P12-VAV PANAM 0252-9MH610.pdf
PDF 199 KB Posted
- Attached to
- Z2DA--CFM - Rebalance HVAC System Federal contract opportunity
- Solicitation number
- Not on record
About this file
This document is an HVAC air terminal unit and fan coil unit schedule for a VA medical center renovation project. It provides specifications for 91 single duct air terminal units to be installed on various floors of the building, including required sizes, maximum and minimum airflow capacities, water flow rates, and control types. It also schedules 4 fan coil units for the basement level and specifies control types for computer room air conditioners and additional fan coil units on floors 1 through 6. Notes provide references to other drawings for schedule capacities and sound attenuator requirements.
View the file
Other files for this federal contract opportunity
Show all 50
Z2DA--CFM - Rebalance HVAC System has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES:
1. FOR SYMBOL LISTS, ABBREVIATIONS, AND GENERAL
NOTES THAT APPLY TO ALL DRAWINGS SEE THE
9MH-0 SERIES OF DRAWINGS.
2. FOR GENERAL DETAILS SEE THE 9MH-5 SERIES OF
DRAWINGS.
3. FOR CONTROL DIAGRAMS SEE THE 9MH-8 SERIES OF
DRAWINGS.
4. FOR VALVE INFORMATION SEE NOTE 27 ON 9MH002.
SLVHCS
REPLACEMENT MEDICAL CENTER
PROJECT
629-HS2-401
DATE
LOCATION
CHECKED DRAWN
PROJECT TITLE PROJECT NUMBER
DOCUMENT SET PACKAGE
DRAWING NUMBERAPPROVED: PROJECT DIRECTOR
DRAWING TITLE
ARCHITECT/ENGINEERS:CONSULTANTS: OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
NEW ORLEANS, LOUISIANA
REVISIONS: DATE
B
A
D
C
E
VA FORM 08-6231
O N E E
IG
H T I N C H O N E F O O T
O N E Q U A R T E R I N C H O N E F O O T
O N E H A L F I N C H O N E F O O T
T H R E E Q U A R T E R S I N C H O N E F O O T
T H R E E I N C H E S O N E F O O T
O N E I N C H F O R T Y F E E T
FULLY SPRINKLERED
SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL
KORDA/NEMETH ENGINEERING / STRUCTURAL
BR+A CONSULTING ENGINEERS / MECHANICAL, ELECTRICAL & PLUMBING
ARCHITECTURAL ENGINEERING / PLUMBING
SCALES ASSOCIATES / FIRE PROTECTION
COMMUNICATIONS DESIGN GROUP / LOW VOLTAGE
DESMAN ASSOCIATES / PARKING
CODE CONSULTANTS, INC. / CODE CONSULTANT
THE SEXTANT GROUP / AV & ACOUSTICAL
HAMMER DESIGN ASSOCIATES / FOOD SERVICE
PYBURN & ODOM / ABATEMENT
123456
F
B
A
D
C
E
F
Construction Documents 1
O N E S
IX
T E E N T H I N C H O N E F O O T
O N E A N D O N E H A L F I N C H E S O N E F O O T
BUILDING NUMBER
9MH610
BLDG 9 HVAC AIR TERMINAL UNIT AND FAN COIL
UNIT SCHEDULE
TA RPBJUNE 7, 2011
EWP_03
SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (FLOOR 1)
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 09-1Q E 1100 350 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-2 09-1Q D 750 350 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-3 1Q133 09-1Q B 650 650 0.5 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-4 1Q-C06 09-1Q C 650 650 1.0 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-5 09-1Q B 450 450 0.5 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-6 1Q-C04 09-1Q D 1000 1000 1.5 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-7 1Q-C04 09-1Q D 800 800 1.5 CV DETAIL 3 ON 9MH804 NOTE (2)
S-8 1Q-C05 09-1Q D 800 800 1.5 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-9 1Q130 09-1Q E 1100 350 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-10 1Q130 09-1Q D 750 350 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-11 1Q146 09-1Q C 800 800 1.0 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-12 1Q102 09-1Q C 1500 950 1.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-13 1Q122 09-1Q F 1500 825 1.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-14 1Q115 09-1Q B 200 100 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-15 1Q114D 09-1Q E 1050 550 1.25 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-16 1Q114 09-1Q G 1750 1750 3.0 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-17 1Q114A 09-1Q F 1500 900 1.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-18 1Q114A 09-1Q B 400 400 .75 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-19 1Q139 09-1Q D 800 800 1.5 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-20 1Q108B 09-1Q B 500 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (1),(2)
S-21 1Q100 09-1Q E 1200 350 0.75 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-22 09-1Q D 875 875 1.25 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-23 1Q102 09-1Q G 1800 950 1.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-24 1Q100 09-1Q E 900 350 0.75 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-25 1Q123B 09-1Q C 300 150 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-26 09-1Q B 375 150 0.5 VCV DETAIL 4 ON 9MH804 NOTE (1),(2)
S-27 1Q107 09-1Q B 400 150 0.5 VCV DETAIL 4 ON 9MH804 NOTE (1),(2)
S-28 1Q144 09-1Q B 950 475 0.5 VCV DETAIL 4 ON 9MH804 NOTE (1),(2)
S-29 1Q115 09-1Q C 600 225 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-30 1Q123B 09-1Q C 400 200 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (FLOOR 2)
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 2Q138 09-2Q G 2000 750 1.25 VCV DETAIL 4 ON 9MH804 NOTE (1),(2),(3)
S-2 2Q138 09-2Q C 600 300 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-3 2Q138 09-2Q D 800 375 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-4 2Q127 09-2Q E 1000 525 1.25 VCV DETAIL 4 ON 9MH804 NOTE (1),(2),(3)
S-5 2Q127 09-2Q C 500 250 0.75 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-6 2Q123 09-2Q B 400 200 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-7 2Q-C01 09-2Q C 600 300 0.75 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-8 2Q121 09-2Q C 525 300 0.75 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-9 2Q121 09-2Q E 1300 1300 2.25 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-10 2Q121 09-2Q D 750 275 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-11 2Q121 09-2Q C 600 300 0.75 VCV DETAIL 4 ON 9MH804 NOTE (1),(2)
S-12 2Q128 09-2Q A 200 200 0.5 CV DETAIL 3 ON 9MH804 NOTE (2)
S-13 2Q126 09-2Q A 150 75 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-14 2Q101 09-2Q F 1650 1650 2.75 CV DETAIL 3 ON 9MH804 NOTE (2)
S-15 2Q-C01 09-2Q E 1000 350 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-16 2Q-C03 09-2Q B 325 175 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-17 2Q-C01 09-2Q E 1000 350 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-18 2Q101 09-2Q D 800 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-19 2Q109 09-2Q E 950 350 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-20 2Q-C01 09-2Q E 1000 350 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-21 2Q110 09-2Q C 800 800 1.5 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-22 2Q108 09-2Q B 225 125 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-23 2Q103 09-2Q D 750 750 1.25 CV DETAIL 3 ON 9MH804 NOTE (2)
S-24 2Q108 09-2Q B 400 400 1.0 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-25 2Q106 09-2Q B 250 100 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-26 2Q104 09-2Q C 450 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-27 2Q102 09-2Q B 300 100 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (FLOOR 4)
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 4Q102 09-4Q B 375 125 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-2 4Q104 09-4Q C 450 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-3 4Q-C01 09-4Q B 300 300 0.75 CV DETAIL 3 ON 9MH804 NOTE (2)
S-4 4Q108 09-4Q A 150 100 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-5 4Q106 09-4Q B 300 300 0.75 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-6 4Q-C01 09-4Q C 450 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-7 4Q118 09-4Q D 700 700 1.5 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-8 4Q120 09-4Q B 200 200 0.5 CV DETAIL 3 ON 9MH804 NOTE (2)
S-9 4Q101J 09-4Q C 450 225 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-10 4Q-C01 09-4Q B 350 150 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-11 4Q124 09-4Q C 450 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (1),(2)
S-12 4Q130 09-4Q C 600 325 0.75 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-13 4Q130 09-4Q D 725 725 1.75 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-14 4Q130B 09-4Q A 150 100 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-15 4Q132 09-4Q B 200 200 0.5 CV DETAIL 3 ON 9MH804 NOTE (2)
S-16 4Q134 09-4Q B 300 100 0.5 VCV DETAIL 4 ON 9MH804 NOTE (1),(2)
S-17 4Q138 09-4Q C 450 225 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-18 4Q142 09-4Q B 300 300 0.75 CV DETAIL 3 ON 9MH804 NOTE (2)
S-19 4Q144 09-4Q B 300 125 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-20 4Q139 09-4Q B 300 150 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-21 4Q-C03 09-4Q C 475 225 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-22 4Q135 09-4Q B 400 200 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-23 4Q125 09-4Q C 600 200 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-24 4Q123 09-4Q C 600 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-25 4Q123 09-4Q B 200 200 0.5 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-26 4Q141 09-4Q D 775 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-27 4Q117 09-4Q E 1025 350 0.75 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-28 4Q109 09-4Q D 700 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-29 4Q101G 09-4Q B 375 375 1.0 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-30 4Q101G 09-4Q C 600 200 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-31 4Q101H 09-4Q B 225 100 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (FLOOR 5)
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 5Q141 09-5Q E 1200 375 0.75 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-2 5Q141 09-5Q A 200 125 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-3 5Q141 09-5Q C 450 175 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-4 5Q-C03A 09-5Q B 400 200 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-5 5Q132 09-5Q E 1200 375 0.75 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-6 5Q-C02 09-5Q B 325 175 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-7 5Q133 09-5Q C 475 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-8 5Q129 09-5Q E 975 350 0.75 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-9 5Q-C03A 09-5Q C 500 375 0.75 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-10 5Q126 09-5Q B 300 175 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-11 5Q126 09-5Q D 975 975 1.75 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-12 5Q122 09-5Q B 450 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-13 5Q118 09-5Q B 325 325 0.5 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-14 5Q116 09-5Q B 300 175 0.5 VCV DETAIL 4 ON 9MH804 NOTE (1),(2)
S-15 5Q121 09-5Q C 450 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (1),(2)
S-16 5Q114 09-5Q B 300 175 0.5 VCV DETAIL 4 ON 9MH805 NOTE (2)
S-17 5Q112 09-5Q D 900 900 1.5 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-18 5Q142 09-5Q B 300 150 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-19 5Q113 09-5Q C 650 300 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-20 5Q111 09-5Q C 575 200 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-21 5Q108 09-5Q C 450 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-22 5Q142 09-5Q A 225 125 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-23 5Q100A 09-5Q F 1650 525 1.0 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-24 5Q-C01 09-5Q C 600 325 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-25 5Q100A 09-5Q D 850 425 0.75 VCV DETAIL 4 ON 9MH804 NOTE (2)
SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (FLOOR BQ)
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 BQ110 09-BQ H 2700 1125 2.0 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-2 BQ110 09-BQ H 2700 1125 2.0 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-3 BQ110 09-BQ E 1400 1400 2.25 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-4 BQ110 09-BQ D 700 700 1.25 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-5 BQ110 09-BQ G 1800 1800 3.0 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-6 BQ110 09-BQ E 1000 1000 1.75 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-7 BQ138 09-BQ C 650 650 1.0 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-8 BQ106 09-BQ E 1100 1100 1.75 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-9 BQ106 09-BQ H 3000 3000 5.0 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (FLOOR 3)
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)
CONTROL
TYPE
CONTROL
SEQUENCE Remarks
S-1 3Q140 09-3Q B 225 100 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-2 3Q140 09-3Q E 1300 650 1.25 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-3 3Q140 09-3Q C 500 200 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-4 3Q144 09-3Q D 800 300 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-5 3Q140 09-3Q A 200 100 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-6 3Q140 09-3Q C 500 200 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-7 3Q138 09-3Q B 225 125 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-8 3Q123 09-3Q A 275 275 0.5 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-9 3Q123 09-3Q C 600 200 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-10 3Q119 09-3Q D 725 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-11 3Q134 09-3Q C 450 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-12 3Q128A 09-3Q B 225 125 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-13 3Q128A 09-3Q D 800 800 1.5 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-14 3Q111 09-3Q C 600 300 0.75 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-15 3Q128 09-3Q C 450 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (1),(2)
S-16 3Q126 09-3Q C 600 300 0.75 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-17 3Q-C02 09-3Q D 850 275 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-18 3Q126 09-3Q D 775 775 1.5 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-19 3Q101A 09-3Q C 600 200 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-20 3Q122 09-3Q C 450 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-21 3Q101G 09-3Q C 600 225 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-22 3Q112 09-3Q A 225 225 0.5 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-23 3Q108 09-3Q C 450 250 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-24 3Q104 09-3Q B 300 100 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-25 3Q114 09-3Q A 200 100 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-26 3Q106 09-3Q A 150 150 0.5 CV DETAIL 3 ON 9MH804 NOTE (2)
S-27 3Q101-1 09-3Q C 500 500 1.25 CV DETAIL 3 ON 9MH804 NOTE (1),(2)
S-28 3Q101J 09-3Q B 350 150 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
S-29 3Q101K 09-3Q C 450 150 0.5 VCV DETAIL 4 ON 9MH804 NOTE (2)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE (FLOOR BQ)
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
FCU-1 BQ105 09-BQ A1 CV DETAIL 2 ON 9MH804 NOTE (1)
FCU-2 BQ106 09-BQ E1 CV DETAIL 1 ON 9MH804 NOTE (1)
FCU-3 09-BQ B1 CV DETAIL 2 ON 9MH804 NOTE (1)
FCU-4 09-BQ B1 CV DETAIL 2 ON 9MH804 NOTE (1)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE (FLOOR 1)
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC-1 09-1Q H2 CV DETAIL 1 ON 9MH805 NOTE (1)
CAC-2 1Q-C05 09-1Q H1 CV DETAIL 1 ON 9MH805 NOTE (1)
CAC-3 1Q112 09-1Q H1 CV DETAIL 1 ON 9MH805 NOTE (1)
CAC-4 1Q112 09-1Q H1 CV DETAIL 1 ON 9MH805 NOTE (1)
FCU-1 1Q-C03 09-1Q E1 CV DETAIL 1 ON 9MH804 NOTE (1)
FCU-2 1Q126 09-1Q F1 CV DETAIL 1 ON 9MH804 NOTE (1)
FCU-3 1Q117 09-1Q F1 CV DETAIL 1 ON 9MH804 NOTE (1)
FCU-4 1Q117 09-1Q F1 CV DETAIL 1 ON 9MH804 NOTE (1)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE (FLOOR 2)
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC-1 2Q-C01 09-2Q H1 CV DETAIL 1 ON 9MH805 NOTE (1)
FCU-1 2Q-C03 09-2Q E1 CV DETAIL 1 ON 9MH804 NOTE (1)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE (FLOOR 3)
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC-1 3Q-C01A 09-3Q H1 CV DETAIL 1 ON 9MH805 NOTE (1)
FCU-1 3Q101-1 09-3Q E1 CV DETAIL 1 ON 9MH804 NOTE (1)
FCU-2 3Q125 09-3Q G2 CV DETAIL 1 ON 9MH804 NOTE (1)
FAN COIL UNIT/ COMPUTER ROOM AC SCHEDULE (FLOOR 4)
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC-1 4Q-C01 09-4Q H1 CV DETAIL 1 ON 9MH805 NOTE (1)
FCU-1 4Q-C03 09-4Q E1 CV DETAIL 1 ON 9MH804 NOTE (1)
FCU-2 4Q131 09-4Q G1 CV DETAIL 1 ON 9MH804 NOTE (1)
FAN COIL UNIT / COMPUTER ROOM AC SCHEDULE (FLOOR 5)
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
CAC-1 5Q-C01 09-5Q H1 CV DETAIL 1 ON 9MH805 NOTE (1)
FCU-1 09-5Q E1 CV DETAIL 1 ON 9MH804 NOTE (1)
FAN COIL UNIT / COMPUTER ROOM AC SCHEDULE (FLOOR 6)
MARK LOCATION
AREA AND/OR
BLDG SERVED SIZE
CONTROL
TYPE CONTROL SEQUENCE Remarks
FCU-1 09-6Q C1 CV DETAIL 2 ON 9MH804 NOTE (1)
FCU-2 09-6Q C1 CV DETAIL 2 ON 9MH804 NOTE (1)
FCU-3 09-6Q D1 CV DETAIL 2 ON 9MH804 NOTE (1)
FCU-4 09-6Q D1 CV DETAIL 2 ON 9MH804 NOTE (1)
NOTE: (1) INTEGRAL SOUND ATTENUATING DEVICE NOT REQUIRED.
(2) REFER TO DRAWING 9MH607 FOR SCHEDULE CAPACITIES FOR VCV AND CV.
(3) REFER TO DRAWING 9MH603 FOR DOWNSTREAM SOUND ATTENUATOR REQUIREMENT.
NOTE: (1) REFER TO DRAWING 9MH607 FOR SCHEDULE CAPACITIES FOR FCU AND CAC.
NOTE: (1) INTEGRAL SOUND ATTENUATING DEVICE NOT REQUIRED.
(2) REFER TO DRAWING 9MH607 FOR SCHEDULE CAPACITIES FOR VCV AND CV.
(3) REFER TO DRAWING 9MH603 FOR DOWNSTREAM SOUND ATTENUATOR REQUIREMENT.
NOTE: (1) REFER TO DRAWING 9MH607 FOR SCHEDULE CAPACITIES FOR FCU AND CAC.
NOTE: (1) REFER TO DRAWING 9MH607 FOR SCHEDULE CAPACITIES FOR FCU AND CAC.
NOTE: (1) REFER TO DRAWING 9MH607 FOR SCHEDULE CAPACITIES FOR FCU AND CAC.
NOTE: (1) REFER TO DRAWING 9MH607 FOR SCHEDULE CAPACITIES FOR FCU AND CAC.
NOTE: (1) REFER TO DRAWING 9MH607 FOR SCHEDULE CAPACITIES FOR FCU AND CAC.
NOTE: (1) REFER TO DRAWING 9MH607 FOR SCHEDULE CAPACITIES FOR FCU AND CAC.
NOTE: (1) INTEGRAL SOUND ATTENUATING DEVICE NOT REQUIRED.
(2) REFER TO DRAWING 9MH607 FOR SCHEDULE CAPACITIES FOR VCV AND CV.
(3) REFER TO DRAWING 9MH603 FOR DOWNSTREAM SOUND ATTENUATOR REQUIREMENT.
NOTE: (1) INTEGRAL SOUND ATTENUATING DEVICE NOT REQUIRED.
(2) REFER TO DRAWING 9MH607 FOR SCHEDULE CAPACITIES FOR VCV AND CV.
(3) REFER TO DRAWING 9MH603 FOR DOWNSTREAM SOUND ATTENUATOR REQUIREMENT.
NOTE: (1) INTEGRAL SOUND ATTENUATING DEVICE NOT REQUIRED.
(2) REFER TO DRAWING 9MH607 FOR SCHEDULE CAPACITIES FOR VCV AND CV.
(3) REFER TO DRAWING 9MH603 FOR DOWNSTREAM SOUND ATTENUATOR REQUIREMENT.
NOTE: (1) INTEGRAL SOUND ATTENUATING DEVICE NOT REQUIRED.
(2) REFER TO DRAWING 9MH607 FOR SCHEDULE CAPACITIES FOR VCV AND CV.
(3) REFER TO DRAWING 9MH603 FOR DOWNSTREAM SOUND ATTENUATOR REQUIREMENT.
1 Addendum # 1 06/17/11
3 Addendum # 3 07/01/11
RFI:00847 -Air Terminal Unit sizing incorrect and should meet the criteria on the Air Terminal Unit Schedule on drawing
9MH605.
RFI-847.1, 5TH
FLOOR S-12 SIZE
SHOULD BE "C"