RFQ_Atch2-Drawing_Example.pdf
PDF 728 KB Posted
- Attached to
- Pressure Reducing Valves
- Solicitation number
- PAN414-19-P-4793
About this file
drawing - example
View the file
Other files
| File | Type | Posted |
|---|---|---|
| B08-RFQ_Amd_1_Atch1-Salient_Characteristics.docx | DOCX document | |
| RFQ_Atch1-Salient_Characteristics.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SE QUESTO DISEGNO È PIÙ PICCOLO DI 841 X 594 mm È UN DISEGNO A DIMENSIONI RIDOTTE
NOTE: / NOTA:
IF THIS DRAWING IS LESS THAN 841 X 594 mm IT IS A REDUCED SIZE DRAWING
SCALE / SCALA
1:50
DEPOT PRESSURE REGULATION SYSTEM DN 300 - AS PER NOTE IN SHEET F-001 (*)
TECHNICAL SPECIFICATIONS
SPECIFICHE TECNICHE
PRESSURE REDUCING UL LISTED
PRESSURE REDUCING DN 12”VALVES UL LISTED GLOBE / GLOBE-TYPE, DIRECT-SEALING DIAPHRAGM VALVE, STRAIGHT FLOW PATTERN, FLANGED CONNECTIONS . HYDRAULIC CONTROLLED PRESSURE REDUCING VALVE, ACTUATED BY THE PIPELINE PRESSURE.
BODY AND COVER : CAST STEEL ASTM A 216 WCB
ELASTOMER: NEOPRENE
PILOT MODEL: CXPR SS 316
FLANGES: ANSI 150 RF
COATING: EPOXY COATING PROTECT 300/400 MICRON RAL 3020
PRESSURE GAUGE: N.2 0-25 BAR SS 316 CASE PROCESS CONNECTION MADE IN SS 63 MM ¼” NPT
FITTINGS: SS 316
TUBING: SS 316
PRESSURE RELIEF VALVE
PRESSURE RELIEF VALVES DN 100 UL LISTED GLOBE / GLOBE-TYPE, DIRECT-SEALING DIAPHRAGM VALVE, STRAIGHT FLOW PATTERN, FLANGED CONNECTIONS . HYDRAULIC CONTROLLED
PRESSURE REDUCING VALVE, ACTUATED BY THE PIPELINE PRESSURE.
BODY AND COVER : CAST STEEL ASTM A 216 WCB
ELASTOMER : NEOPRENE
PILOT MODEL: CXPS SS 316
FLANGES: ANSI 150 RF
COATING: EPOXY COATING PROTECT 300/400 MICRON RAL 3020
PRESSURE GAUGE: N.1 0-25 BAR SS 316 CASE , PROCESS CONNECTION MADE IN SS 63 MM ¼” NPT
FITTINGS: SS 316
TUBING: SS 316
STRAINER
Y FILTER.DN 12” UL LISTED GLOBE STRAIGHT FLOW PATTERN, FLANGED CONNECTIONS.
BODY AND COVER : DUCTILE CAST IRON ASTM A 536
FLANGES: ANSI 150 RF
COATING: EPOXY COATING PROTECT 300/400 MICRON RAL 3020
BUTTERFLY VALVE
Y FILTER.DN 12” UL LISTED GLOBE STRAIGHT FLOW PATTERN, FLANGED CONNECTIONS.
BODY AND COVER : DUCTILE CAST IRON ASTM A 536
FLANGES: ANSI 150 RF
COATING: EPOXY COATING PROTECT 300/400 MICRON RAL 3020
SCALE / SCALA
1:50
CAMP DARBY PRESSURE REGULATION SYSTEM DN 150 - AS PER NOTE IN
SHEET F-001 (*)
02 03 010401
762.5
CONNECTION JOINT
STEEL/HDPE
GIUNTO DI TRANSIZIONE
ACCIAIO/PEAD
CONNECTION JOINT
STEEL/HDPE
GIUNTO DI TRANSIZIONE
ACCIAIO/PEAD
03 0102 0401
GAUGE
MANOMETRO
GAUGE
MANOMETRO
426.4
CONNECTION JOINT
STEEL/HDPE
GIUNTO DI TRANSIZIONE
ACCIAIO/PEAD
CONNECTION JOINT
STEEL/HDPE
GIUNTO DI TRANSIZIONE
ACCIAIO/PEAD
GAUGE
MANOMETRO
GAUGE
MANOMETRO
TECHNICAL SPECIFICATIONS
SPECIFICHE TECNICHE
PRESSURE REDUCING UL LISTED
PRESSURE REDUCING DN 6” VALVES UL LISTED GLOBE / GLOBE-TYPE, DIRECT-SEALING DIAPHRAGM VALVE, STRAIGHT FLOW PATTERN, FLANGED CONNECTIONS . HYDRAULIC CONTROLLED PRESSURE REDUCING VALVE, ACTUATED BY THE PIPELINE PRESSURE.
BODY AND COVER : CAST STEEL ASTM A 216 WCB
ELASTOMER: NEOPRENE
PILOT MODEL: CXPR SS 316
FLANGES: ANSI 150 RF
COATING: EPOXY COATING PROTECT 300/400 MICRON RAL 3020
PRESSURE GAUGE: N.2 0-25 BAR SS 316 CASE PROCESS CONNECTION MADE IN SS 63 MM ¼” NPT
FITTINGS: SS 316
TUBING: SS 316
PRESSURE RELIEF VALVE
PRESSURE RELIEF VALVES DN 80 UL LISTED GLOBE / GLOBE-TYPE, DIRECT-SEALING DIAPHRAGM VALVE, STRAIGHT FLOW PATTERN, FLANGED CONNECTIONS . HYDRAULIC CONTROLLE
DPRESSURE REDUCING VALVE, ACTUATED BY THE PIPELINE PRESSURE.
BODY AND COVER : CAST STEEL ASTM A 216 WCB
ELASTOMER : NEOPRENE
PILOT MODEL: CXPS SS 316
FLANGES: ANSI 150 RF
COATING: EPOXY COATING PROTECT 300/400 MICRON RAL 3020
PRESSURE GAUGE: N.1 0-25 BAR SS 316 CASE , PROCESS CONNECTION MADE IN SS 63 MM ¼” NPT
FITTINGS: SS 316
TUBING: SS 316
STRAINER
Y FILTER.DN 6” UL LISTED GLOBE STRAIGHT FLOW PATTERN, FLANGED CONNECTIONS.
BODY AND COVER : DUCTILE CAST IRON ASTM A 536
FLANGES: ANSI 150 RF
COATING: EPOXY COATING PROTECT 300/400 MICRON RAL 3020
BUTTERFLY VALVE
Y FILTER.DN 6” UL LISTED GLOBE STRAIGHT FLOW PATTERN, FLANGED CONNECTIONS.
BODY AND COVER : DUCTILE CAST IRON ASTM A 536
FLANGES: ANSI 150 RF
COATING: EPOXY COATING PROTECT 300/400 MICRON RAL 3020
PLAN VIEW
SECTION
PLAN VIEW
SECTION
NOTES / NOTE
PIPES AND COMPONENTS MUST BE INSULATED, SEALED AND COVERED
WITH ALUMINUM PLATE
LE TUBAZIONI E I COMPONENTI DOVRANNO ESSERE COIBENTATI,
SIGILLATI E RICOPERTI CON LAMIERINO IN ALLUMINIO
NOTES / NOTE
PIPES AND COMPONENTS MUST BE INSULATED, SEALED AND COVERED
WITH ALUMINUM PLATE
LE TUBAZIONI E I COMPONENTI DOVRANNO ESSERE COIBENTATI,
SIGILLATI E RICOPERTI CON LAMIERINO IN ALLUMINIO
THE NEW SYSTEM SHALL BE SIZED IN ORDER TO ENSURE A RESIDUAL
PRESSURE OF 4 BAR AT THE ENTRANCE OF THE EXISTING BUILDING FOR
PROPER OPERATION OF EXISTING FIRE FIGHTING SYSTEMS WITHOUT
CHANGES TO EXISTING SYSTEMS. PRESSURE REDUCER SHALL BE
INSTALLED ON ALL INDUSTRIAL UTILITIES EVEN IF NOT INDICATED ON
DRAWINGS
IL NUOVO IMPIANTO SARA' DIMENSIONATO PER GARANTIRE
UNA PRESSIONE RESIDUA DI 4 BAR ALL'INGRESSO DEI
FABBRICATI ESISTENTI PER IL CORRETTO FUNZIONAMENTO
DEGLI IMPIANTI ANTINCENDIO ESISTENTI, SENZA COMPORTARE
MODIFICHE AGLI IMPIANTI ESISTENTI. RIDUTTORI DI PRESSIONE
SARANNO INSTALLATI IN TUTTE LE UTENZE INDUSTRIALI
ANCHE SE NON INDICATI NEI DISEGNI
M o d
D
A R
B Y
L
A R
G E
D a t a d i s t a m p a a g o s t o
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
N
M
L
I
H
G
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
N
M
L
I
H
G
F
E
D
C
B
A
DB
F504B
RNEG
PROJECT NUMBER
CHECKED BYENGINEERED BYDRAWN BY
BP
DATE SHEET
SYMBOL DESCRIPTION OF REVISION DRAWN DATE APPROVAL
OF SCALE
MODIFY/REPAIR DMC INFRASTRUCTURE - INDUSTRIAL WATER
MAY 2016ED-00126-4P AS SHOWN F
b i s d w g
FINAL SUBMISSION
DMC PWO
U.S. Army Garrison Italy, APO AE 09613
PROJECT NUMBER
CHECKED BYENGINEERED BYDRAWN BY
BP
DATE SHEET
SYMBOL DESCRIPTION OF REVISION DRAWN DATE APPROVAL
OF SCALE
MODIFY/REPAIR DMC INFRASTRUCTURE - INDUSTRIAL WATER
MAY 2016ED-00126-4P AS SHOWN F
b i s d w g
FINAL SUBMISSION
DMC PWO
U.S. Army Garrison Italy, APO AE 09613
DETAILS
DETTAGLI
1 MODIFICATION FOR PRESSURE REGULATION SYSTEM FP AUGUST 2019 BP
File details come from the government source that posted it.