P01 - DRAWINGS 2 - Copy.pdf
PDF 9 MB Posted
- Solicitation number
- 36C24220B0067
About this file
This document is a set of construction drawings and specifications for an upgrade and improvement project to plumbing systems at the East Orange Veterans Affairs Medical Center. Key details include upgrading and improving plumbing piping systems across multiple buildings; replacing fixtures, equipment, and associated components; addressing deficiencies through repairs, replacements, and renovations; and removing obsolete plumbing as indicated. The project involves demolition, new installation, and reconfiguration of domestic cold and hot water, sanitary waste and vent, and other piping. Bidders are required to thoroughly inspect existing conditions and coordinate work between trades to complete upgrades per code and specifications.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24220B0067 0002_1.docx | DOCX document | |
| S05 - Answers to RFIs.pdf | ||
| 36C24220B0067 0001_1.docx | DOCX document | |
| Specifications Combined.pdf | ||
| P07 - Wage Determination - Essex County NJ 11-05-2020.pdf | ||
| P01 - DRAWINGS 1 - Copy.pdf | ||
| P01 - DRAWINGS 3 - Copy.pdf | ||
| P01 - DRAWINGS 5 - Copy.pdf | ||
| P01 - DRAWINGS 4 - Copy.pdf | ||
| Specifications Combined - Copy.pdf | ||
| 36C24220B0067_2.docx | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F.R.O.
GENERAL PLUMBING SYMBOLS, NOTES AND
ABBREVIATIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
FOR BID CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
IMPROVE AND UPGRADE
PL SYSTEM
561-18-101
08/18/2020Revisions: Date:
VANJ HEALTHCARE SYSTEM
385 TREMONT AVE,
EAST ORANGE, NJ 07018
D.L.E.
PL-001
AutoCAD SHX Text EXISTING DEAD LEG PIPING TO BE REMOVED. REMOVE ALL ASSOCIATED FIXTURES, VALVES, CAPS AND OTHER APPURTENANCES.
AutoCAD SHX Text CUT AND CAP DEAD LEG PIPING BACK TO TEE. DISTANCE FROM CAP TO EXISTING PIPING TO REMAIN NOT TO EXCEED TWICE THE DIAMETER OF THE BRANCH, RISER, OR MAIN THAT IT IS CONNECTED TO.
AutoCAD SHX Text
FINISHED FLOOR
AutoCAD SHX Text
EXISTING PIPING
AutoCAD SHX Text
TYPICAL POINT OF CONNECTION
AutoCAD SHX Text
%%UPLUMBING PIPING SYMBOLS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WB
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ARCHITECTURAL ABBREVIATIONS
AutoCAD SHX Text MR MECHANICAL ROOM MECHANICAL ROOM MS MECHANICAL SPACE MECHANICAL SPACE PB PIPE BASEMENT PIPE BASEMENT PH PENTHOUSE PENTHOUSE SR SERVICE ROOMSERVICE ROOM
AutoCAD SHX Text A ATTIC ATTIC AS ATTIC SPACE ATTIC SPACE B BASEMENT BASEMENT COR CORRIDOR CORRIDOR G GROUND FLOOR GROUND FLOOR MEZZ MEZZANINEMEZZANINE
AutoCAD SHX Text BFP REDUCED PRESSURE BACKFLOW REDUCED PRESSURE BACKFLOW REDUCED PRESSURE BACKFLOW PREVENTER BP BOOSTER PUMP BOOSTER PUMP BT BATHTUB BATHTUBBATHTUB
AutoCAD SHX Text A/E ARCHITECT/ENGINEER ARCHITECT/ENGINEER AFF ABOVE FINISHED FLOOR ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE ABOVE FINISHED GRADE AP ACCESS PANEL ACCESS PANEL ASHRAE AMERICAN SOCIETY OF HEATING, AMERICAN SOCIETY OF HEATING, REFRIGERATION, AIR CONDITIONING ENGINEERS ASME AMERICAN SOCIETY OF MECHANICAL AMERICAN SOCIETY OF MECHANICAL ENGINEERS ASPE AMERICAN SOCIETY OF PLUMBING AMERICAN SOCIETY OF PLUMBING ENGINEERS
AutoCAD SHX Text C CELSIUS CELSIUS CO CLEANOUT CLEANOUT CS CLINICAL SINK CLINICAL SINK Cu COPPER COPPER CV CONTROL VALVE CONTROL VALVE CW COLD WATERCOLD WATER
AutoCAD SHX Text DI DEIONIZED WATER DEIONIZED WATER DEIONIZED WATER DN DOWN DOWN DOWN DOE DEPARTMENT OF ENERGY DEPARTMENT OF ENERGY DEPARTMENT OF ENERGY DW DISHWASHER DISHWASHER DISHWASHER DWG DRAWING DRAWING DRAWING DWH DOMESTIC WATER HEATER DOMESTIC WATER HEATERDOMESTIC WATER HEATER
AutoCAD SHX Text EL ELEVATION ELEVATION ELEVATION EMCS ENERGY MANAGEMENT CONTROL ENERGY MANAGEMENT CONTROL SYSTEM EPA ENVIRONMENTAL PROTECTION ENVIRONMENTAL PROTECTION ENVIRONMENTAL PROTECTION AGENCY AGENCY EPACT ENERGY POLICY ACT ENERGY POLICY ACT ESH EMERGENCY SHOWER EMERGENCY SHOWER ET EXPANSION TANK EXPANSION TANK EWH ELECTRIC WATER HEATER ELECTRIC WATER HEATER EWS EYE WASH STATION EYE WASH STATION EWS/SH EYE WASH/DRENCH SHOWER EYE WASH/DRENCH SHOWER EX EXISTINGEXISTING
AutoCAD SHX Text F FAHRENHEIT FAHRENHEIT FCW FILTERED COLD WATER FILTERED COLD WATER FD FLOOR DRAIN FLOOR DRAIN FDC FIRE DEPARTMENT FIRE DEPARTMENT (HOSE) CONNECTION FM FLOW METER FLOW METER FS FLOOR SINK FLOOR SINK FS FLOW SWITCHFLOW SWITCH
AutoCAD SHX Text GAL GALLON GALLON GALLON GPD GALLONS PER DAY GALLONS PER DAY GALLONS PER DAY GPH GALLONS PER HOUR GALLONS PER HOUR GALLONS PER HOUR GPM GALLONS PER MINUTE GALLONS PER MINUTEGALLONS PER MINUTE
AutoCAD SHX Text H&CW HOT AND COLD WATER HOT AND COLD WATER HB HOSE BIB HOSE BIB HOSE BIB HEX HEAT EXCHANGER HEAT EXCHANGER HEAT EXCHANGER HP HORSEPOWER HORSEPOWER HORSEPOWER HS HAND SINK HAND SINK HST HOT WATER STORAGE TANK HOT WATER STORAGE TANK (DOMESTIC) (DOMESTIC) HW HOT WATER HOT WATER HWB HOT WATER BOILER HOT WATER BOILER HOT WATER BOILER HWCP HOT WATER CIRCULATING PUMP HOT WATER CIRCULATING PUMP HWP HOT WATER PUMP HOT WATER PUMP HOT WATER PUMP HWR HOT WATER RETURNHOT WATER RETURN
AutoCAD SHX Text ID INSIDE DIAMETER INSIDE DIAMETER IPC INTERNATIONAL PLUMBING CODE INTERNATIONAL PLUMBING CODE IRW IRRIGATION WATER IRRIGATION WATER IWH INSTANTANEOUS WATER HEATERINSTANTANEOUS WATER HEATER
AutoCAD SHX Text
KDHW KITCHEN DOMESTIC HOT WATERKITCHEN DOMESTIC HOT WATER
AutoCAD SHX Text LAV LAVATORY LAVATORY LAVATORY LCW LABORATORY COLD WATER LABORATORY COLD WATER LABORATORY COLD WATER LHW LABORATORY HOT WATER LABORATORY HOT WATERLABORATORY HOT WATER
AutoCAD SHX Text M METER METER MED MEDICAL MEDICAL MER MECHANICAL EQUIPMENT ROOM MECHANICAL EQUIPMENT ROOM MOU MEMORANDUM OF MEMORANDUM OF UNDERSTANDING MSB MOP SERVICE BASINMOP SERVICE BASIN
AutoCAD SHX Text NC NORMALLY CLOSED NORMALLY CLOSED NIC NOT IN CONTRACT NOT IN CONTRACT NO NORMALLY OPEN NORMALLY OPEN NPW NON POTABLE WATER NON POTABLE WATER NTS NOT TO SCALENOT TO SCALE
AutoCAD SHX Text O2 OXYGEN OXYGEN OXYGEN OC ON CENTER ON CENTER ON CENTER OD OUTSIDE DIAMETER OUTSIDE DIAMETER OUTSIDE DIAMETER OR OPERATING ROOM OPERATING ROOM OPERATING ROOM OLVF OVERFLOW OVERFLOWOVERFLOW
AutoCAD SHX Text PD PRESSURE DROP OR PRESSURE DROP OR PRESSURE DROP OR DIFFERENCE DIFFERENCE PDI PLUMBING AND DRAINAGE PLUMBING AND DRAINAGE PLUMBING AND DRAINAGE INSTITUTE INSTITUTE PG PRESSURE GAUGE PRESSURE GAUGE PRESSURE GAUGE PP PLUMBING PUMP PLUMBING PUMP PLUMBING PUMP PPM PARTS PER MILLION PARTS PER MILLION PARTS PER MILLION PRS PRESSURE REDUCING STATION PRESSURE REDUCING STATION PRESSURE REDUCING STATION PRV PRESSURE REDUCING VALVE PRESSURE REDUCING VALVE PRESSURE REDUCING VALVE PSI POUNDS PER SQUARE INCH POUNDS PER SQUARE INCH POUNDS PER SQUARE INCH PSIA POUNDS PER SQUARE INCH POUNDS PER SQUARE INCH POUNDS PER SQUARE INCH ATMOSPHERE ATMOSPHERE PSIG POUNDS PER SQUARE INCH POUNDS PER SQUARE INCH POUNDS PER SQUARE INCH GAUGE GAUGE PTRV PRESSURE TEMPERATURE RELIEF PRESSURE TEMPERATURE RELIEF PRESSURE TEMPERATURE RELIEF VALVE VALVE PW POTABLE WATER POTABLE WATERPOTABLE WATER
AutoCAD SHX Text RP RECIRCULATION PUMP RECIRCULATION PUMP RECIRCULATION PUMP RO REVERSE OSMOSIS WATER REVERSE OSMOSIS WATERREVERSE OSMOSIS WATER
AutoCAD SHX Text SCW SOFTENED COLD WATER SOFTENED COLD WATER SOFTENED COLD WATER SQFT/SF SQUARE FEET SQUARE FEET SS STAINLESS STEEL STAINLESS STEEL STAINLESS STEEL ST STORAGE TANK STORAGE TANKSTORAGE TANK
AutoCAD SHX Text TCV TEMPERATURE CONTROL TEMPERATURE CONTROL TEMPERATURE CONTROL VALVE VALVE TEMP TEMPERATURE TEMPERATURE TEMPERATURE TMV THERMOSTATIC MIXING VALVE THERMOSTATIC MIXING VALVE THERMOSTATIC MIXING VALVE TP TRAP PRIMER TRAP PRIMER TRAP PRIMER TSTAT THERMOSTAT THERMOSTAT TWR TEMPERED WATER RETURN TEMPERED WATER RETURN TEMPERED WATER RETURN TWS TEMPERED WATER SUPPLY TEMPERED WATER SUPPLY TEMPERED WATER SUPPLY TYP TYPICAL TYPICALTYPICAL
AutoCAD SHX Text
VB VACUUM BREAKER VACUUM BREAKERVACUUM BREAKER
AutoCAD SHX Text WC WATER CLOSET WATER CLOSET WATER CLOSET WG WATER GAUGE WATER GAUGE WATER GAUGE WH WATER HEATER WATER HEATER WATER HEATER WHA WATER HAMMER ARRESTER WATER HAMMER ARRESTER WATER HAMMER ARRESTER WL WATER LINE WATER LINE WATER LINE WM WATER METER WATER METER WATER METER WOG WATER OIL GAS WATER OIL GAS WATER OIL GAS WPD WATER PRESSURE DROP WATER PRESSURE DROP WATER PRESSURE DROP WSFU WATER SUPPLY FIXTURE UNITSWATER SUPPLY FIXTURE UNITS
AutoCAD SHX Text
PLUMBING ABBREVIATIONS
AutoCAD SHX Text
NOTE: NOT ALL ABBREVIATIONS AND SYMBOLS USED
AutoCAD SHX Text
NOTE: NOT ALL ABBREVIATIONS AND SYMBOLS USED
AutoCAD SHX Text
NOTE: NOT ALL ABBREVIATIONS AND SYMBOLS USED
AutoCAD SHX Text
X-XX-XXX-XXX-X
AutoCAD SHX Text
DEAD LEG NUMBER
AutoCAD SHX Text
BUILDING NUMBER
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
ROOM NUMBER
AutoCAD SHX Text
%%UDEAD LEG TAG
AutoCAD SHX Text
%%UMIXING VALVE STATION TAG
AutoCAD SHX Text M.V.S.
AutoCAD SHX Text X-X-X
AutoCAD SHX Text
BUILDING NUMBER
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
MIXING VALVE NUMBER
AutoCAD SHX Text NOTE: PLUMBING DRAWINGS & RISER DIAGRAMS ARE BASED ON OBSERVED PLUMBING DRAWINGS & RISER DIAGRAMS ARE BASED ON OBSERVED EXISTING/AS-BUILT CONDITIONS AND NOT ALL PIPING WAS ACCESSIBLE. CONTRACTOR SHALL VERIFY ALL PIPE SIZES AND LENGTHS
AutoCAD SHX Text
%%UGENERAL PLUMBING SYMBOLS
AutoCAD SHX Text
DIRECTION OF FLOW
AutoCAD SHX Text
SIDE CONNECTION
AutoCAD SHX Text BOTTOM CONNECTION, 45%%d OR 90%%d
AutoCAD SHX Text TOP CONNECTION, 45%%d OR 90%%d
AutoCAD SHX Text
RISE OR DROP IN PIPE
AutoCAD SHX Text
CAPPED OUTLET
AutoCAD SHX Text
POINT OF CONNECTION BETWEEN NEW
AutoCAD SHX Text
PRESSURE GAGE
AutoCAD SHX Text
THERMOMETER
AutoCAD SHX Text
STRAINER
AutoCAD SHX Text
AutoCAD SHX Text
PIPE UP
AutoCAD SHX Text
PIPE DOWN
AutoCAD SHX Text
HOSE BIB
AutoCAD SHX Text
BALL VALVE
AutoCAD SHX Text
CHECK VALVE
AutoCAD SHX Text
VALVE ON DROP
AutoCAD SHX Text
GATE VALVE
AutoCAD SHX Text
GLOBE VALVE
AutoCAD SHX Text
WATER FILTER
AutoCAD SHX Text
NON-INSULATED PIPING
AutoCAD SHX Text
DEAD LEG IDENTIFICATION
AutoCAD SHX Text
CIRCULATOR PUMP
AutoCAD SHX Text
EYE WASH
AutoCAD SHX Text
SHOWER HEAD
AutoCAD SHX Text
CAP OR PLUG
AutoCAD SHX Text
WB
AutoCAD SHX Text
WASHER BOX
AutoCAD SHX Text
AND EXISTING WORK
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
X-XX-XXX-XXX-X
AutoCAD SHX Text
NI-X
AutoCAD SHX Text
WB
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AIR HAMMER ARRESTER
AutoCAD SHX Text
PIPE UP AND DOWN
AutoCAD SHX Text
BUTTERFLY VALVE
AutoCAD SHX Text
BALANCING VALVE
AutoCAD SHX Text
%%UPLUMBING PIPING SYMBOLS
AutoCAD SHX Text
DOMESTIC HOT WATER, HOT WATER
AutoCAD SHX Text
DOMESTIC COLD WATER, COLD WATER
AutoCAD SHX Text
DOMESTIC HOT WATER RETURN, HOT WATER RETURN
AutoCAD SHX Text
TEMPERED WATER
AutoCAD SHX Text
DOMESTIC COLD WATER, COLD WATER "ENLARGED PLANS ONLY"
AutoCAD SHX Text
DOMESTIC HOT WATER RETURN, HOT WATER RETURN
AutoCAD SHX Text
"ENLARGED PLANS ONLY"
AutoCAD SHX Text T
AutoCAD SHX Text
DOMESTIC HOT WATER, HOT WATER "ENLARGED PLANS ONLY"
AutoCAD SHX Text
CW
AutoCAD SHX Text
HW
AutoCAD SHX Text
HWR
AutoCAD SHX Text DEAD LEG REMOVAL NOTES: 1. REMOVE ALL TYPE "A" DEAD LEG PIPING AND ASSOCIATED FIXTURES, HANGERS, VALVES AND FITTINGS REMOVE ALL TYPE "A" DEAD LEG PIPING AND ASSOCIATED FIXTURES, HANGERS, VALVES AND FITTINGS FOR DOMESTIC WATER BACK TO BRANCH TEE AND CAP TEE. (REMOVE ACCESSIBLE PIPING WITHOUT DISTURBING EXISTING WALL CONSTRUCTION) 2. SHUT OFF SERVICE TO BRANCH AT NEAREST VALVE. CUT AND CAP DEAD LEG PIPING BACK TO TEE. SHUT OFF SERVICE TO BRANCH AT NEAREST VALVE. CUT AND CAP DEAD LEG PIPING BACK TO TEE. DISTANCE FROM CAP TO EXISTING BRANCH TO REMAIN, NOT TO EXCEED TWICE THE DIAMETER OF THE BRANCH, RISER, OR MAIN THAT IT IS CONNECTED TO. 3. WHEN DEAD LEG REMOVAL INCLUDES FIXTURES, ALL EQUIPMENT RELATED TO FIXTURE SHALL BE WHEN DEAD LEG REMOVAL INCLUDES FIXTURES, ALL EQUIPMENT RELATED TO FIXTURE SHALL BE REMOVED AND WALL PATCHED TO MATCH ORIGINAL CONDITION. DRAINS SHALL BE CAPPED FLUSH WITH WALL OR FLOOR SURFACE. 4. EXISTING PIPING SHALL BE CUT BACK FAR ENOUGH INTO THE BUILDING CONSTRUCTION TO ALLOW A EXISTING PIPING SHALL BE CUT BACK FAR ENOUGH INTO THE BUILDING CONSTRUCTION TO ALLOW A CAP CONSTRUCTED OF THE SAME PIPING MATERIAL, WITH A JOINT RATED AT THE SAME PRESSURE OF THE ADJOINING FITTINGS TO BE INSTALLED, AND THE CAP TO BE CONCEALED WITHIN THE PATCHED WALL, CEILING, OR FLOOR. 5. OPEN ALL LOW POINT DRAINS. LOCATE AND IDENTIFY AN ISOLATION VALVE UPSTREAM OF THE SECTION OPEN ALL LOW POINT DRAINS. LOCATE AND IDENTIFY AN ISOLATION VALVE UPSTREAM OF THE SECTION IN QUESTION AND OPEN OF THE PIPING TO RELEASE ANY VACUUM AND ALLOW REMAINING WATER TO DRAIN. BLOW COMPRESSED AIR INTO THE PIPING TO REMOVE ANY RESIDUAL WATER. IF IN THE EVENT THE ISOLATION VALVE DOES NOT HOLD, THE CONTRACTOR SHALL PERFORM VALVE REPAIR/REPLACEMENT.
AutoCAD SHX Text GENERAL PLUMBING WORK SCHEDULING/PHASING NOTES: : 1. ALL MEANS OF EGRESS SHALL BE MAINTAINED AND ACCESSIBLE. I.C.R.A. BARRIERS (IF REQUIRED), ALL MEANS OF EGRESS SHALL BE MAINTAINED AND ACCESSIBLE. I.C.R.A. BARRIERS (IF REQUIRED), SHALL BE ERECTED AND TAKEN DOWN AS REQUIRED TO MEET THE VA SCHEDULING REQUIREMENTS. 2. ALL WORK REQUIRED WITHIN CORRIDORS SHALL BE PERFORMED TO MAINTAIN ACCESSIBILITY THROUGH ALL WORK REQUIRED WITHIN CORRIDORS SHALL BE PERFORMED TO MAINTAIN ACCESSIBILITY THROUGH THE MEANS OF EGRESS IN ACCORDANCE WITH THE CONTRACT DOCUMENTS AND VA CONSTRUCTION POLICY AND PERFORMED OVERNIGHT AS DIRECTED BY VA. 3. WORK ON THE PATIENT TOILET/SHOWER ROOMS SHALL BE LIMITED TO A MAXIMUM OF WORK ON THE PATIENT TOILET/SHOWER ROOMS SHALL BE LIMITED TO A MAXIMUM OF (2)TOILET/SHOWERS ROOMS ON ANY GIVEN FLOOR AT A TIME. NO BATHROOM SHALL BE LEFT IN AN INOPERATIVE CONDITION OVER A WEEKEND. 4. WORK IN OFFICES AND EXAM ROOMS SHALL BE LIMITED TO (2) ROOMS AT A TIME. WORK IN OFFICES AND EXAM ROOMS SHALL BE LIMITED TO (2) ROOMS AT A TIME. 5. CONTRACTOR SHALL COORDINATE CLOSELY WITH THE V.A. ON ANY PATIENT RELOCATIONS FROM CONTRACTOR SHALL COORDINATE CLOSELY WITH THE V.A. ON ANY PATIENT RELOCATIONS FROM PROPOSED WORK AREA, PRIOR TO CONTRACTOR'S WORK IN PATIENT AREAS.
AutoCAD SHX Text PLUMBING GENERAL DEMOLITION NOTES: 1. REMOVE ALL OBSOLETE PLUMBING FIXTURES, EQUIPMENT, PIPING, INSULATION, HANGERS, CONTROLS, REMOVE ALL OBSOLETE PLUMBING FIXTURES, EQUIPMENT, PIPING, INSULATION, HANGERS, CONTROLS, PADS, AND SUPPORTS UNLESS OTHERWISE INDICATED TO REMAIN. DISCONNECT PLUMBING FROM EQUIPMENT WHICH IS TO BE REMOVED BY OTHERS. PIPING MADE OBSOLETE BY THE NEW CONSTRUCTION SHALL BE REMOVED BACK TO MAIN OR AS SHOWN ON DRAWINGS AND CAPPED ABOVE CEILINGS, BELOW FLOORS OR IN WALLS SO THAT IT IS COMPLETELY CONCEALED AT THE COMPLETION OF THE PROJECT. PIPING REMOVED FROM THE EXISTING PLUMBING SYSTEM SHALL NOT BE USED IN THE INSTALLATION OF THE NEW SYSTEM. 2. DEMOLITION INCLUDES, BUT IS NOT LIMITED TO, REMOVAL AND LEGAL DISPOSAL OF EQUIPMENT AND DEMOLITION INCLUDES, BUT IS NOT LIMITED TO, REMOVAL AND LEGAL DISPOSAL OF EQUIPMENT AND SYSTEMS MADE OBSOLETE AND/OR REPLACED BY NEW WORK. DEMOLITION INCLUDES RELOCATION OR REINSTALLATION, DISCONNECTIONS AND RECONNECTIONS OF SERVICES, SUPPORTS, AND SUBSEQUENT FINAL SUPPORTS, TEMPORARY CAPPING, AND REROUTING OF TEMPORARY SERVICES TO PERMIT NEW OR RENOVATION WORK TO PROCEED. 3. THE DEMOLITION WORK INDICATED ON THE DRAWING IS INTENDED TO ASSIST THE CONTRACTOR AND THE DEMOLITION WORK INDICATED ON THE DRAWING IS INTENDED TO ASSIST THE CONTRACTOR AND GIVE GENERAL INFORMATION. NOT ALL DEMOLITION OR TEMPORARY CONNECTIONS ARE SHOWN. PRIOR TO SUBMITTING BID, THE CONTRACTOR SHALL VISIT THE PROJECT SITE AND REVIEW EXISTING CONDITIONS. PRIME CONTRACTOR IS RESPONSIBLE TO DETERMINE THE FULL EXTENT OF DEMOLITION, FOR ALL TRADES, AND INCLUDE ALL REQUIRED DEMOLITION WORK, FOR ALL TRADES, IN HIS BID, WHETHER OR NOT SPECIFICALLY SHOWN ON DRAWINGS. NO ADDITIONAL COST WILL BE GRANTED FOR DEMOLITION. LEGALLY DISPOSE OF ALL ITEMS AND MATERIALS, EXCEPT ANY ITEMS SPECIFICALLY DESIGNATED BY THE VA TO BE SALVAGED. REMOVE AND PLACE THE DESIGNATED SALVAGED EQUIPMENT IN A LOCATION DIRECTED BY THE VA AT NO ADDITIONAL EXPENSE. 4. REFER TO GENERAL CONSTRUCTION TRADE DEMOLITION DRAWINGS AS WELL AS THE PLUMBING REFER TO GENERAL CONSTRUCTION TRADE DEMOLITION DRAWINGS AS WELL AS THE PLUMBING DRAWINGS FOR FIXTURES AND EQUIPMENT THAT HAVE TO BE REMOVED DUE TO THE NEW CONSTRUCTION AND RENOVATIONS AND EXTENT OF AREA TO BE DEMOLISHED. 5. PLUMBING CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING. THE PLUMBING CONTRACTOR PLUMBING CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING. THE PLUMBING CONTRACTOR SHALL CUT AND PATCH THE EXISTING WALLS AND TO MATCH EXISTING. PLUMBING CONTRACTOR SHALL REMOVE/REPLACE EXISTING CEILING TILES AND GRID AS REQUIRED TO ACCOMPLISH INDICATED PLUMBING WORK, UNLESS SPECIFICALLY INDICATED OTHERWISE. 6. PLUMBING CONTRACTOR SHALL COORDINATE ALL DEMOLITION AND NEW WORK WITH THE PHASING AS PLUMBING CONTRACTOR SHALL COORDINATE ALL DEMOLITION AND NEW WORK WITH THE PHASING AS OUTLINED IN DRAWINGS AND SPECIFICATIONS. THE PLUMBING CONTRACTOR SHALL PROVIDE LABOR AND MATERIALS AS REQUIRED TO MAINTAIN CONTINUED OPERATION OF THE PLUMBING SYSTEM THROUGH THE PHASES OF WORK AS INDICATED IN THE CONTRACT DOCUMENTS.
AutoCAD SHX Text GENERAL PLUMBING NOTES: 1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE PLUMBING SYSTEM AS INDICATED ON THE DRAWINGS, AS SPECIFIED, AND AS REQUIRED BY CODE. 2. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND INDICATIVE OF WORK TO BE THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND INDICATIVE OF WORK TO BE PERFORMED. THE DRAWINGS ARE NOT INTENDED TO SHOW EVERY PIPE, FITTING, VALVE OR APPURTENANCE REQUIRED FOR A COMPLETE INSTALLATION. DO NOT SCALE LOCATION DIMENSIONS FROM THESE DRAWINGS. DRAWINGS ARE NOT TO BE SCALED FOR THE ACCURATE CUTTING OF PIPE OR ITS EXACT LOCATION. BEFORE ANY PIPING IS INSTALLED, CONFER WITH ALL OTHER CONTRACTORS IN ORDER TO ESTABLISH THE LOCATION OF THEIR PIPING, CONDUIT, DUCTWORK, GRILLES, FOUNDATIONS, STRUCTURAL STEEL, LIGHTING FIXTURES AND OTHER EQUIPMENT SO AS TO AVOID INTERFERENCE. FAILURE TO COORDINATE SHALL NOT RESULT IN ANY ADDITIONAL EXPENSE TO THE OWNER. 3. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING AND VERIFYING ALL THE CONTRACTOR IS RESPONSIBLE FOR CHECKING AND VERIFYING ALL CONDITIONS AND DIMENSIONS AND FOR COORDINATION OF THEIR WORK WITH THAT OF ALL OTHER TRADES. PERFORM WORK IN A NEAT, ORDERLY MANNER AND WITH THE LEAST POSSIBLE INTERFERENCES. 4. WORK SHALL CONFORM TO OR MEET THE REQUIREMENTS OF THE MOST WORK SHALL CONFORM TO OR MEET THE REQUIREMENTS OF THE MOST CURRENT EDITION OF: ANSI/ASHRAE STANDARD 188-2015 LEGIONELLOSIS: RISK MANAGEMENT FOR BUILDING WATER SYSTEMS. A. INTERNATIONAL PLUMBING CODE; 2012 IPC INTERNATIONAL PLUMBING CODE; 2012 IPC B. INTERNATIONAL ENERGY CONSERVATION CODE; 2012 IBC INTERNATIONAL INTERNATIONAL ENERGY CONSERVATION CODE; 2012 IBC INTERNATIONAL BUILDING CODE; 2012 IECC C. NEC (NFPA 70) NEC (NFPA 70) D. ALL FEDERAL, STATE AND LOCAL CODES AND ORDINANCES ALL FEDERAL, STATE AND LOCAL CODES AND ORDINANCES E. VA DESIGN GUIDE (PLUMBING) VA DESIGN GUIDE (PLUMBING) F. VHA DIRECTIVE 1061-PREVENTION OF HEALTHCARE-ASSOCIATED VHA DIRECTIVE 1061-PREVENTION OF HEALTHCARE-ASSOCIATED LEGIONELLA DISEASE AND SCALD INJURY FROM POTABLE WATER DISTRIBUTION SYSTEMS. 5. THE PLUMBING CONTRACTOR SHALL PROVIDE SENSORS, CONTROLLERS, WIRING, THE PLUMBING CONTRACTOR SHALL PROVIDE SENSORS, CONTROLLERS, WIRING, ETC. NECESSARY TO INTEGRATE MONITORING POINTS WITH THE FACILITY BUILDING MANAGEMENT SYSTEM (SEE SPECIFICATIONS AND DRAWINGS). 6. THE PLUMBING CONTRACTOR SHALL PROVIDE NECESSARY ANTI-SCALD MIXING THE PLUMBING CONTRACTOR SHALL PROVIDE NECESSARY ANTI-SCALD MIXING VALVES AT ALL FIXTURES (SINKS, LAVATORIES, AND SHOWERS) WHICH RECEIVE HOT WATER IN EXCESS OF 110 DEG. F. 7. CONTRACTOR SHALL PROTECT THE PIPING FROM STRESS AND STRAIN. CONTRACTOR SHALL PROTECT THE PIPING FROM STRESS AND STRAIN. 8. ALL MATERIALS, EQUIPMENT AND DEVICES SHALL, AS A MINIMUM, MEET THE ALL MATERIALS, EQUIPMENT AND DEVICES SHALL, AS A MINIMUM, MEET THE REQUIREMENTS OF UL WHERE UL REQUIREMENTS ARE ESTABLISHED FOR THOSE ITEMS. ALL ITEMS SHALL BE CLASSIFIED BY UL AS SUITABLE FOR THE PURPOSE OF THE CODE. 9. WHERE PIPES PENETRATE FIRE RATED OR SMOKE RATED BARRIERS (WALLS, WHERE PIPES PENETRATE FIRE RATED OR SMOKE RATED BARRIERS (WALLS, FLOORS AND CEILINGS). SEAL PENETRATIONS IN ACCORDANCE WITH NFPA 90A WITH UL LISTED FIRE STOPPING SYSTEM. UTILIZE HILTI FIRESTOPPING PRODUCTS PER VA REQUIREMENTS. 10. REFER TO SCHEMATIC DIAGRAMS FOR ALL PIPE SIZES AND PIPING LOCATIONS REFER TO SCHEMATIC DIAGRAMS FOR ALL PIPE SIZES AND PIPING LOCATIONS NOT SHOWN ON THE PLANS UNLESS NOTED OTHERWISE ON THE DRAWINGS. 11. COORDINATE LOCATION OF PIPING ABOVE CEILING WITH ELECTRICAL PANELS BY COORDINATE LOCATION OF PIPING ABOVE CEILING WITH ELECTRICAL PANELS BY ELECTRICAL CONTRACTOR. DO NOT INSTALL PIPING IN DEDICATED SPACE FOR ELECTRIC PANEL. 12. ALL EQUIPMENT AND MATERIALS INCORPORATED IN THIS WORK SHALL BE NEW ALL EQUIPMENT AND MATERIALS INCORPORATED IN THIS WORK SHALL BE NEW UNLESS NOTED OTHERWISE AND SHALL BE CURRENT PRODUCTS BY MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH PRODUCTS. 13. ALL FACTORY APPLIED COATINGS AND FINISHES SHALL BE PROVIDED WITHOUT ALL FACTORY APPLIED COATINGS AND FINISHES SHALL BE PROVIDED WITHOUT RUST, SCRATCHES OR DENTS. 14. PROVIDE OWNER WITH CERTIFICATES OF FINAL INSPECTION AND ACCEPTANCE PROVIDE OWNER WITH CERTIFICATES OF FINAL INSPECTION AND ACCEPTANCE FROM THE AUTHORITY HAVING JURISDICTION. 15. COMPLETE LAYOUT DRAWINGS SHALL BE REQUIRED BY SECTION 22 05 11 - COMPLETE LAYOUT DRAWINGS SHALL BE REQUIRED BY SECTION 22 05 11 - COMMON WORK RESULTS FOR PLUMBING, PARAGRAPH, SUBMITTALS. CONSTRUCTION WORK SHALL NOT START ON ANY SYSTEM UNTIL THE LAYOUT DRAWINGS HAVE BEEN REVIEWED BY THE PROFESSIONAL AND THE VA. COORDINATION REQUIREMENTS: 1. COORDINATE LOCATIONS AND INSTALLATION OF PLUMBING WORK TO AVOID COORDINATE LOCATIONS AND INSTALLATION OF PLUMBING WORK TO AVOID CONFLICTS AND INTERFERENCES, MODIFICATIONS DUE TO FIELD CONDITIONS SHALL BE COMPLETELY RESOLVED BY CONTRACTOR IN ACCORDANCE WITH RECOMMENDATIONS OF THE VA. 2. COORDINATE FINAL LOCATIONS OF HOSPITAL PLUMBING EQUIPMENT WITH COORDINATE FINAL LOCATIONS OF HOSPITAL PLUMBING EQUIPMENT WITH ARCHITECTURAL PLANS. PLUMBING INSTALLATION REQUIREMENTS: 1. INSTALL ALL EQUIPMENT AND MATERIAL IN ACCORDANCE WITH MANUFACTURER INSTALL ALL EQUIPMENT AND MATERIAL IN ACCORDANCE WITH MANUFACTURER PRINTED INSTALLATION INSTRUCTIONS AND RECOMMENDATIONS. MAINTAIN CLEARANCES FOR ACCESS TO MAINTAIN AND SERVICE EQUIPMENT, VALVES AND CONTROLS. 2. ALL WORK SHALL BE PERFORMED IN A NEAT, WORKMANLIKE MANNER SO AS ALL WORK SHALL BE PERFORMED IN A NEAT, WORKMANLIKE MANNER SO AS NOT TO DAMAGE ANY SURFACES, EQUIPMENT OR MATERIALS. 3. ALL EQUIPMENT AND PIPING SHALL BE SUPPORTED IN AN APPROVED MANNER ALL EQUIPMENT AND PIPING SHALL BE SUPPORTED IN AN APPROVED MANNER FROM THE BUILDING STRUCTURE AND INCLUDE HANGERS AND RESTRAINTS IN ACCORDANCE WITH ALL APPLICABLE CODES. 4. PROVIDE PIPE ESCUTCHEONS AT ALL EXPOSED PENETRATIONS OF FLOORS, PROVIDE PIPE ESCUTCHEONS AT ALL EXPOSED PENETRATIONS OF FLOORS, WALLS AND CEILINGS. 5. THE MANUFACTURERS AND MODEL NUMBERS LISTED ON THE SCHEDULES AND THE MANUFACTURERS AND MODEL NUMBERS LISTED ON THE SCHEDULES AND DETAILS ARE THE BASIS OF DESIGN FOR THIS PROJECT. THIS INFORMATION IS PROVIDED FOR REFERENCE PURPOSE ONLY AND IS NOT INTENDED TO PRECLUDE SUBMITTAL OF OTHER MANUFACTURERS OF EQUAL QUALITY SUBJECT TO APPROVAL BY THE VA PROJECT ENGINEER. 6. RUNOUTS TO EQUIPMENT SHALL BE SIZED AS INDICATED AND INCREASED OR RUNOUTS TO EQUIPMENT SHALL BE SIZED AS INDICATED AND INCREASED OR REDUCED AT POINT OF FINAL CONNECTION TO EQUIPMENT. 7. ALL SYSTEMS SHALL BE TESTED FOR PROPER OPERATION IN ACCORDANCE WITH ALL SYSTEMS SHALL BE TESTED FOR PROPER OPERATION IN ACCORDANCE WITH APPLICABLE CODE OR REGULATION. 8. CONTRACTOR SHALL SEAL ALL PIPE PENETRATIONS THROUGH WALL, FLOORS CONTRACTOR SHALL SEAL ALL PIPE PENETRATIONS THROUGH WALL, FLOORS AND WATERTIGHT. SEAL ALL PIPE PENETRATION THROUGH FIRE-RATED PARTITIONS WITH UL RATED FIRE RETARDANT CAULKING COMPOUND. FIRESTOPPING SHALL BE AS MANUFACTURED BY HILTI PRODUCTS. (SEE FIRESTOPPING NOTES IN GENERAL PLUMBING NOTES)
AutoCAD SHX Text 1100 CHURCH STREET HONESDALE, PA 18431 570-253-0846 OFFICE 570-253-1935 FAX WWW.NEINFRA.COM
AutoCAD SHX Text L
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text Y
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text L
AutoCAD SHX Text V
AutoCAD SHX Text M
AutoCAD SHX Text P
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text No. PE059715
AutoCAD SHX Text
ENGINEER
AutoCAD SHX Text
REGISTERED
AutoCAD SHX Text M
AutoCAD SHX Text W
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text F
AutoCAD SHX Text H
AutoCAD SHX Text O
AutoCAD SHX Text
MATTHEW DAVID LESOINE
AutoCAD SHX Text
METER
AutoCAD SHX Text M
AutoCAD SHX Text
EYE WASH COMBINATION WITH EMERGENCY SHOWER
AutoCAD SHX Text
%%UCROSS CONNECTION TAG
AutoCAD SHX Text
BUILDING NUMBER
AutoCAD SHX Text
FLOOR NUMBER
AutoCAD SHX Text
CROSS CONNECTION NUMBER
AutoCAD SHX Text
XX-XX
AutoCAD SHX Text
XX-XX
AutoCAD SHX Text
ROOM NUMBER
AutoCAD SHX Text
%%UBACK FLOW PREVENTER TAG
AutoCAD SHX Text
BUILDING NUMBER
AutoCAD SHX Text
FLOOR NUMBER
AutoCAD SHX Text
BACK FLOW PREVENTER NUMBER
AutoCAD SHX Text
X-XX-XXX-XXX
AutoCAD SHX Text
ROOM NUMBER
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DEAD LEG REMOVAL DETAIL
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL SINK AND
AutoCAD SHX Text
PL-001
AutoCAD SHX Text
DEAD LEG TYPE
AutoCAD SHX Text
SANITARY LINE (SAN)
AutoCAD SHX Text
SAN
AutoCAD SHX Text
CO
AutoCAD SHX Text
FD
AutoCAD SHX Text
FCO
AutoCAD SHX Text
RUNNING TRAP
AutoCAD SHX Text
FD
AutoCAD SHX Text
FLOOR DRAIN WITH TRAP (FD)
AutoCAD SHX Text
FLOOR DRAIN WITHOUT TRAP (FD)
AutoCAD SHX Text
FLOOR CLEANOUT (FCO)
AutoCAD SHX Text
CLEANOUT FLUSH (FC)
AutoCAD SHX Text
WCO
AutoCAD SHX Text
WALL CLEANOUT (WCO)
AutoCAD SHX Text
FIXTURE DRAIN WITH TRAP
AutoCAD SHX Text
%%USANITARY LINE SYMBOLS
AutoCAD SHX Text
SANITARY VENT LINE (V)
AutoCAD SHX Text
%%UGENERAL SANITARY SYMBOLS
AutoCAD SHX Text
PIPE UP
AutoCAD SHX Text
PIPE DOWN
AutoCAD SHX Text
CAP OR PLUG
AutoCAD SHX Text
PRESSURE REGULATING VALVE
AutoCAD SHX Text
LIMIT OF DEMOLITION
AutoCAD SHX Text GENERAL SANITARY PIPING NOTE: 1. TYPICAL-ALL SANITARY PIPES REPRESENTED ON THE SANITARY PIPING PLANS ARE LOCATED WITHIN TYPICAL-ALL SANITARY PIPES REPRESENTED ON THE SANITARY PIPING PLANS ARE LOCATED WITHIN THE CEILING OF THE FLOOR PLAN THEY ARE REPRESENTED ON AND SERVER THE ASSOCIATED FIXTURES ON THE FLOOR LOCATED ABOVE.
1 C 124 033 South Wall N N/A Cu 36'' 4" CW A Cap None Ball N/A Class I 1/PL-102 11/06/2018 N/A
1 C 124 034 South Wall N N/A Cu 36'' 4" CW A Cap None Ball N/A Class I 1/PL-102 11/06/2018 N/A
1 C 124 035 South Wall N N/A Cu 300'' 5" CW A Closed Valve None Gate N/A Class I 1/PL-102 11/06/2018 N/A
1 C 124 036 South Wall N N/A Cu 36'' 2" CW A Closed Valve Equipment Ball N/A Class I 1/PL-102 11/06/2018 N/A
1 C 124 037 Center of room N N/A Cu 6'' 2" HWR B Spigot None Globe 6" Class I 1/PL-103 12/04/2018 N/A
1 C 124 038 Center of room N N/A Cu 6'' 1 1/2" HWR B Spigot None Globe 6" Class I 1/PL-103 12/04/2018 N/A
1 C 124 039 Center of room N N/A Cu 6'' 3/4" CW B Spigot None Globe N/A Class I 1/PL-103 12/04/2018 N/A
1 C 124 040 Center of room N N/A Cu 12'' 1 1/4" CW A Cap None Gate N/A Class I 1/PL-103 12/04/2018 N/A
1 C 124 041 Center of room N N/A Cu 6'' 3/4" HW B Spigot None Globe 6" Class I 1/PL-103 12/04/2018 N/A
1 C 124 042 North Wall N N/A Cu 7'' 3/4" HW A Cap None None 7" Class I 1/PL-103 12/04/2018 N/A
1 C 124 043 Center of room N N/A Cu 3'' 3/4" CW A Closed Valve None Gate N/A Class I 1/PL-102 06/03/2018 N/A
1 C 124 044 Center of room N N/A Cu 6'' 3/4" CW A Closed Valve None Globe N/A Class I 1/PL-102 06/03/2018 N/A
1 C 124 045 Center of room N N/A Cu 8'' 1/2" HW A Closed Valve None Ball 8" Class I 1/PL-102 06/03/2018 N/A
1 C 124 046 East Wall N N/A Cu 8'' 3/4" CW B Spigot None Ball N/A Class I 1/PL-102 06/03/2018 N/A
1 C 124 047 East Wall N N/A Cu 8'' 3/4" CW A Cap None None N/A Class I 1/PL-102 06/03/2018 N/A
1 C 124 048 North Wall N N/A Cu 12'' 1" CW B Spigot None Ball N/A Class I 1/PL-106 10/13/2018 N/A
1 C 124 048 West Wall N N/A Cu 16" 1 1/4" CW B Spigot None Ball N/A Class I 1/PL-106 10/13/2018 N/A
1 C 132 001 Center of room N N/A Cu 12'' 3/4" CW A Closed Valve None Gate N/A Class I 1/PL-105 11/06/2018 N/A
1 C 132 002 Center of room N N/A Cu 12'' 3/4" HWR A Cap None Gate 12" Class I 1/PL-105 11/06/2018 N/A
1 C 132 003 Center of room N N/A Cu 8'' 3/4" HWR A Closed Valve None Gate 8" Class I 1/PL-105 11/06/2018 N/A
1 C 132 004 North Wall N N/A Cu 120'' 3/4" HWR A Plug None Ball 8" Class I 1/PL-102 11/09/2018 N/A
1 C 132 005 North Wall N N/A Cu 6'' 1" CW A Closed Valve None Globe N/A Class I 2/PL-105 11/09/2018 N/A
1 C 132 006 North Wall N N/A Cu 6'' 1" HW A Cap None Globe 6" Class I 2/PL-105 11/09/2018 N/A
1 C 132 007 North Wall N N/A Cu 6'' 1" HWR A Cap None Globe 6" Class I 2/PL-105 11/09/2018 N/A
1 C 132 008 North Wall N N/A Cu 6'' 3/4" CW A Closed Valve None Globe N/A Class I 1/PL-102 11/09/2018 N/A
1 C 132 009 North Wall N N/A Cu 6'' 3/4" HW A Closed Valve None Globe 6" Class I 1/PL-102 11/09/2018 N/A
1 C 132 010 South Wall N N/A Cu 12" 1/2" CW B Spigot None Gate N/A Class I 1/PL-102 11/06/2018 N/A
1 C 132 011 North Wall N N/A Cu 397" 1/2" CW A Closed Valve None None N/A Class I 1/PL-102 11/06/2018 N/A
1 C 132 012 North Wall N N/A Cu 20'' 1/2" CW A Cap None None N/A Class I 1/PL-102 11/06/2018 N/A
1 C 132 013 South Wall Y Brick/CMU/
Concrete Cu 168'' 1/2" CW B Fixture Water
Fountain Ball N/A Class I 1/PL-102 11/06/2018 N/A
1 C 135 001 North Wall N N/A Cu 102'' 3/4" CW B Closed Valve Equipment Ball N/A Class I 1/PL-102 11/06/2018 N/A
1 C 135 002 East Wall N N/A Cu 16'' 3/4" CW A Closed Valve None Globe N/A Class I 3/PL-105 11/06/2018 N/A
1 C 135 003 East Wall N N/A Cu 440'' 3/4" CW A Closed Valve None Ball N/A Class I 1/PL-102 11/06/2018 N/A
1 C 136 001 South Wall N N/A Cu 80'' 1 1/4" CW A Closed Valve None Ball N/A Class I 1/PL-105 10/12/2018 N/A
1 C 136 002 West Wall N N/A Cu 12'' 1/2" HWR A Cap None Ball 12" Class I 1/PL-105 10/12/2018 N/A
1 C 136 003 South Wall Y Varies Cu 15" 1" CW A Cap None None N/A Class I 1/PL-105 10/12/2018 N/A
1 C 137 001 Center of room N N/A Cu 420'' 3/4" CW B Spigot None Ball N/A Class I 1/PL-102 10/13/2018 N/A
1 C 137 002 Center of room N N/A Cu 6" 3/4" CW B Spigot None Ball N/A Class I 4/PL-105 10/13/2018 N/A
1 C 140 001 West Wall N N/A Cu 8'' 3/4" HW A Closed Valve None Globe 5" Class I 1/PL-102 11/08/2018 N/A
1 C 140 002 West Wall N N/A Cu 8'' 3/4" HWR A Closed Valve None Globe 5" Class I 1/PL-102 11/08/2018 N/A
1 C 140 003 North Wall N N/A Cu 3'' 3/4" CW A Closed Valve None Globe N/A Class I 2/PL-105 11/09/2018 N/A
1 C 140 004 North Wall N N/A Cu 1080'' 1" CW A Cap None Globe N/A Class I 2/PL-105 11/09/2018 N/A
1 C CS 001 South Wall N N/A Cu 8'' 1/2" CW A Closed Valve None Gate N/A Class I 1/PL-102 11/08/2018 N/A
1 C CS 002 South Wall N N/A Cu 8'' 1/2" HW A Closed Valve None Gate 4" Class I 1/PL-102 11/08/2018 N/A
1 C CS 003 South Wall N N/A Cu 8'' 1/2" HWR A Closed Valve None Gate 4" Class I 1/PL-102 11/08/2018 N/A
1 C CS 004 South Wall N N/A Cu 272'' 3/4" HWR B Spigot None None None Class I 1/PL-102 11/08/2018 N/A
1 C CS2 001 East Wall N N/A Cu 8'' 3/4" CW A Closed Valve None Globe N/A Class I 1/PL-102 01/08/2019 N/A
1 C CS2 002 East Wall N N/A Cu 15'' 3/4" HWR A Closed Valve None Globe 15" Class I 1/PL-102 01/08/2019 N/A
1 C CS2 003 North Wall N N/A Cu 5'' 3/4" CW A Closed Valve None Globe N/A Class I 1/PL-102 01/08/2019 N/A
1 C CS2 004 North Wall N N/A Cu 12'' 3/4" HW A Closed Valve None Globe 6" Class I 1/PL-102 01/08/2019 N/A
1 C CS2 005 Center of room N N/A Cu 7'' 3/4" CW A Closed Valve None Globe N/A Class I 1/PL-102 01/08/2019 N/A
1 C CS4 001 East Wall N N/A Cu 7'' 3/4" CW A Closed Valve None Globe N/A Class I 1/PL-101 01/08/2019 N/A
1 C CS4 002 East Wall N N/A Cu 5'' 3/4" HWR A Closed Valve None Globe 5" Class I 1/PL-101 01/08/2019 N/A
1 C CS4 003 East Wall N N/A Cu 5'' 3/4" HW A Closed Valve None Globe 5" Class I 1/PL-101 01/08/2019 N/A
1 C CS4 004 Center of room N N/A Cu 2'' 3/4" CW A Cap None None N/A Class I 1/PL-101 01/08/2019 N/A
1 C CS4 005 West Wall N N/A Cu 7'' 3/4" CW A Closed Valve None Globe N/A Class I 1/PL-101 01/08/2019 N/A
1 C CS4 006 West Wall N N/A Cu 7'' 3/4" HW A Closed Valve None Globe 5" Class I 1/PL-101 01/08/2019 N/A
1 C CS4 007 West Wall N N/A Cu 3'' 3/4" CW A Closed Valve None Globe N/A Class I 1/PL-101 01/08/2019 N/A
1 C CS5 001 East Wall N N/A Cu 6'' 3/4" HWR A Closed Valve None Globe 6" Class I 1/PL-104 01/08/2019 N/A
1 C CS5 002 East Wall N N/A Cu 7'' 3/4" HW A Closed Valve None Globe 7" Class I 1/PL-104 01/08/2019 N/A
1 C CS7 001 West Wall N N/A Cu 288'' 3/4" CW A Plug None None N/A Class I 1/PL-101 01/09/2019 N/A
1 C CS7 002 West Wall N N/A Cu 3'' 1/2" HW A Plug None None 3" Class I 1/PL-101 01/09/2019 N/A
1 C CS7 003 West Wall N N/A Cu 24'' 3/4" HW A Plug None Globe 3" Class I 1/PL-101 01/09/2019 N/A
1 C CS7 004 Center of room N N/A Cu 96'' 3/4" CW A Cap None None N/A Class I 1/PL-101 01/09/2019 N/A
1 C CS7 005 West Wall N N/A Cu 36'' 3/4" CW A Plug None Globe N/A Class I 1/PL-101 01/09/2019 N/A
1 C CS7 006 Center of room N N/A Cu 13'' 3/4" CW A Closed Valve None Globe N/A Class I 1/PL-101 01/09/2019 N/A
1 C CS7 007 Center of room N N/A Cu 26'' 1 1/4" CW A Plug None Globe N/A Class I 1/PL-101 01/09/2019 N/A
1 C CS7 008 North Wall N N/A Cu 38'' 1 1/4" HW A Cap None Globe None Class I 1/PL-101 01/09/2019 N/A
1 C CS7 009 North Wall N N/A Cu 26'' 3/4" CW A Closed Valve None Ball N/A Class I 1/PL-101 01/09/2019 N/A
1 C CS7 010 North Wall N N/A Cu 12'' 1/2" CW A Closed Valve None Globe N/A Class I 1/PL-101 01/09/2019 N/A
1 C CS7 011 North Wall N N/A Cu 12'' 1/2" CW A Cap None None N/A Class I 1/PL-101 01/09/2019 N/A
1 C CS7 012 South Wall N N/A Cu 48'' 1/2" CW A Cap None None N/A Class I 1/PL-101 01/09/2019 N/A
1 C CS7 013 Center of room N N/A Cu 144'' 1/2" HW A Cap None Globe 20" Class I 1/PL-101 01/09/2019 N/A
1 C CS7 014 Center of room N N/A Cu 336'' 1/2" CW A Cap None None N/A Class I 1/PL-101 01/09/2019 N/A
1 C CS7 015 North Wall N N/A Cu 36'' 2" CW A Closed Valve None Gate N/A Class I 1/PL-101 01/09/2019 N/A
1 C CS7 016 Center of room N N/A Cu 4'' 1" CW A Closed Valve None Gate N/A Class I 1/PL-101 01/09/2019 N/A
1 C Outside 001 West Wall Y Brick/CMU/
Concrete Cu 168'' 1" CW B Spigot None Gate N/A Class I 1/PL-102 04/24/2019 N/A
East Orange VAMC Dead Leg Schedule Type A - Pipe length greater than twice the diameter of the pipe size terminating at Cap, Valve, or Fitting.
Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used Plumbing Fixture Type C - Pipe length greater than 25 feet terminating at a frequently used
Plumbing Fixture
Dead Leg Tag Number
Dead Leg Location in Room
Architectural Demolition
Needed (Y/N)
Wall Type Piping Material
Length of Dead Leg
Pipe Pipe Size
Use (Cold Water "CW", Hot
Water "HW", Hot Water
Return "HWR", or Tempered Water "TW")
Dead Leg Type (see above) Termination Fixture
Served Valve Type
Length of Hot Water Piping Not Insulated
Location in I.C.R.A.
Drawing Number to be
Referenced
Date of Inspection Comments
Building Number
Floor Number
Room Number
Dead Leg
Numbe r
Cap
East Orange VAMC Dead Leg Schedule Type A - Pipe length greater than twice the diameter of the pipe size terminating at Cap, Valve, or Fitting.
Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used Plumbing Fixture Type C - Pipe length greater than 25 feet terminating at a frequently used
Plumbing Fixture
Dead Leg Tag Number
Dead Leg Location in Room
Architectural Demolition
Needed (Y/N)
Wall Type Piping Material
Length of Dead Leg
Pipe Pipe Size
Use (Cold Water "CW", Hot
Water "HW", Hot Water
Return "HWR", or Tempered Water "TW")
Dead Leg Type (see above) Termination Fixture
Served Valve Type
Length of Hot Water Piping Not Insulated
Location in I.C.R.A.
Drawing Number to be
Referenced
Date of Inspection Comments
Building Number
Floor Number
Room Number
Dead Leg
Numbe r
1 C 7 001 South Wall N N/A Cu 35'' 3/4" CW A Cap None Ball N/A Class I 1/PL-101 12/06/2018 N/A
1 C 101 001 West Wall N N/A Cu 360'' 3/4" CW A Cap None Gate N/A Class I 1/PL-101 12/04/2018 N/A
1 C 101 002 West Wall N N/A Cu 10'' 1 1/2" CW A Closed Valve None Ball N/A Class I 1/PL-101 12/04/2018 N/A
1 C 101 003 South Wall N N/A Cu 5'' 1" CW A Cap None Globe N/A Class I 1/PL-101 12/04/2018 N/A
1 C 102 001 South Wall N N/A Cu 14'' 3/4" HW A Closed Valve None Globe 7" Class I 1/PL-101 01/11/2019 N/A
1 C 102 002 South Wall N N/A Cu 14'' 3/4" HWR A Closed Valve None Globe 7" Class I 1/PL-101 01/11/2019 N/A
1 C 102 003 South Wall Y Plaster/Sheetrock Cu 144'' 3/4" CW A Cap None None N/A Class I 1/PL-101 01/11/2019 N/A
1 C 102 004 North Wall N N/A Cu 20'' 1" HW A Cap None None 20" Class I 1/PL-101 01/11/2019 N/A
1 C 102 005 Center of room N N/A Cu 216'' 3/4" CW A Closed Valve None Ball N/A Class I 1/PL-101 01/11/2019 N/A
1 C 102 006 South Wall N N/A Cu 216'' 3/4" CW B Spigot None Ball N/A Class I 1/PL-101 01/11/2019 N/A
1 C 104 001 South Wall N N/A Cu 168" 1" HW A Closed Valve None None 168" Class I 1/PL-101 05/30/2019 N/A
1 C 104 002 Center of room N N/A Cu 18'' 1 1/4" HW B Spigot None Gate 20" Class I 1/PL-101 05/30/2019 N/A
1 C 104 003 Center of room N N/A Cu 60" 3/4" CW B Spigot None Ball N/A Class I 1/PL-101 05/30/2019 N/A
1 C 107 001 Center of room N N/A Cu 30'' 3/4" CW A Plug None Globe N/A Class I 1/PL-101 12/05/2018 N/A
1 C 107 002 Center of room N N/A Cu 72'' 1/2" HW A Cap None Globe 2" Class I 1/PL-101 12/05/2018 N/A
1 C 107 003 South Wall N N/A Cu 5'' 3/4" CW B Spigot None Globe N/A Class I 2/PL-105 12/05/2018 N/A
1 C 107 004 South Wall N N/A Cu 5'' 3/4" HW B Spigot None Globe 5" Class I 2/PL-105 12/05/2018 N/A
1 C 107 005 Center of room N N/A Cu 360'' 3/4" CW A Plug None Globe N/A Class I 2/PL-105 01/30/2019 N/A
1 C 107 006 Center of room N N/A Cu 360'' 3/4" HW A Plug None Globe 360" Class I 2/PL-105 01/30/2019 N/A
1 C 110 001 South Wall Y Varies Cu 558'' 1/2" CW C Fixture Sink Gate N/A Class I 1/PL-101 04/23/2019 N/A
1 C 110 002 South Wall Y Varies Cu 598'' 1/2" HW C Fixture Sink Gate 425" Class I 1/PL-101 04/23/2019 N/A
1 C 110A 001 West Wall N N/A Cu 7'' 3/4" CW A Closed Valve None Globe N/A Class I 4/PL-104 12/06/2018 N/A
1 C 110A 002 West Wall N N/A Cu 5'' 3/4" HW A Closed Valve None Globe 5" Class I 4/PL-104 12/06/2018 N/A
1 C 110A 003 West Wall N N/A Cu 5'' 3/4" HWR A Closed Valve None Globe 5" Class I 4/PL-104 12/06/2018 N/A
1 C 110A 004 West Wall Y Varies Cu Unknown 3/4" CW B Fixture Shower None N/A Class I 4/PL-104 12/06/2018 N/A
1 C 110A 005 West Wall Y Varies Cu Unknown 3/4" HW B Fixture Shower None Unknown Class I 4/PL-104 12/06/2018 N/A
1 C 111 001 Center of room N N/A Cu 15'' 3/4" CW A Cap None Ball N/A Class I 1/PL-101 11/09/2018 N/A
1 C 111 002 Center of room N N/A Cu 4'' 3/4" CW A Closed Valve None Ball N/A Class I 1/PL-101 11/09/2018 N/A
1 C 112 002 West Wall N N/A Cu 10'' 1" CW A Closed Valve None Globe N/A Class I 3/PL-104 11/09/2018 N/A
1 C 112 003 West Wall N N/A Cu 10'' 3/4" CW A Cap None Globe N/A Class I 3/PL-104 11/09/2018 N/A
1 C 112 004 East Wall N N/A Cu 216'' 3/4" CW A Closed Valve None Ball N/A Class I 3/PL-104 11/09/2018 N/A
1 C 112 005 Center of room N N/A Cu 30'' 3/4" CW A Closed Valve None Ball N/A Class I 3/PL-104 11/09/2018 N/A
1 C 112 006 North Wall N N/A Cu 14'' 3/4" CW A Closed Valve None Globe N/A Class I 3/PL-104 11/09/2018 N/A
1 C 112 007 North Wall N N/A Cu 14'' 3/4" HWR A Closed Valve None Globe 5" Class I 3/PL-104 11/09/2018 N/A
1 C 112 008 North Wall N N/A Cu 36'' 3/4" HWR A Closed Valve None Globe 6" Class I 3/PL-104 11/09/2018 N/A
1 C 112A 001 West Wall N N/A Cu 7'' 3/4" HW A Cap None None None Class I 1/PL-101 01/11/2019 N/A
1 C 114 001 East Wall N N/A Cu 4'' 3/4" HWR A Closed Valve None Globe 4" Class I 2/PL-104 11/09/2018 N/A
1 C 114 002 West Wall N N/A Cu 216'' 3/4" HW A Cap None None None Class I 2/PL-104 11/09/2018 N/A
1 C 116 001 West Wall Y Plaster/Sheetrock Cu 800'' 3/4" CW B Fixture Shower Globe N/A Class I 1/PL-101 11/09/2018 N/A
1 C 116 002 West Wall Y Plaster/Sheetrock Cu 800'' 3/4" HW B Fixture Shower Globe None Class I 1/PL-101 11/09/2018 N/A
1 C 117 001 North Wall N N/A Cu 120'' 3/4" CW B Fixture Eyewash Ball N/A Class I 1/PL-101 11/09/2018 N/A
1 C 117 002 North Wall N N/A Cu 4'' 3/4" CW A Closed Valve None Ball N/A Class I 1/PL-101 11/09/2018 N/A
1 C 117 003 East Wall N N/A Cu 20'' 3/4" CW A Closed Valve None Globe N/A Class I 1/PL-101 11/09/2018 N/A
1 C 117 004 East Wall N N/A Cu 20'' 3/4" HW A Closed Valve None Globe 3" Class I 1/PL-101 11/09/2018 N/A
1 C 119 001 East Wall N N/A Cu 8" 1 1/4" HWR A Plug None Globe None Class I 4/PL-104 05/30/2019 N/A
1 C 119 002 South Wall N N/A Cu 168'' 1/2" CW B Spigot None None N/A Class I 1/PL-101 05/30/2019 N/A
1 C 119 002 West Wall N N/A Cu 351'' 1/2" CW A Cap None Ball N/A Class I 1/PL-101 05/30/2019 N/A
1 C 122G 001 South Wall N N/A Cu 48'' 1 1/2" CW A Plug None None N/A Class I 1/PL-102 11/08/2018 N/A
1 C 122G 002 South Wall N N/A Cu 36'' 3/4" HW A Plug None None 15" Class I 1/PL-102 11/08/2018 N/A
1 C 122G 003 South Wall N N/A Cu 8'' 1 1/2" CW A Plug None Globe N/A Class I 5/PL-105 11/08/2018 N/A
1 C 122G 004 South Wall N N/A Cu 480'' 1/2" CW A Spigot None Globe N/A Class I 5/PL-105 11/08/2018 N/A
1 C 122G 005 South Wall N N/A Cu 8'' 1/2" HWR A Closed Valve None Globe 2" Class I 5/PL-105 11/08/2018 N/A
1 C 122G 006 South Wall N N/A Cu 8'' 1/2" HWR A Closed Valve None Globe 2" Class I 5/PL-105 11/08/2018 N/A
1 C 124 001 South Wall N N/A Cu 12'' 3/4" CW A Cap None Ball N/A Class I 1/PL-106 10/12/2018 N/A
1 C 124 002 South Wall N N/A Cu 12'' 3/4" CW A Closed Valve None Ball N/A Class I 1/PL-106 10/12/2018 N/A
1 C 124 003 South Wall N N/A Cu 36'' 1 1/4" CW A Plug None Ball N/A Class I 1/PL-106 10/12/2018 N/A
1 C 124 004 North Wall N N/A Cu 10'' 3/4" CW A Cap None Ball N/A Class I 1/PL-106 10/12/2018 N/A
1 C 124 005 North Wall N N/A Cu 10'' 3/4" CW A Cap None Ball N/A Class I 1/PL-106 10/12/2018 N/A
1 C 124 006 Center of room N N/A Cu 10'' 2 1/2" HWR A Cap None None None Class I 1/PL-106 10/12/2018 N/A
1 C 124 007 Center of room N N/A Cu 166'' 2 1/2" HW A Plug None None 6" Class I 1/PL-106 10/12/2018 N/A
1 C 124 008 Center of room N N/A Cu 16'' 2" CW A Cap None None N/A Class I 1/PL-106 10/12/2018 N/A
1 C 124 009 West Wall N N/A Cu 6'' 2" HWR B Spigot None Gate None Class I 1/PL-102 05/30/2019 N/A
1 C 124 010 West Wall N N/A Cu 4'' 3/4" HWR A Closed Valve None Gate 4" Class I 1/PL-102 10/13/2018 N/A
1 C 124 011 South Wall N N/A Cu 10'' 2" HW A Cap None None 10" Class I 1/PL-106 10/12/2018 N/A
1 C 124 012 South Wall N N/A Cu 6'' 2" HW A Cap None None 6" Class I 1/PL-106 10/12/2018 N/A
1 C 124 013 South Wall N N/A Cu 12'' 3/4" HW A Cap None Ball 6" Class I 1/PL-106 10/12/2018 N/A
1 C 124 014 Center of room N N/A Cu 20'' 3/4" CW B Spigot None Gate N/A Class I 1/PL-106 10/13/2018 N/A
1 C 124 015 East Wall N N/A Cu 22'' 1 1/4" CW B Spigot None Ball N/A Class I 1/PL-106 10/13/2018 N/A
1 C 124 016 Center of room N N/A Cu 14'' 2 1/2" CW A Cap None Ball N/A Class I 1/PL-102 10/13/2018 N/A
1 C 124 023 West Wall N N/A Cu 6'' 3/4" HWR A Closed Valve None Ball 6" Class I 1/PL-102 10/13/2018 N/A
1 C 124 024 West Wall N N/A Cu 12'' 1" HWR B Spigot None Ball 12" Class I 1/PL-102 10/13/2018 N/A
1 C 124 025 West Wall N N/A Cu 9'' 1" HWR A Cap None Ball 9" Class I 1/PL-102 10/13/2018 N/A
1 C 124 026 West Wall N N/A Cu 4'' 1 1/2" CW A Closed Valve None Gate N/A Class I 1/PL-102 10/13/2018 N/A
1 C 124 027 South Wall N N/A PVC 24'' 1 1/2" CW A Cap None None N/A Class I 2/PL-106 10/13/2018 N/A
1 C 124 029 Center of room N N/A Cu 15'' 3/4" CW B Spigot None Globe N/A Class I 1/PL-106 11/06/2018 N/A
1 C 124 030 Center of room N N/A Cu 15'' 3/4" HWR B Spigot None Globe 15" Class I 1/PL-106 11/06/2018 N/A
1 C 124 031 Center of room N N/A Cu 600'' 2" CW A Closed Valve None Ball N/A Class I 1/PL-102 11/06/2018 N/A
1 C 124 032 South Wall N N/A Cu 60'' 2" CW A Closed Valve None Ball N/A Class I 1/PL-102 11/06/2018 N/A Cap
V.A.C.
DEAD LEG SCHEDULE 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
FOR BID CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
IMPROVE AND UPGRADE
PL SYSTEM
561-18-101
08/18/2020Revisions: Date:
VANJ HEALTHCARE SYSTEM
385 TREMONT AVE,
EAST ORANGE, NJ 07018
D.L.E.
PL-010
AutoCAD SHX Text 1100 CHURCH STREET HONESDALE, PA 18431 570-253-0846 OFFICE 570-253-1935 FAX WWW.NEINFRA.COM
AutoCAD SHX Text L
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text Y
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text L
AutoCAD SHX Text V
AutoCAD SHX Text M
AutoCAD SHX Text P
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text No. PE059715
AutoCAD SHX Text
ENGINEER
AutoCAD SHX Text
REGISTERED
AutoCAD SHX Text M
AutoCAD SHX Text W
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text F
AutoCAD SHX Text H
AutoCAD SHX Text O
MATTHEW DAVID LESOINE
East Orange VAMC Dead Leg Schedule Type A - Pipe length greater than twice the diameter of the pipe size terminating at Cap, Valve, or Fitting.
Type B - Pipe length greater than twice the diameter of the pipes terminating at an infrequently used Plumbing Fixture Type C - Pipe length greater than 25 feet terminating at a frequently used
Plumbing Fixture
Dead Leg Tag Number
Dead Leg Location in Room
Architectural Demolition
Needed (Y/N)
Wall Type Piping Material
Length of Dead Leg
Pipe Pipe Size
Use (Cold Water "CW", Hot
Water "HW", Hot Water
Return "HWR", or Tempered Water "TW")
Dead Leg Type (see above) Termination Fixture
Served Valve Type
Length of Hot Water Piping Not Insulated
Location in I.C.R.A.
Drawing Number to be
Referenced
Date of Inspection Comments
Building Number
Floor Number
Room Number
Dead Leg
Number
1 B 101 001 West Wall N N/A Cu 28'' 1/2" CW B Spigot None None N/A Class I 1/PL-107 12/05/2018 N/A
1 B 102 001 North Wall N N/A Cu 10'' 1/2" CW B Spigot None Globe N/A Class I 2/PL-111 12/04/2018 N/A
1 B 102 002 North Wall N N/A Cu 12'' 1/2" HW B Spigot None Globe 12" Class I 2/PL-111 12/04/2018 N/A
1 B 102 003 North Wall N N/A Cu 20'' 3/4" CW B Closed Valve None Globe N/A Class I 2/PL-111 12/04/2018 N/A
1 B 102 004 West Wall N N/A Cu 48'' 1" CW A Plug None Globe N/A Class I 2/PL-111 12/04/2018 N/A
1 B 102 005 West Wall N N/A Cu 14'' 1" HW A Plug None Globe None Class I 2/PL-111 12/04/2018 N/A
1 B 102 006 Center of room N N/A Cu 16'' 1" HW B Closed Valve Spigot Gate 5" Class I 3/PL-111 12/04/2018 N/A
1 B 102 007 Center of room N N/A Cu 6'' 3/4" HWR B Closed Valve Spigot Gate 2" Class I 3/PL-111 12/04/2018 N/A
1 B 102 008 Center of room N N/A Cu 5'' 3/4" HW A Closed Valve None Gate None Class I 3/PL-111 12/04/2018 N/A
1 B 102 009 Center of room N N/A Cu 6'' 1" HWR B Spigot None Globe 6" Class I 3/PL-111 12/04/2018 N/A
1 B 102 010 North Wall N N/A Cu 96'' 1/2" CW B Fixture Water
Fountain Globe N/A Class I 2/PL-111 12/04/2018 N/A
1 B 102 011 West Wall Y Brick/CMU/
Concrete Cu 249'' 1 1/2" CW A Cap None None N/A Class I 3/PL-111 12/04/2018 N/A
1 B 108 001 Center of room N N/A Cu 5'' 3/4" HW A Closed Valve None Globe 5" Class I 1/PL-107 01/23/2019 N/A
1 B 110 001 North Wall N N/A Cu 6'' 1/2" HW A Closed Valve None Ball 6" Class II 2/PL-108 01/22/2019 N/A
1 B 110 002 North Wall N N/A Cu 204'' 1/2" CW A Closed Valve None Ball 6" Class II 2/PL-108 01/22/2019 N/A
1 B 110 003 North Wall N N/A Cu 20'' 1/2" CW B Fixture Water
Fountain Ball N/A Class II 1/PL-108 01/22/2019 N/A
1 B 110 004 Center of room Y Varies Cu 360'' 1/2" HW A Cap None Gate 360" Class II 1/PL-108 01/22/2019 N/A
1 B 110 005 Center of room Y Varies Cu 240'' 1/2" CW A Closed Valve None Gate N/A Class II 1/PL-108 01/22/2019 N/A
1 B 110 006 Center of room N N/A Cu 38'' 1/2" CW A Closed Valve None Ball N/A Class II 1/PL-108 01/22/2019 N/A
1 B 110 007 West Wall N N/A Cu 13'' 1/2" CW A Plug None Ball N/A Class II 1/PL-108 01/22/2019 N/A
1 B 110 010 Center of room Y Varies Cu 120'' 1/2" HW A Closed Valve None Globe 5" Class II 1/PL-108 01/23/2019 N/A
1 B 110 011 Center of room N N/A Cu 456'' 3/4" CW A Cap None Ball N/A Class II 1/PL-108 01/28/2019 N/A
1 B 110 012 Center of room N N/A Cu 456'' 3/4" HW A Cap None Ball 15" Class II 1/PL-108 01/28/2019 N/A
1 B 110 013 Center of room N N/A Steel 60" 1/2" CW B Fixture Eyewash None N/A Class II 1/PL-108 01/30/2019 N/A
1 B 110 014 South Wall Y Varies Cu 303'' 1/2" CW B Fixture
Freezer/R efrigerat or Ball N/A Class II 1/PL-108 01/30/2019 N/A
1 B 110C 001 South Wall N N/A Cu 7'' 1/2" CW A Cap None Globe N/A Class II 1/PL-108 01/22/2019 N/A
1 B 110C 002 South Wall N N/A Cu 3'' 1/2" HW A Plug None Gate 3" Class II 1/PL-108 01/22/2019 N/A
1 B 110C 003 West Wall N N/A Galvanize d Unknown 3/4" CW B Spigot None Ball N/A Class II 1/PL-108 06/04/2019 N/A
1 B 110C 004 North Wall Y Brick/CMU/
Concrete Cu Unknown 1" CW B Spigot None Ball N/A Class II 1/PL-108 01/30/2019 N/A
1 B 110C 005 North Wall Y Brick/CMU/
Concrete Cu Unknown 1" CW B Spigot None Ball N/A Class II 1/PL-108 01/30/2019 N/A
1 B 110C 006 South Wall N N/A Cu 48'' 1/2" CW B Fixture Eyewash Ball N/A Class II 1/PL-108 01/30/2019 N/A
1 B 110C 007 South Wall N N/A Cu 48'' 1/2" HW B Fixture Eyewash Ball 48" Class II 1/PL-108 01/30/2019 N/A
1 B 128 001 Center of room N N/A Cu 240'' 3/4" CW B Fixture Equipme nt Globe N/A Class I 1/PL-108 12/07/2018 N/A
1 B 128 002 Center of room N N/A Cu 326'' 3/4" CW A Plug None Globe N/A Class I 1/PL-108 12/07/2018 N/A
1 B 128 003 South Wall N N/A Cu 240'' 1 1/4" CW B Spigot None Ball N/A Class I 6/PL-111 12/07/2018 N/A
1 B 128 004 South Wall N N/A Cu 44" 3/4" TW B Fixture Eyewash Ball 44" Class I 6/PL-111 12/07/2018 N/A
1 B 128 005 South Wall N N/A Cu 24'' 3/4" CW A Closed Valve None Ball N/A Class I 1/PL-107 12/07/2018 N/A
1 B 128 006 East Wall N N/A Cu 432'' 3/4" CW B Spigot None Ball N/A Class I 1/PL-108 12/07/2018 N/A
1 B 128 007 Center of room N N/A Cu 228'' 1/2" CW B Fixture Ice
Machine Ball N/A Class I 1/PL-108 12/07/2018 N/A
1 B 128A 001 Center of room N N/A Cu 7'' 1/2" HW A Cap None Globe None Class I 1/PL-108 12/07/2018 N/A
1 B 128D 001 Center of room N N/A Cu 6'' 3/4" CW B Spigot None Gate N/A Class I 1/PL-108 12/07/2018 N/A
1 B 133 001 Center of room N N/A Cu 120'' 1/2" CW A Cap None None N/A Class I 1/PL-108 12/07/2018 N/A
1 B 133 002 Center of room N N/A Cu 144'' 1/2" HW A Cap None None None Class I 1/PL-108 12/07/2018 N/A
1 B 134 001 East Wall Y Varies Cu 144'' 1/2" CW B Fixture Water
Fountain None N/A Class II 1/PL-108 12/07/2018 N/A
1 B 134D 001 Center of room N N/A Cu 10'' 1/2" CW A Plug None Ball N/A Class II 1/PL-108 12/07/2018 N/A
1 B 134D 002 Center of room N N/A Cu 10'' 1/2" HW A Plug None Ball 10" Class II 1/PL-108 12/07/2018 N/A
1 B 134D 003 Center of room N N/A Cu 12'' 3/4" CW A Cap None None N/A Class II 5/PL-111 12/07/2018 N/A
1 B 134D…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .