APPENDIX A.docx
DOCX document 16 KB Posted
- Attached to
- Rental of five (5) 70 ton AC Units with Heaters
- Solicitation number
- N42158-24-Q-A001
About this file
This document outlines interface requirements for rental equipment connected to temporary utility services at the Naval Sea Systems Command (NAVSEA). It specifies mechanical, 110-120V, 220V, 440V, and other voltage connection standards for rental generators and air conditioning units between 50-400 amps. These interface requirements must be met by any vendor providing rental equipment under NAVSEA Solicitation N42158-24-Q-A001 for the rental of five 65-70 ton air conditioning units with heaters. Vendors must acknowledge and agree to adhere to the interface terms and specifications in the Statement of Work prior to providing equipment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SF-30 amendment.pdf | ||
| Table A.docx | DOCX document | |
| Solicitation Amendment.docx | DOCX document | |
| N4215824RC40170 Solicitation.pdf | ||
| AC Rental QA.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX “A”
Interface Requirements For Rental Equipment Hook-up To NNSY Temporary Service
NOTE: All Rental Equipment received by NNSY must be supplied with proper interface connectors shown below to allow hook-up by NNSY Shop 99. There may be specific equipment that will require NNSY Shop 99 evaluation to determine proper cabling and connectors.
Mechanical Service: Shall have ½ inch male 6000# CPV Union End outlet connection interface.
110-120 VAC Service: Material Manufactured by Duraline 20 Amp or less- 3 foot tail of 12/3 cable w/3MT20 crowsfoot plug Over 20 Amp and up to 50 Amp : 3 foot tail of 6/3 cable w/3MT50 crowsfoot plug
440 VAC Service: Material Manufactured by Duraline 20 Amp or less- 3 foot tail of 12/4 cable w/ 4MT20 crowsfoot plug Over 20 Amp and up to 50 Amp- 3 foot tail of 6/4 cable w/ 4MT50 crowsfoot plug Above can also be used on 220VAC Any service over 50 Amp requires box cable
440 VAC 50-100 Amp Service: Material manufactured by Crouse Hinds 50- 100 Amps 3-5 foot length of 2/4 cable w/male camlock twist connectors:
Part Numbers:
Brass -A200036-2 Black Sleeve- A200706-7 White Sleeve- A200706-12 Red Sleeve-A200706-9
Over 100 and up to 225 Amps: 3- 5 foot length of 3 conductor 3/0 cable with camlock connectors:
Part Numbers:
Brass - A200038-2 Black Sleeve- A2000706-13 White Sleeve-A2000706-18 Red Sleeve- A2000706-15
Over 225 and up to 400 Amps: 5-15 length of 500 MCM cable w/camlock connectors:
Part Numbers:
Brass- A20028-2 Black Sleeve-A200056- White Sleeve-A200056-6 Red Sleeve- A200056-3
I hereby acknowledge and understand the specifications and agree to adhere to the terms provided in section 5 of the Statement of Work: Contractor Requirements.
| ____________________________________________ | _____________________ | |
| Signature | Date |
File details come from the government source that posted it. Updated .