Paonia 2MG Tank Rehab Bid Drwgs.pdf

PDF 1003 KB Posted

Attached to
RFP 2025-04 2MG Tank Rehab
Solicitation number
2025-04
Issued by
Eagle County, Colorado

About this file

The document is a set of bid drawings for the 2MG Tank Rehabilitation project for the Town of Paonia, Colorado, prepared by SGM Engineering (SGM) in March 2025. The project involves comprehensive rehabilitation of a two-million-gallon (2MG) water storage tank located near the Lamborn Water Treatment Plant. The scope of work includes repairing the interior and exterior of the tank, replacing tank components, removing and replacing tank roofing, and performing all associated rehabilitation tasks. The project drawings provide detailed technical specifications for the tank repair, including overflow details, roof support sections, handrail configurations, and structural modifications.

The bid documents are designed for electronic submission via email to Cory Heiniger, the Public Works Director, with specific contact information provided for project inquiries. The project engineer is Brandyn Bair, P.E. (License #42640), and the drawings include a vicinity map showing the tank's location in a forested area. While specific budget details are not explicitly stated in the drawings, the comprehensive technical specifications suggest a significant infrastructure investment aimed at maintaining the town's potable water storage infrastructure. The drawings indicate precise engineering specifications, including structural steel requirements, welding standards, and detailed repair methodologies to ensure the tank meets current water storage and safety standards.

View the file

Other files

File Type Posted
Add#1_Paonia 2MG Tank Rehab.pdf PDF
Add#2_Paonia 2MG Tank Rehab.pdf PDF
Paonia 2MG Tank Project Manual.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

R ev is io n

Dwg No.

Job No.

Drawn by:

Date:

File:

PE:QC:

D at e By

Pr oj ec t M ile st on e:

2013-471.013

SF

03.18.25

BB

2MG Tank Rehabilitation

XX

Scope of Work

· Recoat interior and exterior of 2MG Tank

· Repair or replace misc. steel tank components

· Remove and replace tank hatch

· Remove and replace tank vent

2MG Tank

Project Contacts

Stefen Wynn, Town Administrator

Vicinity Map

Project Engineer stefenw@townofpaonia.com (970)527-4101

Brandyn Bair, P.E. 42640

BI

D

D R

AW

IN

G S

2MG Tank Rehabilitation

Town of Paonia

Town of Paonia

118 West Sixth Street, Suite 200 Glenwood Springs, CO 81601 970.945.1004 www.sgm-inc.com

214 Grand Ave.

Paonia, CO 81428

Bid Drawings March 2025

Title:

2M G

T an k R eh ab ilit at io n

Cover

To w n of

P ao ni a

W es t S ixt h St re et

, S ui te

G le nw oo d

Sp rin gs , C

O

0.

5.

w w

.s gm

-in c.

co m

Lamborn WTP

Cory Heiniger, PW Director coryheiniger_PW@townofpaonia.com (970)527-4101

AutoCAD SHX Text i:\2013\2013-471 town of paonia\013-2mg tank coating\H-Dwgs\Civil\PS-Sheetset\2MG Tank Rehabilitation.dwg Plotted: 3/19/2025 9:40 AM By: Scott Forrester Plotted: 3/19/2025 9:40 AM By: Scott Forrester3/19/2025 9:40 AM By: Scott Forrester By: Scott ForresterScott Forrester

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

UNCC 1-800-922-1987

AutoCAD SHX Text Sheet List Table

AutoCAD SHX Text Sheet Number

AutoCAD SHX Text Sheet Title

AutoCAD SHX Text

AutoCAD SHX Text Cover

AutoCAD SHX Text G1

AutoCAD SHX Text General Notes

AutoCAD SHX Text S1

AutoCAD SHX Text Tank Rehabilitation Plan

AutoCAD SHX Text S2

AutoCAD SHX Text Tank Rehabilitation Details is io n

Dwg No.

Job No.

Drawn by:

Date:

File:

PE:QC:

D at e By

Pr oj ec t M ile st on e:

2013-471.013

SF

03.18.25

BB

2MG Tank Rehabilitation

XX

G1

BI

D

D R

AW

IN

G S

Title:

2M G

T an k R eh ab ilit at io n

General Notes

To w n of

P ao ni a

W es t S ixt h St re et

, S ui te

G le nw oo d

Sp rin gs , C

O

0.

5.

w

.s gm

-in c.

i:\2013\2013-471 town of paonia\013-2mg tank coating\H-Dwgs\Civil\PS-Sheetset\2MG Tank Rehabilitation.dwg Plotted: 3/19/2025 9:40 AM By: Scott Forrester Plotted: 3/19/2025 9:40 AM By: Scott Forrester3/19/2025 9:40 AM By: Scott Forrester By: Scott ForresterScott Forrester

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

1. CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, AND ELEVATIONS PRIOR TO START OF CONSTRUCTION. NOTIFY CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, AND ELEVATIONS PRIOR TO START OF CONSTRUCTION. NOTIFY ENGINEER OF ANY DISCREPANCIES OR CONFLICTS FOUND IN THE CONTRACT DOCUMENTS AND/OR FIELD CONDITIONS. 2. NO HOLES, OPENINGS, OR ALTERATIONS TO THE EXISTING TANK MAY BE MADE WITHOUT PRIOR WRITTEN APPROVAL OF THE OWNER, NO HOLES, OPENINGS, OR ALTERATIONS TO THE EXISTING TANK MAY BE MADE WITHOUT PRIOR WRITTEN APPROVAL OF THE OWNER, ENGINEER, OR AS SHOWN ON THE DRAWINGS. 3. SHORING AND SCAFFOLDING REQUIRED FOR STRUCTURAL REPAIRS ARE THE CONTRACTOR'S RESPONSIBILITY. SHORING AND SCAFFOLDING REQUIRED FOR STRUCTURAL REPAIRS ARE THE CONTRACTOR'S RESPONSIBILITY. 4. AS-BUILT OR RECORD DRAWINGS WERE NOT AVAILABLE FOR THIS TANK. AS-BUILT OR RECORD DRAWINGS WERE NOT AVAILABLE FOR THIS TANK. 5. THE CONTRACTOR SHALL REVISE FRAMING MEMBERS, PLATES AND CONNECTIONS AS DIRECTED BY THE ENGINEER IN ORDER TO THE CONTRACTOR SHALL REVISE FRAMING MEMBERS, PLATES AND CONNECTIONS AS DIRECTED BY THE ENGINEER IN ORDER TO ACCOMMODATE ACTUAL FIELD CONDITIONS, DIMENSIONS AND GEOMETRY AT NO ADDITIONAL COST TO THE OWNER. 6. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF CONSTRUCTION WITH THIRD PARTY NON-DESTRUCTIVE TESTING COMPANY AND CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF CONSTRUCTION WITH THIRD PARTY NON-DESTRUCTIVE TESTING COMPANY AND OWNER HIRED WELDING AND COATING INSPECTORS. 7. CLEANING AND DISINFECTION OF THE TANK IS THE CONTRACTORS RESPONSIBILITY AND SHALL BE COORDINATED WITH THE OWNER CLEANING AND DISINFECTION OF THE TANK IS THE CONTRACTORS RESPONSIBILITY AND SHALL BE COORDINATED WITH THE OWNER PRIOR TO DISINFECTION. 8. THE CONTRACTOR SHALL CONTACT ALL UTILITY OWNERS TO VERIFY BOTH LOCATION AND DEPTH OF UTILITIES (WATER, FIBER OPTIC, THE CONTRACTOR SHALL CONTACT ALL UTILITY OWNERS TO VERIFY BOTH LOCATION AND DEPTH OF UTILITIES (WATER, FIBER OPTIC, DRAIN/OVERFLOW, GAS, PHONE, ELECTRIC, CABLE, AND OTHER) BEFORE ANY WORK BEGINS. CONTRACTOR SHALL BEAR THE RESPONSIBILITY FOR THE PROTECTION OF UTILITIES DURING CONSTRUCTION. NO ADDITIONAL PAYMENT WILL BE MADE FOR UTILITIES LOCATED BUT NOT SHOWN IN DRAWINGS. 9. THE CONTRACTOR WILL BE RESPONSIBLE FOR RESTORING DISTURBED AREAS AT THE SITE. THE CONTRACTOR WILL BE RESPONSIBLE FOR RESTORING DISTURBED AREAS AT THE SITE. 10. THE CONTRACTOR IS REQUIRED TO PROVIDE ALL SUBMITTALS AS OUTLINED IN THE CONTRACT DOCUMENTS. THE CONTRACTOR IS REQUIRED TO PROVIDE ALL SUBMITTALS AS OUTLINED IN THE CONTRACT DOCUMENTS. 11. THE EXISTING TANK INTERIOR AND EXTERIOR COATINGS CONTAIN LEAD-BASED PAINT. CONTRACTOR IS RESPONSIBLE FOR ALL LEAD THE EXISTING TANK INTERIOR AND EXTERIOR COATINGS CONTAIN LEAD-BASED PAINT. CONTRACTOR IS RESPONSIBLE FOR ALL LEAD ABATEMENT PROCEDURES AND DISPOSAL OF LEAD-BASED PAINT MATERIALS.

AutoCAD SHX Text

GENERAL NOTES:

AutoCAD SHX Text

STRUCTURAL STEEL INSTALLATION:

AutoCAD SHX Text

1. REFER TO SPECIFICATIONS 05100, 05510, AND 05523 FOR ADDITIONAL REQUIREMENTS. REFER TO SPECIFICATIONS 05100, 05510, AND 05523 FOR ADDITIONAL REQUIREMENTS. 2. FURNISH AND INSTALL TEMPORARY BRACING FOR NEW FRAMING AS NECESSARY TO PROVIDE STABILITY DURING ERECTION AND TO FURNISH AND INSTALL TEMPORARY BRACING FOR NEW FRAMING AS NECESSARY TO PROVIDE STABILITY DURING ERECTION AND TO PREVENT DISTORTION OR DAMAGE TO THE FRAMING DUE TO WIND, SEISMIC, OR ERECTION FORCES. 3. REMOVE TEMPORARY BRACING WHEN ERECTION IS COMPLETE. REMOVE TEMPORARY BRACING WHEN ERECTION IS COMPLETE. 4. FIELD WELDING SHALL BE DONE BY WELDERS CURRENTLY QUALIFIED AND APPROVED FOR THE PROCEDURES USED. NO WELDING FIELD WELDING SHALL BE DONE BY WELDERS CURRENTLY QUALIFIED AND APPROVED FOR THE PROCEDURES USED. NO WELDING SHALL BE COMPLETED WHEN SURFACES ARE WET, EXPOSED TO RAIN OR WIND, OR WHEN WELDERS ARE EXPOSED TO INCLEMENT CONDITIONS THAT WILL AFFECT THE QUALITY OF WORKMANSHIP.

AutoCAD SHX Text

INSPECTION, TESTING AND QUALITY ASSURANCE:

AutoCAD SHX Text

1. STRUCTURAL STEEL CONSTRUCTION WILL BE INSPECTED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE (IBC) 2015 AND STRUCTURAL STEEL CONSTRUCTION WILL BE INSPECTED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE (IBC) 2015 AND ENGINEER. 2. FIELD WELDING WILL BE INSPECTED VISUALLY AND BY NON-DESTRUCTIVE TESTING BY A THIRD PARTY AWS CERTIFIED WELDING FIELD WELDING WILL BE INSPECTED VISUALLY AND BY NON-DESTRUCTIVE TESTING BY A THIRD PARTY AWS CERTIFIED WELDING INSPECTOR PROVIDED BY THE OWNER. RADIOGRAPH TESTING OF THE DOOR SHEET IS THE RESPONSIBILITY OF THE CONTRACTOR. 3. ACCEPTANCE CRITERIA AND TESTING FREQUENCY FOR INSPECTED WELDS SHALL BE IN ACCORDANCE WITH TABLE 6.1 OF AWS D1.1. ACCEPTANCE CRITERIA AND TESTING FREQUENCY FOR INSPECTED WELDS SHALL BE IN ACCORDANCE WITH TABLE 6.1 OF AWS D1.1. AND SPECIFICATION 05523. 4. THE OWNER WILL HIRE A NACE CERTIFIED COATING INSPECTOR. NEW COATING SYSTEMS SHALL BE TESTED AND INSPECTED PER THE OWNER WILL HIRE A NACE CERTIFIED COATING INSPECTOR. NEW COATING SYSTEMS SHALL BE TESTED AND INSPECTED PER SPECIFICATION 09713.

AutoCAD SHX Text

1. AN INDEPENDENT LATERAL ANALYSIS WAS NOT COMPLETED AS PART OF THIS PROJECT. UNDERSTANDING THE TANK WAS ORIGINALLY AN INDEPENDENT LATERAL ANALYSIS WAS NOT COMPLETED AS PART OF THIS PROJECT. UNDERSTANDING THE TANK WAS ORIGINALLY DESIGNED TO MEET AWWA D100, WHICH INCLUDES LATERAL LOADS, THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE DESIGN CALCULATION PACKAGE SEALED BY A LICENSED PROFESSIONAL ENGINEER IN THE STATE OF COLORADO FOR ALL REPLACEMENT FRAMING, INCLUDING A COMPLETE LATERAL ANALYSIS. 2. THE FOLLOWING MINIMUM STANDARDS AND DESIGN LOADS SHOULD BE USED. DESIGN CODES: THE FOLLOWING MINIMUM STANDARDS AND DESIGN LOADS SHOULD BE USED. DESIGN CODES: A. INTERNATIONAL BUILDING CODE (IBC), 2015. INTERNATIONAL BUILDING CODE (IBC), 2015. B. AMERICAN WATER WORKS ASSOCIATION (AWWA) STANDARD FOR WELDED STEEL TANKS FOR WATER STORAGE, 2011 WITH AMERICAN WATER WORKS ASSOCIATION (AWWA) STANDARD FOR WELDED STEEL TANKS FOR WATER STORAGE, 2011 WITH HISTORIC VERSIONS WHERE APPROPRIATE. C. AMERICAN PETROLEUM INSTITUTE (API) 650, 11TH EDITION, 2007. AMERICAN PETROLEUM INSTITUTE (API) 650, 11TH EDITION, 2007. D. AMERICAN PETROLEUM INSTITUTE (API) 653, 5TH EDITION, 2014. AMERICAN PETROLEUM INSTITUTE (API) 653, 5TH EDITION, 2014. E. AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) 360-05, 13TH EDITION. AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) 360-05, 13TH EDITION. F. AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE), MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES 7, 2010. AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE), MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES 7, 2010. DESIGN LOADS: A. DEAD LOAD MEMBER SELF WEIGHT AND PERMANENT EQUIPMENT (490 PCF) DEAD LOAD MEMBER SELF WEIGHT AND PERMANENT EQUIPMENT (490 PCF) MEMBER SELF WEIGHT AND PERMANENT EQUIPMENT (490 PCF) B. ROOF LIVE LOAD 15 PSF, AWWA D100 ROOF LIVE LOAD 15 PSF, AWWA D100 15 PSF, AWWA D100 C. SNOW LOAD SNOW LOAD GROUND 55 PSF, SEAC 2016 COLORADO DESIGN SNOW LOADS 55 PSF, SEAC 2016 COLORADO DESIGN SNOW LOADS ROOF 50 PSF, ASCE 7-10 50 PSF, ASCE 7-10 D. WIND (SEE NOTE 1, ABOVE) WIND (SEE NOTE 1, ABOVE) BASIC WIND SPEED 120 MPH, ASCE 7-10 BASIC WIND SPEED 120 MPH, ASCE 7-10 120 MPH, ASCE 7-10 Iw 1.15, AWWA D100 1.15, AWWA D100 EXPOSURE C C WIND PRESSURES ±30.0 PSF (SIDEWALL), AWWA D100 ±30.0 PSF (SIDEWALL), AWWA D100 ±30.0 PSF (ROOF), AWWA D100 E. SEISMIC (SEE NOTE 1 ABOVE) SEISMIC (SEE NOTE 1 ABOVE) OCCUPANCY IV IV IMPORTANCE FACTOR, Ie 1.5 1.5 SOIL SITE CLASS D, ASSUMED D, ASSUMED Ss 0.161g 0.161g S1 0.054g 0.054g Fa 1.60 1.60 Fv 2.40 2.40 SDS 0.171g 0.171g SD1 0.087g 0.087g SEISMIC DESIGN CATEGORY C (PER ASCE 7-10)C (PER ASCE 7-10)

AutoCAD SHX Text

STRUCTURAL DESIGN AND LOADS FOR REPLACEMENT VERTICAL FRAMING:

LANDSCAPE NOTES: 1. ALL AREAS DISTURBED BY BUILDING OR UTILITY CONSTRUCTION OR OVER-LOT GRADING SHALL BE ALL AREAS DISTURBED BY BUILDING OR UTILITY CONSTRUCTION OR OVER-LOT GRADING SHALL BE REVEGETATED WITH DRYLAND SEED MIXTURE. PROVIDE FRESH, CLEAN, NEW-CROP SEED COMPLYING WITH TOLERANCE FOR PURITY AND GERMINATION ESTABLISHED BY OFFICIAL SEED ANALYSIS OF NORTH AMERICA. PROVIDE SEED OF GRASS SPECIES, PROPORTIONS AND MINIMUM PERCENTAGES OF PURITY, GERMINATION, AND MAXIMUM PERCENTAGE OF WEED SEED, AS SPECIFIED. 2. FOR DRYLAND SEEDED AREAS, PROVIDE FERTILIZER WITH COMMERCIAL TYPE MIXTURE OF 16-16-8 OR FOR DRYLAND SEEDED AREAS, PROVIDE FERTILIZER WITH COMMERCIAL TYPE MIXTURE OF 16-16-8 OR SIMILAR RATION, NOT LESS THAN 15 LBS PER ACRE FOR NITROGEN RATE. 3. MULCH ALL SEEDED AREAS WITH CONWEB LONG FIBER MULCH, HAY OR STRAW. MATERIAL FOR STRAW MULCH ALL SEEDED AREAS WITH CONWEB LONG FIBER MULCH, HAY OR STRAW. MATERIAL FOR STRAW MULCHING SHALL CONSIST OF STRAW OR OATS, BARLEY, WHEAT OR RYE AND SHALL NOT CONTAIN SEED OF NOXIOUS WEEDS. CLEAN FIELD HAY MAY BE SUBSTITUTED FOR STRAW WHEN APPROVED BY THE ENGINEER. STRAW OR HAY IN SUCH AN ADVANCED STAGE OR DECOMPOSITION AS TO SMOTHER OR RETARD THE NORMAL GROWTH OF GRASS WILL NOT BE ACCEPTED. CONWEB FIBER MULCH, PREVIOUSLY SPECIFIED, SHALL BE APPLIED AT A RATE OF 1500 LBS./ACRE. HAY OR STRAW SHALL BE APPLIED IN A UNIFORM MANNER AT A RATE OF 1.5 TONS/ACRE. 4. PROVIDE EROSION CONTROL BLANKET ON ALL SLOPES OF 2:1 OR STEEPER. PROVIDE EROSION CONTROL BLANKET ON ALL SLOPES OF 2:1 OR STEEPER. 5. PRIOR TO REVEGETATION, PLANTING OR TOPSOIL PLACEMENT, ALL CUT OR FILL SLOPES WILL BE CONTOURED PRIOR TO REVEGETATION, PLANTING OR TOPSOIL PLACEMENT, ALL CUT OR FILL SLOPES WILL BE CONTOURED TO BLEND WITH ADJACENT TERRAIN. VARIOUS SLOPE MOLDING TECHNIQUES WILL BE USED TO ENHANCE THE AESTHETIC QUALITY OF THE SLOPE, WHILE MAXIMIZING THE REVEGETATION POTENTIAL. ALL CUT AND FILL SLOPES ALSO BEING ROUNDED AT THE TOE TO BLEND WITH THE EXISTING TERRAIN. ADDITIONALLY, WHERE SOILS AND STEEPNESS OF SLOPES PERMIT, TERRACES WILL BE CONSTRUCTED TO AID THE REVEGETATION PROCESS. 6. SEEDING SHALL BE DONE BY HYDROSEEDING, DRILLING, OR HAND BROADCASTING. HYDROSEED SHALL BE SEEDING SHALL BE DONE BY HYDROSEEDING, DRILLING, OR HAND BROADCASTING. HYDROSEED SHALL BE APPLIED IN A WATER AND LIGHT MULCH SLURRY AFTER WHICH MULCH WILL BE APPLIED TO COVER THE SEED. ANY AREAS THAT CANNOT BE REACHED BY HYDROSEEDING OR DRILL SEEDING SHALL BE HAND BROADCAST. AREAS SEEDED BY HAND BROADCASTING SHALL BE LIGHTLY RAKED. 7. DRYLAND SEEDING SHALL BE PERFORMED AS SOON AS PRACTICAL AFTER COMPLETING OF CONSTRUCTION, DRYLAND SEEDING SHALL BE PERFORMED AS SOON AS PRACTICAL AFTER COMPLETING OF CONSTRUCTION, WITHIN THE APPROPRIATE SEASON. SEEDING SHALL BE PERFORMED AFTER SPRING THAW UNTIL JUNE 30TH, OR AFTER SEPTEMBER 1 UNTIL CONSISTENT GROUND FREEZE. CONTRACTOR SHALL BE RESPONSIBLE FOR REGULAR WATERING UNTIL ESTABLISHED.

is io n

Dwg No.

Job No.

Drawn by:

Date:

File:

PE:QC:

D at e By

Pr oj ec t M ile st on e:

2013-471.013

SF

03.18.25

BB

2MG Tank Rehabilitation

XX

S1

BI

D

D R

AW

IN

G S

Title:

2M G

T an k R eh ab ilit at io n

Tank Rehabilitation Plan

To w n of

P ao ni a

W es t S ixt h St re et

, S ui te

G le nw oo d

Sp rin gs , C

O

0.

5.

w

.s gm

-in c.

REMOVE EXISTING VENT AND INSTALL NEW 24" RISER AND AST-VENT, RE:DETAIL 3, SHEET S2

AutoCAD SHX Text

TANK REPAIR PLAN

AutoCAD SHX Text

EX. 30" SHELL MANWAY

AutoCAD SHX Text

REMOVE AND REPLACE 24" MANWAY WITH 36"X36" BILCO TYPE E HATCH AND 6" RISER

AutoCAD SHX Text DEMOLISH E. LADDER SAFETY CAGE AND INSTALL OSHA COMPLIANT PERSONAL FALL PROTECTION SYSTEM

AutoCAD SHX Text R52.00±

AutoCAD SHX Text

EX. 8" INLET

AutoCAD SHX Text

ROOF FRAMING /FLOOR VIEW

AutoCAD SHX Text

ROOF SHELL /FLOOR VIEW

AutoCAD SHX Text

ROOF SHELL /FLOOR VIEW

AutoCAD SHX Text

INSTALL NEW CENTER COLUMN CAPITAL RE: DETAIL 2, SHEET S2

AutoCAD SHX Text

ROOF FRAMING /FLOOR VIEW

AutoCAD SHX Text

EX. OUTER C-CHANNEL RAFTERS (ASSUMES C9X20 SECTION), QTY 45

AutoCAD SHX Text

EX. LATERAL BRACING

AutoCAD SHX Text 90°

AutoCAD SHX Text

EX. INNER C-CHANNEL RAFTERS (ASSUMES C9X20 SECTION), QTY 30

AutoCAD SHX Text

EX. 30" SHELLMANWAY

AutoCAD SHX Text

INSTALL 6" OVERFLOWRE: DETAIL 1, SHEET S2

AutoCAD SHX Text

EX. 8" OUTLET

AutoCAD SHX Text

EX. DRAIN LINE

AutoCAD SHX Text

CUT EXISTING C-CHANNEL RAFTERS BACK TO PROVIDE 3' CLEARANCE FROM CENTER OF TANK

AutoCAD SHX Text 98.00'

AutoCAD SHX Text STEEL HANDRAIL PER DETAIL, SHEET S2. WELD BASES TO TANK. TYP. OF BOTH SIDES OF ACCESS HATCH.

AutoCAD SHX Text i:\2013\2013-471 town of paonia\013-2mg tank coating\H-Dwgs\Civil\PS-Sheetset\2MG Tank Rehabilitation.dwg Plotted: 3/19/2025 9:40 AM By: Scott Forrester Plotted: 3/19/2025 9:40 AM By: Scott Forrester3/19/2025 9:40 AM By: Scott Forrester By: Scott ForresterScott Forrester

AutoCAD SHX Text

AutoCAD SHX Text is io n

Dwg No.

Job No.

Drawn by:

Date:

File:

PE:QC:

D at e By

Pr oj ec t M ile st on e:

2013-471.013

SF

03.18.25

BB

2MG Tank Rehabilitation

XX

S2

BI

D

D R

AW

IN

G S

Title:

2M G

T an k R eh ab ilit at io n

Tank Rehabilitation Details

To w n of

P ao ni a

W es t S ixt h St re et

, S ui te

G le nw oo d

Sp rin gs , C

O

0.

5.

w

.s gm

-in c.

T.O. BASE SLAB 6517.2'

AutoCAD SHX Text NOTES: 1. CARBON PIPE SHALL CONFORM TO AWWA CARBON PIPE SHALL CONFORM TO AWWA C200-17 AND SHALL BE COATED PER SPECIFICATION 09713. 2. ALL WETTED MATERIALS SHALL BE ALL WETTED MATERIALS SHALL BE NSF-600 CERTIFIED FOR POTABLE WATER CONTACT AND SHALL BE CERTIFIED LEAD FREE.

AutoCAD SHX Text

1:12 ROOF SLOPE

AutoCAD SHX Text

OVERFLOW 6547.45'

AutoCAD SHX Text

12" BELOW BOTTOM OF BEAM

AutoCAD SHX Text 12"x6" WELDED STEEL FLARED FITTING

AutoCAD SHX Text INSTALL NEW 6" WELDED STEEL OVERFLOW PIPE & FITTINGS TO ESTABLISH 1' OF FREEBOARD ABOVE WEIR

AutoCAD SHX Text

INSTALL OVERFLOW PIPE SUPPORT, SEE DETAIL A THIS SHEET

AutoCAD SHX Text 1/4

AutoCAD SHX Text

TYP.

AutoCAD SHX Text 14" x 36" DIAM. PATCH PLATE AT PIPE PENETRATION

AutoCAD SHX Text CHANNEL C6x8.2 (2 PER SUPPORT)

AutoCAD SHX Text 30°

AutoCAD SHX Text

BENT PLATE 3/8", 2 PER SUPPORT

AutoCAD SHX Text

PLATE 3/8", TYP.

AutoCAD SHX Text

PIPE

AutoCAD SHX Text 1/4

AutoCAD SHX Text

TYP.

AutoCAD SHX Text 1/4

AutoCAD SHX Text

TYP.

AutoCAD SHX Text 1/4

AutoCAD SHX Text

TYP.

AutoCAD SHX Text

EXIST. ROOF PLATE. REMOVE AND REPLACE ROOF PLATE AS NEEDED

AutoCAD SHX Text 2'-0" I.D.

AutoCAD SHX Text 1/4

AutoCAD SHX Text

PLATE 1/4" STEEL RISER (BOLT PATTERN TO MATCH VENT FLANGE)

AutoCAD SHX Text

1/4" PLATE. I.D. AND O.D. PER VENT MANUFACTURER FLANGE

AutoCAD SHX Text

GASKET

AutoCAD SHX Text

24" ALLUMINUMAST-VENT, AS MANUFACTURED BY ADVANCED TANK AND CONSTRUCTION

AutoCAD SHX Text 3'-0"

AutoCAD SHX Text 1/4

AutoCAD SHX Text

TANK

AutoCAD SHX Text

1/2" HOLE FOROWNER FURNISHED PADLOCK

AutoCAD SHX Text 3/4" x2" SS BOLTS, BOLT PATTERN PERVENT MANUFACTURER

AutoCAD SHX Text

NOTE: 1. GASKET AND BOLTS PROVIDED GASKET AND BOLTS PROVIDED WITH VENT.

AutoCAD SHX Text 1/4

AutoCAD SHX Text CURVED 4x4x1/2 SEAM WELD ENDS TOGETHER TO MAKE CONTINUOUS

AutoCAD SHX Text

EXISTING RAFTER SECTION SEE PLAN

AutoCAD SHX Text 5/16

AutoCAD SHX Text

EX. 1' CYLINDRICAL STEEL COLUMN

AutoCAD SHX Text PLATE 1" x 1'-10" (A36)

AutoCAD SHX Text 1/4

AutoCAD SHX Text PLATE 1" x 1'-10" (A36)

AutoCAD SHX Text 3/16

AutoCAD SHX Text 45°

AutoCAD SHX Text

AS NEEDED

AutoCAD SHX Text

(2)-5/8" A325-N BOLTS @ 2 1/4"GA IN SHORT SLOTTED HOLES, TYP EA C9 RAFTER

AutoCAD SHX Text R=4'-0"

AutoCAD SHX Text

NOTE 2

AutoCAD SHX Text NOTES: 1. ALL CUT AND SHEARED EDGES OF NEW ALL CUT AND SHEARED EDGES OF NEW FRAMING AND CONNECTIONS SHALL BE GROUND TO A MINIMUM OF " RADIUS. 14" RADIUS. 2. PROVIDE " THICK x 72" DIAM. DOUBLER PROVIDE " THICK x 72" DIAM. DOUBLER 14" THICK x 72" DIAM. DOUBLER OVER EXISTING ROOF SHELL TO MATCH EXISTING OPENING TO NEW VENT OPENING. ATTACH DOUBLER W/CONTINUOUS WELD AT ALL EDGES.

AutoCAD SHX Text

3/4" HOLES(TYP.)

AutoCAD SHX Text

8 SPACES ON ANGLE

AutoCAD SHX Text

FOR SQ. TUBES

AutoCAD SHX Text TUBE 2" x 2" x 1/4" WALL (A500B)

AutoCAD SHX Text ANGLE 4" x 4" x 1/2" (A36) 4'-0" INSIDE RADIUS

AutoCAD SHX Text

6'-0" MAX BETWEEN POSTS

AutoCAD SHX Text 3'-6"

AutoCAD SHX Text

1 " STEEL PIPE 12" STEEL PIPE RAILS (TYP 2)

AutoCAD SHX Text

1 " STEEL 12" STEEL PIPE POSTS

AutoCAD SHX Text

4" TOE

AutoCAD SHX Text

WELD OR FITTINGS @ ALL JOINTS

END CAPS ON ALL RAILS

AutoCAD SHX Text

21" (MAX)

AutoCAD SHX Text i:\2013\2013-471 town of paonia\013-2mg tank coating\H-Dwgs\Civil\PS-Sheetset\2MG Tank Rehabilitation.dwg Plotted: 3/19/2025 9:40 AM By: Scott Forrester Plotted: 3/19/2025 9:40 AM By: Scott Forrester3/19/2025 9:40 AM By: Scott Forrester By: Scott ForresterScott Forrester

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text S2

AutoCAD SHX Text

OVERFLOW DETAIL

AutoCAD SHX Text

SCALE: 1/4" = 1'-0"

AutoCAD SHX Text A

AutoCAD SHX Text S2

AutoCAD SHX Text A

AutoCAD SHX Text S2

AutoCAD SHX Text

SECTION

AutoCAD SHX Text

SCALE: 3/4" = 1'-0"

AutoCAD SHX Text

AutoCAD SHX Text S2

AutoCAD SHX Text

ROOF VENT DETAIL

AutoCAD SHX Text

SCALE: 1/2" = 1'-0"

AutoCAD SHX Text

AutoCAD SHX Text S2

AutoCAD SHX Text

ROOF SUPPORT DETAIL

AutoCAD SHX Text

SCALE: 1/2" = 1'-0"

AutoCAD SHX Text B

AutoCAD SHX Text S2

AutoCAD SHX Text

ROOF SUPPORT SECTION

AutoCAD SHX Text

SCALE: 1/2" = 1'-0"

AutoCAD SHX Text B

AutoCAD SHX Text S2

AutoCAD SHX Text

AutoCAD SHX Text S2

AutoCAD SHX Text

HANDRAIL DETAIL

SCALE: 1/2" = 1'-0"

Sheets and Views
Cover
G1 General Notes
S1 Tank Rehabilitation Plan
S2 Tank Rehabilitation Details