MISCELLANEOUS EQUIPMENT SCHEDULE
SECTION REFERENCE
ROOM NUMBER
DETAIL REFERENCE
XXXX
GENERAL MECHANICAL SYMBOLS
NOTE DESIGNATION
PLUMBING FIXTURE MARK
GRILLE OR DIFFUSER MARK
M
FD
A.D.
NOTE:
SUBMIT COMPLETE MANUFACTURER’S DATA FOR ALL MISCELLANEOUS EQUIPMENT SCHEDULED ON THIS SHEET AND COMPLY WITH ALL GENERAL SUBMITTAL REQUIREMENTS AS FOUND IN SECTION 15000 OF SPECIFICATIONS.
MECHANICAL LEGEND
ABBREV.
HWS
SYMBOL DESCRIPTION
HEATING WATER SUPPLY
HEATING WATER RETURNHWR
CHILLED WATER SUPPLYCHWS
CHILLED WATER RETURNCHWR
MEDIUM PRESSURE STEAMMPS
LOW PRESSURE STEAMLPS
PUMPED CONDENSATEPC
GRAVITY CONDENSATEC
DOMESTIC COLD WATERDCW
DOMESTIC HOT WATERDHW
DOMESTIC HOT WATER RECIRCDHWR
INDUSTRIAL COLD WATERICW
INDUSTRIAL HOT WATER RECIRCIHWR
DEIONIZED WATERDI
SPECIAL EQUIPMENT DRAIND
SANITARY SEWER SOIL AND WASTES
SANITARY SEWER VENTV
CARBON DIOXIDECO
COMPRESSED AIRA
NATURAL GASG
VACUUMVAC
SYMBOL
PIPE UP
DESCRIPTION
PIPE DOWN
FLEXIBLE PIPE
UNION
CONCENTRIC REDUCER
ECCENTRIC REDUCER
DIRECTION OF DOWNWARD
DIRECTION OF FLOW
VALVE IN VERTICAL PIPE
GATE VALVE
GLOBE VALVE
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
BACKFLOW PREVENTOR
BALANCE COCK &
THREE−WAY MOTORIZED VALVE
TWO−WAY MOTORIZED VALVE
SOLENOID VALVE
GAS COCK
PRESSURE REDUCING VALVE
OR
OR
OR
OR
OR
SHEET METAL DUCT
DESCRIPTIONSYMBOL
12"x8"
SHEET METAL DUCT
SPIN−IN VOLUME DAMPER
ACCESS DOOR
FIRE DAMPER
FLEXIBLE DUCT CONNECTION
TURNING VANES
MOTORIZED DAMPER
THERMOSTAT OR TEMPERATURE SENSOR
HUMIDITY OR DEW POINT SENSOR
POINT OF NEW CONNECTION
(FIRST FIGURE INDICATES FACING SIDE)
(EXTERIOR INSULATION)
BALANCE CFM
INDICATES UNIT TYPE
INDICATES UNIT NUMBER
MECHANICAL EQUIPMENT IDENTIFICATION
A.D. ACCESS DOOR
ABBREVIATIONS
ABOVE FINISH FLOORA.F.F.
APPROVEDAPP’D
CONNECTION OR CONNECTCONN.
DETAILDET.
EXISTING(E)
END ON MAINE.O.M.
EXHAUST AIREXH
FRESH AIRF.A.
FLOOR CLEAN−OUTFCO
FIRE EXTINGUISHER CABINETF.E.C.
SAFETY CABINET EXHAUST AIRSCEA
GENERAL EXHAUST AIRGEA
MECHANICAL (CONTRACTOR)MECH.
MANUFACTURERMFR
REFERENCEREF.
SUPPLY AIRSA
SHEET METALS.M.
PROJECT SPECIFICATIONSSPEC’S
TO EXISTING SYSTEM
(ELEVATION)
OR INCREASER
OR INCREASER
FLOW INDICATOR
PIPE PITCH
MANUAL AIR VENT
AUTOMATIC AIR VENT
RELIEF VALVE
FLOW SWITCH
PRESSURE GAUGE
HOSE BIBB
THERMOMETER
DIFFERENTIAL PRESSURE SWITCH
INSTRUMENT GAUGE WELL
IGW
OR
OR STRAINER
DESCRIPTIONSYMBOL
S.S. STAINLESS STEEL
INDUSTRIAL HOT WATERIHW
EQUIPMENT WHICH IS SPECIFIED OR SCHEDULED TO BE SUPPLIED WITH VIBRATION ISOLATION MUST BE SEPARATELY RESTRAINED TO MEET SEISMIC ZONE 3 REQUIREMENTS AS SPECIFIED IN 15090, OR MUST BE SUPPLIED WITH RESTRAINED ISOLATORS SPECIFICALLY SIZED AND SELECTED TO MEET ZONE 3 REQUIREMENTS.
TEMPERATURE CONTROL(S)T.C.
TYPICALTYP
AIR FILTER GAUGES: GAUGE SHALL BE DWYER MAGNAHELIC MODEL 2002 OR APPROVED EQUAL. FOUR INCH DIAL FACE, 0"−2.0" W.C. RANGE. PROVIDE WITH ADJUSTABLE SIGNAL FLAG OPTION AND MANUFACTURER’S AIR FILTER GAUGE INSTALLATION KIT INCLUDING MOUNTING HARDWARE, STATIC PRESSURE TIPS, TUBING, VALVES AND COMPRESSION FITTINGS.
AIR SEPARATOR AS−1 (HEATING WATER): SPIROTHERM "SPIROVENT" MICRO−BUBBLE AIR SEPARATOR WITH AUTOMATIC AIR VENT, 2−1/2" LINE SIZE, WITH FLANGED OR GROOVED CONNECTIONS AND BOTTOM THREADED CLEANOUT/DRAIN PLUG. UNIT SHALL
FEATURE 150 PSI PRESSURE RATING AT 270° F.
AIR SEPARATORS AS−2 (CHILLED WATER): SPIROTHERM "SPIROVENT" MICRO−BUBBLE AIR SEPARATOR WITH AUTOMATIC AIR VENT, 3" LINE SIZE, WITH FLANGED OR GROOVED CONNECTIONS AND BOTTOM THREADED CLEANOUT/DRAIN PLUG. UNIT SHALL FEATURE
150 PSI PRESSURE RATING AT 270° F.
EXPANSION TANKS ET−1 (HEATING WATER SYSTEM) : PARTIAL ACCEPTANCE CAPTIVE AIR EXPANSION TANK WITH REPLACEABLE BLADDER. TANK SHALL BE FACTORY CHARGED TO 30 PSIG WITH DRY NITROGEN AND SHALL BE SUITABLE FOR FLOOR MOUNTING OR HORIZONTAL SUSPENSION FROM CEILING. EXPANSION TANK SHALL BE TACO MODEL CX−30 WITH 8 GALLON TOTAL VOLUME
AND 5 GALLON ACCEPTANCE OR APPROVED EQUAL.
EXPANSION TANK ET−2 (CHILLED WATER SYSTEM) : PARTIAL ACCEPTANCE CAPTIVE AIR EXPANSION TANK WITH REPLACEABLE BLADDER. TANK SHALL BE FACTORY CHARGED TO 30 PSIG WITH DRY NITROGEN AND SHALL BE SUITABLE FOR FLOOR MOUNTING OR HORIZONTAL SUSPENSION FROM CEILING. EXPANSION TANK SHALL BE TACO MODEL CX−30 WITH 8 GALLON TOTAL VOLUME
AND 5 GALLON ACCEPTANCE OR APPROVED EQUAL.
FRESH AIR INTAKE PLENUM ACCESS DOOR (1 REQUIRED) : FRESH AIR PLENUM ACCESS DOORS SHALL BE INSULATED DOUBLE WALL CONSTRUCTED WITH 18 GAUGE SOLID GALVANIZED SHEET STEEL INNER AND OUTER PANELS, INSULATED CAVITY, 9"x9"x1/4" THICK SAFETY GLASS WINDOW WITH EXTRUDED ALUMINUM FRAME, SOLID METAL DOOR FRAME, BALL BEARING HINGES, DOUBLE GASKET DOOR SEALS AND LATCH/PULL TYPE DOOR LATCHES. NOMINAL DOOR THICKNESS SHALL BE 4". DIRECTION OF DOOR SWING SHALL BE AS INDICATED ON PLANS. PROVIDE DOORS AS MANUFACTURED BY METAL FORM/COMMERCIAL ACOUSTICS OR APPROVED EQUAL. DIMENSIONS FOR ALL DOORS SHALL BE 24" WIDE BY 66" TALL OR NEXT LARGER STANDARD SIZE.
GLYCOL SOLUTION FOR HEATING & CHILLED WATER SYSTEMS : SOLUTION SHALL BE FACTORY PREMIXED 40% PROPYLENE GLYCOL, 60% DISTILLED WATER, DOW CHEMICAL "DOW−FROST" (NO SUBSTITUTES). PROVIDE 200 GALLONS. TURN OVER SPARE GLYCOL TO OWNER FOR FUTURE USE. PROVIDE WITH ONE HAND−CRANK DRUM PUMP FOR 55 GALLON DRUM AND ONE REFRACTOMETER FOR CHECKING GLYCOL CONCENTRATION, MISCO MODEL 7084VP (1−800−358−1100).
GLYCOL MAKE−UP UNIT (DUPLEX) FOR HEATING & CHILLED WATER SYSTEMS : FACTORY PACKAGED DUPLEX GLYCOL SOLUTION MAKE−UP SYSTEM CONSISTING OF A PAINTED STEEL FRAME, PUMPS AND STARTERS, ADJUSTABLE PRESSURE RELIEF VALVES PIPED TO TANK, PUMP ISOLATION VALVES, PRESSURE GAUGES, LOW LIQUID LEVEL ALARM AND PUMP CUT−OFF, CONTACTS FOR REMOTE ALARM AND A 50 GALLON TRANSLUCENT POLYETHYLENE RESERVOIR TANK. UNIT FOR STANDARD PLUG−IN CONNECTION TO 115V POWER OUTLET. PUMPS SHALL EACH PRODUCE 1.5 GPM AT 100 PSIG. PROVIDE NEPTUNE MODEL G−50−2A OR EQUAL.
HEAT EXCHANGER HX−1 (COOLING): SINGLE WALL PLATE AND FRAME TYPE HEAT EXCHANGER WITH STAINLESS STEEL PLATES AND LINERS. UNIT RATINGS FOR LOW TEMPERATURE (PLANT CHILLED WATER) SIDE SHALL BE 93 GPM OF WATER WITH AN ENTERING WATER TEMPERATURE OF 44°F AND LEAVING AT 54°F WITH A PRESSURE DROP OF 5.92 PSIG. UNIT RATINGS FOR HIGH TEMPERATURE (CHILLED WATER) SIDE SHALL BE 100 GPM OF 40% PROPYLENE GLYCOL/60% WATER ENTERING AT 57°F AND LEAVING AT 47°F WITH A PRESSURE DROP NOT EXCEEDING 9.63 PSIG. UNIT SHALL HAVE SAME SIDE WATER CONNECTIONS FOR HOT AND COLD SIDE SUPPLY AND RETURN WATER. UNIT SHALL BE FACTORY PROVIDED WITH JACKETED, REMOVABLE INSULATION HOUSING WITH CLIP RETAINERS. PROVIDE ALPHA−LAVAL MODEL M6−FG OR APPROVED EQUAL WITH 161 PLATES. UNIT FRAME
SHALL BE SIZED TO ALLOW THE INSTALLATION OF NOT LESS 12 ADDITIONAL PLATES.
HUMIDIFIER (H−7.1): HUMIDIFIER GRID SHALL BE ALL STAINLESS AND NONMETALLIC CONSTRUCTED FOR MEDIUM PRESSURE STEAM AND SHALL FEATURE VERTICAL DISPERSION TUBES ON 6" CENTERS. PARTS EXPOSED TO THE AIRSTREAM SHALL BE COATED WITH A HIGH TEMPERATURE, NON−ABSORBANT INSULATION WITH A MINIMUM ’R’ VALUE OF 0.5 TO MINIMIZE SENSIBLE HEAT GAIN. THE UNIT SHALL PRODUCE A MAXIMUM STEAM ABSORPTION DISTANCE OF 18" FOR 10,500 CFM OF DRY INCOMING 55°F AIR AND A LEAVING AIR RH OF 85%. PROVIDE DRISTEEM MODEL LV UTRA−SORB HUMIDIFIER GRID (48" WIDE X 48" HIGH) OR APPROVED EQUAL. UNIT SHALL BE PROVIDED WITH A FACTORY PACKAGED STAINLESS STEEL CONTROL VALVE WITH 24 VOLT ELECTRIC ACTUATOR FOR 4−24 MV CONTROL AND 30 PSIG STEAM SUPPLY PRESSURE. UNIT SHALL PROVIDE 500 LBS/HR STEAM.
LABORATORY AIR COMPRESSORS (LAC−7.1, LAC−7.2) :
SEE SPECIFICATION SECTION 15252.
LABORATORY VACUUM PUMPS (LVP−7.1, LVP−7.2) :
RELOCATED.
LOUVER L−1 HEAT PLATES AND PEX TUBING: HEATING PLATES SHALL BE HEAVY EXTRUDED ALUMINUM WITH INTEGRAL CHANNEL FOR NOMINAL 1/2" DIAMETER PEX TUBING, MODEL "THERMOFIN U" BY RADIANT ENGINEERING (406) 587−3442) OR APPROVED EQUAL.
PEX TUBING SHALL BE ENGEL METHOD PEX WITH OXYGEN BARRIER, 1/2" DIAMETER, RATED FOR CONTINUOUS OPERATION AT 180
DEGREES F AT 100 PSIG, HEATWAY MODEL E−PEX B OR APPROVED EQUAL.
MAKE−UP WATER METER: THERMOPLASTIC BODY, MAGNETIC DRIVE DISC WATER METER WITH SEALED TOTALIZING REGISTER.
UNIT RATED 97% ACCURATE DOWN TO 1/8 GPM FLOW AND A MAXIMUM FLOW RATE OF 15 GPM. TOTALIZER SHALL READ IN U.S.
GALLONS UP TO TEN THOUSAND GALLONS. PROVIDE BADGER RCDL i" M25 DISK METER RATED TO 100°F OR APPROVED EQUAL.
DATUM ELEVATION FOR ACFM IS 3,500 FT. STATIC PRESSURE IS INCHES WATER COLUMN. TEMPERATURES ARE
IN DEGREES FAHRENHEIT. RPM IS APPROXIMATE.
MODULAR DRAW−THRU AIR HANDLER WITH 16 GAUGE GALVANIZED STEEL REMOVABLE EXTERIOR PANELS, 2" THICK INSULATED SOLID DOUBLE−WALL CONSTRUCTION, AND FULLY INSULATED FLOORS. PROVIDE WITH 12" SIDE LOAD FILTER SECTION FOR USE WITH 2" PREFILTERS, 14" SIDE LOAD FILTER SECTION FOR USE WITH 4" FINAL CARTRIDGE FILTERS, 36" CHILLED WATER COOLING COIL SECTION, 12" HOT WATER HEATING COIL SECTION, AND SUPPLY FAN COMPARTMENT WITH A MINIMUM CLASS II BELT DRIVEN AIRFOIL FAN WITH TOP−BACK DISCHARGE AS SHOWN AND A DISCHARGE VELOCITY NOT EXCEEDING 1,800 FEET PER MINUTE.
THE FAN SHALL HAVE L10−200,000 HOUR RATED BEARINGS. MOTOR SHALL BE ODP PREMIUM EFFICIENCY, SIZED AS SCHEDULED, AND SUITABLE FOR USE WITH A VARIABLE FREQUENCY DRIVE. FAN DRIVE ASSEMBLIES SHALL BE RATED AS SPECIFIED. FAN AND MOTOR ASSEMBLIES SHALL BE FACTORY MOUNTED ON SPRING ISOLATED BASES AND SEISMICALLY RESTRAINED. ALL COMPARTMENTS SHALL BE FITTED WITH INSULATED DOUBLE WALL ACCESS DOORS. COIL AND FAN SECTIONS SHALL BE FITTED WITH 12"x12" VISION PANELS AND 100W VAPOR TIGHT INCANDESCENT LIGHT FIXTURES FACTORY WIRED TO A COMMON SWITCH MOUNTED ON THE EXTERIOR OF THE UNIT. PROVIDE WITH DOUBLE SLOPING NON−RECESSED STAINLESS STEEL DRAIN PANS IN BOTH COIL SECTIONS TO ALLOW COIL WASHDOWN. SEE HEATING AND/OR COOLING COIL SCHEDULE AND FILTER SCHEDULE FOR APPLICABLE PERFORMANCE. UNITS SHALL FEATURE FACTORY OR FIELD MOUNTED FILTER GAGES (SEE MISCELLANEOUS EQUIPMENT SCHEDULE). SEE DRAWING BELOW FOR UNIT ARRANGEMENT. SEE SPECIFICATION SECTION 15763 FOR ADDITIONAL REQUIREMENTS.
PROVIDE WITH 48" ACCESS SECTION BETWEEN FAN AND HEATING COIL SECTION, AND 6" BASE RAIL FOR
LENGTH OF ENTIRE UNIT.
10,500
FAN
ACFM
AIR HANDLER SCHEDULE
MODELUNIT
AH−7.1 McQUAY
MFR TYPE
AF/2
TYPESIZE
460V/3Ø
ELECT.
RPM
4.692.0
E.S.P. T.S.P.
15.0
HP
MOTOR
NOTES
DROPS ARE IN INCHES OF WATER COLUMN. FLUID PRESSURE DROPS ARE IN FEET OF WATER COLUMN.
ARE IN DEGREES FAHRENHEIT. FLUID IS WATER UNLESS OTHERWISE NOTED. AIR PRESSURE
DATUM ELEVATION FOR ACFM IS 3,500 FT. STATIC PRESSURE IS INCHES WATER COLUMN. TEMPERATURES
10,500
10,500
ACFM
HEATING AND/OR COOLING COIL SCHEDULE
AH−7.2
C/C
AH−7.2
H/C
WATER
TYPE
WATER
H/C
AH−7.1
UNIT
C/C
AH−7.1
McQUAY
MFR ROWSIZE
(1)
10 384
MBH
FPI
WATERAIR
−20 55−
18040.4
81.4 44
NOTES
140 4.8
11.954 AH−7.2 McQUAY
HEATING AND CHILLED WATER COILS TO BE PROVIDED AS INTEGRAL PART OF REFERENCED AIR HANDLER.
PERFORMANCE DATA IS FOR 40% PROPYLENE GLYCOL. COIL FACE VELOCITY SHALL NOT EXCEED 500 FPM
FOR THE SCHEDULED AIR FLOW.
HEAT RECOVERY COIL PROVIDED IN WEATHER PROOF AIR HANDLER CABINET WITH 36" COIL SECTION AND 36" INLET PLENUM WITH 2" 30% PANEL FILTERS. SEE DRAWING BELOW FOR DIMENSIONS. CABINET
CONSTRUCTION SHALL BE SIMILAR TO THE SCHEDULED AIR HANDLER UNITS.
DUCT MOUNTED REHEAT COIL.
460V/3Ø
INDUSTRIAL (ACID) WASTEIW
IV INDUSTRIAL (ACID) VENT
HOT
TW TEMPERED WATER
CHILLED
10,500
WATERC/C
HRC−7.1 12 41712 75 62 48 3581.0 45 9.50CHILLED
McQUAY
McQUAY
42X66 (1)
42x69
(1) 42x69
INSERTION LOSS IN DECIBELS FOR THE GIVEN OCTAVE BAND NUMBER AND ASSOCIATED CENTER FREQUENCY IN HERTZ. RINK, INDUSTRIAL ACOUSTICS COMPANY, AND DYNASONICS ARE EQUIVALENT MANUFACTURERS
RECTANGULAR, NO−MEDIA, DISSIPATIVE MEDIUM VELOCITY SILENCER. ALL STAINLESS STEEL
CONSTRUCTION.
SOUND ATTENUATOR SCHEDULE
DIMENSIONS
16"
W
MFR
(CFM) 4
S.P.
0.21
(WG) 1
LOSS
FACE
+1750
(FPM)
60"
H
16"
L 63
NOTES
8K
4K2K
1K 6 7
1916" 5 100.21+175060"16" 1 810 1021
1916" 5 100.21+175060"16" 1 810 1021
1916" 5 100.21+175060"16" 1 810 1021
SINGLE WIDTH, SINGLE INLET, BELT DRIVEN INDUSTRIAL MATERIAL HANDLER WITH BACKWARD INCLINED FLAT BLADE WHEEL, FULLY WELDED 10 GAUGE STEEL HOUSING, L10−200,000 HOUR PILLOW BLOCK BEARINGS, AND BAKED POWDER COAT FINISH. MOTOR SHALL BE PREMIUM EFFICIENCY INVERTER DUTY RATED AND SIZED AS SCHEDULED FOR FUTURE EXPANSION. PROVIDE FAN WITH OPTIONAL DRAIN TAPPING, BOLTED ACCESS DOOR, INLET AND OUTLET FLANGES, INLET AND OUTLET COMPANION FLANGES, SHAFT SEALS, WEATHER COVER, CONCRETE ISOLATION BASE, AND FACTORY SIZED RESTRAINED SPRING VIBRATION ISOLATORS TO MEET IBC SEISMIC REQUIREMENTS. FAN SHALL OPERATE OVER THE ENTIRE RANGE OF VOLUME AND STATIC PRESSURE SCHEDULED. PROVIDE MOTOR ON RIGHT OR LEFT SIDE AS REQUIRED FOR MAINTENANCE. PROVIDE WITH VARIABLE FREQUENCY DRIVE IN A COMPACT VERTICAL
ARRANGEMENT AND IN ACCORDANCE WITH SECTION 15180 EXCEPT WITHOUT BYPASS.
ROOF MOUNTED, BELT DRIVEN, DOWNBLAST CENTRIFUGAL EXHAUST VENTILATOR CONSTRUCTED WITH 16 GAUGE ALUMINUM HOUSING, ALUMINUM BACKWARD INCLINED FAN WHEEL, AND HEAVY DUTY REGREASABLE BALL BEARINGS IN CAST IRON PILLOW BLOCK HOUSINGS RATED FOR L50 LIFE IN EXCESS OF 200,000 HOURS.
PROVIDE WITH 18 GAUGE INSULATED GALVANIZED STEEL ROOF CURB WITH OPTIONAL DAMPER TRAY, AND GRAVITY BACKDRAFT DAMPER. PROVIDE WITH FACTORY MOUNTED DISCONNECT ON UNIT IN NEMA 4
ENCLOSURE.
DATUM ELEVATION IS 3,500 FEET, TEMPERATURE IS 70° F UNLESS OTHERWISE NOTED,
STATIC PRESSURE IS IN INCHES WATER COLUMN, LWA IS A−RATED SOUND POWER
LEVEL IN DECIBELS DURING NORMAL OPERATION ACCORDING TO AMCA STANDARD 301.
480V/3/60CWHD 9 90 7.56.0 17683,100UPBLAST
FAN SCHEDULE
WODP
W
W
W
480V/3/60 WODP
480V/3/60 WODP
480V/3/60 WODP
CWHD 9 90 7.56.0 17683,100UPBLAST
CCWHD 9 90 7.56.0 17683,100UPBLAST
CCWHD 9 90 7.56.0 17683,100UPBLAST
ODP0.7569 120V/1/609890.52,900DOWN−−− −
BLAST
2,700 WATERBC−7101 1 59.99 55 − 77.7 1803.0 140 4.9HOTMcQUAY 24x24
BC−7102
BC−7103
BC−7106
WATER 1 3.08 55 − 70.4 1800.2 140 0.01HOTMcQUAY 9x9
WATER
HOTMcQUAY
WATER 1 1.78 55 − 72.2 1800.1 140 0.01HOTMcQUAY 9x9
WATERBC−7201 HOTMcQUAY
BC−7202
BC−7203
BC−7206
WATER
HOTMcQUAY
WATER
HOTMcQUAY
WATER 1 8.78 55 − 77.2 1800.4 140 0.01HOTMcQUAY 12x12
BC−7207 WATER 1 8HOTMcQUAY 12x12
WATER
WATER
McQUAY HOT
CHILLEDMcQUAY
BC−7208 WATER
HOTMcQUAY 9x9
BC−7107 WATER
HOTMcQUAY
BC−7108 WATER 1 8HOTMcQUAY 9x9
BC−7109 WATER
HOTMcQUAY
BC−7209 WATER 1 8HOTMcQUAY 24x12
BC−7211 450
WATER 1 10.38 55 − 76.0 1800.5 140 0.01HOTMcQUAY 12x12
10,500
10,5002 (1)
10 384
9 90
−20 55−
18040.4
81.4 44
140 4.8
11.954
42X66 (1)
42x69
10,500AF/2 20344.692.0 15.0
4509.1 55 − 73.7 1800.5 140 0.01
1001.7 55 − 72.2 1800.1 140 0.01
114019.1 55 − 72.2 1801.0 140 0.2
10,500451 −20 24.7− 81.4 45 13.833 PREHEAT MODE
10,500451 −20 24.7− 81.4 45 13.833 PREHEAT MODE
2,7001 59.99 55 − 77.7 1803.0 140 4.924x24
2001 3.08 55 − 70.4 1800.2 140 0.019x9
2001 3.08 55 − 70.4 1800.2 140 0.019x9
2001 3.08 55 − 70.4 1800.2 140 0.019x9
1 8 1001.7 55 − 72.2 1800.1 140 0.01
2001 3.08 55 − 70.4 1800.2 140 0.019x9
4001 8.78 55 − 77.2 1800.4 140 0.0112x12
BC−7204 WATER
HOTMcQUAY 2501 4.08 55 − 71.3 1800.2 140 0.019x9
CONDENSATE PUMPING TRAP PT−A.1: PRESSURE MOTIVE SKID MOUNTED PUMPING TRAP ASSEMBLY WITH ELEVATED VENTED RECEIVER TANK AND DUPLEX LOW PROFILE REDUNDANT PUMPING TRAPS. EACH TRAP SHALL BE RATED TO PRODUCE 12,500 POUNDS PER HOUR OF CONDENSATE FLOW USING 75 PSIG MOTIVE STEAM AND WORKING AGAINST A 25 PSIG BACKPRESSURE.
TRAPS SHALL BE CONSTRUCTED OF ASTM A48 CLASS 30 CAST IRON WITH INVESTMENT CAST STAINLESS STEEL MECHANISM, STAINLESS STEEL FLOAT AND INCONEL X−750 SPRINGS AND SHALL HAVE A MAXIMUM OPERATING PRESSURE RATING OF 125 PSIG.
THE RECEIVER INLET CONNECTION SHALL NOT BE HIGHER THAN 60". THE UNIT SHALL HAVE A 3 YEAR NO−FAIL WARRANTY.
PROVIDE ARMSTRONG INTERNATIONAL MODEL DPT−312−LBRP OR APPROVED EQUAL BY SPIRAX SARCO OR WATSON MCDANIEL.
CONDENSATE PUMPING TRAP PT−A.2: PRESSURE MOTIVE PUMPING TRAP ASSEMBLY FEATURING DUPLEX FIELD−MOUNTED LOW PROFILE REDUNDANT PUMPING TRAPS. PUMPING TRAPS ARE FOR CONNECTION TO AN EXISTING ELEVATED VENTED RECEIVER.
EACH TRAP SHALL BE RATED TO PRODUCE 12,500 POUNDS PER HOUR OF CONDENSATE FLOW USING 75 PSIG MOTIVE STEAM AND WORKING AGAINST A 25 PSIG BACKPRESSURE. TRAPS SHALL BE CONSTRUCTED OF ASTM A48 CLASS 30 CAST IRON WITH INVESTMENT CAST STAINLESS STEEL MECHANISM, STAINLESS STEEL FLOAT AND INCONEL X−750 SPRINGS AND SHALL HAVE A MAXIMUM OPERATING PRESSURE RATING OF 125 PSIG. THE UNIT SHALL HAVE A 3 YEAR NO−FAIL WARRANTY. PROVIDE ARMSTRONG INTERNATIONAL MODEL PT−312 OR APPROVED EQUAL BY SPIRAX SARCO OR WATSON MCDANIEL.
REV
DATE
CIVIL:
REVIEWED BY:
STRUCTURAL:
ELECTRICAL:
MECHANICAL:
ARCHITECTURAL:
HAMILTON, MONTANA
SHEET OF 90
DATE
06/19/09
31 30
A
5 3
13B23
M0.1
LEGEND & SCHEDULES
BUILDING 7: MECHANICAL