

ROOF #3 AND #4: FIELD TO BE FIXED HEIGHT AND TAPERED POLYISOCYANURATE INSULATION OVER VAPOR BARRIER ON ROOF DECK AND STRUCTURE. TAPERED TO BE 1/8": 1'-0" (TYP). POLYISOCYANURATE

INSULATION DEPTH AT DRAINS TO BE 1 1/2" TYP.

FULLY ADHERED FSM OVER TAPERED AND/OR FIXED HEIGHT POLYISOCYANURATE INSUL

(1 1/2" DEPTH AT ROOF DRAIN) OVER CONTINUOUS VAPOR BARRIER ON ROOF DECK (TYP)

SHADING ON ROOF PLANS INDICATE AREAS WHERE TAPERED POLYISOCYANURATE INSULATION IS TO BE USED OVER FIXED HGT POLYISOCYANURATE INSULATION AS REQUIRED TO PROVIDE POSITIVE DRAINAGE TO

ROOF DRAINS AND AS SCHEDULED ABOVE (TYP)

SL = 1/4":1'-0"

(TYP U.O.N.)

TYP

A151

2" RD

NOT FOR

CONSTRUCTION

SHEET NUMBER:

STATE PROJECT NO.:

SHEET REVISIONS:

SHEET ISSUE DATE:

SHEET NAME:

DRAWN BY:CHECKED BY:

Spectrum Design Project No.:

PROJ. MGR.:

KEY PLAN:

PROJECT PHASE:

J:

\2

\2 .4

A rc h\

2_

A

0.

d w g

, P lo tt ed

B y:

d m cc a rt, P lo tte d:

J an

7,

- 7 :4

5a m

23112

COMMUNITY COLLEGE

a r c h i t e c t s e n g i n e e r s

Plaza Suite 1 10 Church Avenue, SE Roanoke, VA 24011 540.342.6001

SPECTRUMPC.COM

A150

GEG DCV DGM

CONSTRUCTION DOCUMENTS

02.03.2025

'-1

0"

70'-0"38'-0" 95'-0"

'-8

1'

-0

158'-6"8'-0"36'-6"

'-0

'-1 0"

'-8

ROOF 5

TEAR OFF TO

DECK

ROOF 5

TEAR OFF TO

DECK

RI

DG

E

RI

DG

E

RI

DG

E

RI

DG

E

RI

DG

E

RI

DG

E

RI

DG

E

GAS LINE OVER

PARAPET

GAS LINE

GA

S

LI

NE

GA

S

LI

NE

GA

S

LI

NE

EXIST SLOPED STRUCTURE

1/4": 1'-0" (TYP)

EXIST SLOPED STRUCTURE

1/4": 1'-0" (TYP)

EXIST SLOPED STRUCTURE

1/4": 1'-0" (TYP)

EXIST SLOPED STRUCTURE

1/4": 1'-0" (TYP)

1/4":1'-0"1/4":1'-0"

1/4":1'-0"1/4":1'-0"

1/4":1'-0"1/4":1'-0"

1/4":1'-0"1/4":1'-0"

ROOF 2

REF A150 FOR CONT

SN-1

SN-1

SN-1

SN-1

SN-1

EXIST SLOPED STRUCTURE

1/4": 1'-0" (TYP)

EXIST SLOPED STRUCTURE

1/4": 1'-0" (TYP)

EXIST SLOPED STRUCTURE

1/4": 1'-0" (TYP)

EXIST ROOF HATCH

w/ GUARD TO

REMAIN (TYP)

RI

DG

E

RI

DG

E

RI

DG

E

RI

DG

E

PARTIAL ROOF PLAN

8' 4' 0 8' 16'

GRAPHIC SCALE: 1/8" = 1'-0"

A152

TYP

A152

TYP

SIM

A152

6A

SIM

A152

6A

SIM

A152

6A

TYP

A152

TYP

A152

TYP

A152

SIM

A152

TYP

A152

TYP

A152

6A

TYP

A152

6A

SIM

A152

SIM

A152

SIM

A152

SIM

A152

TYP

A152

TYP

A152

TYP

A152

SIM

A152

SIM

A152

VERTICAL TERM BARVERTICAL TERM BAR

CRICKET

SIM

A152

6A

SIM

A152

SIM

A152

SIMA152

SIMA152

TYPA152

TYP

A152

A152

TYPA152

TYPA152

TYPA152

WALKWAY PADS

(TYP)

TYPA152

TYPA152

A152

TYP

TYPA152

PROVIDE PREFINISHED

SURFACE APPLIED ALUM

COUNTERFLASHING @

VERT WALL TERMINATION

(REF DETAIL 6B/A152; TYP)

PROVIDE PREFINISHED

SURFACE APPLIED ALUM

COUNTERFLASHING @

VERT WALL TERMINATION

(REF DETAIL 6B/A152; TYP)

PROVIDE PREFINISHED

SURFACE APPLIED ALUM

COUNTERFLASHING @ VERT

WALL TERMINATION (REF

DETAIL 6B/A152 SIM)

4" RD

4" RD

4" RD

4" RD

4" RD

4" RD

4" RD

4" RD

4" RD

4" RD

4" RD

4" RD

4" RD

4" RD

ROOF 5

TEAR OFF TO

DECK

ROOF 1

REF A150 FOR CONT

TYP

SIM

A152

6A

TYP

A152

6A

EXIST OVERFLOW TO

REMAIN. TIE NEW

FSM IN AS REQ'D

(TYP)

EXIST OVERFLOW TO

REMAIN. TIE NEW

FSM IN AS REQ'D

(TYP)

EXIST OVERFLOW TO

REMAIN. TIE NEW

FSM IN AS REQ'D

(TYP)

EXIST OVERFLOW TO

REMAIN. TIE NEW

FSM IN AS REQ'D

(TYP)

PROVIDE NON

PENETRATING SAFETY

GUARDRAIL (REF

SPECIFICATIONS (TYP)

PROVIDE NON

PENETRATING SAFETY

GUARDRAIL (REF

SPECIFICATIONS (TYP)

PROVIDE NON

PENETRATING SAFETY

GUARDRAIL (REF

SPECIFICATIONS (TYP)

SIM

A152

6A

SIM

A152

6A

SIM

A152

6A

TYP

A152

6A

TYP

A152

6A

TYP

A152

6A

REMOVE EXISTING

WALL MATERIALS

AS REQ'D TO

PROVIDE NEW

4" H x 13" W

OVERFLOW

SCUPPER (TYP)

REMOVE EXISTING

WALL MATERIALS

AS REQ'D TO

PROVIDE NEW

4" H x 13" W

OVERFLOW

SCUPPER (TYP)

REMOVE EXISTING

WALL MATERIALS

AS REQ'D TO

PROVIDE NEW

4" H x 13" W

OVERFLOW

SCUPPER (TYP)

REMOVE EXISTING

WALL MATERIALS

AS REQ'D TO

PROVIDE NEW

4" H x 13" W

OVERFLOW

SCUPPER (TYP)

REMOVE EXISTING

WALL MATERIALS

AS REQ'D TO

PROVIDE NEW

4" H x 13" W

OVERFLOW

SCUPPER (TYP)

REMOVE EXISTING

WALL MATERIALS

AS REQ'D TO

PROVIDE NEW

4" H x 13" W

OVERFLOW

SCUPPER (TYP)

REMOVE EXISTING WALL

MATERIALS AS REQ'D TO

PROVIDE NEW

4" H x 13" W OVERFLOW

SCUPPER (TYP)

REMOVE EXISTING

WALL MATERIALS

AS REQ'D TO

PROVIDE NEW

4" H x 13" W

OVERFLOW

SCUPPER (TYP)

REMOVE EXISTING

WALL MATERIALS

AS REQ'D TO

PROVIDE NEW

4" H x 13" W

OVERFLOW

SCUPPER (TYP)

REMOVE EXISTING

WALL MATERIALS

AS REQ'D TO

PROVIDE NEW

4" H x 13" W

OVERFLOW

SCUPPER (TYP)

EXIST GAS LINE TO

REMAIN (TYP)

REMOVE EXISTING

WALL MATERIALS

AS REQ'D TO

PROVIDE NEW

4" H x 13" W

OVERFLOW

SCUPPER (TYP)

PROVIDE NEW

ROOF LADDER

(TYP)

NOTES: 1. REFERENCE ROOF SCHEDULE (A150) FOR NEW ROOF COMPOSITION (TYP)

PROVIDE AT SAME HEIGHT AFF FOR LEVEL APPEARANCE ON EXTERIOR ELEVATIONS (TYP)

2. NEW EMERGENCY OVERFLOW SCUPPERS ARE TO BE PROVIDED AND SIZED AS NOTED ON ROOF PLANS.

SL = 1/4":1'-0"

(TYP, U.O.N.)

TYP

A151

2" RD

NOT FOR

CONSTRUCTION

SHEET NUMBER:

STATE PROJECT NO.:

SHEET REVISIONS:

SHEET ISSUE DATE:

SHEET NAME:

DRAWN BY:CHECKED BY:

Spectrum Design Project No.:

PROJ. MGR.:

KEY PLAN:

PROJECT PHASE:

J:

\2

\2 .4

A rc h\

2_

A

1.

d w g

, P lo tt ed

B y:

d m cc a rt, P lo tte d:

J an

7,

- 7 :4

6a m

23112

COMMUNITY COLLEGE

a r c h i t e c t s e n g i n e e r s

Plaza Suite 1 10 Church Avenue, SE Roanoke, VA 24011 540.342.6001

SPECTRUMPC.COM

A151

GEG DCV DGM

CONSTRUCTION DOCUMENTS

02.03.2025

PATRICK & HENRY

SHEET NOTES:

SN-1: REMOVE EXISTING ABANDONED ROOF CURB AND PATCH EXISTING

ROOF DECK BY THE FOLLOWING PROCEDURE PRIOR TO RE ROOF:

STEEL DECK:

PATCH EXISTING OPENINGS IN STEEL DECK PRIOR TO RE ROOF.

OVERLAY EXISTING DECK PENETRATIONS w/22 GA (MIN) DECKING

MATCHING EXISTING PROFILE. NEW DECK SHALL OVERLAP THE

EXISTING DECK PENETRATIONS BY A MINIMUM OF TWO FLUTES

ALONG THE SIDES AND SPAN TO CLOSEST STEEL JOIST BEYOND

THE ENDS OF THE PENETRATIONS. FASTEN TO STEEL JOISTS w/

PDFS SPACED AT 12" OC MAX THRU THE EXISTING DECK WHERE

APPLICABLE. FASTEN NEW DECK TO EXISTING DECK ALONG THE

SIDES WITH 2 ROWS OF #10 SCREWS @ 12" OC STAGGERED ALONG

THE TOP FLUTE.

MECH EQUIP/ROOF HATCH

CURB SUPPORT TERMINATION (TYP)

VENT PIPE/POST

FIELD FLASH TERMINATION (TYP)

8" M

IN

C

UR

B

HG

T

AB

V

HI

GH

ES

T

AD

J

M

EM

BR

AN

E

RO

OF

T

ER

M H

GT

8"

M

IN

HOT STACK

TERMINATION (TYP)

8" M

IN

NEW RAIN HOOD; SEAL

TOP EDGE (TYP)

EXISTING PIPE, ETC.

CLAMPING RING

METAL DAM; MECH.

ATT. METAL DAM @ 12"

O.C., TYP.

EXISTING

ROOF DECK

PT WD BLOCKING

AS REQ'D

TIE NEW DAM FLASHING INTO

FULLY ADHERED FSM MEMBRANE

SYSTEM

BONDING ADHESIVE, TYP.

LAP SEALANT, TYP.

SPLICE ADHESIVE, TYP.

BONDING ADHESIVE, TYP.

FSM FLASHING, TYP.

4"

PARAPET WALL

TERMINATION (TYP)

FULLY ADHERED FSM ROOF

MEMBRANE OVER CONT BASE

LAYER RIGID INSUL (R-30 MIN)

AND TAPERED ROOF INSUL AS

REQ'D ON CONT VAPOR

BARRIER OVER ROOF DECK;

REF ROOF PLAN A150 FOR

ADDITIONAL INFO

FSM ROOF MEMBRANE

FLASHING

LAP SEALANT TYP @

EDGES AS SHOWN

EXIST WALL

FIELD VERIFY

DIMENSIONS (TYP)

REINF PERIMETER PLATE; SET IN WATER

CUTOFF MASTIC AND MECH ATT @ 12" OC

TYP

PARAPET WALL/SCUPPER

TERMINATION (TYP)

FSM ROOF MEMBRANE

FLASHING EXTEND INTO

EXIST SCUPPER AS SHOWN

(TYP)

REINF PERIMETER PLATE; SET IN

WATER CUTOFF MASTIC AND MECH ATT

@ 12" OC (TYP)

FULLY ADHERED FSM ROOF

MEMBRANE OVER CONT BASE

LAYER RIGID INSUL (R-30 MIN)

AND TAPERED ROOF INSUL ON

CONT VAPOR BARRIER OVER

ROOF DECK; REF ROOF PLANS

A150 & A151 (TYP)

PREFINISHED

ALUM ROOF

EDGE OVER

CONCEALED

CLEAT; MECH

ATT @ 12" OC

MAX (TYP)

EXTEND FSM OVER PARAPETS TYP AS SHOWN

PT WOOD BLOCKING TYP

EXIST WALL

FIELD VERIFY

DIMENSIONS

(TYP)

FSM ROOF

MEMBRANE

FLASHING

LAP SEALANT TYP @ EDGES AS SHOWN

SLOPE

EXISTING

OVERFLOW

SCUPPER SLEEVE

TO REMAIN.

RESEAL EXTERIOR

PERIMETER (TYP)

PITCH POCKET (PP)

TERMINATION (TYP)

AP

PR

OX

" V .I.

F.

ROOF TO VERT

WALL TERMINATION (TYP)

EXIST THROUGHWALL FLASHING & COUNTER

FLASHING TO REMAIN. PROVIDE TERM BAR

TERMINATION AT WALL AS SHOWN. SET IN WATER CUT

OFF MASTIC & MECH ATT @ 12" OC (TYP)

FULLY ADHERED FSM ROOF

MEMBRANE OVER CONT BASE

LAYER RIGID INSUL (R-30 MIN)

AND TAPERED ROOF INSUL AS

REQ'D ON CONT VAPOR

BARRIER OVER ROOF DECK;

REF ROOF PLAN A150 & A151

FOR ADDITIONAL INFO

FSM ROOF MEMBRANE FLASHING

SPLICE ADHESIVE

LAP SEALANT TYP @

EDGES AS SHOWN

EXIST WALL

FIELD VERIFY DIMENSIONS

(TYP)

REINF PERIMETER PLATE; SET IN WATER

CUTOFF MASTIC AND MECH ATT @ 12" OC

TYP

SLOPE

ROOF DRAIN

TERMINATION (TYP)

ROOF DRAIN

STRAINER

C DRAIN

FULLY ADHERED FSM; EXTEND

1/2" MIN INTO DRAIN BOWL

R-

M

IN

D

RA

IN

S (N

.T .S

. T

YP

SLOPESLOPE

R-

M

IN

R-

M

IN

R-

M

IN

R-

M

IN

R-

M

IN

R-

M

IN

R-

M

IN

FI

EL

D

VE

RF

Y

PA

RA

PE

T

HE

IG

HT

(T

YP

FI

EL

D

VE

RF

Y

PA

RA

PE

T

HE

IG

HT

(T

YP

R-

M

IN

R

OO

F

#1

1 2"

M

IN

IN

SU

L

DE

PT

H

R

OO

F

#3

PARAPET WALL TO

VERTICAL WALL TERMINATION (TYP)

PREFINISHED ALUM

ROOF EDGE OVER

CONCEALED CLEAT;

MECH ATT @ 12" OC

MAX (TYP)

EXTEND FSM UP VERT @ WALL

BEYOND. PROVIDE TERM BAR @

TOP EDGE (TYP AS SHOWN)

EXIST WALL

FIELD VERIFY DIMENSIONS

(TYP)

PROVIDE VERT TERM

BAR BEYOND (TYP)

PROVIDE VERT TERM

BAR BEYOND (TYP)

PREFINISHED 4" SURFACE APPLIED ALUM

COUNTERFLASHING OVER VERT MEMBRANE @ VERT WALL

BEYOND; SEAL TOP EDGE; MECH ATT @ 4" OC MAX (TYP)

6" M

IN

V

ER

T

M

EM

BR

AN

E

PREFINISHED ALUM ROOF EDGE OVER

CONCEALED CLEAT; MECH ATT @ 12" OC

MAX (TYP)

BONDING ADHESIVE

BONDING ADHESIVE

SPLICE ADHESIVE

SPLICE

ADHESIVE

BONDING

ADHESIVE

BONDING ADHESIVE

SPLICE ADHESIVE

BONDING ADHESIVE

SPLICE ADHESIVE

REINF PERIMETER PLATE; SET IN WATER

CUTOFF MASTIC AND MECH ATT @ 12" OC

TYP

SPLICE ADHESIVE

BONDING ADHESIVE

BONDING ADHESIVE

FULLY ADHERED FSM ROOF

MEMBRANE. EXTEND OVER

PARAPETS AS SHOWN (TYP)

BONDING ADHESIVE

SPLICE ADHESIVE

PT WOOD BLOCKING TYP

NOTE: IF EXISTING EQUIPMENT CURB ALLOWS 8" MIN CURB HEIGHT ABOVE

NEW ROOF MEMBRANE, EXISTING CURB MAY REMAIN. IF NOT, NEW

INSULATED CURB SHALL BE INSTALLED ON NEW P.T. WOOD BLOCKING.

NEW ROOF DRAIN RD.

SEE SPECIFICATIONS

NOTE: EXISTING ROOF DRAIN ASSEMBLIES INCLUDING BODIES, STRAINERS,

FLASHING RINGS, ETC. SHALL BE REMOVED AND REPLACED WITH NEW 4"

ROOF DRAIN ASSEMBLIES (TYP EXCEPT AT ROOFS #3 & #4). ROOFS #3 & #4

DRAINS ARE TO BE REMOVED AND REPLACED WITH NEW 2" ROOF DRAIN

ASSEMBLIES AS NOTED. CONNECT NEW ROOF DRAINS TO EXISTING RAIN

LEADER PIPES BELOW EXISTING ROOF DECK AND ABOVE EXISTING

CEILINGS. APPLIES TO ALL ROOF DRAINS.

NOTE: SEE DETAIL REFERENCE

ON BOTH SHEETS A150 AND A151

PARAPET WALL/SCUPPER

TERMINATION (TYP)

FSM ROOF MEMBRANE

FLASHING EXTEND INTO

SCUPPER AS SHOWN (TYP)

REINF PERIMETER PLATE; SET IN

WATER CUTOFF MASTIC AND MECH ATT

@ 12" OC (TYP)

FULLY ADHERED FSM ROOF

MEMBRANE OVER CONT BASE

LAYER RIGID INSUL (R-30 MIN)

AND TAPERED ROOF INSUL ON

CONT VAPOR BARRIER OVER

ROOF DECK; REF ROOF PLANS

A150 & A151 (TYP)

M

AT

CH

E

XI

ST

F

AC

E D

EP

TH

O F

CO

PI

NG

R

EM

OV

ED

T

YP

PREFINISHED

ALUM ROOF

EDGE OVER

CONCEALED

CLEAT; MECH

ATT @ 12" OC

MAX (TYP)

EXTEND FSM OVER PARAPETS TYP AS SHOWN

PT WOOD BLOCKING TYP

EXIST WALL

FIELD VERIFY

DIMENSIONS

(TYP)

FSM ROOF

MEMBRANE

FLASHING

LAP SEALANT TYP @ EDGES AS SHOWN

PROVIDE PREFINISHED ALUM

RECTANGULAR THROUGH WALL

OVERFLOW SCUPPER SLEEVE w/

MTG FLANGE AT PARAPET INTERIOR

AS SHOWN. REF ROOF PLANS FOR

REQUIRED LOCATIONS AND SIZES.

SEAL EXTERIOR PERIMETER (TYP)R-

M

IN

BONDING ADHESIVE

BONDING ADHESIVE

SPLICE ADHESIVE

SPLICE

ADHESIVE

BONDING

ADHESIVE

PROVIDE PREFINISHED BRAKE METAL

WRAPPED P.T. 1x2 ESCUTCHEON

PLATE. BRAKE METAL TO MATCH

SCUPPER COLOR (SEAL PERIMETER,

TYP)

1/

2"

CONT BASE LAYER

RIGID INSUL (R-30

MIN) AND TAPERED

ROOF INSUL (TYP)

CONT BASE LAYER

RIGID INSUL (R-30

MIN) AND TAPERED

ROOF INSUL (TYP)

CONT BASE LAYER

RIGID INSUL (R-30

MIN) AND TAPERED

ROOF INSUL (TYP)

CONT BASE LAYER

RIGID INSUL (R-30

MIN) AND TAPERED

ROOF INSUL (TYP)

M

AT

CH

E

XI

ST

F

AC

E D

EP

TH

O F

CO

PI

NG

R

EM

OV

ED

F

.V

TY

P)

M

AT

CH

E

XI

ST

F

AC

E D

EP

TH

O F

CO

PI

NG

R

EM

OV

ED

T

YP

M

AT

CH

E

XI

ST

F

AC

E D

EP

TH

O F

CO

PI

NG

R

EM

OV

ED

F

.V

(T

YP

2 1/2"

2'-0"

1' -0

" T

YP

" M

AX

1' -0

" T

YP

7"

MIN

7"

MIN

3/4" Ø STEEL NON SLIP RUNGS

@ 12" OC (TYP)

2 1/2" x 1/2" STEEL

PLATE RAILS (TYP)

FLARE RAILS TO 24"

WIDTH TYP @ TOP

RUNG

TOP OF FLARE

FLARE RAILS TO 24"

WIDTH TYP @ TOP

RUNG

3' -6

4"

2'-1"

FIELD

VERIFY

FIELD VERIFY

1'-4"

1'-5"

1' -0

" T

YP

3 8"

3' -6

3 8"

4"

HIGH ROOF #2

LOW ROOF #5

APPROX TOP OF

EXISTING

PARAPET WALL

2' -0

EQ

C

CR

OS

S

BA

R

1' -8

" F

IE

LD

V

ER

IF

Y

C

RU

NG

STEEL ROOF LADDER (ALL

WELDED CONSTRUCTION, GRIND

WELDS SMOOTH AND PAINT TYP)

SECTION ELEVATION

ROOF LADDER DETAIL

PROVIDE RUNG

PLATFORM OVER

PARAPET AS

SHOWN

ANGLE; 2" x 1.25" x 14"

BOTH SIDES OF

PLATFORM AS

SHOWN

PROVIDE RUNG

PLATFORM OVER

PARAPET AS

SHOWN

ANGLE; 2" x 1.25" x 14"

BOTH SIDES OF

PLATFORM AS

SHOWN

2 1/2" x 1/2" STEEL

PLATE STRINGERS (TYP OF 2)

C

RU

NG

C

RU

NG

C

RU

NG

C RUNG

C

RU

NG

PARAPET

WIDTH

& HGT

" M

AX

C

RU

NG

" M

AX

4' -8

" A

PP

RO

X

FI

EL

D

VE

RI

FY

5' -0

/4

" A

PP

RO

X, F

IE

LD

V

ER

IF

Y

RE

Q' D

LA

DD

ER

H

GT

C RUNG

2 1/2" W x 3/8" THK STEEL BENT PLATE

WALL BRACKET. WELD TO LADDER

STRINGERS, SET IN WATER CUT-OFF

MASTIC AND MECH ATT TO CMU

SUBSTATE w/ 12" Ø EPOXY ANCHS. SEAL

PERIMETER( TYP)

1' 6" 0

GRAPHIC SCALE: 3/4" = 1'-0"

1' 2'

SHEET NUMBER:

STATE PROJECT NO.:

SHEET REVISIONS:

SHEET ISSUE DATE:

SHEET NAME:

DRAWN BY:CHECKED BY:

Spectrum Design Project No.:

PROJ. MGR.:

KEY PLAN:

PROJECT PHASE:

J:

\2

\2 .4

A rc h\

2_

A

2.

d w g

, P lo tt ed

B y:

d m cc a rt, P lo tte d:

J an

7,

- 7 :4

8a m

23112

COMMUNITY COLLEGE

a r c h i t e c t s e n g i n e e r s

Plaza Suite 1 10 Church Avenue, SE Roanoke, VA 24011 540.342.6001

SPECTRUMPC.COM

A152

GEG DCV DGM

CONSTRUCTION DOCUMENTS

02.03.2025

File details come from the government source that posted it. Updated .