NFPA101 NFPA72 Fire Code.pdf

PDF 43 KB Posted

Attached to
Access Control System Upgrade (Amendment 0002)
Solicitation number
FA4830-24-Q-0049
Issued by

About this file

This document is a solicitation for an Access Control System (ACS) upgrade at Moody AFB. The key requirements include:

The government is seeking a contractor to upgrade the existing LenelS2 ACS for Building 115, using DOD Common Access Cards (CAC) for access. The system must have 6 CAC readers/PIN keypads, with 5 on the exterior of the building. All exterior readers must have weather protection. The system must interface with the building's fire alarm system to automatically unlock doors during emergencies per NFPA 72 and NFPA 101 codes.

A computer system will be installed to control access, with features like immediate lockdown and scheduled door locking/unlocking. The entire system, including cabling, must come with a 1-year warranty, and the contractor must provide on-site service within 48 hours of notification. The contractor must also provide system training for military and civilian personnel. This is a 100% Small Business Set-Aside solicitation, with a site visit scheduled for 20Sep24 and questions due by 23Sep24.

View the file

Other files

File Type Posted
Questions and Answers - Site Visit.pdf PDF
Combo ACS.pdf PDF
Building 115 ACS System Diagram.pdf PDF
Base Map - ACS.pdf PDF
ACS SOW May 24.pdf PDF
Base Pass - ACS.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NFPA 101, Life Safety Code (2024 Edition)

7.2.1.6.2 * Sensor-Release of Electrical Locking Systems.

7.2.1.6.2.1

Where permitted in Chapters 11 through 43, door assemblies in the means of egress shall be permitted to be equipped with sensor-release electrical locking system hardware provided that all of the following criteria are met:

(1)

A sensor shall be provided on the egress side, arranged to electrically unlock the door leaf in the direction of egress upon detection of an approaching occupant.

(2)

Door leaves shall automatically electrically unlock in the direction of egress upon loss of power to the sensor or to the part of the locking system that electrically locks the door leaves.

(3)

Door locks shall be arranged to electrically unlock in the direction of egress from a manual release device complying with all of the following criteria:

(a) The manual release device shall be located on the egress side, 40 in. to 48 in. (1015 mm to 1220 mm) vertically above the floor, and within 60 in. (1525 mm) of the secured door openings, except as otherwise permitted by 7.2.1.6.2.1(3)(b).

(b) The requirement of 7.2.1.6.2.1(3)(a) to locate the manual release device within 60 in.

(1525 mm) of the secured door opening shall not apply to previously approved existing installations.

(c) The manual release device shall be readily accessible and clearly identified by a sign that reads as follows: PUSH TO EXIT.

(d) When operated, the manual release device shall result in direct interruption of power to the electrical lock — independent of the locking system electronics — and the lock shall remain unlocked for not less than 30 seconds.

(4)

Activation of the building fire-protective signaling system, if provided, shall automatically electrically unlock the door leaves in the direction of egress, and the door leaves shall remain electrically unlocked until the fire-protective signaling system has been manually reset.

(5)

The activation of manual fire alarm boxes that activate the building fire-protective signaling system specified in 7.2.1.6.2.1(4) shall not be required to unlock the door leaves.

(6)

Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically electrically unlock the door leaves in the direction of egress, and the door leaves shall remain electrically unlocked until the fire-protective signaling system has been manually reset.

(7)

The egress side of sensor-release electrically locked egress doors, other than existing sensor-release electrically locked egress doors, shall be provided with emergency lighting in accordance with Section 7.9.

(8)*

Door electromechanical or electromagnetic locking hardware for new installations shall be listed in accordance with UL 294, Access Control System Units, or UL 1034, Burglary-

Resistant Electric Locking Mechanisms.

NFPA 72, National Fire Alarm and Signaling Code (2022 Edition)

21.10 Electrically Locked Doors.

21.10.1*

Electrically locked doors in a required means of egress shall unlock in the direction of egress where required by other laws, codes, and governing standards.

21.10.2

For all means of egress doors connected in accordance with 21.10.1 where secondary power supplies of fire alarm control units are used, they shall comply with 10.6.7.

21.10.3*

Secondary power supplies of fire alarm control units shall not be utilized to maintain means of egress doors in the locked condition unless the fire alarm control unit is arranged with circuitry and su icient secondary power to ensure that the means of egress doors will unlock within 10 minutes of loss of primary power.

21.10.4

Locks powered by independent power supplies dedicated to lock power and access control functions, and that unlock upon loss of power, shall not be required to comply with

21.10.2.

21.10.5

If means of egress doors are unlocked by the fire alarm system, the unlocking function shall occur prior to, or concurrent with, activation of any public-mode notification appliances in the area(s) served by the normally locked means of egress doors.

21.10.6

All doors that are required to be unlocked by the fire alarm system in accordance with

21.10.1 shall remain unlocked until the fire alarm condition is manually reset.