N62478-24-Q-2674 Q and A 1.pdf

PDF 415 KB Posted

Attached to
Remove and Dispose of Diesel Fuel
Solicitation number
N6247824Q2674
Issued by

About this file

This document is a set of questions and answers regarding the removal and disposal of approximately 17,000 gallons of diesel fuel from two underground storage tanks at the US Navy Joint Base Wahiawa.

The key details are:

  • The fuel is stored in two underground storage tanks - one 5,000-gallon tank at Building 106 and one 20,000-gallon tank at Building 234.
  • The fuel has been in use for several years to power emergency generators that are run monthly for maintenance.
  • Fuel samples were tested in April 2023, with the lab report attached.
  • The Navy is open to additional fuel sampling and testing if needed to determine the best waste management solution.
  • The related federal contract opportunity is for the contractor to properly remove, transport, and dispose of the 17,000 gallons of diesel fuel. The contract will require the contractor to provide all labor, supervision, equipment, documentation, and other necessary tasks.

View the file

Other files

File Type Posted
Pictures of NCTAMS Bldgs 106 and 234 UST Sites.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ques�on 1: Is the fuel in barrels/containers?

Ques�on 2: Or how is it contained?

At Wahiawa Annex Building 106, the fuel is stored in one 5,000-gal capacity underground storage tank.

At Wahiawa Annex Building 234, the fuel is stored in one 20,000-gal capacity underground storage tank.

Ques�on 3: How long has the fuel been si�ng at these loca�ons?

Don’t know how long the diesel fuel has been in the USTs (underground storage tank), but it has been several years. The diesel fuel is used to power emergency generators which were run on a monthly basis for maintenance and opera�onal checks. If there was a power outage than the emergency generators would also kick on. When needed, the UST would be topped off as needed.

Ques�on 4: Has the fuel been tested to acknowledge if its complete waste?

We had the diesel fuel in the Bldg. 234 UST sampled and tested back in April 2023. Laboratory analysis report atached.

Ques�on 5: Is it possible to have a sample of the fuel to properly determine what is the best possible solu�on of waste management?

If it would help to get this accomplished, we can sample and test the diesel fuel in the Bldg. 106 UST and Bldg. 234’s UST again if the lab report provided does not suffice.

23PH-0982

2-D S15, ULTRA LOW SULFUR DIESEL

FROM TO

NAVSUP FLEET LOGISTICS CENTER JOINT BASE PEARL HARBOR HICKAM NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

FUEL LABORATORY, CODE 704

300 NECHES ST. BLDG 1685

PEARL HARBOR, HI 96860

LAB SAMPLE NUMBER SAMPLE DESCRIPTION

DATE SAMPLED DATE RECEIVED DATE TESTS COMPLETED

4/14/2023 1:55 PM 4/18/2023

PRODUCT CODE TEST TYPE SAMPLE VOLUME

DS2 B2 QUART

REPRESENTATIVE VOLUME REPORT CREATED BY SAMPLE TAKEN BY

12,500 AE

MIN MAX USE RESULT UNIT

PASS PASS

REPORT C&B

REPORT SLIGHT

REPORT NONE

REPORT L6.0

52 73.0 °C

REPORT 36.9

REPORT 839.3 kg/m3

0.05 <0.05 %vol

15 1597.90 mg/kg

REPORT 184.0 °C

REPORT 228.8 °C

REPORT 281.7 °C

282 338 277 - 343 332.2 °C

REPORT 356.3 °C

REPORT 2.6 %vol

3 1A

REPORT -4.5 °C

40 53.7

ASTM D975 REF (B): MIL-STD-3004

PRODUCT AS REPRESENTED BY SAMPLE MEET:

SPEC. LIMITS OF REF (A)? USE LIMITS OF REF (B)? NO

REMARKS:

TESTED BY VERIFIED BY

BG/BF/LE/AE

COPPER CORROSION, 3h @50°C

D5453 SULFUR

End user shall verify that the product meets their specification requirements before use and forward this report to their Military service control point.

Results relate only to the sample(s) tested as received by the NAVSUP FLC Fuel Laboratory. The laboratory does not guarantee that the sample(s) submitted is representative of the entire source from which the sample(s) was claimed to be taken from.

NOT SUITABLE FOR USE

REF (A):

D86

ANALYSIS OF

23PH-0982

11:15 AM

D93

D4052

FLASH POINT, PMCC

GRAVITY, API @60°F

NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND, HAWAII PRJ42, NCTPAC-234 UST,

QUALITY CHECK

RY

4/14/2023

COLOR, ASTM

D4052 DENSITY @15°C

5:39 PM

WATER & SEDIMENT

DISTILLATION, IBP

GALLON

TEST

METHOD

D4176

D6045

TEST

APPEARANCE

VISUAL OBSERVANCE

VORTEX OBSERVANCE (PARTICULATES)

VORTEX OBSERVANCE (WATER)

D2709

NO

D976 CETANE INDEX

10% RECOVERED

50% RECOVERED

90% RECOVERED

END POINT

RESIDUE & LOSS

CLOUD POINTD5773

D130

N62478-24-Q-2674 Q&A1.pdf
Diesel Fuel Laboratory Test Report for Bldg 234 UST (4-18-2023) (002).pdf