NFC - Construction Drawing Set.pdf
PDF 6 MB Posted
- Solicitation number
- S-24800-00016791
- Issued by
- Oregon
About this file
This is a construction drawing set prepared by CIDA, Inc. for the Oregon Military Department's Central Oregon Unit Training Equipment Site (COUTES) Latrine Expansion project located at 2899 Ochoco Way in Redmond, Oregon. The project comprises an approximately 350 square foot interior remodel that updates the women's toilet/shower room to be ADA compliant, repurposes the men's locker room into a women's locker room, and relocates the men's locker room to the existing women's locker room space. The work includes creating new doorway openings in existing concrete masonry unit walls for pedestrian connectivity and minor modifications to existing utilities, electrical systems, and plumbing fixtures. The project is designed under the 2022 Oregon Structural Specialty Code (OSSC 2022) for a Type II-A sprinklered construction with occupancy classifications including Assembly, Business, and Hazardous occupancies. No site work is proposed, and no modifications to existing required fire-rated assemblies are planned. The drawing set includes architectural plans, reflected ceiling plans, wall sections, finish schedules, plumbing details, mechanical and electrical plans, fire life safety provisions, and structural details for new openings in the exterior masonry walls.
The construction documents detail comprehensive specifications for materials and installation requirements, including gypsum board assemblies, ceramic tile finishes with specific color and grout selections, resilient base, steel toilet compartments with stainless steel hardware, grab bars and accessibility features complying with ADA and ANSI A117.1 standards, and various toilet room accessories. All finishes are specified with exact manufacturer names, models, and colors, including painted surfaces in Sherwin Williams SW 6168 Moderne White with epoxy finish for wet areas and new 2"x2" floor tile in Desert Gray Speckled by Daltile. Structural steel for new header beams at doorway openings is specified as ASTM A36 with welding by certified welders using E70XX electrodes per AWS standards. The project requires special inspection in accordance with the 2022 OSSC Chapter 17 for structural steel work, material verification through certified mill test reports, and continuous observation of welding operations. MEP engineering is provided by R&W Engineering of Beaverton, Oregon, with the architect/structural engineer being CIDA, Inc. of Portland, Oregon.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ITB 200038C001 final for posting.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OMD REDMOND - LOCKER ROOM EXPANSION
REDMOND, OREGON
LEGAL DESCRIPTION
TAX LOT: 1513000000116
TAX MAP: 150565 - 15 13 00
CIDA, INC.
15895 SW 72ND AVE, SUITE 200
PORTLAND, OREGON 97224
(T): (503) 226-1285 (F): (503) 226-1670
CONTACT: MYA PALUCH
RELEASES
COVER SHEET
/2
/2
P
A G
E T
U R
N C
H E C
K S
E T
CS1 COVER SHEET & SITE PLAN
ARCHITECTURAL
A1.1 DEMOLITION PLAN & FLOOR PLAN
CLIENTOREGON MILITARY DEPARTMENT
1/32"=1'-0"
BUILDING KEY PLAN3
NORTH
CS1
PROJECT DESCRIPTION
THIS PROJECT IS AN APPROXIMATELY 350 SQUARE FOOT INTERIOR REMODEL AT OMD'S EXISTING CENTRAL OREGON TRAINING EQUIPMENT SITE (COUTES) AT 2899 OCHOCO WAY IN REDMOND OREGON. THE AREA OF WORK INCLUDES UPDATING THE WOMEN'S TOILET/SHOWER ROOM TO BE ADA COMPLIANT, RE-PURPOSING THE MEN'S LOCKER ROOM INTO A WOMEN'S
LOCKER ROOM AND RELOCATING THE MEN'S LOCKER ROOM TO THE EXISTING WOMEN'S LOCKER ROOM. THESE IMPROVEMENTS REQUIRE NEW DOORWAY SIZED OPENINGS IN EXISTING CMU WALLS FOR PEDESTRIAN CONNECTIVITY. IN
ADDITION THERE ARE MINOR MODIFICATIONS TO EXISTING UTILITIES, ELECTRICAL, AND OF PLUMBING FIXTURES. NO WORK
WITHIN HIGH-HAZARD OCCUPANCY AREAS PROPOSED AND NO MODIFICATIONS TO EXISTING
REQUIRED FIRE RATED ASSEMBLIES PROPOSED. NO SITE WORK IS PROPOSED.
STRUCTURAL
A4.1 WALL SECTIONS & FINISH FLOOR PLAN
A1.1 STRONGBACKING DETAILS
A6.1 ENLARGED T.R. PLANS & ELEVATIONS
FLS1 FIRE LIFE SAFETY PLAN
BUILDING CODE INFORMATION
DESIGN CODE: OSSC 1986
DESIGN CODE (AREA OF WORK) OSSC 2022
CONSTRUCTION TYPE: II-A (SPRINKLERED)
OCCUPANCY (NO CHANGE): A, B, H-4, H-2 (SEPARATED)
BUILDING AREA (NO CHANGE): 10,627 SF
AREA OF WORK: 350 SF
BUILDING HEIGHT (NO CHANGE) +/- 24'-0"
SEE FIRE AND LIFE SAFETY SHEET FOR FULL CODE SUMMARY
A1.2 DEMOLITION RCP & REFLECTED CEILING PLAN
2899 OCHOCO WAY
REDMOND, OREGON 97756
(T): (555) 555-5555
CONTACT: ARCHITECT
MEP ENGINEERR&W ENGINEERING
9615 SW ALLEN BLVD #107
BEAVERTON, OREGON, 97005
(T): (503) 292-6000
CONTACT: ARCHITECT
23456789
4CONTRACTORTBD
ARCHITECT/ STRUCTURAL ENGINEER
230257.01
/0
/2
P A
G E T
U R
N C
H E C
K S
E T
/0
/2
P E R
M
IT
S E T
C 2025 CIDA, P.C./CIDA ALL RIGHTS RESERVED
IS
S U
E D
D A
T E
1 5 8 9 5 S W 7 2 N D A V E S U I T E 2 0 0
P O R T L A N D , O R E G O N 9 7 2 2 4
T E L : 5 0 3 . 2 2 6 . 1 2 8 5
F A X : 5 0 3 . 2 2 6 . 1 6 7 0
W W W . C I D A I N C . C O M
E :\a d ca d d \2
\0
.0
O
M D
R e d m o n d \0
-C u rr e n t\
C A
D \0
C
S .d w g
D e c
, 2
:1 p m
ARCHITECTURE
ENGINEERING
P L A N N I N G
I N T E R I O R S
T E N
A N
T I M
P R
O V
E M
E N
T F
O R
O M
D R
ED
M
O N
D
LO
CK
ER
R
O O
M E
XP
A
N
SI
O N
O
C H
O C
O W
A Y
R E D
M O
N D
, O R
E G
O N
NO SCALE
VICINITY MAP2
NORTH
CS1
H W
Y . 9
O C
H O
C O
W A
Y
OCHOCO HWY
REDMOND M
UNICIPAL A
IRPORT
SITE
CS1
COVERSHEET
1"=150'
ARCHITECTURAL SITE PLAN - FOR REFERENCE ONLY1
NORTH
CS1
SITE
N U
N
IT
M A
IN
C
A N
A L
REDMOND-POWELL BUTTE RD
GN1 GENERAL NOTES
AREA OF WORK
A1.1
A6.2 ENLARGED T.R. PLANS & ELEVATIONS
MECHANICAL
M2.1 FLOOR PLAN - MECHANICAL
M0.1 MECHANICAL SCHEDULES, LEGENDS, SPECIFICATIONS
ELECTRICAL
E1.1 FLOOR PLAN - ELECTRICAL
E2.1 PARTIAL FLOOR PLAN - POWER
E0.1 ELECTRICAL SCHEDULES, LEGENDS, ABBREVIATIONS
E2.2 PARTIAL FLOOR PLAN - LIGHTING
E3.1 ELECTRICAL SPECIFICATION
P0.1 PLUMBING SCHEDULES, LEGENDS, AND ABBREVIATIONS
PLUMBING
PD2.1 FLOOR PLAN - PLUMBING DEMOLITION
P2.1 FLOOR PLAN - WASTE AND VENT
P2.2 FLOOR PLAN - HOT AND COLD WATER
P3.1 PLUMBING SPECIFICATIONS
P3.2 PLUMBING SPECIFICATIONS
P3.3 PLUMBING SPECIFICATIONS
/0
/2
P
E R
M
IT
S E T
PRELIMINARY
PLAN ONLY-NOT
FOR
CONSTRUCTION
IN
T
ER
IO
R D
IA
G
O N
A L
5'
-9
/2
15'-10"
28'-6"
11'-6"
50'-6"
14'-0"
29'-6"
29'-8"
86'-6"
72'-2"
81'-9" 4 '-0
'-1
'-1
'-3
'-1
'-1
'-4
(E) FLAMMABLE
MATERIALS STORAGE
(E) WORK BAYS
(E) WOMEN'S T.R.
(E) MEN'S T.R.
WOMEN'S
LOCKER ROOM
(E) BREAK ROOM
(E) COMM/ELECTRICAL
MEN'S
LOCKER ROOM
CORRIDOR
CUSTODIAL
'-0
'-8
(E) GENERAL
FOREMAN
(E) FOREMAN
(E) SUPPLY ROOM
(E) CLERK
(E) LIBRARY
MECHANICAL
24'-4" 40'-6"
'-1
'-0
'-1
10'-0" 51'-7"
16'-0" 62'-6"
'-5
'-9
" 1 '-9
'-1
FE
C
D
IST
A N
C E B
ET
W
EEN
EX
IT
S
57'-2"
FE
C
FEC
FE
C
FECFEC
FE
C
FE
C
230257.01
/0
/2
P A
G E T
U R
N C
H E C
K S
E T
/0
/2
P E R
M
IT
S E T
C 2025 CIDA, P.C./CIDA ALL RIGHTS RESERVED
IS
S U
E D
D A
T E
1 5 8 9 5 S W 7 2 N D A V E S U I T E 2 0 0
P O R T L A N D , O R E G O N 9 7 2 2 4
T E L : 5 0 3 . 2 2 6 . 1 2 8 5
F A X : 5 0 3 . 2 2 6 . 1 6 7 0
W W W . C I D A I N C . C O M
E :\a d ca d d \2
\0
.0
O
M D
R e d m o n d \0
-C u rr e n t\
C A
D \0
F
L S F
IR
E L
IF
E S
A
FE
T Y
P L A
N .d w g
D e c
, 2
:1 p m
ARCHITECTURE
ENGINEERING
P L A N N I N G
I N T E R I O R S
T E N
A N
T I M
P R
O V
E M
E N
T F
O R
O M
D R
ED
M
O N
D
LO
CK
ER
R
O O
M E
XP
A
N
SI
O N
O
C H
O C
O W
A Y
R E D
M O
N D
, O R
E G
O N
FLS1
FIRE LIFE SAFETY PLAN
ORIGINAL PERMIT DESIGN CODE: 1986 OREGON STRUCTURAL SPECIALTY CODE (OSSC 1986)
CURRENT PERMIT DESIGN CODE: 2022 OREGON STRUCTURAL SPECIALITY CODE (OSSC 2022)
CURRENT PERMIT ENERGY CODE: 2021OREGON EFFICIENCY SPECIALTY CODE (OESC 2021)
BUILDING GROSS AREA: 10,627 SF
AREA OF WORK: 350 SF
USE AND OCCUPANCY CLASSIFICATION (CHAPTER 3):
OCCUPANCY CLASSIFICATION (302): A
B H-4
H-2* (SEPARATED)
GENERAL BUILDING HEIGHTS AND AREAS (CHAPTER 5):
EXISTING. NO CHANGE PROPOSED.
TYPE OF CONSTRUCTION (CHAPTER 6):
CONSTRUCTION TYPE: II-N, SPRINKLERED (II-A)
FIRE RATING REQUIREMENTS:
THIS IS AN EXISTING II-N SPRINKLERED CONSTRUCTION:
EXTERIOR LOAD-BEARING WALLS 1 HR RATED REQUIRED (NO CHANGE)
INTERIOR NON-LOAD BEARING WALLS 1 HR RATED REQUIRED
ROOF CONSTRUCTION 1 HR RATED REQUIRED (NO CHANGE)
EXISTING AND PROPOSED CONSTRUCTION MEETS THESE REQUIREMENTS.
FIRE PROTECTION AND LIFE SAFETY SYSTEMS (CHAPTER 9):
903 AUTOMATIC SPRINKLER SYSTEMS
903.2.5 GROUP H: AUTOMATIC FIRE SPRINKLERS SHALL BE PROVIDED IN HIGH HAZARD OCCUPANCIES AS REQUIRED IN SECTIONS
903.2.5.1 THROUGH 903.2.5.
MEANS OF EGRESS (CHAPTER 10):
1004 OCCUPANT LOAD - SEE OCCUPANT TABLE ON THIS SHEET
1005.3 EGRESS SIGNAGE - SEE 1/FLS1 PLAN FOR DOOR SIGNS
1006 EXIT AND EXIT ACCESS DOORWAYS
1006.1 NUMBER OF EXITS AND EXIT ACCESS DOORWAYS: H-OCCUPANCY
1006.2.1 NUMBER OF EXITS REQUIRED: 10
NUMBER OF EXITS PROVIDED: 10
MAX LENGTH OF COMMON PATH H-2 (SPRINKELERED): 100', LONGEST LENGTH PROVIDED(NO CHANGE) -- SEE 1/FLS1
MAX LENGTH OF COMMON PATH H-4 (SPRINKELERED): 175', LONGEST LENGTH PROVIDED(NO CHANGE) -- SEE 1/FLS1
1007 EXIT OR EXIT ACCESS DOORWAY CONFIGURATION
1007.1 EXCEPTION 2, WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903 .1.1 OR 903.1.2, THE SEAPARATION DISTANCE OF THE EXIT DOORS OR EXIT ACCESS DOORWAYS SHALL NOT BE LESS THAN ONE-THIRD OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA RESERVED.
SEE FLS1 FOR DIMENSIONS PROVIDED.
1008 MEANS OF EGRESS ILLUMINATION
ILLUMINATION LEVEL (OSSC 1008.2.1)
MINIMUM 1 FOOT CANDLE AT THE WALKING SURFACE LEVEL
1008.3.2 AREAS REQUIRED TO BE ILLUMINATED BY EMERGENCY POWER
CORRIDORS, EXIT PASSAGEWAYS, AND EXIT ENCLOSURES
INTERIOR EXIT DISCHARGE ELEMENTS
EXTERIOR LANDINGS
1008.3.4 DURATION
EMERGENCY POWER SHALL BE PROVIDED FOR A DURATION OF NINETY(90) MINUTES MINIMUM
1008.3.5 ILLUMINATION LEVEL UNDER EMERGENCY POWER
ILLUMINATION EMERGENCY POWER (OSSC 1008.3.5):
INITIAL ILLUMINATION: 1 FOOT-CANDLE AVERAGE W/ 0.1 FOOT-CANDLE MINIMUM AT ANY POINT AT FLOOR LEVEL
END OF EMERGENCY LIGHTING PERIOD: 0.6 FOOT-CANDLE AVERAGE W/ 0. FOOT-CANDLE MINIMUM AT ANY POINT AT FLOOR LEVEL
1009 ACCESSIBLE MEANS OF EGRESS (OSSC 1009):
1009.1 REQUIRED ACCESSIBLE MEANS OF EGRESS: 2
ACCESSIBLE MEANS OF EGRESS PROVIDED: 3
1013 EXIT SIGNS
SEE FLS1 FOR LOCATIONS OF EXIT SIGNAGE
ILLUMINATION (OSSC 1013.3): EXIT SIGNS ARE REQUIRED TO BE INTERNALLY OR EXTERNALLY ILLUMINATED
ACCESSIBILITY (CHAPTER 11):
SEE FLOOR PLANS FOR REQUIRED CLEARANCES AT DOORS, TOILET ROOMS AND FIXTURES
SEE DETAILS AND INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS
SEE FLS 1 FOR SIGNAGE LOCATIONS
SIGNAGE GRAPHICS, LOCATION & MOUNTING TO COMPLY WITH OSSC CH. 11
OSSC 1105 ACCESSIBLE ENTRANCES
1105.1 PUBLIC ENTRANCES - ALL PUBLIC ENTRANCES ARE ACCESSIBLE
INTERIOR ENVIRONMENT: (CHAPTER 12):
1210.2 TOILET AND BATHROOM REQUIREMENTS: FINISH MATERIALS
ALL MATERIALS TO COMPLY WITH SMOOTH, NON-ABSORBENT SURFACE CRITERIA.
EXISTING BUILDING AND STRUCTURES (CHAPTER 34):
3403.1.3 ALTERATION, ADDITION, OR CHANGE OF OCCUPANCY
THE ALTERATION OF ALL EXISTING BUILDINGS SHALL COMPLY WITH THIS SECTION AND ONE OF THE METHODS LISTED IN SECTION
3403.1.3.1, 3403.1.3.2, 3403.1.3.3 AS SELECTED BY THE APPLICANT.
3403.1.3.2 WORK AREA COMPLIANCE METHOD
COMPLIANCE WITH THE APPLICABLE REQUIREMENTS OF SECTIONS 3406 AND 3412
GENERAL BUILDING CODE NOTES
A. APPLICABLE CODES: ALL WORK SHALL BE IN CONFORMANCE WITH ALL FEDERAL,
STATE, AND LOCAL CODES. SPECIFICATIONS AND STANDARDS SHALL MEAN, AND
ARE INTENDED TO BE, THE LATEST EDITION, AMENDMENT OR REVISION OF SUCH
REFERENCE STANDARD IN EFFECT AS OF THE DATE OF THE CONTRACT
DOCUMENTS.
B. PRIOR TO START OF WORK, CONTRACTOR TO VERIFY EXISTING CONDITIONS
INDICATED AND NOTIFY ARCHITECT OF ANY DISCREPANCIES.
C. ALL DEMO WORK IN EXISTING FACILITY ASSUMED TO BE NON-STRUCTURAL -
CONTRACTOR TO CONFIRM DEMO CONDITIONS INDICATED & NOTIFY A/E IF
ANY ARE DISCOVERED OR QUESTIONED TO BE STRUCTURAL.
D. PROVIDE EXIT ILLUMINATION AND SIGNAGE PER SECTION 1006 & SIGNAGE PER
SECTION 1011 OF THE IBC.
E. ALL HARDWARE TO COMPLY W/ ADA REQUIREMENTS.
F. ALL EQUIPMENT BY OTHERS.
G. CONTRACTOR TO COORDINATE ALL EQUIPMENT BY TENANT WITH POWER,
WATER DATA AND MECHANICAL REQUIREMENTS.
BUILDING CODE ANALYSIS
NEW WALLS- REFER TO SHEET A1.1 FOR WALL TYPE INFORMATION
(E) ILLUMINATED EXIT SIGN
FEC (E) FIRE EXTINGUISHER CABINET- COORDINATE QUANTITY
AND LOCATION WITH FIRE MARSHAL PRIOR TO INSTALLATION
FLS FLOOR LEGEND
(N) DIRECTIONAL ILLUMINATED EXIT SIGN
HOSE BIB
NEW
EXISTING
(N)
(E)
CORRIDOR
ROOM NAME & NUMBER
NOT IN SCOPE
TOTAL BUILDING PLUMBING FIXTURE CALCULATIONS
OCCUPANCY CLASSIFICATION
TOTAL OCCUPANT
LOAD
REQUIRED WATER CLOSET RATIO -
(URINALS MAY REPLACE WC AT RATIO
OF 1 URINAL PER 2/3 WC)
REQUIRED
LAVATORY RATIO
REQUIRED
WATER
CLOSETS
REQUIRED
LAVATORIES
A
ACCESSORY
ASSEMBLY
30 1:125 1:65 1:200 0.24 ; 0.46 0.15
B BUSINESS 5 1:25 1ST 50; 1:50 1:40 1ST 80; 1:80 0.20 0.125
H-2
FLAMMABLE
STORAGE
2 1:100 1:100 0.02 0.02
H-4 FABRICATION 31 1:100 1:100 0.31 0.31
TOTAL NUMBER OF FIXTURES REQUIRED 1.23 0.605
TOTAL NUMBER OF FIXTURES PROVIDED 4 3
1/8" = 1'-0"
FIRE LIFE SAFETY PLAN1
FLS1
N.I.S.
N.I.S.
OSSC 1004 OCCUPANCY LOAD TABLE
ROOM
# NAME OCCUPANCY TYPE LOAD FACTOR AREA LOAD
(E) FLAMMABLE
MATERIALS STORAGE
HIGH HAZARD-2 150 2
103 (E) WORK BAYS HIGH HAZARD-4 200 6144 31
105 (E) CLERK BUSINESS 150 115 1
106 (E) GENERAL FOREMAN BUSINESS 150 168 2
107 (E) FOREMAN BUSINESS 150 247 2
(E) SUPPLY ROOM/
TOOL ROOM
H4 150 990 7
(E) MECHANICAL
ROOM
ACCESSORY MECHANICAL 300 135 1
110 (E) CORRIDOR-1 N/A -- 180 --
111 (E) WOMEN'S T.R. N/A -- 136 --
112 (E) CUSTODIAL ACCESSORY STORAGE 300 24 1
113 (E) MEN'S T.R. N/A -- 200 --
114 MEN'S LOCKER
ROOM N/A 50 324 7
115 (E) BREAK ROOM ACCESSORY ASSEMBLY 150 226 2
116 WOMEN'S LOCKER
ROOM N/A 50 189 4
117 (E) COMM/ELECTRICAL ACCESSORY MECHANICAL 300 226 1
118 (E) LIBRARY ACCESSORY ASSEMBLY 50 324 7
119 (E) CORRIDOR-2 N/A -- 180 --
TOTAL OCCUPANT LOAD
10-0" 60'-0"
50'-0"
TRAVEL DISTANCE TO EXIT ACCESS
EGRESS PATH
COMMON PATH OF EGRESS TRAVEL DISTANCE TO
POINT AT WHICH CHOICE OF 2 EXITS ARE AVAILABLE
POINT AT WHICH CHOICE OF 2 EXITS BECOMES AVAILABLE
COMMON PATH OF EGRESS TRAVEL
TOTAL TRAVEL DISTANCE TO EXIT ACESS
NORTH
PRELIMINARY
PLAN ONLY-NOT
A.
DIVISION 1 GENERAL REQUIREMENTS
1.1 GENERAL CONDITIONS
A. ALL WORK UNDER THIS CONTRACT TO BE IN ACCORDANCE WITH THE GENERAL CONDITIONS OF THE CONTRACT FOR
CONSTRUCTION AIA DOCUMENT A201, 2007 EDITION OR OTHER APPROVED FORMAT.
B. WHERE ANY ARTICLE, PARAGRAPH, SUBPARAGRAPH OR CLAUSE OF THE GENERAL CONDITIONS ISMODIFIED OR DELETED BY THESE
SUPPLEMENTS, THE UNALTERED PROVISIONS OF THAT ARTICLE, PARAGRAPH, SUBPARAGRAPH OR CLAUSE SHALL REMAIN IN EFFECT.
1.2 INTERPRETATION
A. VIEWED OR APPROVED BY ARCHITECT/ENGINEER SHALL MEAN WRITTEN REVIEW OR APPROVAL BY ARCHITECT/ENGINEER OR AN
AUTHORIZED CONSULTANT.
B. REFERENCE IN THE SPECIFICATIONS TO A SINGLE ITEM OR PIECE OF EQUIPMENT SHALL APPLY TO AS MANY SUCH ITEMS AS ARE
INDICATED ON DRAWINGS OR REQUIRED TO COMPLETE THE PROJECT.
C. INDICATING AN ITEM OR METHOD ON THE DRAWINGS REQUIRES THE CONTRACTOR TO FURNISH, FABRICATE AND INSTALL THE
ITEM, UNLESS INDICATED OTHERWISE.
1.3 FEES
A. UNLESS OTHERWISE INDICATED IN THE CONTRACT DOCUMENTS, THE OWNER SHALL PAY FOR PLAN CHECK FEES AND BUILDING
PERMIT FEES, INCLUDING SEWER, GAS AND WATER CONNECTION FEES, AS WELL AS OTHER ASSESSMENTS OR FEES ESTABLISHED BY
THE AUTHORITY HAVING JURISDICTION. THE CONTRACTORSHALL PAY FOR ALL OTHER PERMITS, FEES, LICENSES AND INSPECTIONS
NECESSARY FOR PROPER EXECUTION AND COMPLETION OF WORK, INCLUDING PLUMBING, MECHANICAL AND ELECTRICAL PERMIT
FEES.
1.4 SUBSTITUTIONS
A. SUBSTITUTION REQUESTS: SUBMIT THREE COPIES OF EACH REQUEST FOR CONSIDERATION. IDENTIFY PRODUCT OR FABRICATION
OR INSTALLATION METHOD TO BE REPLACED. INCLUDE SPECIFICATION SECTION NUMBER AND TITLE AND DRAWING NUMBERS
AND TITLES.
B. SUBSTITUTIONS FOR CAUSE: SUBMIT REQUESTS FOR SUBSTITUTION IMMEDIATELY UPON DISCOVERY OF NEED FOR CHANGE, BUT
NOT LATER THAN 15 DAYS PRIOR TO TIME REQUIRED FOR PREPARATION AND REVIEW OF RELATED SUBMITTALS.
C. SUBSTITUTIONS FOR CONVENIENCE: ARCHITECT WILL CONSIDER REQUESTS FOR SUBSTITUTION IF RECEIVED WITHIN 60 DAYS
AFTER THE NOTICE OF AWARD.
1.5 SUBMITTALS
A. SHOP DRAWINGS: PREPARE PROJECT-SPECIFIC INFORMATION, DRAWN ACCURATELY TO SCALE. DO NOT BASE SHOP DRAWINGS
ON REPRODUCTIONS OF THE CONTRACT DOCUMENTS OR STANDARD PRINTED DATA,UNLESS SUBMITTAL BASED UPON
ARCHITECT'S DIGITAL DATA DRAWING FILES IS OTHERWISE PERMITTED.
B. SAMPLES: SUBMIT SAMPLES FOR REVIEW OF KIND, COLOR, PATTERN, AND TEXTURE FOR A CHECK OF THESE CHARACTERISTICS WITH
OTHER ELEMENTS AND FOR A COMPARISON OF THESE CHARACTERISTICS BETWEEN SUBMITTAL AND ACTUAL COMPONENT AS
DELIVERED AND INSTALLED.
C. PRODUCT DATA: COLLECT INFORMATION INTO A SINGLE SUBMITTAL FOR EACH ELEMENT OF CONSTRUCTION AND TYPE OF
PRODUCT OR EQUIPMENT.
1.6 EXECUTION REQUIREMENTS
A. CUTTING AND PATCHING: COMPLY WITH REQUIREMENTS FOR AND LIMITATIONS ON CUTTING AND PATCHING OF
CONSTRUCTION ELEMENTS.
1. STRUCTURAL ELEMENTS: WHEN CUTTING AND PATCHING STRUCTURAL ELEMENTS, NOTIFY ARCHITECT OF LOCATIONS AND
DETAILS OF CUTTING AND AWAIT DIRECTIONS FROM THE ARCHITECT BEFORE PROCEEDING. SHORE, BRACE, AND SUPPORT
STRUCTURAL ELEMENT DURING CUTTING AND PATCHING. DO NOT CUT AND PATCH STRUCTURAL ELEMENTS IN A MANNER
THAT COULD CHANGE THEIR LOAD-CARRYING CAPACITY OR INCREASE DEFLECTION
2. OPERATIONAL ELEMENTS: DO NOT CUT AND PATCH OPERATING ELEMENTS AND RELATED COMPONENTS IN A MANNER
THAT RESULTS IN REDUCING THEIR CAPACITY TO PERFORM AS INTENDED OR THAT RESULTS IN INCREASED MAINTENANCE
OR DECREASED OPERATIONAL LIFE OR SAFETY.
3. OTHER CONSTRUCTION ELEMENTS: DO NOT CUT AND PATCH OTHER CONSTRUCTION ELEMENTS OR COMPONENTS IN A
MANNER THAT COULD CHANGE THEIR LOAD-CARRYING CAPACITY, THAT RESULTS IN REDUCING THEIR CAPACITY TO
PERFORM AS INTENDED, OR THAT RESULTS IN INCREASED MAINTENANCE OR DECREASED OPERATIONAL LIFE OR SAFETY.
4. VISUAL ELEMENTS: DO NOT CUT AND PATCH CONSTRUCTION IN A MANNER THAT RESULTS IN VISUAL EVIDENCE OF
CUTTING AND PATCHING. DO NOT CUT AND PATCH EXPOSED CONSTRUCTION IN A MANNER THAT WOULD, IN
ARCHITECT'S OPINION, REDUCE THE BUILDING'S AESTHETIC QUALITIES. REMOVE AND REPLACE CONSTRUCTION THAT HAS
BEEN CUT AND PATCHED IN A VISUALLY UNSATISFACTORY MANNER.
B. EXISTING CONDITIONS: THE EXISTENCE AND LOCATION OF UNDERGROUND AND OTHER UTILITIES AND CONSTRUCTION
INDICATED AS EXISTING ARE NOT GUARANTEED. BEFORE BEGINNING SITEWORK, INVESTIGATE AND VERIFY THE EXISTENCE AND
LOCATION OF UNDERGROUND UTILITIES, MECHANICAL AND ELECTRICAL SYSTEMS, AND OTHER CONSTRUCTION AFFECTING THE
WORK.
C. BEFORE CONSTRUCTION, VERIFY THE LOCATION AND INVERT ELEVATION AT POINTS OF CONNECTION OF SANITARY SEWER, STORM SEWER, AND WATER-SERVICE PIPING; UNDERGROUND ELECTRICAL SERVICES, AND OTHER UTILITIES.
D. SITE IMPROVEMENTS: LOCATE AND LAY OUT SITE IMPROVEMENTS, INCLUDING PAVEMENTS, GRADING, FILL AND TOPSOIL
PLACEMENT, UTILITY SLOPES, AND RIM AND INVERT ELEVATIONS.
E. BUILDING LINES AND LEVELS: LOCATE AND LAY OUT CONTROL LINES AND LEVELS FOR STRUCTURES, BUILDING FOUNDATIONS, COLUMN GRIDS, AND FLOOR LEVELS, INCLUDING THOSE REQUIRED FOR MECHANICAL AND ELECTRICAL WORK. TRANSFER SURVEY
MARKINGS AND ELEVATIONS FOR USE WITH CONTROL LINES AND LEVELS. LEVEL FOUNDATIONS AND PIERS FROM TWO OR MORE
LOCATIONS.
F. TEMPORARY SUPPORT: PROVIDE TEMPORARY SUPPORT OF WORK TO BE CUT.
G. PROTECTION: PROTECT IN-PLACE CONSTRUCTION DURING CUTTING AND PATCHING TO PREVENT DAMAGE. PROVIDE
PROTECTION FROM ADVERSE WEATHER CONDITIONS FOR PORTIONS OF PROJECT THAT MIGHT BE EXPOSED DURING CUTTING
AND PATCHING OPERATIONS.
H. ADJACENT OCCUPIED AREAS: AVOID INTERFERENCE WITH USE OF ADJOINING AREAS OR INTERRUPTION OF FREE PASSAGE TO
ADJOINING AREAS.
I. EXISTING UTILITY SERVICES AND MECHANICAL/ELECTRICAL SYSTEMS: WHERE EXISTING SERVICES/SYSTEMS ARE REQUIRED TO BE
REMOVED, RELOCATED, OR ABANDONED, BYPASS SUCH SERVICES/SYSTEMS BEFORE CUTTING TO MINIMIZE INTERRUPTION TO
OCCUPIED AREAS.
J. CUTTING: CUT IN-PLACE CONSTRUCTION BY SAWING, DRILLING, BREAKING, CHIPPING, GRINDING, AND SIMILAR OPERATIONS, INCLUDING EXCAVATION, USING METHODS LEAST LIKELY TO DAMAGE ELEMENTS RETAINED OR ADJOINING CONSTRUCTION. IF
POSSIBLE, REVIEW PROPOSED PROCEDURES WITH ORIGINAL INSTALLER; COMPLY WITH ORIGINAL INSTALLER'S WRITTEN
RECOMMENDATIONS.
K. PATCHING: PATCH CONSTRUCTION BY FILLING, REPAIRING, REFINISHING, CLOSING UP, AND SIMILAR OPERATIONS FOLLOWING
PERFORMANCE OF OTHER WORK. PATCH WITH DURABLE SEAMS THAT ARE AS INVISIBLE AS PRACTICABLE. PROVIDE MATERIALS
AND COMPLY WITH INSTALLATION REQUIREMENTS SPECIFIED IN OTHER SECTIONS, WHERE APPLICABLE.
L. CLEANING: CLEAN PROJECT SITE AND WORK AREAS DAILY, INCLUDING COMMON AREAS. ENFORCE REQUIREMENTS STRICTLY.
DISPOSE OF MATERIALS LAWFULLY.
M. PROVIDE FINAL PROTECTION AND MAINTAIN CONDITIONS THAT ENSURE INSTALLED WORK IS WITHOUT DAMAGE OR
DETERIORATION AT TIME OF SUBSTANTIAL COMPLETION.
DIVISION 2 EXISTING CONDITIONS
2.1 SELECTIVE DEMOLITION
A. GENERAL: DEMOLISH AND REMOVE EXISTING CONSTRUCTION ONLY TO THE EXTENT REQUIRED BY NEW CONSTRUCTION AND AS
INDICATED. USE METHODS REQUIRED TO COMPLETE THE WORK WITHIN LIMITATIONS OF GOVERNING REGULATIONS AND AS
FOLLOWS:
1. NEATLY CUT OPENINGS AND HOLES PLUMB, SQUARE, AND TRUE TO DIMENSIONS REQUIRED. USE CUTTING METHODS LEAST
LIKELY TO DAMAGE CONSTRUCTION TO REMAIN OR ADJOINING CONSTRUCTION. USE HAND TOOLS OR SMALL POWER
TOOLS DESIGNED FOR SAWING OR GRINDING, NOT HAMMERING AND CHOPPING, TO MINIMIZE DISTURBANCE OF ADJACENT
SURFACES. TEMPORARILY COVER OPENINGS TO REMAIN.
2. CUT OR DRILL FROM THE EXPOSED OR FINISHED SIDE INTO CONCEALED SURFACES TO AVOID MARRING EXISTING FINISHED
SURFACES.
3. DO NOT USE CUTTING TORCHES UNTIL WORK AREA IS CLEARED OF FLAMMABLE MATERIALS. AT CONCEALED SPACES, SUCH
AS DUCT AND PIPE INTERIORS, VERIFY CONDITION AND CONTENTS OF HIDDEN SPACE BEFORE STARTING FLAME-CUTTING
OPERATIONS. MAINTAIN WATCH AND PORTABLE FIRE-SUPPRESSION DEVICES DURING FLAME-CUTTING OPERATIONS.
4. LOCATE SELECTIVE DEMOLITION EQUIPMENT AND REMOVE DEBRIS AND MATERIALS SO AS NOT TO IMPOSE EXCESSIVE LOADS
ON SUPPORTING WALLS, FLOORS, OR FRAMING.
5. DISPOSE OF DEMOLISHED ITEMS AND MATERIALS PROMPTLY.
B. REUSE OF BUILDING ELEMENTS: PROJECT HAS BEEN DESIGNED TO RESULT IN END-OF-PROJECT RATES FOR REUSE OF BUILDING
ELEMENTS AS FOLLOWS. DO NOT DEMOLISH BUILDING ELEMENTS BEYOND WHAT IS INDICATED ON DRAWINGS WITHOUT
ARCHITECT'S APPROVAL.
C. REMOVED AND SALVAGED ITEMS:
1. CLEAN SALVAGED ITEMS: PACK OR CRATE ITEMS AFTER CLEANING. IDENTIFY CONTENTS OF CONTAINERS.
2. STORE ITEMS IN A SECURE AREA UNTIL DELIVERY TO OWNER.
3. PROTECT ITEMS FROM DAMAGE DURING TRANSPORT AND STORAGE.
D. REMOVED AND REINSTALLED ITEMS: CLEAN AND REPAIR ITEMS TO FUNCTIONAL CONDITION ADEQUATE FOR INTENDED REUSE.
PAINT EQUIPMENT TO MATCH NEW EQUIPMENT.
1. PACK OR CRATE ITEMS AFTER CLEANING AND REPAIRING. IDENTIFY CONTENTS OF CONTAINERS.
2. PROTECT ITEMS FROM DAMAGE DURING TRANSPORT AND STORAGE.
3. REINSTALL ITEMS IN LOCATIONS INDICATED. COMPLY WITH INSTALLATION REQUIREMENTS FOR NEW MATERIALS AND
EQUIPMENT. PROVIDE CONNECTIONS, SUPPORTS, AND MISCELLANEOUS MATERIALS NECESSARY TO MAKE ITEM FUNCTIONAL
FOR USE INDICATED.
E. EXISTING ITEMS TO REMAIN: PROTECT CONSTRUCTION INDICATED TO REMAIN AGAINST DAMAGE AND SOILING DURING
SELECTIVE DEMOLITION. WHEN PERMITTED BY ARCHITECT, ITEMS MAY BE REMOVED TO A SUITABLE, PROTECTED STORAGE
LOCATION DURING SELECTIVE DEMOLITION CLEANED AND REINSTALLED IN THEIR ORIGINAL LOCATIONS AFTER SELECTIVE
DEMOLITION OPERATIONS ARE COMPLETE.
DIVISION 4 MASONRY
4.1 CONCRETE MASONRY UNITS
A. GENERAL: REFER TO STRUCTURAL DRAWINGS FOR NOTES AND REQUIREMENTS FOR CONCRETE MASONRY UNIT CONSTRUCTION.
B. COLD-WEATHER REQUIREMENTS: COMPLY WITH COLD-WEATHER CONSTRUCTION REQUIREMENTS CONTAINED IN
ACI 530.1/ASCE 6/TMS 602.
C. HOT-WEATHER REQUIREMENTS: COMPLY WITH HOT-WEATHER CONSTRUCTION REQUIREMENTS CONTAINED IN
ACI 530.1/ASCE 6/TMS 602.
DIVISION 5 METALS
5.1 STRUCTURAL STEEL
A. GENERAL: REFER TO STRUCTURAL DRAWINGS FOR NOTES AND REQUIREMENTS FOR STRUCTURAL STEEL.
5.2 COLD FORM STEEL FRAMING
A. ALL COLD-FORMED STEEL FRAMING SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS AND IN ACCORDANCE WITH THE LATEST EDITION OF SPECIFICATIONS FOR THE DESIGN OF OLD-FORMED
STEEL STRUCTURAL MEMBERS BY THE AMERICAN IRON AND STEEL INSTITUTE.
B. STEEL FOR ALL 14 AND 16 GAGE STUDS AND JOISTS, AND FOR ALL DIAGONAL TENSION STRAPS SHALL HAVE A MINIMUM YIELD
STRENGTH OF 50,000 PSI. STEEL FOR ALL 18 AND 20 GAGE STUDS AND JOISTS, AND FOR ALL GAGES OF TRACK, ACCESSORIES AND
BRIDGING SHALL HAVE A MINIMUM YIELD STRENGTH OF 30,000 PSI. STEEL SHALL BE GALVANIZED AT LOCATIONS EXPOSED TO
WEATHER AND WHENEVER NOTED ON THE DRAWINGS.
C. ALL STUDS SHALL BE SECURELY SEATED FOR FULL END BEARING ON TOP AND BOTTOM TRACK. UNLESS NOTED OTHERWISE, PROVIDE DOUBLE STUDS AT ALL JAMBS, CORNERS, INTERSECTIONS, BEAM BEARINGS AND JOIST BEARINGS.
D. BRIDGING SHALL BE INSTALLED PER MANUFACTURER'S RECOMMENDATION WITH THE FOLLOWING MINIMUM REQUIREMENTS:
1. FOR NON-BEARING WALLS, PROVIDE BRIDGING AT MID-HEIGHT FOR WALLS LESS THAN OR EQUAL TO 10'-0" HIGH, AND 5'-0"
O.C. MAXIMUM FOR WALLS GREATER THAN 10'-0" HIGH.
2. FOR BEARING WALLS, PROVIDE BRIDGING EQUALLY SPACED AT 4'-0" MAXIMUM. IN ADDITION, BRIDGING SHALL BE PROVIDED
AT ROOF LINES AND ELSEWHERE AS NOTED ON THE DRAWINGS, SOLID BLOCKING SHALL BE INSTALLED IN LIEU OF BRIDGING
WHERE NOTED ON THE DRAWINGS.
E. STEEL STUD WALLS: STEEL STUD WALLS SHALL BE 18 GAGE @ 16" O.C. UNLESS NOTED OTHERWISE ON PLANS. TRACK ANCHOR
BOLTS SHALL BE 1/2" DIAMETER PLACED NOT TO EXCEED 4'-0" O.C. UNLESS NOTED OTHERWISE. ANCHOR BOLTS SHALL BE PLACED
AT ALL JAMBS, CORNERS, INTERSECTIONS AND WALL ENDS. ALL BOTTOM TRACKS SHALL HAVE A MINIMUM OF 2 ANCHOR BOLTS.
F. ALL WELDING SHALL BE PERFORMED BY WELDERS EXPERIENCED IN LIGHT GAGE STEEL FRAMING WORK.
5.3 METAL FABRICATIONS
A. DELEGATED DESIGN: DESIGN LADDERS AND STAIRS, INCLUDING COMPREHENSIVE ENGINEERING ANALYSIS BY A QUALIFIED
PROFESSIONAL ENGINEER, USING PERFORMANCE REQUIREMENTS AND DESIGN CRITERIA INDICATED.
B. SHOP DRAWINGS: SHOW FABRICATION AND INSTALLATION DETAILS FOR METAL FABRICATIONS.
C. DELEGATED-DESIGN SUBMITTAL: FOR INSTALLED PRODUCTS INDICATED TO COMPLY WITH PERFORMANCE REQUIREMENTS AND
DESIGN CRITERIA, INCLUDING ANALYSIS DATA SIGNED AND SEALED BY THE QUALIFIED PROFESSIONAL ENGINEER RESPONSIBLE FOR
THEIR PREPARATION.
D. FERROUS METALS:
1. STEEL PLATES, SHAPES, AND BARS: ASTM A 36/A 36M.
2. STAINLESS-STEEL BARS AND SHAPES: ASTM A 276, TYPE 304.
3. STEEL TUBING: ASTM A 500, COLD-FORMED STEEL TUBING. STEEL PIPE: ASTM A 53/A 53M, STANDARD WEIGHT
(SCHEDULE 40) UNLESS OTHERWISE INDICATED.
E. FASTENERS: UNLESS OTHERWISE INDICATED, PROVIDE TYPE 304 STAINLESS-STEEL FASTENERS FOR EXTERIOR USE AND ZINC-PLATED
FASTENERS WITH COATING COMPLYING WITH ASTM B 633 OR ASTM F 1941 (ASTM F 1941M), CLASS FE/ZN 5, AT EXTERIOR
WALLS.
F. MISCELLANEOUS MATERIALS:
1. UNIVERSAL SHOP PRIMER: FAST-CURING, LEAD- AND CHROMATE-FREE, UNIVERSAL MODIFIED-ALKYD PRIMER COMPLYING WITH
MPI#79 AND COMPATIBLE WITH TOPCOAT.
2. GALVANIZING REPAIR PAINT: HIGH-ZINC-DUST-CONTENT PAINT COMPLYING WITH SSPC-PAINT 20 AND COMPATIBLE WITH
PAINTS SPECIFIED TO BE USED OVER IT.
G. STRUCTURAL STEEL DOOR FRAMES:
1. FABRICATE STRUCTURAL-STEEL DOOR FRAMES FROM STEEL SHAPES FULLY WELDED TOGETHER, WITH 5/8-BY-1-1/2-INCH
(16-BY-38-MM) STEEL CHANNEL STOPS. PLUG-WELD BUILT-UP MEMBERS AND CONTINUOUSLY WELD EXPOSED JOINTS.
REINFORCE FRAMES AND DRILL AND TAP AS NECESSARY TO ACCEPT FINISH HARDWARE.
2. GALVANIZE EXTERIOR STEEL FRAMES.
H. FINISHES:
1. COMPLY WITH NAAMM'S "METAL FINISHES MANUAL FOR ARCHITECTURAL AND METAL PRODUCTS" FOR RECOMMENDATIONS
FOR APPLYING AND DESIGNATING FINISHES.
2. FINISH METAL FABRICATIONS AFTER ASSEMBLY.
3. GALVANIZING: HOT-DIP GALVANIZE ITEMS AS INDICATED TO COMPLY WITH ASTM A 153/A 153M FOR STEEL AND IRON
HARDWARE AND WITH ASTM A 123/A 123M FOR OTHER STEEL AND IRON PRODUCTS.
4. SHOP PRIME IRON AND STEEL ITEM NOT INDICATED TO BE GALVANIZED UNLESS THEY ARE TO BE EMBEDDED IN CONCRETE, SPRAYED-ON FIREPROOFING, OR MASONRY, OR UNLESS OTHERWISE INDICATED.
5. PREPARATION FOR SHOP PRIMING: PREPARE SURFACES TO COMPLY WITH SSPC-SP 6/NACE NO. 3, "COMMERCIAL BLAST
CLEANING.
DIVISION 7 THERMAL AND MOISTURE PROTECTION
7.1 SEALANTS
A. PRECONSTRUCTION TESTING
1. PRECONSTRUCTION COMPATIBILITY AND ADHESION TESTING: USE MANUFACTURER'S STANDARD TEST METHOD TO
DETERMINE WHETHER PRIMING AND OTHER JOINT SPECIFIC JOINT PREPARATION TECHNIQUES ARE REQUIRED TO OBTAIN
RAPID, OPTIMUM ADHESION OF JOINT SEALANTS TO JOINT SUBSTRATES.
2. PRECONSTRUCTION FIELD-ADHESION TESTING: BEFORE INSTALLING SEALANTS, FIELD TEST THEIR ADHESION TO PROJECT
JOINT SUBSTRATES. TEST JOINT SEALANTS ACCORDING TO METHOD A, FIELD-APPLIED SEALANT JOINT HAND PULL TAB, IN
APPENDIX X1 IN ASTM C 1193 OR METHOD A, TAIL PROCEDURE, IN ASTM C 1521.
3. TESTING AGENCY QUALIFICATIONS: QUALIFIED ACCORDING TO ASTM C 1021 TO CONDUCT THE TESTING INDICATED.
B. WARRANTY
1. SPECIAL INSTALLER'S WARRANTY: MANUFACTURER'S STANDARD FORM IN WHICH INSTALLER AGREES TO REPAIR OR REPLACE
JOINT SEALANTS THAT DO NOT COMPLY WITH PERFORMANCE AND OTHER REQUIREMENTS SPECIFIED IN THIS SECTION
WITHIN SPECIFIED WARRANTY PERIOD (TWO YEARS FROM DATE OF SUBSTANTIAL COMPLETION).
2. SPECIAL MANUFACTURER'S WARRANTY: MANUFACTURER'S STANDARD FORM IN WHICH JOINT-SEALANT MANUFACTURER
AGREES TO FURNISH JOINT SEALANTS TO REPAIR OR REPLACE THOSE THAT DO NOT COMPLY WITH PERFORMANCE
AND OTHER REQUIREMENTS SPECIFIED IN THIS SECTION WITHIN SPECIFIED WARRANTY PERIOD (TWO YEARS FROM DATE
OF SUBSTANTIAL COMPLETION).
C. SILICONE JOINT SEALANTS
1. MILDEW-RESISTANT NEUTRAL-CURING SILICONE JOINT SEALANT : ASTM C 920.
2. TYPE: SINGLE COMPONENT (S).
3. GRADE: [NONSAG (NS)].
4. CLASS: 100/50.
5. USES RELATED TO EXPOSURE: NONTRAFFIC (NT).
D. ACOUSTICAL JOINT SEALANT
1. ACOUSTICAL JOINT SEALANT: MANUFACTURER'S STANDARD NONSAG, PAINTABLE, NONSTAINING LATEX SEALANT
COMPLYING WITH ASTM C 834. PRODUCT EFFECTIVELY REDUCES AIRBORNE SOUND TRANSMISSION THROUGH PERIMETER
JOINTS AND OPENINGS IN BUILDING CONSTRUCTION AS DEMONSTRATED BY TESTING REPRESENTATIVE ASSEMBLIES
ACCORDING TO ASTM E 90.
E. JOINT SEALANT BACKING
1. CYLINDRICAL SEALANT BACKINGS: ASTM C 1330, TYPE C (CLOSED-CELL MATERIAL WITH A SURFACE SKIN), TYPE O
(OPEN-CELL MATERIAL), TYPE B (BICELLULAR MATERIAL WITH A SURFACE SKIN), OR ANY OF THE PRECEDING TYPES, AS
APPROVED IN WRITING BY JOINT-SEALANT MANUFACTURER FOR JOINT APPLICATION INDICATED, AND OF SIZE AND DENSITY
TO CONTROL SEALANT DEPTH AND OTHERWISE CONTRIBUTE TO PRODUCING OPTIMUM SEALANT PERFORMANCE.
2. BOND-BREAKER TAPE: POLYETHYLENE TAPE OR OTHER PLASTIC TAPE RECOMMENDED BY SEALANT MANUFACTURER.
F. MISCELLANEOUS MATERIALS
1. PRIMER: MATERIAL RECOMMENDED BY JOINT-SEALANT MANUFACTURER WHERE REQUIRED FOR ADHESION OF SEALANT
TO JOINT SUBSTRATES INDICATED, AS DETERMINED FROM PRECONSTRUCTION JOINT-SEALANT-SUBSTRATE TESTS AND
FIELD TESTS.
2. CLEANERS FOR NONPOROUS SURFACES: CHEMICAL CLEANERS ACCEPTABLE TO MANUFACTURERS OF SEALANTS AND
SEALANT BACKING MATERIALS.
3. MASKING TAPE: NONSTAINING, NONABSORBENT MATERIAL COMPATIBLE WITH JOINT SEALANTS AND SURFACES ADJACENT
TO JOINTS.
G. SURFACE CLEANING OF JOINTS: CLEAN OUT JOINTS IMMEDIATELY BEFORE INSTALLING JOINT SEALANTS TO COMPLY WITH
JOINT-SEALANT MANUFACTURER'S WRITTEN INSTRUCTIONS.
1. REMOVE LAITANCE AND FORM-RELEASE AGENTS FROM CONCRETE.
2. CLEAN NONPOROUS JOINT SUBSTRATE SURFACES WITH CHEMICAL CLEANERS OR OTHER MEANS THAT DO NOT STAIN, HARM
SUBSTRATES, OR LEAVE RESIDUES CAPABLE OF INTERFERING WITH ADHESION OF JOINT SEALANTS.
3. JOINT PRIMING: PRIME JOINT SUBSTRATES WHERE RECOMMENDED BY JOINT-SEALANT MANUFACTURER OR AS INDICATED BY
PRECONSTRUCTION JOINT-SEALANT-SUBSTRATE TESTS OR PRIOR EXPERIENCE. APPLY PRIMER TO COMPLY WITH
JOINT-SEALANT MANUFACTURER'S WRITTEN INSTRUCTIONS. CONFINE PRIMERS TO AREAS OF JOINT-SEALANT BOND; DO
NOT ALLOW SPILLAGE OR MIGRATION ONTO ADJOINING SURFACES.
4. MASKING TAPE: USE MASKING TAPE WHERE REQUIRED TO PREVENT CONTACT OF SEALANT OR PRIMER WITH ADJOINING
SURFACES THAT OTHERWISE WOULD BE PERMANENTLY STAINED OR DAMAGED BY SUCH CONTACT OR BY CLEANING
METHODS REQUIRED TO REMOVE SEALANT SMEARS. REMOVE TAPE IMMEDIATELY AFTER TOOLING WITHOUT DISTURBING
JOINT SEAL.
H. INSTALLATION
1. SEALANT INSTALLATION STANDARD: COMPLY WITH RECOMMENDATIONS IN ASTM C 1193 FOR USE OF JOINT SEALANTS AS
APPLICABLE TO MATERIALS, APPLICATIONS, AND CONDITIONS INDICATED.
2. INSTALL SEALANT BACKINGS OF KIND INDICATED TO SUPPORT SEALANTS DURING APPLICATION AND AT POSITION REQUIRED
TO PRODUCE CROSS-SECTIONAL SHAPES AND DEPTHS OF INSTALLED SEALANTS RELATIVE TO JOINT WIDTHS THAT ALLOW
OPTIMUM SEALANT MOVEMENT CAPABILITY.
3. DO NOT LEAVE GAPS BETWEEN ENDS OF SEALANT BACKINGS.
4. DO NOT STRETCH, TWIST, PUNCTURE, OR TEAR SEALANT BACKINGS.
5. REMOVE ABSORBENT SEALANT BACKINGS THAT HAVE BECOME WET BEFORE SEALANT APPLICATION AND REPLACE THEM
WITH DRY MATERIALS.
I. INSTALL BOND-BREAKER TAPE BEHIND SEALANTS WHERE SEALANT BACKINGS ARE NOT USED BETWEEN SEALANTS AND BACKS OF
JOINTS.
J. INSTALL SEALANTS USING PROVEN TECHNIQUES THAT COMPLY WITH THE FOLLOWING AND AT THE SAME TIME BACKINGS ARE
INSTALLED:
1. PLACE SEALANTS SO THEY DIRECTLY CONTACT AND FULLY WET JOINT SUBSTRATES.
2. COMPLETELY FILL RECESSES IN EACH JOINT CONFIGURATION.
3. PRODUCE UNIFORM, CROSS-SECTIONAL SHAPES AND DEPTHS RELATIVE TO JOINT WIDTHS THAT ALLOW OPTIMUM SEALANT
MOVEMENT CAPABILITY.
K. TOOLING OF NONSAG SEALANTS: IMMEDIATELY AFTER SEALANT APPLICATION AND BEFORE SKINNING OR CURING BEGINS, TOOL
SEALANTS ACCORDING TO REQUIREMENTS SPECIFIED IN SUBPARAGRAPHS BELOW TO FORM SMOOTH, UNIFORM BEADS OF
CONFIGURATION INDICATED; TO ELIMINATE AIR POCKETS; AND TO ENSURE CONTACT AND ADHESION OF SEALANT WITH SIDES
OF JOINT.
1. REMOVE EXCESS SEALANT FROM SURFACES ADJACENT TO JOINTS.
2. USE TOOLING AGENTS THAT ARE APPROVED IN WRITING BY SEALANT MANUFACTURER AND THAT DO NOT DISCOLOR
SEALANTS OR ADJACENT SURFACES.
3. PROVIDE CONCAVE JOINT PROFILE PER FIGURE 8A IN ASTM C 1193, UNLESS OTHERWISE INDICATED.
L. ACOUSTICAL SEALANT INSTALLATION: COMPLY WITH ASTM C 919 AND WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS.
M. CLEAN OFF EXCESS SEALANT OR SEALANT SMEARS ADJACENT TO JOINTS AS THE WORK PROGRESSES BY METHODS AND WITH
CLEANING MATERIALS APPROVED IN WRITING BY MANUFACTURERS OF JOINT SEALANTS AND OF PRODUCTS IN WHICH JOINTS
OCCUR.
N. FIELD-ADHESION TESTING: FIELD TEST JOINT-SEALANT ADHESION TO JOINT SUBSTRATES AS FOLLOWS:
1. PERFORM 10 TESTS FOR THE FIRST 1000 FEET OF JOINT LENGTH FOR EACH KIND OF SEALANT AND JOINT SUBSTRATE.
2. PERFORM 1 TEST FOR EACH 1000 FEET OF JOINT LENGTH THEREAFTER OR 1 TEST PER EACH FLOOR PER ELEVATION.
3. TEST METHOD: TEST JOINT SEALANTS ACCORDING TO METHOD A, FIELD-APPLIED SEALANT JOINT HAND PULL TAB, IN
APPENDIX X1 IN ASTM C 1193 OR METHOD A, TAIL PROCEDURE, IN ASTM C 1521.
4. EVALUATION OF FIELD-ADHESION TEST RESULTS: SEALANTS NOT EVIDENCING ADHESIVE FAILURE FROM TESTING OR
NONCOMPLIANCE WITH OTHER INDICATED REQUIREMENTS WILL BE CONSIDERED SATISFACTORY. REMOVE SEALANTS THAT
FAIL TO ADHERE TO JOINT SUBSTRATES DURING TESTING OR TO COMPLY WITH OTHER REQUIREMENTS. RETEST FAILED
APPLICATIONS UNTIL TEST RESULTS PROVE SEALANTS COMPLY WITH INDICATED REQUIREMENTS.
O. INTERIOR JOINTS IN HORIZONTAL TRAFFIC SURFACES.
1. CONTROL AND EXPANSION JOINTS IN TILE FLOORING.
2. OTHER JOINTS AS INDICATED.
3. JOINT SEALANT: URETHANE.
4. JOINT-SEALANT COLOR: AS SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OF COLORS.
P. INTERIOR JOINTS IN VERTICAL SURFACES AND HORIZONTAL NONTRAFFIC SURFACES.
1. VERTICAL JOINTS ON EXPOSED SURFACES OF WALLS AND PARTITIONS.
2. PERIMETER JOINTS BETWEEN INTERIOR WALL SURFACES AND FRAMES OF INTERIOR DOORS AND WINDOWS.
3. OTHER JOINTS AS INDICATED.
4. JOINT SEALANT: LATEX.
5. JOINT-SEALANT COLOR: AS SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OF COLORS.
Q. MILDEW-RESISTANT INTERIOR JOINTS IN VERTICAL SURFACES AND HORIZONTAL NONTRAFFIC SURFACES.
1. JOINTS BETWEEN PLUMBING FIXTURES AND ADJOINING WALLS, FLOORS, AND COUNTERS.
2. TILE CONTROL AND EXPANSION JOINTS WHERE INDICATED.
3. OTHER JOINTS AS INDICATED.
4. JOINT SEALANT: SILICONE.
5. JOINT-SEALANT COLOR: AS SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OF COLORS.
R. JOINT-SEALANT APPLICATION: INTERIOR ACOUSTICAL JOINTS IN VERTICAL SURFACES AND HORIZONTAL NONTRAFFIC SURFACES.
1. ACOUSTICAL JOINTS WHERE INDICATED.
2. OTHER JOINTS AS INDICATED.
3. JOINT SEALANT: ACOUSTICAL.
JOINT-SEALANT COLOR: AS SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OF COLORS.
DIVISION 9 FINISHES
9.1 NON-STRUCTURAL METAL FRAMING
A. FRAMING MEMBERS, GENERAL: COMPLY WITH ASTM C 754 FOR CONDITIONS INDICATED.
B. STEEL SHEET COMPONENTS: COMPLY WITH ASTM C 645 REQUIREMENTS FOR METAL, UNLESS OTHERWISE INDICATED.
C. PROTECTIVE COATING: MANUFACTURER'S STANDARD CORROSION-RESISTANT ZINC COATING, UNLESS OTHERWISE INDICATED.
D. TIE WIRE: ASTM A 641/A 641M, CLASS 1 ZINC COATING, SOFT TEMPER, 0.0625-INCH- (1.59-MM-) DIAMETER WIRE, OR DOUBLE
STRAND OF 0.0475-INCH- (1.21-MM-) DIAMETER WIRE.
E. HANGER ATTACHMENTS TO CONCRETE:
1. ANCHORS: FABRICATED FROM CORROSION-RESISTANT MATERIALS WITH HOLES OR LOOPS FOR ATTACHING WIRE HANGERS
AND CAPABLE OF SUSTAINING, WITHOUT FAILURE, A LOAD EQUAL TO 5 TIMES THAT IMPOSED BY CONSTRUCTION AS
DETERMINED BY TESTING ACCORDING TO ASTM E 488 BY AN INDEPENDENT TESTING AGENCY.
2. POWDER-ACTUATED FASTENERS: SUITABLE FOR APPLICATION INDICATED, FABRICATED FROM CORROSION-RESISTANT
MATERIALS WITH CLIPS OR OTHER DEVICES FOR ATTACHING HANGERS OF TYPE INDICATED, AND CAPABLE OF
SUSTAINING, WITHOUT FAILURE, A LOAD EQUAL TO 10 TIMES THAT IMPOSED BY CONSTRUCTION AS DETERMINED BY
TESTING ACCORDING TO ASTM E 1190 BY AN INDEPENDENT TESTING AGENCY.
3. WIRE HANGERS: ASTM A 641/A 641M, CLASS 1 ZINC COATING, SOFT TEMPER, 0.162-INCH (4.12-MM) DIAMETER.
4. FLAT HANGERS: STEEL SHEET, 1 BY 3/16 INCH (25.4 BY 4.76 MM) BY LENGTH INDICATED.
F. CARRYING CHANNELS: COLD-ROLLED, COMMERCIAL-STEEL SHEET WITH A BASE-METAL THICKNESS OF 0.0538 INCH (1.37 MM) AND
MINIMUM 1/2-INCH- (12.7-MM-) WIDE FLANGES.
G. STEEL STUDS AND RUNNERS: ASTM C 645. MINIMUM BASE-METAL THICKNESS: 0.0179 INCH (0.45 MM).
H. SLIP-TYPE HEAD JOINTS: WHERE INDICATED, PROVIDE ONE OF THE FOLLOWING:
1. DOUBLE-RUNNER SYSTEM: ASTM C 645 TOP RUNNERS, INSIDE RUNNER WITH 2-INCH- (50.8-MM-) DEEP FLANGES IN
THICKNESS NOT LESS THAN INDICATED FOR STUDS AND FASTENED TO STUDS, AND OUTER RUNNER SIZED TO FRICTION FIT
INSIDE RUNNER.
2. DEFLECTION TRACK: STEEL SHEET TOP RUNNER MANUFACTURED TO PREVENT CRACKING OF FINISHES APPLIED TO INTERIOR
PARTITION FRAMING RESULTING FROM DEFLECTION OF STRUCTURE ABOVE; IN THICKNESS NOT LESS THAN INDICATED FOR
STUDS AND IN WIDTH TO ACCOMMODATE DEPTH OF STUDS.
I. FLAT STRAP AND BACKING PLATE: STEEL SHEET FOR BLOCKING AND BRACING IN LENGTH AND WIDTH
INDICATED. MINIMUM BASE-METAL THICKNESS: 0.0179 INCH (0.45 MM).
J. COLD-ROLLED CHANNEL BRIDGING: 0.0538-INCH (1.37-MM) BARE-STEEL THICKNESS, WITH MINIMUM 1/2-INCH- (12.7-MM-) WIDE
FLANGES.
K. HAT-SHAPED, RIGID FURRING CHANNELS: ASTM C 645. MINIMUM BASE METAL THICKNESS: 0.0179 INCH (0.45 MM).
L. COLD-ROLLED FURRING CHANNELS: 0.0538-INCH (1.37-MM) BARE-STEEL THICKNESS, WITH MINIMUM 1/2-INCH- (12.7-MM-) WIDE
FLANGES.
M. FASTENERS FOR METAL FRAMING: OF TYPE, MATERIAL, SIZE, CORROSION RESISTANCE, HOLDING POWER, AND OTHER PROPERTIES
REQUIRED TO FASTEN STEEL MEMBERS TO SUBSTRATES.
N. INSTALLATION STANDARD: ASTM C 754.
1. GYPSUM BOARD ASSEMBLIES: ALSO COMPLY WITH REQUIREMENTS IN ASTM C 840 THAT APPLY TO FRAMING INSTALLATION.
O. SUSPEND HANGERS FROM BUILDING STRUCTURE AS FOLLOWS:
1. INSTALL HANGERS PLUMB AND FREE FROM CONTACT WITH INSULATION OR OTHER OBJECTS WITHIN CEILING PLENUM THAT
ARE NOT PART OF SUPPORTING STRUCTURAL OR SUSPENSION SYSTEM.
2. SPLAY HANGERS ONLY WHERE REQUIRED TO MISS OBSTRUCTIONS AND OFFSET RESULTING HORIZONTAL FORCES BY
BRACING, COUNTERSPLAYING, OR OTHER EQUALLY EFFECTIVE MEANS.
3. WHERE WIDTH OF DUCTS AND OTHER CONSTRUCTION WITHIN CEILING PLENUM PRODUCES HANGER SPACINGS THAT
INTERFERE WITH LOCATIONS OF HANGERS REQUIRED TO SUPPORT STANDARD SUSPENSION SYSTEM MEMBERS, INSTALL
SUPPLEMENTAL SUSPENSION MEMBERS AND HANGERS IN THE FORM OF TRAPEZES OR EQUIVALENT DEVICES.
4. DO NOT ATTACH HANGERS TO STEEL ROOF DECK.
5. DO NOT ATTACH HANGERS TO PERMANENT METAL FORMS. FURNISH CAST-IN-PLACE HANGER INSERTS THAT EXTEND
THROUGH FORMS.
6. DO NOT ATTACH HANGERS TO ROLLED-IN HANGER TABS OF COMPOSITE STEEL FLOOR DECK.
7. DO NOT CONNECT OR SUSPEND STEEL FRAMING FROM DUCTS, PIPES, OR CONDUIT.
P. SEISMIC BRACING: SWAY-BRACE SUSPENSION SYSTEMS WITH HANGERS USED FOR SUPPORT.
Q. WHERE STUDS ARE INSTALLED DIRECTLY AGAINST EXTERIOR MASONRY WALLS OR DISSIMILAR METALS AT EXTERIOR WALLS, INSTALL ISOLATION STRIP BETWEEN STUDS AND EXTERIOR WALL.
R. INSTALL TRACKS (RUNNERS) AT FLOORS AND OVERHEAD SUPPORTS. EXTEND FRAMING FULL HEIGHT TO STRUCTURAL SUPPORTS
OR SUBSTRATES ABOVE SUSPENDED CEILINGS, EXCEPT WHERE PARTITIONS ARE INDICATED TO TERMINATE AT SUSPENDED
CEILINGS. CONTINUE FRAMING AROUND DUCTS PENETRATING PARTITIONS ABOVE CEILING.
S. SLIP-TYPE HEAD JOINTS: WHERE FRAMING EXTENDS TO OVERHEAD STRUCTURAL SUPPORTS, INSTALL TO PRODUCE JOINTS AT TOPS
OF FRAMING SYSTEMS THAT PREVENT AXIAL LOADING OF FINISHED ASSEMBLIES.
9.2 GYPSUM WALLBOARD
A. GENERAL: COMPLYING WITH ASTM C 36/C 36M OR ASTM C 1396/C 1396M, AS APPLICABLE TO TYPE OF GYPSUM BOARD
INDICATED AND WHICHEVER IS MORE STRINGENT.
B. REGULAR TYPE: THICKNESS: 5/8 INCH (15.9 MM). LONG EDGES: TAPERED.
C. TYPE X: THICKNESS: 5/8 INCH (15.9 MM). LONG EDGES: TAPERED.
D. WATER-RESISTANT GYPSUM BACKING BOARD: ASTM C 630/C 630M OR ASTM C 1396/C 1396M, 5/8 INCH (15.9 MM), TYPE X.
E. CEMENTITIOUS BACKER UNITS: ANSI A108.1, THICKNESS: AS INDICATED ON DRAWINGS.
F. INTERIOR TRIM: ASTM C 1047.
G. JOINT TREATMENT: COMPLY WITH ASTM C 475/C 475M.
H. JOINT TAPE:
1. INTERIOR GYPSUM WALLBOARD: PAPER.
2. EXTERIOR GYPSUM SOFFIT BOARD: PAPER.
3. GLASS-MAT GYPSUM SHEATHING BOARD: 10-BY-10 GLASS MESH.
4. TILE BACKING PANELS: AS RECOMMENDED BY PANEL MANUFACTURER.
I. JOINT COMPOUND FOR INTERIOR GYPSUM WALLBOARD: FOR EACH COAT USE FORMULATION THAT IS
COMPATIBLE WITH OTHER COMPOUNDS APPLIED ON PREVIOUS OR FOR SUCCESSIVE COATS
J. JOINT COMPOUND FOR TILE BACKING PANELS: WATER-RESISTANT GYPSUM BACKING BOARD: USE SETTING-TYPE
TAPING COMPOUND AND SETTING-TYPE, SANDABLE TOPPING COMPOUND.
K. JOINT COMPOUND FOR CEMENTITIOUS BACKER UNITS: AS RECOMMENDED BY BACKER UNIT MANUFACTURER.
L. STEEL DRILL SCREWS: ASTM C 1002, UNLESS OTHERWISE INDICATED.
M. APPLYING AND FINISHING PANELS, GENERAL:
1. COMPLY WITH ASTM C 840.
2. WATER-RESISTANT GYPSUM BACKING BOARD: INSTALL AT SHOWERS, TUBS, AND WHERE INDICATED. INSTALL WITH 1/4-INCH
(6.4-MM) GAP WHERE PANELS ABUT OTHER CONSTRUCTION OR PENETRATIONS.CEMENTITIOUS BACKER UNITS: ANSI A108.1, AT LOCATIONS INDICATED TO RECEIVE TILE.
N. CONTROL JOINTS: INSTALL CONTROL JOINTS AT LOCATIONS INDICATED ON DRAWINGS.
O. GYPSUM BOARD FINISH LEVELS: FINISH PANELS TO LEVELS INDICATED BELOW:
1. LEVEL 1: CEILING PLENUM AREAS, CONCEALED AREAS, AND WHERE INDICATED.
2. LEVEL 2: PANELS THAT ARE SUBSTRATE FOR TILE.
3. LEVEL 4: AT PANEL SURFACES THAT WILL BE EXPOSED TO VIEW, UNLESS OTHERWISE INDICATED.
9.3 TILING
A. PROVIDE SAMPLES FOR EACH TYPE AND COMPOSITION OF TILE AND FOR EACH COLOR AND FINISH REQUIRED.
B. ANSI CERAMIC TILE STANDARD: PROVIDE STANDARD GRADE TILE THAT COMPLIES WITH ANSI A137.1 FOR TYPES, COMPOSITIONS, AND OTHER CHARACTERISTICS INDICATED.
C. REFER TO DRAWINGS FOR TILE MANUFACTURER, PATTERN, COLOR, AND SIZES.
D. PORTLAND CEMENT MORTAR (THICKSET) INSTALLATION MATERIALS: ANSI A108.02.
E. LATEX-PORTLAND CEMENT MORTAR (THIN SET): ANSI A118.4.
F. ORGANIC ADHESIVE: ANSI A136.1, TYPE I, WITH A VOC CONTENT OF 65 G/L OR LESS WHEN CALCULATED ACCORDING TO
40 CFR 59, SUBPART D (EPA METHOD 24).
G. POLYMER-MODIFIED TILE GROUT: ANSI A118.7.
H. TROWELABLE UNDERLAYMENTS AND PATCHING COMPOUNDS: LATEX-MODIFIED, PORTLAND CEMENT-BASED FORMULATION
PROVIDED OR APPROVED BY MANUFACTURER OF TILE-SETTING MATERIALS FOR INSTALLATIONS INDICATED.
I. GROUT SEALER: MANUFACTURER'S STANDARD SILICONE PRODUCT FOR SEALING GROUT JOINTS AND THAT DOES NOT CHANGE
COLOR OR APPEARANCE OF GROUT.
J. COMPLY WITH TCA'S "HANDBOOK FOR CERAMIC TILE INSTALLATION" FOR TCA INSTALLATION METHODS SPECIFIED IN TILE
INSTALLATION SCHEDULES. COMPLY WITH PARTS OF THE ANSI A108 SERIES "SPECIFICATIONS FOR INSTALLATION OF CERAMIC TILE"
THAT ARE REFERENCED IN TCA INSTALLATION METHODS, SPECIFIED IN TILE INSTALLATION SCHEDULES, AND APPLY TO TYPES OF
SETTING AND GROUTING MATERIALS USED.
9.4 RESILIENT BASE AND ACCESSORIES
A. RESILIENT BASE STANDARD: ASTM F 1861.
1. MATERIAL REQUIREMENT: TYPE TS (RUBBER, VULCANIZED THERMOSET) OR TYPE TP (RUBBER, THERMOPLASTIC).
2. MANUFACTURING METHOD: GROUP I (SOLID, HOMOGENEOUS).
3. STYLE: COVE (BASE WITH TOE) OR STRAIGHT (FLAT OR TOELESS).
4. MINIMUM THICKNESS: 0.125 INCH (3.2 MM).
5. HEIGHT: AS INDICATED ON DRAWINGS.
6. LENGTHS: COILS IN MANUFACTURER'S STANDARD LENGTH.
7. CORNERS: JOB FORMED OR PREFORMED.
8. COLORS AND PATTERNS: AS SELECTED BY ARCHITECT FROM FULL RANGE OF INDUSTRY COLORS.
B. ADHESIVES: WATER-RESISTANT TYPE RECOMMENDED BY MANUFACTURER TO SUIT RESILIENT PRODUCTS AND SUBSTRATE
CONDITIONS INDICATED.
C. PREPARE SUBSTRATES ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS TO ENSURE ADHESION OF RESILIENT
PRODUCTS.
DO NOT INSTALL RESILIENT PRODUCTS UNTIL THEY ARE SAME TEMPERATURE AS THE SPACE WHERE THEY ARE
TO BE INSTALLED.
C. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLING RESILIENT PRODUCTS.
D. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR CLEANING AND PROTECTION OF RESILIENT PRODUCTS.
DIVISION 10 SPECIALTIES
10.1 STEEL TOILET COMPARTMENTS
A. QUALITY ASSURANCE:
1. SURFACE-BURNING CHARACTERISTICS: AS DETERMINED BY TESTING IDENTICAL PRODUCTS ACCORDING TO ASTM E 84, OR
ANOTHER STANDARD ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION, BY A QUALIFIED TESTING AGENCY. IDENTIFY
PRODUCTS WITH APPROPRIATE MARKINGS OF APPLICABLE TESTING AGENCY.
2. REGULATORY REQUIREMENTS: COMPLY WITH APPLICABLE PROVISIONS IN THE U.S. ARCHITECTURAL & TRANSPORTATION
BARRIERS COMPLIANCE BOARD'S "AMERICANS WITH DISABILITIES ACT (ADA) AND ARCHITECTURAL BARRIERS ACT (ABA)
ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES" AND ICC/ANSI A117.1 FOR TOILET COMPARTMENTS DESIGNATED
AS ACCESSIBLE.
B. STEEL TOILET COMPARTMENTS:
1. TOILET-ENCLOSURE STYLE: FLOOR-MOUNTED
2. URINAL-SCREEN STYLE: WALL HUNG, FLAT PANEL.
3. DOOR, PANEL, AND PILASTER CONSTRUCTION: SEAMLESS, METAL FACING SHEETS PRESSURE LAMINATED TO CORE MATERIAL;
WITH CONTINUOUS, INTERLOCKING MOLDING STRIP OR LAPPED-AND-FORMED EDGE CLOSURES; CORNERS SECURED BY
WELDING OR CLIPS AND EXPOSED WELDS GROUND SMOOTH. PROVIDE WITH NO-SIGHTLINE SYSTEM. EXPOSED SURFACES
SHALL BE FREE OF PITTING, SEAM MARKS, ROLLER MARKS, STAINS, DISCOLORATIONS, TELEGRAPHING OF CORE MATERIAL, OR OTHER IMPERFECTIONS.
C. URINAL-SCREEN CONSTRUCTION: FLAT-PANEL URINAL SCREEN: MATCHING PANEL CONSTRUCTION.
D. FACING SHEETS AND CLOSURES: ELECTROLYTICALLY COATED STEEL SHEET WITH NOMINAL BASE-METAL (UNCOATED)
THICKNESSES STANDARD WITH MANUFACTURER.
E. PILASTER SHOES AND SLEEVES (CAPS): STAINLESS-STEEL SHEET, NOT LESS THAN 3 INCHES (76 MM) HIGH, FINISHED TO MATCH
HARDWARE.
F. STEEL-SHEET FINISH: MANUFACTURER'S STANDARD BAKED-ON FINISH, WITH ONE COLOR IN EACH ROOM.
1. COLOR: AS SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE.
G. HARDWARE AND ACCESSORIES: MANUFACTURER'S STANDARD DESIGN, HEAVY-DUTY OPERATING HARDWARE AND ACCESSORIES.
1. MATERIAL: STAINLESS STEEL.
H. OVERHEAD BRACING: MANUFACTURER'S STANDARD CONTINUOUS, EXTRUDED-ALUMINUM HEAD RAIL WITH ANTIGRIP PROFILE
AND IN MANUFACTURER'S STANDARD FINISH.
I. ANCHORAGES AND FASTENERS: MANUFACTURER'S STANDARD EXPOSED FASTENERS OF STAINLESS STEEL OR CHROME-PLATED
STEEL OR BRASS, FINISHED TO MATCH THE ITEMS THEY ARE SECURING, WITH THEFT-RESISTANT-TYPE HEADS. PROVIDE SEX-TYPE
BOLTS FOR THROUGH-BOLT APPLICATIONS. FOR CONCEALED ANCHORS, USE STAINLESS STEEL, HOT-DIP GALVANIZED STEEL, OR
OTHER RUST-RESISTANT, PROTECTIVE-COATED STEEL.
J. DOOR SIZE AND SWINGS: UNLESS OTHERWISE INDICATED, PROVIDE 28-INCH- (610-MM-) WIDE, IN-SWINGING DOORS FOR
STANDARD TOILET COMPARTMENTS AND 36-INCH- (914-MM-) WIDE, OUT-SWINGING DOORS WITH A MINIMUM 32-INCH- (813-MM-)
WIDE, CLEAR OPENING FOR COMPARTMENTS DESIGNATED AS ACCESSIBLE.
K. COMPLY WITH MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS. INSTALL UNITS RIGID, STRAIGHT, LEVEL, AND PLUMB.
SECURE UNITS IN POSITION WITH MANUFACTURER'S RECOMMENDED ANCHORING DEVICES.
L. HARDWARE ADJUSTMENT: ADJUST AND LUBRICATE HARDWARE ACCORDING TO HARDWARE MANUFACTURER'S WRITTEN
INSTRUCTIONS FOR PROPER OPERATION. SET HINGES ON IN-SWINGING DOORS TO HOLD DOORS OPEN APPROXIMATELY 30
DEGREES FROM CLOSED POSITION WHEN UNLATCHED. SET HINGES ON OUT-SWINGING DOORS TO RETURN DOORS TO FULLY
CLOSED POSITION.
10.2 TOILET ACCESSORIES
A. SUBMIT PROPOSED PRODUCT SCHEDULE.
B. TOILET TISSUE (ROLL) DISPENSER:
1. DESCRIPTION: SEE INTERIOR ELEVATION KEYNOTES.
2. MOUNTING: SURFACE MOUNTED.
D. LIQUID-SOAP DISPENSER:
1. DESCRIPTION: SEE INTERIOR ELEVATION KEYNOTES.
E. GRAB BAR:
1. MOUNTING: FLANGES WITH CONCEALED FASTENERS.
2. MATERIAL: STAINLESS STEEL, 0.05 INCH (1.3 MM) THICK.
3. FINISH: SMOOTH, NO. 4, SATIN FINISH.
4. OUTSIDE DIAMETER: 1-1/4 INCHES (32 MM).
5. CONFIGURATION AND LENGTH: AS INDICATED ON DRAWINGS..
F. SEAT-COVER DISPENSER:
1. MOUNTING: SURFACE MOUNTED.
2. EXPOSED MATERIAL AND FINISH: STAINLESS STEEL, NO. 4 FINISH (SATIN).
3. LOCKSET: TUMBLER TYPE.
G. MIRROR UNIT:
9. FRAME: STAINLESS-STEEL CHANNEL.
10. CORNERS: MANUFACTURER'S STANDARD.
11. SIZE; AS INDICATED.
H. UNDER LAVATORY GUARD:
1. DESCRIPTION: INSULATING PIPE COVERING FOR SUPPLY AND DRAIN PIPING ASSEMBLIES, THAT PREVENT DIRECT CONTACT
WITH AND BURNS FROM PIPING, AND ALLOW SERVICE ACCESS WITHOUT REMOVING COVERINGS.
2.. MATERIAL AND FINISH: ANTIMICROBIAL, MOLDED-PLASTIC, WHITE.
I. INSTALL ACCESSORIES ACCORDING TO MANUFACTURERS' WRITTEN INSTRUCTIONS, USING FASTENERS APPROPRIATE TO
SUBSTRATE INDICATED AND RECOMMENDED BY UNIT MANUFACTURER. INSTALL UNITS LEVEL, PLUMB, AND FIRMLY ANCHORED IN
LOCATIONS AND AT HEIGHTS INDICATED.
10.3 SIGNAGE
C. PROVIDE ONE TOILET ROOM SIGN AT EACH DOOR TO TOILET ROOM WITH INTERNATIONAL SYMBOL FOR ACCESSIBILITY IN
ACCORDANCE WITH ANSI 117.1 AND ADA.
PROVIDE ONE TACTILE EXIT SIGN AT EACH MEANS OF EGRESS EXTERIOR EXIT DISCHARGE DOOR COMPLYING WITH ANSI 117.1.
230257.01
/0
/2
P A
G E T
U R
N C
H E C
K S
E T
/0
/2
P E R
M
IT
S E T
C 2025 CIDA, P.C./CIDA ALL RIGHTS RESERVED
IS
S U
E D
D A
T E
1 5 8 9 5 S W 7 2 N D A V E S U I T E 2 0 0
P O R T L A N D , O R E G O N 9 7 2 2 4
T E L : 5 0 3 . 2 2 6 . 1 2 8 5
F A X : 5 0 3 . 2 2 6 . 1 6 7 0
W W W . C I D A I N C . C O M
E :\a d ca d d \2
\0
.0
O
M D
R e d m o n d \0
-C u rr e n t\
C A
D \0
G
N .d w g
D e c
, 2
:1 p m
ARCHITECTURE
ENGINEERING
P L A N N I N G
I N T E R I O R S
T E N
A N
T I M
P R
O V
E M
E N
T F
O R
O M
D R
ED
M
O N
D
LO
CK
ER
R
O O
M E
XP
A
N
SI
O N
O
C H
O C
O W
A Y
R E D
M O
N D
, O R
E G
O N
GN1
GENERAL NOTES
PRELIMINARY
PLAN ONLY-NOT
A
B
C
D
E
A
B
C
D
E
230257.01
/0
/2
P A
G E T
U R
N C
H E C
K S
E T
/0
/2
P E R
M
IT
S E T
C 2025 CIDA, P.C./CIDA ALL RIGHTS RESERVED
IS
S U
E D
D A
T E
1 5 8 9 5 S W 7 2 N D A V E S U I T E 2 0 0
P O R T L A N D , O R E G O N 9 7 2 2 4
T E L : 5 0 3 . 2 2 6 . 1 2 8 5
F A X : 5 0 3 . 2 2 6 . 1 6 7 0
W W W . C I D A I N C . C O M
E :\a d ca d d \2
\0
.0
O
M D
R e d m o n d \0
-C u rr e n t\
C A
D \A
.1
D E M
O P
L A
N A
N D
F L O
O R
P L A
N .d w g
D e c
, 2
:1 p m
ARCHITECTURE
ENGINEERING
P L A N N I N G
I N T E R I O R S
T E N
A N
T I M
P R
O V
E M
E N
T F
O R
O M
D R
ED
M
O N
D
LO
CK
ER
R
O O
M E
XP
A
N
SI
O N
O
C H
O C
O W
A Y
R E D
M O
N D
, O R
E G
O N
A
A1.1
DEMO & FLOOR PLAN
GENERAL NOTES
DEMOLITION LEGEND
DEMOLITION KEYNOTES
(E) EXTERIOR WALL
EXISTING(E)
NEW(N)
FACE OF FINISHF.O.F.
1. ALL CONDITIONS SHOWN OR IMPLIED ON THE DRAWINGS SHALL BE VERIFIED BY THE
CONTRACTOR PRIOR TO CONSTRUCTION. NOTIFY ARCHITECT / ENGINEER OF ANY
DISCREPANCIES PRIOR TO THE START OF WORK.
2. ALL DIMENSIONS ARE TO CENTER OF STUD AT NEW WALLS AND TO FACE OF FINISH AT
EXISTING EXTERIOR WALLS U.N.O.
3. PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED AND INSTALLED AS REQUIRED BY
APPLICABLE STANDARDS
4. ALL ELECTRICAL OUTLETS TO CONFORM W/ 2025 OREGON SPECIALTY ELECTRICAL CODE.
5. CONTRACTOR SHALL VERIFY AND CONFIRM EXISTING CONDITIONS SHOWN OR IMPLIED
ON DRAWINGS PRIOR TO START OF CONSTRUCTION. NOTIFY A/E OF ANY
DISCREPANCIES.
6. APPLICABLE CODES: ALL WORK SHALL BE IN CONFORMANCE WITH ALL FEDERAL, STATE,
AND LOCAL CODES. ALL CODE REFERENCES IN THE DRAWINGS AND SPECIFICATIONS
SHALL MEAN, AND ARE INTENDED TO BE THE LATEST EDITION, AMENDMENT OR REVISION
OF SUCH REFERENCED STANDARD IN EFFECT AS OF THE DATE OF THE CONTRACT
DOCUMENTS.
7. CONTRACTOR SHALL COORDINATE ALL REQUIRED TESTING AND INSPECTIONS.
8. ALL DOOR HARDWARE SHALL MEET THE REQUIREMENTS OF ANSI A117.1 2009 EDITION
AND THE ADA.
9. ALL DOORS AND WINDOWS SHALL MEET OR EXCEED THE ENERGY PERFORMANCE
REQUIREMENTS INDICATED IN THE DRAWINGS AND SPECS.
10. FIRE EXTINGUISHERS SHALL BE LOCATED AS REQUIRED BY SECTION 906 OFC AND
APPROVED BY LOCAL FIRE MARSHALL.
11. LIGHT AND VENTILATION NOT INDICATED ON THESE PLANS SHALL BE
PROVIDED AS PER SECTION 1203 & 1205 OSSC.
12. PROVIDE EXIT ILLUMINATION AND SIGNAGE PER SECTION 1006 & SIGNAGE PER SECTION
1011 OF THE OSSC.
13. DIMENSIONS LOCATING INTERIOR WALLS ARE TO CENTER OF WALL UNLESS NOTED
OTHERWISE.
14. ALL EXISTING PLUMBING FIXTURES ARE TO REMAIN, UNLESS OTHERWISE NOTED.
DEMOLISH DOOR
HOSE BIB+HB
FLOOR PLAN KEYNOTES
A INTERIOR STUD WALL
1/4" = 1'-0"
DEMOLITION PLAN1
NORTH
A1.1
DEMOLISH PORTION OF WALL
CORRIDOR
ROOM NAME & NUMBER
UNLESS NOTED OTHERWISEU.N.O.
FD
FLOOR DRAIN
1/4" = 1'-0"
FLOOR PLAN2
NORTH
A1.1
B
REMOVE AND SALVAGE FURNITURE FOR REUSE
DEMOLISH WALL
C
DEMOLISH PLUMBING FIXTURED
DEMOLISH WALL - OPENING SIZE PER STRUCTURAL
(E) CORRIDOR
(E) WOMEN'S T.R.
(E) CUSTODIAL
(E) MEN'S T.R.
MEN'S LOCKER ROOM
WOMEN'S…