P01 - Attachment A-Room Listing.pdf
PDF 103 KB Posted
- Attached to
- H999--Air Testing and Balancing Federal contract opportunity
- Solicitation number
- 36C25225Q0281
About this file
This document is a comprehensive room listing spreadsheet for air testing and balancing services across multiple VA medical facilities, including the Tomah VA Medical Center and several Community-Based Outpatient Clinics (CBOCs). The detailed table specifies 76 distinct rooms across buildings 400, 402, 452, and Wausau CBOC, categorizing each room by function such as Airborne Infection Isolation, Clean Storage, Soiled Storage, Dental Treatment Room, and Sterile Processing (SPS) areas. Each room entry includes specific requirements for air changes per hour and required minimum pressure differential, with testing frequency set as annually occurring in the same month and not exceeding 365 days. The pressure differentials range from negative to positive, with values typically at -0.01 or +0.01 water column pressure, and some specialized areas requiring double negative or double positive pressurization.
The final row provides a critical procedural note that for any failed room test, the contractor shall return to retest up to five rooms per site visit, with a maximum of two additional site visits per year after the Tomah VAMC has corrected the initial failure. This document appears to be part of a solicitation (36C25225Q0281) for air testing and balancing services for the Department of Veterans Affairs Veterans Health Administration's Veterans Integrated Service Network 12, covering multiple medical facilities and specifying precise environmental control requirements for various specialized medical spaces.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25225Q0281.docx | DOCX document | |
| P07 - WD 2015-4929 Rev 27 12.23.2024.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Required Air Changes per Hr.
Required Minimum Pressure Differential
1 400 4052 Airborne Infection Isolation Room Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 2 400 4054 Airborne Infection Isolation Room Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 3 400 1039 Airborne Infection Isolation Room Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 4 400 1108A Airborne Infection Isolation Room Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 5 400 1108B Airborne Infection Isolation Room Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 6 400 1066D Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 7 400 1088 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 8 400 1096A Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 9 400 1260 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 10 400 1264A Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 11 400 2000 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 12 400 2002 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 13 400 2018 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 14 400 2019 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 15 400 2021 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 16 400 2022 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 17 400 2023 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 18 400 2025 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 19 400 2026 SPS sterile Storage durables Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 20 400 2034 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 21 400 2034A Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 22 400 3003 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 23 400 3014A Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 24 400 3014C Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 25 400 30177 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 26 400 3026 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 27 400 3058 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 28 400 3061 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 29 400 3062 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 30 400 1018 Soiled Storage Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 31 400 1066B Soiled Storage Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 32 400 2024 Soiled Storage Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 33 400 2036 Soiled Storage Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 34 400 3014 Soiled Storage Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 35 400 3036 IV medication Annually occurring on same month, not to exceed 365 days 10 Double Neg -.02 water column pressure 36 400 3064 Soiled Storage Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 37 400 3A160 Soiled Storage (Dental) Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 38 400 4037 Acute medical Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 39 402 1229 Soiled Storage Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 40 400 3A152 Dental Treatment Room Annually occurring on same month, not to exceed 365 days 15 Positive +0.01 water column pressure 41 400 3A153 Dental Treatment Room Annually occurring on same month, not to exceed 365 days 15 Positive +0.01 water column pressure 42 400 3A155 Dental Treatment Room Annually occurring on same month, not to exceed 365 days 15 Positive +0.01 water column pressure 43 400 3A157 Dental Treatment Room Annually occurring on same month, not to exceed 365 days 15 Positive +0.01 water column pressure 44 400 3A159 Dental Treatment Room Annually occurring on same month, not to exceed 365 days 15 Positive +0.01 water column pressure 45 400 3A169 Dental Treatment Room Annually occurring on same month, not to exceed 365 days 15 Positive +0.01 water column pressure 46 400 3A171 Dental Treatment Room Annually occurring on same month, not to exceed 365 days 15 Positive +0.01 water column pressure
BuildingItem # Room Room Function Frequency of Testing
47 400 3A173 Dental Treatment Room Annually occurring on same month, not to exceed 365 days 15 Positive +0.01 water column pressure 48 400 3A156 SPS-Storage Sterile Durables Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 49 400 3A175 Dental Treatment Room Annually occurring on same month, not to exceed 365 days 15 Positive +0.01 water column pressure 50 Wausau CBOC 1702 Dental Treatment Room Annually occurring on same month, not to exceed 365 days 15 Positive +0.01 water column pressure 51 Wausau CBOC 1704 Dental Treatment Room Annually occurring on same month, not to exceed 365 days 15 Positive +0.01 water column pressure 52 Wausau CBOC 1715 SPS-Storage Sterile Durables Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 53 Wausau CBOC 1604 SPS-Storage Sterile Durables Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 54 452 15219 SPS- CleanDurables Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 55 452 15223 SPS-Steam Sterilizer Area Annually occurring on same month, not to exceed 365 days 10 Double Pos +0.02 water column pressure 56 452 15225 SPS-Sterilizer Room- Mechanical Annually occurring on same month, not to exceed 365 days 10 Negative -0.01 water column pressure 57 452 15214 SPS-PPE Ante Room/Clean Work Room Annually occurring on same month, not to exceed 365 days 10 Positive +0.01 water column pressure 58 452 15227 SPS-Clean Work Room Annually occurring on same month, not to exceed 365 days 4 Double Pos +0.02 water column pressure 59 452 15120 SPS-Dispatch Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 60 452 15235/15237 SPS-Decontamination Area/HLD Annually occurring on same month, not to exceed 365 days 10 Double Neg -.02 water column pressure 61 452 15200 SPS-Unisex Restroom Annually occurring on same month, not to exceed 365 days 10 Negative -0.01 water column pressure 62 452 15202 SPS-Unisex Restroom Annually occurring on same month, not to exceed 365 days 10 Negative -0.01 water column pressure 63 452 15241 SPS-PPE Soiled Ante Room Annually occurring on same month, not to exceed 365 days 10 Negative -0.01 water column pressure 64 400 3014 Cryogenic Holding Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 65 Wausau CBOC 1340 Cryogenic Holding Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 66 400 3014A Smoke Evacuation (Hyfrecader Room) Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 67 400 1060 Smoke Evacuation (Hyfrecader Room) Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 68 Wausau CBOC 1601 Smoke Evacuation (Hyfrecader Room) Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 69 LaCrosse CBOC 1411 Smoke Evacuation (Hyfrecader Room) Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 70 400 1092 Soiled utility Annually occurring on same month, not to exceed 365 days 10 Negative -0.01 water column pressure 71 400 1093 Clean Storage Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 72 400 1095 clean utility Annually occurring on same month, not to exceed 365 days 4 Positive +0.01 water column pressure 73 400 1108 A Isolation room Ante room Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 74 400 1108 B Isolation Room Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 75 400 2005 Radiology soiled utility Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure 76 Wausau CBOC 1710 Soiled utility( dental) Annually occurring on same month, not to exceed 365 days 12 Negative -0.01 water column pressure
Tomah VA Medical Center and all CBOC's
N/A On a failed room test, and after the Tomah VAMC has corrected the failure, Contractor shall return for retesting, of up to, but not to exceed, five (5) rooms, per site visit, with a maximum of two (2) additional site visits per year.
Sheet1
File details come from the government source that posted it. Updated .