Statement of Work The contractor shall provide quantity one (1) Refrigerated Air Cooling Unit in accordance with the below specifications.
Cooling Unit Specifications:
Coolant Characteristics:
Coolant Composition Supply Rate Supply Temperature Supply Pressure, adjustable Filtration
Filtered air 26 lbs/min 60° ± 3°F 11” ± 2” water column, typical 100 microns
Environment, Operating:
Temperature Relative Humidity
Altitude
10° to 27°C (50° to 80°F) To 95% at 10°C to 50% at 27°C (with condensation) To 1,000 feet above MSL
| Environment, Non-operating |
| -35° to +55°C (-31° to +131°F) |
Power Requirements
115/230 VAC 3-phase 60 Hz 50A
Interlock Activators
Low air flow Air over temperature AC failure
| Electrical Box Door Controls/Indicators |
| Circuit Breaker w/ Phase Lights |
Clogged Filter Indicator Over Temperature Indicator Low Pressure Indicator Audible Alarm with Reset Running Time Meter Fuse, Control Circuit
| Electrical Box, Inside |
| Compressor Switch |
| Front Panel Indicators |
| Supply Temperature Gauge |
Supply Pressure Gauge Calibration Port With Valve
Condensing Unit Refrigerant Compressor Fan
R-22 3 hp, 3-phase 1/3 hp, 1-phase
Air Blower
Centrifugal, 7½ hp, 3480 RPM, 3-phase
Dimensions (approximate) Width Depth Height Weight Output duct
48” 48” 72” 1500 lbs 6”
Additional requirements: Unit must be on casters