N62478-24-Q-2674 Q and A 1.pdf
PDF 415 KB Posted
- Attached to
- Remove and Dispose of Diesel Fuel
- Solicitation number
- N6247824Q2674
About this file
This document is a set of questions and answers regarding the removal and disposal of approximately 17,000 gallons of diesel fuel from two underground storage tanks at the US Navy Joint Base Wahiawa.
The key details are:
- The fuel is stored in two underground storage tanks - one 5,000-gallon tank at Building 106 and one 20,000-gallon tank at Building 234.
- The fuel has been in use for several years to power emergency generators that are run monthly for maintenance.
- Fuel samples were tested in April 2023, with the lab report attached.
- The Navy is open to additional fuel sampling and testing if needed to determine the best waste management solution.
- The related federal contract opportunity is for the contractor to properly remove, transport, and dispose of the 17,000 gallons of diesel fuel. The contract will require the contractor to provide all labor, supervision, equipment, documentation, and other necessary tasks.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Pictures of NCTAMS Bldgs 106 and 234 UST Sites.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Ques�on 1: Is the fuel in barrels/containers?
Ques�on 2: Or how is it contained?
At Wahiawa Annex Building 106, the fuel is stored in one 5,000-gal capacity underground storage tank.
At Wahiawa Annex Building 234, the fuel is stored in one 20,000-gal capacity underground storage tank.
Ques�on 3: How long has the fuel been si�ng at these loca�ons?
Don’t know how long the diesel fuel has been in the USTs (underground storage tank), but it has been several years. The diesel fuel is used to power emergency generators which were run on a monthly basis for maintenance and opera�onal checks. If there was a power outage than the emergency generators would also kick on. When needed, the UST would be topped off as needed.
Ques�on 4: Has the fuel been tested to acknowledge if its complete waste?
We had the diesel fuel in the Bldg. 234 UST sampled and tested back in April 2023. Laboratory analysis report atached.
Ques�on 5: Is it possible to have a sample of the fuel to properly determine what is the best possible solu�on of waste management?
If it would help to get this accomplished, we can sample and test the diesel fuel in the Bldg. 106 UST and Bldg. 234’s UST again if the lab report provided does not suffice.
23PH-0982
2-D S15, ULTRA LOW SULFUR DIESEL
FROM TO
NAVSUP FLEET LOGISTICS CENTER JOINT BASE PEARL HARBOR HICKAM NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
FUEL LABORATORY, CODE 704
300 NECHES ST. BLDG 1685
PEARL HARBOR, HI 96860
LAB SAMPLE NUMBER SAMPLE DESCRIPTION
DATE SAMPLED DATE RECEIVED DATE TESTS COMPLETED
4/14/2023 1:55 PM 4/18/2023
PRODUCT CODE TEST TYPE SAMPLE VOLUME
DS2 B2 QUART
REPRESENTATIVE VOLUME REPORT CREATED BY SAMPLE TAKEN BY
12,500 AE
MIN MAX USE RESULT UNIT
PASS PASS
REPORT C&B
REPORT SLIGHT
REPORT NONE
REPORT L6.0
52 73.0 °C
REPORT 36.9
REPORT 839.3 kg/m3
0.05 <0.05 %vol
15 1597.90 mg/kg
REPORT 184.0 °C
REPORT 228.8 °C
REPORT 281.7 °C
282 338 277 - 343 332.2 °C
REPORT 356.3 °C
REPORT 2.6 %vol
3 1A
REPORT -4.5 °C
40 53.7
ASTM D975 REF (B): MIL-STD-3004
PRODUCT AS REPRESENTED BY SAMPLE MEET:
SPEC. LIMITS OF REF (A)? USE LIMITS OF REF (B)? NO
REMARKS:
TESTED BY VERIFIED BY
BG/BF/LE/AE
COPPER CORROSION, 3h @50°C
D5453 SULFUR
End user shall verify that the product meets their specification requirements before use and forward this report to their Military service control point.
Results relate only to the sample(s) tested as received by the NAVSUP FLC Fuel Laboratory. The laboratory does not guarantee that the sample(s) submitted is representative of the entire source from which the sample(s) was claimed to be taken from.
NOT SUITABLE FOR USE
REF (A):
D86
ANALYSIS OF
23PH-0982
11:15 AM
D93
D4052
FLASH POINT, PMCC
GRAVITY, API @60°F
NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND, HAWAII PRJ42, NCTPAC-234 UST,
QUALITY CHECK
RY
4/14/2023
COLOR, ASTM
D4052 DENSITY @15°C
5:39 PM
WATER & SEDIMENT
DISTILLATION, IBP
GALLON
TEST
METHOD
D4176
D6045
TEST
APPEARANCE
VISUAL OBSERVANCE
VORTEX OBSERVANCE (PARTICULATES)
VORTEX OBSERVANCE (WATER)
D2709
NO
D976 CETANE INDEX
10% RECOVERED
50% RECOVERED
90% RECOVERED
END POINT
RESIDUE & LOSS
CLOUD POINTD5773
D130
| N62478-24-Q-2674 Q&A1.pdf |
| Diesel Fuel Laboratory Test Report for Bldg 234 UST (4-18-2023) (002).pdf |