OR Standard Drawing Set.pdf

PDF 3 MB Posted

Attached to
26PW16 - 2026 Storm Water Improvements
Solicitation number
S-KR1079-00018476
Issued by
Oregon

About this file

This is an Oregon Standard Drawings document published by the Oregon Department of Transportation (ODOT) and applicable to state and local contract opportunities within Oregon. The document comprises a comprehensive set of technical standard drawings (RD250 through RD700 series) detailing specifications for water infrastructure construction, including thrust blocking, pipe installation, trenching, street cuts, manhole construction, inlet systems, and curb and gutter work. The drawings provide standardized details for contractors performing work on water distribution and storm sewer systems, with effective dates ranging from December 1, 2025 through May 31, 2027. These standards apply to commercial-grade concrete construction, pipe bedding and backfill requirements, manhole configurations, concrete inlet designs, and traffic-compatible surface restoration. The document does not specify project quantities, response dates, bid due dates, site visits, or award dates, as it functions as a reference standard rather than a solicitation document.

The Oregon Standard Drawings establish material specifications and construction procedures binding on all contractors performing work under contracts referencing these standards. All materials must comply with current Oregon Standard Specifications and conform to referenced ASTM standards (including ASTM A615 Grade 60 reinforcing steel, ASTM C478 for precast manhole products, ASTM C913 for precast inlets, ASTM C923 for resilient connectors, and ASTM A48 for cast iron components). The document requires consultation with a registered professional engineer for design verification and explicitly notes that selection and use of these standard drawings remain the sole responsibility of the user. No pricing information, funding sources, set-asides, incumbent contractor information, or contract pricing terms are included in this technical reference document.

View the file

Other files

File Type Posted
Plan Set.pdf PDF
Specification Documents~2.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RD250

THRUST BLOCKING

R D

.d g n

REVISIONMM-YYYY

25-JUL-2017N/A

J U

L

TABLE B

B

T

Hard shale

Sand and gravel cemented with clay

Sand and gravel

Sand

Soft Clay

Muck, peat, etc.

10,000

Stirrup (Typ.)

THRUST BLOCK BEARING AREA EQUATION

DETERMINE REQUIRED BEARING AREA.

DETERMINED BY THE ENGINEER, USE THE FOLLOWING PROCEDURE TO

NOTE: WHEN THRUST BLOCK BEARING AREA IS NOT SPECIFIED ON THE PLANS OR

Bearing Area

Thrust Block Table Pressure

Design (Test) Pressure

37320

Soil = Sand A = 11.2 sq.ft.

Fitting = Tee

Pipe = 14" From Table B, B = 2000

Example: Design (Test) Pressure = 150 PSI From Table A, T = 37320

= A =

5. Determine required bearing area (A) in sq. ft. as follows:

4. Determine Soil Bearing Capacity (B) of soil from Table B.

3. Determine Table Pressure from Table A.

2. Determine Design (Test) Pressure from Standard Specifications or Special Provisions.

1. Determine thrust (T) for type of fitting or joint and size of pipe from Table A.

(See Table C)

16"

14"

12"

10"

8"

6"

4"

48740

37320

27405

19045

12185

69245

53010

38940

27045

17310

37050

28370

20840

14480

19360

14815

10880

DIA.

PIPE

PSI

Pressure

Table

Ends

Dead

Tee &

Bend

90 deg

Bend

45 deg

Bend deg

22.5

Bend deg

11.25

D ECBA

Thrust (T) at fittings in Pounds

Soil Type

(B) in PSF

Soil Bearing Capacity

BLOCKING (HORIZONTAL)

CONCRETE THRUST

THRUST BLOCKING

VERTICAL BEND

CONVEX

TEE CROSS STRADDLE

TEECROSSBEND

WYE

TABLE A

(See Table C)

7. See project plans for details not shown.

(ASTM A615), Grade 60. Coat with coal tar epoxy after installation.

6. Stirrups shall be deformed galvanized cold rolled steel AASHTO M31

5. Keep concrete clear of all joints and accessories.

contact with concrete

4. Wrap pipe and/or fittings with 2 layers of polyethylene film where in

3. All concrete shall be commercial grade concrete.

2. Pour concrete blocking against undisturbed earth.

1. Contractor to provide blocking adequate to withstand full test pressure.

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

DIMENSION TABLE

16"

14"

12"

10"

8"

6"

4"

22.5

11.25

22.5

11.25

22.5

11.25

22.5

11.25

22.5

11.25

22.5

11.25

22.5

11.25

12.63

6.89

3.44

9.70

5.26

2.62

6.89

3.91

1.94

4.97

2.62

1.39

3.22

1.65

0.86

1.79

0.95

0.48

0.77

0.43

0.21

7.0

5.7

4.5

6.4

5.2

4.1

5.7

4.7

3.7

4.1

4.1

3.3

4.4

3.5

2.9

3.6

3.0

2.4

2.8

2.3

1.8

(in)

Embmt.

Stirrup

Bar

Stirrup

(in)

Dia.

Stirrup

(ft)

Size

Cube

(cy)

Volume

Concrete

(deg)

Angle

Bend

PSI

Pressure

Table in.

DIA.

PIPE

CONVEX VERTICAL BENDS

CONCRETE BLOCKING FOR

TABLE C

the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2026 - May 31, 2027

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

Standard Drawing, while

The selection and use of this

RD300

INSTALLATIONS

PIPE ZONE AND MULTIPLE

TRENCH BACKFILL, BEDDING,

R D

.d g n

14-JUL-2014N/A

J U

L

C

"A" note 4)

(See general

Tracer wire

MULTIPLE INSTALLATIONS

DIAMETER MIN. SPACE BETWEEN PIPES

(in)

"A"

(in)

"B"

(in)

"C"

(in)

"D"

TABLE A

Finish grade stabilization, as required

Trench foundation see Table A

"C" Pipe bedding, Top of subgrade as directed

Topsoil or existing material

Surfacing-match

Base material m a te r ia l

E x c a v a te d n a ti v e

C la s s A c r u s h e d r o c k

C la s s B o r m a x

1 ( c le a n s a n d

C la s s C

A s d ir e c te d m a te r ia l m a x

C la s s D p it o r b a r r u n

C L

S M

C la s s E

T re n c h b a c k fi ll a re a P ip e z o n eS e e T a b le

A

D

Nom."B" "B"

Pipe diameter

24" min.

m in

D ia

Up to 48"

48" to 72"

24"

) dia. of pipe2

One half (

4. See Std. Dwg. RD336 for tracer wire details (When required).

3. Pipes over 72" diameter are structures, and are not applicable to this drawing.

diameter.

used and the pipe is ≥ 36" diameter, increase dimension "B" to nominal pipe

2. For pipe installation in embankment areas where the trench method will not be

1. Surfacing of paved areas shall comply with street cut Std. Dwg. RD302.

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

see general note 3.

For pipes over 72" diameter, the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2025 - May 31, 2026

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

RD302

STREET CUT

R D

.d g n

20-JUL-2020N/A

J U

L

(Actual)

Trench width whichever is greater. Compact as specified.

4. Place AC mix minimum thkn. of 6" or the thkn. of the removed pavement, details.

3. For joining new concrete to existing concrete, see contract plans for sepecific or to the thickness of removed pavement, whichever is greater.

2. Concrete pavement shall be replaced with concrete to a minimum thickness of 8"

1. All existing AC or PCC pavement shall be sawcut prior to repaving.

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

(AC patch only) with tack material and sand

Seal surface over joint concrete as specified

CLSM or full depth asphalt

Compacted aggregate base, backfill as specified

Compacted trench

(Extg.)

Undisturbed base

Extg. pvmt.

see general notes

Pvmt. replacement, min.

6" min.

6"

Min. width=Roller width plus 2" m in

Tack coat cut edges (AC only) the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2025 - May 31, 2026

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

RD335

R D

.d g n

21-JUN-2019N/A

J U

L

(See general note 5)

24" max.

MANHOLE WITH PRECAST CONICAL TOP

MANHOLE WITH PRECAST FLAT SLAB TOP

6. All connecting pipes shall have a tracer wire, or approved alternate.

5. Adjust 24" maximum.

4. See Std. Dwg. RD344 for manhole base section.

3. See Std. Dwg. RD345 for pipe to manhole connections.

the Engineer.

2. Standard precast manhole section diameter shall be 48". Use 42" if specified by

1. All precast products shall conform to requirements of ASTM C478.

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

12. Location, elevation, diameter, slope, and number of pipe(s) varies, see project plans.

11. See Std. Dwg. RD342 for shallow manholes.

10. Max. pipe diameter varies with pipe material.

9. See Std. Dwg. RD356 for manhole covers and frames, manhole adjustment rings, etc.

8. See Std. Dwg. RD336 for details not shown.

7. See Std. Dwg. RD336 for manhole steps.

plastic or rubber ring to form a watertight seal sealed with non-shrink grout, preformed

Frame and precast grade ring(s) shall be

(See Details "B" & C" on Std. Dwg. RD336)

See general note 7, if steps are not required.

specified. Concentric cone may be used

Provide manhole steps unless otherwise to form a watertight seal grout, preformed plastic or rubber ring

All joints shall be sealed with non-shrink

Joint type varies with manufacturer (Typ.)

(See Detail "A" on Std. Dwg. RD336)

Tracer wire, (See general note 10)

Pipe (Typ.)

(Precast base shown)

Manhole base

Base rock

"/ft. min.2 slope varies:

Concrete bench, (As required)

Precast riser(s) conical top

Precast on Std. Dwg. RD336)

(See Detail "A"

Tracer wire, (As required)

Adjustment ring(s)

Manhole cover and frame

Finish grade

(As required)

Precast grade ring(s)

(See general note 5)

24" max.

Varies (12" max.)

25"

(42" if specified)

48"

(See general note 3)

Pipe connection varies (Typ.)

T y p m in m in

25"

Manhole cover and frame

Finish grade

(As required)

Precast grade ring(s) on Std. Dwg. RD336)

(See Detail "A"

Tracer wire, on Std. Dwg. RD336)

(See Detail "A"

Tracer wire, (As required)

Adjustment ring(s)

Varies (12" max.)

Precast flat slab top

Precast riser(s) (As required)

STORM SEWER MANHOLE

STANDARD

the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2025 - May 31, 2026

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

RD336

MANHOLE DETAILS

STANDARD

R D

.d g n

16-JAN-2019N/A

J U

L

X m in

Manhole cover and frame

Finish grade

(Typ.)

tracer wire fastener for

Non corrosive

Tracer wire

18" above top of manhole cover

Leave enough free wire to extend

Coil and secure wire to fastener.

precast flat slab top)

(See Std. Dwg. RD335 for

Precast conical top shown

Tracer wire

(As required) ring(s)

Precast grade

(As required)

Adjustment ring(s)

Place tracer wire directly over pipe centerline and on top of the pipe zone material.

6. All connecting pipes shall have a tracer wire, or approved alternate.

5. Adjust 24" maximum.

4. See Std. Dwg. RD344 for manhole base section.

3. See Std. Dwg. RD345 for pipe to manhole connections.

Engineer.

2. Standard precast manhole section diameter shall be 48". Use 42" if specified by the

1. All precast products shall conform to requirements of ASTM C478.

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

12. See project plans for details not shown.

11. See Std. Dwg. RD342 for shallow manholes.

10. Max. pipe diameter varies with pipe material.

9. See Std. Dwg. RD356 for manhole covers and frames, manhole adjustment rings, etc.

8. See Std. Dwg. RD335 for details not shown.

See Detail "C" for alignment of steps, and manhole cover and frame.

When H=42" or less omit steps.

7. Steps shall conform to requirements of ASTM C478.

and frame

Manhole cover Finish grade

Lowest flow line outfall pipe), or as directed.

azimuth right from lowest

See plans for X (measured

Manhole steps

(Align with steps)

Manhole cover and frame

Lowes tou tfal lpip e m a x s p a c in g

H v a r

"8

6"

13" to 16"

Var.

13" to 16"

Var.

(See general note 6) (See general note 7)

NOTE: No conflict with pipe align with available shelf.

See ODOT's QPL for acceptable alternate manhole steps.

(See general note 7)

TRACER WIRE

DETAIL "A"

MANHOLE STEPS

DETAIL "B"

AND MANHOLE STEPS ORIENTATION

PRECAST FLAT SLAB TOP

OR

PRECAST CONICAL TOP

DETAIL "C"

FRONT SIDE

PLAN

PLAN

the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2025 - May 31, 2026

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

RD339

CONNECTIONS

PIPE TO STRUCTURE

R D

.d g n

REVISED NOTES07-2021

20-JAN-2023N/A

J A

N

PLAN PLAN

grout

Non-shrink

(See general note 5)

Tracer wire

(See general note 1)

Sump shown

(typ.)

grout

Non-shrink

(See general note 5)

Tracer wire (Typ.)

(See general note 1)

Sump shown

(See general note 5)

Tracer wire (Typ.)

(See general note 7)

Pipe zone (Typ.)

(See general note 7)

Pipe zone (Typ.)

(See general note 6)

Resilient connector

(See general note 5)

Tracer wire

(See general note 1)

Sump shown

(See general note 1)

Sump shown

(See general note 6)

Resilient connector (Typ.)

(See general note 5)

Tracer wire (Typ.)

(See general note 7)

Pipe zone (Typ.)

(See general note 7)

Pipe zone (Typ.)

(See general note 5)

Tracer wire (Typ.)

(See general note 6)

Resilient connector (Typ.)

CONNECTION OF FLEXIBLE PIPE TO STRUCTURECONNECTION OF RIGID PIPE TO STRUCTURE

SECTION C-CSECTION D-DSECTION A-ASECTION B-B

B

B

A A C C

D

D

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

7. Pipe zone varies, see Std. Dwg. RD300.

6. When flexible pipe is used, install resilient connectors conforming to requirements of ASTM C923.

See Std. Dwg. RD336 for tracer wire details.

5. All connecting pipes shall have a tracer wire, or approved alternate.

4. Maximum pipe diameter varies with pipe material.

3. Location, elevation, diameter, slope, and number of pipe(s) varies, see project plans.

2. See appropriate standard drawings or special project details for other similar structures.

1. See Std. Dwgs. RD364, RD365, and RD366 for inlet details not shown.

04-2022 REVISED NOTES

01-2023 REVISED DETAILS AND NOTES

(typ.)

grout

Non-shrink

(typ.)

grout

Non-shrink the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2025 - May 31, 2026

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

RD344

BASE SECTION

STANDARD MANHOLE

R D

.d g n

14-JUL-2014N/A

J U

L

(For invert channel details, see precast option at right)

PRECAST MANHOLE BASECAST IN PLACE MANHOLE BASE

SECTION B-BSECTION A-A

A A B B

(See general note 11)

Tracer wire, 12" cc max.

#3 bars, 1 - #4 Hoop (Both ways)

#4 bars, 12" cc undisturbed material

Pour concrete against

2"

Joint type as required

(See general note 11)

Tracer wire, 2 - #4 hoops bottom half of pipe

Shape channel to match

(See general note 2)

Channel

(42" if specified)

48" 8" m in

(See general note 11)

Tracer wire (Typ.)

8"

4" 3 - #4 hoops the contractor at the option of be round or octagonal, Outside of base may

Lap 10'' unless otherwise shown.

clear of nearest face of conc., All reinforcement shall be 2"

48" (42"ifspecified)

(Both ways)

#4 bars, 12" ctr. ctr.

12" ctr. ctr. max.

#3 bars, (T y p

(42" if specified)

48"

INVERT CHANNEL

min.

8" bottom half of largest pipe

Shape channel to match

(See general note 2)

Channel

(See general note 11)

Tracer wire, 6" min.

note 12

See general

"/ft. min.2 slope varies:

Concrete bench, (See general note 11)

Tracer wire, Base rock transition sections.

uniform flow lines with gradual

Construct invert channels to and/or riser(s).

May occur in manhole base section

As measured at inner manhole wall.

(See general note 11)

Tracer wire (Typ.)

m in b etw een

(T yp p ip e p en etratio n s

Pipe(s) may extend 2" max. beyond the interior manhole wall.

6. Extend pipe into manhole and grout smooth.

5. Use on 42" and 48" diameter manhole.

4. Max. pipe diameter varies with pipe material.

3. Bases may be precast or cast in place.

2. Channels shall be constructed to provide smooth slopes and radii to outlet pipe.

1. All concrete shall be commercial grade concrete.

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

12. At spring line of pipe, extend channel up to crown line on 12:1 batter.

11. See Std. Dwg. RD336 for tracer wire details.

10. See Std. Dwg. RD336 for manhole steps details.

9. See Std. Dwg. RD345 for pipe to manhole connections.

8. All precast products shall conform to the requirements of ASTM C478.

plans.

7. Location, elevation, diameter, slope, and number of pipe(s) varies, see project

PLANPLAN

the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2025 - May 31, 2026

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

RD345

CONNECTIONS

PIPE TO MANHOLE

R D

.d g n

REVISED DETAILS AND NOTES01-2023

20-JAN-2023N/A

J A

N

CONNECTION OF RIGID PIPE TO MANHOLE

SECTION A-A

SECTION B-B

B

B

PLAN

A A

SECTION B-B

SECTION A-A

B

A A

B

PLAN

(See general note 6)

Tracer wire slope var. (See general note 7)

Concrete invert channel, slope var. (See general note 7)

Concrete invert channel, (See general note 6)

Tracer wire (Typ.)

(See general note 14)

Pipe zone (Typ.)

(See general note 14)

Pipe zone (Typ.)

slope var. (See general note 7)

Concrete invert channel, (See general note 6)

Tracer wire (Typ.)

Grout (Typ.)

Non-shrink

"/ft. min.2 slope var.

Concrete bench, "/ft. min.2 slope var.

Concrete bench, "/ft. min.2 slope var.

Concrete bench, slope var. (See general note 7)

Concrete invert channel, slope var. (See general note 7)

Concrete invert channel, (See general note 6)

Tracer wire

"/ft. min.2 slope var.

Concrete bench, (See general note 8)

Resilient connector

"/ft. min.2 slope var.

Concrete bench, (See general note 8)

Resilient connector (Typ.)

(See general note 6)

Tracer wire (Typ.)

(See general note 8)

Resilient connector (Typ.) slope var. (See general note 7)

Concrete invert channel, (See general note 6)

Tracer wire (Typ.)

(See general note 14)

Pipe zone (Typ.)

(See general note 14)

Pipe zone (Typ.)

"/ft. min.2 slope var.

Concrete bench, Pipe zone varies, see Std. Dwg. RD300.14.

manhole adjustment rings, etc.

See Std. Dwg. RD356 for manhole covers and frames,13.

See Std. Dwg. RD344 for manhole base section.12.

See Std. Dwg. RD342 for shallow manholes.11.

See Std. Dwg. RD336 for manhole steps details.10.

not shown.

See Std. Dwgs. RD335, RD336, and RD338 for details9 .

conforming to requirements of ASTM C923.

When flexible pipe is used, install resilient connectors8.

slopes and radii to outlet pipe.

Invert channels shall be constructed to provide smooth7.

details.

approved alternate. See Std. Dwg. RD336 for tracer wire

All connecting pipes shall have a tracer wire, or6.

Maximum pipe diameter varies with pipe material.5.

pipe(s) varies, see project plans.

Location, elevation, diameter, slope, and number of4.

All concrete shall be commercial grade concrete.3.

Manhole base sections may be precast or cast-in-place.2.

ASTM C478.

All precast sections shall conform to requirements of1.

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

CONNECTION OF FLEXIBLE PIPE TO MANHOLE

Grout (Typ.)

Non-shrink

Grout (Typ.)

Non-shrink the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2025 - May 31, 2026

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

8. See ODOT's QPL for alternate bolt-down products.

to bicycle or pedestrian use.

subject7. Manhole grate allowed only in locations not rings.

6. See ODOT's QPL for alternate manhole adjustment adjustment.

5. See Std. Dwg. RD360 for manhole frame

4. See Std. Dwg. RD336 for manhole steps.

origin.

manufacturer's initials, heat number and point of

3. Covers and frames shall be stamped with may be submerged (no holes).

2. Watertight covers required if located where cover holes maximum.have two easement areas. Covers for sanitary manholes shall drain manhole where located in pedestrian ways or

Tamperproof covers required on sanitary or storm1.

A A

PLAN

pavement, concrete gutter or walk.

frame is to be placed in concrete, Coat outside of frame with asphalt where

NOTE:

COVER SECTION A-A

FRAME SECTION A-A

"4

6" "4 3 1"

"4

2"

"4

"4

"4

2"

"8

"4

1 2 note 4.

of 20 feet or greater. See general required for mannholes with depths

*36 inch minimum diameter cover is

"4

"4

"4

"4

COVER AND FRAME

STANDARD MANHOLE

" clearance8

"4

25" (*36") " min.2 m in

"4

"4

"4

23"

"2

" chamfer8 m a x all around to a true bearing to be machined

Cover and frame

PLAN

frame. See general note 7.

For use with standard manhole

NOTE:

BB

SECTION B-B

bearing on frame around for true

Machine finish all

STANDARD MANHOLE GRATE

"4

17"

"4

"4

ADJUSTMENT RING

MANHOLE

For use with Standard Manhole Frame

SECTION C-C

PLAN

C C bearing all around

Machine to true mastic sealant

" preformed8 non-machined surfaces to be ±0.06". See general note 6 grey cast iron ASTM A48, Class 35B. Tolerance on

" and 3". Material to be2

", 2", 22

* Standard depths 1 designation heat number initials and

Manufacturer's

1" 1"

27"

23"

"4

7 "

25"

E

E

D D

Storm

PLAN

p ic k h o le

SECTION D-D

MANHOLE COVER AND FRAME

CAST IRON SUBURBAN

PLAN

SECTION E-E

AND WATERTIGHT COVER

CAST IRON TAMPERPROOF

Watertight for sanitary covers

2 holes maximum

Tamperproof, Down Detail

See Bolt

"4 or suburban pattern

Frames available in standard

BOLT DOWN DETAIL

See general note 8 so that one bolt boss is located over the manhole steps.

hexagonal head, bronze or stainless steel. Install frame

" pentagonal or2

"x12

Three required, equally spaced, NOTE:

m in m a x

26" min.

25" for details

Section A-A

See Cover 23"

"2

"4

For use on local streets only, as specified

For tamperproof and watertight covers tamperproof cover gasket, omit for

" neoprene4 cover

Manhole three required per cover stainless steel washer, " thick8

" OD x4 cover three required per

Flat rubber washer, 1"

Manhole frame maximum

Sanitary, 2 holes

RD356

AND FRAMES

MANHOLE COVERS

R D

.d g n

REVISED DETAILS AND NOTES07-2022

15-JUL-2022N/A

J U

L the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2025 - May 31, 2026

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

RD360

ADJUSTMENT

MANHOLE FRAME

R D

.d g n

21-JUL-2015N/A

J U

L wearing course

Asph. conc.

base course

Asph. conc.

(Or others listed in ODOT's QPL) as reqd.

Conc. manhole adjustment rings

(See general note 10)

Mortar 2" max.

See Alternate "A"

Raise as dir.

& frame

Manhole cover

C u t li n e

C u t li n e

Finish grade or hoop

#4 bar

" min. (Typ.)2

(Typ.)

3" min.

Thkn. - 2" min.

Asph. conc.

12" min.

Thkn. - 2" min.

Asph. conc.

12" min.

(Min. 12" thkn.)

P.C. concrete

Backfill with early strength

(Min. 12" thkn.)

P.C. concrete

Backfill with early strength

(Or others listed in ODOT's QPL) as reqd.

Conc. manhole adjustment rings

Raise as dir.

See Alternate "A"

(See general note 10)

Mortar 2" max.

or hoop

#4 bar

" min. (Typ.)2

(Typ.)

3" min.

12" min. 12" min.

Finish grade wearing course

Asph. conc.

base course

Asph. conc.

C u t li n e

C u t li n e

& frame

Manhole cover wearing course

Asph. conc.

base course

Asph. conc.

(Min. 12" thkn.)

P.C. concrete

Backfill with early strength

(Or others listed in ODOT's QPL) as reqd.

Conc. manhole adjustment rings

C u t li n e

C u t li n e

12" min. 12" min.

Finish grade & frame

Manhole cover

Raise as dir.

See Alternate "A"

(See general note 10)

Mortar 2" max.

(Typ.)

3" min.

" min. (Typ.)2 or hoop

#4 bar

- 2 each

#4 bar Cut line frame

Manhole cover & frame

Manhole cover &

Cut line

- 2 each

#4 hoop o f t r a v e l

D ir e c ti o n

12" min.

m in

(T yp

Manhole frame adjusment ring

Conc. manhole

Manhole note 10)

(See general

Mortar 2" max.

12. See Std. Dwg. RD356 for manhole covers and frames.

11. See Std. Dwg. RD336 for tracer wire details.

10. Use epoxy for synthetic grade rings.

9. See appropriate manhole standard drawings for details not shown.

8. See Std. Dwg. RD336 for manhole steps details.

7. Finish joint with asphalt seal and sand.

6. Apply tack coat to edges of existing pavement before installing patch.

5. Protect from traffic loading until conc. has cured to 3000 psi.

concrete.

4. Backfill with early strength Portland Cement Concrete. All concrete shall be commercial grade and leveling mortar, as shown.

3. Raise manhole cover and frame to finish grade by installing conc. manhole adjustment rings

2. Saw cut square or circular excavation around manhole 12" min. from manhole frame.

1. Cover manhole with building paper and const. asph. conc. base course and wearing courses.

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

SQUARE CUT

PLAN

CIRCULAR CUT

PLAN

METHOD "A"

METHOD "B"

METHOD "C"

ALTERNATE "A"

the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2026 - May 31, 2027

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

RD364

TYPE G-1, G-2, G-2M, & G-2MA

CONCRETE INLETS

R D

.d g n

21-JUL-2015N/A

J U

L

4" drain pipe

Base drain, m in

INLET TYPE W W

G-1

G-2, G-2M, G-2MA

"8 71'-8"8

72'-8

"8 33'-3 "8

32'-3

TYPE G-1, G-2, G-2M

TYPE G-2MA

WITHOUT SUMP

DETAIL A

TABLE A

SECTION A - A

SECTION B - B

SECTION C-C

C C

PLAN

PLAN

B

B

A A

(See general note 5)

Tracer wire when directed

Shape bottom m in (T y p

6" W

W

6" b r e a k

G r a d e

Finish grade

(See general note 9) when required

" preformed filler,4

Subgrade

(See general note 5)

Tracer wire

(See general note 11)

(Typ.)

Pipe connection varies

(See general note 3)

Sump

"2

(See general note 4)

Curb (Type var.)

Aggr. backfill n o r m a l

6"

V a r ie s

W6" 6"

W

Normal pavement slope

(See general note 2)

Frame & grate see inlet G-2

For details not shown, face of concrete unless shown or noted otherwise

All reinforcement to be placed 2" clear of nearest

NOTE:

#4 bars @ 6"

#4 bars "2

(See general note 2)

Frame & grate

6'-0"

"4

2'-46"

"4

3'-4

(See general note 10)

Pay limit for conc. inlet

6"

1'-6"

6"

V a r ie s m in

Top of curb

4" drain pipe (Typ.)

Base drain, (Typ.)

Aggr. backfill

Subgrade

(See general note 5)

Tracer wire (Typ.)

(See general note 11)

(Typ.)

Pipe connection varies

(See general note 3)

Sump normal

6"

(See general note 11)

(Typ.)

Pipe connection varies flow line

Depressed gutter flow line

Normal gutter

(Typ.)

Slope 1:12 nom.

(See general note 9) when required

" preformed filler,4

Top back of curb

Top face of curb

(Typ.)

Aggr. backfill

4" drain pipe (Typ.)

Base drain, (See general note 9) when required

" preformed filler,4

Concrete inlet

(See general note 2)

Frame & grate

(See general note 5)

Tracer wire (Typ.)

Normal gutter flow line

11. See Std. Dwg. RD339 for pipe to structure connections.

10. See Std. Dwg. RD363 for gutter transition section, when curb and gutter are required.

" preformed filler (in concrete pavement or gutter only) to extend through thickness of concrete.4

9.

8. All concrete shall be commercial grade concrete.

7. Location, elevation, diameter, slope, and number of pipe(s) varies, see project plans.

6. Max. pipe diameter varies with pipe material.

5. See Std. Dwg. RD336 for tracer wire details, or approved alternate.

4. For curb details, see Std. Dwgs. RD700 & RD701.

3. Provide sump only where shown on plans, and allowed by jurisdiction. See Detail A for inlet without sump.

For frame and grate details, see Std. Dwg. RD365.

Type 1 grate allowed only in locations not subject to bicycle or pedestrian use.

2. Graphics show G-1 inlet with Type 2 grate. See Table A for inlet dimensions.

crushed aggregate shall be provided. All precast inlets shall conform to requirements of ASTM C913.

"-04

1. Where precast inlets are used as an alternate to cast-in-place inlets, a 4" compacted leveling bed of sand or

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2025 - May 31, 2026

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

RD365

FOR CONCRETE INLETS

FRAMES & GRATES

R D

.d g n

14-JUL-2014N/A

J U

L all bars

Both ends "16

"4

4 corners "4 32'-4 h e x b a r o f e q u iv a le n t a r e a r o u n d r e c t.

o r

C r o s s b a r s h e x b a r o f e q u iv a le n t a r e a r o u n d r e c t.

o r

C r o s s b a r s flat bar each end

"2

"x28

"x2" or8

(Typ.)

" on center8 at 1

" flat bars2

"x28

Bearing bars

T y p ic a l a ll b a rs see general note 3

For cross bars, third inner bar and every outer bars both ends, Typical "16

"2

2" b a r s o n c e n te r s

1'-9"

(Bicycle-safe) edge flat bars

" sq.2

"x22

"8

1'-9

2 each end

"x3" bolt8 angle (Typ.)

"8

"x2

3"x2

"4

1'-10

"4

4 anchors

"4

4 corners

T y p

" (Typ.)2

2 each end

"x3" bolt8 5 "

2 each end

"x3" bolt8

(Typ.)

" on center8 at 1

" flat bars2

"x28

Bearing bars flat bar each end

"2

"x28

"x2" or8 see general note 3

For cross bars, third inner bar and every outer bars both ends, Typical

"2

2T y p ic a l a ll b a rs

3 "16

2'-3"

"2

1'-1 "2

1'-1 b a r s o n c e n te r s

(2 grates required per inlet, as shown)

(Bicycle-safe)

2"

2 each end

"x3" bolt8

"8

2'-3 edge flat bars

" sq.2

"x22 angle (Typ.)

"8

"x2

3"x2

"4

4 anchors

" (Typ.)2

T y p

(Typ.)

sq. edge flat bar

"2

"x28

"2

(Typ.)

sq. edge flat bars

"4

"x2'-62

"x28

Bearing bars

"2

"2

2'-3"

Spacing 3" O.C.

(See general note 2)

5. Cast iron grate and frame are acceptable alternates. See ODOT's QPL.

4. Hot dip galvanize after fabrication.

resistance welded or electroforged to bearing bars.

" cross bars shall be flush with the top of grate surface and may be fillet welded,8

3.

2. Type 1 grate allowed only in locations not subject to bicycle or pedestrian use.

1. For inlet details, see appropriate inlet standard drawing(s).

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

(TYPE 1)

G-2, G-2M, G-2MA, CG-2 GRATE

(TYPE 2)

G-2, G-2M, G-2MA, CG-2 GRATE

(TYPE 2)

G-1, CG-1 GRATE

G-1, CG-1 FRAME G-2, G-2M, G-2MA, CG-2 FRAME

the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2026 - May 31, 2027

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

RD371

TYPE CG-3

CONCRETE INLET BASE

R D

.d g n

21-JUL-2015N/A

J U

L

KEYWAY DETAIL PLAN

PAY LIMIT

SECTION B - B SECTION A - A

B

B

A A

PLAN

(See general note 5)

Curb and gutter

(See general note 3)

Inlet top note 4)

(See general

Tracer wire

(When reqd.)

Detail below

See Keyway

6" rad.

note 10)

(See general varies (Typ.)

Pipe connection

(See general note 7)

Sump

(See general note 4)

Tracer wire see general note 6)

(When reqd., Base drain (Typ.)

(See general note 5)

Curb and gutter

(See general note 10)

(Typ.)

Pipe connection varies

(See general note 7)

Sump

2'-0"6" 6"

V a r ie s

3'-0"

6" 2'-6"

3'-6"

V a r ie s

(See general note 3)

Inlet top

(When reqd.)

See Keyway Detail below

Subgrade

V a r ie s

6"

C u r b b a tt e r

Gutter line

Lip of gutter

Top back of curb

Top face of curb

Top of curb

3'-0" 3'-6" 3'-0"

Pay limit for concrete inlet curb & gutter

Pay limit curb & gutter

Pay limit

3'-6"

2'-6"6" 6"

S e e g e n e r a l n o te

C u r b a n d g u tt e r

(See general note 4)

Tracer wire

Gutter line

Lip of gutter

Top face of curb

C u r b b a tt e r

Top of curb

Top back of curb6"

"2

2 "2

1"

10. See Std. Dwg. RD339 for pipe to structure connections.

9. Max. pipe diameter varies with pipe material.

8. Location, elevation, diameter, slope, and number of pipe(s) varies, see project plans.

For sump details, see Std. Dwg. RD364.

7. Provide sump only where shown on plans, and allowed by jurisdiction.

6. See Std. Dwg. RD364 for base drain details.

5. See Std. Dwgs. RD700 & RD701 for curb and gutter details.

4. See Std. Dwg. RD336 for tracer wire details, or approved alternate.

3. See Std. Dwgs. RD372 & RD373 for inlet top details.

All precast inlets shall conform to requirements of ASTM C913.

"-0 crushed aggregate shall be provided.4 a 4" compacted leveling bed of sand or

2. Inlet base may be cast-in-place or precast. Where precast inlet base is used as an alternate,

1. All concrete shall be commercial grade concrete.

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2026 - May 31, 2027

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

RD372

OPTION 1, TYPE CG-3

CONCRETE INLET TOP

R D

.d g n

16-JAN-2019N/A

J U

L

E and cover (See general note 8)

" rise)2 adjustment ring (With 1

Cast iron manhole manhole adjustment ring)

#6 bars (Both ways, under

E

E

M in

.3

#3 bars

Gutterline

Bottom ofcurb&gutter

#3 bars

Gutterline

(Typ.)

bolt, with nut, galv.

"x12" anchor2

Bottom ofcurb&gutter

(When reqd.)

See Keyway Detail

"2

8"2

2'-6"

3'-6"

6" 6"

E

3"

E

6" 2'-0"

3'-0"

6"

V a r ie s manhole adjustment ring)

#6 bars (Both ways, under and cover (See general note 8)

" rise)2 adjustment ring (With 1

Cast iron manhole

Normalgutterline

"16

(When reqd.)

See Keyway Detail

2 - #6 bars)

(Under the

#4 hoop bar bolt, with nut, galv. (Typ.)

"x12" anchor2

#3 bars #3 bars

2%

B a tt e r :1 manhole adjustment ring)

#6 bars (Both ways, under

2 - #6 bars)

(under the

#4 hoop bar and cover (See general note 8)

" rise)2 adjustment ring (With 1

Cast iron manhole

Top back of curb

Top of curb

Top face of curb

Gutter line

C u r b b a tt e r

#3 bars

(Typ.)

6" rad.

(Typ.)

" rad.4

(Typ.)

bolt, with nut, galv.

"x12" anchor2

S e e g e n e r a l n o te

C u r b a n d g u tt e r

" "2

1"

6"

"2

18" (Min.)

(Bend at midway to match gutter pan) structure into gutter pan, #3 bars, project 18" (Min.) beyond

(Bend at midway to match gutter pan)

#3 bars, project 18" (Min.) beyond structure, 2 - #6 bars)

(Under the

#4 hoop bar

Top face of curb

Normal gutter line

(See SECTION B-B) structure into gutter pan, #3 bars, project 18" (Min.) beyond

KEYWAY DETAIL

PLAN

SECTION A - A SECTION B - B

B

B

A A

8. See Std. Dwg. RD356 for cast iron manhole adjustment ring and cover.

7. See Std. Dwgs. RD700 & RD701 for curb and gutter details.

6. See Std. Dwg. RD371 for inlet pay limit.

5. See Std. Dwg. RD371 for inlet base details.

7 below).

4. Vary anchor bolt length and reinforcing bar placement as required by curb exposure E (See note

3. All reinforcement shall be 2" clear of nearest face of conc., unless otherwise shown.

ASTM C913.

2. Inlet top may be cast-in-place or precast. All precast inlets shall conform to requirements of

1. All concrete shall be commercial grade concrete.

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2026 - May 31, 2027

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

RD700

CURBS

R D

.d g n

20-JUL-2020N/A

J U

L

6"

E specify in plans

Var. 24" or 30"

6"

E

" rad.4

Batter 6:1

" rad.4 seegutterpan notes

Slopevaries, T y p

2" (Typ.)

(See general note 11)

STANDARD CURB MOUNTABLE CURB

CURB ENDING DETAIL

MOUNTABLE CURB AND GUTTERCURB AND GUTTER

MOUNTABLE CURB

LOW PROFILE MODIFICATION FOR KEYWAY

WEEP HOLE DETAIL

VALLEY GUTTER

O.D.O.T. & City of Portland Standard "H"=16"

" rad.4

1:4slope

6:1

Batter

(Slope var.)

Finish grade seegutterpan notes

Slopevaries, 12"

LOW PROFILE MOUNTABLE CURB AND GUTTER

" rad.4 or specifiy in plans

18" norm.

a s d ir e c te d o n p la n s o r v a r y a s s h o w n

(Where shown on plans)

** 0" at curb ramp n o r m

1.5' 4.5'

6'

Face of curb

"2

R

1 " to joint filler (Full depth)

Preformed expansion

Asph. conc. pvmt. (ACP)

Grade of roadway upon extension of curb.

To be removed

(Slope var.)

Finish grade

" rad.4

Batter 6:1

" rad.8 m in

H v a ri a b le

E

(See general note 11)

6"

E

(See general note 11)

3" rad.

(Slope var.)

Finish grade

Batter 6:1

(Slope var.)

Finish grade m in

Batter 6:1

3" rad.

3" rad.

" rad.8

(Slope var.)

Finish grade

Batter 6:1 allowed by jurisdiction.

Vary where shown on plans, and

Vary slope as reqd. for drainage.

Slope 4.0% max. at curb ramps.

Slope 5.0% normal.

GUTTER PAN NOTES:

specify in plans

Var. 24" or 30"

6"

6" Normal curb

V a r

E seegutterpan notes

Slopevaries, Slop evar.

(1:4 max.)

Top of curb " (Max.)4

Bottom of curb

Gutter line

Batter 6:1 for each 1" difference in ''E''.

having a slope of 1:1 or steeper). Minimum desirable transition length shall be 20'

(''E'' Is the total vertical dimension of those curb surfaces

4. Transitions shall be used to connect curbs of different exposures ''E''.

3. Const. curb contraction joints at 15' maximum spacing, and at ends of each inlet and curb ramp.

ends of each driveways.

2. Const. curb expansion joints at 200' maximum spacing, and at points of tangency, and at curb. Vary as shown on plans or as directed. O.D.O.T standard "E"=7".

1. Curb exposure ''E'' = 6" to 9", as measured vertically from flowline to highest point on

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

or as directed as shown on plans

8" norm., vary

(Slope var.)

Finish grade

" rad.4 3" rad.4

1:4slope

* 0" for Truck Apron thkn. (4" min.)

Future sidewalk be poured at the same time curb and sidewalk will not

Form shelf into curb when

2"

(Type var.)

curb and gutter

Curb, or

(Where req'd.)

3" PVC pipe, (Type var.)

curb and gutter

Curb, or weep hole

3" dia.

(Slope var.)

Finish grade

5%

(Where shown on plans, and allowed by jurisdiction)

(Where shown on plans)

Var.

V a r

12"

(Slope var.)

Finish grade

20"

40"

20"

" rad.4

#4 @ 12" centers (Slope var.)

Finish grade

" rad.4

T y p .)centers

#4 @ 7"

6"

"8

1 "8

" rad.8

" rad.8

(Finishedsurface)

5.0%

(Finishedsurface

5.0%

11. On or along state highways, curb and gutter is required at curb ramp.

10. For curb ramp details, see Std. Dwgs. RD900 series.

9. For drainage curbs, see Std. Dwg. RD701.

8. For sidewalk details, and monolithic curb & sidewalk, see Std. Dwgs. RD720 & RD721.

7. Dimensions adjacent to radii are measured to the point of intersection of curb surfaces.

6. Dimensions are nominal, vary to conform with curb machine approved by the engineer.

surface slope), unless otherwise shown, or as directed.

5. Tops of all curbs shall slope toward the roadway at 1.5% max. (Max. 2.0% finished the current Oregon Standard Specifications.

All materials shall be in accordance with

DATE REVISION DESCRIPTION

OREGON STANDARD DRAWINGS

DATE

SDR

BOOK NO.

CALC.

Effective Date: December 1, 2026 - May 31, 2027

Professional Engineer.

first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with

File details come from the government source that posted it. Updated .