DRAWING NOTES:
1. CONTRACTOR STAGING AREA WILL BE AVAILABLE THROUGH
THE DURATION O F THE PROJECT BUT MUST BE KEPT CLEAN
AND DEBRIS SECURED FROM FLYING.
2. ACCESS ROAD TO STAGING AREA SHALL NOT BE BLOCKED
DURING DELIVERIES OR PICKUP TIMES.
3. CONTRACTOR SHALL PROVIDE THEIR OWN SECURED ACCESS
TO ALL ROOF AREAS.
4. MAINTAIN AREAS AROUND THE BUILDINGS CLEAN FROM
ROOFING DEBRIS.
5. CONTRACTOR SHALL AT ALL TIMES CONDUCT HIS OPERATIONS
TO ENSURE THE LEAST INCONVENIENCE TO THE PUBLIC AND
STAFF.
6. HEAVY TRAFFIC SHALL NOT BE ROUTED TO ROADWAYS CLOSE
TO SEAWALLS. CONTRACTOR SHALL COORDINATE WITH
CONTRACTING OFFICER REPRESENTATIVE FOR ACCESS OF
ALL TRAFFIC TO AND FROM STAGING AND LAY DOWN AREA.
1. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS.
2. REMOVE EXISTING MEMBRANE ROOF SYSTEM, INSULATION, FLASHING,
ACCESSORIES AND DISPOSE PROPERLY.
3. REMOVE WOOD NAILERS AND EDGE WOOD TRIMS AND DISPOSE PROPERLY.
4. REMOVE EXISTING EQUIPMENT STANDS.
5. REMOVE EXISTING LIGHTNING PROTECTION SYSTEM AERIALS AND BASES.
6. CONTRACTOR SHALL ENSURE ROOF DEBRIS IS PROPERLY REMOVED AND
DISPOSED OF APPROPRIATELY. CONTRACTOR SHALL TAKE EVERY MEASURE
NECESSARY TO AVOID FLYING DEBRIS OFF THE ROOF INTO THE GROUND AND
BAY. CONTRACTOR SHALL IMMEDIATELY REMOVE SUCH DEBRIS WHEN IT
OCCURS.
7. CONTRACTOR SHALL PROVIDE THEIR OWN ACCESS TO THE ROOF AND WILL
COORDINATE LOCATION WITH CONTRACTING OFFICER REPRESENTATIVE.
8. CONTRACTOR MUST SECURE ALL ASSIGNED LAYDOWN AREAS WITH A MINIMUM
OF ORANGE SAFETY FENCING. ALL FEATURES INCLUDING NEARBY TREES SHALL
ALSO BE PROTECTED.
BREEZEWAY ROOF EQUIPMENT STAND SETUP 2
VC ROOF
ROOF LAYOUT
VC ROOF
BREEZEWAY ROOF STAGING AREA
RESTAURANT SIDE
STAGING AREA
RESTAURANT SIDE
ANTENNA
VC ROOF
PARAPET DETAIL
VC ROOF
ROOF MOUNTED CONDENSING UNIT SETUP 1
VC ROOF
CABLE GEAR
VC ROOF
ELEVATED ROOF
VC ROOF
SERVICE ENTRANCE
VC ROOF
PLUMBING VENT
VC ROOF
ANTENNA CABLE GEAR
VC ROOF
ROOF ACCESS LADER LOCATION
VC ROOF
ROOF MOUNTED CONDENSING UNIT SETUP 2
GENERAL NOTES:
2. INSTALL NEW FULLY ADHERED POLYISOCIANURATE ROOF INSULATION. MINIMUM
THICKNESS AT LOWEST POINT IS 3". SLOPE UP TO MEET MINIMUM 1:48 (
" PER 12")
SLOPE.
3. INSTALL NEW FULLY ADHERED 3-PLY SBS MODIFIED BITUMINOUS BUR SYSTEM
WITH CAP SHEET.
4. EXISTING EQUIPMENT STANDS TO BE REPLACED, SEE SHEET A-3.3.
5. PAINT PARAPET AND AREAS AFFECTED BY THIS WORK TO MATCH EXISTING
HISTORICAL COLOR SCHEME.
6. REFER TO SHEET A1.1 FOR ADDITIONAL DETAIL ON EACH ROOF AREA.
7. INSTALL NEW LIGHTNING PROTECTION SYSTEM, SEE SHEET A-3.4 FOR PLAN AND
DETAILS.
2. INSTALL NEW FULLY ADHERED POLYISOCIANURATE ROOF
INSULATION. MINIMUM THICKNESS AT LOWEST POINT IS 3". SLOPE UP
TO MEET MINIMUM 1:48 (
" PER 12") SLOPE.
3. INSTALL NEW FULLY ADHERED 3-PLY SBS MODIFIED BITUMINOUS BUR
SYSTEM WITH CAP SHEET.
4. INSTALL NEW PARAPET DETAIL AS INDICATED. FLASHING AS
INDICATED TYPICAL ON ALL EQUIPMENT STANDS ON ROOF. NEW
EXTRUDED ALUMINUM EQUIPMENT STANDS SHALL BE FABRICATED
AND INSTALLED IN ACCORDANCE WITH STRUCTURAL REQUIREMENTS
OF THE 2010 FLORIDA BUILDING CODE. ALL EXISTING EQUIPMENT
SHALL BE RE-INSTALLED ON NEW STANDS AND TESTED PRIOR TO
ACCEPTANCE.
5. FLASH ALL ROOF PENETRATIONS FOLLOWING CORRESPONDING
DETAIL ON SHEETS A3.1- A3.2.
6. LOCATE MEMBRANE LAYER VENTS AS RECOMMENDED BY SBS
MODIFIED BITUMINOUS ROOF SYSTEM MANUFACTURER, SEE DETAIL 5
ON SHEET A3.1.
7. INSTALL NEW LIGHTNING PROTECTION SYSTEM, SEE SHEET A-3.3 FOR
PLAN AND DETAILS.
KEY PLAN
Level 1
8' - 0"
Level 1
8' - 0"
Level 2
20' - 6"
Level 2
20' - 6"
Roof Plan
30' - 6"
MSL
0' - 0"
Level 1
8' - 0"
Level 2
20' - 6"
DRAWING NOTES:
1. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS.
2. ELEVATIONS ARE PROVIDED FOR ILLUSTRATION PURPOSES.
3. INSTALL NEW FULLY ADHERED 3-PLY SBS MODIFIED
BITUMINOUS BUR SYSTEM WITH CAP SHEET.
4. INSTALL NEW PARAPET DETAIL AS INDICATED.
5. BID INCLUDES ALL WORK ASSOCIATED TO THE REPLACEMENT
OF EXISTING TPO ROOFING FOR NEW SBS MODIFIED
BITUMINOUS BUR SYSTEM WITH ALL ACCESSORIES OVER THE
VISITORS CENTER SIDE AND INTERCONNECTING BREEZEWAY
UP TO BUT NOT INCLUDING RESTAURANT SIDE. INSTALLATION
OF NEW ROOF ACCESS LADDER ON THE RESTAURANT SIDE
SHALL BE PART OF THIS PROJECT.
FASTENERS STAGGERED APPROX.
6" O.C. ON ROOF FLANGE
FASTENERS APPROX. 12" O.C.
(6" O.C. AT CORNERS)
CONTINUOUS GALVANIZED
ANCHOR CLEAT
4" CONCEALED JOINT
SPLICE PLATES
10" ALUMINUM FASCIA
TYPICAL
1. INSTALL CONTINUOUS ANCHOR CLEAT OVER THE TURNED DOWN CAP SHEET, NAILING PER INSTRUCTIONS.
2. SET PREFABRICATED CORNER SECTIONS.
3. INSTALL FASCIA LENGTHS WITH CONCEALED JOINT-SPLICE PLATES AT ALL JOINTS.
4. PRIME PERFORATED TOP PLATE THEN CAREFULLY SEAL THE FLASHING PLY TO THE CAP SHEET.
PERFORATED TOP PLATE
-PRIME BEORE SETTING FLASHING
CAP SHEET
NOTE:
MULTI-PLY MODIFIED
BITUMEN ROOF MEMBRANE
3" MINIMUM THICKNESS OF
POLYISOCYANURATE INSULATION
AT LOWEST END
NEW WOOD
BLOCKING
PAINT ALL EXPOSED WOOD EDGES
NEW STRUCTURAL FRAME
CAULK
DRAW BAND WITH BUTYL TAPE
WATERTIGHT UMBRELLA OVERLAPPING
JACK BY RADIUS OF 3" TO 4"
1/4" MINIMUM
1/4" MINIMUM CLEARANCE TO PIPE
ROOF DECK
CLEARANCE
TO UMBRELLA
BASE FLASHING
COVERBORAD INSULATION
MULTI-PLY MODIFIED
BITUMEN ROOF MEMBRANE SYSTEM
M
I
N
ROLL LEAD FLASHING 1" DOWN
INTO PIPE
PLUMBING VENT STACK
2. MINIMUM 18" CLEARANCE FROM PIPES,
M
I
N
SHEET METAL PLATE OVER ROOF SLAB
ROOF INSULATION
CAP SHEET
BASE FLASHING
WALLS AND CURBS.
NOTE:
PRIMED LEAD FLASHING, MINIMUM 2
1/2 TO 4 LBS. SET PRIMED FLANGE IN
ROOFCEMENT ON MOP, COLD MB,
SA-MB AND BUR. SET PRIMED FLANGE
IN HEAT SOFTENED MEMBRANE ON
TORCH APP AND HW SBS
1. SHEET LEAD MINIMUM OF 2-1/2 POUNDS PER
SQUARE FOOT.
MULTI-PLY MODIFIED
BITUMEN ROOF MEMBRANE
GENERAL NOTES:
1. DETAILS SHALL CONFORM TO NRCA 2005 OR LATER
VERSION FOR SBS MODIFIED BITUMINOUS
ROOFING.
2. ALL MATERIALS SHALL NEW OFF STOCK ITEMS.
3. GRAVEL STOP VARIES IN PROFILE. PROFILE GAUGE
SHALL FOLLOW NRCA MINIMUM FOR BOTH
ALUMINUM FASCIA AND CLEATS.
1. DETAILS SHALL CONFORM TO NRCA 2005 OR LATER
VERSION FOR SBS MODIFIED BITUMINOUS
ROOFING.
2. ALL MATERIALS SHALL NEW OFF STOCK ITEMS.
3. INSTALL NEW ALUMINUM TRANSITION LADDER.
INSTALLATION OF THIS LADDER WILL BE
AUTHORIZED ONCE INTERNAL NPS
COMPLIANCE DOCUMENTATION HAS BEEN
COMPLETED.
2. INSTALL NEW ALUMINUM ROOF ACCESS LADDER WITH CAGE. INSTALLATION OF THIS LADDER WILL BE AUTHORIZED
ONCE INTERNAL NPS COMPLIANCE DOCUMENTATION HAS BEEN COMPLETED.
3. NEW EXTRUDED ALUMINUM EQUIPMENT STANDS SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH
STRUCTURAL REQUIREMENTS OF THE 2010 FLORIDA BUILDING CODE. ALL EXISTING EQUIPMENT SHALL BE
RE-INSTALLED ON NEW STANDS AND TESTED PRIOR TO ACCEPTANCE.
1. SEE SPECIFICATION 264113 LIGHTNING PROTECTION.
2. THE PLANS ARE SCHEMATIC - THE INSTALLATION
SHALL COMPLY WITH NFPA 780 AND NFPA 70.
3. INSTALL ALL AIR TERMINALS, ROOF CONDUCTORS, AND
VERTICAL CONDUCTORS DOWN TO APPROXIMATE
GRADE, AND TIE TO NEW COPPER GROUNDING ROD TO
PROVIDE A NEW COMPLETE FULLY CERTIFIED SYSTEM.
4. AIR TERMINALS SHALL BE GLUED DOWN SYSTEM ONLY
AND SHALL BE LISTED BY UNDERWRITERS LABORATORY.
5. COMPLETED SYSTEM SHALL BEAR U.L. MASTER LABEL
AND SHALLBE SECURED BY SYSTEM INSTALLER IN
ACCORDANCE WITH UL96A.
6. CONTRACTOR SHALL VERIFY COMPATIBILITY OF
ADHESIVE ON MEMBRANE ROOF APPLICATION PRIOR
TO INSTALLATION.