Performance Work Statement - LAMS Electrical Outlets_Redacted.pdf

PDF 166 KB Posted

Attached to
Electrical Outlets
Solicitation number
F3N0616023A006
Issued by

About this file

This is a Memorandum for Record from the Department of the Air Force 86th Airlift Wing (USAFE) documenting a Statement of Work for electrical outlet installation at Ramstein Air Base in Germany.

The contractor shall provide all labor, materials, equipment, supervision, and transportation necessary to install electrical outlets in two Large Area Maintenance Shelters (LAMS) supporting Air Transportation Function (ATF) cargo operations. The installation must serve mission-essential equipment including pallet build-up equipment, inspection tools, and operational support equipment. All work must comply with the National Electrical Code (NEC/NFPA 70) for U.S. requirements and Verband der Elektrotechnik (VDE) standards for German electrical installations. The contractor must provide qualified personnel, all required tools and materials, ensure safe and professional execution, and coordinate activities with the designated government representative. Work shall be performed Monday through Friday between 08:00 and 16:00, excluding both U.S. Federal and German holidays.

The electrical system shall include specific branded components: one Steidle outer distribution panel supporting both LAMS, two Spelsberg inner distribution panels (one per tent), Hager B16A fuses (6 per tent, 12 total) and 63A main fuses (1 per tent, 2 total), Weidmuller DIN rail terminal blocks (18 per tent, 36 total), and Merten Aquastar 230V moisture-proof weather-resistant electrical outlets (6 per tent, 12 total). All components must meet applicable electrical safety standards and be suitable for outdoor or semi-covered operational environments. Upon completion, the contractor must verify functionality of all outlets, ensure proper grounding and circuit protection, remove installation debris, and notify the government representative for final inspection. The work location is at the Large Area Maintenance Shelter adjacent to Building 3452 at Ramstein Air Base within a controlled and gated operational cargo facility requiring coordinated contractor access and compliance with installation security procedures.

View the file

Other files

File Type Posted
Salient-Characteristics LAMS Outlets.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF THE AIR FORCE

86TH AIRLIFT WING (USAFE)

05 March 2026

MEMORANDUM FOR RECORD

FROM:

SUBJECT: ATF Large Area Maintenance Shelter (LAMS) Electrical Outlets Installation

1. General Description.

The contractor shall provide all labor, materials, equipment, supervision, and transportation necessary to install electrical outlets in the Large Area Maintenance Shelter (LAMS) supporting Air Transportation Function (ATF) cargo operations.

The purpose of this installation is to provide reliable electrical power for mission-essential equipment used in cargo processing operations, including pallet build up equipment, inspection tools, and operational support equipment.

The contractor shall ensure all work complies with the National Electrical Code(NEC/NFPA 70) for U.S. requirements and Verband der Elektrotechnik (VDE) standards for German electrical installations.

2. General Requirement.

2.1. The contractor shall perform all work under their own responsibility and provide qualified personnel capable of performing electrical installation work.

The contractor shall:

- Provide all required tools, equipment, and materials.

- Ensure all electrical installations comply with applicable U.S. electrical standards, German electrical codes, and base civil engineering regulations.

This includes the NEC for U.S. requirements and VDE standards for German electrical installations.

- Ensure the work is performed in a safe and professional manner.

- Coordinate work activities with the designated government representative.

2.2. Special Requirements

The electrical outlets will be installed within the two LAMS utilized by the ATF for cargo staging, pallet build up, and equipment operations.

The installed outlets shall support equipment such as:

- Inspection equipment

- Cargo processing equipment

- Maintenance tools

The installation must ensure sufficient electrical capacity to support operational requirements while maintaining compliance with NEC for U.S. requirements and VDE for German requirements.

2.3. Electrical Installation Requirements

The contractor shall provide and install all materials necessary to support the installation of electrical outlets within the LAMS facility. All materials shall meet applicable electrical safety standards and be suitable for outdoor or semi-covered operational environments.

The electrical system shall include the following components:

• Electrical Distribution Components

- Outer Distribution Panel

Brand: Steidle (or equivalent)

Quantity: 1 unit supporting both LAMS

- Inner Distribution Panels

Brand: Spelsberg (or equivalent)

Quantity: 1 per tent (2 total)

• Circuit Protection Components

- Inlets in Inner Distribution – B16A Fuse

Brand: Hager (or equivalent)

Quantity: 6 per tent (12 total)

- Main Fuse Inner Distribution – 63A

Brand: Hager (or equivalent)

Quantity: 1 per tent (2 total)

• Electrical Connection Components

-DIN Rail Terminal Blocks

Brand: Weidmuller (or equivalent)

German reference: Reihenklemme

Quantity: 18 per tent (36 total)

• Electrical Outlets

-Moisture-proof Electrical Outlets – 230V

Brand: Merten Aquastar (or equivalent)

Type: Weather resistant/ moisture protected outlets suitable for outdoor or semi-covered environments.

Quantity: 6 per tent (12 total)

3. Hours of Operation

3.1. Work Schedule

All work shall be performed during normal work hours between 08:00 and 16:00 Monday through Friday. No work shall be performed on German or American holidays.

U.S. Federal Holidays

Date German Holidays Date

New Year’s Day Jan 1, 2026 New Year’s Day Jan 1, 2026 MLK Jr Day Jan 19, 2026 Good Friday Apr 3, 2026 President’s Day Feb 16, 2026 Easter Monday Apr 6, 2026 Memorial Day May 25, 2026 Labour Day May 1, 2026 Juneteenth Jun 19, 2026 Ascension Day May 14, 2026 Independence Day

Jul 3, 2026 Whit Monday May 25, 2026

Labor Day Sep 7, 2026 Corpus Christi Jun 4, 2026 Columbus Day Oct 12, 2026 German Unity

Day Oct 3, 2026

Veterans Day Nov 11, 2026 All Saints Day Nov 1, 2026 Thanksgiving Day

Nov 26, 2026 Christmas Eve Dec 24, 2026

Christmas Dec 25, 2026 Christmas Day Dec 25, 2026 New Year’s Eve Dec 31, 2026

3.2. Work Location

Large Area Maintenance Shelter adjacent to Building 3452 Ramstein Air Base.

The work area is located within controlled and gated operational cargo facility.

Contractor access to the site must be coordinated in advance with the ATF designated POC. Personnel and vehicles must comply with all installation access procedures and security requirements.

4. Completion Requirements.

4.1. Upon completion of installation, the contractor shall:

- Verify functionality of all electrical outlets.

- Ensure proper grounding and circuit protection.

- Remove all installation debris and equipment

- Notify the government representative for final inspection.

Work will be considered complete once the installation has been inspected and accepted by the government.