Statement of Work 1/4/2018 The contractor shall provide quantity one (1) Refrigerated Air Cooling Unit in accordance with the below specifications.

Cooling Unit Specifications:

Coolant Characteristics:

Coolant Composition

Supply Rate

Supply Temperature

Supply Pressure, adjustable

Filtration Filtered air

26 lbs/min

60° ± 3°F

11” ± 2” water column, typical

100 microns

Environment, Operating:

Temperature

Relative Humidity

Altitude 10° to 27°C (50° to 80°F)

To 95% at 10°C to 50% at 27°C (with condensation)

To 1,000 feet above MSL

Environment, Non-operating
-35° to +55°C (-31° to +131°F)
Power Requirements
115/230 VAC 3-phase 60 Hz 50A
Interlock Activators
Low air flow

Air over temperature

AC failure

Electrical Box Door Controls/Indicators
Circuit Breaker w/ Phase Lights

Clogged Filter Indicator

Over Temperature Indicator

Low Pressure Indicator

Audible Alarm with Reset

Running Time Meter

Fuse, Control Circuit

Electrical Box, Inside
Compressor Switch
Front Panel Indicators
Supply Temperature Gauge

Supply Pressure Gauge

Calibration Port With Valve

Condensing Unit

Refrigerant

Compressor

Fan R-22

3 hp, 3-phase

1/3 hp, 1-phase

Air Blower
Centrifugal, 7½ hp, 3480 RPM, 3-phase

Dimensions (approximate)

Width

Depth

Height

Weight

Output duct 48”

48”

72”

1500 lbs

6”

Additional requirements:

-Unit shall be on casters.

-Standard Commercial User’s Manual to be delivered with the unit.

***This requirement does not include the removal of the existing unit or installation for this new unit.