LIMITED HAZARDOUS MATERIALS SURVEY REPORT
WRIGHT BROTHERS MONUMENT
VISITOR’S CENTER
KILL DEVIL HILLS, NORTH CAROLINA
PREPARED FOR:
HAGER SMITH DESIGN PA
300 SOUTH DAWSON STREET
RALEIGH, NORTH CAROLINA 27601 USA
ISSUE DATE: SEPTEMBER 8, 2015
F&R PROJECT NUMBER: 66T-0146
PREPARED BY: REVIEWED BY:
DENISE A. POPEO ALAN LEDERMAN, CIH, CSP, CHMM
ENVIRONMENTAL HEALTH & SAFETY GROUP MANAGER ENVIRONMENTAL PROJECT MANAGER
TABLE OF CONTENTS
PAGE
1.0 EXECUTIVE SUMMARY
1.1 PROJECT INFORMATION
1.2 SCOPE OF SERVICES
1.2.1 LIMITED HAZARDOUS MATERIALS SURVEY
1.2.2 ASBESTOS
1.2.3 LEAD-BASED PAINT SCREENING
1.2.4 POTENTIAL HAZARDOUS MATERIALS SURVEY
1.2.5 MOLD
2.0 METHODOLOGY
2.1 ASBESTOS-CONTAINING MATERIAL (ACM)
2.1.1 SUSPECT ASBESTOS MATERIALS
2.2 LEAD-BASED PAINT (LBP)
2.3 POTENTIAL HAZARDOUS MATERIALS
2.4 MOLD
2.4.1 SPORE TRAP SAMPLING/ANALYSIS (AIR-O-CELL)
2.4.2 DIRECT IDENTIFICATION SAMPLING (TAPE LIFT)
3.0 RESULTS
3.1 ACM RESULTS
3.2 POSITIVE LBP RESULTS
3.3 MOLD RESULTS
3.4 POTENTIAL HAZARDOUS MATERIALS
4.0 CONCLUSIONS AND RECOMMENDATIONS
4.1 ASBESTOS
4.2 LEAD-BASED PAINT
4.3 MOLD
4.4 POTENTIAL HAZARDOUS MATERIALS
4.4.1 MERCURY
4.4.2 PCBS…………………
5.0 APPLICABLE REGULATIONS
5.1 EPA NESHAP REGULATIONS FOR ACM
5.2 OSHA REGULATIONS FOR LBP
5.3 EPA REGULATIONS OF LBP DISPOSAL
5.4 MOLD
5.5 UNIVERSAL WASTE
6.0 LIMITATIONS
APPENDIX A SITE PHOTOGRAPHS
APPENDIX B FLOOR PLANS
APPENDIX C ASBESTOS DOCUMENTATION, LABORATORY REPORTS
APPENDIX D LEAD XRF DATA
APPENDIX E CERTIFICATIONS
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
1.0 EXECUTIVE SUMMARY
1.1 PROJECT INFORMATION
Froehling and Robertson, Inc. (F&R) performed a first Limited Hazardous Materials Survey of the Wright
Brothers Memorial Visitor’s Center in Kill Devil Hills, NC on April 24 and 25, 2012; a second investigation was conducted on August 25 and 26, 2015 due to inaccessibility and scheduling. The survey area consists of approximately 9,600 square feet and was originally constructed in the late 1950s. The building is a one-story, reinforced-concrete, steel and glass structure with an asymmetrical plan.
The following is a summary of our findings and is not intended to replace more detailed information contained elsewhere in this report.
Asbestos (2%-50% Chrysotile) was detected in the hot water pipe aircell insulation located in the public restrooms, pipe chase between the public restrooms, Bookstore, Bookstore offices, Bookstore storage closets and Bookstore restroom. The pipe wrap associated with the aircell insulated pipes contained asbestos (2% Chrysotile). Any additional aircell insulation found during renovations should be considered asbestos containing material (ACM). Asbestos (2% Chrysotile) was detected in the plaster within the wire mesh of the flight room soffits and in the exterior Mechanical room ceilings. The exterior transite window panel boards of the bookstore and its adjacent storage room also showed concentrations of asbestos (55%
- 60% Chrysotile) and should be considered as ACM. Mirror mastic in the Bookstore bathroom should be presumed ACM.
In addition to the above identified ACM, F&R recommends that inaccessible building materials listed in
Section 4.1 of this report also be assumed to be asbestos-containing until sampling determines otherwise.
F&R further recommends that a North Carolina Licensed Asbestos Abatement Contractor be engaged to properly remove the asbestos prior to demolition/renovation.
Lead based paint (LBP) was found in several metal door components, baseboards, metal display supports, and metal columns. In addition, the utility sink in the Book Store tested positive for LBP. Should renovations take place that will impact identified lead components, F&R recommends that workers with
Occupational Safety and Health Administration (OSHA) Lead in Construction training be engaged to perform this work.
Mold spore count levels detected inside the lobby area were not elevated when compared to outside background levels. Additionally, the mold genera detected inside the lobby was consistent with the outside mold spore background levels. However, F&R observed water damaged areas on the lobby ceiling.
Reportedly, water leaks are still active in this area and water infiltration occurs from down a column in the
Flight Room during rain events.
1.2 SCOPE OF SERVICES
1.2.1 LIMITED HAZARDOUS MATERIALS SURVEY
The purpose of the Limited Hazardous Materials Survey is to identify regulated materials that require special handling procedures during renovation, demolition, or maintenance of the subject building.
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
The Hazardous Materials Survey was limited to the below scope and separated into three parts; an
Asbestos Survey, a Lead Based Paint Screening, and Other Hazardous Materials Survey including polychlorinated biphenyls (PCB)-containing fluorescent light ballasts, mercury-containing thermostats, and mercury-containing fluorescent lamps. Limited mold sampling was performed at the time of the inspection as directed by Hager Smith.
1.2.2 ASBESTOS
A North Carolina Licensed Asbestos Inspector conducted a limited non-invasive survey of the interior and exterior of the subject structure for asbestos containing materials (ACMs).
1.2.3 LEAD‐BASED PAINT SCREENING
A North Carolina Licensed Lead Inspector performed the limited lead based paint (LBP) screening. This investigation was not a comprehensive surface‐by‐surface investigation for LBP, but rather a screening survey of painted surfaces where the presence of lead‐based paint is suspected. A Niton X‐ray Fluorescence
(XRF) Lead Paint Analyzer was used to screen surface coatings that may contain lead.
1.2.4 HAZARDOUS MATERIALS SURVEY
A limited non‐invasive visual survey of the subject building was performed for the identification of potential hazardous materials to include the following: polychlorinated biphenyls (PCB)-containing fluorescent light ballasts, mercury-containing thermostats, and mercury-containing fluorescent lamps.
1.2.5 MOLD
At the time of the inspection, F&R was asked to obtain tape lift samples and spore trap samples (air samples) for mold. The samples were taken at locations as directed by Hager Smith Design personnel.
2.0 METHODOLOGY
2.1 ASBESTOS-CONTAINING MATERIAL (ACM)
A non-invasive visual survey and sampling for suspect ACM were conducted on the interior and exterior of the subject building. The survey was conducted in general accordance with National Emission Standards for
Hazardous Air Pollutants (NESHAP‐40 CFR 61 Subpart M) regulations.
Asbestos bulk samples were packaged, labeled, and submitted for analysis under standard chain‐of‐custody procedures. The samples were submitted to EMSL Analytical, Inc. (EMSL) in Morrisville, North Carolina and analyzed by a trained asbestos analyst using polarized light microscopy (PLM) with dispersion staining techniques. This analytical method is defined in 40 CFR; Part 763, Volume 2.210. EMSL is accredited by the
National Voluntary Laboratory Accreditation Program (NVLAP) and the North Carolina Department of
Natural Resources (NCDENR) to analyze suspect asbestos-containing bulk materials.
A total of one hundred twenty one (121) samples were collected and analyzed for their asbestos content via Polarized Light Microscopy (PLM) following Environmental Protection Agency (EPA) Method 600/R-
93/116.
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
2.1.1 Suspect Asbestos Materials
The following is a list of the suspect materials sampled on April 2012 and August 2015 in the renovation areas as designated by the Client:
12”x12” vinyl floor tile and associated mastic
4” vinyl cove base and associated mastic
Rolled floor
Pipe elbows
Air Cell pipe insulation
Wrap on Air Cell pipes
Roof core
Tar under roof flashing
Roof pitch pocket around vent pipes
Concrete ceiling material
Foil wrap on fiberglass in exterior HVAC room ducts
2’x4’ drop ceiling tile
1’x1’ ceiling tile and associated mastic
2’x2’ ceiling tile
Wall block mortar
Mastic sealant on round duct
Glaze on cast iron sewer pipe
Air cell pipe insulation
Duct mastic
Duct seam tape
Ceiling duct
Exterior wall concrete boards, concrete filler and texture coating
Exterior panel textured coating
Honeycomb plaster above ceiling
Plaster ceiling
Exterior window caulk
Mastic on pipe wrap above ceiling
Textured ceiling material
Coal tar mastic on acoustic tile
Wrap on fiber glass insulation
Mastic pucks on 1’x1’ ceiling tile
Mud elbow on pipe chase in baths
Exterior window panel boards
Exterior plaster soffits
2.2 LEAD-BASED PAINT (LBP)
A North Carolina Licensed Lead Inspector performed the limited lead based paint (LBP) screening on the interior and exterior of the subject building. A Niton X‐ray Fluorescence (XRF) Lead Paint Analyzer was used to screen surface coatings that may contain lead. A total of seventy seven (77) readings, including calibrations, were collected as part of this screening.
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
2.3 POTENTIAL HAZARDOUS MATERIALS
F&R performed a limited non‐invasive visual survey of the subject building for the identification of potential hazardous materials including the following: polychlorinated biphenyls (PCB)-containing fluorescent light ballasts, mercury-containing thermostats, and mercury-containing fluorescent lamps.
2.4 MOLD
2.4.1 SPORE TRAP SAMPLING (AIR-O-CELL)/ANALYSES
F&R performed limited mold air testing to profile the air in the building with regards to fungal air quality.
Samples were obtained from areas as directed by Hager Smith. Elevation of fungal air counts within these areas can be used as an indicator of the possible presence of fungal growth generated by sources of moisture within a building. We note, however, that the absence of elevated counts does not necessarily suggest the absence of moisture damage or lack of fungal growth.
For analysis of airborne fungal spores, samples were collected onto Bioaerosol Sampling Cassettes (Air-O-
Cell™ Spore Trap) cassettes. The samples were collected at a flow rate of 15 liters per minute (Lpm) over a
10-minute period. Analytical data was requested for the total number of spores per cubic meter of air
(count/m3).
Calibration of the sampling equipment was performed with a precision flowmeter (a secondary calibration source). F&R flow meters are calibrated against a primary standard (Dry Cal). Field calibration was performed before and at the completion of sampling. EMSL performed the sample analysis. EMSL is an
American Industrial Hygiene Association (AIHA) Environmental Microbiology Laboratory Accreditation
Program (EMLAP) accredited laboratory for microbial analysis. A total of two (2) spore trap samples were collected and analyzed as part of this investigation.
2.4.2 DIRECT IDENTIFICATION SAMPLING (TAPE LIFT)
Direct tape lift samples were collected from selected areas in the facility which exhibited visible signs of mold growth. Samples were obtained from areas as directed by Hager Smith. The direct tape lift samples were collected by pressing a Zefon Bio-TapeTM Surface Sampler across each of the selected areas. The tape was then affixed to a microscope slide for direct microscopic examination. Each tape sample was placed in a sealed container and the samples were delivered under chain of custody to EMSL for laboratory analysis.
It is important to note that this is a qualitative test to determine the genera of mold present and is only indicative of the location sampled. A total of four (4) tape lift samples were collected as part of this investigation.
3.0 RESULTS
3.1 ACM RESULTS
Limited asbestos sampling was done on the interior and exterior of the structure. Tables 1A and 1B show the results of the sampling from April 2012 and August 2015 respectively.
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
Table 1A – April 2012 Investigation ACM Laboratory Results
Sample # Sample Location Material Analytical
Results
1 Lobby 12X12 Vinyl floor tile – light grey NAD
2 Lobby 12X12 Vinyl floor tile – light grey NAD
3 Lobby 12X12 Vinyl floor tile – light grey NAD
4 Lobby Mastic associated with lt. grey floor tile NAD
5 Lobby Mastic associated with lt. grey floor tile NAD
6 Lobby Mastic associated with lt. grey floor tile NAD
7 Lobby 12X12 Vinyl floor tile – yellow NAD
8 Lobby 12X12 Vinyl floor tile – yellow NAD
9 Lobby 12X12 Vinyl floor tile – yellow NAD
10 Lobby Mastic associated with yellow floor tile NAD
11 Lobby Mastic associated with yellow floor tile NAD
12 Lobby Mastic associated with yellow floor tile NAD
13 Throughout 4” black vinyl baseboard NAD
14 Throughout 4” black vinyl baseboard NAD
15 Throughout 4” black vinyl baseboard NAD
16 Throughout Mastic associated with 4” baseboard NAD
17 Throughout Mastic associated with 4” baseboard NAD
18 Throughout Mastic associated with 4” baseboard NAD
19 Book Store 12X12 vinyl floor tile – dark grey NAD
20 Book Store 12X12 vinyl floor tile – dark grey NAD
21 Book Store 12X12 vinyl floor tile – dark grey NAD
22 Book Store Mastic associated with dark grey floor tile NAD
23 Book Store Mastic associated with dark grey floor tile NAD
24 Book Store Mastic associated with dark grey floor tile NAD
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
Sample # Sample Location Material Analytical
Results
25 Book Store Bathroom Terrazzo-look rolled floor NAD
26 Book Store Bathroom Terrazzo-look rolled floor NAD
27 Storage Closet Pipe elbows NAD
28 Storage Closet Pipe elbows NAD
29 Storage Closet & Pipe Chase Canvas pipe wrap NAD
30 Storage Closet & Pipe Chase Air Cell pipe insulation 50% Chrysotile
33 Storage Closet & Pipe Chase Canvas pipe wrap NAD
70 Storage Closet & Pipe Chase Canvas pipe wrap NAD
31 Storage Closet & Pipe Chase Air Cell pipe insulation 50% Chrysotile
32 Storage Closet & Pipe Chase Air Cell pipe insulation Not Analyzed
34 Storage Closet & Pipe Chase Air Cell pipe insulation Not Analyzed
35 Flight Room 12X12 Vinyl floor tile – turquoise NAD
36 Flight Room 12X12 Vinyl floor tile – turquoise NAD
37 Flight Room 12X12 Vinyl floor tile – turquoise NAD
38 Flight Room Mastic associated with turquoise floor tile
NAD
39 Flight Room Mastic associated with turquoise floor tile
NAD
40 Flight Room Mastic associated with turquoise floor tile
NAD
41 Main Roof Roof Core NAD
42 Main Roof Roof Core - Binder NAD
42 Main roof Roof Core – Tar NAD
43 Main Roof Roof Core – Binder NAD
43 Main Roof Roof Core – Tar NAD
44 Roof Tar under flashing NAD
45 Roof Tar under flashing NAD
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
Sample # Sample Location Material Analytical
Results
46 Roof Tar under flashing NAD
47 Roof Pitch pocket around vent pipes NAD
48 Roof Pitch pocket around vent pipes NAD
49 Roof Pitch pocket around vent pipes NAD
50 Flight Room Plaster/concrete in wire mesh 2% Chrysotile
66 Exterior HVAC Room Plaster/Concrete in wire mesh NAD
51 Exterior HVAC Room Silver foil wrap on duct work NAD
52 Lobby 2’X4’ ceiling tile NAD
53 Lobby 2’X4’ ceiling tile NAD
54 Lobby 2’X4’ ceiling tile NAD
55 Lobby Adhesive on 1’X1’ ceiling tile NAD
56 Lobby Adhesive on 1’X1’ ceiling tile NAD
57 Lobby Adhesive on 1’X1’ ceiling tile NAD
58 Lobby 1’X1’ ceiling tile NAD
59 Lobby 1’X1’ ceiling tile NAD
60 Lobby 1’X1’ ceiling tile NAD
61 Book Store 2’X2’ ceiling tile NAD
62 Book Store 2’X2’ ceiling tile NAD
63 Book Store 2’X2’ ceiling tile NAD
64 Exterior Restrooms Terrazzo-look rolled floor NAD
65 Exterior Restrooms Terrazzo-look rolled floor NAD
67 Flight room dome Textured ceiling NAD
68 Flight room dome Textured ceiling NAD
69 Flight room dome Textured ceiling NAD
NAD – No Asbestos Detected
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
Table 1B – August 2015 Investigation
Sample # Sample Location Material Analytical
Results
1 Book Store - Storage Room Wall Block Mortar – grey/white NAD
2 Book Store - Storage Room Wall Block Mortar – tan/beige NAD
3 Book Store - Storage Room Mastic Sealant on Round Duct Not Analyzed
4 Book Store - Storage Room Glaze on Cast Iron Sewer Pipe - Brown NAD
5 Book Store - Storage Room Air cell Pipe Insulation – tan/beige 2% Chrysotile
6, 7 Mechanical Room #2 Duct Mastic - white NAD
8, 9 Mechanical Room #2 Duct Mastic - grey NAD
10 Mechanical Room #2 Duct Seam Tape – white/silver NAD
11 Mechanical Room #2 Duct Seam Tape – tan/white NAD
12, 13 Mechanical Room #2 Ceiling Duct - Yellow Duct Mastic - green NAD
14, 15 Exterior Walls Mechanical
Room Texture coating - white NAD
16, 17 Exterior Walls Mechanical
Room Concrete Board – grey NAD
18, 19 Exterior Walls Mechanical
Room Concrete filler – tan/white NAD
Exterior Walls Mechanical
Room Textured Coating on Panel – tan/white NAD
Exterior Walls Mechanical
Room Textured Coating on Panel – grey/white NAD
22 Mechanical Room #1 Honeycomb Plaster Above Ceiling – white NAD
23 Mechanical Room #1 Honeycomb Plaster Above Ceiling - grey NAD
24 Mechanical Room #1 and 2 Plaster Ceiling – white/yellow NAD
25 Mechanical Room #1 and 2 Plaster Ceiling – grey NAD
26, 27 Mechanical Room #1 Brown Exterior Window Caulk – grey NAD
28, 29 Flight Room Plaster Ceiling skim coat – white/yellow NAD
28A, 29A Flight Room Plaster Ceiling base coat – grey NAD
30, 31 Flight Room - Above Ceiling Mastic on Pipe Wrap – brown/black/yellow
NAD
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
Table 1B – August 2015 Investigation
Sample # Sample Location Material Analytical
Results
32 Flight Room Textured Ceiling – brown/tan NAD
33, 34 Flight Room Textured Ceiling – tan/beige NAD
35, 36 Flight & Display Coal Tar Mastic on Acoustic Tile – brown/black
NAD
37, 38 Display Wrap on Fiberglass Insulation over Hard
Duct – brown/black
NAD
39, 40 Lobby Museum Mastic Pucks on 1'x1' Ceiling Tile – brown/yellow
NAD
41, 42 Baths - Pipe Chase Mud elbows - brown NAD
43 Exterior under Windows Window Panel Board – grey/white/green 55% Chrysotile
44 Exterior under Windows Window Panel Board – grey/white/red 60% Chrysotile
45, 46 Exterior Plaster Soffits Skim Coat – white/beige NAD
45A, 46A Exterior Plaster Soffits Base Coat - grey NAD
NAD – No Asbestos Detected
3.2 POSITIVE LEAD-BASED PAINT RESULTS (PLEASE SEE ATTACHED SPREADSHEET FOR COMPLETE SAMPLING DATA)
Table 2 below depicts the paint samples collected from the interior of the facility that were determined to be lead-based paint. No exterior paint samples collected were determined to be lead-based paint.
Table 2 Positive Lead XRF Results – Wright Brothers Memorial
Room Component/Substrate Condition Lead (Pbc) mg/cm2
Action Level mg/cm2
Lobby Metal column – grey Intact 6.7 1
Lobby Metal support bracket – orange Intact 6.2 1
Book Store Metal door casing – orange Intact 2.9 1
Book Store Metal door casing2 – orange Intact 2.2 1
Book Store Closet Metal door casing – brown Intact 1.2 1
Book Store Closet Porcelain Janitors Sink Intact 3.3 1
Book Store Closet Metal entrance door – green Intact 1.6 1
Flight Room Metal baseboard – orange Intact 1.7 1
Flight Room Metal door – orange Intact 1.1 1
Flight Room Metal door – orange Intact 2.3 1 mg/cm2=milligrams per square centimeter
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
3.3 MOLD RESULTS
F&R observed water damaged areas on the lobby ceiling. Reportedly, the leaks are still active. In addition, areas of the water damaged textured ceiling in the Flight Room had been repaired. Reportedly, water infiltration occurs from down a column in the Flight Room during rain events.
Below are the results from the direct identification samples (tape lift) and spore trap (air-o-cell) samples.
Table 3 Mold Sampling
Sample Number
Sample Type
Sample Location Analytical Results
TL-1 Tape Lift Flight Room inactive return air duct
Pollen - Rare
TL-2 Tape Lift Exterior HVAC room return air duct
Epicoccum – Rare Pollen - Rare
TL-3 Tape Lift Office HVAC return air duct None detected
TL-4 Tape Lift Flight Room active return air duct
Alternaria – Rare Bipolaris – Rare Curvularia – Rare Paecilomyces – Rare Rust – Rare Hyphal Fragment* – Rare Pollen - Rare
17532391 Spore Trap Lobby at help desk Total Fungal Spores 907 count/m3
17532388 Spore Trap Outside at court yard Total Fungal Spores 10600 count/m3
Key: Count/m
= spores per cubic meter of air *Sample contains fruiting structures and/or hyphae associated with spores
N/A – Not available Rare - 1 – 10 spores Low - 11 - 100 spores Medium – 101 - 1000 spores High - > 1000 spores
Note: There are currently no regulatory standards or guidelines with respect to acceptable microbial levels inside buildings. This data has been interpreted qualitatively using general industry standards and previous experience. In general, industry standards call for inside microbial levels to be less than 25%- 50% of outdoor levels in buildings with mechanically filtered air.
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
3.4 POTENTIAL HAZARDOUS MATERIALS
F&R performed a limited non‐invasive visual survey of the subject building for the identification of potential hazardous materials including the following: PCB-containing fluorescent light ballasts, mercury-containing thermostats, and mercury-containing fluorescent lamps.
F&R inspected a representative number of light fixtures for PCB’s. F&R did not observe any Non-PCB labels on the inspected light ballasts, therefore, all ballasts should be considered PCB-containing unless a Non-
PCB label is observed on the ballast.
A total of 32 mercury-containing lamps were identified on the site. One thermostat was observed to be potentially mercury-containing. Mercury lamp components and locations are listed in the below Table.
Table 4 Mercury-Containing Lighting – Wright Brothers Memorial
Room Use Type Quantity
Display room Wall display lighting Fluorescent - Mercury 32
4.0 CONCLUSIONS AND RECOMMENDATIONS
4.1 ASBESTOS
Asbestos (50% Chrysotile) was detected in the hot water pipe insulation (aircell) located in the Bookstore offices, Bookstore, Bookstore bath, Bookstore storage, Bookstore janitor’s closet, public restrooms, and the pipe chase in the public restrooms. This material was observed in fair condition. Any additional air-cell insulation found during renovations should be considered ACM.
Asbestos (2% Chrysotile) was detected in concrete within the wire mesh of the flight room HVAC panel and in the exterior HVAC room ceiling. The material was observed in fair condition. Any additional concrete on wire mesh found during renovation should be considered ACM.
Asbestos (55%-60% Chrysotile) found in the transite panel board underneath the exterior windows. This material was observed in fair condition.
Table 5 Asbestos Containing Materials Summary
Sample Description
Location Percent & Asbestos
Type NESHAP Category
Approx.
Quantity
Remove
Aircell pipe insulation
Restrooms & pipe chase, Bookstore, Bookstore storage, Bookstore offices, Bookstore bathroom
50% Chrysotile
Regulated Asbestos Containing Material (RACM)
190 lf Yes
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
Table 5 Asbestos Containing Materials Summary
Sample Description
Location Percent & Asbestos
Type NESHAP Category
Approx.
Quantity
Remove
Canvas wrap on Aircell pipes
Restrooms & pipe chase, Bookstore, Bookstore storage, Bookstore offices, Bookstore bathroom
50% Chrysotile
Regulated Asbestos Containing Material (RACM)
Included above
Yes
Plaster within wire mesh
Soffits in Flight Room, Mechanical Rooms ceilings, Columns in
Display Area
2% Chrysotile
Regulated Asbestos Containing Material (RACM)
1,900 sf Yes
Transite window panels
Below windows at Bookstore and Bookstore offices
55% - 60% Chrysotile
Category II Non-friable ACM 3 Panels Yes
Mirror Mastic Bookstore Employee Bath Presumed
ACM
Category II Non-Friable ACM 1 Mirror Yes
In addition to the identified ACM, F&R recommends that the following inaccessible building materials be assumed to be asbestos-containing until sampling determines otherwise:
Exterior vapor barrier and associated mastic (not observed during this investigation)
Mastic behind panel walls & Flight Room sign
Vibration dampers
Fire doors Additional site observations include:
Areas behind solid walls and ceilings were inaccessible and could not be visually surveyed for the presence of ACM. ACM including, but not limited to, thermal pipe and pipe fitting insulation may exist in these locations.
F&R recommends that an asbestos abatement specification be developed and incorporated into the overall project prior to renovation and/or demolition of the building.
F&R recommends that an Operation and Maintenance (O&M) plan be developed and implemented to manage all known and suspect ACMs in the building in accordance with 29 CFR 1926.1101 until the building is demolished or all ACMs are abated.
4.2 LEAD-BASED PAINT
Several metal door components, baseboards, metal display supports, and metal columns tested positive for lead-based paint when compared to the HUD action level of 1.0 mg/cm². In addition, the utility sink in the
Book Store tested positive for LBP. Should renovations take place that will impact identified lead components, F&R recommends that workers with OSHA Lead in Construction training be engaged to perform this work.
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
4.3 MOLD
Based upon the results of airborne spore count sampling data for the lobby, spore count levels detected inside the lobby area do not appear to be elevated when compared to outside background levels.
Additionally, the mold genera detected inside the lobby were consistent with the outside mold spore background levels.
Several fungal spores, fungal structures, and fungal hyphae were found on the room tape lift samples taken from exterior HVAC room return air duct and the Flight Room active return air duct. The tape lift samples taken from the non-active return air duct in the Flight Room and the office return air show pollen but not fungal spores, fungal structures, or hyphae. The concentration of spores on the tape lifts were in the rare range.
Based upon data obtained from this survey and visual observations, F&R recommends that the owner consult with an engineer or qualified contractor to verify that all sources of moisture intrusion have been identified and corrected. Potential sources for excessive moisture intrusion include, but are not limited to, roof leaks, failing exterior finishes, HVAC imbalances, failing insulation, and/or excessive humidity from other various causes. In addition F&R makes the following general recommendations:
Remove and replace water-stained ceiling tiles.
Maintain HVAC filter changes throughout the building in accordance with the manufacturer’s recommendations.
In general, F&R recommends that the temperature and relative humidity levels inside the building be maintained within the acceptable indoor guidelines as outlined by American Society if Heating Refrigeration and Air Conditioning Engineers ASHRAE.
o Acceptable indoor relative humidity range is 30-60% RH (reference ASHRAE 55-2010).
o Acceptable indoor summer temperature range is 73-79 °F (reference ASHRAE 55-2010).
o Acceptable indoor winter temperature range is 68-74 °F (reference ASHRAE 55-2010).
Due to known historic water intrusion in the building, there is the potential to encounter mold impacted materials during demolition and/or renovation. If during demolition/renovation, contractor personnel observe suspect mold contamination, work should immediately cease in the area until a designated Industrial Hygienist can be contacted to inspect the area. If mold is verified in the work area, the impacted materials should be removed by a qualified contractor using engineering controls prior to recommencing general demolition/renovation work.
Complete remediation of all microbial organisms within a building cannot be guaranteed. It is important to note that the reported mold levels are only reflective of conditions at the time of this test and that mold populations can vary over time, depending upon a number of conditions, including environmental factors (i.e., temperature and relative humidity). Once removed, if significant mold growth reappears, or if the occupants experience prolonged allergic-type health complaints, they should seek further investigation of the problem.
4.4 POTENTIAL HAZARDOUS MATERIALS
4.4.1 MERCURY
A total of 32 mercury containing lamps were identified on the site. One (1) thermostat was observed to be potentially mercury-containing. The mercury containing components should be recycled or disposed of at a landfill where hazardous materials are accepted. The lamps are considered Universal Construction
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
Waste. The Universal Waste Rule (EPA UWR) specifically mentions batteries, hazardous waste lamps, mercury containing equipment, and pesticides that are recalled, suspended, or collected for discarding as
Universal Wastes.
4.4.2 PCBS
F&R inspected a representative number of light fixtures for PCB’s. F&R did not observe any Non-PCB labels on the inspected light ballasts, therefore, all ballasts should be considered PCB-containing unless a Non-
PCB label is observed on the ballast.
5.0 APPLICABLE REGULATIONS
5.1 EPA / NESHAP REGULATIONS FOR ASBESTOS CONTAINING MATERIALS
The U.S. Environmental Protection Agency promulgated the National Emission Standards for Hazardous Air Pollutants (NESHAP) [40 CFR Part 61], which addresses the application, removal, and disposal of asbestos-containing materials (ACM). Under NESHAP the following categories are defined for asbestos-containing materials:
Friable - When dry, can be crumbled, pulverized, or reduced to powder by hand pressure.
Non-Friable - When dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.
Category I Non-Friable ACM - Packings, gaskets, resilient floor coverings, and asphalt roofing products containing more than 1% asbestos.
Category II Non-Friable ACM – Any material, excluding Category I Non-friable ACM, contains more than 1% asbestos.
Regulated Asbestos Containing Material (RACM) – One of the following:
1. Friable ACM
2. Category I Non-friable ACM that has become friable.
3. Category I Non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading.
4. Category II Non-friable ACM that has a high probability of becoming, or has become, friable by the forces expected to act on the material in the course of demolition or renovation operations.
Under NESHAP, the following actions are required:
1. Prior to the commencement of demolition or renovation activities, the building owner must inspect the affected facility or part of the facility where the demolition or renovation activities will occur for the presence of asbestos.
2. Remove all RACM from the facility before any activity begins that would break up, dislodge, or similarly disturb the material or preclude access for subsequent removal.
3. RACM need not be removed if:
a) It is Category I non-friable ACM that is not in poor condition.
b) It is on a facility component that is encased in concrete or other similar material and is adequately wet whenever exposed.
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
c) It was not accessible for testing and was therefore not discovered until after demolition began and because of the demolition the material cannot be safely removed.
d) It is Category II non-friable ACM and the probability is low that the material will become crumbled, pulverized, or reduced to powder during demolition.
5.2 OSHA REGULATIONS FOR LEAD-CONTAINING PAINT
Positive and negative results are based on the US Department of Housing and Urban Development (HUD) Guidelines. It is important to note that if a component is negative based on the HUD standard, it may still contain concentrations of lead in the paint which, when disturbed, may generate lead dust greater than the maximum exposure concentration of 30 micrograms per cubic millimeter established by the OSHA “Lead Exposure in Construction Rule (29 CFR 1926.62).” The OSHA standard gives no guidance on acceptable levels of lead in paint at which no exposure to airborne lead (above the action level) would be expected.
Rather, OSHA defines airborne concentrations, and references specific types of work practices and operations from which a lead hazard may be generated (reference 29 CFR 1926.62, section d).
Environmental and personnel monitoring should be conducted during any removal or demolition process (as appropriate) to determine actual personal exposure. This monitoring information can be used to determine the levels of personnel protection and environmental controls required for work involving specific removal/demolition processes on specific structures. Under OSHA requirements, the Contractor performing the work will be required to conduct this monitoring and follow all of the other requirements found in 29 CFR 1926.62. It is important to note that environmental controls will vary dependent upon the content of lead in paint, the process used to remove it, duration of the work, and the amount of paint to be removed.
5.3 EPA Regulations for Lead Based Paint Disposal
Based on the levels of lead found on painted building components throughout the property, it is anticipated that these components can be disposed of as non-hazardous waste. However, it is recommended that a Toxic Characteristic Leaching Procedure (TCLP) sample of the waste stream from demolition and renovation activities be collected to determine proper disposal procedures in accordance with Resource Conservation and Recovery Act (RCRA) regulations related to lead. Should painted components from this facility be sent to a recycling facility, this report should be made available to the accepting facility to properly notify them of the lead content of these components. Please note that compliance with RCRA regulations does not relieve the demolition contractor of the OSHA requirements referenced above.
5.4 MOLD
There are currently no regulatory standards or guidelines with respect to acceptable microbial levels inside buildings. This data has been interpreted qualitatively using general industry standards and previous experience. In general, industry standards call for inside microbial levels to be less than 25%-50% of outdoor levels in buildings with mechanically filtered air.
5.5 UNIVERSAL WASTE
The identified mercury containing and PCB-containing components should be recycled or disposed of at a landfill where hazardous materials are accepted. These materials are considered Universal Construction Waste. The Universal Waste Rule (EPA UWR) specifically mentions batteries, hazardous waste lamps, mercury containing equipment, and pesticides that are recalled, suspended, or collected for discarding as Universal Wastes.
Wright Brothers Memorial Limited Hazardous Materials Survey F&R Project # 66T-0146 September 8, 2015
6.0 LIMITATIONS
This report has been prepared for the exclusive use of the Hager Smith Design P.A., National Park Service, and/or their agents. This report has been prepared in accordance with generally accepted environmental practices. No other warranty, expressed or implied, is made. Our observations are based upon conditions readily visible at the site at the time of our site visit.
During this study, suspect asbestos samples were submitted for analysis at an NVLAP-accredited laboratory via polarized light microscopy. As with any similar survey of this nature, actual conditions exist only at the precise locations from which suspect asbestos samples were collected. Certain inferences are based on the results of this sampling and related testing to form a professional opinion of conditions in areas beyond those from which the samples were collected. No other warranty, expressed or implied, is made.
Under this scope of services, F&R assumes no responsibility regarding response actions (e.g. O&M Plans, Encapsulation, Abatement, Removal, Tenant Notification, etc.) initiated as a result of these findings. F&R assumes no liability for the duties and responsibilities of the Client with respect to compliance with these regulations. Compliance with regulations and response actions are the sole responsibility of the Client and should be conducted in accordance with local, state, and/or federal requirements and should be performed by appropriately qualified and licensed-personnel, as warranted.
Our observations and recommendations are based upon conditions readily visible at the site at the time of our site visit, and upon current industry standards. During F&R’s inspection, accessible areas were visually surveyed for the presence of suspect lead-based paint (LBP) containing materials. Inaccessible areas, such as behind solid ceilings or behind solid walls were not surveyed, therefore some lead-containing materials may not have been identified. Areas inspected for lead-based paint containing materials were limited to those designated by the scope of services by the Client. As with any similar survey of this nature, actual conditions exist only at the precise locations from which LBP samples were measured. Certain inferences are based on the results of this sampling and related testing to form a professional opinion of conditions in areas beyond those from which the samples were collected. No other warranty, expressed or implied, is made. Individuals who have completed the EPA/State approved lead risk assessor course collected all samples. Lead Dust Wipes and Soil samples were not collected. F&R did not sample drinking water, appliances, or bathroom fixtures as part of the scope of work.
The scope of services performed was limited to those requested by the Client and does not constitute a full microbial assessment of the site or a comprehensive moisture survey of the site. Because of the nature of this type of work (microbial contamination reduction) and the difficulties involved in conducting remediation work, F&R cannot guarantee that the methods or recommendations described in this report will eliminate all microbial contamination within the building, or prevent return of microbial contamination or re-growth under favorable conditions. Since monitoring the performance of the remediation work is beyond F&R's scope of services, F&R also cannot be held responsible for the performance or execution of the remediation work.
It is important to note that microbial levels may fluctuate dependent upon a variety of factors including the weather and time of year. The data provided in this study is only indicative of conditions sampled at the immediate time of the study. Professional services and scientific analyses have been performed, and recommendations prepared in accordance with customary principles in the fields of engineering and analytical science. This warranty is in lieu of all other warranties expressed or implied. The work performed in conjunction with this assessment and the data developed is intended as a description of available information at the dates and locations given. This report does not warrant against future operations or conditions, nor does it warrant against extant, or future, conditions of a type or at a location not investigated.
APPENDIX A
SITE PHOTOGRAPHS
ASBESTOS PHOTO LOG
Wright Brothers Memorial Asbestos Photolog
Kitty Hawk, North Carolina
Photo 1 - A view of the display area in the museum.
Photo 2 - View of the light grey 12”X12” vinyl floor tile sampled in the lobby and lobby display area.
Kitty Hawk, North Carolina
Photo 3 - View of the flight room sign containing unknown mastic (not sampled). ACM plaster through mesh on rear side of wall.
Photo 4 - View of pipe covering sampled in the vicinity of the lobby display area.
Kitty Hawk, North Carolina
Photo 5 - A view of the lobby display area.
Photo 6 - A view of the 4” black vinyl baseboard. ACM plaster through wire mesh on rear side of column.
Kitty Hawk, North Carolina
Photo 7 - View of the yellow 12”X12” floor tile sampled in the lobby display area.
Photo 8 - View of the 2”X4” acoustic drop ceiling tiles sampled in the lobby area.
Kitty Hawk, North Carolina
Photo 9 - General view of the book shop area
Photo 10 - View of the 2”X2” acoustic ceiling tiles sampled in the book shop area.
Kitty Hawk, North Carolina
Photo 11 - View of the dark grey 12”X12” floor tile sampled in the book store.
Photo 12 - View of the terrazzo-look rolled floor in the book store restroom.
Kitty Hawk, North Carolina
Photo 13 - View of the pipe elbows sampled in Book Store storage.
Photo 14 - View of the ACM Air Cell Pipe insulation and wrap.
Kitty Hawk, North Carolina
Photo 19 – View ACM of the plaster through wire mesh.
Photo 20 - View of the grey mastic on the HVAC duct.
Kitty Hawk, North Carolina
Photo 15 - General view of the flight room.
Photo 16 - View of the Turquoise 12”X12” floor tiles sampled in the flight room.
Kitty Hawk, North Carolina
Photo 17 - View of the textured ceiling material sampled in the flight room.
ACM plaster through wire mesh in columns.
Photo 18 - Additional view of the textured ceiling material in the flight room.
Kitty Hawk, North Carolina
Photo 19 – Black mastic on pipe wrap.
Photo 20 - View of the panel insulation and coal tar in display.
Kitty Hawk, North Carolina
Photo 19 - View of the blue ceiling tile peg-boards sampled.
Photo 20 - View of ‘hockey puck’ mastic associated with blue ceiling tile.
Kitty Hawk, North Carolina
Photo 21 - View of the ACM plaster within the wire mesh in Flight Room ceiling.
Photo 22 – Close view on the ACM plaster ceiling with wire mesh.
Kitty Hawk, North Carolina
Photo 21 – Assume mirror mastic as ACM.
Photo 22 - View of the terrazzo-look rolled floor in the outside restroom that was sampled.
Kitty Hawk, North Carolina
Photo 23 - View of ACM pipe wrap on ACM aircell insulation in pipe chase.
Photo 24 - View of mud elbow on piping.
Kitty Hawk, North Carolina
Photo 23 – Duct in Display wall.
Photo 24 – HVAC Duct mastic – tan.
Kitty Hawk, North Carolina
Photo 23 – Tan duct mastic under tape.
Photo 24 – HVAC Duct mastic – white.
Kitty Hawk, North Carolina
Photo 25 – Duct wrap.
Photo 26 – Window caulking.
Kitty Hawk, North Carolina
Photo 27 - View of ACM transite panel boards below the 3 windows on the exterior side of the Bookstore and Bookstore storage.
Photo 28 – Close view of the ACM transite window panel.
Kitty Hawk, North Carolina
Photo 29 - General view of the roof where the roof flashing tar and pitch pockets were sampled.
Photo 30 - Additional view of the roof.
LEAD PAINT PHOTO LOG
Lead Paint Photolog
Kitty Hawk, North Carolina
Photo 31 - View of the lobby entrance door casing sampled.
Photo 32 - General view of the concrete columns in the lobby area.
Kitty Hawk, North Carolina
Photo 33 - View of the drywall and laminate sampled in the lobby display area.
Photo 34 - View of the metal column sampled in the lobby area.
Positive for LBP
Kitty Hawk, North Carolina
Photo 35 - View of the metal support in the lobby area that was sampled.
Positive for LBP
Photo 36 - View of the red and grey painted floor in the book store closet area.
Kitty Hawk, North Carolina
Photo 37 - View of the utility sink in the book store closet area. Positive for
LBP
Photo 38 - View of the green metal door, orange door frame, brown door jamb in the utility closet of the book store. Positive for
LBP.
Kitty Hawk, North Carolina
Photo 39 - View of the green metal door and orange door frame book store closet area. Positive for LBP.
Photo 40 - View of the green metal door & orange door frame at bookstore entrance. Positive for LBP.
Kitty Hawk, North Carolina
Photo 41 - View of the concrete supports in the flight room.
Photo 42 - Exterior view of the metal window casings for the flight room.
Kitty Hawk, North Carolina
Photo 43 - View of the partition walls in the outside restroom.
Photo 44 - View of the glazed block walls in the outside restroom.
Kitty Hawk, North Carolina
Photo 45 - View of the changing table in the outside restroom.
Photo 46 - View of the glazed block wall in the utility closet of the bookstore
Kitty Hawk, North Carolina
Photo 47 - View of the orange metal baseboard in the Flight Room. Positive for LBP.
HAZARDOUS MATERIALS PHOTO LOG
Potential Hazardous Materials Photolog
Kitty Hawk, North Carolina
Photo 48 - View of small incandescent can-light fixtures along the exterior of the book store.
Photo 49 - View of exterior flood lights observed in vicinity of the building entrance; at the far side of the building; and courtyard entrance.
Kitty Hawk, North Carolina
Photo 50 - View of incandescent track lighting in the display area.
Photo 51 - View of exterior emergency lighting fixture
Kitty Hawk, North Carolina
Photo 52 - View of incandescent light observed in the employee bathroom.
Photo 53 - View of u-shaped fluorescent light observed in the book store and rest room light fixtures.
Kitty Hawk, North Carolina
Photo 54 - View of fluorescent bulbs used for the book store shelves.
Photo 55 - View of potential mercury-containing 4’ fluorescent tubes used in the employee office and storage area.
Kitty Hawk, North Carolina
Photo 56 - View of wall potential mercury-containing mounted thermostat .
Photo 57 - A view of wall mounted thermostat in bookstore office.
Kitty Hawk, North Carolina
Photo 58 - View of a mercury-containing light bulb observed in the book store closet.
Photo 59 - The brand of the mercury-containing light bulb observed in the book store closet.
MOLD PHOTO LOG
Limited IAQ Photolog
Kitty Hawk, North Carolina
Photo 60 - View of dust-loading observed within the HVAC ducts.
Photo 61 - Additional view of the dust-loading observed.
Limited IAQ Photolog
Kitty Hawk, North Carolina
Photo 62 - A closer view of the dust-loading observed within the HVAC ducts.
Photo 63 - View of a dust-loaded HVAC vent observed in he book store closet.
APPENDIX B
FLOOR PLANS
DN
DN
DN
DN
DN
DNDN
DN
ASSEMBLY/FLIGHT
ROOM
MUSEUM
LOBBY
WOMEN'S TOILET
MEN'S TOILET
MECH. MECH.
MECHANICAL ROOM
5A 5B
BOOKSTORE
OFC.
BOOKSTORE
OFC.
BOOKSTORE
STAFF
TOILET
JAN.
CLO. STO.
INFO.
0 88 16
SCALE OF FEET
EXISTING UNDERGROUND ELECTRICAL SERVICE
EXISTING UNDERGROUND
TEL/DATA LINE
TITLE OF DRAWING
PMIS/PKG. NO.
SHEET
OF
DRAWING NO.
PRIME/ARCH: CIVIL: MECHANICAL:
ELECTRICAL:STRUCTURAL:LANDSCAPE:
HAGERSMITH DESIGN, PA
300 S. DAWSON STREET
HAGERSMITH DESIGN, PA
300 S. DAWSON STREET
HAGERSMITH DESIGN, PA A/E CONTRACT NUMBER 1443CX2000
152008
SUB SHEET NO.DESIGNED:
CAD:
TECH. REVIEW:
DATE:
RALEIGH, NC
RALEIGH, NC
LYSAGHT ASSOCIATES
RALEIGH, NC
Approver
4 10
EXISTING FLOOR PLANSUD ASSOCIATES
DURHAM, NC
SUD ASSOCIATES
DURHAM, NC
CAPE HATTERAS NATIONAL
SEASHORE/WRIGHT BROTHERS NATIONAL
MEMORIAL VISITOR CENTER
Designer
Author
Checker
2-17-14
A-2
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Typewritten Text ACM Transite Window Panels
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Typewritten Text ACM Aircell Pipe Insulation and ACM Wrap
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Text Box
DPopeo Text Box
DPopeo Text Box
DPopeo Text Box
DPopeo Line
DPopeo Typewritten Text
POSITIVE ASBESTOS LOCATIONS
DPopeo Text Box
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Typewritten Text ACM Plaster Through Wire Mesh
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Line
DPopeo Line
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Line
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Line
DPopeo Typewritten Text
DPopeo Typewritten Text
DPopeo Line
DPopeo Line
DPopeo Line
DPo…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .