OC_Phoenix_BAS_and_Smoke_Control_-_100%_Drawings.pdf

PDF 21 MB Posted

Attached to
Corrections Phoenix Smoke Control and Building Automation Systems Replacement
Solicitation number
Y22-7025
Issued by
Orange County, Orlando City, Florida

About this file

This document is a comprehensive set of 100% construction drawings for the Orange County Corrections Phoenix Building Replacement of the Smoke Control and Building Automation Systems project, dated December 14, 2021. The project involves replacing existing smoke control and building automation systems across multiple buildings (Buildings A, B, and C) at the Orange County Corrections facility located at 2400 33rd Street, Orlando, Florida. The drawings cover detailed mechanical, electrical, and control system plans for replacing pneumatic fire-smoke dampers, thermostats, control panels, exhaust fans, air handling units, and integrating new digital building automation systems with enhanced smoke control capabilities.

The project includes replacing existing control systems with new UL 864 controllers, sensors, and building automation system panels, with a focus on improving smoke control, ventilation, and system monitoring. The drawings specify technical details for replacing equipment such as rooftop units (RTUs), smoke exhaust fans, electric duct heaters, and damper actuators across different building zones. Electrical plans detail power distribution, panel replacements, and interface requirements for the new control systems. The project appears to be funded by Orange County and is designed to upgrade the facility's critical life safety and environmental control infrastructure with modern, integrated systems that provide enhanced monitoring, control, and emergency response capabilities.

View the file

Other files

File Type Posted
Y22-7025.pdf PDF
OC_Phoenix_BAS_and_Smoke_Control_-_100%_Specifications.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

100% CONSTRUCTION DOCUMENTS

DECEMBER 14, 2021

ORANGE COUNTY MAYOR

JERRY L. DEMINGS

DISTRICT 1 COMMISSIONER

NICOLE H. WILSON

DISTRICT 2 COMMISSIONER

CHRISTINE MOORE

DISTRICT 3 COMMISSIONER

MAYRA URIBE

DISTRICT 4 COMMISSIONER

MARIBEL GOMEZ CORDERO

DISTRICT 5 COMMISSIONER

EMILY BONILLA

DISTRICT 6 COMMISSIONER

VICTORIA P. SIPLIN

Sheet

Number Sheet Name Scale

Sheet

Issued

G-000 COVER SHEET AND SHEET INDEX

Yes

M-101

BUILDINGS B AND C FIRST LEVEL HVAC PLAN

1/8"=1'-0" Yes

No Scale

M-401 HVAC SCHEDULES

No Scale Yes

M-001 HVAC SYMBOLS LEGEND AND GENERAL NOTES

YesNo Scale

M-102 1/8"=1'-0" Yes

DRAWING INDEX

BOARD OF COUNTY COMMISSIONERS

BUILDINGS B AND C SECOND LEVEL HVAC PLAN

M-103 1/8"=1'-0" Yes

BUILDINGS B AND C ROOF LEVEL HVAC PLAN

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st em s

DAVID L. HEIDEMAN

FL PE NO. 76792

G-001

COVER SHEET AND

SHEET INDEX

DLH

DLH

TJF

M-301 PHOENIX CHILLER PLANT CONTROLS

No Scale YesM-302

No Scale YesM-303

PHOENIX C1 THRU C6 SEQUENCE, OVERVIEW AND PARTS LIST

No Scale YesM-304

PHOENIX RTU-C7 AND C8 SEQUENCE, OVERVIEW AND PARTS LIST

No Scale YesM-305

PHOENIX AHU-1 THRU 7 SEQUENCE, OVERVIEW AND PARTS LIST

No Scale YesM-306

PHOENIX SF-1 THRU 8 SEQUENCE, OVERVIEW AND PARTS LIST

SMOKE CONTROL SYSTEM SEQUENCE, OVERVIEW AND PART LIST

No Scale Yes

Orange County Corrections

Phoenix Building Replacement of the Smoke

Control and Building Automation Systems

E-001 ELECTRICAL LEGEND SYMBOL AND NOTES No Scale Yes

E-101 BUILDINGS B AND C FIRST LEVEL ELEC PLAN

Yes

E-102 Yes

E-103 Yes

E-401 ENLARGED ELECTRICAL PLANS Yes

E-402 Yes

E-601 EXISTING ELECTRICAL ONE LINE DIAGRAM

No Scale Yes

E-801 ELECTRICAL PANEL SCHEDULE

No Scale Yes

E-701 FIRE ALARM AND SMOKE CONTROL RISER DIAGRAM - DEMOLITION

No Scale Yes

E-702 FIRE ALARM AND SMOKE CONTROL RISER DIAGRAM - NEW No Scale Yes

E-711 ELECTRICAL SMOKE CONTROL DETAILS No Scale Yes

BUILDINGS B AND C SECOND LEVEL ELEC PLAN

BUILDINGS B AND C ROOF LEVEL ELEC PLAN

ENLARGED ELECTRICAL PLANS

1/8"=1'-0"

1/8"=1'-0"

1/8"=1'-0"

1/4"=1'-0"

1/4"=1'-0"

M-104 1/8"=1'-0" Yes

BUILDING A FIRST LEVEL HVAC PLAN

M-105 1/8"=1'-0" Yes

BUILDING A FIRST LEVEL PIPING PLAN

M-106 1/8"=1'-0" Yes

BUILDING A MECHANICAL MEZZANINE PLANS

E-104 YesBUILDING A FIRST LEVEL ELEC PLAN 1/8"=1'-0"

E-105 YesBUILDING A ELECTRICAL MEZZAININE PLANS 1/8"=1'-0"

M-501 SEQUENCE OF OPERATIONS

No Scale Yes

MECHANICAL

ELECTRICAL

M-601 HVAC DETAILS

No Scale Yes

M-502 DAMPER CONTROL SCHEMATIC DIAGRAMS

No Scale Yes

No Scale YesM-307 FIREFIGHTER SMOKE CONTROL PANEL

No Scale YesM-308 MAINTENANCE SMOKE EXTRACT CONTROL PANEL

AutoCAD SHX Text

KEY WEST

AutoCAD SHX Text

MIAMI

AutoCAD SHX Text

WEST PALM BEACH

AutoCAD SHX Text

OKEECHOBEE

AutoCAD SHX Text

FT. PIERCE

AutoCAD SHX Text

LAKE

AutoCAD SHX Text

OKEECHOBEE

AutoCAD SHX Text

MELBOURNE

AutoCAD SHX Text

HAINES CITY

AutoCAD SHX Text

KISSIMMEE

AutoCAD SHX Text

ORLANDO

AutoCAD SHX Text

LEESBURG

AutoCAD SHX Text

LAKELAND

AutoCAD SHX Text

TAMPA

AutoCAD SHX Text

BRADENTON

AutoCAD SHX Text

FT. MYERS

AutoCAD SHX Text

DAYTONA BEACH

AutoCAD SHX Text

OCALA

AutoCAD SHX Text

GAINESVILLE

AutoCAD SHX Text

ST. AUGUSTINE

AutoCAD SHX Text

JACKSONVILLE

AutoCAD SHX Text

LAKE CITY

AutoCAD SHX Text

PERRY

AutoCAD SHX Text

TALLAHASSEE

AutoCAD SHX Text

APALACHICOLA

AutoCAD SHX Text

PANAMA

AutoCAD SHX Text

CITY

AutoCAD SHX Text

MARIANNA

AutoCAD SHX Text

PENSACOLA

AutoCAD SHX Text

PROJECT LOCATION

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text N

GENERAL INSTALLATION NOTES

ALL COMMUNICATION CABLING SHALL BE RUN SEPARATE FROM ANY POWER WIRING.

REFER TO SPECIFICATION DIVISIONS 23 & 26 REGARDING WIRING AND CONDUIT REQUIREMENTS.

ALL CONDUIT MUST HAVE A PULL STRING INCLUDED.

LABELING, ETC... HAND WRITTEN LABELS ARE NOT ACCEPTABLE.

ALL WIRING MUST BE CLEARLY LABELED AT TERMINATION POINTS. ACCEPTABLE METHODS INCLUDE BRADY

ACTUAL CONFIGURATION OF DUCTING SYSTEMS IS TO BE DETERMINED BY OTHERS, AND CONFIGURATION

SHOWN ON THE FOLLOWING PAGES ARE FOR DIAGRAMMATIC PURPOSES ONLY.

ACTUAL CONFIGURATION OF PIPING SYSTEMS IS TO BE DETERMINED BY OTHERS, ANY CONFIGURATION

SHOWN ON THE FOLLOWING PAGES ARE FOR DIAGRAMMATIC PURPOSES ONLY.

ALL CONDUIT AND WIRING MUST BE INSTALLED PARALLEL TO THE BUILDING LINES.

ALL WORK SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER & MUST MEET THE APPROVAL OF

ALL WALL PENETRATIONS MUST BE SLEEVED AND SEALED PER THE SPECIFICATIONS. IF THE WALL IS A RATED WALL, F.B.O. IS AN ACRONYM FOR FURNISHED BY OTHERS.

MAXIMUM FLEXIBLE CONDUIT LENGTH NOT TO EXCEED 3 FEET.

LOCATE NEW PANELS AND ASSOCIATED COMMUNICATION CABLES 6' MIN. DISTANCE FROM ANY VFD

PANEL OR HIGH POWER CONDUIT. INSTALLATION MUST CONFORM WITH ALL NATIONAL AND LOCAL CODES.

WIRING COLOR CODE:

BL = BLUE BK = BLACK BR = BROWN GR = GREEN

GY = GRAY O = ORANGE

P = PURPLE

R = RED Y = YELLOW WH = WHITE

OUTSIDE AIR

OUTSIDE AIR/HUMIDITY SENSOR

MAGNETIC STARTER

LOW LIMIT PRESSURE SWITCH

HIGH LIMIT PRESSURE SWITCH

MEDIA CONVERTER

LINE VOLT THERMOSTAT

PROGRAMMABLE CONTROLLER

I/O MODULE

SETPOINT CONTROLLER

HOT WATER VALVE

HUMIDIFIER

INLET GUIDE VANES

EXPANSION MODULE

OSA

0HS

MS

LLS

HLS

MC

LVT

MP581

MP503

MP501

HWV

HUM

IGV

ABB.

EX2

SYMBOLDESCRIPTION

DIFFERENTIAL PRESSURE TRANSMITTER

DIFFERENIIAL PRESSURE SWIICH

DUCT TEMPERATURE SENSOR

DOMESTIC WATER HEATER

FAN POWERED UNIT

FREEZE STAT

FLOAT SWITCH

FIRE STAT

FILTER

DAMPER END SWITCH

ELECTRIC DUCT HEATER

DUCT SMOKE DETECTOR

DPT

DPS

DTS

DWH

HE

HC

FPU

FZT

FS

FRT

FLT

ES

EDH

DSD

ABB.SYMBOLDESCRIPTION

BUILDING CONTROL UNIT

COOLING COIL

CHILLED WATER VALVE

MOTORIZED DAMPER

DUCT HUMIDITY SENSOR

DUCT CARBON DIOXIDE SENSOR

CURRENT TRANSMITTER

CURRENT SENSING SWITCH WITH RELAY

CURRENT SENSING SWITCH

CENTRAL CONTROL PANEL

AIR HANDLING UNIT

AIR FLOW RING

AIR FLOW MONITORING STATION

AVERAGING TEMPERATURE SENSOR

SYMBOL

BCU

CC

CHWV

DM

DHS

DCO

CT

CSSR

CSS

CCP

AHU

AFR

AFM

ATS

ABB.

BCU

C

C

VARI TRAC II

CCP

сss

CSSR

CT

Ü û

2-WAY

3-WAY

C H

W V

D M

B

D H

S

A F

R

A F

M

A T

S

D M

A

C H

W V

RLY

RIB

SHS

RPS

PPU

SEQ

SA

RA

PWS

PCM

OTS

ZN517

SP

ZN511/521

UNITARY CONTROLLER

ZONE CONTROLLER

RELAY

RELAY IN A BOX

SPACE HUMIDITY SENSOR

ROOM PRESSURE SENSOR

PARALLEL FAN POWERED UNIT

SEQUENCER RELAY MODULE

SUPPLY AIR

RETURN AIR

DC POWER SUPPLY

PROGRAMMABLE CONTROL MODULE

OUTSIDE TEMPERATURE SENSOR

SURGE PROTECTION

TCI

UPCM

UCP

UCM

TUC

TCM

VAV

TDM

TR

TU

TKR

SPTS

TC

STS

TRANE CONTROL INTERFACE

UNIVERSAL PROGRAMMABLE CONTROL MODULE

UNIT CONTROL PANEL

UNIT CONTROL MODULE

TERMINAL UNIT CONTROL

THERMOSTAT CONTROL MODULE

VARIABLE AIR VOLUME BOX

TRAC MOTORIZED DAMPER

TRANSFORMER

TERMINAL UNIT

TRACKER 100 STAT

STRAP ON TEMPERATURE SENSOR

TIME CLOCK

SPACE TEMPERATURE SENSOR

VFD

ZDU

WTS

WFM

WFS

VARIABLE FREQUENCY DRIVE

ZONE DAMPER UNIT

WELL TEMPERATURE SENSOR

WATER FLOW METER

WATER FLOW SWITCH

DESCRIPTION SYMBOL ABB. DESCRIPTION ABB.SYMBOL DESCRIPTIONSYMBOL ABB.DESCRIPTION

HEAT EXCHANGER

HEATING COIL

ZDM

WTS

VFD

OR CARD NUMBER

TERMINAL BLOCK

DEVICE NUMBER

CONTROLLER

POINT NUMBER

POINT TYPE

MULTIPLE CONTROL DEVICE CALLOUT DESCRIPTON

TERMINAL BLOCK

OR CARD NUMBER

B0

1 1

POINT TYPE

POINT NUMBER

SINGLE CONTROL DEVICE CALLOUT DESCRIPTON

H E

R E

S E

T

F Z

T F

R T

W F

M

R E

S E

T

ABBREVIATIONS AND SYMBOL LEGEND

ZN

ZN

ZN

PCM

PWS

RA

RIB

RLY

RPS

SA

SEQ

VAV

UPCM

UCP

TUC

TU

TRACKER

STAT X

TCM

TCI

1:00

TC

STS

SPTS

PPU

SP

SHS

TDM-X

OPS

DPT

DWH

FS

FPU

C

H

D T

S

E D

H

H W

V

M

H U

M

M о s o

OSA

MS

5O3

MP

MP

MC

L H

LLS

IGV

HL

HLS

EX2

OHS

MP.581

H W

V

M

3-WAY

2-WAY

UCM

THE ENGINEER, ORANGE COUNTY CAPITAL FACILITIES AND ORANGE COUNTY CORRECTION FACILITIES.

THE PENETRATION SHALL BE SEALED WITH PREVIOUSLY SUBMITTED AND ACCEPTED FIRE PROOFING MATERIAL INSTALLED

AS RECOMMENDED BY THE MATERIAL MANUfFACTURER.

CONTRACTOR TO PROVIDE TEMPORARY ROOFTOP AIR HANDLERS AND TEMPORARY SMOKE EXHAUST FANS FOR SMOKE ZONES

UNDER CONSTRUCTION IF THOSE ZONES ARE TO REMAIN CONTINUALLY OCCUPIED. EACH TEMPORARY UNIT TO BE TIED INTO

FIRE ALARM OR PROVIDE FIRE WATCH. ALL LIFE SAFETY REQUIREMENTS SHALL BE PROVIDED AS REQUIRED BY THE AHJ.

EXISTING CONTROLLERS, SENSORS, T-STATS AND WIRING TO BE REPLACED WITH NEW UL 864 CONTROLLERS, NEW SENSORS, NEW T-STATS AND NEW WIRING. SEE SPECIFICATIONS FOR REPLACEMENT OF CONTROL SYSTEMS.

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-001

HVAC SYMBOLS LEGEND

AND GENERAL NOTES

DLH

DLH

TJF

20x10 RETURN AIR UP

14x14 SUPPLY DUCT UP TO 2ND FLOOR

20x10 EXHAUST DUCT UP TO 2ND FLOOR

SUPPLY DUCT UP TO 2ND FLOOR

14x14 SUPPLY DUCT UP TO 2ND FLOOR

EXHAUST DUCT UP TO 2ND FLOOR

20x10 EXHAUST DUCT UP TO 2ND FLOOR

14x14 SUPPLY DUCT UP TO 2ND FLOOR

SUPPLY DUCT UP TO 2ND FLOOR

SUPPLY DUCT UP TO 2ND FLOOR

FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.) FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.)

FIRE DAMPERS (TYP.)

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 3 ON SHEET M-601

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 3 ON SHEET M-601

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 3 ON SHEET M-601

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 3 ON SHEET M-601

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 3 ON SHEET M-601

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 3 ON SHEET M-601

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 3 ON SHEET M-601

SEE PURGE AIR DETAIL AT OUTSIDE

AIR INTAKE DETAIL 3 ON SHEET M-601

14x14 PURGE AIR UP

14x14 PURGE AIR UP

14x14 PURGE AIR UP

14x14 SUPPLY AIR DUCT UP

14x14 PURGE AIR UP

14x14 PURGE AIR UP

14x14 PURGE AIR UP

UP TO EF-9

DS/CU-1

S/A FROM

SECOND

FLOOR AND

RTU-8

R/A FROM

SECOND

FLOOR AND

RTU-8

x

8x6

8x4

10x8

24x8 x x

10x8

10x8

10x8

10x8

10x8

10x8 x x

28x8

10x8

10x8 x

10x8

8x6

8x6

10x6

12x8 x x

10x6

10x6 x x x

14x10 x x

14x8

8x6 x x x x x x x

8x6 x

10x6

12x6 x

10x6

12x8 x x x x x x x x x x x x x x x x

14x8 x

10x6

10x6

10x6 x x

12x8

8x4 x

8x4

14x10

12x6 x x x

12x6 x

14x10

10x6

10x6 x x

10x6 x x

14x8 x x x x x x x x x x x x x x x

14x1212x8

10x6

12x6 x x x x

14x10

8x4

12x8

10x6

14x12

12x6 x x x

6 1 x x x x x x x x x x x x x

10x6

8x6

10x6

14x8 x

14x14 PURGE AIR UP

FIRE DAMPERS (TYP.)

EXISTING FIRE ALARM CONTROL PANEL

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-101

BUILDINGS B AND C

FIRST LEVEL HVAC PLAN

DLH

DLH

TJF

BUILDINGS B AND C FIRST LEVEL HVAC PLAN

SCALE: 1/8" = 1'-0"

REMOVE EXISTING PNEUMATIC FIRE - SMOKE DAMPER AND

INSTALL NEW FIRE - SMOKE DAMPER, ACTUATOR AND SMOKE

DETECTOR. THE SMOKE DETECTOR SHALL BE INSTALLED

WITHIN 5'-0" OF THE DAMPER.

REMOVE EXISTING THERMOSTATS AND HUMIDISTATS WITH

ASSOCIATED EXISTING WIRING AND REPLACE WITH NEW DDC

THERMOSTATS AND HUMIDISTATS AND WIRING (TYPICAL).

INSTALL NEW DDC CONTROLLER AND WIRING FOR EXISTING

AC-1/CU-1 UNIT AT BUILDING B.

ALL EXISTING DUCTWORK SHALL BE CLEANED PER

SPECIFICATION SECTION 230130.52.

REPLACE EXISTING/DUCT ACCESS DOOR AT FIRE/SMOKE

DAMPER. IF DOOR DOES NOT EXISTS, INSTALL NEW DOOR.

REPLACE EXISTING PRIMARY FIREFIGHTER'S

SMOKE CONTROL PANEL WITH NEW UL 864

PRIMARY FIREFIGHTER'S SMOKE CONTROL

PANEL.

REPLACE EXISTING BUILDING AUTOMATION

SYSTEM PANEL WITH NEW UL 864 BAS

CONTROL PANEL.

REPLACE EXISTING SECONDARY

FIREFIGHTER'S SMOKE CONTROL PANEL

WITH NEW UL 864 SECONDARY

FIREFIGHTER'S SMOKE CONTROL PANEL.

DEMO EXISTING PNEUMATIC AIR COMPRESSOR AND ALL

EXISTING PNEUMATIC TUBING AND WIRING. TURN OVER TO

OWNER.

KEYED NOTES

UL 864 SMOKE CONTROL SYSTEM

UL 864 SMOKE CONTROL SYSTEM

1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS

DRAWING IS EXISTING UNLESS NOTED OTHERWISE.

GENERAL NOTES

AutoCAD SHX Text P

P

20x10 EXHAUST DUCT DN TO 1ST FLOOR

14x14 SUPPLY DUCT DN TO 1ST FLOOR

20x10 EXHAUST DUCT DN TO 1ST FLOOR 14x14 SUPPLY DUCT DN TO 1ST FLOOR

14x14 SUPPLY DUCT DN TO 1ST FLOOR

20x10 EXHAUST DUCT DN TO 1ST FLOOR

20x10 EXHAUST DUCT DN TO 1ST FLOOR

14x14 SUPPLY DUCT DN TO 1ST FLOOR

SUPPLY DUCT DN TO 1ST FLOOR

SUPPLY DUCT DN

TO 1ST FLOOR

46x14 S/A FROM RTU-8

FROM

RTU-7

FROM

RTU-7

FROM

RTU-7

FROM

RTU-7

FROM

RTU-7

R/A FROM

RTU-8

RTU ABOVE

RTU ABOVE

RTU ABOVE

RTU ABOVE

RTU ABOVE

RTU ABOVE

RTU ABOVE

x x x

12x8

12x6

8x4 x x x x

8x4 x x x x x x x

10x6

6x4

24x6

10x8

24x6

24x6

24x6

24x6

24x14

30x14

10x8

10x8

10x6

10x6

10x6

10x10

18Ø x x x x x x x x x x x x

8x6

8x6 x x x x

8x610x8 x x x x x x x x x x x x x x

8x6

8x6 x x x x

8x610x8 x x x x x x x x x x x x x x

8x6

8x6 x x x x

8x6 10x8

RTU ABOVE

x x x x x x x x x x x x x x

8x6

8x6 x x x x

8x6 10x8

RTU ABOVE

REMOVE EXIST DUCT BLOCK AND CAP DUCT PROPERLY.

REMOVE F/S DAMPER AND DUCT THROUGH WALL.

PATCH WALL AS REQUIRED TO MAINTAIN RATING

REMOVE EXIST DUCT BLOCK AND CAP DUCT PROPERLY.

REMOVE F/S DAMPER AND DUCT THROUGH WALL.

PATCH WALL AS REQUIRED TO MAINTAIN RATING

FIRE DAMPER (TYP.)

FIRE DAMPER (TYP.)

FIRE DAMPER (TYP.)

FIRE DAMPER (TYP.)

RTU

C4

RTU

C3

RTU

C1

RTU

C2

RTU

C5

FIRE DAMPER (TYP.)

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-102

BUILDINGS B AND C

SECOND LEVEL HVAC PLAN

DLH

DLH

TJF

BUILDINGS B AND C SECOND LEVEL HVAC PLAN

SCALE: 1/8" = 1'-0"

REMOVE EXISTING PNEUMATIC FIRE - SMOKE DAMPER AND INSTALL NEW

FIRE - SMOKE DAMPER, ACTUATOR AND SMOKE DETECTOR. THE SMOKE

DETECTOR SHALL BE INSTALLED WITHIN 5'-0" OF THE DAMPER. INSTALL

DUCT ACCESS DOOR IF NONE EXISTS ON AT LEAST ONE SIDE OF F/S

DAMPER (SIDE OF ACTUATOR).

REMOVE EXISTING THERMOSTATS AND HUMIDISTATS WITH ASSOCIATED

EXISTING WIRING AND REPLACE WITH NEW DDC THERMOSTATS AND

HUMIDISTATS AND WIRING (TYPICAL).

KEYED NOTES

ALL EXISTING DUCTWORK SHALL BE CLEANED PER

SPECIFICATION SECTION 230130.52.

UL 864 SMOKE CONTROL SYSTEM

UL 864 SMOKE CONTROL SYSTEM

1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS

DRAWING IS EXISTING UNLESS NOTED OTHERWISE.

GENERAL NOTES

AutoCAD SHX Text

SECURITY CONTROL EQUIP

AutoCAD SHX Text B-204

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

P

EXIST. SA - DN TO ZONE 4

SERVING

ZONE 4

EXIST. RA -

DN - ZONE 4

EXIST. SA -

DN - ZONE 3

EXIST. SEF-14

SERVES ZONE 4

EXIST. F/S DAMPER

EXIST. F/S DAMPER

EXIST. F/S DAMPER

EXIST. F/S DAMPER

EXIST. SA -

DN - ZONE 5

EXIST. SEF-18

SERVES - ZONE 4

EXIST. RA -

DN - ZONE 5

EXIST. F/S DAMPER

SERVING

ZONE 3

EXIST. RA -

DN - ZONE 3

EXIST. F/S DAMPER

EXIST. SEF-15

SERVES ZONE 3

EXIST. F/S DAMPER

EXIST. RA -

DN - ZONE 5

EXIST. SA -

DN - ZONE 5

EXIST. F/S DAMPER

EXIST.SEF-19

SERVING

ZONE 4

SERVING

ZONE 2

EXIST. SA -

DN - ZONE 2

EXIST. F/S DAMPER

EXIST. F/S DAMPER

EXIST. RA -

DN - ZONE 2

SERVING

ZONE 2

EXIST.SEF-16

SERVING

ZONE 1

EXIST. F/S DAMPER

EXIST. F/S DAMPER

EXIST. SA -

DN - ZONE 1

EQUIPMENT NOT INCLUDED IN UL

864 SMOKE CONTROL SYSTEM

RTU

C7

SEF

C14

RTU

C4

EF

C10

EDH

C14

SERVING

ZONE 5

RTU

C6

SEF

C18

EDH

C13

EDH

C11

EF

C12

SEF

C17

RTU

C2

EDH

C8

3 2

SEF

C15

RTU

C3

EF

C11

EDH

C10

(EXISTING)

(EXISTING)

(EXISTING)

(EXISTING)

(EXISTING)

SERVING

ZONE 1

SERVING

ZONE 1

EF

C13

SEF

C16

2 3 5

RTU

C1

EDH

C8

(EXISTING)

RTU

C8

2 3 5

EDH

C15

(EXISTING)

2 3 5

SEF

C19

2 3 5

EDH

C12

(EXISTING)

SERVING

ZONE 5

RTU

C5

30x20

20x20

30x20

20x20

30x20

20x20

30x20

20x20

26x14

26x14

46x14

28x16 x x

26x14

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-103

BUILDINGS B AND C

ROOF LEVEL HVAC PLAN

DLH

DLH

TJF

BUILDINGS B AND C ROOF LEVEL HVAC PLAN

SCALE: 1/8" = 1'-0"

KEYED NOTES

REMOVE EXISTING PNEUMATIC FIRE - SMOKE DAMPER AND INSTALL

NEW FIRE - SMOKE DAMPER, ACTUATOR AND SMOKE DETECTOR.

THE SMOKE DETECTOR SHALL BE INSTALLED WITHIN 5'-0" OF THE

DAMPER. INSTALL DUCT ACCESS DOOR IF NONE EXISTS ON AT

LEAST ONE SIDE OF F/S DAMPER (SIDE OF ACTUATOR).

REMOVE ALL EXISTING VALVE ACTUATORS, TEMPERATURE

SENSORS, DIFFERENTIAL PRESSURE SENSORS, ELECTRIC DUCT

HEATERS. REPLACE ALL DEVICES WITH NEW DEVICES CONNECTED

TO NEW BMS SYSTEM. SEE SHEET M-303 FOR ADDITIONAL DETAILS.

REMOVE EXISTING AHU CONTROLLER AND REPLACE WITH NEW DDC

CONTROLLER AND WIRING FOR EXISTING ROOF TOP UNIT.

REPLACE CONTROL DEVICES FOR EXISTING EXHAUST FANS WITH

NEW DEVICES CONNECTED TO NEW BMS.

ALL EXISTING DUCTWORK, TERMINAL UNITS, SUPPLY FANS, AIR

HANDLING UNITS, EXHAUST FANS AND OTHER EQUIPMENT SHALL

BE CLEANED PER SPECIFICATION SECTION 230130.52.

UL 864 SMOKE CONTROL SYSTEM

UL 864 SMOKE CONTROL SYSTEM

1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS

DRAWING IS EXISTING UNLESS NOTED OTHERWISE.

GENERAL NOTES

REPLACE EXISTING ELECTRIC DUCT HEATER WITH NEW SCR

ELECTRIC DUCT HEATER OF SAME CAPACITY.

2. CONTRACTOR SHALL REFER TO THE CONTROL DRAWINGS TO

VERIFY THE SCOPE OF WORK AND THE THE EQUIPMENT SCHEDULES

FOR THE SIZES AND CAPACITIES OF EXISTING AND/OR NEW

EQUIPMENT.

REMOVE AND REPLACE EXISTING SMOKE EXHAUST FAN.

REMOVE EXISTING DUCT SMOKE DETECTOR AND EXISTING

WIRING. REPLACE WITH NEW DUCT SMOKE DETECTOR AND

WIRING. PROVIDE STAINLESS STEEL ENCLOSURE WITH CLEAR

VIEWING WINDOW TO SMOKE DETECTOR. PROVIDE NEW

DOUBLE-WALL INSULATED DUCT ACCESS DOOR FOR

MAINTENANCE FOR NEW DUCT SMOKE DETECTOR.

PROVIDE NEW DUCT SMOKE DETECTOR WITH NEW STAINLESS

STEEL ENCLOSURE AND CLEAR VIEWING WINDOW TO SMOKE

DETECTOR. PROVIDE NEW DOUBLE-WALL INSULATED DUCT

ACCESS DOOR FOR MAINTENANCE FOR NEW DUCT SMOKE

DETECTOR.

PROVIDE NEW VFD FOR REPLACED SMOKE EXHAUST FAN

IN NEMA 4X STAINLESS STEEL ENCLOSURE. PROVIDE NEW

UNISTRUT MOUNTING ON BRACKETS AT RTU DUNNAGE,

NEXT TO EXISTING DISCONNECTS.

400 400

400 400

400 400

300 100

SF

A8

EDH

A23

SF

A7

EDH

A22

SF

A6

EDH

A21

SF

A5

EDH

A20

SF

A4

EDH

A19

SF

A3

EDH

A18

SF

A2

EDH

A17

SF

A1

EDH

A16

CU

A2

AC

A2

EF

A1

AC

A1

CU

A1

UH

A1

EF

A20

EF

A2

EF

A3

AHU

A6

AHU

A7

AHU

A4

EF

A6

AHU

A3

AHU

A2

AHU

A1

6 8

6 8

EF

A5

6 8

8 9

AHU

A5

8 9

8 9

EF

A7

EF

A8

6 8

6 8

EF

A4

6 8

8 8

30x14 30x10

18x10

30x14 30x10

18x10

30x14 30x10

18x10

30x14 30x10

18x10

30x14 30x10

18x10

30x14 30x10

18x10

30x14 30x10

18x10

30x14 30x10

18x10

30x14 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x

24x6

12x10

12x10

12x10

12x10

12x10

18x10

12x8

20x14

12x6

10x8

12x8

12x10

12x8

24x8

12x10

24x14

14x10

24x8

24x12

16x12

12x10 x x x

10x6

18x14 x x x

10x8

6x4

12x8

12x8

12x8

12x8

10x6

10x6 x x

6x4

8x6

24x424x2 x

8x4

8x4

8x6

8x6 x x

24x8

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-104

BUILDING A

FIRST LEVEL HVAC PLAN

DLH

DLH

TJFBUILDING A FIRST LEVEL HVAC PLAN

SCALE: 1/8" = 1'-0"

REMOVE EXISTING PNEUMATIC FIRE - SMOKE DAMPER AND INSTALL NEW FIRE - SMOKE DAMPER, ACTUATOR

AND SMOKE DETECTOR. THE SMOKE DETECTOR SHALL BE INSTALLED WITHIN 5'-0" OF THE DAMPER. INSTALL

DUCT ACCESS DOOR IF NONE EXISTS ON AT LEAST ONE SIDE OF F/S DAMPER (SIDE OF ACTUATOR).

REMOVE EXISTING THERMOSTATS AND HUMIDISTATS WITH ASSOCIATED EXISTING WIRING AND REPLACE WITH

NEW DDC THERMOSTATS AND HUMIDISTATS AND WIRING (TYPICAL).

REPLACE EXISTING TRANE CONTROL PANEL WITH NEW JOHNSON CONTROLS BMS PANEL.

REPLACE EXISTING ELECTRIC DUCT HEATER WITH NEW SCR ELECTRIC DUCT HEATER OF SAME CAPACITY.

REPLACE EXISTING SUPPLY FAN CONTROLLER WITH NEW DDC CONTROLLER.

REPLACE EXISTING EXHAUST FAN CONTROLLER WITH NEW CONTROLLER CONNECTED TO BMS (TYPICAL).

REPLACE EXISTING UNIT HEATER CONTROLLER WITH NEW CONTROLLER CONNECTED TO BMS (TYPICAL).

KEYED NOTES

ALL EXISTING DUCTWORK, TERMINAL UNITS, SUPPLY FANS, AIR HANDLING UNITS, EXHAUST FANS AND

OTHER EQUIPMENT SHALL BE CLEANED PER SPECIFICATION SECTION 230130.52.

REPLACE EXISTING AIR HANDLING UNIT CONTROLLER WITH NEW AIR HANDLING UNIT CONTROLLER

CONNECTED TO THE NEW BAS SYSTEM.

1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS

DRAWING IS EXISTING UNLESS NOTED OTHERWISE.

GENERAL NOTES

REMOVE EXISTING PNEUMATIC DAMPER ACTUATORS AND PNEUMATIC TUBING. REPLACE WITH NEW

ELECTRONIC DAMPER ACTUATORS, PROVIDE NEW DDC CONTROLLERS AND CONNECT TO BAS SYSTEM.

PROVIDE NEW DUCT SMOKE DETECTOR. PROVIDE NEW DOUBLE-WALL DUCT ACCESS DOOR FOR

MAINTENANCE FOR NEW DUCT SMOKE DETECTOR.

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

T

3" CHWS&R

1 1/2" CHWS&R

2 1/2" CHWS&R

1 1/2" CHWS&R

1" CHWS&R

2" CHWS&R

2 1/2" CHWS&R

1 1/2" CHWS&R

1" CHWS&R

1" CHWS&R

AHU

A5

AHU

A7

AHU

A4

AHU

A6

AHU

A3

AHU

A2

AHU

A1

3" CHWS&R TO &

FROM BUILDING

3/4" HWR

2" HW

3" CW

1 1/2" HWR

2" HWS

12" FLUE UP

TO ROOF

4" FLUE

UH-1

GWH-1

CHEMICAL

SHOT FEEDER

6" CHR

6" CHWR

3" CHWS

6" CHR

CHILLED WATER

MAKE-UP[

3/4"

BACKFLOW/PRV ASSEMBLY

ASC PANEL

FOR CHILLERS

6" CHWS

6" CHWS

6" CHWS

3" CHWS

6" CHWR

2 1/2" HWS

1 1/2" HWR

X

X

X

X

X

X X X X X

X

X

X

X

X

CHILLER YARD

CH-1

CH-2

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-105

BUILDING A

FIRST LEVEL PIPING PLAN

DLH

DLH

TJF

BUILDING A FIRST LEVEL PIPING PLAN

SCALE: 1/8" = 1'-0"

ENLARGED MECH ROOM 110

SCALE: 1/4" = 1'-0"

CHILLER YARD

SCALE: 1/8" = 1'-0"

EXISTING CHILLERS BEING REPLACED UNDER SEPARATE CONTRACT.

KEYED NOTES

1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS

DRAWING IS EXISTING UNLESS NOTED OTHERWISE.

GENERAL NOTES

MECHANICAL MEZZANINE

A-200

1 1/2"

26x14 x

14x12

M

M

M

M x x x x

14x12 x

14x12

28x14

20x14

1 1/2" 1 1/2"

1 1/2"

1 1/2"

1 1/2"

1 1/2"

1 1/2"

2 1/2"

2 1/2"

AHU-5

EXISTING CONTROL

PANEL (TYPICAL)

2"

2"

AHU

A5

AHU

A7

2 3

AHU

A6

AHU

A4

12 2

AHU-7

DDC PANEL

26x16 x x x

24x12

14x26

26x14

M

M

M

16x12

18x16 x

2"

1 1/2"

1 1/2"

1 1/2"

1 1/2"

1 1/2"

1 1/2"

EXISTING CONTROL

PANEL (TYPICAL)

2"

MECHANICAL MEZZANINE

A-201

AHU-2

AHU

A2

AHU

A1

AHU

A3

1 2

DDC PANEL

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-106

BUILDING A MECHANICAL

MEZZANINE PLANS

DLH

DLH

TJF

BUILDING A MECHANICAL MEZZANINE 200 PLAN

SCALE: 1/4" = 1'-0"

BUILDING A MECHANICAL MEZZANINE 201 PLAN

SCALE: 1/4" = 1'-0"

REPLACE PNEUMATIC FIRE - SMOKE DAMPER WITH NEW FIRE

SMOKE DAMPER,ACTUATOR AND SMOKE DETECTOR. THE

SMOKE DETECTOR SHALL BE INSTALLED WITHIN 5'-0" OF THE

DAMPER. INSTALL INSPECTION DOOR AND ACCESS PANEL

WITHIN 5'0" OF DAMPER IF ONE DOES NOT EXIST.

ALL EXISTING DUCTWORK, TERMINAL UNITS, SUPPLY FANS, AIR

HANDLING UNITS, EXHAUST FANS AND OTHER EQUIPMENT

SHALL BE CLEANED PER SPECIFICATION SECTION 230130.52.

REPLACE EXISTING AIR HANDLING UNIT CONTROLLER WITH

NEW AIR HANDLING UNIT CONTROLLER CONNECTED TO THE

NEW BAS SYSTEM.

REPLACE EXISTING MOTORIZED DAMPER CONTROLLER AND

DAMPER ACTUATOR WITH NEW MODULATING ACTUATOR WITH

POSITION INDICATOR.

KEYED NOTES

1. ALL EQUIPMENT, DUCTWORK AND PIPING INDICATED ON THIS

DRAWING IS EXISTING UNLESS NOTED OTHERWISE.

GENERAL NOTES

REMOVE EXISTING DUCT SMOKE DETECTOR AND EXISTING

WIRING. REPLACE WITH NEW DUCT SMOKE DETECTOR AND

WIRING. INSTALL NEW DOUBLE WALL INSULATED DUCT ACCESS

DOOR FOR MAINTENANCE NEXT TO EACH SMOKE DETECTOR.

WELL

TEMPERATURE

SENSOR

WELL

TEMPERATURE

SENSOR

WELL

TEMPERATURE

SENSOR

WELL

TEMPERATURE

SENSOR

FLOW

SWITCH

FLOW

SWITCH

OTS-1

AI

5 3

4 6

BI

DPS-2

CHWP-2

1 4

BO

4 1

BI

4 2

BI

ALARM

STATUS

ALARM

4 3

BI

4 4

BI

STATUS

CH-2

COMPRESSOR

EVAPORATOR

WTS-1

AI

5 1

WTS-2

AI

5 2

COMPRESSOR

EVAPORATOR

CH-1

C O

N T

R O

L

P

A N

E L

C O

N T

R O

L

P

A N

E L

B0

1 3

CHWP-1

HL

DPS-1

4 5

BI

MS

S/S

RIB-2

MS

S/S

RIB-1

HL

UPCM

EXISTING

ENC-1

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-301

PHOENIX CHILLER

PLANT CONTROLS

DLH

DLH

TJF

THE BAS WORK INDICATED ON THIS DRAWING IS NOT

INCLUDED IN THIS PROJECT. THIS WORK IS BEING

PERFORMED AS PART OF ANOTHER PROJECT. THIS

CONTRACTOR SHALL INTERFACE WITH THE BUILDING

AUTOMATION SYSTEM FULLY INCORPORATING THE

CONTROLS INDICATED AS WELL AS VERIFYING THAT THE

CONTROLS PORTION OF TESTING AND BALANCING AND

COMMISSIONING OF THE NEW CHILLER INSTALLATION

INDICATED IS INCLUDED EITHER IN THE ORIGINAL CHILLER

CONSTRUCTION BID PACKAGE OR THIS BID PACKAGE.

NOTE:

FOR INFORMATION ONLY

KEYED NOTES

REMOVE AND REPLACE EXISTING SENSOR CONNECT TO NEW BAS SYSTEM.

REMOVE AND REPLACE EXISTING DAMPER CONTROLLER CONNECT TO NEW BAS SYSTEM.

REMOVE EXISTING DAMPER ACTUATOR AND REPLACE WITH NEW 24v ACTUATOR WITH POSITION SENSOR.

REMOVE AND REPLACE EXISTING DAMPER WITH NEW LOW LEAKAGE F/S DAMPER. CONTRACTOR SHALL

VERIFY SIZE OF DAMPER.

REMOVE AND REPLACE EXISTING CHILLED WATER CONTROL VALVE. CONNECT TO NEW BAS SYSTEM.

REMOVE EXISTING DAMPER AND ACTUATOR. SEAL SUPPLY AIR DUCT OPENING AS SHOWN.

REMOVE AND REPLACE EXISTING EDH. CONNECT CONTROLS TO NEW BAS.

EA

NO

3 3

AO

1 5

B0

M

EP-2

HL

DPS-2

5 3

BI

EA/RA

5 2

AI

5 1

AI

1 6

B0

M

1 4

B0

EP-1

SD-1EDH-1

3 1

AO

4 4

BI

L H

DPS-1

4 1

AI

ATS-1

C

C

LH

DPT-1

4 5

AI

ATS-2

4 2

AI

ATS-3

4 3

AI

4 6

AI

LH

DPT-2DM-1

1 3

B0

TYPICAL FOR 12

1EA/RTU-C1 THRU RTU-C4

4EA/RTU-C5 & RTU-C6

S/S

1 1

B0

RIB-1

MS

EA NC EA

S/S

MS

TYPICAL FOR 4

MS

S/S

RIB-2

RIB-X

2 1

BO

TYPICAL FOR 4

2EA/RTU-C5&C6

TO SPACENCOA

EF#

SMOKE EF#

RTU#

C12 C11 C13 C12 C11 C10

C16 C17 C15 C14 C19 C18

EXHAUST FAN INTERLOCK SCHEDULE

C1 C2 C3 C4 C5 C6

NO SA

NO NC

NOOA

C O

O L

I N

G

C

O I L

C H

W V

F I L T

E R

C

C

C O

O L

I N

G

C

O I L

F I L T

E R

NO

AO

3 2 C

H W

S

C H

W R

C H

W S

C H

W R

C H

W V

M

C M

B

2 3

1 1 1

1 1

2 3

2 3

2 3

2 3

2 3

M

M

M

M

M

SUPPLY AIR FAN

SMOKE EXHAUST FAN

P S

A1

EA/RA GRILLE

1 EA/RTU-C1, C2, C3, C4.

RTU-C1 - EF-13

RTU-C2 - EF-12

RTU-C3 - EF-11

RTU-C4 - EF-10

REMOVE AND REPLACE EXISTING SMOKE EXHAUST FAN.

INSTALL NEW STATIC PRESSURE SENSOR. EXTEND PRESSURE SENSOR BELOW

EXHAUST/RETURN AIR GRILLE IN ORDER TO SENSE THE SPACE PRESSURE.

RTU-C1 THRU RTU-C6 CONTROL DIAGRAM

SEF-C14 THRU SEF -C19 CONTROL DIAGRAM SMOKE EXHAUST MAKE-UP AIR CONTROL DIAGRAM

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-302

PHOENIX C1 THRU C6

SEQUENCE, OVERVIEW

DLH

DLH

AND PARTS LIST

REPLACE EXISTING DAMPER ACTUATOR WITH NEW 120V MOTORIZED DDC ACTUATOR.

REPLACE EXISTING DEVICE WITH NEW DEVICE CONNECTED TO BMS.

REPLACE EXISTING VALVE ACTUATOR WITN NEW 24V MOTORZIED DDC ACTUATOR.

REPLACE EXISTING CONTROLLER WITH NEW METASYS DDC CONTROLLER. REUSE AVAILABLE WIRING.

REMOVE EXISTING DEVICE. REPLACE WITH 24V TRANSFORMER.

REPLACE EXISTING DEVICE WITH NEW DIGITAL FREEZESTAT, CONNECTED TO BMS.

KEYED NOTES

MM

M

M

EP-2

3 2

B0

C

C

H L

DPS-1

FZT-1

R-1

2 3

BI

2 1

BI

SD-1

HL

DPS-2

2 4

BI

DTS-2

5 AI2

AI

RIB-1

MS

3 1

B0

CP-1

M

3 4

B0

3 5

B0

DTS-1

5 ZN

AI

M

EP-1

1 24

B0

SARA

OA

F I L

T E

R

C O

O L I N

G

C

O I L

C V

C H

W S

C H

W R

NONO

NC

RTU-C7 AND RTU-C8 CONTROL DIAGRAM

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-303

PHOENIX RTU-C7 AND C8

SEQUENCE, OVERVIEW

DLH

DLH

REPLACE EXISTING DAMPER ACTUATOR WITH NEW 120V MOTORIZED DDC ACTUATOR.

REPLACE EXISTING DEVICE WITH NEW DEVICE CONNECTED TO BMS.

REPLACE EXISTING VALVE ACTUATOR WITN NEW 24V MOTORZIED DDC ACTUATOR.

REPLACE EXISTING CONTROLLER WITH NEW METASYS DDC CONTROLLER. REUSE AVAILABLE WIRING.

REMOVE EXISTING DEVICE. REPLACE WITH 24V TRANSFORMER.

REPLACE EXISTING STAGED HEAT FOR NEW SCR HEATER.

KEYED NOTES

MM

M

M

EP-2

3 2

B0

C

C

H L

DPS-1

FZT-1

R-1

2 3

BI

2 1

BI

STAGE-2

RIBRIB

STAGE-1

RIB

STAGE-3

SD-1 EDH-1

HL

DPS-2

2 4

BI

3 10

B0

3 7

B0

3 8

B0

DTS-2

5 AI2

AI

RIB-1

MS

3 1

B0

CP-1

M

3 4

B0

3 5

B0

DTS-1

5 ZN

AI

M

EP-1

1 24

B0

SARA

OA

F I L

T E

R

C O

O L

I N

G

C

O I L

C V

NONO

NC

AHU-1 THRU AHU-7 CONTROL DIAGRAM

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-304

PHOENIX AHU-1 THRU 7

SEQUENCE, OVERVIEW

DLH

DLH

SA

DTS-2

5 AI2

AI

MS

RIB-1

5 J11

B0

EDH-1

STAGE-1

RIB

5 J9

B0

L H

DPS-2

4 1

BI

DTS-1

3 ZN

AI

RA

OA

M

CP-1

J1 1

AO

M

M

NO

NC

REMOVE EXISTING PNEUMATIC

ACTUATORS AND REPLACE WITH

NEW ELECTRONIC ACTUATORS,

CONNECT TO BMS

SF-1 THRU SF-8 CONTROL DIAGRAM

SD-1

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-305

PHOENIX SF-1 THRU 8

SEQUENCE, OVERVIEW

DLH

DLH

PL-1 GPL-3 G PL-5 G PL-6 GPL-4 G PL-2 G

EF-17 ON EF-14 ONEF-16 ON EF-18 ON EF-19 ONEF-15 ON

ON

OFF

AUTO AUTO

OFF

ON

AUTO

OFF

ON

AUTO

OFF

ON

(RTU-2)

S-2

(RTU-1)

S-1

(RTU-3)

S-3

ZONE 2

PRIMARY SMOKE PURGE PANEL

ZONE 4ZONE 1 ZONE 5ZONE 3

LOCATED IN CONTROL. ROOM B-105LOCATED IN COMM. ROOM C-110

EXISTING POWER 120VAC

EXISTING

FACP

FSCS

UPCM-1

120VAC

POWER

TRACER SUMMIT

BUILDING CONTROL UNIT

PHOENIX

BCU

DETAIL

COMM RISER

SEE PAGE 2 FOR

120VAC

POWER

PL-9 G PL-10 G PL-8 G PL-7 G PL-11 G PL-12 G

EF-16 ON EF-15 ONEF-17 ON EF-14 ON EF-18 ON EF-19 ON

MAN

S-7

(RTU-1)

S-8

(RTU-2)

S-9

(RTU-3)

S-10

(RTU-4)

MAN MAN MAN

AUTO AUTO AUTO AUTO AUTO

ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5

EXISTING POWER 120VAC

SECONDARY SMOKE PURGE PANEL

POWER

120VAC

FSCS

UPCM-8

UNIVERSAL

PROGRAMMABLE CONTROL MODULE

UNIVERSAL

PROGRAMMABLE CONTROL MODULE

REMOVE PRIMARY SMOKE PURGE

PANEL IN ITS ENTIRETY.

REMOVE SECONDARY SMOKE PURGE

PANEL IN ITS ENTIRETY.

SEQUENCE OF OPERATION - SF A1 - A8

NORMAL

OPERATION

OCCUPIED MODE

HEATING MODE

UNOCCUPIED

MODE

EMERGENCY

DURING NORMAL OPERATION EACH SUPPLY FAN SHALL BE AUTOMATICALLY CONTROLLED BY EACH INDIVIDUAL

DDC SF EQUIPMENT CONTROLLER. THE INDIVIDUAL CONTROLLER AND THE DDC SYSTEM SHALL BE

PROGRAMMED TO ALLOW EACH SF TO FUNCTION ACCORDING TO THE FOLLOWING SEQUENCE. EACH SF

SHALL BE PROVIDED WITH A CONTROL PANEL THAT WILL INCLUDE AT A MINIMUM:

1. H-O-A SWITCH

2. LED LIGHTS TO INDICATE THE POSITION OF THE H-O-A SWITCH

DURING OCCUPIED MODE OPERATION, THE SF SHALL RECEIVE A SIGNAL TO START FROM THE CONTROLLER

OR THE BAS SYSTEM. THE NORMALLY CLOSED OA DAMPER SHALL BE OPENED AND THE RA DAMPER SHALL BE

CLOSED. VERIFY THE RETURN AIR DAMPER IS CLOSED AND THE SUPPLY AIR DAMPER ARE OPEN THEN

ENERGIZE THE SUPPLY AIR FAN. THE STATUS OF THE SF SUPPLY AIR FAN SHALL BE MONITORED BY A

DIFFERENTIAL PRESSURE SWITCH ACROSS THE FAN. IF A FAN IS COMMANDED TO BE ENERGIZED BUT CAN

NOT BE VERIFIED BY THE DIFFERENTIAL PRESSURE SWITCH, AN ALARM SHALL BE SENT TO THE BAS SYSTEM

INDICATING THE FAN IS ABNORMALLY OFF. THE UNIT CONTROLS SHALL MODULATE THE OA DAMPER AND THE

RA DAMPER TO CONTROL THE RETURN AIR TEMPERATURE TO 80 DEG. F.

IF THE RETURN AIR TEMPERATURE FALLS BELOW 70 DEG. F. THE ELECTRIC HEAT SHALL BE ENGAGED TO

MAINTAIN THE RETURN AIR TEMPERATURE AT 70 DEG. F.

THE SF SUPPLY AIR FAN SHALL BE DE-ENERGIZED DURING UNOCCUPIED MODE. THE OA DAMPER SHALL BE

CLOSED AND THE ELECTRIC HEAT SHALL BE DE-ENERGIZED. THE RA DAMPER SHALL BE OPENED.

UPON RECEIVING A FIRE ALARM SIGNAL FOR BUILDING A, THE UNIT SUPPLY AIR FAN SHALL BE DE-ENERGIZED, THE OA DAMPER SHALL BE CLOSED AND THE RA DAMPER CLOSED.

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-306

SMOKE CONTROL SYSTEM

SEQUENCE, OVERVIEW

DLH

DLH

AND PART LIST

SMOKE ZONE 1

2. PROVIDE INTERFACES OF THIS CONTROL PANEL WITH THE DDC HVAC BUILDING CONTROL SYSTEM AND WITH THE BUILDING FIRE ALARM SYSTEM, TO ACCOMPLISH ALL OPERATIONAL MOOES AND SEQUENCES OF OPERATION REQUIRED BY THE CONTRACT DOCUMENTS.

3. WITH SWITCH IN AUTO POSITION, SYSTEM SHALL BE ENERGIZED AUTOMATICALLY BY SIGNAL FROM THE FIRE ALARM SYSTEM.

4. WITH SWITCH IN OFF POSITION, SMOKE ZONE SHALL BE MANUALLY DE-ENERGIZED OUT OF SMOKE MODE FOR FIRE DEPARTMENT OVERRIDE. AND SMOKE CONTROL FANS SHALL STOP AND ASSOCIATED DAMPERS SHALL CLOSE.

5. WITH SWITCH IN HAND POSITION, SMOKE ZONE SHALL BE MANUALLY ENERGIZED IN SMOKE EXHAUST MODE FOR FIRE DEPARTMENT OVERRIDE, OR FOR SYSTEM TESTING.

NOTES:

FIRE FIGHTERS SMOKE CONTROL PANEL

NOT TO SCALE

FIRE FIGHTERS SMOKE CONTROL PANEL

FOR FIRE DEPARTMENT MANUAL OVERRIDE CONTROL, AND TESTING

CONTROLS FLOW DIAGRAM

NOT TO SCALE

I/O PANEL 1

UL864

FIRE FIGHTERS

SMOKE CONTROL

PANEL

FIRE ALARM

PANEL

(BY DIV. 16)

DUCT DETECTOR

FLOW SWITCH

PULL STATION

ZONE 1

ZONE 2

ZONE 3

ZONE 4

ZONE 5

BMS

FA

UL 864 FIELD

EQUIPMENT

CONTROLLER

UL 864

NETWORK

ENGINE

UL 864 FIELD

EQUIPMENT

CONTROLLER

METASYS

USER

INTERFACE

METASYS

ADS SERVER

MAINTENANCE

SMOKE CONTROL

OVERRIDE PANEL

NOTES:

1. FIRE FIGHTERS SMOKE CONTROL PANEL SHALL HAVE HIGHEST LEVEL AUTHORITY TO OVERRIDE ALL SMOKE CONTROL FUNCTIONS.

2. PROGRAMMED FIRE EVENT AND SMOKE CONTROL ACTIONS SHALL HAVE SECONDARY LEVEL AUTHORITY TO SMOKE CONTROL FUNCTIONS.

3. MAINTENANCE SMOKE EXTRACT CONTROL PANEL SHALL HAVE TERTIARY LEVEL AUTHORITY TO SMOKE CONTROL FUNCTIONS, WHICH SHALL

BE USED FOR POST-EVENT MAINTENANCE, TESTING AND BALANCING DUTIES.

1. PROVIDE A UL 864 LISTED PANEL ASSEMBLY THAT PROVIDE THE FOLLOWING FUNCTIONS AND CONTROLABILITY. THIS PANEL SHALL PROVIDE OVERRIDE AUTHORITY OF ALL AUTOMATIC FIRE ALARM SMOKE CONTROL OPERATIONS FOR MANUAL USE BY THE FIRE DEPARTMENT.

PROVIDE SIGNAGE AND LOCKING KEY PER FIRE DEPARTMENT.

6. PROVIDE THE FOLLOWING COLORS FOR THE POSITION AND STATUS LIGHTS:

H-O-A POSITION: HAND - WHITE

OFF - RED

AUTO - GREEN

ZONE STATUS: OFF - RED

ON - GREEN

FAULT - AMBER

7. PROVIDE COLOR GRAPHIC OF EACH FLOOR, IDENTIFYING SMOKE ZONES AS SHOWN ABOVE. EACH GRAPHIC SHALL CLEARLY IDENTIFY ZONES THAT ARE IN ACTIVE FIRE ALARM, WHICH ZONES ARE IN SMOKE EXHAUST MODE, AS WELL AS CURRENT

NEGATIVE/POSITIVE PRESSURE RELATIONSHIPS.

RTU-C1

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 2

RTU-C2

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 4

RTU-C4

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 3

RTU-C3

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 5

RTU-C5 & RTU-C6

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

PILOT LIGHT WITH LABEL, TYPICAL

MANUAL ROTARY HOA SWITCH WITH LABEL

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-307

FIREFIGHTER SMOKE

CONTROL PANEL

DLH

1. PROVIDE INTERFACES OF THIS CONTROL PANEL WITH THE DDC HVAC BUILDING CONTROL SYSTEM AND WITH THE BUILDING FIRE ALARM SYSTEM, TO ACCOMPLISH ALL OPERATIONAL MOOES AND SEQUENCES OF OPERATION REQUIRED BY THE CONTRACT DOCUMENTS.

2. WITH SWITCH IN AUTO POSITION, SYSTEM SHALL BE ENERGIZED AUTOMATICALLY BY SIGNAL FROM THE FIRE ALARM SYSTEM.

3. WITH SWITCH IN OFF POSITION, SMOKE ZONE SHALL BE MANUALLY DE-ENERGIZED OUT OF SMOKE MODE. AND SMOKE CONTROL FANS SHALL STOP AND ASSOCIATED DAMPERS SHALL CLOSE.

4. WITH SWITCH IN HAND POSITION, SMOKE ZONE SHALL BE MANUALLY ENERGIZED IN SMOKE EXHAUST MODE FOR SMOKE PURGE, OR FOR SYSTEM TESTING.

NOTES:

MAINTENANCE SMOKE EXTRACT CONTROL PANEL

NOT TO SCALE

MAINTENANCE SMOKE EXTRACT CONTROL PANEL

FOR POST-EVENT MAINTENANCE, TESTING AND BALANCING

5. PROVIDE THE FOLLOWING COLORS FOR THE POSITION AND STATUS LIGHTS:

H-O-A POSITION: HAND - WHITE

OFF - RED

AUTO - GREEN

ZONE STATUS: OFF - RED

ON - GREEN

FAULT - AMBER

6. PROVIDE COLOR GRAPHIC OF EACH FLOOR, IDENTIFYING SMOKE ZONES AS SHOWN ABOVE. EACH GRAPHIC SHALL CLEARLY IDENTIFY ZONES THAT ARE IN ACTIVE FIRE ALARM, WHICH ZONES ARE IN SMOKE EXHAUST MODE, AS WELL AS CURRENT

NEGATIVE/POSITIVE PRESSURE RELATIONSHIPS.

SMOKE ZONE 1

RTU-C1

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 2

RTU-C2

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 4

RTU-C4

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 3

RTU-C3

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

SMOKE ZONE 5

RTU-C5 & RTU-C6

HAND

OFF

AUTO

OFF

ZONE STATUS

ON FAULT

PILOT LIGHT WITH LABEL, TYPICAL

MANUAL ROTARY HOA SWITCH WITH LABEL

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-308

MAINTENANCE SMOKE

EXTRACT CONTROL PANEL

DLH

ROOF TOP UNIT SCHEDULE - EXISTING UNITS

G E

N E

R A

L

I N

F O

R M

A T

I O

N

MARK RTU-C1 RTU-C2 RTU-C3 RTU-C4 RTU-C5 RTU-C6 RTU-C7 RTU-C8

MANUFACTURER TRANE TRANE TRANE TRANE TRANE TRANE TRANE TRANE

SA (CFM)

4650 5000 5000 5000 2370 2370 3300 4190

OA (CFM)

1880 1880 1880 1880 730 730 400 565

RA (CFM)

2770 3120 3120 3120 1640 1640 2900 3625

TOTAL AIR (CFM)

4650 5000 5000 5000 2370 2370 3300 4190

ESP (IN. WG)

1.6 1.7 1.7 1.7 1.5 1.5 1.5 1.8

TSP (IN. WG)

4.03 4.31 4.31 4.31 3.59 3.59 4.19 4.28

RPM 1487 1542 1542 1542 1876 1876 1738 1569

MOTOR HP 7.5 7.5 7.5 7.5 3 3 5 7.5

VOLTAGE 460 460 460 460 460 460 460 460

PHASE 3 3 3 3 3 3 3 3

O A

C

O O

L I N

G

C O

I L

EAT (DB/WB DEG. F.)

88/79 88/79 88/79 88/79 88/79 88/79 88/79 88/79

LAT (DB/WB DEG. F.)

55/54.9 55/54.9 55/54.9 55/54.9 55/54.9 55/54.9 53/52.9 55/54.9

SENS (MBH)

69.5 69.5 69.5 69.5 27.0 27.0 15.7 20.9

TOTAL (MBH)

163.6 163.6 163.6 163.6 63.5 63.5 37.0 49.2

GPM 32.7 32.7 32.7 32.7 12.7 12.7 7.4 9.8

WPD (FT H20 MAX)

2.21 2.21 2.21 2.21 2.52 2.52 1.08 1.3

EWT/LWT (F)

45/55 45/55 45/55 45/55 45/55 45/55 45/55 45/55

AIR PD (IN H20

0.16 0.16 0.16 0.16 0.18 0.18 0.18 0.34

T O

T A

L

A

I R

C O

O L

I N

G

C

O I L

EAT (DB/WB DEG. F.)

67.1/61.3 67.1/61.6 67.1/61.3 67.1/61.3 68.8/62.2 68.8/62.2 72.6/62.1 72.3/62.0

LAT (DB/WB DEG. F.)

54.7/54.1 54.8/54.3 54.7/54.1 54.7/54.1 54.2/53.8 54.2/53.8 53.6/53.1 51.6/51.4

SENS (MBH)

63.6 67.6 63.6 63.6 38.1 38.1 69.0 95.4

TOTAL (MBH)

96.9 106.5 96.9 96.9 58.1 58.1 85.7 126.1

GPM 19.4 0.3 19.4 19.4 11.6 11.6 17.1 25.2

WPD (FT H20 MAX)

4.0 4.7 4.0 4.0 1.7 1.7 1.6 6.2

EWT/LWT (F)

45/55 45/55 45/55 45/55 45/55 45/55 45/55 45/55

AIR PD (IN H20

0.55 0.64 0.55 0.55 0.44 0.44 0.62 0.58

O A

F I L

T E

R

TYPE PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP.

THICKNESS 4" 4" 4" 4" 4" 4" 4" 4"

EFFICIENCY% 30 30 30 30 30 30 30 30

FRAME ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE

T O

T A

L

A I R

F I L

T E

R

TYPE PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP. PLEAT. DISP.

THICKNESS 4" 4" 4" 4" 4" 4" 4" 4"

EFFICIENCY% 30 30 30 30 30 30 30 30

FRAME ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE

H E

A T

I N

G

E Q

U I P

M E

N T

MARK EDH-C8 EDH-C9 EDH-C10 EDH-C11 EDH-C12 EDH-C13 EDH-C14 EDH-C15

MAX CFM 4650 5000 5000 5000 2370 2370 3300 4190

EAT/LAT (DEG. DB)

56.6/85.6 57.6/86.2 57.6/86.2 57.6/86.2 58.6/85.0 58.6/85.0 66.0/80.0 65.5/80.4

TOTAL KW 43 46 46 46 17 17 15 20

VOLTS 460 460 460 460 460 460 460 460

PHASE 3 3 3 3 3 3 3 3

STAGES SCR SCR SCR SCR SCR SCR SCR SCR

NOTES

1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3

NOTES

PROVIDE NEW JCI BAS CONTROLLER COMPATABLE WITH UL-864 SMOKE CONTROL SYSTEM FOR RTU 1, 2, 3, 4, 5, AND 6.

2 PROVIDE NEW JCI BAS CONTROLLER FOR RTU 7 AND 8

3 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.

EXHAUST FAN SCHEDULE - EXISTING EQUIPMENT

MARK EF-A1 EF-A2 EF-A3 EF-A4 EF-A5 EF-A6 EF-A7 EF-A8 EF-B9 EF-C10 EF-C11 EF-C12 EF-C13 EF-A20 EF-A21

SERVICE

CAR

EXST

Y0-TECH

EXHAUST

Y0-TECH

EXHAUST

Y0-TECH

EXHAUST

Y0-TECH

EXHAUST

Y0-TECH

EXHAUST

VO-TECH

EXHAUST

Y0-TECH

EXHAUST

BLDG.B

RESTRMS

NW POD NE POD SE POD SW POD

BLDG A

MECH RM

FIRE PMP

ROOM

MANUF. CAR-MON

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

COOK COOK COOK COOK

GREEN

HECK

GREEN

HECK

MODEL 10F GB120-4 GB120-4 GB-90-4 GB120-3 GB-70-4 GB-90-4 GB-90-4 BCF-106

ACEB

ACEB

ACEB

ACEB

GB-90-4 GB-140-3

TYPE CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT CENT

AIR FLOW

RATE (CFM)

1200 1000 1000 750 1300 150 750 750 410 1550 1750 1650 1600 1000 2100

STATIC PRESS

(IN. W.C)

4.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.75 0.9 0.9 0.9 0.9 0.125 0.125

MAX FAN RPM 1725 1180 1410 1410 1550 1290 1410 1410 1811 1425 1237 1469 1446 1410 1170

H.P. 2 0.25 0.25 0.25 0.33 0.25 0.25 0.25 0.25 0.5 0.5 0.5 0.5 0.25 0.33

VOLTS 460 120 120 120 120 120 120 120 120 120 120 120 120 120 120

PHASE 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

NOTES

1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5

NOTES

1 CONNECT ALL EXHAUST FANS TO NEW JCI BAS SYSTEM

2 EXHAUST FANS EF-A1 THROUGH AND INCLUDING EF-A8 SHALL BE ENERGIZED BY EXISTING WALL SWITCH

EXHAUST FANS EF-A1 THROUGH EF-A8, EF-B9, EF-A20 AND EF-A21 SHALL BE MONITORED FOR STATUS AND

ABNORMAL OFF ONLY. ABNORMAL OFF SHALL GENERATE AN ALARM IN THE BAS SYSTEM.

4 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.

5 PROVIDED FOR SIZING INFORMATION ONLY.

SUPPLY FAN SCHEDULE - EXISTING EQUIPMENT

G E

N E

R A

L

I N

F O

R M

A T

I O

N

MARK SF-A1 SF-A2 SF-A3 SF-A4 SF-A5 SF-A6 SF-A7 SF-A8

SERVICE

CLIMATE

CHANGER

CLIMATE

CHANGER

CLIMATE

CHANGER

CLIMATE

CHANGER

CLIMATE

CHANGER

CLIMATE

CHANGER

CLIMATE

CHANGER

CLIMATE

CHANGER

MANUF

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

GREEN

HECK

MODEL GB-140-3 GB-140-3 GB-140-3 GB-140-3 GB-140-3 GB-140-3 GB-140-3 GB-140-3

TYPE CENT CENT CENT CENT CENT CENT CENT CENT

AIR FLOW

RATE (CFM)

3300 3300 3300 3300 3300 3300 3300 3300

STATIC PRESS

(IN. W.C)

0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5

MAX FAN RPM 482 482 482 482 482 482 482 482

H.P. 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75

VOLTS 460 460 460 460 460 460 460 460

PHASE 3 3 3 3 3 3 3 3

MARK EDH-A16 EDH-A17 EDH-A18 EDH-A19 EDH-A20 EDH-A21 EDH-A22 EDH-A23

AIR FLOW

RATE (CFM)

3300 3300 3300 3300 3300 3300 3300 3300

EAT/LAT

(DEG. F.)

52/86 52/86 52/86 52/86 52/86 52/86 52/86 52/86

TOTAL KW 16 16 16 16 16 16 16 16

VOLTS 460 460 460 460 460 460 460 460

PHASE 3 3 3 3 3 3 3 3

STAGES SCR SCR SCR SCR SCR SCR SCR SCR

NOTES

1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3

NOTES

1 CONNECT ALL SUPPLY FANS TO NEW JCI BAS SYSTEM

2 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.

3 PROVIDED FOR SIZING INFORMATION ONLY.

SPLIT AC UNIT SCHEDULE - EXISTING EQUIPMENT

MARK MANUF

AIR

HANDLER

MODEL

COND.

MODEL

SUPPLY FAN COOLING AIR UNIT COND.

NOTES

TOTAL

CFM

OA

CFM

COND.

EAT

(DEG. F)

EVAP EAT

DB/WB

(DEG. F)

EVAP LAT

DB/WB

(DEG. F)

TOT CAP

(MBH)

SENS CAP

(MBH)

STAGES MIN EER

VOLTS/PH/

HZ

VOLTS/PH/

HZ

AC-A1 CU-A1 MITSUBISHI PUYA-12 PLAA-12 320 0 95 75/65 52/52 12 10.32 1 13.8 208/1/60 208/1/60

AC-A2 CU-A2

NOTES

1 CONNECT ALL EQUIPMENT TO NEW JCI BAS SYSTEM

2 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.

3 PROVIDED FOR SIZING INFORMATION ONLY.

AHU SCHEDULE - EXISTING UNITS

GENERAL INFORMATION COOLING COIL HEATING EQUIPMENT

NOTES

MARK MANUF.

FAN CFM

ESP

(IN WG)

TSP

(IN WG)

MOTOR

HP

MOTOR

BHP

VOLTS/

PH/HZ

FAN

OUTLET

EAT

(DB/WB)

LAT

(DB/WB)

COOLING

CAPACITY

CHILLED

WATER

FLOW

RATE

PRESSURE DROP

CW

VALVE

MARK CFM

EAT/LAT TOTAL

VOLTS PHASE STAGES

TOTAL

SENS

(MBH)

TOT

(MBH)

EWT/LWT

(F.)

(GPM)

FLUID

(FT)

AIR (IN)

TYPE

(DEG. F)

KW

AHU-A1 TRANE 1550 750 1.5 1.84 1 0.77 460/3/60 14x14 85/71.8 56.6 98.8 45/55 19.7 3.9 0.3 2-WAY EDH-A1 1550 52/85.0 15 460 3 SCR 1,2,3

AHU-A2 TRANE 1500 750 1.5 1.82 1 0.74 460/3/60 14x14 86.1/72.3 52/51.84 56.7 98.6 45/55 19.7 3.9 0.3 2-WAY EDH-A2 1500 52/86.1 15 460 3 SCR 1,2,3

AHU-A3 TRANE 2330 1350 1.75 2.51 2 1.62 460/3/60 14x14 86.1/73.2 52/51.9 87.37 160.05 45/55 31.9 8.9 0.6 2-WAY EDH-A3 2330 52/86.1 26 460 3 SCR 1,2,3

AHU-A4 TRANE 2700 600 1.5 2.46 2.5 1.99 460/3/60 14x14 80.2/67 52/51.9 83.92 122.98 45/55 24.5 5.6 0.8 2-WAY EDH-A4 2700 52/80.2 17 460 3 SCR 1,2,3

AHU-A5 TRANE 1550 1000 2.1 2.5 1.5 0.96 460/3/60 14x14 86.9/72.8 52/51.9 60.7 103.4 45/55 24.1 2.6 0.4 2-WAY EDH-A5 1550 52/86.9 19 460 3 SCR 1,2,3

AHU-A6 TRANE 1720 800 1.5 1.82 1 0.74 460/3/60 14x14 86.3/73.2 52/51.9 57.1 104.1 45/55 20.7 4.3 0.3 2-WAY EDH-A6 1720 52/86.3 17 460 3 SCR 1,2,3

AHU-A7 TRANE 3700 1000 1.75 2.22 2 1.78 460/3/60 18x18 81.7/68.5 52/51.9 95.10 147.9 45/55 29.5 3.8 0.4 2-WAY EDH-A7 3700 52/81.7 26 460 3 SCR 1,2,3

NOTES

PROVIDE NEW JCI BAS CONTROLLER FOR FOR ALL AHU'S

2 REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND ADDITIONAL SCOPE OF WORK.

3 PROVIDED FOR SIZING INFORMATION ONLY.

EXHAUST FAN SCHEDULE - NEW EQUIPMENT

MARK SEF-C14 SEF-C15 SEF-C16 SEF-C17 SEF-C18 SEF-C19

SERVICE

NW POD

SMOKE

NE POD

SMOKE

SE POD

SMOKE

SW POD

SMOKE

CNE CSW

MANUF. COOK COOK COOK COOK COOK COOK

MODEL

ACRUB

ACRUB

ACRUB

ACRUB

ACRUB

ACRUB

TYPE CENT CENT CENT CENT CENT CENT

AIR FLOW

RATE (CFM)

5800 5800 5800 5800 2000 2000

STATIC PRESS

(IN. W.C)

0.75 0.75 0.75 0.75 0.5 0.5

MAX FAN RPM 539 539 539 539 683 683

H.P. 1.5 1.5 1.5 1.5 0.33 0.33

VOLTS 460 460 460 460 460 460

PHASE 3 3 3 3 1 1

NOTES

1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5 1,2,3,4,5

NOTES

1 CONNECT ALL EXHAUST FANS TO NEW JCI BAS SYSTEM

2 INSTALL VFD FOR EACH EXHAUST FAN.

3 EACH FAN SHALL BE RATED FOR SMOKE CONTROL SERVICE.

REFER TO OTHER DRAWINGS FOR SEQUENCE OF OPERATIONS AND

ADDITIONAL SCOPE OF WORK.

5 PROVIDED FOR SIZING INFORMATION ONLY.

Sheet Number:Designed By:

JOB No.100071175

Phase:

Checked By:

Date Issued:DECEMBER 14, 2021

PROFESSIONAL SEALS:

CLIENT:

SHEET TITLE:

ISSUE LOG

CONSULTANT:

QC Review:

SHEET INFORMATION:

PROJECT NAME:

482 SOUTH KELLER ROAD

ORLANDO, FL 32810

PHONE: 407.647.7275 FAX: 407.740.8958

No. Date Description

O ra ng e

Co un ty C or re ct io ns

3r d St re et

, O rla nd o, F L

100% CD

Ph oe ni x

Bu ild in g

Re pl ac em en t o f t he

S m ok e

Co nt ro l a nd B ui ld in g

Au to m at io n

Sy st

M-401

HVAC SCHEDULES

DLH

SEQUENCE OF OPERATION - RTU C1 - C6

NORMAL

OPERATION

OA CW COIL

VALVE

DURING NORMAL OPERATION EACH RTU SHALL BE AUTOMATICALLY CONTROLLED BY EACH INDIVIDUAL DDC

RTU EQUIPMENT CONTROLLER. THE INDIVIDUAL CONTROLLER AND THE DDC SYSTEM SHALL BE

PROGRAMMED TO ALLOW EACH RTU TO FUNCTION ACCORDING TO THE FOLLOWING SEQUENCE. EACH RTU

SHALL BE PROVIDED WITH A CONTROL PANEL THAT WILL INCLUDE AT A MINIMUM:

1. H-O-A SWITCH

2. LED LIGHTS TO INDICATE THE POSITION OF THE H-O-A SWITCH

DURING NORMAL OPERATION, THE RTU SHALL RECEIVE A SIGNAL TO START FROM THE CONTROLLER OR THE

BAS SYSTEM. THE NORMALLY CLOSED OA DAMPER SHALL BE OPENED TO THE POSITION SET BY THE TEST

AND BALANCE CONTRACTOR DURING THE T&B OF THE SYSTEM (MIN. OA SET POINT). AT THE SAME TIME, THE

NORMALLY CLOSED DAMPER INCLUDED WITH THE TOILET AND SHOWER EXHAUST FAN INTERCONNECTED TO

THE RTU SHALL ALSO BE OPENED. VERIFY THE NORMALLY OPEN RETURN AIR DAMPER AND SUPPLY AIR

DAMPER ARE OPEN. AFTER A DELAY OF 20 SECONDS (ADJ.) THE RTU SUPPLY AIR FAN AND THE ASSOCIATED

TOILET AND SHOWER EXHAUST FAN INTERCONNECTED WITH THE RTU SHALL BE ENERGIZED. THE STATUS OF

THE RTU SUPPLY AIR FAN AND THE TOILET EXHAUST FAN SHALL BE MONITORED BY A DIFFERENTIAL

PRESSURE SWITCH ACROSS EACH FAN. IF A FAN IS COMMANDED TO BE ENERGIZED BUT CAN NOT BE

VERIFIED BY THE DIFFERENTIAL PRESSURE SWITCH, AN ALARM SHALL BE SENT TO THE BAS SYSTEM

INDICATING THE FAN IS ABNORMALLY OFF. IF THE NORMALLY OPEN RETURN AIR AND/OR SUPPLY AIR DAMPER

ARE NOT OPEN, THE BAS SHALL OPEN THE DAMPERS PRIOR TO ENERGIZING THE SUPPLY AIR FAN.

THE OA CW COIL VALVE SHALL BE UTILIZED TO REDUCE THE INCOMMING OA TEMPERATURE TO 53 DEG. F

(ADJ.). THE OA CW COIL VALVE IS A MODULATING THREE WAY VALVE. BETWEEN OUTSIDE AIR

TEMPERATURES OF 38 DEG. F. (ADJ.) AND 53 DEG. F. (ADJ.) THE OA CW COIL VALVE SHALL BE SHUT OFF.

WHEN THE OA AIR TEMPERATURE RISES ABOVE 53 DEG. F. (ADJ.) THE OA CW COIL VALVE SHALL MODULATE

TO CONTROL THE OA AIR TEMPERATURE DOWNSTREAM OF THE OA CW COIL TO 53 DEG. F. (ADJ.). IF THE

OUTSIDE AIR TEMPERATURE FALLS TO 38 DEG. F. (ADJ.) OR LOWER, THE OA CW COIL VALVE SHALL BE OPENED

TO THE COIL 100% UNTIL THE OA TEMPERATURE RISES ABOVE 40 DEG. F. (ADJ.) AT WHICH TIME THE VALVE

SHALL BE CLOSED.

MAIN CW COIL

VALVE

HEATING

CONTROL

LOW MIXED AIR

TEMPERATURE

LOW RA

TEMPERATURE

THE MAIN CW COIL VALVE IS A MODULATING THREE WAY VALVE. THE MAIN CW VALVE SHALL BE CLOSED

WHEN THE MIXED AIR TEMPERATURE IS 52 DEG. F. (ADJ.) OR BELOW. THE MAIN CW COIL VALVE SHALL

MODULATE TO MAINTAIN THE RA TEMPERATURE OF 74 DEG. F. (ADJ.).

T…