P01_673_23_115 Bid Documents_Maps.pdf

PDF 4 MB Posted

Attached to
Y1DA--FY25: NRM (PROJ:673-23-115) BB Renovate Pharmacy Hood Ductwork
Solicitation number
36C24825R0112
Issued by

About this file

These are bid documents for a renovation project at the James A. Haley Veterans Hospital in Tampa, Florida. The project, designated VA Project #673-23-115, involves renovating pharmacy hood ductwork on the facility's ground floor. The detailed mechanical drawings show plans for demolishing existing exhaust ductwork, installing new ductwork, and replacing HEPA filters for three pharmacy hoods (Biological Safety Cabinets and Compounding Aseptic Containment Isolators). The renovation requires careful coordination with hospital staff, maintaining infection control protocols, and protecting existing equipment during construction. Specific requirements include maintaining a minimum 1'-6" clearance behind hoods, installing new telescopic adjustable sleeves, and reconnecting existing airflow alarms. The project is fully sprinklered and must comply with multiple building, fire, and healthcare facility codes.

View the file

Other files

File Type Posted
P01_673_23_115 BB SOW REV.docx DOCX document
36C24825R0112.docx DOCX document
P01_673_23_115 Specifications.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Contact:

VAMC

Eric Richardson Contracting Officer Represenative(COR) James A. Haley 13000 Bruce B Downs Blvd, Tampa, FL 33612 p: 813-503-3657 e: Eric.Richardson7@va.gov

M402 MECHANICAL SECTION VIEWS

550 North Reo Street, Suite 203 Tampa, FL 33609

G101 INFECTION CONTROL RISK ASSESMENT PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

G100

COVER SHEET

A

Fi le

P at h

/1 5/

1:

:0

AM

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

GUIDON MES JV II, LLC

1221 N PENNSYLVANIA ST.

INDIANAPOLIS, IN 46202

(317) 800-6388

DAVID KEITH, P.E.

AE RENOVATE PHARMACY HOOD

DUCTWORK

673-23-115

11/12/2024 AO ESRevisions: Date:

BID DOCUMENTS

13000 BRUCE B. DOWNS BOULEVARD

TAMPA, FL 33612

PROJECT

AREA

N

SHEET LIST

SHEET NUMBER SHEET NAME

GENERAL

G100 COVER SHEET

ARCHITECTURE

A101 FLOOR PLAN

MECHANICAL

M001 MECHANICAL LEGEND AND GENERAL NOTES

M101 PARTIAL GROUND FLOOR PLAN - MECHANICAL

DEMOLITION

M401 PARTIAL FIRST FLOOR PLAN - AIR DISTRIBUTION

DEMOLITION

Contact:Contact:

MES Group.

Philip Beauchamp Project Manager

MECHANICAL,ELECTRICAL &PLUMBINGOWNER

GUIDON

Erin Sikorski Architect 1221 North Pennsylvania Street Indianapolis, IN 46202 p: 317.800.6388 e: esikorski@guidon.com

ARCHITECT

p:813-331-5084 ext: 2040 e: Philip.Beauchamp@MESGROUPINC.COM

VICINITY MAP

JAMES A. HALEY VETERANS HOSPITAL

TAMPA, FLORIDA

AE Renovate Pharmacy Hood Ductwork

VA PROJECT #673-23-115

N

PROJECT LOCATION

11/12/2024

STOR

HAZ

ANTE

NON-HAZ

HAZ BUFFER

STERILE NON-HAZ BUFFER

STERILE

MISSING DOSE

1ST DOSE/

STORAGE

ANTE

HAZ

(E) BSC (E) BSC(E) CACI

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

/1 5/

1:

:0

AM

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

GUIDON MES JV II, LLC

1221 N PENNSYLVANIA ST.

INDIANAPOLIS, IN 46202

(317) 800-6388

DAVID KEITH, P.E.

AE RENOVATE PHARMACY HOOD

DUCTWORK

673-23-115

11/12/2024 PBJ MANRevisions: Date:

BID DOCUMENTS

13000 BRUCE B. DOWNS BOULEVARD

TAMPA, FL 33612

PROJECT

AREA

KEY PLANN

11/12/2024

G101

INFECTION CONTROL RISK

ASSESSMENT PLAN

G101

1 INFECTION CONTROL RISK ASSESSMENT PLAN

SCALE: 1/4" = 1'-0"N

A. COORDINATE FULL SCOPE OF WORK OF WORK WITH ENGINEERING DRAWINGS AND

FIELD VERIFICATION. CONTRACTOR IS RESPONSIBLE FOR SCOPE OF ABOVE CEILING

WORK REQUIRED WITHIN PROJECT BOUNDARY.

B. COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL (IC) BARRIER WALL

CONSTRUCTION AND INFECTION CONTROL (IC) MEASURES WITH COR AND PATIENT

SAFETY/INFECTION CONTROL REPRESENTATIVE. TEMPORARY IC BARRIER WALL

CONSTRUCTION LOCATIONS IN DRAWING ARE APPROXIMATE. CONTRACTOR SHALL

PROVIDE DRAWING TO COR AND PATIENT SAFETY/INFECTION CONTROL

REPRESENTATIVE ONCE ICRA PROTOCOLS AND PLAN IS APPROVED.

C. SCHEDULE AND TIME OF CONSTRUCTION WORK TO BE APPROVED BY COR AND

PHARMACY STAFF BEFORE CONSTRUCTION MAY BEGIN. PROVIDE INFORMATION FOR

ABOVE CEILING WORK IN THE CONTRACTOR REQUIRED CMP SCHEDULE FOR WORK

REQUIRED WITHIN THE PROJECT BOUNDARY.

D. ABOVE CEILING WORK SHALL TAKE PLACE AS DIRECTED BY THE COR. IN AREAS THAT

REQUIRE ABOVE CEILING WORK WHERE CEILINGS ARE TO REMAIN, CEILING TILES

SHALL BE REMOVED AND STORED IN A SAFE MANOR UNTIL CEILING TILES CAN BE

REINSTALLED. DAMAGED AND BROKEN CEILING TILES SHALL BE REPLACED BY

CONTRACTOR. ANY DAMAGED HARD CEILINGS SHALL BE REPAIRED AND PAINTED TO

MATCH EXISTING.

E. EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED DURING

NORMAL BUSINESS HOURS. SEE SPECIFICATION FOR HOURS OF OPERATION.

F. PROVIDE THE FOLLOWING INFECTION CONTROL MEASURES, A 24"x36" STICKY

WALK-OFF MAT, AND HAND SANITIZER AT EACH TEMPORARY DOOR LOCATION. MAT

SHALL BE REPLACED OR CLEANED AS NECESSARY.

G. PROVIDE THE VA AND OSHA REQUIRED TEMPORARY SIGNAGE AT EACH TEMPORARY

DOOR LOCATION.

H. ALL NEW MATERIAL MOVED THROUGH THE FACILITY SHALL BE COVERED WITH 4 MIL.

POLY SHEET.

I. ALL DEMOLITION MATERIAL SHALL BE REMOVED FROM THE PROJECT BOUNDARY

THROUGH THE FACILITY TO DUMPSTER ALONG VA APPROVED ROUTE IN ENCLOSED

DUMPSTER CART DESIGNED FOR SUCH PURPOSE WITH LID.

J. ALL MATERIAL, DEBRIS, AND HAZARDOUS MATERIALS SHALL BE PROPERLY STORED IN

DESIGNATED AREAS AND APPROVED CONTAINERS. FLAMMABLE MATERIALS SHALL

NOT BE STORED IN THE FACILITY.

K. PROVIDE CONTAINMENT CART FOR ABOVE CEILING ACCESS OUTSIDE PROJECT

BOUNDARY.

GENERAL NOTES

KEYNOTES -

EXISTING STERILE HAZARDOUS BUFFER ROOM SLIDING DOORS SHALL BE UTILIZED AS

THE TEMPORARY INFECTION CONTROL BARRIER DOOR DURING CONSTRUCTION.

EXISTING DOORS SHALL REMAIN OPERABLE DURING ENTIRETY OF CONSTRUCTION.

PROVIDE TEMPORARY INFECTION CONTROL BARRIER CONSTRUCTION AROUND

PASS-THROUGH WINDOW OPENING. TEMPORARY BARRIER SHALL BE CONSTRUCTED

PER SPECIFICATIONS AND ICRA GUIDELINES.

N A101

1 FLOOR PLAN

SCALE: 1/2" = 1'-0"

HAZ BUFFER

STERILE

EXISTING CACI

EXISTING 18x18

ACCESS PANEL

EXISTING 18x18

ACCESS PANEL

EXISTING BSC

EXISTING 12x12

ACCESS PANEL

EXISTING CEILING CAVITY.

DEMOLISH CAVITY IN ENTIRETY,

MATCH EXISTING ADJACENT

CEILING ASSEMBLY AND

FRAMING. REPAINT ENTIRE

CEILING. (SEE PHOTOS ABOVE)EXISTING

CHASE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A101

FLOOR PLAN

A

Fi le

P at h

/1 5/

1:

:0

AM

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

GUIDON MES JV II, LLC

1221 N PENNSYLVANIA ST.

INDIANAPOLIS, IN 46202

(317) 800-6388

DAVID KEITH, P.E.

AE RENOVATE PHARMACY HOOD

DUCTWORK

673-23-115

11/12/2024 AO ESRevisions: Date:

BID DOCUMENTS

13000 BRUCE B. DOWNS BOULEVARD

TAMPA, FL 33612

PROJECT

AREA

KEY PLANN

GENERAL CONSTRUCTION NOTES

THE CONTRACT DOCUMENT DRAWINGS HAVE BEEN PREPARED USING REVIT®

SOFTWARE IN A MICROSOFT WINDOWS ENVIRONMENT. A BUILDING INFORMATION

MODEL (BIM) HAS BEEN DEVELOPED FOR DESIGN COMMUNICATION. THE MODEL

DOES NOT CONTAIN COMPLETE INFORMATION FOR USE IN COST ESTIMATING,

SYSTEMS PERFORMANCE, COORDINATION, SCHEDULING, OR FACILITIES

MANAGEMENT.

THE CONTRACT DOCUMENT DRAWINGS HAVE BEEN PREPARED USING THE

CONSTRUCTION SPECIFICATIONS INSTITUTE'S UNIFORM DRAWING SYSTEM AND THE

NATIONAL CAD STANDARD AND VA STANDARD AS GUIDES.

DISCREPANCIES IN THE CONTRACT DOCUMENTS SHALL BE IMMEDIATELY BROUGHT

TO THE ATTENTION OF THE ARCHITECT AND OWNER’S REPRESENTATIVE/COR.

CONTRACTOR SHALL PROVIDE THE HIGHER GRADE OF QUALITY AND/OR GREATER

QUANTITY OF WORK WHEN BIDDING IF A CLARIFICATION CAN NOT BE OBTAINED BY

THE BID DUE DATE.

CONTRACTOR IS RESPONSIBLE FOR COORDINATING SCOPE OF WORK WITH OWNER’S

REPRESENTATIVE/COR AND VARIOUS FACILITY PERSONNEL INVOLVED WITH UTILITY

SHUT DOWN, INFECTION CONTROLS, OCCUPANT/EMPLOYEE SAFETY, ACCESS

CONTROL, ETC.

ANY INDICATION OF PROJECT LIMITS OR BOUNDARY OF DEMARCATION ARE SHOWN

FOR THE CONVENIENCE OF THE CONTRACTOR, THE FULL SCOPE OF THE PROJECT

LIMIT OF BOUNDARY REQUIRES COORDINATION WITH THE DESIGN SCOPE OF WORK

AND ACCESS TO EXISTING UTILITIES FOR TIE IN.

DRAWINGS ARE PREPARED FROM FIELD VERIFICATION, EXISTING FACILITY DRAWING

BASE FILES, AND USING DIMENSIONS, CONFIGURATIONS AND DETAILS OF SPECIFIC

MANUFACTURERS AS A BASIS OF DESIGN. CONTRACTOR IS RESPONSIBLE FOR

VERIFICATION OF ACTUAL DIMENSIONS, THE COORDINATION OF THE DETAILS WITH

THE PRODUCTS WHICH ARE PROVIDED PER THE SCOPE OF THE SPECIFICATIONS AND

THE SURROUNDING CONSTRUCTION. CONTRACTOR SHALL VERIFY DIMENSIONS,

ROUGH-IN DIMENSIONS, CONNECTIONS, AND OVERALL INSTALLATION REQUIREMENTS.

CONTRACTOR IS RESPONSIBLE FOR THE COMPLETION OF THE ENTIRE SCOPE OF

WORK OUTLINED IN THE CONTRACT DOCUMENTS. CONTRACTOR IS RESPONSIBLE FOR

THE COORDINATION OF ALL SUB-CONTRACTORS AND THE SCOPE OF WORK THEY

PROVIDE. SUB-CONTRACTORS ARE RESPONSIBLE FOR THEIR FULL SCOPE OF WORK

WITHIN THE CONTRACT DOCUMENTS, TRADES ARE NOT SEGMENTED TO ONLY

CERTAIN SHEETS AND SPECIFICATIONS, CROSS COORDINATION IS REQUIRED.

CONTRACTOR AND SUB-CONTRACTORS ARE BOTH RESPONSIBLE FOR

UNDERSTANDING INFORMATION OUTLINED IN THE SPECIFICATIONS, KEY NOTES,

GENERAL NOTES, LEGEND, CODES, ETC., PROVIDED IN THE CONTRACT DOCUMENTS.

CONTRACTOR AND SUB-CONTRACTORS ARE BOTH RESPONSIBLE FOR PROVIDING

AND MAINTAINING SMOKE/FIRE RATINGS OF NEW CONSTRUCTION AND EXISTING

CONSTRUCTION AS INDICATED ON DRAWINGS. THIS INCLUDES PATCHING

PENETRATIONS IN SHAFTS, WALLS, SLABS AND ROOF. ONLY U.L. APPROVED

METHODS, MATERIALS AND INSTALLATION ARE ACCEPTABLE.

MECHANICAL DRAWINGS SHOW

INFORMATION IN A DIAGRAMMATIC FASHION WITHOUT DIMENSIONING. THE GENERAL

CONTRACTOR IS TO COORDINATE THE LOCATIONS OF ALL MECHANICAL

EQUIPMENT WITH RESPECT TO THE ARCHITECTURAL

DETAILING OF SHAFTS, CHASES, CEILING CONSTRUCTION, ETC.

CONTRACTOR IS RESPONSIBLE FOR VERIFYING DIMENSIONS IDENTIFIED AND NOT

IDENTIFIED IN THE CONTRACT DOCUMENTS WITH THE EXISTING AND NEW

CONSTRUCTION ELEMENTS. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION

BETWEEN THE CONTRACT DOCUMENTS, INSTALLED AND UNINSTALLED

CONSTRUCTION BEFORE THE ORDERING OF MATERIALS AND EQUIPMENT. NOTIFY

ARCHITECT AND OWNER’S REPRESENTATIVE/COR OF ANY DISCREPANCIES OR

MISSING DIMENSIONS.

DO NOT SCALE THE DRAWINGS. DRAWING SCALES AS INDICATED ARE FOR GENERAL

ORIENTATION AND CONTEXT ONLY.

THE TERM "ALIGN" MEANS TO INSTALL DIFFERENT/SIMILAR COMPONENTS OF

CONSTRUCTION TO PROVIDE A FLUSH FINISH SURFACE.

ALL DIMENSIONS INDICATED ARE TO FACE OF EXISTING MEMBERS, FACE OF NEW

STRUCTURAL MEMBERS, FACE OF NEW MASONRY, FACE OF NEW STUDS OR COLUMN

GRID LINES UNLESS NOTED OTHERWISE.

FIRST FLOOR ELEVATION 0’-0” IS EQUAL TO THE FINISH FLOOR SLAB OF THE EXISTING

SLAB FLOOR CONSTRUCTION UNLESS NOTED OTHERWISE.

ROUGH OPENINGS SHALL ALLOW FOR SHIM SPACE.

CONTRACTOR TO PROVIDE WORK WHERE DETAILS AND NOTES ARE IDENTIFIED AS

“TYPICAL” OR “SIMILAR” EACH INSTANCE THAT IS THE SAME IN NATURE TO THE DETAIL,

AREA, OR ITEM REFERENCED.

PROVIDED WORK SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR.

CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF DELIVERY, MOUNTING,

INSTALLATION, NECESSARY BLOCKING AND ROUGH-IN.

INSTALLED WORK IS THE CONTRACTOR INSTALLING OWNER FURNISHED MATERIALS

AND EQUIPMENT. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF MATERIAL

DELIVERY, MOUNTING, INSTALLATION AND ROUGH IN.

FURNISHED WORK IS THE CONTRACTOR FURNISHING THE MATERIALS AND

EQUIPMENT TO THE OWNER. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF

DELIVERY AND ROUGH-IN.

ALL PROVIDED WORK SHALL BE WITH NEW MATERIALS UNLESS SPECIFICALLY CALLED

OUT AS SALVAGED OR RELOCATED WITHIN THE CONTRACT DOCUMENTS.

ALL PERSONS DIRECTLY OR INDIRECTLY ASSOCIATED WITH THE PROJECT SHALL BE

FAMILIAR WITH THE RULES AND REGULATIONS OF THE OCCUPATIONAL SAFETY AND

HEALTH ACT, AND IMPLEMENT THOSE RULES AS THEY APPLY TO THIS PROJECT.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND PROTECTING ALL

UTILITY LINES. LOCATIONS SHOWN ARE APPROXIMATE. REPAIR ALL DAMAGE TO

UTILITY LINES CAUSED BY CONSTRUCTION OPERATIONS AT NO COST TO THE OWNER.

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TEMPORARY BRACING AND SHORING

REQUIRED DURING CONSTRUCTION.

CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ADJACENT CONSTRUCTION,

FINISHES, EQUIPMENT, AND TRAVEL ROUTE TO AND FROM THE CONSTRUCTION SITE.

ANY DAMAGE OR UNACCEPTABLE WEAR BY THE CONSTRUCTION TEAM SHALL BE

REPAIRED/REPLACED BY THE CONTRACTOR AT NO COST TO THE OWNER.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

11/12/2024

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

/1 5/

1:

:0

AM

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

GUIDON MES JV II, LLC

1221 N PENNSYLVANIA ST.

INDIANAPOLIS, IN 46202

(317) 800-6388

DAVID KEITH, P.E.

AE RENOVATE PHARMACY HOOD

DUCTWORK

673-23-115

11/12/2024 PBJ MANRevisions: Date:

BID DOCUMENTS

13000 BRUCE B. DOWNS BOULEVARD

TAMPA, FL 33612

11/12/2024

M001

GENERAL NOTES, LEGENDS,

ABBREVIATIONS & DETAILS

KEYNOTE

CONTINUATION SYMBOL

NUMBER OF SHEET WHERE DETAIL APPEARS

NUMBER OF DETAIL ON SHEET

REVISION NUMBER - SHOWN ON PLANS

ROOM NAME AND NUMBER

NEW CONNECTION TO EXISTING

ITEM TO BE DEMOLISHED

AREA NOT IN CONTRACT

Room

18"x12"

18"/12"

(E)

18"Ø

EXHAUST AIR

SUPPLY AIR

TYPE (REFER TO SCHEDULES)

CFM

EXISTING DUCT TAG

OVAL DUCT SIZE TAG (WIDTH / HEIGHT)

SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)

RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE

RECTANGULAR RETURN/TRANSFER AIR DUCT RISE

ROUND DUCT SIZE TAG (DIAMETER)

DUCT BEING DEMOLISHED

ROUND SUPPLY/OUTSIDE AIR DUCT RISE

ROUND RETURN/TRANSFER AIR DUCT RISE

RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE

ROUND EXHAUST/RELIEF AIR DUCT RISE

DROP

DROP

DROP

DROP

DROP

DROP

EXISTING HOOD

TO REMAIN (E) BSC

ABV ABOVE

AC AIR CONDITIONING

ADD ADDENDUM

AFF ABOVE FINISHED FLOOR

ALT ALTERNATE

AP ACCESS PANEL

ARCH ARCHITECT/ARCHITECTURAL

BFF BELOW FINISHED FLOOR

BTU BRITISH THERMAL UNITS

BTUH BTU PER HOUR

CAP CAPACITY

CFM CUBIC FEET PER MINUTE

CLG CEILING

D DEGREE

DB DRY BULB

DIA DIAMETER

DN DOWN

EAT ENTERING AIR TEMP

ELEC ELECTRICAL

EQUIP EQUIPMENT

EWT ENTERING WATER TEMP

EA EXHAUST AIR

EXIST EXISTING

F DEGREES FAHRENHEIT

FL FLOOR

FPM FEET PER MINUTE

FT FOOT/FEET

GAL GALLON

GF GAS-FIRED

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

HP HORSEPOWER

IN INCH

LAT LEAVING AIR TEMP

LWT LEAVING WATER TEMP

MA MIXED AIR

MAX MAXIMUM

MBH ONE THOUSAND BTUH

MCF ONE THOUSAND CUBIC FEET

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MTR MOTOR

MUA MAKE-UP AIR

NC NOISE CRITERIA

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

NUM NUMBER

OA OUTSIDE AIR

PD PRESSURE DROP

PLBG PLUMBING

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH

GAUGE

PWR POWER

R

DUCT RISER

RA RETURN AIR

REC RECESSED

RED REDUCER

RH RELATIVE HUMIDITY

RLA RELIEF AIR

RM ROOM

RPM REVOLUTIONS PER MINUTE

SF SQUARE FOOT

SA SUPPLY AIR

SF SQUARE FOOT

SP STATIC PRESSURE

THERMOSTAT

TD TEMPERATURE DROP

TEMP TEMPERATURE

TYP TYPICAL

VENT VENTILATION

WB WET BULB

SUPPLY

DIFFUSER

BSC BIOLOGICAL SAFETY CABINET

CACI COMPOUNDING ASEPTIC

CONTAINMENT ISOLATOR

F EXHAUST FAN

EQUIPMENT ABBREVIATIONS

18"x18" SA

18"x18" EA

1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATIVE OF

WORK TO BE PROVIDED (FURNISHED AND INSTALLED) UNDER THIS

CONTRACT. DRAWINGS SHOULD NOT BE SCALED.

2. THE CONTRACTOR IS RESPONSIBLE TO EXAMINE THE EXISTING

CONDITIONS UNDER WHICH THEY SHALL OPERATE AND VERIFY THE

EXTENT OF WORK REQUIRED TO COMPLETE THE WORK UNDER THIS

CONTRACT.

3. PRIOR TO ORDERING AND FABRICATING ANY EQUIPMENT, IT IS THE

RESPONSIBILITY OF THE CONTRACTOR TO EXAMINE THE PHYSICAL

CONDITIONS AT THE PROJECT SITE AND VERIFY SPACE AND SUFFICIENT

CLEARANCES ARE AVAILABLE FOR INSTALLING EQUIPMENT, DUCTWORK,

PIPING, AND APPURTENANCES, AND TO DETERMINE ANY NECESSARY

MODIFICATIONS.

4. PERFORM ALL WORK IN COMPLIANCE WITH ALL APPLICABLE FEDERAL,

STATE, AND LOCAL CODES, REGULATIONS, AND STANDARDS ADOPTED BY

THE AUTHORITY HAVING JURISDICTION. IF CONFLICTS EXIST BETWEEN

THESE ENGINEERING DOCUMENTS AND CODES, THE MOST STRINGENT

REQUIREMENTS SHALL GOVERN.

5. ALL CONSTRUCTION WORK SHALL ALSO MEET THE FOLLOWING CODE

REQUIREMENTS:

· INTERNATIONAL BUILDING CODE (IBC) 2024

· INTERNATIONAL EXISTING BUILDING CODE (IEBC) 2024

· INTERNATIONAL MECHANICAL CODE (IMC) 2024

· INTERNATIONAL ENERGY CONSERVATION CODE (IECC) 2021

· NFPA 1-2024, THE UNIFORM FIRE CODE

· NFPA 101-2024, THE LIFE SAFETY CODE

· NFPA 51B-2024, STANDARD FOR FIRE PREVENTION DURING WELDING,

CUTTING AND OTHER HOT WORK

· NFPA 13-2022, STANDARD FOR THE INSTALLATION OF SPRINKLER

SYSTEMS

· NFPA 70-2023, NATIONAL ELECTRICAL CODE

· NFPA 90A-2024, STANDARD FOR THE INSTALLATION OF AIR

CONDITIONING AND VENTING SYSTEMS.

· NFPA 99-2024, STANDARD FOR HEALTH CARE FACILITIES

· NFPA 241-2022, STANDARD FOR SAFEGUARDING CONSTRUCTION,

ALTERATION AND DEMOLITION OPERATIONS.

· VA TECHNICAL INFORMATION LIBRARY (TIL)

· USP-797 & 800

6. CONTRACTOR SHALL COORDINATE AND SEQUENCE DEMOLITION,

CLEANING, AND CONSTRUCTION WORK.

7. CONTRACTOR SHALL NOTE ANY SPECIAL REQUIREMENTS FOR

INSTALLATION OF WORK UNDER THIS CONTRACT. DISMANTLE AND

REASSEMBLE EQUIPMENT AS NECESSARY FOR ENTRY INTO THE BUILDING

AND THE LOCATION OF INSTALLATION.

8. THE CONTRACTOR SHALL MAINTAIN A COMPLETE PROJECT SCHEDULE AND

SHALL UPDATE THIS SCHEDULE WEEKLY. ANY CHANGES SHALL BE NOTED

AND AN UPDATED SCHEDULE SHALL BE PROVIDED TO THE OWNER.

9. ALL PERMITS, FEES, TAXES, ETC SHALL BE PAID BY CONTRACTOR AS PART

OF THE TOTAL PROJECT COST.

10. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS,

PARTITIONS, CEILINGS, AND FLOORS. SEAL ALL PENETRATIONS THROUGH

RATED ASSEMBLIES WITH FIRESTOP MATERIAL IN ACCORDANCE WITH U.L.

REQUIREMENTS TO MAINTAIN THE ASSEMBLY RATING.

11. CONTRACTOR SHALL FURNISH U.L. APPROVED DRAWINGS FOR EACH TYPE

OF FIRE AND SMOKE RATED ASSEMBLY PENETRATION BY DUCTS, PIPES, OR

CONDUITS, AND SHALL DISPLAY THESE DRAWINGS ON THE JOB SITE AT ALL

TIMES DURING CONSTRUCTION.

12. CONTRACTOR SHALL REFER TO ALL DETAILS FOR PROPER GUIDANCE.

13. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT

SUBMITTALS FOR ALL PRODUCTS USED ON PROJECT.

14. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE

CONTRACTOR OF RESPONSIBILITY FOR DEVIATIONS FROM THE

REQUIREMENTS OF CONTRACT DOCUMENTS UNLESS THE CONTRACTOR

HAS RECEIVED WRITTEN APPROVAL FROM THE ENGINEER TO THE SPECIFIC

DEVIATION. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT

RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR ERRORS OR

OMISSIONS IN HIS OR HER SUBMITTAL DATA.

15. THE CONTRACTOR IS REQUIRED TO SUBMIT THREE COMPLETE O&M

MANUALS IN THREE RING BINDERS AT SUBSTANTIAL COMPLETION.

MANUALS SHALL INCLUDE INSTALLATION AND MAINTENANCE DATA ON ALL

NEW EQUIPMENT AND MATERIALS, CERTIFIED TECHNICAL PRODUCT DATA,

EQUIPMENT SHOP DRAWINGS, SPARE PARTS DATA, ETC. PROVIDE AN

INDEX AND ASSOCIATED DIVIDERS.

16. CLOSE OUT DOCUMENTS: THE CONTRACTOR IS TO MAINTAIN ONE SET OF

CONSTRUCTION DRAWINGS ON SITE AND KEEP CURRENT WITH MARK UP

AS-BUILT CONDITIONS DURING CONSTRUCTION OF THE PROJECT. THIS SET

IS TO INCLUDE ALL CONTRACT CHANGES, MODIFICATIONS, AND

CLARIFICATIONS. THIS SET ALONG WITH ALL SHOP DRAWINGS SHALL BE

TURNED OVER TO THE ARCHITECT/ENGINEER AFTER CONSTRUCTION

COMPLETION.

17. IT IS THE RESPONSIBILITY OF ALL BIDDERS TO THOROUGHLY REVIEW AND

UNDERSTAND ALL CONSTRUCTION DOCUMENTS. THIS INCLUDES BUT IS

NOT LIMITED TO ALL DRAWINGS, SPECIFICATION SECTIONS, ETC. THE

DRAWINGS ARE SCHEMATIC IN NATURE. THEREFORE BEFORE STARTING

ANY WORK, THE CONTRACTOR SHALL REVIEW ALL OTHER CONSTRUCTION

DOCUMENTS, VERIFY FIELD CONDITIONS AND SHALL MAKE ANY REQUIRED

MINOR ADJUSTMENTS WITHOUT EXTRA COST TO THE OWNER. ANY MAJOR

DISCREPANCIES FOUND SHALL BE BROUGHT TO THE ATTENTION OF THE

ARCHITECT/ENGINEER. THE BASE BID SHALL REFLECT THE TOTAL COST OF

NEW EQUIPMENT INSTALLATION. THIS INCLUDES LABOR, EQUIPMENT AND

MATERIALS. NO CHANGE ORDERS SHALL BE ISSUED WITHOUT WRITTEN

CONSENT AND APPROVAL FROM ENGINEER AND ARCHITECT.

1. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF FIELD CONDITIONS

PRIOR TO BEGINNING WORK AND ORDERING EQUIPMENT, AND FOR

COORDINATING NEW EQUIPMENT DIMENSIONS AND MEANS AND

METHODS FOR INSTALLATION WITH FIELD CONDITIONS.

2. CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH EXISTING

EQUIPMENT TO ENSURE ALL INLET/OUTLET CONNECTIONS COORDINATE

WITH FIELD INSTALLED DUCTWORK AND MAKE ANY NECESSARY DUCT

MODIFICATIONS TO ENSURE PROPER OPERATION OF MECHANICAL

EQUIPMENT.

3. ALL DUCT CONSTRUCTION, INSTALLATION, AND SUPPORTS ARE TO

COMPLY WITH LATEST EDITION OF SMACNA'S HVAC DUCT

CONSTRUCTION STANDARDS METAL AND FLEXIBLE DUCT. ALL

DUCTWORK SHALL BE 2" PRESSURE CLASS UNLESS OTHERWISE NOTED.

4. ROUND DUCTS AND FITTINGS SHALL BE 18 GAUGE STAINLESS STEEL, ALL

WELDED.

5. CONTRACTOR SHALL PROVIDE A COPY OF THE TEST AND BALANCE

REPORT BY AN AABC OR NEBB CERTIFIED AGENCY. THIS REPORT MUST

BE REVIEWED AND APPROVED BY THE ENGINEER PRIOR TO THE FINAL

INSPECTION. THE CONTRACTOR MUST ALSO PROVIDE ALL REPORTS

REQUIRED BY THE SPECIFICATION. OUTDOOR TEMPERATURE (DB);

OUTSIDE AIR (DB/WB & CFM); SUPPLY AIR AT UNIT DISCHARGE (DB/WB &

CFM); RETURN AIR {MIXED} (DB/WB & CFM); LEAVING COIL (DB/WB);

DIFFUSER/GRILLE (DB/WB); EQUIPMENT (EWT/LWT); EQUIPMENT

(EAT/LAT); EQUIPMENT (GPM); EQUIPMENT (PRESSURES). OUTSIDE AIR

CFM SHALL BE MEASURED DIRECTLY AND NOT CALCULATED FROM THE

DIFFERENCE BETWEEN SUPPLY AIR CFM AND RETURN AIR CFM.

6. CONTRACTOR SHALL MAKE NECESSARY ADJUSTMENTS DURING TEST

AND BALANCE AS REQUIRED TO ENSURE EQUIPMENT IS OPERATING

WITHIN 10% OF THE SPECIFIED CRITERIA. THIS INCLUDES, BUT IS NOT

LIMITED TO, ADJUSTING BELTS, SHEAVES, PULLEYS, AND IMPELLERS.

7. INTENT OF MECHANICAL NOTES ON DRAWINGS IS TO CLARIFY THE

SCOPE OF WORK AND ALERT CONTRACTOR OF EXISTING CONDITIONS.

CONTRACTOR IS TO VISIT THE SITE AND VERIFY ALL CLEARANCES

BEFORE FABRICATION OF DUCTWORK, AND PROVIDE ADDITIONAL

OFFSET AND/OR CHANGES IN DUCT SIZES TO MEET FIELD CONDITIONS.

8. CONTRACTOR SHALL PROVIDE ALL SUPPLEMENTARY STEEL,

STRUCTURES, INSERTS, SLEEVES, AND HANGING DEVICES REQUIRED TO

INSTALL AND ADEQUATELY SUPPORT MECHANICAL EQUIPMENT AND

COMPONENTS IN A MANNER WHICH WILL NOT OVERLOAD BUILDING

STRUCTURE. CONTRACTOR SHALL COORDINATE WITH GENERAL

CONTRACTOR AND ALL BUILDING TRADES TO AVOID CONFLICTS AND TO

MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY.

9. DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE

DIMENSIONS (FREE AREA).

10. CONTRACTOR SHALL THOROUGHLY CLEAN AND ENSURE PROPER

OPERATION OF ANY EXISTING HVAC EQUIPMENT. ANY CHANGE TO THE

SYSTEM SHALL RESULT IN EQUIPMENT MODIFICATIONS (AS REQUIRED)

INCLUDING BUT NOT LIMITED TO REPLACING MOTORS, VFDS, PULLEYS,

SHEAVES, BELTS, ETC.

11. ALL EXHAUST DUCT WORK SHALL BE NON-INSULATED SHEET METAL,

UNLESS NOTED OTHERWISE.

12. PRIOR TO FINAL INSPECTION, PROVIDE RECORD DRAWINGS, SYSTEM

BALANCING REPORT, AND FINAL COMMISSIONING REPORT TO OWNER.

13. FINAL CERTIFICATION SHALL BE PROVIDED BY PROPER HOOD TESTING

AGENCY. COMMISSIONING AGENT, OWNER, AND CONTRACTOR SHALL

ALL BE PRESENT DURING FINAL CERTIFICATION. CONTRACTOR SHALL BE

RESPONSIBLE FOR APPROPRIATELY FIXING ANY ISSUES THAT MAY

PREVENT FINAL CERTIFICATION OF PHARMACY HOODS.

ABBREVIATIONS

GENERAL MECHANICAL SYMBOLS

LIMIT OF DEMOLITION

HVAC SYMBOLS

CD-XX

XXX CFM

RETURN

GRILLE

TYPE (REFER TO SCHEDULES)

CFM

RG-XX

XXX CFM

EXHAUST

GRILLE

TYPE (REFER TO SCHEDULES)

CFM

EG-XX

XXX CFM

SIDEWALL

SUPPLY GRILLE

TYPE (REFER TO SCHEDULES)

CFM

SG-XX

XXX CFM

LINEAR SLOT

DIFFUSER

TYPE (REFER TO SCHEDULES)

CFM

LSD-XX

XXX CFM

GRILLES, REGISTERS & DIFFUSERS TAG

MECHANICAL EQUIPMENT TAGS

GENERAL NOTESMECHANICAL NOTES

N.T.S.

1 EXHAUST OR RETURN BRANCH DUCTWORK

N.T.S.

2 EXHAUST DUCT CONNECTION DETAIL (BSC)

3 EXHAUST DUCT CONNECTION DETAIL (CACI)

N.T.S.

T

Sheet List Table Sheet Number Sheet Title

M001 GENERAL NOTES, LEGENDS, ABBREVIATIONS & DETAILS

M101 PARTIAL GROUND FLOOR PLAN - MECHANICAL

M401 ENLARGED PLAN - STERILE HAZ BUFFER - MECHANICAL

M402 MECHANICAL SECTION VIEWS

STOR

HAZ

ANTE

NON-HAZ

HAZ BUFFER

STERILE NON-HAZ BUFFER

STERILE

FLUID STORAGE

RECIEVING/BREAKDOWN

MISSING DOSE

1ST DOSE/

STORAGE

DISPENSING

RESEARCH

ANTE

HAZ

WORKSTATIONS

VAULT

COMPOUNDING

NON-STERILE

PREPACK

OFFICE

R.ROOM

OFFICE

MD MD

(E )2

6x

E A

M401

(E)10x6 EA

(E)9x12 EA DN

(E)26x12 EA

(E )2

6x

E A

(E)32X10 EA

(E)22X14 EA

UP TO (E) F-1B

ON ROOF

(E)32X10 EA

(E)22X14 EA

UP TO (E) F-1A

ON ROOF

M401

(E) BSC (E) BSC(E) CACI

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

/1 5/

1:

:0

AM

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

GUIDON MES JV II, LLC

1221 N PENNSYLVANIA ST.

INDIANAPOLIS, IN 46202

(317) 800-6388

DAVID KEITH, P.E.

AE RENOVATE PHARMACY HOOD

DUCTWORK

673-23-115

11/12/2024 PBJ MANRevisions: Date:

BID DOCUMENTS

13000 BRUCE B. DOWNS BOULEVARD

TAMPA, FL 33612

11/12/2024

M101

PARTIAL GROUND FLOOR PLAN -

MECHANICAL

M101

1 PARTIAL GROUND FLOOR PLAN - MECHANICAL

SCALE: 1/4" = 1'-0"N

PROJECT

AREA

KEY PLANN

(E )2

6x

E A

EXISTING 18x18

ACCESS PANEL

(E) EG

300 CFM

M402

(E) 12X12 EA DN TO

EXHAUST GRILLE

(E) CD

500 CFM

(TYP. OF 3)

1 1

EXISTING 18x18

ACCESS PANEL

(E) CACI

300 CFM

(E) BSC

600 CFM

(E) BSC

600 CFM

HAZ BUFFER

STERILE

EXISTING 12x12

ACCESS PANEL

(E)18x12 EA (E)12x10 EA

(E)24x12 SA

2 2

EXISTING 18x18

ACCESS PANEL

EXISTING 12x12

ACCESS PANEL

HAZ BUFFER

STERILE

(E) CD

500 CFM

(TYP. OF 3)

EXISTING 18x18

ACCESS PANEL

(E) 12X12 EA DN TO

EXHAUST GRILLE

M402

(E) EG

300 CFM (E

)2 6x

E

A (E)18x12 EA (E)12x10 EA

EXISTING 18x18

ACCESS PANEL

(E)24x12 SA

(E) CACI

300 CFM

(E) BSC

600 CFM

(E) BSC

600 CFM

4 4

5 5

1'-6"

TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

/1 5/

1:

:0

AM

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

GUIDON MES JV II, LLC

1221 N PENNSYLVANIA ST.

INDIANAPOLIS, IN 46202

(317) 800-6388

DAVID KEITH, P.E.

AE RENOVATE PHARMACY HOOD

DUCTWORK

673-23-115

11/12/2024 PBJ MANRevisions: Date:

BID DOCUMENTS

13000 BRUCE B. DOWNS BOULEVARD

TAMPA, FL 33612

PROJECT

AREA

KEY PLANN

11/12/2024

M401

ENLARGED PLAN - STERILE HAZ

BUFFER - MECHANICAL

M401

1 ENLARGED PLAN - MECHANICAL DUCTWORK - DEMOLITION

SCALE: 1/2" = 1'-0"

M401

2 ENLARGED PLAN - MECHANICAL DUCTWORK - NEW WORK

SCALE: 1/2" = 1'-0"N

N

M401

3 IMAGE - EXISTING PHARMACY HOODS LAYOUT

N.T.S.

M401

4 IMAGE - EXISTING FLEXIBLE DUCT IN CEILING CAVITY

N.T.S.

M401

5 IMAGE - EXISTING CLEARANCE BEHIND HOOD TO ADJACENT WALL

N.T.S.

A. EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, GRILLES, AND ASSOCIATED

COMPONENTS SHOWN ON DRAWINGS ARE APPROXIMATE LOCATIONS AND ARE

PROVIDED FOR REFERENCE USE ONLY. FIELD VERIFY AND COORDINATE WITH EXACT

LOCATIONS, ELEVATIONS, SIZES, AND CONDITIONS OF EXISTING COMPONENTS.

B. ALL EXISTING EQUIPMENT TO BE REUSED SHALL BE PRESSURE TESTED, THOROUGHLY

CLEANED, AND SANITIZED TO AVOID POSSIBLE CONTAMINATION.

C. ALL EXISTING EQUIPMENT REMOVED SHALL BE TURNED OVER TO OWNER.

D. CEILING SHALL BE PROPERLY PROTECTED DURING CONSTRUCTION. CONTRACTOR

SHALL REPAIR ANY DAMAGE DURING CONSTRUCTION TO MATCH EXISTING CEILING.

GENERAL NOTES

KEYNOTES -

EXISTING EXHAUST DUCTWORK SHALL BE DEMOLISHED FROM PHARMACY HOOD

TRANSITION PIECE UP TO EXISTING BRANCH DUCT. CAP EXISTING OPENING DURING

CONSTRUCTION. REFER TO SECTION VIEW ON DRAWING M402 FOR MORE

INFORMATION.

CONTRACTOR SHALL REMOVE EXISTING HOOD FROM SPACE DURING DEMOLITION AND

CONSTRUCTION. EXISTING HOOD SHALL BE PROTECTED FROM DAMAGE, DUST, AND

DEBRIS THROUGHOUT ENTIRETY OF CONSTRUCTION WORK.

NEW TELESCOPIC ADJUSTABLE SLEEVE SHALL BE INSTALLED AT CEILING

PENETRATION. CONNECT NEW EXHAUST DUCTWORK TO NEW LOW-PROFILE

TRANSITION AT EXISTING PHARMACY HOOD. REFER TO SECTION VIEW ON DRAWING

M402 FOR MORE INFORMATION.

EXISTING HOOD HEPA FILTER SHALL BE REMOVED AND REPLACED WITH NEW HEPA

FILTER AT COMPLETION OF CONSTRUCTION.

EXISTING SUPPLY GRILLE HEPA FILTER SHALL BE REMOVED AND REPLACED WITH NEW

HEPA FILTER AT COMPLETION OF CONSTRUCTION.

HOODS SHALL HAVE A MINIMUM CLEARANCE OF ~1'-6" BEHIND HOOD TO ADJACENT

WALL TO ALLOW FOR PROPER CLEANING OF SPACE IN ORDER TO COMPLY WITH USP

STANDARDS. CONTRACTOR SHALL OFFSET EXHAUST DUCTWORK ABOVE CEILING AS

REQUIRED TO ALIGN WITH HOOD EXHAUST OPENING. (TYPICAL FOR ALL THREE (3)

PHARMACY HOODS)

(E )8

"Ø E

A

(E)10"Ø EA

(E)12x10 EA(E)26x12 EA (E)18x12 EA

EXISTING BSC EXISTING BSC

EXISTING CACI

(E)12x10 BRANCH

DUCT

(E)12x10 BRANCH

DUCT

(E)12x10 BRANCH

DUCT

CEILING 2 2

3 3

HAZ BUFFER

STERILE 1

8" Ø

E A

(E)12x10 EA(E)26x12 EA (E)18x12 EA

EXISTING BSC

EXISTING CACI

(E)12x10 BRANCH

DUCT

(E)12x10 BRANCH

DUCT

(E)12x10 BRANCH

DUCT

CEILING 4

8" Ø

E A

HAZ BUFFER

STERILE

EXISTING BSC

"Ø

E A

"Ø

E A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

/1 5/

1:

:0

AM

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD A/E:

STAMP

321 4 5 6 7 8 9 10

GUIDON MES JV II, LLC

1221 N PENNSYLVANIA ST.

INDIANAPOLIS, IN 46202

(317) 800-6388

DAVID KEITH, P.E.

AE RENOVATE PHARMACY HOOD

DUCTWORK

673-23-115

11/12/2024 PBJ MANRevisions: Date:

BID DOCUMENTS

13000 BRUCE B. DOWNS BOULEVARD

TAMPA, FL 33612

PROJECT

AREA

KEY PLANN

11/12/2024

M402

MECHANICAL SECTION VIEWS

M402

2 SECTION VIEW - MECHANICAL DUCTWORK - NEW WORK

SCALE: 1/2" = 1'-0"

M402

1 SECTION VIEW - MECHANICAL DUCTWORK - DEMOLITION

SCALE: 1/2" = 1'-0"

A. EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, GRILLES, AND ASSOCIATED

COMPONENTS SHOWN ON DRAWINGS ARE APPROXIMATE LOCATIONS AND ARE

PROVIDED FOR REFERENCE USE ONLY. FIELD VERIFY AND COORDINATE WITH EXACT

LOCATIONS, ELEVATIONS, SIZES, AND CONDITIONS OF EXISTING COMPONENTS.

B. ALL EXISTING EQUIPMENT TO BE REUSED SHALL BE PRESSURE TESTED, THOROUGHLY

CLEANED, AND SANITIZED TO AVOID POSSIBLE CONTAMINATION.

C. ALL EXISTING EQUIPMENT REMOVED SHALL BE TURNED OVER TO OWNER.

D. CEILING SHALL BE PROPERLY PROTECTED DURING CONSTRUCTION. CONTRACTOR

SHALL REPAIR ANY DAMAGE DURING CONSTRUCTION TO MATCH EXISTING CEILING.

DEMOLISH EXISTING EXHAUST DUCTWORK BACK TO EXISTING BRANCH DUCT.

PROTECT EXISTING OPENING DURING CONSTRUCTION.

REMOVE EXISTING HOOD CANOPY TRANSITION PIECE AND RETURN TO OWNER.

STORE EXISTING PHARMACY HOOD IN A PROTECTED AREA AWAY FROM

CONSTRUCTION DUST AND DEBRIS.

STORE EXISTING AIRFLOW ALARM TO PROTECT FROM ANY CONSTRUCTION DUST AND

DEBRIS.

LOCATE EXISTING PHARMACY HOOD IN APPROPRIATE AREA OF EXISTING SPACE.

COORDINATE WITH OWNER. INSTALL GERMFREE "LOW-PROFILE TRANSITION" ON

EXISTING CABINET AND CONNECT TO NEW TELESCOPIC ADJUSTABLE SLEEVE AT

CEILING.

EXISTING AIRFLOW ALARM SHALL BE RE-INSTALLED IN NEW 10"Ø EXHAUST

DUCTWORK BELOW CEILING AND POWER SHALL BE RECONNECTED.

NEW TELESCOPIC ADJUSTABLE SLEEVE SHALL BE INSTALLED IN CEILING AND

CONNECT TO LOW-PROFILE TRANSITION. SLEEVE SHALL BE STAINLESS STEEL.

AIR-TIGHT, HYGIENIC SILICONE FLEXIBLE CEILING SEAL. EQUAL TO CSI "PIPETITE

STANDARD" MODEL.

GENERAL NOTES

KEYNOTES -

G100 COVER SHEET
Model
G101 INFECTION CONTROL RISK ASSESSMENT PLAN
A101 FLOOR PLAN
Model
M001 GENERAL NOTES, LEGENDS, ABBREVIATIONS & DETAILS
M101 PARTIAL GROUND FLOOR PLAN - MECHANICAL
M401 ENLARGED PLAN - STERILE HAZ BUFFER - MECHANICAL
M402 MECHANICAL SECTION VIEWS

File details come from the government source that posted it. Updated .