Access Control and Intrusion Systems Complete Material Submittal
Prepared for :
Phone: (877) 331-2084 FAX: (909) 628-7774 24-Hour Service: (909) 628-8886 Website: www.hcisystems.net
Naval Facilities Engineering Command Southwest
Ontario ● San Diego ● Irvine ● Northern California
P-229 Weapons Test Laboratory And Calibration Laboratory Seal Beach, California
Corporate Office: 1354 South Parkside Place, Ontario, CA 91761
FIRE / LIFE SAFETY & LOW VOLTAGE SPECIALISTS
California Contractor's License # 905493
S y s t e m s I n c.
JRC1
Submittal Stamp
JRC1
Text Box
JRC
JRC1
Text Box 28 16 01-02-00
JRC1
Rectangle
JRC1
Text Box x
JRC1
Text Box
JRC1
Text Box
JRC1
Text Box
JRC1
Text Box
JRC1
Group 7/21/15
JRC1
Text Box
I hereby certify the materials shown and marked in this submittal is that proposed to be incorporated with contract number N62473-10-D-5405-0003, is in compliance with the contract documents, can be installed in the allocated spaces, and is submitted for Government Approval.
Certified by QC Manager________________, Date_______
Approved by DOR______________________,Date_______
Manufacturer Device Model # Description
Lenel PRO-64RUP 64 Access Readers upgrade for all PRO systems
Lenel LNL-2220 Intelligient Dual Reader System Controller
Lenel LNL-1320 Dual Reader Interface Module
Altronix AL600ULX 6 Amp Panel Power Supply
Altronix AL600ULACMB 6 Amp Door Lock Power Supply with Access Control Module Board
Mier BW-103BP 24”W x 30”H x 6”D Enclosure
HID 920PHRNEK00005 iClass Proximity Card / PIV Reader - switchplate reader
Sentrol 1078C-M Recessed Door Contacts
Naval Facilities Engineering Command Southwest P-229 Weapons Test Laboratory And Calibration Laboratory
Arrow 32HB4-N 18awg - 4 conductors shielded plenum- natural
Arrow 31FB6-N 22awg - 6 conductors shielded plenum- natural
Integrated Security Management Software
Enterprise
Advanced Enterprise Security Integration OnGuard Enterprise is the industry’s first multi-server, synchronized database solution designed for enterprises with multiple facilities spread across geographical areas.
OnGuard Enterprise allows corporate security and IT managers to maintain central control over the entire integrated security system, while allowing regional offices to maintain independence and autonomous operations of their respective individual regional security systems.
Central Database Storage Facilities OnGuard Enterprise gives corporate security and IT managers complete command and control over all system and event information. All cardholder and access control field data accumulated at the regional servers is synchronized and logged to a master enterprise server. This gives corporate security managers full viewing control over central alarm monitoring, reporting, and auditing functionality.
Autonomous Regional Operations OnGuard Enterprise gives regional system administrators autonomous control over their individual regions, independent of the enterprise server and corporate wide area network. Each regional system administrator has total control over all access control field hardware and system information related to his respective region. Additionally, regional administrators and operators can view, control, and modify only the information and field hardware that is related to their regions.
Standard Features
• Data Synchronization Between Multiple
Databases via LAN/WAN Connections
• MobileBadge Functionality for Enrolling
Cardholders at Remote Sites
• Segmented Database Architecture
• Open Architecture Design Utilizing Commercial, Off-the-Shelf Products
• Intelligent Fault Tolerant Response System
• Advanced Network Design
• Powerful Import & Export Capabilities
• Multi-Level Regional Server Support
Options
• Multi-Regional Alarm Monitoring
Support
• Unlimited Regional Servers
• Unlimited Levels
• Unlimited Cardholders
• Unlimited Simultaneous Users
• Unlimited Card Readers
• Unlimited Alarm Inputs
• Unlimited Client Workstations
• Unlimited Time Zones
• Unlimited Simultaneous Monitoring
• Unlimited User Privilege Levels
• Unlimited Relay Outputs
* OnGuard offers you scalability that is only limited by the physical limitations of your system size.
lenel.com
Enterprise
Multi-Database Synchronization At periodic intervals, each of the regional servers performs a synchronization process with their “parent” enterprise server via wide area network communication. All access control field and event information, as well as updated cardholder information, is uploaded through all levels to the enterprise server. The enterprise server then distributes any changes received from other regional servers, so that all servers are equipped operating with up-to-date information.
Scalability for Multinational Sites OnGuard Enterprise is scalable, which makes it ideal for any size installation. It supports an unlimited* number of regional servers and client workstations. Its powerful, transaction-based architecture allows the system to grow and expand as the organization grows, while utilizing the same access control field hardware and application software.
Third Party Human Resource Interface OnGuard Enterprise’s advanced interfacing capabilities allow bidirectional communication with third party databases—such as human resource systems—to transfer cardholder information.
Updates occur in real time, and cardholder information is automatically downloaded to all associated access panels. If an employee is terminated, the information is transferred from the HR system to OnGuard Enterprise, which automatically removes all access rights for the cardholder and downloads the required information to the access controllers.
A Single Card Enterprise Solution With OnGuard Enterprise, each cardholder carries a single ID card that is usable at all regional sites in the system. Once the cardholder database has been distributed to the regions, each regional administrator can assign unique access levels for the cardholders that are allowed at his region. OnGuard Enterprise’s advanced security allows system administrators and operators to assign access levels for only those card readers that are in their respective regions.
Multi-Regional Monitoring and Administration OnGuard Enterprise’s power and flexibility allows system operators to monitor alarms in multiple regions simultaneously.
This means that regional operators might, for example, monitor alarm and event information locally during working hours, while enterprise operators might monitor alarms from all of the regions after hours. An unlimited number of regions can be monitored simultaneously. OnGuard Enterprise also allows enterprise system administrators to configure and administer multiple regions from a single site.
Fi ng er R ea d er
C en tr al iz ed
R eg io na l A d m in is tr at io n
O nG ua rd
ID
C re d en ti al C en te r W or ks ta tio n
O nG ua rd
In te gr at ed M on ito rin g
W or ks ta tio n
In te g ra te d
E ve nt s
E ve nt P ro xy
V id eo S ur ve ill an ce C on so le U
S B
S m ar t
C ar d
B ad g e
P ri nt in g /E nc o d in g w ith C om p le te
S m ar t
C ar d an
B io m et ric S up p or t
IP
C am er as Le ne l N
V R
’s
A p p lic at io n S er ve r In te rn et In fo rm at io n S er vi ce s
(II
S
O nG ua rd
R eg io na l S er ve r
Fa ul t To le ra nt
O nG ua rd
R em o te
M o ni to r V id eo
V id eo W al l
E nt ry /E xi t
R ea d er s
3R D
P A
R
TY
IN
TE
G R
AT
E
D H
A R
D W
A R
E
C O
M M
A N
D C
E N
TE
R
V
ID
E O
S O
LU
TI
O N
S Ir is
IS
D
C D oo r
C on tr ol le r up t o d ev ic es
IC
R
C D ua l R ea d er C on tr ol le r up t o d ev ic es
D ua l S ys te m
C on tr ol le r up t o d ev ic es
D ua l P at h C on ne ct io n
A cc es s/
In tr us io n H yb rid
C on tr ol le r
R ea d er
D ua l D oo r In te rf ac e
D ua l D oo r In te rf ac e
D oo r In te rf ac e
Fi ng er H an d
K ey
R ea d er
R ea d er
In p ut
W ire le ss
G at ew ay
M ul tip le
W ire le ss
D ev ic es
M
FG
D ep en d en t
O ut p ut
D ua l R ea d er
In te rf ac e R ea d er In te rf ac e
B io m et ric G at ew ay
D om e Fi xe d
P
TZ
C C
T V
/A na lo g
V id eo
A ud io
D om e Fi xe d
P
TZ
O th er R ec o rd er s
IV
S
V id eo
M ag em en t
S er ve r
W ir el es s G ua rd s
M O
B
IL
E S
O
LU
TI
O
N S
M o b ile
B ad gi ng
M o b ile
M on ito rin g
TC
P
/I P
N E
TW
O
R K
D E
D
IC
AT
E
D V
ID
E
O S
U B
N E
T (R
O U
TE
D
T O
C O
R P
O R
AT
E
N E
T)
In ve st ig at io n C lie nt
E nt ry /E xi t
R ea d er s E nt ry
/E xi t R ea d er s
E nt ry /E xi t
R ea d er s
Fi re
P an el
In tr us io n D et ec tio n
P an el
E N
V
IR
O N
M E
N T
IN
TE
G R
AT
IO
N
D ep ar tm en t
M an ag er
D ec en tr al iz ed A d m in is tr at io n
M on ito rin g
R ec ep tio n V is ito r C he ck
-i n
S ta tio n
TE
R
M
IN
A L
S E
R V
E R
S A
N /N
A S
C E
N
TR
A
LI
Z E
D S
TO
R
A G
E
S er ve r
W E
B C
LI
E
N
TS
D ec en tr al iz ed A cc es s P riv ile ge M an ag em en t
V id eo V ie w er V is ito r H os t
En ter pr ise
S ec ur e
LA
N
/W A
N
A re a S ire n
O ut p ut s
In tr us io n Z on es
In p ut
O ut p ut
Te le p ho ne L in e vi a
O p tio na l W or ld
W id e M od em
C en tr al
S ta ti o n R ec ei ve r
In tr us io n/ B ur g/
Fi re
3rd P ar ty
Fi re
3rd P ar ty
B ur g
S E
C U
R
IT
Y S
E R
IE
S
C O
N
TR
O
LL
E R
S
A C
C E
S S
S E
R
IE
S C
O N
TR
O
LL
E
R S
Op en
Ac ce ss Al lia nc e P ro gr am
W A
N
R E
G
IO
N
(P A
R E
N T)
R E
G
IO
N
(P A
R E
N T)
R E
G
IO
N
(C H
IL
D
M A
S
TE
R R
E G
IO
N
R E
G
IO
N
(C H
IL
D
W A
N
O nG ua rd
ID
C re d en ti al C en te r W or ks ta tio n
C er ti� ca tio n
A ut ho rit y C ar d
/B io m et ric M an ag em en t S ys te m
B ad g e
P ri nt in g /E nc o d in g w ith C om p le te
S m ar t
C ar
B io m et ric S up p or t
C en tr al iz ed
E nt er p ris e A d m in is tr at io n
O nG ua rd
E nt er p ri se
S er ve r
Fa ul t To le ra nt O nG ua rd D at aC on d uI T
O nG ua rd
D at aE xc ha ng e
D at aC on d uI
T Q ue ue
A ct iv e
D ire ct or y
LD
A P
D ire ct or y
M ic ro so ft
M es sa ge
Q ue ue
H um an R es ou rc es
D at ab as e
Lo gi ca l A cc es s C on tr ol S ys te m
E N
V
IR
O N
M E
N
TA
L D
AT
A
A N
D
IN
P U
TS
TC
P
/I P
N E
TW
O
R K
W A
N
M A
S
TE
R R
E G
IO
N
R E
G
IO
N
(P A
R E
N T)
A
LT
E R
N
AT
E L
O C
AT
IO
N
D is as te r R ec o ve ry
B ac ku p
S ec ur ity
S er ve r
E nt er p ri se
M o ni to ri ng
O p er at io ns
C en te r
(866) 788-5095
Specifications subject to change without notice.
©2015 Lenel Systems International, Inc. All rights reserved.
All trademarks are the property of their respective owners.
Lenel is a part of UTC Building & Industrial Systems, a unit of United Technologies Corporation.
OG_SS_ENT_0515
lenel.com ccess C ontrol
LNL-2220
The LNL-2220 Intelligent Dual Reader Controller (IDRC) by Lenel provides a single board solution for interfacing one or two doors to an OnGuard system. In addition, other I/O and reader interface modules can be added on the LNL-2220’s downstream port to expand its capabilities. The LNL-2220 revolutionizes access control system architecture by allowing Ethernet connection directly from an entry location to the OnGuard server, while still providing the security, functionality, and modularity of Lenel’s proven hardware platform. The LNL-2220 is scalable for any access control application, from the most basic to the most sophisticated. In the event of communication loss, the LNL-2220 allows nearly all local functionality to continue unimpaired until the server connection is restored.
Utilizing its native Ethernet communications and an advanced 32-bit processor, the LNL-2220 can communicate upstream to the host computer through its Ethernet port (with a throughput up to eight times greater than the fastest serial connections), or at up to 115.2 Kbps using RS-232 communication directly or through an external dial-up modem. The LNL-2220 can store up to 250,000 cardholders in non-volatile flash memory, and supports selective download for larger cardholder databases. The downstream RS-485 two-wire port can be used to connect up to 32 devices (maximum 64 doors).
Two on-board reader ports support Data1/Data0, Clock/Data, Bioscrypt RS-485 readers and the bidirectional RS-485 Open Supervised Device Protocol (OSDP) communications. Each LNL-2220 supports up to eight different card formats. The LNL-2220 includes eight inputs that support normally open, normally closed, supervised, and unsupervised circuits. In addition, four output relays support fail-safe or fail-secure operation.
Features and Functionality Controller Functionality
■ On-board Ethernet 10/100Base-T port provides up to 8 times greater throughput than serial-to-Ethernet converters. DHCP and fixed IP addressing supported.
■ DNS device naming through DHCP extended commands
■ 6 MB of available on-board, non-volatile flash memory
■ Battery-backed, non-volatile storage of 50,000 events
■ Firmware stored in flash memory, background download of firmware updates supported
■ Supports up to 16 different formats (8 card formats and 8 asset formats)
■ Biometric template storage support for Schlage Recognition Systems®, Bioscrypt®, and Identix®.
■ Direct connection of Bioscrypt RS-485 devices
■ Enhanced anti-passback capabilities
■ Up to 32,000 access level permissions
■ 255 holidays with grouping, 255 timezones, each with 6 intervals
■ Elevator control support for up to 128 floors
■ Individual extended held open and strike times (ADA required)
■ Up to 9-digit user PIN codes
■ 20 status LEDs
■ 2 dedicated inputs for tamper and power failure status
■ 12 or 24 VDC input power
■ Advanced Encryption Standard (AES) 128-bit algorithm for communications
Reader Interface Functionality
■ Supports Data1/Data0, Clock/Data and Lenel OSDP-compatible RS-485 readers and keypads
■ 4 Form-C relay outputs, 5 A at 30 VDC
■ Door contact supervision (open/closed) and REX push-button monitor for each door
■ Strike control and auxiliary output for each door
■ Bicolor reader status LED support plus beeper control, or 2-wire LED support
■ On-board regulator allows 12 VDC reader power from 24 VDC power source
Intelligent Dual Reader Controller
JRC1
Polygon cc es s
C on tr ol
LNL-2220
LNL-1300
Up to 32 Single Reader Interface Modules
LNL-2220
Intelligent
System Controller
OnGuard Security Server
CORPORATE HEADQUARTERS LOCAL AREA NETWORK (TCP/IP)
LNL-1100
Input Control Module
(Up to 16 Inputs per
LNL-1100)
LNL-1200
Output Control Module
(Up to 16 Outputs per
LNL-1200)
RS-485 multidrop
Controller Options
LNL-2220
Dial-Up Modem
LNL-56KEXT
LNL-DC336K
Specifications Primary Power (DC or AC)
DC input:
Event Memory and Clock Backup Communication Ports
Primary (Ethernet) Port:
Alternate Upstream Port 1:
Downstream Port 2:
Inputs Tamper and Power Fail Monitors:
Door position, REX, and AUX:
Outputs Relay outputs:
Reader Power DC output:
Reader Port Compatibility
Environmental Temperature:
Humidity:
Mechanical
Dimensions:
Weight:
Approvals
6 MB On-board flash memory available for cardholder & asset database, 50,000 event battery backed RAM for event log
56 K external modem with cables 12 VDC-powered/33.6 K external modem
* The LNL-2220 is for use in low voltage, power-limited, class 2 circuits only.
12 or 24 VDC ± 15%. 500 mA maximum 3 V lithium, type BR2325, BR2330, CR2330
10/100Base-T Ethernet high-speed port RS-232 9600 to 115.2 Kbps async RS-485 (2-wire) 9600 to 38.4 Kbps async
Unsupervised, dedicated 8, each programmable as normally open or normally closed, supervised or unsupervised circuits
4 Form-C 5 A at 30 VDC relay outputs: 2 strike, 2 auxiliary
12 VDC, 125 mA regulated when 24 VDC powered, or 12 to 24 VDC 125 mA current limited Wiegand Data1/Data0, Magnetic Clock/Data, F/2F single-wire protocol, Bioscrypt RS-485, OSDP (Open Supervised Device Protocol RS-485)
Operating: 32° to 158° F (0° to 70° C) Storage: -67° to 185° F (-55° to 85° C) 0 to 95% RHNC
6 x 8 x 1 in. (152 x 203 x 25 mm) 9 oz. (255 g) nominal UL 294 and 1076-listed, CE-marked, ROHS compliant Advanced Encryption Standard (AES) 128-bit communication algorithm, NIST certification pending
Dual Reader Interface Module
LNL-1320 Series 2 Overview
Lenel offers a Dual Reader Interface (DRI) module for access control solutions. Most access control card readers, keypads, or readers with keypads that use standard Wiegand Data1/Data0 or Clock/Data communication are supported, as are those that support the bidirectional
RS-485 Open Supervised Device Protocol (OSDP). Lock, unlock, and facility code offline access modes are supported on all readers connected to the DRI. Each DRI supports up to eight different card formats as well as issue codes for both magnetic and Wiegand card formats.
The DRI provides a vital link between the Intelligent System Controller
(ISC) and the card reader attached to the interface. As many as 32
DRI modules can be multidropped using RS-485 2-wire or 4-wire communication up to 4,000 feet per port away from the ISC. Each DRI module is individually addressed for increased reporting capabilities with
OnGuard® access control software applications. The DRI includes eight inputs that support normally open, normally closed, supervised, and non-supervised circuits. In addition, six output relays support fail-safe or fail-secure operation.
FEATURES & FUNCTIONALITY
• 12 or 24 VDC power supply
• Supports Data1/Data0, Clock/Data and Lenel OSDP-compatible RS-485 readers and keypads
• Downloadable firmware
• Six Form-C 5 A at 28 VDC relay outputs
• Up to 16 different formats (8 card formats and 8 asset formats)
• Issue code support for magnetic and Wiegand formats
• Door contact supervision (open/closed)
• REX push-button monitor
• Strike control output
• Bicolor reader status LED support and 2-wire LED support
• Beeper control
• Dedicated tamper and power failure circuits
• Support for offline reader access mode
• On-board jumpers for termination
• On-board regulator allows 12 VDC reader support from 24 VDC power source
• DIP switch-selectable addressing
JRC1
Polygon
JRC1
Polygon
(866) 788-5095
Specifications subject to change without notice.
© 2014 Lenel Systems International, Inc. All rights reserved.
LNL_TS_1320s2_063014 lenel.com
Power Supplies & Enclosures
LNL-AL400ULX Lenel® UL Listed 4A, 110VAC Power Supply – 12VDC 4A output, 115VAC input, continuous supply current with enclosure (15.5” x 12.5” x 4.5”), lock, tamper switch, UPS capable (Battery Optional) UL & CUL Approved
LNL-AL600ULX-4CB6 Lenel UL Listed Power Supply – 12VDC 6A output, 115VAC (1.6 amps) input, continuous supply current with enclosure (24” x 18” x 4.5”), lock, tamper switch, power distribution module, UPS capable (Battery Optional) UL & CUL Approved
ABT-12 Battery Kit - 12VDC, 12 AH battery (PS-12120)
Specifications
Primary Power 12 to 24Vdc ±10%, 550mA maximum (plus reader current) 12Vdc @ 450mA (plus reader current) nominal, 18.41 BTUs 24Vdc @ 270mA (plus reader current) nominal, 22.09 BTUs
Outputs 6 outputs, Form-C, 5A @ 28Vdc, resistive
Inputs 8 unsupervised/supervised, standard EOL: 1k/1k ohm, 1% 1/4 watt 2 unsupervised, dedicated for cabinet tamper and UPS fault monitoring
Reader Interface Reader power: 12Vdc ±10% regulated, 125mA maximum each reader (jumper selectable and input voltage (VIN) must be 20Vdc mini-mum) or 12 to 24Vdc ±10% (input voltage passed through) 125mA maximum each reader
Reader Port Compatibility Wiegand Data 1/Data 0 Magnetic Clock/Data F/2F Single Wire Open Supervised Device Protocol
Mechancial Dimension: 6” (152mm)W x 8” (203mm)L x 1” (25mm)H Weight: 11 oz. (312g) nominal
Environmental Temperature Operating: 32°F to 158°F (0°C to +70°C) Storage: -67°F to 185°F (-55°C to +85°C)
Humidity 0% to 95% RHNC
Compliance Approvals FCC Part 15, CE, RoHS, UL 294, UL 1076, ULC CSA-C22.2, CAN/ULC-S319-05, cUL/ORD-C1076
Intelligent System Controller (ISC) Varies per ISC model*
LNL-1320
Dual Reader Interface Module
LNL-1300
Single Reader Interface Module
LNL-1100
Input Control Module Up to 16 Inputs per
LNL-1100
Motion Sensor Alarm
LNL-1200
Output Control Module Up to 16 Outputs per
LNL-1200
RS-485 Multi-drop up to 4000 ft.
Option 1
TC
P
/I P
N E
TW
O
R K
Reader Reader Reader
Option 2
OnGuard Security Server
-OR-
* See ISC datasheets for speci�c capacities.
JRC1
Polygon
• 12VDC or 24VDC selectable output.
• 6 amp supply current.
• Input 115VAC / 60Hz, 1.9 amp.
• Input fuse rated @ 3.5 amp/250V.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current .7 amp.
• Automatic switch over to stand-by battery when
AC fails (zero voltage drop).
• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).
• Battery presence supervision (form “C” contacts).
• AC input and DC output LED indicators.
• Enclosure:
- Combination knockouts are 1/2" and 3/4"
- Accommodates up to two (2) 12VDC/7AH batteries.
• Product weight:
- AL600ULX: 7.6 lbs.
- AL600ULXR: 6.6 lbs.
• Shipping weight:
- AL600ULX: 8.5 lbs.
- AL600ULXR: 7.6 lbs.
AL600ULX(R) Power Supply/Charger
Rev. DSAL600ULX - F07G
Overview
Agency Approvals
Specifications
AL600ULX
• Grey enclosure.
AL600ULXR
• Red enclosure.
• These multi-agency approved single output power supply/chargers convert a 115VAC/60Hz input into one (1) 12VDC or 24VDC non-power limited output.
UL 294 UL Listed for Access Control System Units.
UL 603 UL Listed Standard for Power Supplies for Use with Burglar- Alarm Systems.
UL 1069 UL Listed Hospital Signaling and Nurse Call Equipment.
UL 1481 UL Listed Standard for Safety for Fire Protective Signaling Systems.
CUL Listed - CSA Standard C22.2 No.205-M1983, Signal Equipment.
MEA - NYC Department of Buildings Approved.
CSFM - California State Fire Marshal Approved.
FM - Factory Mutual Approved.
5.10"
6.5625"
3.25"3.25"
5.10"
5.10"
3.25"
1.00"10.50"1.00"
1.00" 1.00"
1.40"
1.20"
1.40"
1.20" 0.75"0.75" 11.00"
12.50"
3.25"
0.9375"
0.9375"
1.40" 4.85" 4.85" 1.40"
1.20"
Bottom
Top
RightLeft
Enclosure Dimensions 13.5”H x 13”W x 3.25”D
Altronix Corp. - 140 58th Street, Brooklyn, NY 11220 • 718-567-8181 • 888-258-7669 • altronix.com
AL600ULACM
• Eight (8) independently controlled fuse protected outputs.
AL600ULACMCB
• Eight (8) independently controlled
PTC protected outputs.
• Class 2 Rated power limited outputs.
• The AL600ULACM / AL600ULACMCB converts an 115VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC Fail-Safe and/or Fail-Secure outputs with a total of 6 amp continuous supply current. These power outputs can be converted to dry form "C" contacts (AL600ULACM only). Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. These units will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. The outputs will operate in both Fail-Safe and/or Fail-Secure modes. The units are designed to be powered by one common power source (factory installed) which will provide power for both the board operation and locking devices, or two (2) totally independent power sources, one (1) providing power for board operation and the other for lock / accessory power.
The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs.
• 12VDC or 24VDC @ 6 amp supply current.
• Power supply input options:
a) One (1) common power input for ACM8/ ACM8CB and lock power (factory installed).
b) Two (2) isolated power inputs - One (1) to power the ACM8/ACM8CB and one (1) for lock accessory power, (external power supply is required). (Current is determined by the power supply connected, not to exceed a maximum of 10 amp total).
• Eight (8) Access Control System trigger inputs.
Input options:
a) Eight (8) normally open (NO) inputs.
b) Eight (8) open collector inputs.
c) Any combination of the above.
• Eight (8) independently controlled outputs.
Output options:
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs.
b) Eight (8) form “C” 5 amp rated relay outputs
(AL600ULACM only).
c) Any combination of the above
(AL600ULACM only).
• Eight (8) auxiliary power outputs (unswitched)
• Output ratings:
- Fuses are rated @ 3.5 amp (AL600ULACM).
- PTCs are rated @ 2.5 amp (AL600ULACMCB).
• ACM8 board main fuse is rated at 10 amp.
• Input 115VAC 60Hz rated @ 1.9 amp.
• Filtered and electronically regulated outputs
(built-in power supply)
• Red LEDs indicate outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry contact input.
b) Polarity reversal input from FACP signaling circuit.
• Alarm output relay indicates that FACP input is triggered (form “C” contact rated @ 1 amp 28VDC not evaluated by UL).
• Green LED indicates when FACP disconnect is triggered.
• Built-in charger for sealed lead acid or gel type batteries.
• AL600ULXB (Power Supply Board) maximum charge current .7 amp.
• Automatic switch over to stand-by battery when AC fails.
• AC input and DC output LED indicators.
• Zero voltage drop when unit switches over to battery backup (AC failure condition).
• Short circuit and thermal overload protection.
• AC fail supervision (form "C" contact).
• Battery fail and battery presence supervision
(form "C" contact).
• Enclosure accommodates up to two (2) 12AH batteries.
• Product weight:
- AL600ULACM: 10.3 lbs.
- AL600ULACMCB: 10.2 lbs.
• Shipping weight:
- AL600ULACM: 11.6 lbs.
- AL600ULACMCB: 11.5 lbs.
AL600ULACM, AL600ULACMCB
Power Supply/Chargers w/Multi-Output Access Power Controllers Rev. DSAL600ULACM - A25F
Overview
Specifications
UL Listed for Access Control Systems Units
(UL 294).
CUL Listed - CSA Standard C22.2 No.205-M1983 Signal Equipment.
Agency Approvals
MEA - NYC Department of Buildings Approved.
CSFM - California State Fire Marshal Approved.
Enclosure Dimensions 15.5”H x 12”W x 4.5”D
393.7 mm x 304.8 mm x 114.3 mm
.875"
1"
1.3"9.97"
13.53"
6.625"
2.25" 3.68" 4.56"
1.22"
1.22"
3.5"
1"
13.25"
2"
1.22"
12"
15.5"
4.5"
2.25" 3.68" 4.56"
1.22"
1.25"
2.2"
1"
Altronix Corp. - 140 58th Street, Brooklyn, NY 11220 • 718-567-8181 • 888-258-7669 • altronix.com
800-473-0213 | info@mierproducts.com | www.mierproducts.com
BW-103R
24”W x 30”H x 6”D
Mier’s standard line of painted cabinets is designed to accommodate a wide variety of uses in the security and home-automation industries.
• The BW-103G is 24”W x 30”H x 6”D, with a removable door with louvers, and is gray
• The BW-103R is the same but in red
• The BW-103BP is the same as the BW-103G with an 22”x28” removable internal back panel
• Rugged construction & one-piece piano hinge for strength
• Key holes for quick and easy mounting
• Durable powder coated finish
• Holes are in place for bolting the door shut, but there is also a knockout to fit Mier’s cam locks
• Multiple, conveniently located electrical knockouts for different applications
Standard color is beige. Other colors available for quantities of 25 or more.
BW-103BP
The removable 22”x28” panel is standard in a BW-103BP. It can be customized (example pictured above) for quantities of 25 or more.
BW-103G, BW-103R, and BW-103BP ElEctRical EnclosuREs
Wireless Vehicle Detection | Driveway Alarms | Drive-Up Window Detection | Buried Sensor Systems | Electrical Boxes | DVR/CPU Lockboxes Rack Enclosures | Outdoor Enclosures | Temperature Controlled Enclosures | UL/NEMA Non-Metallic Enclosures | Siren/Speaker Cabinets Bell Boxes | Structured-Wiring Flush-Mount Cabinets | Power Supply Boxes | Battery Cabinets | Transformer Covers | Custom Fabrication
If you don’t see the enclosure you are looking for, call or e-mail us and we’ll be happy to help! Custom enclosures, colors, and/or graphic-screening available for quantities of 25 or more.
PR
OU
DLY
MADE IN THE USA
FOR OVER 25 YE
AR
S!
hidglobal.com
PHYSICAL ACCESS SOLUTIONS
pivCLASS® Contactless Readers
CONTACTLESS READERS FOR "CONTROLLED" AREAS ENABLE
HIGH SECURITY, INTEROPERABILITY AND COMPLIANCE
� Part of an integrated solution from a single, trusted provider – Enable FIPS 201 compliance per NIST SP 800-116 guidelines and the TWIC Reader Specification.
� Contactless reader solutions for "Controlled" security areas – Meet NIST's "Controlled" security area assurance-level requirements with a single-factor authentication.
� Support multiple card types – Work with PIV, PIV-I, CAC, CIV (a.k.a., PIV-C), TWIC, FRAC, iCLASS® and HID Prox® cards for easy, phased transitions from legacy technology to new PKI-enabled smart cards.
HID Global's pivCLASS Government Solutions portfolio enables facilities to upgrade their existing physical access control system (PACS) to achieve FIPS 201 compliance.
The pivCLASS contactless readers (R10, R15 and
R40) and their proximity-enabled versions deliver the "Controlled" assurance level defined in the
National Institute of Standards and Technology
(NIST) SP 800-116 guidelines when used with the pivCLASS Authentication Module (PAM) to perform a single-factor authentication check:
CHUID + VIS Authentication – The pivCLASS system tests the signature on the PIV Card
Holder Unique IDentifier (CHUID) data object.
The CHUID signature check ensures the card is authentic (came from a valid issuer) and has integrity (has not been altered).
Because the CHUID is a “free read” and will be transmitted unencrypted to any reader, it could be possible for perpetrators to capture a PIV card's CHUID and create a counterfeit card.
However, the required visual check (VIS) of the card secures against this threat by making it possible to identify cards that have been counterfeited or altered.*
CAK Authentication – These pivCLASS readers work with the PAM to perform a PKI challenge-response test in addition to a signature check to validate the card authentication key (CAK).
The challenge-response test ensures the public key in the card authentication certificate is bound to the private key on the card. This CAK authentication secures against cards that have been counterfeited, altered, copied or cloned.
These pivCLASS readers are guaranteed to meet the stringent specifications for operation, reliability and interoperability with other
Genuine HID™ products.
ADDITIONAL PRODUCT FEATURES:
� Architected for maximum security and affordability, these readers utilize the pivCLASS Authentication Module to provide cryptographic functionality and to pass Wiegand-formatted data to the PACS controller. Locating the critical security operations within the secure perimeter, rather than on the attack side of the door, increases security and reader affordability.
� Up to two pivCLASS readers can connect to a pivCLASS Authentication Module via four-wire RS-485 communication to the reader, typically enabling facilities to reuse much of their existing wiring.
� Available in mullion, mini-mullion and wall switch form factors to mount and cover single-gang switch boxes.
� Available with either a pigtail or terminal strip wiring termination.
� Each of these readers can also be ordered with 125 kHz proximity support.
Meet NIST assurance-level requirements for these areas:
* Per SP 800-116, to achieve "Controlled" assurance, the CHUID read must be combined with a visual check (VIS) of the identification card.
“Controlled” Areas “Exclusion” Areas“Limited” Areas“Unrestricted” Areas http://www.hidglobal.com http://www.hidglobal.com
© 2015 HID Global Corporation. All rights reserved. HID, the HID logo, pivCLASS, Genuine HID, and iCLASS are trademarks or registered trademarks of HID Global in the U.S. and/or other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.
2015-02-27-pivclass-fips-controlled-readers-ds-en PLT-00413 hidglobal.com
North America: +1 512 776 9000 Toll Free: 1 800 237 7769 Europe, Middle East, Africa: +44 1440 714 850 Asia Pacific: +852 3160 9800 Latin America: +52 55 5081 1650
SPECIFICATIONS
Model Name R10-H R15-H R40-H RP10-H RP15-H RP40-H
Base Part Number 900NHR 910NHR 920NHR 900PHR 910PHR 920PHR
13.56 MHz Card Compatibility PKI-Based FIPS-201 Credentials including PIV, PIV-I, CIV, CAC, TWIC and FRAC Secure Identity Object (SIO) on iCLASS SE, SE for MIFARE DESFire EV1 and SE for MIFARE Classic standard iCLASS Access Control Application
ISO14443A (MIFARE) CSN
125 kHz Card Compatibility N/A HID, AWID, EM4102
System Requirements These readers require HID pivCLASS Authentication Module (M2000) to support FICAM compliance
Typical Contactless Read Range1 FIPS 201 type cards can be read using either the contact or contactless card interface
FIPS-201 Type Cards, Contactless Interface2
PIV, PIV-I, CIV, CAC, TWIC and FRAC
1" (2.5 cm) 1" (2.5 cm) 1.5" (3.8 cm) 1" (2.5 cm) 1" (2.5 cm) 1.5" (3.8 cm)
13.56 MHz iCLASS, DESFire and MIFARE Cards
iCLASS SE® 2.5" (6.4 cm) 2.5" (6.4 cm) 4.5" (11 cm) 2.5" (6.4 cm) 2.5" (6.4 cm) 4.5" (11 cm)
DESFire® EV1 and HID SE™ 1" (2.5 cm) 1" (2.5 cm) 2" (5.1 cm) 1" (2.5 cm) 1" (2.5 cm) 2" (5.1 cm)
MIFARE® Classic and HID SE® 2.3" (4.0 cm) 2.3" (4.0 cm) 4.5" (11 cm) 2.3" (4.0 cm) 2.3" (4.0 cm) 4.5" (11 cm)
125 kHz Promimity Cards
HID Prox / AWID N/A N/A 2" (5.1 cm) 2" (5.1 cm) 2.5" (6.4 cm)
EM4102 N/A N/A 3.5" (8.9 cm) 3.5" (8.9 cm) 4.0" (10 cm)
Mounting Mini-mullion size;
physically HID
Global's smallest pivCLASS readers;
ideally suited for mullion-mounted door installations, U.S. single-gang J-box (with mud ring) or any flat surface
Mullion size;
physically HID
Global's second smallest pivCLASS readers; ideally suited for mullion-mounted door installations, U.S.
single-gang J-box (with mud ring) or any flat surface
Wall switch size;
designed to mount and cover single-gang switch boxes primarily used in the Americas;
includes a slotted mounting plate for European and Asian back box spacing
Mini-mullion size;
physically HID
Global's smallest pivCLASS readers and are ideally suited for mullion-mounted door installations, U.S.
single-gang J-box (with mud ring) or any flat surface
Mullion size;
physically HID
Global's second smallest pivCLASS readers; ideally suited for mullion-mounted door installations, U.S.
single-gang J-box (with mud ring) or any flat surface
Wall switch size with keypad (illuminated, 4 x 3); designed to mount and cover single-gang switch boxes;
primarily used in the Americas; includes a slotted mounting plate for European and Asian back box spacing
Color Black or Gray
Dimensions 1.9" x 4.1" x 0.9" (4.8 x 10.3 x 2.3 cm)
1.9" x 6.0" x 0.9" (4.8 x 15.3 x 2.3 cm)
3.3" x 4.8" x 1.0" (8.4 x 12.2 x 2.4 cm)
1.9" x 4.1" x 0.9" (4.8 x 10.3 x 2.3 cm)
1.9" x 6.0" x 0.9" (4.8 x 15.3 x 2.3 cm)
3.3" x 4.8" x 1.0" (8.4 x 12.2 x 2.4 cm)
Product Weight (Pigtail) 3.9 oz. (113 g) 5.3 oz. (151 g) 7.7 oz. (220 g) 4.0 oz. (114 g) 5.2 oz. (149 g) 7.8 oz. (222 g)
Product Weight (Terminal Strip) 2.9 oz. (84 g) 4.2 oz. (120 g) 7.5 oz. (215 g) 3.0 oz. (85 g) 4.3 oz. (124 g) 7.6 oz. (216 g)
Operating Voltage Range +12VDC
Current Draw - Normal Standby Current3 60 mA 60 mA 65 mA 75 mA 75 mA 85 mA
Current Draw - Maximum Average4 100 mA 100 mA 110 mA 100 mA 100 mA 110 mA
Current Draw - Peak5 200 mA 200 mA
Operating Temperature -30˚ to 150˚ F (-35˚ to 65˚ C)
Operating Humidity 5% to 95% relative humidity non-condensing
Storage Temperature -67˚ to 185˚ F (-55˚ to 85˚ C)
Environmental Indoor / Outdoor; IP55, IP65 if installed with optional gasket (IP65GSKT)
Transmit Frequency 13.56 MHz 13.56 MHz & 125 kHz
Protocol HID pivCLASS Protocol, CoreStreet Reader Protocol
Cable Distance6 Six conductor connections per reader: full duplex four-wire RS485 for communication (500 ft [152m], 22AWG), (300 ft [91m], 24AWG); two wires for power (500 ft [152m], 22AWG)
Wiring Connection Pigtail or Terminal Strip
Certifications FICAM tested7, UL294 (U.S. & Canada), FCC Certification (U.S.), RoHS2
Housing Material UL94 Polycarbonate
% of recycled content (Pigtail) 10.5% 11.0% 10.5% 10.5% 11.0% 10.5%
% of recycled content (Terminal Strip) 11.0% 11.5% 11.0% 10.5% 11.0% 11.0%
UL Ref Number R10E R15E R40E RP10E RP15E RP40E
Warranty Limited Lifetime 1 Typical read range in air. Different types of metal will cause some degradation (typically up to 20%). Use spacers to space product off metal and improve read range if required. Read ranges for FIPS 201 type cards will vary depending on the card manufacturer.
2 Measured using the SIO Data Model.
3 Standby Average - RMS current draw without a card in the RF field.
4 Maximum Average - RMS current draw during continuous PIV card reads.
5 Peak - highest instantaneous current draw during RF communication.
6 For cable lengths when used in Wiegand mode see "pivCLASS Reader Installation Guide" PLT-01134.
7 FICAM tested as part of complete physical access control systems.
An ASSA ABLOY Group brand http://www.hidglobal.com http://www.hidglobal.com
The GE Interlogix 1078 Series Steel Door contacts are designed specifically for use in the steel doors commonly found in commercial building applications. The unique housing design features a rugged unibody construction with flexible ribbed sides for quick, secure installation without gluing. The magnet housing isolates the magnet from the surrounding steel for maximum gap distances, both make and break. Over seven models including:
Wide Gap, SPDT, DPDT, and Biased for High Security applications make the 1078 Series the most widely used and comprehensive line available.
On available models a terminal connection (T) makes installation easier. Simply strip the wire, insert it into the terminal block and tighten. The terminal accepts any wire size from 14 to 22 gauge, and has a unique one piece design for added strength.
An optional Rare Earth Magnet is available. It is designed for use in metal entry/exit doors with a channel in the top of the door. The magnet eliminates the need to cut a mounting hole in the door channel. The flexible magnet housing can be compressed to accommodate a variety of channel widths for quick, easy installation. Adhesive is recommended.
The contact contains a hermetically sealed magnetic reed switch.
The reed shall be potted in the contact housing with a polyurethane based compound. Contact and magnet housing shall snap-lock into a 3/4" or 1" dia. hole. Housings shall be molded of flame retardant ABS plastic. Color of housings shall be off-white, grey or mahogany brown. The magnet shall be made of Alnico V.
Rare Earth Magnet shall be made of neodymium iron boron.
Snap-lock insulation bushing for tight fit and maximum gap in steel.
Both contact and magnet plastic housings are constructed of one piece of thick-walled ABS plastic for maximum strength and durability.
Standard Features
Fly leads and terminal options available
Designed specifically for use in steel doors
Special ribbed sides allow for easy installation
Rugged unibody construction for maximum durability and reliability
Terminal models available for easier installation
Regular, Wide Gap, SPDT, DPDT, and High Security models available
Rare Earth Magnet designed for steel door with top channel available
Model numbers
1076, 1076W, 1076C, 1076CW, 1076D, 1078, 1078W,
1078C, 1078CT, (R)1078, 1078CTW
Overview
GE Magnetic Contacts Product Information
Architectural and Engineering Specifications
Designed for use in Steel Doors
Optional 1840
Rare Earth Magnet
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Steel Door Contact 3/4” and 1” contacts
1078/1076 Series http://www.clrwtr.com/Sentrol-Recessed-Mount-Contacts.htm
Steel Door Contact 3/4” and 1” contacts 1078/1076 Series
©2002 GE Interlogix. All trademarks are properties of their owners.
C-3617-FLG10K-0403
GE Interlogix
1.125"
2.86 cm
1.125"
2.86 cm
1.00"
2.54 cm
Magnet Part No. 1921
(included)
1.563"
3.97 cm
Dimensions Specifications
Form A: (R)1078, 1078W, 1078C, 1078CT, 1078CTW Voltage 100V AC/DC max.
Current 0.5 A max.
Power 7.5 W max.
Form C: 1076, 1076W, 1076D, 1076C(D), 1076CW, 1076CH Voltage 30V AC/DC max.
Current 0.25 A max.
Power 3.0 W max.
Ordering Information
Model Dia. Loop Type Electrical Config. Hole Required Gap Distance* Color
* Gap distances are nominal make distance ±20%. Gap specifications are for switch to make.
Break distance is approximately 1.1 to 1.5 times make.
1” 1” 1” 1” 1”
3/4”
3/4”
3/4”
1” 3/4”
3/4”
1076W 1076D
1078W 1076C
1076CW
1078C (R)1078
1078CT
1078CTW
Open or Closed Open or Closed Open or Closed
Closed Closed
Open or Closed Open or Closed
Closed Closed Closed Closed
SPDT
SPDT
DPDT
N/O N/O
SPDT
SPDT
N/O N/O N/O N/O
1” x 1.125” 1” x 1.563” 1” x 1.125” 1” x 1.563” 1” x 1.125” 1” x 1.563” 1” x 1.125” 1” x 1.563” 1” x 1.125” 1” x 1.563” .75” x 1.125” .75” x 1.563” .75” x 1.125” .75” x 1.563” .75” x 1.125” .75” x 1.563” 1” x 1.125” 1” x 1.563” .75” x 1.625” .75” x 1.56” .75” x 1.625” .75” x 1.56”
Contact Magnet Wood* Steel* Rare Earth 1” Up to 1/2” Up to 5/8”
2” Up to 1” 3/4” Up to 3/8” Up to 5/8”
1” Up to 1/2” Up to 5/8”
2” Up to 1” 7/8” Up to 3/8” Up to 5/8”
2” Up to 3/4”
1/2” N/A 1” Up to 1/2” Up to 5/8”
7/8” 1/2” 5/8”
5/8” 3/4” N/A
1.125"
2.86 cm
Magnet Part No. 1921C
(included)
.875"
2.22 cm
1.563"
3.97 cm
.375" .962 cm
.750"
1.91 cm
0.89"
2.26 cm
1.813"
4.60 cm
0.5"
1.27 cm
0.625"
1.59 cm
Legs may be cut for
Height Adjustment
1.625"
4.13 cm
Models:
(R)1078, 1078W, 1076, 1076W, 1076D
Models:
1078C, 1076C, 1076CW, 1076CH
Rare Earth Magnet
Protected by U.S. Patent 5,844,458.
(R) prefix indicates Rare Earth Magnet
M, N, G M, N, G M, N, G M, N, G M, N, G M, N, G
M, N M, N, G
M, N M, N
N
Models:
1078CT, 1076CTW,
0.938"
2.36 cm
1.625"
4.13 cm
1.56"
3.96 cm
Magnet Part No. 1929
(included)
0.375"
0.64 cm
0.75"
1.91 cm
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
JRC1
Polygon
Part Number #
32HB4-N
Description: 18 awg 4 conductors Plenum rated jacket - Natural
Approvals: UL type CMP
Conductor: 18 awg 7 Strand Bare copper
Insulation: Low Smoke PVC
Wall Thickness: .008”
Color Code: Black/Red/White/Green
Jacket: Low Smoke Copolymer
Jacket Color: Natural
Wall Thickness: .015”
Nominal OD: .187”
Voltage: 300V
Capacitance: N/A
Impedance: N/A
Temperature Rating: 75C
Surface Print: 18 AWG 4C (UL) us TYPE CL3P/FPLP c(UL)us TYPE CMP, CL3P
3054355
Foot Markers: Yes
Date: 11-15-2012
Corporate Office
13911 Yorba Ave 2368 West Winton Street 6005 South 40 th Street Unit #1
Chino, CA. 91708 Hayward, CA. 94545 Phoenix, AZ. 85042
800.659.3655 866.227.7699 602.438.1030 fax: 909.282.1945 fax: 510.264.2120 fax: 602.438.1060
Part Number #
31FB6-N
Description: 22awg 6 conductors Shielded Plenum rated jacket - Natural
Approvals: UL type CMP
Conductor: 22awg 7 Strand Bare copper
Insulation: Low Smoke PVC
Wall Thickness: .008”
Shield: Alum Mylar with 22 AWG stranded drain wire
Color Code: Black/Red/White/Green/Brown/Blue
Jacket: Low Smoke Copolymer
Jacket Color: Natural
Wall Thickness: .015
Nominal OD: .173
Voltage: 300V
Capacitance: N/A
Impedance: N/A
Temperature Rating: 75C
Surface Print: 22 AWG 6C Shielded (UL) us TYPE CL3P/FPLP c(UL)us TYPE CMP, CL3P 3054355
Foot Markers: Yes
Date: 11-15-2012
Corporate Office
13911 Yorba Ave 2368 West Winton Street 6005 South 40 th Street Unit #1
Chino, CA. 91708 Hayward, CA. 94545 Phoenix, AZ. 85042
800.659.3655 866.227.7699 602.438.1030 fax: 909.282.1945 fax: 510.264.2120 fax: 602.438.1060
| Navy P-229 Weapons Test Laboratory Submittal Package |
| SUBMITTAL COVER SHEET |
| CUT SHEET LIST |
| OG_SS_ENT_0515_new format |
| HW_LNL-2220.pdf |
| Lenel_HW_Catalog_0607 12 |
| Lenel_HW_Catalog_0607 13 |
| LNL_TS_1320s2 |
| DSAL600ULX |
| DSAL600ULACM |
| Mier's BW-103 & 103BP Cut Sheet |
| pivclass-fips-controlled-readers-ds-en |
| 1078 Contact |
File details come from the government source that posted it. Updated .