This is a product data sheet for the NFS2-3030 Intelligent Addressable Fire Alarm Control Panel manufactured by NOTIFIER (by Honeywell). The document provides comprehensive technical specifications and product line information rather than federal procurement details.
The NFS2-3030 is designed for medium- to large-scale facilities and supports up to 3,180 intelligent addressable devices across one to ten Signaling Line Circuits (SLCs). Key system features include a large 640-character LCD display, advanced ONYX intelligent sensing algorithms with drift compensation, FlashScan detection protocol, and modular design allowing per-project configuration. The panel supports up to 159 detectors and 159 modules per SLC, with capabilities for wireless fire protection using SWIFT technology, voice/telephone features, smoke control system support, and FM6320-approved gas detection. Network options accommodate up to 200 nodes on high-speed networks or 103 nodes on standard networks. The system includes multiple central station communication options (UDACT, Internet, Internet/GSM), cloud connectivity through the CLSS Gateway, and supports Boolean logic programming up to 1,000 equations. Compatible devices encompass various intelligent detectors (photoelectric, thermal, multi-criteria, aspiration smoke detectors), relay modules, annunciators, and control modules. The panel is certified for seismic and marine applications, UL/ULC-listed, FM-approved, and complies with UL 864, UL 2610, UL 2572, NFPA 72, and various building codes. Primary input power requirements are 110-120 VAC or 240 VAC at 50/60 Hz with battery charger range of 7-200 AH.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 26R0228 Fire Panels SSN.pdf | ||
| NFS2-640.pdf | ||
| INSPIRE N16.pdf | ||
| Attachment 1 Company Info.docx | DOCX document | |
| NFS-320.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NFS2-3030 Intelligent Addressable Fire Alarm Control Panel NFS2-3030 (left) and NFS2-3030 with DVC audio option (right)
General The NFS2-3030 is an intelligent Fire Alarm Control Panel (FACP) designed for medium- to large-scale facilities. Fire emergency detec-tion and evacuation are extremely critical to life safety, and the NFS2-3030 is ideally suited for these applications. The NFS2-3030 is part of the ONYX® Series of products from NOTIFIER. The NFS2- 3030 is ideal for virtually any application because it features a modu-lar design that is configured per project requirements. With one to ten Signaling Line Circuits (SLCs), the NFS2-3030 supports up to 3,180 intelligent addressable devices.
Information is critical to fire evacuation personnel, and the NFS2- 3030’s large 640-character Liquid Crystal Display (LCD) presents vital information to operators concerning a fire situation, fire progres-sion, and evacuation details.
A host of other options are available, including single- or multi-chan-nel voice; firefighter’s telephone; LED, LCD, or PC-based graphic annunciators; networking; advanced detection products for challeng-ing environments; wireless fire protection; and many additional options.
ONYX® Series panels integrate with the Connected Life Safety Ser-vices (CLSS) platform through the CLSS Gateway, providing connectivity to central station, cloud, and mobile applications. (See HON-62034.) This cloud-based functionality provides reliable pro-tection and remote monitoring of the system, reduced manual data entry, and reporting.
Features
• Certified for seismic applications when used with the appropriate seismic mounting kit.
• Approved for Marine applications when a marine-listed version is used with marine-listed compatible equipment. See DN-60688.
• Complies with UL 2572 Mass Notification Systems (NFS2-3030 version 20 or higher).
• One to ten isolated intelligent Signaling Line Circuits (SLC) Class
A, B, or X.
• Wireless fire protection using SWIFT Smart Wireless Integrated
Fire Technology. See DN-60820.
• Up to 159 detectors and 159 modules per SLC; 318 devices per loop/3,180 per FACP or network node.
– Detectors can be any mix of photo, thermal, or multi-sensor;
wireless detectors are available for use with the FWSG(A).
– Modules include addressable pull stations, normally open con-tact devices, two-wire smoke detectors, notification, or relay;
wireless modules are available for use with the FWSG(A).
• Large 16 line, 640 character LCD backlit display or use display-less as a network node.
• Network options:
– High-speed network for up to 200 nodes (N16e/x, NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCD, NCA-2, DVC-EM, ONYXWorks, NFS-3030, NFS-640, and NCA).
– Standard network for up to 103 nodes (N16e/x, NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCD, NCA-2, DVC-EM, ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP- 300/400, AFP-1010, and AM2020). Up to 54 nodes when DVC- EM is used in network paging.
• Built-in Alarm, Trouble, Security, and Supervisory relays.
• VeriFire® Tools online/offline program option.
• With built-in Degraded Mode operation, the system is capable of general alarm if a fire alarm condition is present even if the cen-tral processing unit (CPU) fails.
• Weekly Occupancy Schedules allow changing sensitivity by time of day and day of week.
• EIA-485 annunciators, including custom graphics.
• History file with 4000-event capacity in nonvolatile memory, plus separate 1000-event alarm-only file.
• Advanced history filters allow sorting by event, time, date, or address.
• Alarm Verification selection per point, with automatic counter.
• Autoprogramming and Walk Test reports.
• Multiple central station communication options:
– Standard UDACT
– Internet
– Internet/GSM
• Positive Alarm Sequence (PAS) Presignal.
• Silence Inhibit and Auto Silence timer options.
• Optional cloud connectivity for remote off site monitoring through
CLSS (see HON-62034)
• Monitor multiple buildings through one off-campus central station, and report through the CLSS Gateway
• Optional remote programing through CLSS
• Field-programmable on panel or on PC, with VeriFire Tools pro-gram, also check, compare.
• Non-alarm points for lower priority functions.
• Remote ACK/Signal Silence/System Reset/Drill via monitor mod-ules.
• Up to 1000 powerful Boolean logic equations.
• Supports SCS Series smoke control system in both HVAC and
FSCS modes.
• FM6320 approved Gas Detection System with FMM-4-20 module and any FM listed gas detector.
• EIA-232 printer port.
• EIA-485 annunciator port.
DN-7070:S • 9/14/2022 — Page 1 of 8
640-CHARACTER DISPLAY FEATURES
• Backlit, 640-character display.
• Program keypad: full QWERTY keypad.
• Up to nine users, each with a password and selectable access levels.
• 11 LED indicators: Power; Fire Alarm; Pre-Alarm; Security;
Supervisory; System Trouble; Other Event; Signals Silenced;
Point Disabled; CPU Failure; Controls Active.
• Membrane Switch Controls: Acknowledge; Signal Silence; Drill;
System Reset; Lamp Test.
• LCD Display: 640 characters (16 lines x 40 characters) with long-life LED backlight.
SWIFT WIRELESS
• Self-healing mesh wireless protocol.
• Each SWIFT Gateway supports up to 49 SWIFT devices.
• Up to 4 wireless gateways can be installed with overlapping net-work coverage.
RELEASING FEATURES
• Ten independent hazards.
• Sophisticated cross-zone (three options).
• Delay timer and Discharge timers (adjustable).
• Abort (four options).
VOICE AND TELEPHONE FEATURES
• Up to eight channels of digital audio.
• 35 watt, 50 watt, 75 watt, and 100/125 watt digital amplifiers
(DAA2/DAX series and DS series).
• Solid state message generation.
• Hard-wired voice control module options.
• Firefighter telephone option.
• 30- to 120-watt analog amplifiers (AA Series).
• Backup tone generator and amplifier option.
FLASHSCAN® INTELLIGENT FEATURES
• Polls up to 318 devices on each loop in less than two seconds.
• Activates up to 159 outputs in less than five seconds.
• Multicolor LEDs blink device address during Walk Test.
• Fully digital, high-precision protocol (U.S. Patent 5,539,389).
• Manual sensitivity adjustment — up to nine levels.
• Pre-alarm ONYX intelligent sensing — up to nine levels.
• Sensitivity levels:
– Photo – 0.5 to 2.35%/foot obscuration.
– High-Sensitivity Photoelectric (VIEW®) – Open Air Protection
(0.5% - 2.0%/ft. obscuration), Special Applications (0.02%- 0.5%/ft. obscuration)
– Multi-Criteria Detector – Open Air Protection (2.52-3.89%/ft.
obscuration), Special Applications (1.13-2.52%/ft. obscuration)
• Drift compensation (U.S. Patent 5,764,142).
• Multi-detector algorithm involves nearby detectors in alarm deci-sion (U.S. Patent 5,627,515).
• Automatic detector sensitivity testing (NFPA-72 compliant).
• Maintenance alert (two levels).
• Self-optimizing pre-alarm.
• Programmable activation of sounder/relay bases during alarm or pre-alarm.
• Read Status displays the level of detector cleanliness.
FRM-1
Relay Contact
NOTE: CPU2-3030 firmware version 14.0 (and higher) can support LCD-160 on the RDP port, or LCD2-80 in terminal mode, but not both at the same time.
CPU2-3030D
display or
CPU2-3030ND
PRN Series Printer
NFS2-3030
Sample System Options
FPTI-951
FSP-951
FST-951
FCO-951
…etc.
Shown in CAB-C4 with display DVC-EM audio in CA-1 in second tier bl ok
-2
3.
w m f
LCD-160/C
LCD2-80
Up to 32 remote displays
EIA-485
EIA-485
SLC Intelligent Loop
3072 annunciator/control points
Optional 2048-point UDACT
Dual phone lines to Central Station
EIA-232
DEVICES
ACM/AEM-24AT
LED Annunciator
LDM-32
Custom Graphics
ACM-8R
Relay Control
NBG-12LX XP6/10 I/O Modules
FMM-1
IDC
FWSG
Page 2 of 8 — DN-7070:S • 9/14/2022
FSV-951 SERIES VIEW® (VERY INTELLIGENT EARLY WARNING)
HIGH-SENSITIVITY SMOKE DETECTOR
• Advanced ONYX intelligent sensing algorithms differentiate between smoke and non-smoke signals.
• Addressable operation pinpoints the fire location.
• Ivory models (-IV) support CLIP mode as well as FlashScan.
• ULC listed models available; “A” models are ULC Listed.
• -R is retrofit, backwards compatible for use with older panels.
FCO-951(A)/-IV ADVANCED MULTI-CRITERIA FIRE/CO DETECTOR
• Detects all four major elements of a fire (smoke, heat, CO, and flame).
• 135°F (57.2°C) fixed-temperature heat detector.
• Transmits an alarm signal due to heat.
• Separate signal for life-safety CO detection.
• Optional addressable sounder base for Temp-3 (fire) or Temp-4
(CO) tone.
• Automatic drift compensation of smoke sensor and CO cell.
• High nuisance-alarm immunity.
• ULC listed models available; “A” models are ULC Listed.
FPTI-951(A) INTELLIGENT MULTI-CRITERIA DETECTOR
• Combined Photoelectric Thermal and Infrared Sensor
• UL 268 7th Edition and UL 521 Listed; Canadian models CAN/
ULC S529 and CAN/ULC S530
• Microprocessor-based technology; combination photo, thermal, and infrared technology.
FPC-951(A) PHOTOELECTRIC/CO SENSOR
• Combined photoelectric and carbon monoxide sensor
FSCO-951(A) INTELLIGENT CO SENSOR
• Carbon monoxide sensor
FS-OSI-RI(A) ADDRESSABLE INTELLIGENT SINGLE-ENDED BEAM
SMOKE DETECTOR
• Intelligent addressable reflector-type linear optical beam smoke detector
• Fast, easy, and intuitive beam alignment indicated by directional
LED arrows
• Long range coverage of 16-328 ft (5-100 m) is standard; no sepa-rate long-range kit required
FMM-4-20 GAS DETECTION MODULE
• Interface to industry-standard linear scale 4-20 mA sensors.
• Five programmable thresholds.
• FM Approved, Class 6320 (Stationary Gas Sensors/Detectors).
INTELLIGENT VESDA-E DETECTORS
• Intelligent aspiration smoke detectors connect directly to the SLC loop of compatible ONYX® Series panels:
– VEA-040-A00-NTF, VEA-040-A10-NTF
– VEP-A00-P-NTF, VEP-A10-P-NTF, VEP-A00-1P-NTF
– VEU-A00-NTF, VEU-A10-NTF
– VES-A00-P-NTF-UL, VES-A10-P-NTF-UL
• Models offer LED display, LCD display, or both
• Coverage options for spaces up to 69,965 square feet
FlashScan® Exclusive World-Leading Detector Protocol At the heart of the NFS2-3030 is a set of detection devices and device protocol — FlashScan (U.S. Patent 5,539,389). FlashScan is an all-digital protocol that gives superior precision and high noise immunity.
As well as giving quick identification of an active input device, this protocol can also activate many output devices in a fraction of the time required by competitive protocols. This high speed also allows the NFS2-3030 to have the largest device per loop capacity in the industry — 318 points — yet every input and output device is sam-pled in less than two seconds. The microprocessor-based FlashScan® detectors have bicolor LEDs that can be coded to pro-vide diagnostic information, such as device address during Walk Test.
ONYX Intelligent Sensing ONYX Intelligent Sensing is a set of software algorithms that provide the NFS2-3030 with industry-leading smoke detection capability.
These complex algorithms require many calculations on each read-ing of each detector, and are made possible by the very high-speed microcomputer used by the NFS2-3030.
Drift Compensation and Smoothing. Drift compensation allows the detector to retain its original ability to detect actual smoke, and resist false alarms, even as dirt accumulates. It reduces mainte-nance requirements by allowing the system to automatically perform the periodic sensitivity measurements required by NFPA 72.
Smoothing filters are also provided by software to remove transient noise signals, usually caused by electrical interference.
Maintenance Warnings. When the drift compensation performed for a detector reaches a certain level, the performance of the detec-tor may be compromised, and special warnings are given. There are three warning levels: (1) Low Chamber value; (2) Maintenance Alert, indicative of dust accumulation that is near but below the allowed limit; (3) Maintenance Urgent, indicative of dust accumulation above the allowed limit.
Sensitivity Adjust. Nine sensitivity levels are provided for alarm detection. These levels can be set manually, or can change automat-ically between day and night. Nine levels of pre-alarm sensitivity can also be selected, based on predetermined levels of alarm. Pre-alarm operation can be latching or self-restoring, and can be used to acti-vate special control functions.
Self-Optimizing Pre-Alarm. Each detector may be set for “Self- Optimizing” pre-alarm. In this special mode, the detector “learns” its normal environment, measuring the peak analog readings over a long period of time, and setting the pre-alarm level just above these normal peaks.
Cooperating Multi-Detector Sensing. A patented feature of ONYX Intelligent Sensing is the ability of a smoke sensor to consider read-ings from nearby sensors in making alarm or pre-alarm decisions.
Without statistical sacrifice in the ability to resist false alarms, it allows a sensor to increase its sensitivity to actual smoke by a factor of almost two to one.
Field Programming Options Autoprogram is a timesaving feature. The FACP “learns” what devices are physically connected and automatically loads them in the program with default values for all parameters. Requiring less than one minute to run, this routine allows the user to have almost immediate fire protection in a new installation, even if only a portion of the detectors are installed.
Keypad Program Edit. The NFS2-3030, like all NOTIFIER intelli-gent panels, has the exclusive feature of program creation and edit-ing capability from the front panel keypad, while continuing to provide fire protection. The architecture of the NFS2-3030 software is such that each point entry carries its own program, including con-trol-by-event links to other points. This allows the program to be entered with independent per-point segments, while the NFS2-3030 simultaneously monitors other (already installed) points for alarm conditions.
VeriFire® Tools is an offline programming and test utility that can greatly reduce installation programming time, and increase confi-dence in the site-specific software. It is Windows® based and pro-vides technologically advanced capabilities to aid the installer. The installer may create the entire program for the NFS2-3030 in the DN-7070:S • 9/14/2022 — Page 3 of 8 comfort of the office, test it, store a backup file, then bring it to the site and download from a laptop into the panel.
Product Line Information
• “Configuration Guidelines” on page 4
• “Main System Components” on page 4
• “Networking Options” on page 4
• “Auxiliary Power Supplies and Batteries” on page 4
• “Audio Options” on page 4
• “Compatible Devices, EIA-232 Ports” on page 5
• “Compatible Devices, EIA-485 Ports” on page 5
• “Compatible Intelligent Devices” on page 5
• “Enclosures, Chassis, and Dress Plates” on page 6
• “Backboxes” on page 7
• “Other Options” on page 7
CONFIGURATION GUIDELINES
Stand-alone and network systems require a main display. On single- FACP systems (one NFS2-3030D), the display option is the CPU2- 3030D. On network systems (two or more networked fire panel nodes), at least one NCD, NCA-2/C, NCS, or ONYXWorks annunci-ation device is required. Options listed as follows.
MAIN SYSTEM COMPONENTS
CPU2-3030D: NFS2-3030 Primary Display. CPU2-3030D ships with keypad/display installed; includes 640-character backlit LCD display, QWERTY programming and control keypad. CPU2-3030 is a central processing unit and requires an AMPS-24(E) power supply. For English ULC applications, use CPU2-3030DC. Non-English versions are available: CPU2-3030D-FR, CPU2-3030D-HE, CPU2-3030D-
KO, CPU2-3030D-PO, CPU2-3030D-SC, CPU2-3030D-SP, CPU2-
3030D-TC, and CPU2-3030D-TH. For English Marine applications order CPU2-3030D-M; for non-English Marine applications order CPU2-3030D-M and the appropriate KP-KIT-XX. (See DN-60688.)
CPU2-3030ND: CPU2-3030 without display. Non-English versions are available: CPU2-3030ND-FR, CPU2-3030ND-HE, CPU2-
3030ND-KO, CPU2-3030ND-PO, CPU2-3030ND-SC, CPU2-
3030ND-SP, CPU2-3030ND-TC.
AMPS-24(E): One required for each NFS2-3030. Addressable power supply and battery charger with two 24 VDC outputs.
Addressable by any FlashScan® or CLIP mode FACP. Charges 7 to 200 AH batteries. Occupies up to five addresses on an SLC, depending on configuration. Primary input power for panel. See DN- 6883.
LCM-320: Loop Control Module. Provides one SLC. NFS2-3030 supports up to five LCM-320s and five LEM-320 expanders for a total of ten SLCs. See DN-6881.
LEM-320: Loop Expander Module. Expands an LCM-320. See DN- 6881.
SAMPLE SYSTEM: Four-loop NFS2-3030 with display: CPU2- 3030D, DP-DISP, two BMP-1s, CHS-M3, two LCM-320s, two LEM- 320s, AMPS-24, SBB-A4, DR-A4, BP2-4, BB-100, batteries.
NETWORKING OPTIONS
NCA-2/C: Network Control Annunciator, 640 characters. An alter-nate primary display for CPU2-3030 can be provided by the NCA-2, NCS, or ONYXWorks. Using NCA-2 as primary display enables non- English languages. On network systems (two or more networked fire panel nodes), one network display (either NCA-2, NCS, or ONYX- Works) is required for every system. On network systems, the NCA- 2 connects (and requires) a standard Network Communication Mod-ule or High-Speed Network Communication Module. Mounts in a row of FACP node or in two annunciator positions. Mounting options include the DP-DISP, ADP-4B, or in an annunciator box, such as the ABS-2D. In CAB-4 top-row applications, a DP-DISP and two BMP-1 blank modules are required for mounting. Order NCA-2C for ULC applications. Non-English versions are available: NCA-2-FR, NCA-2-
HE, NCA-2-KO, NCA-2-PO, NCA-2-SC, NCA-2-SP, NCA-2-TC,
NCA-2-TH. For English ULC applications, order NCA-2C; for marine applications, order NCA-2-M; for non-English marine applications order NCA-2-M and appropriate KP-KIT-XX. See DN-7047.
NCD: Network control display, with a high-definition 10” touch screen. As part of a standalone NFS2-3030 system, the NCD can serve as Primary Display for the panel, to provide control and status capabilities on displayless nodes. On network systems, the NCD connects to (and requires) a standard Network Communication Mod-ule or High-Speed Network Communication Module. Mounting options include the ABS-TD for standalone applications. In the CAB-4 series the NCD can be mounted in the top row with a DP-GDIS1 or lower rows using a DP-GDIS2. See DN-60974.
NCM-W, NCM-F: Standard Network Communications Modules. Wire and multi-mode fiber versions available. See DN-6861.
HS-NCM-W(-2), HS-NCM-MF, HS-NCM-SF, HS-NCM-WMF(-2),
HS-NCM-WSF(-2), HS-NCM-MFSF: High-speed Network Commu-nications Modules that can connect to two nodes. Wire, single-mode fiber, multi-mode fiber, and media conversion models are available.
See DN-60454.
RPT-W, RPT-F, RPT-WF: Standard-network repeater board with wire connection (RPT-W), multi-mode fiber connection (RPT-F), or allow-ing a change in media type between wire and fiber (RPT-WF). Not used with high-speed networks. See DN-6971.
ONYXWorks: UL/ULC-listed graphics PC workstation, ONYXWorks GUI software, and computer hardware. See DN-7048 for specific part numbers.
NFN-GW-EM-3: NFN Gateway, embedded. (Replaces NFN-GW- EM.) See DN-60499.
NWS-3: NOTI•FIRE•NET™ Web Server. See DN-6928.
CAP-GW: Common Alerting Protocol Gateway. See DN-60756.
VESDA-HLI-GW: VESDAnet high-level interface gateway. See DN- 60753.
LEDSIGN-GW: UL-listed sign gateway. Interfaces with classic and high-speed NOTI•FIRE•NET networks through the NFN Gateway.
See DN-60679.
OAX2-24V: UL-listed LED sign, used with LEDSIGN-GW. See DN- 60679.
AUXILIARY POWER SUPPLIES AND BATTERIES
APS2-6R: Auxiliary Power Supply. Provides up to 6.0 amperes of power for peripheral devices. Includes battery input and transfer relay, and overcurrent protection. Mounts on two of four positions on a CHS-4L or CHS-4 chassis. See DN-5952.
ACPS-610: 6.0 A or 10.0 A addressable charging power supply. See
DN-60244.
FCPS-24S6/-24S8: Remote 6 A and 8 A power supplies with battery charger. See DN-6927.
BAT Series: Batteries. AMPS-24 uses two 12 volt, 7 to 200 AH bat-teries. See DN-6933.
AUDIO OPTIONS
NOTE: See “Enclosures, Chassis, and Dress Plates” on page 6 for mounting hardware.
DVC-EM: Digital Voice Command, digital audio processor with mes-sage storage for up to 32 minutes of standard quality (4 minutes at high quality) digital audio. See DN-7045.
DVC-RPU: Digital Voice Command Remote Paging Unit for use with DVC-EM. Includes the keypad/display. See DN-60726.
DS-DB: Digital Series Distribution Board, provides bulk amplification capabilities to the DVC-EM while retaining digital audio distribution capabilities. Can be configured with up to four DS-AMPs, supplying high-level risers spread throughout an installation. See DN-60565.
DVC-KD: DVC-EM keypad for local annunciation and controls; sta-tus LEDs and 24 user-programmable buttons. See DN-7045.
Page 4 of 8 — DN-7070:S • 9/14/2022
DS-AMP/E: 125W, 25 VRMS, or 100W, 70VRMS. 70VRMS requires DS-XF70V step-up transformer. Digital Series Amplifier, part of the DS-DB system. See DN-60663.
DS-RFM, DS-FM, DS-SFM: Fiber conversion modules for DVC-EM, DS-DB distribution board, and DAA2/DAX Series amplifiers. See
DN-60633.
DAA2-5025(E): 50W, 25 Vrms Digital Audio Amplifier assembly with power supply; includes chassis. See DN-60556.
DAA2-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier assembly with power supply; includes chassis. See DN-60556.
DAA2-7525(E): 75W, 25 Vrms digital audio amplifier assembly with power supply; includes chassis. See DN-60556.
DAX-3525(E): 35W, 25 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
DAX-3570(E): 35W, 70.7 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
DAX-5025(E): 50W, 25 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
DAX-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
TELH-1: Firefighter’s Telephone Handset for use with the DVC-EM when mounted in the CA-2 chassis. See DN-7045.
CMIC-1: Microphone used with DVC/DVC-EM. Included with CA-2 chassis assembly. See DN-7045.
RM-1/RM-1SA: Remote microphone assemblies, mount on ADP-4 (RM-1) dress panel or CAB-RM/-RMR (RM-1SA) stand-alone cabi-nets. See DN-6728.
AA-30: Audio Amplifier, 30 watts, 25 Vrms. Includes amplifier and audio input supervision, backup input, and automatic switchover, power supply, cables. See DN-3224.
AA-120/AA-100: Audio Amplifier. AA-120 is 120 watts, 25 Vrms. AA- 100 is 100 watts, 70.7 Vrms. The amplifier contains an integral chas-sis for mounting to a CAB-B4, -C4, or -D4 backbox (consumes one row). Includes audio input and amplified output supervision, backup input, and automatic switchover to backup tone. See DN-3224.
DAA Series Digital Audio Amplifiers: Legacy DAA Series amplifi-ers are compatible with DVC systems running SR4.0. For specific information on DAA-50 series amplifiers, refer to DN-7046. For infor-mation on DAA-7525 Series, refer to DN-60257.
COMPATIBLE DEVICES, EIA-232 PORTS
PRN-7: 80-column printer. See DN-60897
VS4095/5: Printer, 40-column, 24 V. Order from Keltron, Inc. See
DN-3260.
DPI-232: Direct Panel Interface, specialized modem for extending serial data links to remotely located FACPs and/or peripherals. See
DN-6870.
COMPATIBLE DEVICES, EIA-485 PORTS
ACM-24AT: ONYX® Series ACS annunciator – up to 24 points, expandable to 96 of annunciation with Alarm or Active LED, Trouble LED, and switch per circuit. Active/Alarm LEDs can be programmed (by powered-up switch selection) by point to be red, green, or yellow;
the Trouble LED is always yellow. See DN-6862.
AEM-24AT: Same LED and switch capabilities as ACM-24AT;
expands the ACM-24AT to 48, 72, or 96 points. See DN-6862.
ACM-48A: ONYX® Series ACS annunciator – 48 points, expandable to 96 of annunciation with Alarm or Active LED per circuit. Active/ Alarm LEDs can be programmed (by powered-up switch selection) in groups of 24 to be red, green, or yellow. Expandable to 96 points with one AEM-48A. See DN-6862.
AEM-48A: Same LED capabilities as ACM-48A; expands the ACM- 48A to 96 points. See DN-6862.
ACM-8R: Remote Relay Module with eight Form-C contacts. Can be located up to 6,000 ft. (1828.8 m) from panel on four wires. See DN- 3558.
LCD-160: Liquid Crystal Display annunciator, 160-character backlit.
Can store character sets for multiple languages. Order LCD-160C for ULC applications. See DN-6940.
LCD2-80: Terminal and ACS mode. 80-character, backlit LCD dis-play. Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per FACP. See LCD2-80 (DN-60548).
SCS Series: Smoke control station; eight (expandable to 16) cir-cuits. See DN-4818.
TM-4: Transmitter Module. Includes three reverse-polarity circuits and one municipal box circuit. Mounts in panel module position (as in single-address mode applications) or in CHS-M3 position. See
DN-6860.
UDACT-2: Universal Digital Alarm Communicator Transmitter, 636 channel. See DN-60686.
UZC-256: Programmable Universal Zone Coder provides positive non-interfering successive zone coding. Microprocessor-controlled, field-programmable from IBM®-compatible PCs (requires optional programming kit). Mounts on a CHS-4 series chassis within NFS2- 3030.
COMPATIBLE INTELLIGENT DEVICES
NOTE: “A” suffix indicates ULC-Listed model.
FWSG(A) Wireless SWIFT Gateway: Addressable gateway sup-ports wireless SLC devices. Order FWSGA for ULC applications.
See DN-60820.
FCO-951/-IV FlashScan, Addressable intelligent multi-criteria smoke sensors, photo, carbon monoxide, fixed temperature heat detector and infra-red (IR). ULC: FCO-951A/-IV
FPC-951. FlashScan, Combined photoelectric and carbon monoxide sensor. ULC: FPC-951A.
FSCO-951. FlashScan, Addressable carbon monoxide sensor.
ULC: FSCO-951A.
FPTI-951, FPTI-951-IV: Addressable intelligent multi-criteria photo-electric, thermal and IR sensors. ULC: FPTI-951A, FPTI-951A-IV.
FS-OSI-RI: Addressable intelligent single-ended beam smoke detector. ULC: FS-OSI-RIA.
FSP-951: White, low-profile intelligent photoelectric sensor, FlashScan only. ULC: FSP-951A.
FSP-951-IV: Ivory, low-profile intelligent photoelectric sensor.
ULC: FSP-951A-IV
FSP-951T: White, same as FSP-951 but includes a built-in 135°F (57°C) fixed-temperature thermal device. FlashScan only.
ULC: FSP-951TA.
FSP-951T-IV: Ivory, same as FSP-951T but includes a built-in 135°F (57°C) fixed-temperature thermal device. ULC: FSP-951TA-IV.
FSP-951R: White, low-profile intelligent photoelectric sensor, remote test capable. For use with DNR/DNRW. FlashScan only. ULC: FSP-
95RA
FSP-951R-IV: Ivory, low-profile intelligent photoelectric sensor, remote test capable. FlashScan only. ULC: FSP-95RA-IV, for use with DNRA.
FST-951: White, low-profile intelligent 135°F fixed thermal sensor, FlashScan only. Must be mounted to one of the bases listed below.
ULC: FST-951A. See DN-60975.
FST-951-IV: Ivory, low-profile intelligent 135°F fixed thermal sensor, FlashScan and CLIP. Must be mounted to one of the bases listed below. ULC: FST-951A-IV.
FST-951R: White, low-profile intelligent rate-of-rise thermal sensor, FlashScan only. Must be mounted to one of the bases listed below.
ULC: FST-951A
DN-7070:S • 9/14/2022 — Page 5 of 8
FSP-951R-IV: Ivory, low-profile intelligent photoelectric sensor, remote test capable. FlashScan only. ULC: FSP-95RA-IV, for use with DNRA.
FST-951H: White, low-profile intelligent 190°F fixed thermal sensor, FlashScan only. Must be mounted to one of the bases listed below.
ULC: FST-951HA.
FST-951H-IV: Ivory, low-profile intelligent 190°F thermal sensor, FlashScan and CLIP. Must be mounted to one of the bases listed below. ULC: FST-951HA-IV.
FSV-951, FSV-951R:White, intelligent high-sensitivity photoelectric smoke detector. ULC: FSV-951A, FSV-951RA
FSV-951-IV, FSV-951R-IVIvory, intelligent high-sensitivity photoelec-tric smoke detector. ULC: FSV-951A-IV, FSV-951RA-IV.
VEP-A00-P-NTF: Intelligent aspiration smoke detector with LED dis-play, 4 pipes, covers up to 21,520 square feet. UL/ULC. See DN- 61029. UL/ULC Listed.
VEP-A10-P-NTF: Intelligent aspiration smoke detector with LED and LCD display, 4 pipes, covers up to 21,520 square feet. UL/ULC. See DN-61029. UL/ULC Listed.
VEP-A00-1P-NTF: Intelligent aspiration smoke detector with LED display, single pipe, covers up to 10,760 square feet. UL/ULC. See DN-61029. UL/ULC Listed.
VEU-A00-NTF: Intelligent aspiration smoke detector with LED dis-play, 4 pipes, covers up to 69,965 square feet. UL/ULC. See DN- 61034. UL/ULC Listed.
VEU-A10-NTF: Intelligent aspiration smoke detector with LED and LCD display, 4 pipes, covers up to 69,965 square feet. UL/ULC. See DN-61034. UL/ULC Listed.
VEA-040-A00-NTF: Intelligent aspiration with LED display, 40 point-addressable detection points. Covers 36,000 square feet. UL/ULC.
See DN-61036. UL/ULC Listed.
VEA-040-A10-NTF: Intelligent aspiration with LED and LCD display, 40 point-addressable detection points. Covers 36,000 square feet.
UL/ULC. See DN-61036. UL/ULC Listed.
VES-A00-P-NTF-UL: Intelligent scanning aspiration detector with LEDs. See DN-62040. UL 268 7th edition.
VES-A10-P-NTF-UL: Intelligent scanning aspiration detector with 3.5” display. See DN-62040. UL 268 7th edition.
DNR: InnovairFlex low-flow non-relay duct-detector housing.
ULC: DNRA. (Order FSP-951R(A) separately.) See DN-60429.
DNRW: Same as above with NEMA-4 rating, watertight. See DN- 60429.
B224RB-WH: White, low-profile relay base. See DN-60054. ULC:
B224RBA-WH.
B224RB-IV: Ivory, plug-in System Sensor relay base. ULC:
B224RBA-IV.
B224BI-WH: White, isolator base for low-profile detectors. See DN-
60054. ULC: B224BIA-WH.
B224BI-IV: Ivory isolator detector base. ULC: B224BIA-IV.
B300-6: White, standard flanged low-profile mounting base. (For 10-pack order B300-6-BP.) ULC: B300A-6.
B300-6-IV: Ivory, standard flanged low-profile mounting base. ULC:
B300A-6-IV.
B501-WHITE: European-style, 4" (10.16 cm) base. See DN-60054.
(For 10-pack order B501-WHITE-BP.) UL/ULC listed.
B501-BL: Black, 4” standard European flangeless mounting base.
UL/ULC listed.
B501-IV: Ivory color, 4” standard European flangeless mounting base. UL/ULC listed.
B200S-WH: White, intelligent programmable sounder base, capable of producing a variety of tone patterns including ANSI Temporal 3.
Compatible with synchronization protocol. See DN-60054. ULC:
B200SA-WH.
B200S-IV: Ivory intelligent, programmable sounder base. ULC:
B200SA-IV.
B200SCOA-WH: White intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO detectors. Based on B200SA. ULC listed.
B200SCOA-IV: Ivory intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO detectors. Based on B200SA. ULC listed.
B200S-LF-WH: White, low-frequency version of B200S. See DN- 60054.
B200S-LF-IV: Ivory, low-frequency version of B200S.
B200SR-WH: White intelligent programmable sounder base, Tem-poral 3 or Continuous tone. For retrofit installations replacing B501BH series bases. See DN-60054. ULC: B200SRA-WH.
B200SR-IV: Ivory intelligent programmable sounder base, Temporal 3 or Continuous tone. For retrofit installations replacing B501BH series bases. ULC: B200SRA-IV.
B200SR-LF-WH: White, low-frequency version of B200SR. See DN- 60054.
B200SR-LF-IV: Ivory, low-frequency version of B200SR.
FMM-1(A): FlashScan monitor module. See DN-6720.
FDM-1(A): FlashScan dual monitor module. See DN-6720.
FZM-1(A): FlashScan two-wire detector monitor module. See DN- 6720.
FMM-101(A): FlashScan miniature monitor module. See DN-6720.
FMM-4-20: FlashScan 4-20 mA protocol monitor module. See DN- 60411.
FTM-1(A): Firephone Telephone Module connects a remote fire-fighter telephone to a centralized telephone console. Reports status to panel. Wiring to jacks and handsets is supervised. See DN-6989.
FCM-1(A): FlashScan control module. See DN-6724.
FCM-1-REL(A): FlashScan releasing control module. See DN- 60390.
FRM-1(A): FlashScan relay module. See DN-6724.
FDRM-1(A): FlashScan dual monitor/dual relay module. See DN- 60709.
NBG-12LX: Manual pull station, addressable. See DN-6726.
N-MPS series: Manual pull stations, addressable and conventional.
ULC-listed; for use in Canada only. See DN-5497 and DN-60629.
ISO-X(A): Isolator module. See DN-2243.
ISO-6(A): Six fault isolator module. See DN-60844.
XP6-C(A): FlashScan six-circuit supervised control module. See
DN-6924.
XP6-MA(A): FlashScan six-zone interface module; connects intelli-gent alarm system to two-wire conventional detection zone. See DN- 6925.
XP6-R(A): FlashScan six-relay (Form-C) control module. See DN- 6926.
XP10-M(A): FlashScan ten-input monitor module. See DN-6923.
ENCLOSURES, CHASSIS, AND DRESS PLATES
CAB-4 Series Enclosure: NFS2-3030 mounts in a standard CAB-4 Series enclosure (available in four sizes, “A” through “D”). Backbox and door ordered separately; requires BP2-4 battery plate. A trim ring option is available for semi-flush mounting. See DN-6857.
CAB-5 Series Enclosure: NFS2-3030 can mount in CAB-5 Series enclosures designed for INSPIRE panels, using CHS-ADP adapter plate. See DN-62113 for CAB-5 options.
EQ Series Cabinets: EQ series cabinets will house amplifiers, power supplies, battery chargers and control modules. EQ cabinets are available in three sizes, “B” through “D”. See DN-60229.
Page 6 of 8 — DN-7070:S • 9/14/2022
CAB-BM Marine System: Protects equipment in shipboard and waterfront applications. Order CPU2-3030D-M; for non-English marine applications order CPU2-3030D and appropriate KP-KIT-XX.
Also order BB-MB for systems using 100 AH batteries. For a full list of required and optional equipment, see DN-60688.
CHS-M3: Mounting chassis for CPU2-3030. One required for each
CPU2-3030D/3030ND.
DP-DISP: Dress panel for top row in cabinet with CPU2-3030D installed.
DP-1B: Blank dress panel. Provides dead-front panel for unused tiers; covers DAA2/DAX series or AA-series amplifier. See DN-7046.
CHS-BH1: Battery chassis; holds two 12.0 AH batteries. Mounts on the left side of DAA2 chassis. See DN-7046.
CA-1: Chassis, occupies one tier of a CAB-4 Series enclosure. The left side accommodates one DVC-EM and a DVC-KD (optional); and the right side houses a CMIC-1 microphone and its well (optional).
See DN-7045.
CA-2: Chassis assembly, occupies two tiers of a CAB-4 Series enclosure. The left side accommodates one DVC-EM mounted on a half-chassis and one NFS2-3030 or NCA-2 mounted on a half-chas-sis. The right side houses a microphone/handset well. The CA-2 assembly includes CMIC-1 microphone. ADDR Series doors with two-tier visibility are available for use with the CA-2 configuration:
ADDR-B4, ADDR-C4, ADDR-D4 (below).
ADDR-B4*: Two-tier-sized door designed for use with the CA-2 chassis configuration. ADDR Series doors are similar to CAB-4 Series “DR” doors, but a clear window space exposes the top two tiers of the CAB-4 enclosure. Use an SBB-B4 backbox with the ADDR-B4. See DN-7045, DN-6857.
ADDR-C4*: Three-tier-sized door designed for use with the CA-2 chassis configuration. ADDR Series doors are similar to CAB-4 Series “DR” doors, but a clear window space exposes the top two tiers of the CAB-4 enclosure. Use an SBB-C4 backbox with the ADDR-C4. See DN-7045, DN-6857.
ADDR-D4*: Four-tier-sized door designed for use with the CA-2 chassis configuration. ADDR Series doors are similar to CAB-4 Series “DR” doors, but a clear window space exposes the top two tiers of the CAB-4 enclosure. Use an SBB-D4 backbox with the ADDR-D4. See DN-7045, DN-6857.
* Note: Use ADDR-B4/C4/D4 when CA-2 chassis is installed in top two rows with NCA-2 or BP-CA2. Use standard door when CA-2 is not installed in top two rows. For additional configuration information, see the DVC application guide on http://esd.notifier.com.
DPA-1: Dress panel, used with the CA-1 chassis when configured with a DVC-EM, DVC-KD, and CMIC-1. See DN-7045.
DPA-2: Dress Panel used with the CA-2 chassis assembly.
DPA-1A4: Dress panel, used with the CA-1 chassis when the CMIC- 1 is not used. Provides mounting options on right two bays for two ACS annunciators, or for blank plates. See DN-7045.
ADP-4B: Annunciator dress plate. Mounts in rows 2, 3 or 4 of a CAB-4 series enclosure. Used with ACS series annunciators.
BMP-1: Blank module for unused module positions.
DP-1B: Blank dress panel. Provides dead-front panel for unused tiers; covers DAA2/DAX series or AA-series amplifier.
BP2-4: Battery plate, required.
CHS-4L: Low-profile four-position Chassis. Mounts two AA-30 amplifiers.
CHS-4N: Chassis for mounting up to four APS-6Rs.
CHS-6: Chassis used with the XP6 and XP10 Multi-Modules.
Mounts up to six modules in any CAB-4 series row.
NFS-LBB: Battery Box. The NFS-LBB is used to mount up to two 55 AH batteries. Dimensions: Box: 24" (610 mm) wide x 14" (356 mm) high x 7.75" (197 mm) deep. Door: 24.125" (613 mm) wide x 14.25" (362 mm) high; door adds 0.0625" (approx. 1.6 mm) to depth.
BACKBOXES
NOTE: “C” suffix indicates ULC-Listed model.
ABF-1B(C) Annunciator Flush Box
ABF-1DB(C) Annunciator Flush Box with Door. UL/ULC Listed.
ABF-2B Annunciator Flush Box
ABF-2DB(C) Annunciator Flush Box with Door
ABF-4B Annunciator Flush Box
ABS-1TB(C) Annunciator Surface Box
ABS-1B(C) Annunciator Surface Box
ABS-2B Annunciator Surface Box
ABS-2D(C) Annunciator Surface Box
ABS-4D(C) Annunciator Surface Box
BB-100: Backbox for batteries and power supplies. The BB-100 mounts up to two 100 AH batteries and power supply, if needed. 30" (76.20 cm) wide x 25" (63.50 cm) high x 7.5" (19.05 cm) deep; depth includes door.
BB-200: Backbox for batteries and power supplies. Holds up to four 100 AH batteries (200 AH capacity) and power supply. 30" (76.20
cm) wide x 36" (91.44 cm) high x 7.5" (19.05 cm) deep; depth includes door.
BB-UZC: Backbox for housing the UZC-256 for applications where the UZC will not fit in panel enclosure. Black; for red, order BB-UZC- R. See DN-3404.
SEISKIT-CAB: Seismic mounting kit. Required for seismic-certified applications with NFS2-3030 and other equipment in CAB-4 Series Enclosures. Includes battery bracket for two 26 AH batteries.
SEISKIT-LBB: Seismic kit for the NFS-LBB. Includes battery bracket for two 55 AH batteries.
OTHER OPTIONS
CGW-MB: CLSS Gateway for Internet/cloud-based communication between the FACP and peripheral devices. See HON-62034.
HON-CGW-MBB: CLSS Gateway, pre-installed in a cabinet. See
HON-62034.
411: Slave digital alarm communicator. See DN-6619.
411UDAC: Digital alarm communicator. See DN-6746.
IPDACT-2, IPDACT Internet Monitoring Module: Connects to pri-mary and secondary DACT telephone output ports for internet com-munications over customer-provided Ethernet connection. Requires compatible Teldat VisorALARM Central Station Receiver. Can use DHCP or static IP. See DN-60408.
IPCHSKIT: IP Communicator Chassis Mounting Kit. For mounting an IPDACT-2/2UD onto the panel chassis or CHS-4 series chassis.
Use IPENC for external mounting applications.
IPSPLT: Y-adapter option allow connection of both panel dialer out-puts to one IPDACT-2/2UD cable input.
IPENC: External enclosure for IPDACT, includes IPBRKT mounting bracket; Red; for black, order IPENC-B.
HWF2V-COM: LTE Digital Cellular Fire Alarm Communicator and Internet Panel, Verizon LTE / IP. Provides selectable configurable paths: cellular only, IP only, or IP primary with cellular backup. Con-nects to the primary and secondary ports of a DACT. See DH-62010.
(For Canadian applications order IPGSM-4GC. See DH-60771.)
HWF2A-COM: LTE Digital Cellular Fire Alarm Communicator and Internet Panel, AT&T LTE / IP. Provides selectable configurable paths: cellular only, IP only, or IP primary with cellular backup. Con-nects to the primary and secondary ports of a DACT. (For Canadian applications order IPGSM-4GC. See DH-60771.)
NOTE: For other options including compatibility with retrofit equipment, refer to the panel's installation manual, the SLC manual, and the Device Compatibility Document.
DN-7070:S • 9/14/2022 — Page 7 of 8
SPECIFICATIONS
SYSTEM CAPACITY
• Intelligent Signaling Line Circuits........... 1 expandable to 10
• Intelligent detectors ..........................................159 per loop
• Addressable monitor/control modules ..............159 per loop
• Programmable software zones.............................over 2000
• ACS annunciators per CPU2-3030....................... 32 address x 64 or 96 points NOTE: The CPU2-3030 can support up to 96 annunciator address points per ACM-24AT/-48A.
ELECTRICAL SPECIFICATIONS
Primary Input Power:
– AMPS-24: 110-120 VAC, 50/60 Hz, 4.5 A maximum.
– AMPS-24E: 240 VAC, 50/60 Hz, 2.25 A maximum.
DC Output:
– Main 24 VDC: Up to 5.0 A
– Aux 24 VDC: Up to 5.0 A
– 5 VDC: Up to 0.15 A.
Current draw (Standby/Alarm):
– CPU2-3030D board: 0.340 A.
– CPU2-3030ND board: 0.120 A.
– LCM-320: 0.130 A.
– LEM-320: 0.100 A.
– AMPS-24(E)*: 0.13 A.
(Draws power from secondary power source only.)
NOTE: See AMPS-24(E) Manual 51907 for a complete current draw cal-culation sheet and details of input and output values.
Battery charger range: 7 AH – 200 AH. Use separate cabinet for batteries over 26 AH.
Float Rate: 27.6 V.
SHIPPING WEIGHT
• CPU2-3030D: 5.95 lb (2.70 kg).
• CPU2-3030ND: 2.90 lb (1.32 kg).
TEMPERATURE AND HUMIDITY RANGES
This system meets NFPA requirements for operation at 0 – 49°C/32
– 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F.
AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process.
Consult factory for latest listing status.
• UL/ULC Listed: S635.
• Fire Dept. of New York: COA#6211.
• CSFM: 7165-0028:0224 (Commercial).
• FM Approved.
• FM6320 Approved. Class 6320 for Gas Detection.
• City of Chicago.
• City of Denver.
• Singapore Productivity and Standards Board (PSB).
• CCCF listed.
• Fire Services Department (Hong Kong).
Marine Applications: Marine approved systems must be configured using components itemized in this document. (See Main System Components, in “Product Line Information.) Specific connections and requirements for those components are described in the instal-lation document, PN 54756. When these requirements are followed, systems are approved by the following agencies:
• US Coast Guard 161.002/55/0 (Standard 46 CFR and 161.002).
• Lloyd's Register 11/600013 (ENV 3 category).
• American Bureau of Shipping (ABS) Type Approval.
NOTE: For information on marine applications, see DN-60688.
STANDARDS
The NFS2-3030 complies with the following UL Standards and NFPA 72, International Building Code (IBC), and California Building Code (CBC) Fire Alarm Systems requirements:
• UL 864, 10th edition (Control Units and Accessories for Fire
Alarm Systems).
• UL 2610 (Commercial Premises Security Alarm Units and
Systems).
• UL 2572 (Mass Notification Systems). (NFS2-3030 version 20 or higher)
• ULC-S527-11 Standard for the Installation of Fire Alarm Sys-tems.
• LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervi-sory).
• AUXILIARY (Automatic, Manual and Waterflow) (requires TM-4).
• REMOTE STATION (Automatic, Manual, Waterflow and Sprinkler
Supervisory) (requires TM-4).
• PROPRIETARY (Automatic, Manual, Waterflow and Sprinkler
Supervisory). Not applicable for FM.
• EMERGENCY VOICE/ALARM.
• OT, PSDN (Other Technologies, Packet-switched Data Network).
• IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic).
• CBC 2007 (Seismic).
NOTI•FIRE•NET™ and ONYXWorks™ are trademarks; and FlashScan®, NOTIFIER®, ONYX®, SWIFT®, VeriFire® Tools, VESDA®, and VIEW® are all registered trademarks of Honeywell International Inc.
©2022 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Country of Origin: USA