This document outlines specifications for a rental solicitation from the Department of the Navy Naval Sea Systems Command. The solicitation seeks rental of five 65-70 ton air conditioning units with heaters meeting the provided specifications. The units must provide a minimum of 780,000 BTU/hr cooling capacity with at least a 30-degree temperature drop at 12,000 CFM. Additional requirements include a 60 kW heating capacity, 5,000 CFM air output at 40 degree temperature rise, and operating capabilities of 24 hours a day 7 days a week. Bidders must acknowledge their ability to meet the required delivery date and provide technical data sheets for the proposed units.

View the file

Other files

File Type Posted
APPENDIX A.docx DOCX document
SF-30 amendment.pdf PDF
Solicitation Amendment.docx DOCX document
N4215824RC40170 Solicitation.pdf PDF
AC Rental QA.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Table A

Description
Initials

Unit must be air-cooled.

Provide a minimum of 780,000 BTU/hr cooling capacity. Unit must provide at least a 30-degree temperature drop at 12,000 CFM.

Provide at least 12,000 Cubic Feet per Minute (CFM) at 5” Static Pressure.

Unit must have at least two (2), 20” Vent duct inlet connections.

Unit must have at least two (2), 20” Vent duct outlet connections (Dampered).

Must be capable of running 24 hours/day, 7 days/week.

Unit must be a complete system, incorporating all the requirements outlined herein, and shall not use external equipment to meet this SOW (Unless outlined/authorized herein). If external equipment is needed to meet the requirements listed herein (such as In-line heaters), the Contractor must provide all equipment necessary to connect the external equipment to the main A/C unit.

Contractor to adhere to the rigging requirements as outlined in this SOW for contractor equipment at Norfolk Naval Shipyard.

Unit must be free standing and must have forklift slots (capable of being moved with a forklift).

Unit must be affixed with a metal tag designating the supplying company, a POC responsible for repairs and maintenance, and a phone number of the POC who is responsible for repairs and maintenance.

Unit must provide at least the following heating capacity. In-line heaters are acceptable.

Power Requirements: 460 V/ 3 phase/ 60HZ

Provide a minimum of 60 kW heating capacity

Input Rating: 200,000 BTU or better

Air Output: 5,000 CFM minimum

Temperature Control: 40° F Temperature Rise minimum

Thermostatic Controller: Heating and cooling elements must be thermostatically controlled.

Contractor must include brochure or technical data sheet for the unit model that will be rented to NNSY.

Contractor must acknowledge the ability to meet the required delivery date provided within CLINs, or provide closest date that unit can be delivered.