Rental/Lease of 480V Load Bank, Step down Transformer, Cables & Training

N4523A21Q1342 – Questions & Answers

The following questions have been asked and answered below.

Do you require a resistive or reactive load bank? - The unit should be a resistive and reactive unit

What is the kW requirement? - The load bank requirement is 2.5MW, or 2500kW

What is the high side of the transformer voltage? - 4160Volts AC

What is the cable length from the transformer to the generator? - 150 feet

Can the units be unloaded from the trailer or do they need to stay on the trailer (transformer weighs about 20,000lbs)? - The units will need to be off loaded from the trailer.

What is the approximate length of the rental (days, weeks etc.)? – The rental is for 9 months, as per the period of performance in the solicitation.

Do you want me to include transportation or would you arrange it? - As transportation was part of most of the market research quotes received, those arrangements should be included and made by the contractor. Once an award is made, you can coordinate with the government representative on more specifics.

I do not see that I should include auxiliary power for the load bank fan and controller. Our requirement is a minimum of 70A 3-Phase 480V auxiliary power. If you could please confirm that this is something that will be available on site I would greatly appreciate it? The power will be provided at by the site.