OCS DRAHNER SCS FLOOR PLANS.pdf
PDF 2 MB Posted
- Solicitation number
- RFP - OXFO - 240000000577
- Issued by
- Oakland County, Onekama Village, Michigan
About this file
The document provided is a set of floor plans related to the Oxford Schools Drahner Rd. building structured cabling contract opportunity in the state of Michigan, specifically within the jurisdictions of Oakland County and Onekama Village. The plans detail the communications cabling layout, including the placement of data outlets, WAP locations, and other infrastructure. The contract involves the installation of the structured cabling system for this facility. The bidding deadline is 12/5/2023, with an owner review scheduled for 11/20/2023. The contract term and any potential renewal options are not specified in the provided information.
The pricing terms, set asides, incumbents, funding requirements, and other salient financial details are not included in the document. The document focuses on the technical specifications and layout of the communications cabling infrastructure for the Oxford Schools Drahner Rd. building.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| OCS Drahner Cable RFP.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S
S
S
S
S
S
S
S
G
T X
WVUQPML
COMMERCIAL
LAUNDRY
B003
DRYER
EXH.
ROOM
B019
B002
ELEVATOR
EQUIP.
STAIR
A0
CLEAN
LINEN
B004
OFFICE
B006
B001
CORRIDOR
B018
MECHANICAL/
ELECTRICAL
LAUNDRY
B015
B016A
RESTROOM
RESTROOM
B016
JAN
B017
B009A
CLASSROOM
B014
CLASSROOM
STORAGE
B012
STORAGE
B010
STORAGE
B011
STAIR
B0
B001
CORRIDOR
LPA
LPEA
EMDPTRANSFER SWITCH
MSBD
B009B
SENSORY
AREA
B007
CLASSROOM
LPA-27
(R)
(R)
(R)
(R)
(R)
DP- 1
ELEVATOR
STORAGE
B013
STORAGE
B009
(R)
(R)
ALUMINUM POWER
POLE WITH (4) DUPLEX
RECEPTACLES AND
(4) DATA OUTLETS
CR
CR
MDF
0' 5' 10' 20' 30' 40' 50'
NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS
WAP
2D
1D
2D
2D
1D FUTURE SPKR
2D
2D
1D FUTURE SPKR
2D
1D WAP
4D4D
1D WAP
BASEMENT
FLOOR BOX - DATA, QTY
AS SHOWN
CEILING (WAP) DATA OUTLET -
TERMINATE IN SURFACE BOX
OUTLET - DATA, QTY AS
SHOWN
INSTALL COMMS CABINET,
CABINET BY OTHERS
COMMUNICATIONS
SYMBOLS
WALL PHONE (1) DATA
CEILING (CAMERA) DATA OUTLET
TERMINATE IN SURFACE BOX
12/5/2023 BIDDING EGH
11/20/2023 OWNER REVIEW EGH
DATE ISSUE AUTHOR
OCS DRAHNER
FACILITY
COMMUNICATIONS CABLING
T-100
C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473
Phone: 810.720.3820 www.ctpartners.net
T E C H N O L O G Y P A R T N E R S
TECHNOLOGY DESIGN I CONSULTING I PLANNING
KEYPLAN
LV CABLING NOTES
1. CABINETS PROVIDED BY OWNER, INSTALLATION BY
CONTRACTOR. PROPERLY FASTEN TO FLOOR, GROUND
AND BOND. PROVIDE CABLE SUPPORT TO CABINET WHEN
NOT ADJACENT TO WALL.
2. FIRE-STOP ALL PENETRATIONS TO MATCH FIRE RATING OF
PENETRATED PARTITION.
3. GROUND ONE END ONLY OF ARMORED FIBER OPTIC CABLE.
4. PROVIDE 10' SERVICE LOOP IN ALL CABLES TERMINATED IN
MDF OR IDFS. NEATLY COIL AND FASTEN TO STRUCTURE
ALL SERVICE LOOPS.
5. TERMINATE ALL UTP CABLE AT WAO ENDS WITH 8P/8C
(RJ45) JACKS IN FACEPLATES OR SURFACE HOUSINGS
WHEN IN CEILINGS - FASTEN SURFACE BOXES TO
STRUCTURE.
6. PROVIDE SUFFICIENT SERVICE LOOP IN UTP SPEAKER
CABLE TO ALLOW PLACEMENT OF SPEAKERS ANYWHERE
IN ROOM.
7. SPEAKERS AND WAPS BY OTHERS
8. PROVIDE 5M OF SERVICE LOOP AT EACH WAP OUTLET
LOCATION IN CEILINGS.
9. NEATLY COIL AND FASTEN TO STRUCTURE ALL WAO
SERVICE LOOPS IN CEILINGS AT OUTLET.
10. COORDINATE ALL CABLE PULLS, PENETRATIONS AND
OUTLET LOCATIONS WITH OTHER TRADES AND OWNER.
S
S
S
S
S
S
S
S
T X Y Z
H I J N O S
MATCH LINE
E3.1A E3.1B
MATCH LINE
E3.1A E3.1B
COMMUNITY
ROOM
STORAGE
STORAGE
STORAGE
STORAGE
STAIR
A1
RECEIVING/
LOADING
DOCK
CIRCULATION
PARENT
ROOM
KITCH.
STOR.
DISH
WASHING
CAFETERIA
KITCHEN
CAFETERIA
CHAIR
STORAGE
STAIR
D1
PPK
LPEDLPD
JAN.
SOUND
SYSTEM
(R)
(R)
(R)
(R)
MIC
(R)
(R)
(R)
(R)
(R)
(R)
SOUND
RACK
EXISTING
GENERATOR
EXISTING
DTE TRANSFORMER
PPK1
K
GARAGE
(R)
48" AFF
48" AFF
0' 5' 10' 20' 30' 40' 50'
NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS
1D WAP
1D WAP
1D WAP
1D FUTURE SPKR
1D
1D
W
W
FOR EXTERIOR
CAMERA
EXTERIOR
FOR CAMERA
FOR EXTERIOR
CAMERA
UNIT A
UNIT B
FLOOR BOX - DATA, QTY
AS SHOWN
CEILING (WAP) DATA OUTLET -
TERMINATE IN SURFACE BOX
OUTLET - DATA, QTY AS
SHOWN
INSTALL COMMS CABINET,
CABINET BY OTHERS
COMMUNICATIONS
SYMBOLS
WALL PHONE (1) DATA
CEILING (CAMERA) DATA OUTLET
TERMINATE IN SURFACE BOX
12/5/2023 BIDDING EGH
11/20/2023 OWNER REVIEW EGH
DATE ISSUE AUTHOR
C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473
Phone: 810.720.3820 www.ctpartners.net
T E C H N O L O G Y P A R T N E R S
TECHNOLOGY DESIGN I CONSULTING I PLANNING
OCS DRAHNER
FACILITY
COMMUNICATIONS CABLING
T-101A
KEYPLAN
LV CABLING NOTES
1. CABINETS PROVIDED BY OWNER, INSTALLATION BY
CONTRACTOR. PROPERLY FASTEN TO FLOOR, GROUND
AND BOND. PROVIDE CABLE SUPPORT TO CABINET WHEN
NOT ADJACENT TO WALL.
2. FIRE-STOP ALL PENETRATIONS TO MATCH FIRE RATING OF
PENETRATED PARTITION.
3. GROUND ONE END ONLY OF ARMORED FIBER OPTIC CABLE.
4. PROVIDE 10' SERVICE LOOP IN ALL CABLES TERMINATED IN
MDF OR IDFS. NEATLY COIL AND FASTEN TO STRUCTURE
ALL SERVICE LOOPS.
5. TERMINATE ALL UTP CABLE AT WAO ENDS WITH 8P/8C
(RJ45) JACKS IN FACEPLATES OR SURFACE HOUSINGS
WHEN IN CEILINGS - FASTEN SURFACE BOXES TO
STRUCTURE.
6. PROVIDE SUFFICIENT SERVICE LOOP IN UTP SPEAKER
CABLE TO ALLOW PLACEMENT OF SPEAKERS ANYWHERE
IN ROOM.
7. SPEAKERS AND WAPS BY OTHERS
8. PROVIDE 5M OF SERVICE LOOP AT EACH WAP OUTLET
LOCATION IN CEILINGS.
9. NEATLY COIL AND FASTEN TO STRUCTURE ALL WAO
SERVICE LOOPS IN CEILINGS AT OUTLET.
VC
C C
S
S
S
S
C
C
S
S
S
S
S
S
S
S
S
S
A B B1 D E G T X
WVUQPML
N O
MATCH LINE
E3.1A E3.1B
MATCH LINE
E3.1A E3.1B
STAIR
C1
OFFICE
130A
IDF
CORRIDOR
100C
OFFICE
130B
OFFICE
130C
OFFICE
130A
OFFICE
126A
OFFICE
126B
126C
MEETING
ROOM
126D
STORAGE
LOUNGE/
WORKROOM
CLASSROOM
MEETING
ROOM
112A
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
SECURITY
LOBBY
VESTIBULE
STAFF
TOILET
STAFF
TOILET
BOYS
133A
CIRCULATION
GIRLS
131A
CORRIDOR
100B
STUDENT
LOUNGE
OFFICE
OFFICE
117ASTAIR
B1
LPEC
LPC
117B
FILE
ROOM
WORKROOM
STORAGE
112B
OFFICE
125A
125B
SENSORY
ROOM /
SPECIAL
EDUCATION
CONDUIT
UP
IDF
RACK
RELOCATED
LPB
CR
ELEC.
132CR
CR
(R)
(R)
(R)
(R)
(R)
(R)
(R) (R)
OFFICE
130D
(R)
UNI.
RESTROOM
133B
UNI.
TOILET
131B
(R)
LPB-12
LPB-16
IRRIGATION
CONTROLLER
LPC-14
CR
JANITOR
CR
CR
FACP
INTERCOM
0' 5' 10' 20' 30' 40' 50'
NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS
1D FUTURE SPKR
1D WAP
1D FUTURE SPKR
1D WAP
1D WAP
1D WAP
2D
2D
2D
2D
2D
2D 2D
2D
2D
2D
1D 2D
2D 2D
2D
2D
1D
2D
2D
1D
1D
2D
1D FUTURE SPKR
1D FUTURE SPKR
1D FUTURE SPKR
1D
1D FUTURE SPKR 1D FUTURE SPKR
2D 2D
1D 1D
2D
2D 2D
2D
2D
1D FUTURE SPKR
4D
48" AFF
W
EXTERIOR
FOR CAMERA
EXTERIOR
FOR CAMERA
FOR EXTERIOR
CAMERA
UNIT A
UNIT B
FLOOR BOX - DATA, QTY
AS SHOWN
CEILING (WAP) DATA OUTLET -
TERMINATE IN SURFACE BOX
OUTLET - DATA, QTY AS
SHOWN
INSTALL COMMS CABINET,
CABINET BY OTHERS
COMMUNICATIONS
SYMBOLS
WALL PHONE (1) DATA
CEILING (CAMERA) DATA OUTLET
TERMINATE IN SURFACE BOX
T-101B
12/5/2023 BIDDING EGH
11/20/2023 OWNER REVIEW EGH
DATE ISSUE AUTHOR
C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473
Phone: 810.720.3820 www.ctpartners.net
T E C H N O L O G Y P A R T N E R S
TECHNOLOGY DESIGN I CONSULTING I PLANNING
OCS DRAHNER
FACILITY
COMMUNICATIONS CABLING
KEYPLAN
LV CABLING NOTES
1. CABINETS PROVIDED BY OWNER, INSTALLATION BY
CONTRACTOR. PROPERLY FASTEN TO FLOOR, GROUND
AND BOND. PROVIDE CABLE SUPPORT TO CABINET WHEN
NOT ADJACENT TO WALL.
2. FIRE-STOP ALL PENETRATIONS TO MATCH FIRE RATING OF
PENETRATED PARTITION.
3. GROUND ONE END ONLY OF ARMORED FIBER OPTIC CABLE.
4. PROVIDE 10' SERVICE LOOP IN ALL CABLES TERMINATED IN
MDF OR IDFS. NEATLY COIL AND FASTEN TO STRUCTURE
ALL SERVICE LOOPS.
5. TERMINATE ALL UTP CABLE AT WAO ENDS WITH 8P/8C
(RJ45) JACKS IN FACEPLATES OR SURFACE HOUSINGS
WHEN IN CEILINGS - FASTEN SURFACE BOXES TO
STRUCTURE.
6. PROVIDE SUFFICIENT SERVICE LOOP IN UTP SPEAKER
CABLE TO ALLOW PLACEMENT OF SPEAKERS ANYWHERE
IN ROOM.
7. SPEAKERS AND WAPS BY OTHERS
8. PROVIDE 5M OF SERVICE LOOP AT EACH WAP OUTLET
LOCATION IN CEILINGS.
9. NEATLY COIL AND FASTEN TO STRUCTURE ALL WAO
SERVICE LOOPS IN CEILINGS AT OUTLET.
S
S
S
S
S
S
S
T X Y Z
H I J N O S
MEETING
ROOM
IDF
STAIR
D2
OFFICE
217A
OFFICE
216A
DATA
DEN
216B
OFFICE
217B
OFFICE
217DOFFICE
216C
OFFICE
217E
STAFF
TOILET
217H
MEETING
ROOM
216D
STAIR
A2
MATCH LINE
E3.2A E3.2B
MATCH LINE
E3.2A E3.2B
217G
UNI. TOILET
217C
OFFICE
(R)
(R)
(R)
(R)
CR
CR
STORAGE
MECHANICAL
HALL
STORAGE
CORRIDOR
201D
IDF
RACK
4" CONDUIT
SLEEVE
PT1
PT1
PT1
LPH- 17
STORAGE
205A
201A
CENTRAL
CORRIDOR
CR
0' 5' 10' 20' 30' 40' 50'
NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS
2D
2D 2D 2D 2D
2D 2D
2D 2D
2D 2D
2D
2D
2D
2D
2D
2D
2D
2D
2D 2D
1D
2D
2D
2D
UNIT A
UNIT B
FLOOR BOX - DATA, QTY
AS SHOWN
CEILING (WAP) DATA OUTLET -
TERMINATE IN SURFACE BOX
OUTLET - DATA, QTY AS
SHOWN
INSTALL COMMS CABINET,
CABINET BY OTHERS
COMMUNICATIONS
SYMBOLS
WALL PHONE (1) DATA
CEILING (CAMERA) DATA OUTLET
TERMINATE IN SURFACE BOX
T-102A
12/5/2023 BIDDING EGH
11/20/2023 OWNER REVIEW EGH
DATE ISSUE AUTHOR
C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473
Phone: 810.720.3820 www.ctpartners.net
T E C H N O L O G Y P A R T N E R S
TECHNOLOGY DESIGN I CONSULTING I PLANNING
OCS DRAHNER
FACILITY
COMMUNICATIONS CABLING
KEYPLAN
LV CABLING NOTES
1. CABINETS PROVIDED BY OWNER, INSTALLATION BY
CONTRACTOR. PROPERLY FASTEN TO FLOOR, GROUND
AND BOND. PROVIDE CABLE SUPPORT TO CABINET WHEN
NOT ADJACENT TO WALL.
2. FIRE-STOP ALL PENETRATIONS TO MATCH FIRE RATING OF
PENETRATED PARTITION.
3. GROUND ONE END ONLY OF ARMORED FIBER OPTIC CABLE.
4. PROVIDE 10' SERVICE LOOP IN ALL CABLES TERMINATED IN
MDF OR IDFS. NEATLY COIL AND FASTEN TO STRUCTURE
ALL SERVICE LOOPS.
5. TERMINATE ALL UTP CABLE AT WAO ENDS WITH 8P/8C
(RJ45) JACKS IN FACEPLATES OR SURFACE HOUSINGS
WHEN IN CEILINGS - FASTEN SURFACE BOXES TO
STRUCTURE.
6. PROVIDE SUFFICIENT SERVICE LOOP IN UTP SPEAKER
CABLE TO ALLOW PLACEMENT OF SPEAKERS ANYWHERE
IN ROOM.
7. SPEAKERS AND WAPS BY OTHERS
8. PROVIDE 5M OF SERVICE LOOP AT EACH WAP OUTLET
LOCATION IN CEILINGS.
9. NEATLY COIL AND FASTEN TO STRUCTURE ALL WAO
SERVICE LOOPS IN CEILINGS AT OUTLET.
S
S
S
S S S
S
S
S
S
S
S
S
S
S
S
A B B1 D E G T X
WVUQPML
N O
MATCH LINE
E3.2A E3.2B
MATCH LINE
E3.2A E3.1B
201A
CENTRAL
CORRIDOR
HIGH
SCHOOL
CLASSROOM
MIDDLE
SCHOOL
CLASSROOM
OFFICE
OFFICE
209A
MEETING
207A
OFFICE
207B
OFFICE
209B
OFFICE
209D
OFFICE
207D
OFFICE
207C
OFFICE
209C
HALLWAY
201B
OFFICE
207F
OFFICE
209F
STAIR
B2
LOUNGE/
WORKROOM
IDF
OFFICE
209E
OFFICE
207E
210F
SENSORY
ROOM /
SPECIAL
EDUCATION
ELEC.
BOYS
OFFICE
211E
OFFICE
211D
OFFICE
210D
OFFICE
210E
OFFICE
210C
OFFICE
210B
OFFICE
210A
IDF
STAIR
C2
OFFICE
211A
LOUNGE/
WORKROOM
OFFICE
211B
OFFICE
211C
JANITOR
LPEG
LPG
LPH
(RELOCATED)
LPF
(RELOCATED)
RELOCATED
EAGLE SECURITY
PANEL
(R)
(R)
(R)
CR
(R)
CR
CR
CR
(R)(R)(R)
CORRIDOR
201C
4" SLEEVE
IDF
RACK
4" SLEEVE
IDF
RACK
CR
CR
CR
0' 5' 10' 20' 30' 40' 50'
NOT TO SCALE - BAR SCALE APPROXIMATE. FIELD VERIFY ALL DIMENSIONS
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
1D WAP 1D WAP
1D FUTURE SPKR
2D FUTURE SPKR
1D FUTURE SPKR
1D 2D
1D
2D
1D WAP
1D WAP
1D WAP
1D FUTURE SPKR
2D
1D2D
2D
2D
2D
2D
2D 2D
2D 2D
2D 2D 2D 2D
2D 2D2D 2D
2D2D 2D 2D
W
48" AFF
2D
UNIT A
UNIT B
FLOOR BOX - DATA, QTY
AS SHOWN
CEILING (WAP) DATA OUTLET -
TERMINATE IN SURFACE BOX
OUTLET - DATA, QTY AS
SHOWN
INSTALL COMMS CABINET,
CABINET BY OTHERS
COMMUNICATIONS
SYMBOLS
WALL PHONE (1) DATA
CEILING (CAMERA) DATA OUTLET
TERMINATE IN SURFACE BOX
T-102B
12/5/2023 BIDDING EGH
11/20/2023 OWNER REVIEW EGH
DATE ISSUE AUTHOR
C O N V E R G E N T 6197 Miller Road Suite 4 Swartz Creek, MI 48473
Phone: 810.720.3820 www.ctpartners.net
T E C H N O L O G Y P A R T N E R S
TECHNOLOGY DESIGN I CONSULTING I PLANNING
OCS DRAHNER
FACILITY
COMMUNICATIONS CABLING
KEYPLAN
LV CABLING NOTES
1. CABINETS PROVIDED BY OWNER, INSTALLATION BY
CONTRACTOR. PROPERLY FASTEN TO FLOOR, GROUND
AND BOND. PROVIDE CABLE SUPPORT TO CABINET WHEN
NOT ADJACENT TO WALL.
2. FIRE-STOP ALL PENETRATIONS TO MATCH FIRE RATING OF
PENETRATED PARTITION.
3. GROUND ONE END ONLY OF ARMORED FIBER OPTIC CABLE.
4. PROVIDE 10' SERVICE LOOP IN ALL CABLES TERMINATED IN
MDF OR IDFS. NEATLY COIL AND FASTEN TO STRUCTURE
ALL SERVICE LOOPS.
5. TERMINATE ALL UTP CABLE AT WAO ENDS WITH 8P/8C
(RJ45) JACKS IN FACEPLATES OR SURFACE HOUSINGS
WHEN IN CEILINGS - FASTEN SURFACE BOXES TO
STRUCTURE.
6. PROVIDE SUFFICIENT SERVICE LOOP IN UTP SPEAKER
CABLE TO ALLOW PLACEMENT OF SPEAKERS ANYWHERE
IN ROOM.
7. SPEAKERS AND WAPS BY OTHERS
8. PROVIDE 5M OF SERVICE LOOP AT EACH WAP OUTLET
LOCATION IN CEILINGS.
9. NEATLY COIL AND FASTEN TO STRUCTURE ALL WAO
SERVICE LOOPS IN CEILINGS AT OUTLET.
| Sheets and Views |
| OCS DRAHNER SCS 11-21-23-BASEMENT |
| Sheets and Views |
| OCS DRAHNER SCS 11-21-23-1ST FLOOR A |
| Sheets and Views |
| OCS DRAHNER SCS 11-21-23-1ST FLOOR B |
| Sheets and Views |
| OCS DRAHNER SCS 11-21-23-2ND FLOOR A |
| Sheets and Views |
| OCS DRAHNER SCS 11-21-23-2ND FLOOR B |
File details come from the government source that posted it. Updated .