1. REFERENCE: June 16, 2016 - Buy American Act Waiver – Mexico: Page 2, item number

QUESTION: Page 2, item number 5 states that CRI greater than or equal to 70. The 79K39947 Specification for LF3 and LF4 (page 109, 2.1.3.h and page 111, 2.1.4.h respectively) states: CRI greater than or equal to 75. This was not changed in any amendment to date. Will there be an amendment to 79K39947 to reflect this?

ANSWER: For the CRI of the subject fixtures in the BAA, the value shall be equal to or greater than 75 (to match with the specification).

2. REFERENCE: June 16, 2016 - Buy American Act Waiver – Mexico: Page 2, item number

QUESTION: Page 2, paragraph 2 states that the Flextronics units were found to meet the requirements for fixture types LF3 and LF4, but the CRI for the model listed in the basis of design in the 79K39947 Specification for LF3 and LF4 (page 110, 2.1.3.r.3, and page 111, 2.1.4.r.3 respectively) is 70. This does not meet the specified requirements; how is the statement in paragraph 2 valid?

ANSWER: For the CRI of the subject fixtures in the BAA, the value shall be equal to or greater than 75 (to match with the specification).

Additionally, we will clarify the CCT value, item number 4 in the noted list of the BAA, as follows: as noted in the BAA, the CCT is shown as 4000K – 5000K. To clarify, and match the value in the specification, the CCT requirement for the BAA is 4000K.