Statement of Work 1/4/2018 The contractor shall provide quantity one (1) Refrigerated Air Cooling Unit in accordance with the below specifications.
Cooling Unit Specifications:
Coolant Characteristics:
Coolant Composition
Supply Rate
Supply Temperature
Supply Pressure, adjustable
Filtration Filtered air
26 lbs/min
60° ± 3°F
11” ± 2” water column, typical
100 microns
Environment, Operating:
Temperature
Relative Humidity
Altitude 10° to 27°C (50° to 80°F)
To 95% at 10°C to 50% at 27°C (with condensation)
To 1,000 feet above MSL
| Environment, Non-operating |
| -35° to +55°C (-31° to +131°F) |
| Power Requirements |
| 115/230 VAC 3-phase 60 Hz 50A |
| Interlock Activators |
| Low air flow |
Air over temperature
AC failure
| Electrical Box Door Controls/Indicators |
| Circuit Breaker w/ Phase Lights |
Clogged Filter Indicator
Over Temperature Indicator
Low Pressure Indicator
Audible Alarm with Reset
Running Time Meter
Fuse, Control Circuit
| Electrical Box, Inside |
| Compressor Switch |
| Front Panel Indicators |
| Supply Temperature Gauge |
Supply Pressure Gauge
Calibration Port With Valve
Condensing Unit
Refrigerant
Compressor
Fan R-22
3 hp, 3-phase
1/3 hp, 1-phase
| Air Blower |
| Centrifugal, 7½ hp, 3480 RPM, 3-phase |
Dimensions (approximate)
Width
Depth
Height
Weight
Output duct 48”
48”
72”
1500 lbs
6”
Additional requirements:
-Unit shall be on casters.
-Standard Commercial User’s Manual to be delivered with the unit.
***This requirement does not include the removal of the existing unit or installation for this new unit.