NAWCWD Telecommunications Danville Project Specification
Require telephone carrier systems to support 2 new buildings to integrate into existing Nortel MSL-100. Each building requires: 56 Single-lines, 3 Multi-lines, 8 ISDN, and 1 MCU, redundant power supplies, common logic cards, optical transport cards, inter-shelf OC-3 cards, system rectifier, top-of-rack DC fuse panel, and an 8 hour uninterruptable power supplies within each building. The new system will be connected by OC-12C fiber.
The remote sites require 19x84 inch 2-post relay racks anchored with proper grounding with stand-offs for cable management and connected to the wall with 4 foot ladder rack; the Central Office (CO) has existing 23” equipment rack.
Main distribution frame (MDF) wire blocks are required to connect the 25-pair cables for Main-site Central Office (CO). The Remote sites require 110 wire blocks to connect the 25-pair cables between the systems RST equipment.
Require compatible fiber patch cables with Slit Wall Corrugated Orange Loom Tubing between the system equipment and the outside plant (OSP) fiber optic patch panel (FOPP).